B8 Purchase Description Mobile Ground Power Unit 20260917.pdf

PDF 164 KB Posted

Attached to
Mobile Frequency Converter
Solicitation number
W912NS26Q8539
Issued by

About this file

This document is a Statement of Objectives (SOO) for a federal contract opportunity (W912NS26Q8539) issued by the Missouri National Guard for the Aviation Classification Repair Activity Depot (MOAVCRAD). The contracting agency requires two Mobile Frequency Converters to support depot-level maintenance operations across a 14-state region serving 31 aircraft support facilities. The frequency converters must support multiple helicopter platforms including UH-60, CH-47, AH-64, and MV-75 aircraft, providing electrical power for maintenance testing, troubleshooting, adjusting, aircraft starting, and other operational needs.

The Mobile Frequency Converters must meet specific technical requirements including a minimum power output of 90 KVa/72 kW at 261 amps continuous and 565 amps peak; DC output voltage of 270 VDC (2-wire, grounded negative, adjustable ±10%); and AC output voltage of 115/200 VAC, 3 phase, 4 wire, grounded neutral at 400Hz (±0.01%). The units must be capable of 200% overload for 20 seconds on AC output and 2 seconds on DC output, with 3-phase 480VAC 60Hz power input and cable assemblies (100-foot AC input, 60-foot DC and AC outputs). General requirements include weather-resistant coating, mobility on 4 tires, overload/short circuit/overvoltage protection with safety disconnect, automatic input line monitoring, multifunction digital displays, USB port for event extraction, JBusModbus Protocol, 15% Automatic Line Drop Compensation (ALDC), Emergency Power Off switch, I/O monitoring and display, elapsed time meter, fault indicators, and input/output cable racks. The units must comply with ISO 1540, ISO 6858, SAE ARP 5015, MIL-STD-704F, MIL-STD-1472, and DFS-400 specifications. Systems must be delivered mission-ready with minimal maintenance requirements, and warranty will be included as an evaluation factor.

View the file

Other files

File Type Posted
B8 Provisions and Clauses W912NS26Q8539.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

W912NS26Q8539

Missouri National Guard AVCRAD Mobile Frequency Converters

1. The Missouri Army National Guard’s Aviation Classification Repair Activity Depot (MO- AVCRAD) requires two (2) Mobile Frequency Converters to support the MO AVCRAD’s depot level maintenance program for a 14-state region of 31 aircraft support facilities. The Frequency Converters must be able to support multiple aircraft platforms, specifically UH- 60, CH-47, and AH-64, and MV-75. Frequency Converters will be used to provide electrical power to aircraft for maintenance testing, troubleshooting, adjusting, and providing power for aircraft starting as well as other operations.

2. The system must be capable of repeated use and require minimal maintenance and up keep and be lightweight enough to be regularly moved efficiently while safely and repeatedly performing their functions. The EGPUs should be capable of supplying multiple amperages and voltages and be delivered mission ready. Warranty will be included as an evaluation factor.

3. The minimum specifications required to meet MO AVCRAD requirements:

a. Power Requirements

a. Minimum Power Output of 90KVa / 72 kW, at 261 amps, continuous and 565 AMPS peak

b. DC Output voltage of 270 VDC, 2-wire, grounded negative, adjustable plus or minus 10%

c. AC Output voltage of 115/200 VAC, 3 phase, 4 wire, grounded neutral 400Hz plus or minus .01%.

d. Capable of at least 200% overload for 20 seconds on AC output and 200% for two (2) seconds on DC output.

e. Adjustable AC/DC Voltage

f. Power input of 3 Phase, 480VAC 60Hz 3 phase power input.

g. 100-foot AC input power cable, using a BHP10485D plug

h. One 60-foot DC power output cable.

i. One 60-foot AC power output cable.

b. General Requirements

a. be protected from overload, short circuit, over voltage and have a safety disconnect.

b. Capable of operating indoors and outdoors under all weather and lighting conditions.

c. Finished in weather resistant coating

d. Mobile, on 4 tires

e. Automatic input line monitoring.

f. Multifunction digital displays.

g. Equipped with USB port for event extraction.

h. Equipped with JBusModbus Protocol.

i. Equipped with 15% Automatic Line Drop Compensation (ALDC).

j. Equipped with an Emergency Power Off switch (EPO).

k. Equipped with I/O voltage, current, and frequency monitoring and display.

l. Equipped with an elapsed time meter.

m. Equipped with fault indicators.

n. Equipped with input and output cable racks.

o. Designed with input high voltage transient protection from lightning strikes with preventative maintenance annunciation.

p. Output Universal Aircraft Safety Interlock Circuit Disconnect.

q. Units shall meet the following specifications/standards:

1. ISO 1540 Characteristics of Aircraft electrical system.

2. ISO 6858 Aircraft Ground Support electrical supplies.

3. SAE ARP 5015 Ground Equipment 400 Hz ground power performance requirement.

4. MIL-STD-704F Aircraft electrical power characteristics.

5. MIL-STD-1472 Human Engineering Design Criteria.

6. DFS-400 Specifications of 400 Hz aircraft power.