HANGAR 7 DOOR INSTALL RFI’S 2
W912JB-18-B-5000
1. In the solicitation contract form it states that: INSTALL ONE EXTERIOR PERSONNEL DOOR
IN ROOM 123, AND ADD POWER TO TWO HANGAR DOORS IN HANGAR 7. During the walk thru we only looked at the one door, what other door is to be motorized? Or was this a typo?
The Hangar Doors open in opposite directions, one half moves to East pocket and the other moves to the
West pocket. Both doors are to be motorized in the scope of work.
2. Upon looking at the door opener/closer that you want to use, the issue came up that the "pocket" for the door does not appear large enough to allow the drive unit to enter the "pocket" along with the door sections. The limit would need to be set to stop the door before the drive unit hit the wall next to the pocket. Just need to make sure you are aware of this possible issue.
Acknowledged the above statement that accurate quality control is expected to ensure project completion with safety and function as the primary factors.