RFI___3_Generator.docx

DOCX document 19 KB Posted

Attached to
Emergency Generator Installation
Solicitation number
W912K6-13-R-2005
Issued by

View the file

Other files

File Type Posted
sign_in_sheet_generator.pdf PDF
Generator_Site_Plans.dwg DWG drawing
RFI__2_Generator.docx DOCX document
FACILITY_2040_PROPOSED_CONDITION.docx DOCX document
preproposal-emergency_generator.ppt PPT presentation
RFI_1_Generator.docx DOCX document
Map.pdf PDF
W912K6-13-R-0008-P00001.pdf PDF
W912K6-13-R-0008.pdf PDF
EXHIBIT_F.docx DOCX document
SOW_PJMS132022_Install_Emergency_Generator.pdf PDF
Map.pdf PDF
EAL.xlsx XLSX spreadsheet
Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EXHIBIT F

PROPOSAL INQUIRY FORMAT

SOLICITATION W912K6-13-R-0008

NOTE: ALL PRE-PROPOSAL INQUIRIES SHALL BE SUBMITTED VIA EMAIL IN THIS FORMAT!!

EMAIL: 175WG.MSC@ang.af.mil

Date of RFI: 18 September 2013

1. Will autocad backgrounds for each building and generator site be made available by the Government to the contractor upon award for use in preparing design documents? If not, is the contractor responsible to create these backgrounds? Auto CAD Files of the various generator locations will be made available.

2. Please confirm a rental generator is needed on one (1) site: Bldg 2072, Radio Relay. If so, please provide duration of rental. Yes, a rental generator will be necessary to keep building operational. The duration shall be determined by the awarded vendor. Duration should be determined by the length of time vendor will need to complete the wiring of the new ATS, including reenergizing by BGE.

3. Bldg 2030, Dining Hall please confirm type of enclosure for automatic transfer switch; indoors (NEMA 1) OR outdoor (NEMA 3R) NEMA 1

4. Bldg 2120, Headquarters please confirm type of enclosure for automatic transfer switch; indoors (NEMA 1) OR outdoor (NEMA 3R) NEMA 1, shall be located where existing ATS is now located.

5. All transfer switches which are outdoor (NEMA 3R) manufacturer recommends a strip heater within enclosure. Please advise all outdoor (NEMA 3R) ATS’ to include heater. If recommended by manufacturer, please install.