Otay Electrical Supplemental.pdf

PDF 1 MB Posted

Attached to
Otay Electrical Install - San Diego, CA
Solicitation number
W912HZ22Q7676
Issued by

View the file

Other files

File Type Posted
A02 PWS_BTADS-P_Otay_Electrical.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OTAY MESA GATE 499

New Sub Panel Fed from Lighting Control Panel

WIRING DIAGRAM

D

FE

DE R A L AVI AT IO

N

N

OITA

A

RTSINIM

DEPARTMENT OF TRANSPORTATION

FEDERAL AVIATION ADMINISTRATION

MIKE MONRONEY AERONAUTICAL CENTER OKLAHOMA CITY, OKLAHOMA

2/1/2022DATE:

APPROVED BY ---SUBMITTED BY ---

SDC-IMB-G499-2021-001_2-1-22

SHEET 5 OF 7

REV

REVIEWED BY

DESIGNED BY D. FRENCH

. . . .REV . . . . CHKD: APPVD:

. . . .REV . . . . CHKD: APPVD:

ISSUED BY AJW-542

NAS SYSTEM SUPPORT

PROPOSED BTADS SITE 1

WIRING CONFIGURATION

L1 N

15A

BTADS Sub Panel

30A 1 Phase 120V

15A

L2

L3

480V

From Lighting Control

Sub Panel

10A 2 Phase 480V

4KVA 480V Primary, 120V

Secondary Stepdown

Transformer

BTADS EQUIPMENT

OUTLET

30A

SUMP PUMP

GFCI OUTLET

L2LINE

L3LINE

Grounding X4 at the transformer provides the system with a N conductor,creating a 30A 1 Phase

120V service.

X3

X2

X1

X4

H1

H3

H2

H4

120V

10 AWG BLACK, STRANDED,

INSULATED, COPPER

CONDUCTOR

10 AWG WHITE, STRANDED,

INSULATED, COPPER

CONDUCTOR

12 AWG BLACK, STRANDED,

INSULATED, COPPER

CONDUCTOR

12 AWG WHITE, STRANDED,

INSULATED, COPPER

CONDUCTOR

ENCLOSURE

BOND

Conduit exists from Gate 499 to the vaults already. FAA will complete the panel and wiring on page 3. What is needed if to pull the wire through the existing conduit and do the connections at each end as shown on pages 5-7.

WIRING DIAGRAM

D

FE

DE R A L AVI AT IO

N

N

OITA

A

RTSINIM

DEPARTMENT OF TRANSPORTATION

FEDERAL AVIATION ADMINISTRATION

MIKE MONRONEY AERONAUTICAL CENTER OKLAHOMA CITY, OKLAHOMA

2/1/2022DATE:

APPROVED BY ---SUBMITTED BY ---

SDC-IMB-G499-2021-001_2-1-22

SHEET 6 OF 7

REV

REVIEWED BY

DESIGNED BY D. FRENCH

. . . .REV . . . . CHKD: APPVD:

. . . .REV . . . . CHKD: APPVD:

ISSUED BY AJW-542

NAS SYSTEM SUPPORT

PROPOSED BTADS SITE 2

WIRING CONFIGURATION

L1 N

15A

BTADS Sub Panel

30A 1 Phase 120V

15A

L2

L3

480V

From Lighting Control

Sub Panel

10A 2 Phase 480V

4KVA 480V Primary, 120V

Secondary Stepdown

Transformer

BTADS EQUIPMENT

OUTLET

30A

SUMP PUMP

GFCI OUTLET

L2LINE

L3LINE

Grounding X4 at the transformer provides the system with a N conductor,creating a 30A 1 Phase

120V service.

X3

X2

X1

X4

H1

H3

H2

H4

120V

10 AWG BLACK, STRANDED,

INSULATED, COPPER

CONDUCTOR

10 AWG WHITE, STRANDED,

INSULATED, COPPER

CONDUCTOR

12 AWG BLACK, STRANDED,

INSULATED, COPPER

CONDUCTOR

12 AWG WHITE, STRANDED,

INSULATED, COPPER

CONDUCTOR

ENCLOSURE

BOND

WIRING DIAGRAM

D

FE

DE R A L AVI AT IO

N

N

OITA

A

RTSINIM

DEPARTMENT OF TRANSPORTATION

FEDERAL AVIATION ADMINISTRATION

MIKE MONRONEY AERONAUTICAL CENTER OKLAHOMA CITY, OKLAHOMA

2/1/2022DATE:

APPROVED BY ---SUBMITTED BY ---

SDC-IMB-G499-2021-001_2-1-22

SHEET 7 OF 7

REV

REVIEWED BY

DESIGNED BY D. FRENCH

. . . .REV . . . . CHKD: APPVD:

. . . .REV . . . . CHKD: APPVD:

ISSUED BY AJW-542

NAS SYSTEM SUPPORT

PROPOSED BTADS SITE 3

WIRING CONFIGURATION

L1 N

15A

BTADS Sub Panel

30A 1 Phase 120V

15A

L2

L3

480V

(3) Conductor, 4 awg stranded insulated copper wire from

Lighting Control Sub Panel

10A 2 Phase 480V

4KVA 480V Primary, 120V

Secondary Stepdown

Transformer

BTADS EQUIPMENT

OUTLET

30A

SUMP PUMP

GFCI OUTLET

L2LINE

L3LINE

ENCLOSURE

BOND

Grounding X4 at the transformer provides the system with a N conductor,creating a 30A 1 Phase

120V service.

X3

X2

X1

X4

H1

H3

H2

H4

120V

10 AWG BLACK, STRANDED,

INSULATED, COPPER

CONDUCTOR

10 AWG WHITE, STRANDED,

INSULATED, COPPER

CONDUCTOR

12 AWG BLACK, STRANDED,

INSULATED, COPPER

CONDUCTOR

12 AWG WHITE, STRANDED,

INSULATED, COPPER

CONDUCTOR

Gate 499 (Power Source)

TCM 3

V: 120 VAC

A: 30 W: 3600

TCM 2

V: 120 VAC

A: 30 W: 3600

TCM 1

V: 120 VAC

A: 30 W: 3600

Distance: 1497 ft

Distance: 576 ft

Distance: 2385 ft

1. Each of the 3 TCMs only need 120VAC to a subpanel that has a 30-amp breaker then 2 x 15-amp breakers. One 15-amp breaker for the TCM and one 15-amp breaker for the sump pump.

2. 120V*30A = 3600 watts would be required to each TCM.

For Official Use Only (FOUO)

Leg 1

Leg 2

Leg 3

Station 24

TCM1

Station 72

TCM2

Station 120

TCM3

Gate 499POE at Otay Mesa, CA Culvert

For Official Use Only (FOUO)

Off Slide

3. FAA/CBP OTAY Mesa Gate Drawings
4. BTADS Power Requirements with Approximate Distances