BE 215 Chievres Overview

Quarters No. 18

BE 828 Sterrebeek Annex

In st al la tio n

N am e

B ui ld in g N o.

Fl oo r Facility Name To go to location click on description

Cross Connection Ref No.

Click on Ref No. to go to Location on Floor

Plan

Equipment Type Click on Description to go to photograph Quantity Hazard Installed Required BP Size Inches Comments Action

BE215 Chievres AB Commercial 20004 1 Gym and Library 0 Building supply 1 2 None EA Y 1.50

EN 1717 para 6 "for all domestic uses and for the non domestic uses where interior examination is possible and the guarantees sufficient, protection unit shall be a controllable check valve"

Install controllable antipollution check-valve in vertical section coming down near door.(Investigate detail of supply piont)

BE215 Chievres AB Commercial 20004 1 Gym and Library 1 Shower Hose 1 5 None HB N 0.50 Hose too long (???, possibly over 10 years old) Install Shower hose union anti-vacuum valve

BE215 Chievres AB Commercial 20004 1 Gym and Library 3 Hose bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Commercial 20004 1 Gym and Library 4 Hose Bibb (NON Potable) 1 5 None HA N 0.50 Unprotected Install Label NON POTABLE

BE215 Chievres AB Commercial 20030 1 Kennels 1 Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Commercial 20030 1 Kennels 2 Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Commercial 20030 1 Kennels 3 Spare Hot Hose bibb behind Whirlpool 1 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Commercial 20030 1 Kennels 4 Dog Wash Tub 1 5 None HB N 0.50 Hose too long (???, possibly over 5 years old) Install Shower hose union anti-vacuum valve BE215 Chievres AB Commercial 20030 1 Kennels 5 Shower 1 5 None HB N 0.50 Hose too long (???, possibly over 5 years old) Install Shower hose union anti-vacuum valve BE215 Chievres AB Commercial 20030 1 Kennels 6 2 hose bibbs at Janitor Sink location 2 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Commercial 20030 1 Kennels 7 Hose Bibb 2 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Commercial 20030 1 Kennels 8 Dog Wash Tub 1 5 None HB N 0.50 Hose too long (???, possibly over 5 years old) Install Shower hose union anti-vacuum valve BE215 Chievres AB Commercial 20030 1 Kennels 9 Hose Bibbs on wall 3 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Commercial 20030 1 Kennels 10 Hot and Cold Wash down bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Commercial 20030 1 Kennels 11 Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Commercial 20030 1 Kennels 12 Hot and Cold Wash down bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Commercial 20030 1 Kennels 13 Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Commercial 20031 1 Thrift Shop 0 Building supply 1 2 None EA Y 1.25

EN 1717 para 6 "for all domestic uses and for the non domestic uses where interior examination is possible and the guarantees sufficient, protection unit shall be a controllable check valve"

Modify incomimg pipework and Install controllable antipollution check-valve

BE215 Chievres AB Commercial 20031 1 Thrift Shop 1 Water Heater 1 2 PRV EB & AA Y 0.50 No air gap and drain goes up to waste pipe Requires reinstalling with NRV and tundish into new P trap.to met regulations

BE215 Chievres AB Commercial 20046 1 Vehicle Processing 0 Building supply 1 2 None EA Y .50 & 1.50

EN 1717 para 6 "for all domestic uses and for the non domestic uses where interior examination is possible and the guarantees sufficient, protection unit shall be a controllable check valve"

Modify incomimg pipework and Install controllable antipollution check-valve on 1/2 inch drinking water branch. (fire water covered by devices at point of use as pipes in a restricted space)

BE215 Chievres AB Commercial 20046 1 Vehicle Processing 2 Fire Hose Supply Service 1 3 None EA N 1.5 FEUILLE DE TRAVAIL 06-140-010 Manual Installation for fire fighting

Install Controllable antipollution check-valvein 4 foot of vertical pipe

BE215 Chievres AB Commercial 20053 1 O&M Plumbing Shop 1 Potable Water Service, Filter and Drain 1 2 None AA N 0.5 Outlet of filter has sealed connection to drain Instal tundish and drain with trap

BE215 Chievres AB Commercial 20053 1 O&M Plumbing Shop 6 Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Commercial 20053 1 O&M Plumbing Shop 7 Hose Bibb outside 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Commercial 20053 1 O&M Plumbing Shop 8 Hose Bibb outside 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Commercial 20053 1 O&M Plumbing Shop 9 Showers 2 5 None HB N 0.50 Hose too long (???, possibly over 10 years old) Install Shower hose union anti-vacuum valve BE215 Chievres AB Commercial 20053 2 O&M Plumbing Shop 10 Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Commercial 20081 1 Laundry 1 Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Commercial 20081 1 Laundry 2 Hose Bibb 2 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Commercial 20081 1 Laundry 3 Hose Bibb outside 1 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Commercial 20094 1 Wastewater Treatment Plant 0 Building Supply 1 5 None BA Y 0.75 Base Drinking Water Mains need maximum protection

Install 3/4" BA assembly on incoming main in conjunction with water meter below isolating valve and new pipe to wash hand basin with EA to take off upply before BA. A detailed description/proposal of the action to correct the deficiency will be provided as submittal for approval

BE215 Chievres AB Commercial 20094 1 Wastewater Treatment Plant 1 Drum Screen washer 1 5 None N 0.50 To protect internal water quality at wash hand basin BE215 Chievres AB Commercial 20094 1 Wastewater Treatment Plant 2 Backwash Filter 1 5 None Y 0.75 To protect internal water quality at wash hand basin BE215 Chievres AB Commercial 20094 1 Wastewater Treatment Plant 3 Hose Bibb 1 5 None HA N 0.50 To protect internal water quality at wash hand basin Hose union backflow preventer

BE215 Chievres AB Commercial 20150 1S PX (New) 0 Drinking Water 1 2 EB EA Y 2.00

EN 1717 para 6 "for all domestic uses and for the non domestic uses where interior examination is possible and the guarantees sufficient, protection unit shall be a controllable check valve"

Install Controllable antipollution check-valve in horizontal pipe after the meter

BE215 Chievres AB Commercial 20150 1S PX (New) 2

Softener

1 3 None EA Y 0.50

FEUILLE DE TRAVAIL 06-060-010 · Appareil de traitement à usage industriel (Softening of water and anti-trust treatment (water intended for human consumption).

Belgium minimum EA, however, as the water is also used for boiler top up it may require CA.

Install controllable antipollution check-valve

BE215 Chievres AB Commercial 20150 1N PX (New) 4 Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Commercial 20150 1N PX (New) 6 Hose bibb 1 5 None HA N 0.50 Unprotected install HA

BE215 Chievres AB Commercial 20150 1N PX (New) 7 Hot Water Heater with black hose 1 5 PRV EB & AA N 0.50 No check valve or air gap and drain goes up to waste pipe Requires reinstalling with NRV and tundish into new P trap.to met regulations

BE215 Chievres AB Commercial 20150 1N PX (New) 8 Water Heater under sink 1 2 PRV EB & AA Y 0.50 No air gap and drain goes up to waste pipe Requires reinstalling with NRV and tundish into new P trap.to met regulations

BE215 Chievres AB Commercial 20150 1N PX (New) 8 Shampoo Basin with Wand Olymp LavaSit Sychro

2 5 None HB N 0.50 Hose too long Install Shower hose union anti-vacuum valves in pedestal

BE215 Chievres AB Commercial 20150 1N PX (New) 9 Janitor's Sink with unprotected hose bibb

1 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Commercial 20150 1N PX (New) 10 Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Commercial 20150 1N PX (New) 11 Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Commercial 20150 1N PX (New) 12 Hot Water Heater with Red waste pipe 1 2 PRV & EB AA Y 0.50 No air gap and drain goes up to waste pipe Requires tundish into P trap to met regulations

BE215 Chievres AB Commercial 20174 1 POV Insp 1 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Commercial 20182 2 Barracks 1 Shower too long hose 60 5 None HB N 0.50 Hose too long Install Shower hose union anti-vacuum valve BE215 Chievres AB Commercial 20182 2 Barracks 2 Janitor's Sink with threads 1 5 None HA N 0.50 Aerator is removed, could easily hook hose. Re-install aerator

BE215 Chievres AB Commercial 20182 -1 Barracks 6 Building Water Service 1 2 EA EA N 4

Test regime devised to cater for presence of check valves and PRV down-stream. (Clear hose attached to center tapping and filled to 1.6 meters, - Supply valve closed. - Valve body drained beetween supply valve and check valve. - Center tap opened. (Fall in water level with water coming out of drian equals a failure)

FAILED

REPAIR and RETEST

BE215 Chievres AB Commercial 20182 4 Barracks 11 NCO sigle room Shower too long hose 8 5 None HB N 0.50 Hose too long Hose union backflow preventer BE215 Chievres AB Commercial 20185 1 Gate 1, Access/Guard 1 External Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Commercial 20185 1 Gate 1, Access/Guard 2 Sink with threads for tubing 1 5 None HB N 0.50 Dismantle at top of spout and install inline protection. Dismantle at top of spout and Install Shower hose union anti-vacuum valve

BE215 Chievres AB Commercial 20185 1 Gate 1, Access/Guard 3 Building Water Service 1 2 None EA Y 0.50

EN 1717 para 6 "for all domestic uses and for the non domestic uses where interior examination is possible and the guarantees sufficient, protection unit shall be a controllable check valve"

Revise pipework and install controllable antipollution check-valve

BE215 Chievres AB Commercial 20186 1 Auto Skills 1 Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Commercial 20186 1 Auto Skills 2 Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Commercial 20186 1 Auto Skills 3 Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Commercial 20186 1 Auto Skills 4 Building supply 1 2 None EA Y 1.50

EN 1717 para 6 "for all domestic uses and for the non domestic uses where interior examination is possible and the guarantees sufficient, protection unit shall be a controllable check valve"

Revise pipework around meter and install controllable antipollution check-valve

BE215 Chievres AB Commercial 20186 1 Auto Skills 5 Fire Hose reel & hose connection 1 3 None EA N 1.50 FEUILLE DE TRAVAIL 06-140-010 Manual Installation for fire fighting

Install Controllable antipollution check-valve in 3 foot of vertical pipe

BE215 Chievres AB Commercial 20186 1 Auto Skills 6 Fire Hose reel & hose connection 1 3 None EA N 1.50 FEUILLE DE TRAVAIL 06-140-010 Manual Installation for fire fighting

Install Controllable antipollution check-valve in 3 foot of vertical pipe

BE215 Chievres AB Commercial 20191 1C Army Lodge 1 Family suit Bath with Shower Wand Too Long 60 5 None HB N 0.50 Hose too long Install Shower hose union anti-vacuum valve

BE215 Chievres AB Commercial 20191 1C Army Lodge 3 Single Room Bath with Shower Wand Too Long 34 5 None HB N 0.50 Hose too long Install Shower hose union anti-vacuum valve

BE215 Chievres AB Commercial 20191 1C Army Lodge 4 Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Commercial 20191 1A Army Lodge 5 Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Commercial 20191 1A Army Lodge 9 Shower Wand Too Long 1 5 None HB N 0.50 Hose too long Install Shower hose union anti-vacuum valve BE215 Chievres AB Commercial 20191 1A Army Lodge 10 Shower Wand Too Long 1 5 None HB N 0.50 Hose too long Install Shower hose union anti-vacuum valve

BE215 Chievres AB Commercial 20191 EX Army Lodge 11 Fire Supply Service 1 3 BA BA Y 6

EN 1717 Units with an atmospheric vent may not be installed where it is liable to flooding (for examples AA, BA, CA, GA, GB...). Valve tested and appears to be fuctional but FAILED due to location.

This device should be removed from the chamber. Modify pipe work and install device in frost proof box above ground to be enable device to conform to EN1717. This will save on mainteance and testing costs and make it certfiable Retest once reinstalled above ground. A detailed description/proposal of the action to correct the deficiency will be provided as submittal for approval

BE215 Chievres AB Commercial 20200 1 New Commissary 1 Janitor's Sink 2 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Commercial 20200 1 New Commissary 2 Hose Bibb 1 5 None HA N 0.75 Unprotected Hose union backflow preventer BE215 Chievres AB Commercial 20200 1 New Commissary 3 Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Commercial 20200 1 New Commissary 4 Janitor's Sink 2 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Commercial 20200 1 New Commissary 5 Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Commercial 20200 1 New Commissary 6 Domestic Water Service 1 2 EA EA N 2.50

Test regime devised to cater for presence of check valves and PRV down-stream. (Clear hose attached to center tapping and filled to 1.6 meters, - Supply valve closed. - Valve body drained beetween supply valve and check valve. - Center tap opened. (Fall in water level with water coming out of drian equals a failure)

FAILED

REPAIR and RETEST

BE215 Chievres AB Commercial 20+C3:H12 1 Car Wash 1 Sink 1 5 None HA N 0.50 Unprotected Hose union backflow preventer al la tio n

N am e

B ui ld in g N o.

Fl oo r Facility Name To go to location click on description

Cross Connection Ref No. Click on Ref No. to go to Location on Floor Plan

Equipment Type Click on Description to go to photograph Quantity Hazard Installed Required BP Size Inches Comments Action

BE215 Chievres AB Industrial 20001 -1N Readiness Hanger 0 Incomming Supply 1 2 None EA Y 1.50

EN 1717 para 6 "for all domestic uses and for the non domestic uses where interior examination is possible and the guarantees sufficient, protection unit shall be a controllable check valve"

Install controllable antipollution check-valve on 3 foot horizontal section

BE215 Chievres AB Industrial 20001 -1N Readiness Hanger 1 Water Heater 1 2 None EB & AA Y 0.50 Bulex, no air gap on PRV needs tundish drain + check valve

Install combined PRV check and valve and modify drain with tundish

BE215 Chievres AB Industrial 20001 -1N Readiness Hanger 2 Softener 1 2 None CA Y 0.50

FEUILLE DE TRAVAIL 06-060-010 · Appareil de traitement à usage industriel (Softening of water and anti-trust treatment (water intended for human consumption).

Belgium minimum EA, however, as the water is also used for boiler top up it may require CA.

Install controllable antipollution check-valve

BE215 Chievres AB Industrial 20001 1 Readiness Hanger 6 Under basin Water Heater 1 2 PRV EB & AA Y 0.50 No air gap and drain goes up to waste pipe Install combined PRV check and valve and modify drain with tundish

BE215 Chievres AB Industrial 20001 1 Readiness Hanger 7 Under basin Water Heater 1 2 PRV EB & AA Y 0.50 No air gap and drain goes up to waste pipe Install combined PRV check and valve and modify drain with tundish

BE215 Chievres AB Industrial 20001 1 Readiness Hanger 8 Shower 1 5 None HB N 0.50 Hose too long (Princess, possibly over 20 years old) Install Shower hose union anti-vacuum valve BE215 Chievres AB Industrial 20001 1 Readiness Hanger 9 Shower 1 5 None HB N 0.50 Hose too long (Princess, possibly over 20 years old) Install Shower hose union anti-vacuum valve BE215 Chievres AB Industrial 20001 1 Readiness Hanger 10 Manitowoc Ice machine 1 5 AA N 0.50 2 lines both need tundishes Install tundishes and modify waste pipe BE215 Chievres AB Industrial 20001 1 Readiness Hanger 11 Water Heater 1 2 PRV & EB AA Y 0.50 Air gap too small Install tundish and re-route wastepipe BE215 Chievres AB Industrial 20001 1 Readiness Hanger 12 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected outside Hose union backflow preventer BE215 Chievres AB Industrial 20001 1 Readiness Hanger 13 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected outside Hose union backflow preventer BE215 Chievres AB Industrial 20002 1 Aircraft hanger 3 Manitowoc SR 5420 Ice machine 1 5 AA N 0.50 2 lines both need tundishes Install tundishes and modify waste pipe

BE215 Chievres AB Industrial 20002 1 Aircraft hanger 6 Un-protected Hose Bibb (Non Standard, 1/2 male thread)

1 5 None HA N 0.50 Unprotected Remove and cap off

BE215 Chievres AB Industrial 20002 1 Aircraft hanger 7 Shower 1 5 None HB N 0.50 Hose too long (???, possibly over 10 years old) Install Shower hose union anti-vacuum valve BE215 Chievres AB Industrial 20002 1 Aircraft hanger 8 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected outside Hose union backflow preventer BE215 Chievres AB Industrial 20002 1 Aircraft hanger 9 Shower 1 5 None HB N 0.50 Hose too long (???, possibly over 10 years old) Install Shower hose union anti-vacuum valve BE215 Chievres AB Industrial 20002 1 Aircraft hanger 11 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Industrial 20002 1 Aircraft hanger 12 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Industrial 20003 1 Logistics Warehores 1 Water Heater 1 2 PRV & EB AA Y 0.50 Air gap too small Install tundish BE215 Chievres AB Industrial 20003 1 Logistics Warehores 2 Janitors sink 2 5 None HA N 0.50 Unprotected hose bibbs over sink Hose union backflow preventer BE215 Chievres AB Industrial 20003 1 Logistics Warehores 3 Shower 1 5 None HB N 0.50 Hose too long (???, possibly over 10 years old) Install Shower hose union anti-vacuum valve

BE215 Chievres AB Industrial 20003 1 Logistics Warehores 5 Fire Hose Reel 1 3 None EA N 1.5 FEUILLE DE TRAVAIL 06-140-010 Manual Installation for fire fighting

Install Controllable antipollution check-valve in 6 foot of vertical pipe

BE215 Chievres AB Industrial 20003 1 Logistics Warehores 6 Fire Hose Reel 1 3 None EA N 1.5 FEUILLE DE TRAVAIL 06-140-010 Manual Installation for fire fighting

Install Controllable antipollution check-valvein 4 foot of vertical pipe

BE215 Chievres AB Industrial 20006 1 DPW 0 Incomming supply 1 2 None EA Y 1.50

EN 1717 para 6 "for all domestic uses and for the non domestic uses where interior examination is possible and the guarantees sufficient, protection unit shall be a controllable check valve"

Install controllable antipollution check-valve in vertical section above meter (modify valve and branch locations above)

BE215 Chievres AB Industrial 20006 1 DPW 2 Water softener 1 2 None EA Y 0.75

FEUILLE DE TRAVAIL 06-060-010 · Appareil de traitement à usage industriel (Softening of water and anti-trust treatment (water intended for human consumption).

Belgium minimum EA, however, as the water is also used for boiler top up it may require CA.

Install controllable antipollution check-valve

BE215 Chievres AB Industrial 20006 1 DPW 3 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected outside Hose union backflow preventer BE215 Chievres AB Industrial 20006 1 DPW 4 Showers 4 5 None HB N 0.50 Hose too long (GROHE, possibly over 5 years old) Install Shower hose union anti-vacuum valve BE215 Chievres AB Industrial 20006 1 DPW 5 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Industrial 20006 1 DPW 6 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected outside Hose union backflow preventer BE215 Chievres AB Industrial 20006 1 DPW 7 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Industrial 20006 1 DPW 8 Hoshizaki Ice Machine 1 5 AA N 0.50 2 lines both need tundishes Install tundishes and install waste pipe

BE215 Chievres AB Industrial 20006 1 DPW 9 Shower 1 5 None HB N 0.50 Hose too long (HANSGROHE, possibly over 5 years old) Install Shower hose union anti-vacuum valve

BE215 Chievres AB Industrial 20006 1 DPW 10 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected outside Hose union backflow preventer BE215 Chievres AB Industrial 20006 1 DPW 11 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Industrial 20006 1 DPW 12 Un-protected Hose Bibb 1 5 None HA N 0.75 Unprotected Hose union backflow preventer

BE215 Chievres AB Industrial 20006 2 DPW 13 Water Heater 1 2 PRV EB & AA Y 0.50 No air gap and drain goes up to waste pipe Install combined PRV check and valve and modify drain with tundish

BE215 Chievres AB Industrial 20006 2 DPW 15 Janitors sink 2 5 None HA N 0.50 Unprotected hose bibbs over sink Hose union backflow preventer BE215 Chievres AB Industrial 20009 1 424th Airlift Store 1 Shower 1 5 None HB N 0.50 Hose too long (LEDA, possibly over 5 years old) Install Shower hose union anti-vacuum valve BE215 Chievres AB Industrial 20010 1 Fire Station 2 Showers 2 5 None HB N 0.50 Hose too long Install Shower hose union anti-vacuum valve BE215 Chievres AB Industrial 20010 1 Fire Station 3 Shower 1 5 None HB N 0.50 Hose too long (GROHE, possibly over 10 years old) Install Shower hose union anti-vacuum valve BE215 Chievres AB Industrial 20010 1 Fire Station 4 Hose bibb on js 2 5 None HA N 0.50 Unprotected hose bibbs over sink Hose union backflow preventer BE215 Chievres AB Industrial 20010 1 Fire Station 5 Un-protected Hose Bibb (Hot) 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Industrial 20010 1 Fire Station 6 Un-protected Hose Bibbs (H&C) 2 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Industrial 20010 1 Fire Station 7 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected outside Hose union backflow preventer BE215 Chievres AB Industrial 20010 1 Fire Station 8 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Industrial 20010 1 Fire Station 10 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected outside Hose union backflow preventer BE215 Chievres AB Industrial 20021 1 Housing, Storage 2 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Industrial 20023 1 Housing, Admin/Storage 0 Incoming supply 1 2 None EA Y 2.00

EN 1717 para 6 "for all domestic uses and for the non domestic uses where interior examination is possible and the guarantees sufficient, protection unit shall be a controllable check valve"

Install controllable antipollution check-valve in vertical section

BE215 Chievres AB Industrial 20023 1 Housing, Admin/Storage 1 Under basin Water Heater 1 2 PRV EB & AA Y 0.50 No air gap and drain goes up to waste pipe Install combined PRV check and valve and modify drain with tundish

BE215 Chievres AB Industrial 20023 1 Housing, Admin/Storage 2 Hose bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Industrial 20023 1 Housing, Admin/Storage 3 Under basin Water Heater 1 2 PRV EB & AA Y 0.50 No air gap and drain goes up to waste pipe Install combined PRV check and valve and modify drain with tundish

BE215 Chievres AB Industrial 20023 1 Housing, Admin/Storage 4 Incoming supply to softener & test bay 1 5 CA 0.75 One well placed device will protect the drinking water distributions system for the rest of the building from any backflow originating in the washer test area.

Install Backflow preventer with different non controllable pressure zones on vertical 3/4 inch supply coming down near the water softener

BE215 Chievres AB Industrial 20023 1 Housing, Admin/Storage 5 Water Softener 3 BE215 Chievres AB Industrial 20023 1 Housing, Admin/Storage 6 Washer test bay 5 BE215 Chievres AB Industrial 20023 1 Housing, Admin/Storage 7 Industrial washers 5

BE215 Chievres AB Industrial 20024 1 Benelux Sup Training CTR 1 Showesr 2 5 None HB N 0.50 Hose too long (IDEAL STANDARD, possibly over 10 years old) Install Shower hose union anti-vacuum valve

BE215 Chievres AB Industrial 20024 1 Benelux Sup Training CTR 2 Un-protected Hose Bibbs (H&C) 2 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Industrial 20025 1 Self Help 1 Under basin Water Heater 1 2 PRV EB & AA Y 0.50 No air gap and drain goes up to waste pipe Install combined PRV check and valve and modify drain with tundish

BE215 Chievres AB Industrial 20027 1 424th Airlift SQ, OPPS 1 Shower 1 5 None HB N 0.50 Hose too long (???, possibly over 10 years old) Install Shower hose union anti-vacuum valve BE215 Chievres AB Industrial 20027 1 424th Airlift SQ, OPPS 2 Water Heater 1 2 PRV & EB AA Y 0.50 Air gap too small Install tundish and re-route wastepipe BE215 Chievres AB Industrial 20027 1 424th Airlift SQ, OPPS 3 Manitowoc Ice machine 1 5 AA N 0.50 2 lines both need tundishes Install tundishes and modify waste pipe BE215 Chievres AB Industrial 20028 1 424th Airlift SQ, Admin 1 Un-protected Hose Bibbs (H&C) 2 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Industrial 20028 1 424th Airlift SQ, Admin 2 Shower 1 5 None HB N 0.50 Hose too long (FRIEDRICH GROHE, possibly over 10 years old) Install Shower hose union anti-vacuum valve

BE215 Chievres AB Industrial 20029 1 Vacant (DPW) 2 Shower 1 5 None HB N 0.50 Hose missing (GROHE, possibly over 5 years old) Install Shower hose union anti-vacuum valve and new hose/shower head

BE215 Chievres AB Industrial 20041 1 Telephone switch 1 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Industrial 20047 1 Fire Section/BMCT 2 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Industrial 20047 1 Fire Section/BMCT 3 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Industrial 20047 1 Fire Section/BMCT 4 Shower 1 5 None HB N 0.50 Hose too long (FRIEDRICH GROHE, possibly over 10 years old) Install Shower hose union anti-vacuum valve

BE215 Chievres AB Industrial 20047 1 Fire Section/BMCT 5 Shower 1 5 None HB N 0.50 Hose too long (FRIEDRICH GROHE, possibly over 10 years old) Install Shower hose union anti-vacuum valve

BE215 Chievres AB Industrial 20048 1 424th Airlift SQ, POL Lab 0 Incoming supply 1 2 None EA N 2.00

EN 1717 para 6 "for all domestic uses and for the non domestic uses where interior examination is possible and the guarantees sufficient, protection unit shall be a controllable check valve"

Install controllable antipollution check-valve in vertical section

BE215 Chievres AB Industrial 20048 1 424th Airlift SQ, POL Lab 2 Hot & Cold Hose Bibbs 2 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Industrial 20048 1 424th Airlift SQ, POL Lab 3 Shower 1 5 None HB N 0.50 Hose too long (FRIEDRICH GROHE, possibly over 10 years old) Install Shower hose union anti-vacuum valve

BE215 Chievres AB Industrial 20052 -1 DPW Repair Shop 0 Incoming supply PE DN83mm 1 2 None EA Y 3.00

EN 1717 para 6 "for all domestic uses and for the non domestic uses where interior examination is possible and the guarantees sufficient, protection unit shall be a controllable check valve"

Install controllable antipollution check-valve in vertical section before filter and ensure the outlet has an air gap.

BE215 Chievres AB Industrial 20052 -1 DPW Repair Shop 1 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Industrial 20052 -1 DPW Repair Shop 2 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Industrial 20052 -1 DPW Repair Shop 3 Heat Exchanger 1 5 PRV AA N 0.50 Insufficent air gap where drain goes to waste pipe Install tundish and modify waste pipe

BE215 Chievres AB Industrial 20052 -1 DPW Repair Shop 5 Softener 1 2 None EA Y 0.50

FEUILLE DE TRAVAIL 06-060-010 · Appareil de traitement à usage industriel (Softening of water and anti-trust treatment (water intended for human consumption).

Belgium minimum EA, however, as the water is also used for boiler top up it may require CA.

Install controllable antipollution check-valve in vertical section

BE215 Chievres AB Industrial 20052 -1 DPW Repair Shop 6 Firemain to paint booth system 1 3 None EA Y 2.50 Install controllable antipollution check-valve in basement

BE215 Chievres AB Industrial 20052 1 DPW Repair Shop 7 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected outside Hose union backflow preventer

BE215 Chievres AB Industrial 20052 1 DPW Repair Shop 8 Shower 1 5 None HB N 0.50 Hose too long (Make unknown, possibly over 10 years old) Install Shower hose union anti-vacuum valve

BE215 Chievres AB Industrial 20052 1 DPW Repair Shop 9 Shower 1 5 None HB N 0.50 Hose too long (GROHE, possibly over 10 years old) Install Shower hose union anti-vacuum valve BE215 Chievres AB Industrial 20052 1 DPW Repair Shop 10 Shower 1 5 None HB N 0.50 Hose too long (GROHE, possibly under 10 years old) Install Shower hose union anti-vacuum valve BE215 Chievres AB Industrial 20052 1 DPW Repair Shop 11 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Industrial 20052 1 DPW Repair Shop 12 Un-protected Hose Bibb 2 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Industrial 20056 1 Control Tower 0 Incoming supply 1 2 None EA Y 1.5

EN 1717 para 6 "for all domestic uses and for the non domestic uses where interior examination is possible and the guarantees sufficient, protection unit shall be a controllable check valve"

Install controllable antipollution check-valve in horizontal section above meter

BE215 Chievres AB Industrial 20056 1 Control Tower 1 Un-protected Hose Bibb (Hot) 1 5 None HA N 0.50 Unprotected Hot over sink Hose union backflow preventer

BE215 Chievres AB Industrial 20056 1 Control Tower 2 Water Heater 1 2 PRV EB & AA Y 0.50 No air gap and drain goes up to waste pipe Install combined PRV check and valve and modify drain with tundish

BE215 Chievres AB Industrial 20056 1 Control Tower 4 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Industrial 20056 1 Control Tower 5 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Industrial 20056 1 Control Tower 6 Air to water heater 1 2 PRV EB & AA Y 0.50 No air gap and drain goes up to waste pipe Install combined PRV check and valve and modify drain with tundish

BE215 Chievres AB Industrial 20056 1 Control Tower 7 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Industrial 20056 5 Control Tower 8 Under basin Water Heater 1 2 PRV EB & AA Y 0.50 No air gap and drain goes up to waste pipe Install combined PRV check and valve and modify drain with tundish

BE215 Chievres AB Industrial 20102 1 DPW POL store 0 Incoming supply 1 5 None EA Y 0.75 There is no potable water outlets in this mechanical room.

Supply is to washers only, therefore protect distribution system

Install controllable antipollution check-valve in vertical section above before split.

BE215 Chievres AB Industrial 20102 1 DPW POL store 1 3/4 inch feed to Karcher 1 5 None EA N 0.75 Install controllable antipollution check-valve BE215 Chievres AB Industrial 20102 1 DPW POL store 2 1/2 inch feed to Karcher 1 5 None EA N 0.50 Install controllable antipollution check-valve BE215 Chievres AB Industrial 20105 1 Trianing Facility (Admin) 2 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected outside Hose union backflow preventer BE215 Chievres AB Industrial 20105 1 Trianing Facility (Admin) 3 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer

BE215 Chievres AB Industrial 20134 1 MP Station 0 Incoming supply 1 2 None EA Y 2.00

EN 1717 para 6 "for all domestic uses and for the non domestic uses where interior examination is possible and the guarantees sufficient, protection unit shall be a controllable check valve"

Install controllable antipollution check-valve in short 2 inch dia. vertial section after meter (pipes will need modification)

BE215 Chievres AB Industrial 20134 1 MP Station 1 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected outside Hose union backflow preventer

BE215 Chievres AB Industrial 20134 1 MP Station 2 Fire main 1 3 None EA Y 1.00 FEUILLE DE TRAVAIL 06-140-010 Manual Installation for fire fighting

Install Controllable antipollution check-valve in 5 foot of vertical pipe

BE215 Chievres AB Industrial 20134 1 MP Station 4 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Industrial 20134 1 MP Station 5 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected Hose union backflow preventer BE215 Chievres AB Industrial 20134 1 MP Station 6 Ladies shower hose too long 1 5 None HB N 0.50 Hose too long (GROHE, possibly over 8 years old) Install Shower hose union anti-vacuum valve BE215 Chievres AB Industrial 20134 1 MP Station 7 Shower hose too long 1 5 None HB N 0.50 Hose too long (???, possibly over 8 years old) Install Shower hose union anti-vacuum valve BE215 Chievres AB Industrial 20148 EX Haz Mat Storage 1 Un-protected Hose Bibb 1 5 None EB N 1.25 Unprotected outside in burried box Install antipollution check-valve on supply in CV24 BE215 Chievres AB Industrial 20170 1 Old K9 1 Shower 1 5 None HB N 0.50 Hose too long (???, possibly over 10 years old) Install Shower hose union anti-vacuum valve BE215 Chievres AB Industrial 20170 1 Old K9 2 Un-protected Hose Bibb 2 5 None HA N 0.50 Unprotected over janitor's sink Hose union backflow preventer BE215 Chievres AB Industrial 20188 1 Recycling Ctr, Guard Check 1 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected outside Hose union backflow preventer BE215 Chievres AB Industrial 20195 1 Access Control Fac 1 Un-protected Hose Bibb 1 5 None HA N 0.50 Unprotected outside Hose union backflow preventer BE215 Chievres AB Industrial 20195 1 Access Control Fac 2 Un-protected Hose Bibb 2 5 None HA N 0.50 Unprotected Hot and Cold Hose union backflow preventer al la tio n

N am e

B ui ld in g N o.

Fl oo r Facility Name To go to location click on description

Cross Connection Ref No. Click on Ref No. to go to Location on Floor Plan

Equipment Type Click on Description to go to photograph Quantity Hazard Installed Required BP Size Inches Comments Action

BE215 Chievres AB NSHQ 20115 1 Warehouse 0

Incoming supply With water filter

1 2 None EA N 1.0

EN 1717 para 6 "for all domestic uses and for the non domestic uses where interior examination is possible and the guarantees sufficient, protection unit shall be a controllable check valve" Filter and valves located on wall.

Install controllable antipollution check-valve on 2 foot vertical section

BE215 Chievres AB NSHQ 20115 1 Warehouse 1

Hose bibb 1 5 None HA N 0.5 Unprotected Hose union backflow preventer

BE215 Chievres AB NSHQ 20146 1 Break Room 1 Showers 2 5 None HB N 0.50 Hose too long (DIBL mixer, possibly over 10 years old) Install Shower hose union anti-vacuum valve

BE215 Chievres AB NSHQ 20146 1 Break Room 2 Under sink water heater 1 2 PRV EB & AG 0.5 No NRV or air gap on waste line Install combined PRV check and valve and modify drain with tundish

BE215 Chievres AB NSHQ 20160 1 Wharehous/offices 0

Incoming supply With water filter

1 2 None EA N 1.0

EN 1717 para 6 "for all domestic uses and for the non domestic uses where interior examination is possible and the guarantees sufficient, protection unit shall be a controllable check valve" Filter and valves located in wall space

Install controllable antipollution check-valve on 2 foot horizontal section

BE215 Chievres AB NSHQ 20160 1 Wharehous/offices 1

Shower 1 5 None HB N 0.50 Hose too long (???, possibly over 10 years old) Install Shower hose union anti-vacuum valve

BE215 Chievres AB NSHQ 20160 1 Wharehous/offices 2

Sink with wand hose 1 5 None visable HB N 0.50 Install Shower hose union anti-vacuum valve under sink

BE215 Chievres AB NSHQ 20187 1 Kennels 1

Hose Bibb (exterior) 1 5 None HA N 0.5 To protect building #20187 internal water quality Hose union backflow preventer

BE215 Chievres AB NSHQ 20187 1 Kennels 2

Hose Bibb (exterior) 1 5 None HA N 0.5 To protect building #20187 internal water quality Hose union backflow preventer

BE215 Chievres AB NSHQ 20187 1 Kennels 3 Janitor's sink Hose bibbs 2 5 None HA N 0.5 To protect building #20187 internal water quality Hose union backflow preventer

BE215 Chievres AB NSHQ 20187 1 Kennels 4

Shower 1 5 None HB N 0.50 Hose too long (???, possibly over 10 years old) Install Shower hose union anti-vacuum valve

BE215 Chievres AB NSHQ 20187 1 Kennels 5

Dog washing shower 1 5 None visable HB N 0.5 Shower Hose Too Long

Install Shower hose union anti-vacuum valve

BE215

Chievres

AB

Training Area (Unused)

20126 1 Fire Training Area 1 1 5 None visable BA N 3.0 Disissed fire spare syatem. Various pipes, fittings and pumps in below ground chamber subject to flooding Cut connection adjacent to Fire Hydrant FH 26 and abondon.

al la tio n

N am e

B ui ld in g N o.

Fl oo r Facility Name To go to location click on description

Cross Connection Ref No. Click on Ref No. to go to Location on Floor Plan

Equipment Type Click on Description to go to photograph Quantity Hazard Installed Required BP Size Inches Comments Action

Quarters No. 18

BE625 Quarters No. 18 20003 -1 House 0 Building Supply 1 2 None EA N 1.0

EN 1717 para 6 "for all domestic uses and for the non domestic uses where interior examination is possible and the guarantees sufficient, protection unit shall be a controllable check valve"

Install controllable antipollution check-valve on 3 foot horizontal section behind softener

BE625 Quarters No. 18 20003 -1 House 1 Booster pump 1 2 None EA Y 1.0 FEUILLE DE TRAVAIL: 01-008-001 • Surpression domestique Re-install according to regulations

BE625 Quarters No. 18 20003 -1 House 2 Softener 1 2 EA EA Y 0.50

FEUILLE DE TRAVAIL 06-060-010 · Appareil de traitement à usage industriel (Softening of water and anti-trust treatment (water intended for human consumption). Belgium minimum EA but wast should have air gap

Install tun dish

BE625 Quarters No. 18 20003 -1 House 3 Hose bibb 1 5 None HA N 0.5 To protect building internal water quality Hose union backflow preventer BE625 Quarters No. 18 20003 -1 House 5 Hose bibb 1 5 None HA N 0.5 To protect building internal water quality Hose union backflow preventer BE625 Quarters No. 18 20003 1 House 6 External Hose bibb 1 5 None HA N 0.5 To protect building internal water quality Hose union backflow preventer BE625 Quarters No. 18 20003 1 House 7 Internal Hose Bibbs 2 5 None HA N 0.5 To protect building internal water quality Hose union backflow preventer BE625 Quarters No. 18 20003 2 House 8 Rear Bth room Bath hose too long 1 5 None HB N 0.5 Hose too long Install Shower hose union anti-vacuum valve BE625 Quarters No. 18 20003 2 House 9 Rear Bth room Shower hose too long 1 5 None HB N 0.5 Hose too long Install Shower hose union anti-vacuum valve BE625 Quarters No. 18 20003 2 House 10 Front Bth room Bath hose too long 1 5 None HB N 0.5 Hose too long Install Shower hose union anti-vacuum valve

BE625 Quarters No. 18 20003 2 House 11 Front Bth room Shower hose too long 1 5 None HB N 0.5 Hose too long Install Shower hose union anti-vacuum valve al la tio n

N am e

B ui ld in g N o.

Fl oo r Facility Name To go to location click on description

Cross Connectio n Ref No.

Click on Ref No. to go to Location on Floor Plan

Equipment Type Click on Description to go to photograph Quantity Hazard Installed Required BP Size Inches Comments Action

Sterrebeek

BE828 Sterrebeek Annex 80001 -1 Boiler Room 0 Incomming Protection 1 2 BA BA N 2.0

Honeywell 2 inch RPZ device. Initial test indicated that the first check and releif valve were stuck. This device is situated in a floodable basement (drainage is bt small sump pump and basement has been flooded in recent history FAILED EN 1717 para 6 "for all domestic uses and for the non domestic uses where interior examination is possible and the guarantees sufficient, protection unit shall be a controllable check valve"

Remove this device, this supplies the commercial dish washer in kitchen which has an Air Gap. Insert testable single check valve (EA). This will save on mainteance and testing costs and satisfy regulations (provided boiler make-up is disconnected).

BE828 Sterrebeek Annex 80001 -1 Boiler Room 1 Softener for Boiler Make-up 1 2 BA BA Y 0.5

Honeywell 1/2 inch RPZ device. Initial inspection that the releif valve is stuck open. This device is situated in a floodable basement (drainage is bt small sump pump and basement has been flooded in recent history) FAILED

Remove this device and modify boiler top up to be separated with an Air Gap. (Remove flexible pipe link and only connect when top up required, using flexible link with Certified double check valve.) This will save on mainteance and testing costs.

BE828 Sterrebeek Annex 80001 -1 Boiler Room 2 Hose Bibb 1 5 None HA N 0.5 To protect building internal water quality This hose bibb is on the drinking water side of other protection deveices.

Balnk off and relocate to down steam side of No. 2 PPZ

Blank off 1/2 inch hose bib

BE828 Sterrebeek Annex 80001 1 DODDS School Kitchen 1 Water Heater PRV Outlet 1 5 EA AA N 0.5 To protect building internal water quality The relief oultlet of the PRV is not correctly insatlled Modify waste connection to give air gap

BE828 Sterrebeek Annex 80002 -1 DODDS Elementary School 0 Building Supply 1 2 None EA N 3.0

EN 1717 para 6 "for all domestic uses and for the non domestic uses where interior examination is possible and the guarantees sufficient, protection unit shall be a controllable check valve"

Install controllable antipollution check-valve on 3 foot vertictal section

BE828 Sterrebeek Annex 80002 1 DODDS Elementary School 1 Janitors sink 1 5 None HA N 0.5 To protect building internal water quality Hose union backflow preventer

BE828 Sterrebeek Annex 80002 1 DODDS Elementary School 2 Water Heater PRV Outlet 1 5 EA AA 0.5 To protect building internal water quality The relief oultlet of the PRV is not correctly installed and no check valve apparent

Modify waste connection to give air gap a and install combined PRV with internal check valve

BE828 Sterrebeek Annex 80002 2 DODDS Elementary School 3 Janitors sink 1 5 None HA N 0.5 To protect building internal water quality Hose union backflow preventer

BE828 Sterrebeek Annex 80003 -1 DODDS High Scool 0 Building Supply 1 2 None EA N 3.0

EN 1717 para 6 "for all domestic uses and for the non domestic uses where interior examination is possible and the guarantees sufficient, protection unit shall be a controllable check valve"

Install controllable antipollution check-valve on 3 foot vertictal section. To be checked: all cold water should be on a system with a BA to protect the school building water supply

BE828 Sterrebeek Annex 80003 1 DODDS High Scool 1 Janitors sink 1 5 None HA N 0.5 To protect building internal water quality Hose union backflow preventer BE828 Sterrebeek Annex 80003 1 DODDS High Scool 2 Room H1 Laboratory Cold sink sets 6 5 None HA N 0.5 To protect building internal water quality Hose union backflow preventer BE828 Sterrebeek Annex 80003 1 DODDS High Scool 3 Room H1 Laboratory Cold sink 1 5 None HA N 0.5 To protect building internal water quality Hose union backflow preventer

BE828 Sterrebeek Annex 80003 1 DODDS High Scool 4 Room H1 Teachers Desk Laboratory Hot & Cold sink

1 5 None HA N 0.5 To protect building internal water quality Hose union backflow preventer

BE828 Sterrebeek Annex 80003 1 DODDS High Scool 5 Chemical Preparation sink. Treaded spout on H/C combination fawcet

1 5 None HA N 0.5 To protect building internal water quality Hose union backflow preventer

BE828 Sterrebeek Annex 80003 1 DODDS High Scool 6 Room H3 Laboratory Cold sink sets 6 5 None HA N 0.5 To protect building internal water quality Hose union backflow preventer BE828 Sterrebeek Annex 80003 1 DODDS High Scool 7 Room H3 Laboratory sink 1 5 None HA N 0.5 To protect building internal water quality Hose union backflow preventer

BE828 Sterrebeek Annex 80003 1 DODDS High Scool 8 Room H3 Teachers Desk Laboratory Hot & Cold sink

1 5 None HA N 0.5 To protect building internal water quality Hose union backflow preventer

BE828 Sterrebeek Annex 80003 2 DODDS High Scool 9 Janitors sink 1 5 None HA N 0.5 To protect building internal water quality Hose union backflow preventer

BE828 Sterrebeek Annex 80011 1 Health Clinic 0 Building Supply 1 5 None EA N 1.25

EN 1717 para 6 "for all domestic uses and for the non domestic uses where interior examination is possible and the guarantees sufficient, protection unit shall be a controllable check valve"

Install controllable antipollution check-valve on 3 foot vertictal section in Mechanical room

BE828 Sterrebeek Annex 80011 1 Health Clinic 2 Room 100 Hose Bibb on softened water

1 5 None HA N 0.5 To protect softened/ boiler make-up water Hose union backflow preventer

BE828 Sterrebeek Annex 80011 1 Health Clinic 4 Room 162 Shower Hose too long 1 5 None HB N 0.5 To protect building internal water quality Install Shower hose union anti-vacuum valve

BE828 Sterrebeek Annex 80011 1 Health Clinic 5 Room 150 Water connection to cutter 1 4 None EA N 0.5 To protect building internal water quality Install on feed to cold water fawceta hose union backflow preventerand and mark NON POTABLE

BE828 Sterrebeek Annex 80013 1 DODDS Art & Music 1 Sink shower hose too long 1 4 None HB N 0.5 To protect building internal water quality Install Shower hose union anti-vacuum valve beneath sink

BE828 Sterrebeek Annex 80013 1 DODDS Art & Music 2 Sink shower hose too long 1 4 None HB N 0.5 To protect building internal water quality Install Shower hose union anti-vacuum valve beneath sink

BE828 Sterrebeek Annex 80013 1 DODDS Art & Music 3 Sink shower hose too long 1 4 None HB N 0.5 To protect building internal water quality Install Shower hose union anti-vacuum valve beneath sink

BE828 Sterrebeek Annex 80014 1 DODDS Gym 0 Room 21 Incoming protection 1 2 EA EA N 3.0

Test regime devised to cater for possibility of check valves down-stream and leaky valves on supply. (Hose attached to center tapping and filled to approx 3.5 meters, - Supply valve closed, Close downstream valve, - Clear hose attached to valve body drain beetween supply valve and check valve and taken over highest point on supply line in mech room. - Center tap opened.

(Increase in water flow of water coming out of drian equals a failure) FAILED 25/9/15

REPAIR and RETEST

BE828 Sterrebeek Annex 80014 1 DODDS Gym 1 Water Softener discharge no air gap 1 2 EA AA N 0.5

FEUILLE DE TRAVAIL 06-060-010 · Appareil de traitement à usage industriel (Softening of water and anti-trust treatment (water intended for human consumption).

Belgium minimum EA, however, as the water is also used for boiler top up it may require CA.

Install tun dish and waste water drain

BE828 Sterrebeek Annex 80014 1 DODDS Gym 2 Room 21 Hose Bibb 1 5 None HA N 0.5 To protect building internal water quality Hose union backflow preventer BE828 Sterrebeek Annex 80014 1 DODDS Gym 3 Ice machine 1 5 AG AA N 0.5 AG required on drain from ice machine Install tun dish and waste water drain BE828 Sterrebeek Annex 80014 1 DODDS Gym 4 Rooms 19 & 20 Hose Bibbs 2 5 None HA N 0.5 To protect building internal water quality Hose union backflow preventer

BE828 Sterrebeek Annex 80015 1 Youth Center 0 Drinking Water Feed 1 2 BA EA N 2.0 NOTE According to the drawimgs Building has only 1 water feed line and that is from the fire main: Therefore all water could be considered NON Potable PASSED 29/9/15

This device could be removed as it supplies the commercial/domestic equipment in kitchen which have Air Gaps. Insert testable single check valve (EA). This will save on mainteance and testing costs and satisfy regulations (provided boiler make-up is disconnected).

BE828 Sterrebeek Annex 80015 1 Youth Center 2 Hose bibb 1 5 None HA N 0.5 To protect building internal water quality Hose union backflow preventer

BE828 Sterrebeek Annex 80015 1 Youth Center 3 Boiler make-up 1 3 BA BA Y 0.75 FAILED

Remove this device and modify boiler top up to be separated with an Air Gap. (Only connect when top up required, using flexible link with Certified double check valve.) This will save on mainteance and testing costs.

BE828 Sterrebeek Annex 80015 1 Youth Center 4 Hose Bibbs 4 5 None HA N 0.5 To protect building internal water quality Hose union backflow preventer

BE828 Sterrebeek Annex 80018 1 Water Treatment (Meter Bldg) Site

Supply Point

See Composite photo

The recent modifica tions to the supply point appear to have been done with out referenc e to Belgaqu a standars

TO PROTECT PUBLIC SUPPLY & SITE DRINKING

WATER SYSTEM FROM FIRE FIGHTING WATER

SYSYEM

Install EA on supply main and BA (RPZ) on fire main. A detailed description/proposal of the action to correct the deficiency will be provided as submittal for approval

BE828 Sterrebeek Annex 80018 1 Water Treatment (Meter Bldg) Site

Supply Point

See photo

BE828 Sterrebeek Annex 80018 1 Water Treatment (Meter Bldg) Site

Supply Point

See photo

BE828 Sterrebeek Annex 80018 1 Water Treatment (Meter Bldg) Site

Supply Point

See photo

BE828 Sterrebeek Annex 80018 1 Water Treatment (Meter Bldg) Site

Supply Point

See photo

BE828 Sterrebeek Annex 80018 1 Water Treatment (Meter Bldg) Site

Supply Point

See photo

BE828 Sterrebeek Annex 80018 1…