REQUEST FOR INFORMATION
Contract No.:
Question To: 184 CES From: Harbin Construction LLC
(Architect) Attn: Capt Baird Ihme (G.C.)
2200 Centennial Rd Salina, KS 67401
Date: From: Kathy McCandless RFI Number: 003
COST IMPACT: YES / NO
Specification Section: Plan Sheet: A2.2 Attachment
Query Title:
Answer Needed By: asap
Electrical Contractor is to provide 2 new fire alarm speakers. Can you tell us who is currently providing the fire alarm? Will they be required to program them?
Project Manager Response:
Drawings incorrectly depict two speakers at each location. Only one new speaker is required in the Women’s Restroom. Speakers are tied to the Mass Notification System so the new speaker can be run in parallel with the existing ones and no programming will be required.
Sign/Date:
COTR Response:
COTR Sign/Date: