Responses to Questions (RFIs) #2, 3 Sep 2019, RFQ: W912LA-19-B-9003
Q1 – Please clarify if the new fire alarm system is to be installed to meet current ADA audio/visual code requirements, or if it just needs to be capable of expanding to ADA requirements and provide outputs to the Monaco mass notification system in the future. Prior response was not applicable to this RFI and non-responsive.
A1 – Capable of expanding to ADA requirements and provide outputs to Monaco MNS
Q2 - Will programming and/or necessary modification to existing Monaco system for integration with new fire alarm system be provided by others?
A2 – Programming and/or necessary modification to existing Monaco System for integration with new Fire alarm system shall be provided by Contractor.
Q3 - Can a bid extension be granted due to a supplementary RFI submittal? We request the later of 9/10/19 or 4 business days after this RFI is answered.
A3 – Bid opening cannot be extended.