QAs_w_Answers_for_RFIs__2_Fire_Suppression.pdf

PDF 72 KB Posted

Attached to
Repair Hangar Fire Suppression System
Solicitation number
W912LA-19-B-9003
Issued by

About this file

RFIs with answers #2

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Responses to Questions (RFIs) #2, 3 Sep 2019, RFQ: W912LA-19-B-9003

Q1 – Please clarify if the new fire alarm system is to be installed to meet current ADA audio/visual code requirements, or if it just needs to be capable of expanding to ADA requirements and provide outputs to the Monaco mass notification system in the future. Prior response was not applicable to this RFI and non-responsive.

A1 – Capable of expanding to ADA requirements and provide outputs to Monaco MNS

Q2 - Will programming and/or necessary modification to existing Monaco system for integration with new fire alarm system be provided by others?

A2 – Programming and/or necessary modification to existing Monaco System for integration with new Fire alarm system shall be provided by Contractor.

Q3 - Can a bid extension be granted due to a supplementary RFI submittal? We request the later of 9/10/19 or 4 business days after this RFI is answered.

A3 – Bid opening cannot be extended.

File details come from the government source that posted it.