W81G6722375126
Electrical System Installation for Eau Galle Equestrian RV Park.
This solicitation is issued as a Request for Quote (RFQ) under the authority of FAR Part 13 - Simplif ied Acquisition Procedures, and is 100% set-aside for small business concerns. The estimated magnitude of this project is betw een $100,000 and $250,000.
The NAICS for this project is 238210, Electrical Contractors and Other WiTring Installation Contractors w ith a size standard of $16.5 Million.
In accordance w ith FAR 28.102-1, performance and payment bonds are required for any construction contract exceeding $150,000;
contracts betw een $35,000 and $150,000 only require payment bonds.
SCOTT E HENDRIX 651-290-5406
NOTE: In sealed bid solicitations "offer" and "offeror" mean "bid" and "bidder".
10. THE GOVERNMENT REQUIRES PERFORMANCE OF THE WORK DESCRIBED IN THESE DOCUMENTS
NEGOTIATED
31-Aug-2022
(RFP)
(IFB)
CALL:
B. TELEPHONE NO. (Include area code) (NO COLLECT CALLS)
See Item 7
2. TYPE OF SOLICITATION
SEALED BID
3. DATE ISSUED
9. FOR INFORMATION A. NAME
SOLICITATION
NSN 7540-01-155-3212 1442-101 STANDARD FORM 1442 (REV. 4-85)
Prescribed by GSA FAR (48 CFR) 53.236-1(e)
11. The Contractor shall begin performance w ithin _______10 calendar days and complete it w ithin ________ calendar days after receiving aw ard, X notice to proceed. This performance period is X mandatory, negotiable. (See _________________________FAR 52.211-10
12 A. THE CONTRACTOR MUST FURNISH ANY REQUIRED PERFORMANCE AND PAYMENT BONDS?
(If "YES," indicate within how many calendar days after award in Item 12B.)
X YES NO
13. ADDITIONAL SOLICITATION REQUIREMENTS:
A. Sealed offers in original and __________ copies to perform the w ork required are due at the place specif ied in Item 8 by ___________ local time ______________14 Sep 2022 (date). If this is a sealed bid solicitation, offers must be publicly opened at that time.
shall be marked to show the offeror's name and address, the solicitation number, and the date and time offers are due.
B. An offer guarantee is, X is not required.
C. All offers are subject to the (1) w ork requirements, and (2) other provisions and clauses incorporated in the solicitation in full text or by reference.
D. Offers providing less than _______60 calendar days for Government acceptance after the date offers are due w ill not be considered and w ill be rejected.
SOLICITATION, OFFER,
AND AWARD
(Construction, Alteration, or Repair)
1. SOLICITATION NO.
IMPORTANT - The "offer" section on the reverse must be fully completed by offeror.
4. CONTRACT NO.
7. ISSUED BY CODE
CONTRACTING DIVISION
USACE - ST PAUL
332 MINNESOTA STREET
SUITE E1500
SAINT PAUL MN 55101
W912ES
PAGE OF PAGES
CODE
(Title, identifying no., date):
12B. CALENDAR DAYS
10:00 AM (hour) Sealed envelopes containing offers
5. REQUISITION/PURCHASE REQUEST NO. 6. PROJECT NO.
8. ADDRESS OFFER TO (If Other Than Item 7)
FAX:TEL: 651-290-5414 TEL: FAX:
W912ES22Q0093 1 OF 56
20B. SIGNATURE
(REV. 4-85)STANDARD FORM 1442 BACK
TO SIGN
NSN 7540-01-155-3212
SOLICITATION, OFFER, AND AWARD (Continued) (Construction, Alteration, or Repair)
CODE FACILITY CODE
17. The offeror agrees to perform the w ork required at the prices specif ied below in strict accordance w ith the terms of this solicitation, if this offer is accepted by the Government in w riting w ithin ________ calendar days after the date offers are due.
the minimum requirements stated in Item 13D. Failure to insert any number means the offeror accepts the minimum in Item 13D.)
AMOUNTS SEE SCHEDULE OF PRICES
18. The offeror agrees to furnish any required performance and payment bonds.
19. ACKNOWLEDGMENT OF AMENDMENTS
(The offeror acknowledges receipt of amendments to the solicitation -- give number and date of each)
AMENDMENT NO.
DATE
20A. NAME AND TITLE OF PERSON AUTHORIZED TO SIGN
OFFER (Type or print)
AWARD (To be completed by Government)
21. ITEMS ACCEPTED:
22. AMOUNT 23. ACCOUNTING AND APPROPRIATION DATA
24. SUBMIT INVOICES TO ADDRESS SHOWN IN ITEM
(4 copies unless otherwise specified)
CODE
(Insert any number equal to or greater than
20C. OFFER DATE
25. OTHER THAN FULL AND OPEN COMPETITION PURSUANT TO
10 U.S.C. 2304(c) 41 U.S.C. 253(c)
CODE27. PAYMENT WILL BE MADE BY:26. ADMINISTERED BY
(Include ZIP Code)14. NAME AND ADDRESS OF OFFEROR 15. TELEPHONE NO. (Include area code)
See Item 14
(Include only if different than Item 14)16. REMITTANCE ADDRESS
30B. SIGNATURE
29. AWARD (Contractor is not required to sign this document.)
document and return _______ copies to issuing office.) Contractor agrees Your of f er on this solicitation, is hereby accepted as to the items listed. This award con-to f urnish and deliv er all items or perf orm all work, requisitions identif ied summates the contract, which consists of (a) the Gov ernment solicitation and on this f orm and any continuation sheets f or the consideration stated in this y our of f er, and (b) this contract award. No f urther contractual document is contract. The rights and obligations of the parties to this contract shall be necessary .
gov erned by (a) this contract award, (b) the solicitation, and (c) the clauses, representations, certif ications, and specif ications or incorporated by ref er-ence in or attached to this contract.
30A. NAME AND TITLE OF CONTRACTOR OR PERSON AUTHORIZED 31A. NAME OF CONTRACTING OFFICER (Type or print)
30C. DATE
(Type or print)
TEL: EMAIL:
31B. UNITED STATES OF AMERICA 31C. AWARD DATE
BY
CONTRACTING OFFICER WILL COMPLETE ITEM 28 OR 29 AS APPLICABLE
(Contractor is required to sign this28. NEGOTIATED AGREEMENT
(M ust be fully completed by offeror)OFFER
W912ES22Q0093
Section 00 10 00 - Solicitation
SUBMITTAL INSTRUCTIONS
This solicitation is a Request for Quotes (RFQ), which should result in one firm fixed price contract. This solicitation is not an invitation for bids (IFB) or request for proposals (RFP).
Any questions concerning this solicitation shall only be accepted via email at scott.e.hendrix@usace.army.mil
Please submit your quote as a PDF attachment to an email sent to Scott.E.Hendrix@usace.army.mil
Evaluation of quotes shall be conducted under the auspices of FAR Part 13.
Quotes shall be evaluated by Price and Past Performance.
Quotes shall contain the following:
Complete Blocks 14, 15 and 20 a-c (with signature in block 20b) on the SF 1442 Complete the Price Schedule Complete 52.204-8 Annual Representations and Certifications (Oct 2018) Provide no more than five examples of projects similar in scope, to include contact information of the receiving service/organization.
All pricing (unit, total, subtotal, grand total, etc.) must be in whole penny amounts.
Offeror shall be registered in SAM (System for Award Management) https://www.sam.gov to include the FAR and DFARS Reps and Certs sections with the NAICS code applicable to the solicitation.
For assistance with SAM, please contact:
SAM by GSA Hours of Operation: Monday – Friday 8am to 8pm ET, U.S. Calls 866-606-8220 Service desk website: http://www.fsd.gov/gsafsd_sp
Quotes must be received no later than the date and time stated in the solicitation. Quotes received after the deadline are Late, and may not be considered for contract award.
Please monitor Contract Opportunities (https://sam.gov/content/opportunities) for any amendments to the solicitation. It is the responsibility of the vendor to specifically acknowledge ALL amendments prior to the solicitation close. The preferred method of acknowledging an amendment is to return a signed copy of the amendment (form SF30) first page as a PDF email attachment with your quote. Failure to acknowledge amendments may result in your offer not being considered for award.
As a component of the U.S. Government, the U.S. Army Corps of Engineers is exempt from Federal, State and Local taxes, including sales taxes. Please do not include sales tax(es) in quoted price.
mailto:scott.e.hendrix@usace.army.mil mailto:Scott.E.Hendrix@usace.army.mil https://sam.gov/content/opportunities
ITEM NO SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT
0001 1 Job
INSTALLATION OF ELECTRICAL SERVICES
FFP
AT EAU GALLE
FOB: Destination
MILSTRIP: W81G6722375126
PURCHASE REQUEST NUMBER: W81G6722375126
PSC CD: N059
NET AMT
DELIVERY INFORMATION
CLIN DELIVERY DATE QUANTITY SHIP TO ADDRESS DODAAC /
CAGE
0001 16-JUN-2023 1 EAU GALLE DAM
BRADLEY LABADIE
W501 EAU GALLE DAM ROAD
SPRING VALLEY WI 54767-9057
1 (715) 778-5562 X 5716 FOB: Destination
965702
SCOPE OF WORK
ELECTRICAL SYSTEM INSTALLATION FOR EAU GALLE EQUESTRIAN RV
PARK
U.S. ARMY CORPS OF ENGINEERS
SPRING VALLEY, WISCONSIN
The Contractor will install new RV pedestals, sub-panel, lighting, and corresponding conductors at Eau Galle Equestrian RV Park located at N1832 Dugan Road, Spring Valley, WI 54767.
1 General
1.1 Project Description
The work at Eau Galle consists of installing 12, 50 Amp RV pedestals, installation of a new sub-panel, and installing lighting and receptacles at the vault toilet. Further information is available in the following sections. The Contractor is responsible for all costs and materials, related to this project. Items include, but are not limited to, cable, panels, pedestals, circuit breakers, lighting, installation hardware, labor, and permitting cost. A site visit is recommended and can be arrange with the POC; Brad LaBadie. The pedestal locations for each site will be marked by the Eau Galle staff prior to the site visit.
Figure 1. Eau Galle Equestrian Park.
1.1.1 Campsites
There are 10 existing campsites, with campsites 3 and 4 being double RV sites that each have two pedestals. The pedestals will be supplied power from the main panel located in the well house.
Circuit arrangements and sizes are shown in figure 2.
The well house panel is a 400 Amp, 3-wire, 42 space, Square D NQOD4 panelboard. The manufacturer recommended circuit breakers are Square D type LA, LH, and Q4. Other brand/type circuit breakers may be UL listed for the panel and it is the contractor’s responsibility to determine what circuit breakers are used.
All buried conductors must be aluminum type USE with XLPE insulation meeting the requirements of section 2.2.1
1.1.2 Vault Toilet
A 100 Amp subpanel will be installed at the existing vault toilet as indicated in figure 3. The subpanel must be outdoor rated NEMA 3R, placed inside a larger NEMA 4 steel enclosure. The outer NEMA 4 enclosure must have a drip shield and locking handle or hasp. A rigid galvanized conduit stub and bushing will be used to protect the conductor from damage in accordance with
NFPA 70, 305(D).
Three GFCI receptacles will be installed, one in each restroom and one on the exterior of the building with the exterior receptacle being on its own circuit. The exterior receptacle will include a while-in-use weather cover and must be mounted 48 inches above the ground. Surface mounted wall lights will be installed in each restroom and an outdoor wall pack, with photocell, will be installed on the exterior of the building.
All Conduits run outdoors must be galvanized rigid type with weather tight hubs. All conduits inside the vault toilet must be surface mounted EMT, surface mounted Schedule 40 PVC, or Schedule 80 PVC.
A grounding electrode must be installed according to NFPA 70.
Figure 8. Vault toilet layout.
1.2 Schedule
The work must be completed by June 16th, 2023. The contractor shall provide a work schedule in writing at least 1 week prior to the start of work. Point of contact for questions is Brad LaBadie, 651-290-5716.
1.3 Safety
The contractor must perform all work in a safe manner and in accordance with U.S. Army Corps of Engineers EM 385-1-1, Safety and Health Requirements Manual.
1.4 Submittals
The Contractor shall submit shop drawings and material certifications electronically via email to the Contracting Officer’s Representative (COR) after award and prior to construction activity.
Government review turnaround time will be within five (5) business days from the date of receipt by the Contracting Officer. The Contractor will be notified by the Contracting Officer of the results of the review and of final approval. Any work performed prior to notification of approval shall be at the Contractor’s own risk. Government approval is required for submittals with a “G” designation; submittals not having a “G” designation are for information only. When used, a designation following the “G” designation identifies the office that will review the submittal for the Government.
The following submittals are required if used in the system design:
a. Product Data Panelboards; G Low Voltage Underground Cable; G Wire and Cable; G Outlet Boxes, Pull Boxes, and Junction Boxes; G Circuit Breakers; G RV Pedestals; G Buried Warning Tape; G Conduits; G Lighting; G Receptacles; G
b. Test Reports
Continuity Test; G Insulation Resistance Test; G Ground-Fault Receptacle Test; G
c. Manufacturer’s Instructions Manufacture’s Instructions
1.5 Quality Control
1.5.1 Regulatory Requirements
Ensure equipment, materials, installation, and workmanship are in accordance with the mandatory and advisory provisions of NFPA 70, unless more stringent requirements are specified or indicated.
2 Products
2.1 Equipment
2.1.1 Panelboards
Provide panelboards in accordance with NEMA PB 1, UL 67, and UL 50. Ensure panelboards for use as service equipment are also in accordance with UL 869A. Ensure panelboard enclosure are NEMA 250, Type 3R. Ensure panelboards have current rating, number of phases, and number of wires as indicated or specified herein. Ensure panelboards are rated for 240-volt (maximum), single-phase, 60-hertz. Ensure each panelboard, as a complete unit, has a short-circuit current rating equal to or greater than the integrated equipment rating indicated, but in no case less than 10,000 amperes symmetrical. Finish panelboards with baked enamel. Finish color is ASTM D1535 No. 61 gray conforming to FED-STD-595. Exterior hardware to be stainless steel. Provide enclosure fronts with latchable hinged doors.
Provide panelboards with bolt-on circuit breakers only. Use of plug-in style breaker is not permitted. Ensure panelboards are designed such that individual breakers can be removed without disturbing adjacent units or without loosening or removing supplemental insulation supplied as means of obtaining required clearance. Provide main lugs or main circuit breakers mounted "above" branch breakers with current ratings as indicated. Use of sub-feed breakers is not acceptable unless specifically indicated otherwise. Where "space only" is indicated, make provisions for future installation of breakers. Submit detail drawings and manufacturer's standard product data for panelboards. Detail drawings consist of fabrication and assembly drawings for all parts of the work in sufficient detail to verify conformity with all requirements. Ensure drawings for panelboards indicate details of bus layout, overall physical features, dimensions, ratings, service requirements, and weights of equipment.
2.1.2 Circuit Breakers
Provide bolt-on type, molded-case, manually operated, trip-free circuit breakers, with inverse time thermal-overload protection and instantaneous magnetic short-circuit protection. Completely enclose circuit breakers in a molded case, with a factory-sealed, calibrated sensing element to prevent tampering. Plug-in type, tandem, and half-size circuit breakers are not permitted.
Provide sufficient interrupting capacity of the panel and lighting branch circuit breakers to successfully interrupt the maximum short-circuit current imposed on the circuit at the breaker terminals. Provide circuit breaker interrupting capacities with a minimum of 10,000 A and that conform to NEMA AB 3. Series rating of circuit breakers or overcurrent protective devices to achieve indicated interrupt rating is permitted.
Provide the common-trip-type multipole circuit breakers having a single operating handle and a two-position on/off indication. Provide circuit breakers with temperature compensation for operation in an ambient temperature of 40 degrees C 104 degrees F. Provide circuit breakers that have root mean square (rms) symmetrical interrupting ratings sufficient to protect the circuit being supplied. Interrupting ratings may have selective-type tripping (time delay, magnetic, thermal, or ground fault).
Provide a phenolic-composition breaker body capable of having such accessories as handle extension, handle-locking, and padlocking devices attached where required to meet lockout/tag-out requirements of NFPA 70E.
2.1.3 RV Pedestals
Provide RV pedestals as shown on the drawings and specified herein. Pedestals shall be UL listed suitable for RV service equipment and shall be factory prewired and assembled with twin 450MCM Cu/Al loop feed lugs. Construction shall be galvanized G90 steel, 0.053 inches material thickness.
Pedestals shall include factory wired NEMA receptacles as follows: one 14-50, one TT30, and one 5-20WR. Pedestals shall include factory prewired circuit breakers to match the above receptacles; one 50amp two pole, one 30amp single pole, and one 20amp single pole with GFCI.
Pedestals shall be designed for underground service and include rolled edges on the post bottoms to protect service cable.
Paint to be electro-deposition e-coat, ANSI 67 gray color.
2.1.4 Outlet Boxes, Pull Boxes and Junction Boxes
Ensure outlet boxes for use with conduit systems are in accordance with NEMA FB 1 UL 514A, UL 514B, UL 514C and are not less than 40 millimeter 1-1/2 inches deep. Furnish all pull and junction boxes with screw-fastened covers.
2.1.5 Rigid Steel Conduit
Provide hot dipped galvanized rigid steel conduit complying with NEMA RN 1, ANSI C80.1, UL 6 and UL 5 as applicable. Except where installed underground, or in corrosive areas, provide polyvinylchloride (PVC), or protect from corrosion by painting with bitumastic coating or wrapping with corrosion inhibiting tape.
Use threaded fittings for rigid steel conduit.
Use solid gaskets. Ensure conduit fittings with blank covers have gaskets, except in clean, dry areas or at the lowest point of a conduit run where drainage is required.
Provide covers with captive screws and are accessible after the work has been completed.
2.1.6 Electrical Metallic Tubing (EMT)
Ensure EMT is in accordance with UL 797, UL 5, and ANSI C80.3 and is zinc coated steel.
Provide zinc-coated couplings and connectors that are raintight, compression type with insulated throat. Crimp, spring, or setscrew type fittings are not acceptable
2.1.7 Rigid Nonmetallic Conduit
Ensure rigid nonmetallic conduit complies with NEMA TC 2, NEMA TC 3, and UL 651 as applicable with a wall thickness not less than Schedule 40.
2.1.8 Receptacles
Provide the following:
a. UL 498, hard use (also designated heavy-duty), grounding-type.
b. Ratings and configurations: as indicated.
c. Bodies: ivory as per NEMA WD 1.
d. Face and body: thermoplastic supported on a metal mounting strap.
e. Dimensional requirements: per NEMA WD 6.
f. Screw-type, side-wired wiring terminals or of the solderless pressure type having suitable conductor-release arrangement.
g. Grounding pole connected to mounting strap.
h. The receptacle: containing triple-wipe power contacts and double or triple-wipe ground contacts.
2.1.8.1 Weatherproof Receptacles
Provide receptacles, UL listed for use in "wet locations." Include cast metal box with gasketed, hinged, lockable and weatherproof while-in-use, die-cast metal/aluminum cover plate.
2.1.8.2 Ground-Fault Circuit Interrupter Receptacles
UL 943, duplex type for mounting in standard outlet box. Provide device capable of detecting current leak of 6 milliamperes or greater and tripping per requirements of UL 943 for Class A ground-fault circuit interrupter devices. Provide screw-type, side-wired wiring terminals or prewired (pigtail) leads.
2.1.9 Lighting
Provide side mounted light fixture on the common wall in each toilet stall. The fixture shall be LED damp location canopy type, nominal 20 Watts 120 VAC, 60 HZ. The fixture shall supply a minimum of 2000 lumens, with a color temperature between 4000 and 5000 K. The nominal size shall not exceed 1 ft. X 1 ft. Mount near ceiling. The fixture shall be UL, ETL or CuL listed.
Provide occupancy sensor for automatic lighting control for each stall. The light switch will be for override on. The occupancy sensor shall mount on the common wall in each toilet stall.
Sensor shall be passive infrared type, 400 watts 120 VAC. To mount to a switch or light fixture box.
Provide outdoor light fixture in the front of the new vault toilet. See the attached drawing. The light fixture shall be wired to a separate breaker in the sub panel. And shall be activated by a photocell. The photocell may be a part of the fixture or may be separate. The outdoor light fixture shall be an outdoor wall pack 25-Watt LED type. Polycarbonate with dark bronze finish, color temperature between 4000 and 5000K. 120 VAC, 60 HZ. The fixture shall supply a minimum 1500 lumens. The fixture shall be UL listed. Operating temperature between -30 Deg F to 120 Deg F.
2.2 Materials
2.2.1 Buried Low Voltage Insulated Conductor
Insulated conductors must be rated 600 volts and conform to the requirements of NFPA 70, including listing requirements. Wires and cables manufactured more than 24 months prior to date of delivery to the site are not acceptable. Buried conductors must conform to UL 854, type USE.
2.2.1.1 Conductor Types
Cables sizes indicated are for aluminum conductors type USE unless otherwise noted.
2.2.1.2 Insulation Material
Provide insulation which is a cross-linked thermosetting polyethylene (XLPE) type, meeting the requirements of, as applicable, or an ethylene-propylene rubber (EPR) type meeting the requirements of NEMA WC 70.
2.2.1.3 Insulation Thickness
The insulation thickness for single-conductor and multiple-conductor power cables rated 2,000 volts and below must be as required by NEMA WC 70, as applicable. Some thicknesses of NEMA WC 70 will be permitted only for single conductor cross-linked thermosetting polyethylene insulated cables without a jacket. NEMA WC 70 ethylene-propylene rubber-insulated conductors must have a jacket.
2.2.1.4 Direct Buried
Provide cables identified for direct burial.
2.2.2 Low Voltage Wire Connectors and Terminals
Provide a uniform compression over the entire conductor contact surface. Use solderless terminal lugs on stranded conductors. For use with aluminum conductors: UL 486A-486B. For connecting aluminum to copper, connectors must be the circumferentially compressed, metallurgically bonded type.
2.2.3 Vault Toilet Wire and Cable
Provide wires and cables in accordance applicable requirements of NFPA 70 and UL for type of insulation, jacket, and conductor specified or indicated. Do not use wires and cables manufactured more than 12 months prior to date of delivery to site.
Minimum branch circuit size must be No. 14 AWG.
Ensure connectors used in wire systems comply with UL 486A-486B and UL 486C as applicable.
2.2.3.1 Insulation
Unless specified or indicated otherwise or required by NFPA 70, provide power and lighting wires rated for 600-volts, Type THWN/THHN conforming to UL 83 or Type XHHW conforming to UL 44, except that grounding wire may be type TW conforming to UL 83; remote-control and signal circuits: Type TW or TF, conforming to UL 83. Where lighting fixtures require 90-degree Centigrade (C) conductors, provide only conductors with 90-degree C insulation or better.
2.2.4 Grounding and Bonding
2.2.4.1 Driven Ground Rods
Provide copper-clad steel ground rods conforming to UL 467 not less than ¾ inch in diameter by 10 feet in length.
2.2.4.2 Grounding Conductors
Stranded-bare copper conductors must conform to ASTM B8, Class B, soft-drawn. Solid-bare copper conductors must conform to ASTM B1 for size No. 8 and smaller.
2.2.5 Buried Warning and Identification Tape
Polyethylene plastic and metallic core or metallic-faced, acid- and alkali-resistant, polyethylene plastic warning tape manufactured specifically for warning and identification of buried utility lines.
Provide tape on rolls, 3-inch minimum width, red colored, electric warning, and identification imprinted in bold black letters continuously over the entire tape length. Warning and identification to read, "CAUTION, BURIED ELECTRIC LINE BELOW" or similar wording.
Color and printing shall be permanent, unaffected by moisture or soil.
3 Execution
3.1 Preparation
Submit manufacturer's instructions including special provisions required to install equipment components and system packages. Special provisions include impedances, hazards, and safety precautions.
Protect metallic materials against corrosion. Provide equipment enclosures with the standard finish by the manufacturer when used for most indoor installations. Do not use aluminum when in contact with earth or concrete and, where connected to dissimilar metal, protect by using approved fittings and treatment.
Except where other equivalent protective treatment is specifically approved in writing, provide hot-dip galvanized ferrous metals for items such as, anchors, bolts, braces, boxes, bodies, clamps, fittings, guards, nuts, pins, rods, shims, thimbles, washers, and miscellaneous items not made of corrosion-resistant steel.
3.2 Installation
Underground service conductors must be continuous from service entrance equipment to outdoor power system connection.
3.2.1 Direct Burial Cable System
Direct-bury cables in the earth to the requirements of NFPA 70.
3.2.2 Trenching
Excavate trenches for direct-burial cables to provide a minimum cable cover of 610 mm 24 inches below finished grade for power conductors operated at 600 volts or less. When rock is encountered, remove to a depth of at 3 inches below the cable and fill the space with sand or clean earth free from particles larger than ¼ inch. Bottoms of trenches must be smooth and free of stones and sharp objects. Where materials in bottoms of trenches are other than sand, 3-inch layer of sand must be laid first and compacted to approximate densities of surrounding firm soil.
Trenches must be not less than 8 inches wide and must be in straight lines between cable markers.
Bends in trenches must have a radius consistent with the cable manufacturer's published minimum cable bending radius for the cable installed.
3.2.3 Cable Installation
Unreel cables along the sides of or in trenches and carefully place on sand or earth bottoms.
Pulling cables into direct-burial trenches from a fixed reel position is not permitted, except as required to pull cables through conduits under paving or railroad tracks. Where two or more cables are laid parallel in the same trench, space cables laterally at not less than 3 inches apart.
3.2.4 Buried Warning and Identification Tape
Provide buried utility lines with utility identification tape. Bury tape 12 inches below finished grade.
3.2.5 Terminating Aluminum Conductors
Terminate aluminum conductors to copper bus either by: (1) in line splicing a copper pigtail to the aluminum conductor (copper pigtail must have an ampacity at least that of the aluminum conductor); or (2) using a circumferential compression type, aluminum bodied terminal lug UL listed for AL/CU and steel Belleville spring washers, flat washers, bolts, and nuts. Belleville spring washers must be cadmium-plated hardened steel. Install the Belleville spring washers with the crown up toward the nut or bolt head, with the concave side of the Belleville bearing on a heavy-duty, wide series flat washer of larger diameter than the Belleville. Tighten nuts sufficient to flatten Belleville and leave in that position. Lubricate hardware with joint compound prior to making connection. Wire brush and apply joint compound to conductor prior to inserting in lug.
3.2.6 Grounding Systems
NFPA 70, except provide grounding systems with a resistance to solid earth ground not exceeding 25 Ohms.
3.2.6.1 Grounding Electrodes
Provide cone pointed driven ground rods driven full depth plus 12 inches, installed to provide an earth ground of the appropriate value for the equipment being grounded. If the specified ground resistance is not met, provide an additional ground rod in accordance with the requirements of NFPA 70 (placed not less than 6 feet from the first rod). Should the resultant (combined) resistance exceed the specified resistance, measured not less than 48 hours after rainfall, notify the Contracting Officer immediately.
3.2.7 RV Pedestals
Install RV pedestal according to figure 4. Secure pedestal to the in-ground rated post with galvanized hardware.
Figure 4. RV pedestal installation detail.
3.2.8 Conduits and Fittings
Ensure that conduit runs between outlet and outlet, between fitting and fitting, or between outlet and fitting does not contain more than the equivalent of three 90-degree bends, including those bends located immediately at the outlet or fitting. Do not install crushed or deformed conduit.
Avoid trapped conduit runs where possible. Take care to prevent the lodgment of foreign material in the conduit, boxes, fittings, and equipment during the course of construction. Clear any clogged conduit of obstructions or replace conduit.
Conduit and raceway runs concealed in or behind walls, above ceilings, or exposed on walls and ceilings 1470 millimeter 5 feet or more above finished floors and not subject to mechanical damage may be electrical metallic tubing (EMT).
Install conduit parallel with or at right angles to ceilings, walls, and structural members where located above accessible ceilings and where conduit will be visible after completion of project.
3.2.8.1 Rigid Steel Conduit
Make field-made bends and offsets with approved Hickey bending tool or conduit bending machine. Use long radius conduit for elbows larger than 2-1/2 inches.
3.2.8.2 Electrical Metallic Tubing (EMT)
Ground EMT in accordance with NFPA 70, using pressure grounding connectors especially designed for EMT.
3.2.8.3 Rigid Nonmetallic Conduit
Install a green insulated copper grounding conductor in conduit with conductors and solidly connect to ground at each end. Size grounding wires in accordance with NFPA 70.
3.2.8.4 Conduit Support
Support conduit by pipe straps, wall brackets, threaded rod conduit hangers, or ceiling trapeze.
Fasten by wood screws to wood; by toggle bolts on hollow masonry units; by concrete inserts or expansion bolts on concrete or brick; and by machine screws, welded threaded studs, or spring tension clamps on steel work. Threaded C-clamps may be used on rigid steel conduit only. Do not weld conduits or pipe straps to steel structures. Do not exceed one-fourth proof test load for load applied to fasteners. Provide vibration resistant and shock-resistant fasteners attached to concrete ceiling. Do not cut main reinforcing bars for any holes cut to depth of more than 40 mm 1 1/2 inches in reinforced concrete beams or to depth of more than 20 mm 3/4 inch in concrete joints.
Fill unused holes. In partitions of light steel construction, use sheet metal screws. In suspended-ceiling construction, run conduit above ceiling. Do not support conduit by ceiling support system.
Conduit and box systems: supported independently of both (a) tie wires supporting ceiling grid system, and (b) ceiling grid system into which ceiling panels are placed. Do not share supporting means between electrical raceways and mechanical piping or ducts. Coordinate installation with above-ceiling mechanical systems to assure maximum accessibility to all systems.
3.2.9 Boxes and Fittings
Provide pull boxes where necessary in the conduit system to facilitate conductor installation.
Securely mount boxes and enclosures to the building structure using supports that are independent of the conduit entering or leaving the boxes.
Mount all wall-mounted outlet and switch boxes 48 inches as measured between the bottom of the box and the finished floor or ground.
3.3 Field Fabricated Nameplate
Provide number, location, and letter designation of nameplates as indicated
3.4 Field Quality Control
After completion of the installation and splicing, and prior to energizing the conductors, perform wire and cable continuity and insulation tests as herein specified before the conductors are energized.
Provide all necessary test equipment, labor, and personnel to perform the tests, as herein specified.
Isolate completely all wire and cable from all extraneous electrical connections at cable terminations and joints. Use substation and switchboard feeder breakers, disconnects in combination motor starters, circuit breakers in panel boards, and other disconnecting devices to isolate the circuits under test.
Perform insulation-resistance test on each field-installed conductor with respect to ground and adjacent conductors. Applied potential is 500 volts dc for 300 volt rated cable and 1000 volts dc for 600 volt rated cable. Take readings after 1 minute and until the reading is constant for 15 seconds. Minimum insulation-resistance values is not less than 25 Megohms for 300 volt rated cable and 100 Megohms for 600 volt rated cable. For circuits with conductor sizes AWG No. 8 and smaller insulation resistance testing is not required.
Perform continuity test to insure correct cable connection end-to-end (i.e., correct phase conductor, grounded conductor, and grounding conductor wiring). Repair and verify any damages to existing or new electrical equipment resulting from mis-wiring. Receive approval for all repairs prior to commencement of the repair.
Perform ground-fault receptacle test for ground-fault receptacles with a "load" (such as a plug-in light) to verify that the "line" and "load" leads are not reversed.
Submit test reports in accordance with referenced standards in this section.
Final acceptance requires the successful performance of wire and cable under test. Do not energize any conductor until the final test reports are reviewed and approved.
ELECTRICAL PEDESTAL
EXISTING WELL HOUSE PANEL
PANEL: Vault Toilet LOCATION:
VOLTAGE (V): 120/240 PHASE: BUS RATING (A): 100
NEUTRAL: MAIN BREAKER (A): 100 200% NEUTRAL:
MINIMUM AIC (kA): 18 GROUND BUS:
YES
NO
YES
WIRE SERVICE: 3 SERVICE ENTRANCE: NO
ENCLOSURE TYPE: 3R FEED THRU LUGS: NO
MOUNTING: SURFACE PANEL SOURCE: WH Panel IG BUS: YES SOURCE LOCATION: Well House
SPD (L-N, L-G, N-G): NO
NOTES
WIRING
REQUIREMENT BRANCH CIRCUIT LOAD
DESCRIPTION
CONN.
LOAD
(VA)
LOAD
TYPES CKT.
DF CKT.
CONN. CIRCUIT BREAKERS CKT.
CONN. CKT.
DF LOAD
TYPES CONN. LOAD
(VA) BRANCH CIRCUIT LOAD
DESCRIPTION
WIRING
REQUIREMENT NOTES CB SPACE
#/PHASE CB
No. 12 AWG Indoor GFCI Receptacles 360 R L1-N 20/1 1 L1 2 20/1 L1-N Spare No. 12 AWG Outdoor GFCI Receptacle 180 R L2-N 20/1 3 L2 4 20/1 L2-N Spare Spare L1-N 15/1 5 L1 6 15/1 L1-N Spare No. 14 AWG Lighting 200 L L2-N 15/1 7 L2 8 Blank Blank 9 L1 10 Blank Blank 11 L2 12 Blank Blank 13 L1 14 Blank Blank 15 L2 16 Blank Blank 17 L1 18 Blank
SUB-TOTAL LEFT SIDE (KVA) 0.74 0.74 SUB-TOTAL RIGHT SIDE (KVA)
LOAD TYPES
DEMAND
(KVA) DEMAN
D
FACTO
PANEL
DEMAND
(KVA)
CONNECTED LOAD LEFT SIDE
(KVA) TOTAL PER PHASE
(KVA) CONNECTED LOAD RIGHT SIDE (KVA)
PHASE CURRENT
UNASSIGNED LOAD
TYPE R (DF) 0.36 L1-N 0.36 L1-N LINE 1 3.00
LINE-2 3.17 A
A
L = LIGHTING LOAD 0.20 0.20 0.38 L2-N 0.38 L2-N
R = RECEPTACLE
LOAD 0.54 0.54 L1-L2 L1-L2
A = APPLIANCE LOAD TOTAL CONN. LOAD: 0.74
PANEL DEMAND: 0.74 PANEL DF: 1.00
MIN. PANEL AMP.: 3.17
DESIGN MARGIN: 42.00 DESIGN AMPACITY: 4.50
KVA
KVA
A A
LINE LOAD BALANCE
H = HEATING LOAD LINE 1 97.3% LINE 2 102.7%
M = MOTOR LOAD
E = EQUIPMENT LOAD
S = SUB-PANEL LOAD
FT = FEED THRU LOAD
O = OTHER LOAD
TOTAL 0.74 0.74
NOTES: SPD RATINGS (WHEN INDICATED YES):
SURGE CURRENT RATING PER PHASE (8X20uS):
UL 1449 SUPPRESSION VOLTAGE RATINGS (SVR):
1 No. 8 AWG GROUNDING ELECTRODE CONDUCTOR.
Section 00 21 00 - Instructions
CLAUSES INCORPORATED BY REFERENCE
52.204-7 System for Award Management OCT 2018 52.204-16 Commercial and Government Entity Code Reporting AUG 2020 52.222-5 Construction Wage Rate Requirements--Secondary Site of the
Work
MAY 2014
52.225-10 Alt I Notice of Buy American Requirement--Construction Materials (Feb 2009) Alternate I
MAY 2014
252.225-7056 Prohibition Regarding Business Operations with the Maduro Regime
MAY 2022
CLAUSES INCORPORATED BY FULL TEXT
52.222-23 NOTICE OF REQUIREMENT FOR AFFIRMATIVE ACTION TO ENSURE EQUAL
EMPLOYMENT OPPORTUNITY FOR CONSTRUCTION (FEB 1999)
(a) The offeror's attention is called to the Equal Opportunity clause and the Affirmative Action Compliance Requirements for Construction clause of this solicitation.
(b) The goals for minority and female participation, expressed in percentage terms for the Contractor's aggregate workforce in each trade on all construction work in the covered area, are as follows:
Goals for minority participation for each trade
Goals for female participation for each trade
2.9% 6.9%
These goals are applicable to all the Contractor's construction work performed in the covered area. If the Contractor performs construction work in a geographical area located outside of the covered area, the Contractor shall apply the goals established for the geographical area where the work is actually performed. Goals are published periodically in the Federal Register in notice form, and these notices may be obtained from any Office of Federal Contract Compliance Programs office.
(c) The Contractor's compliance with Executive Order 11246, as amended, and the regulations in 41 CFR 60-4 shall be based on (1) its implementation of the Equal Opportunity clause, (2) specific affirmative action obligations required by the clause entitled "Affirmative Action Compliance Requirements for Construction,'' and (3) its efforts to meet the goals. The hours of minority and female employment and training must be substantially uniform throughout the length of the contract, and in each trade. The Contractor shall make a good faith effort to employ minorities and women evenly on each of its projects. The transfer of minority or female employees or trainees from Contractor to Contractor, or from project to project, for the sole purpose of meeting the Contractor's goals shall be a violation of the contract, Executive Order 11246, as amended, and the regulations in 41 CFR 60-4. Compliance with the goals will be measured against the total work hours performed.
(d) The Contractor shall provide written notification to the Deputy Assistant Secretary for Federal Contract Compliance, U.S. Department of Labor, within 10 working days following award of any construction subcontract in excess of $10,000 at any tier for construction work under the contract resulting from this solicitation. The notification shall list the --
(1) Name, address, and telephone number of the subcontractor;
(2) Employer's identification number of the subcontractor;
(3) Estimated dollar amount of the subcontract;
(4) Estimated starting and completion dates of the subcontract; and
(5) Geographical area in which the subcontract is to be performed.
(e) As used in this Notice, and in any contract resulting from this solicitation, the "covered area" is Eau Galle Equestrian RV Park located at N1832 Dugan Road, Spring Valley, WI 54767 in St. Croix county.
(End of provision)
52.252-1 SOLICITATION PROVISIONS INCORPORATED BY REFERENCE (FEB 1998)
This solicitation incorporates one or more solicitation provisions by reference, with the same force and effect as if they were given in full text. Upon request, the Contracting Officer will make their full text available. The offeror is cautioned that the listed provisions may include blocks that must be completed by the offeror and submitted with its quotation or offer. In lieu of submitting the full text of those provisions, the offeror may identify the provision by paragraph identifier and provide the appropriate information with its quotation or offer. Also, the full text of a solicitation provision may be accessed electronically at this/these address(es):
FAR: https://www.acquisition.gov/browse/index/far DFARS: https://www.acquisition.gov/dfars
52.252-5 AUTHORIZED DEVIATIONS IN PROVISIONS (NOV 2020)
(a) The use in this solicitation of any Federal Acquisition Regulation (48 CFR Chapter 1) provision with an authorized deviation is indicated by the addition of "(DEVIATION)" after the date of the provision.
(b) The use in this solicitation of any Defense Federal Acquisition Regulation Supplement (48 CFR Chapter 2) provision with an authorized deviation is indicated by the addition of "(DEVIATION)" after the name of the regulation.
(End of provision) https://www.acquisition.gov/browse/index/far https://www.acquisition.gov/dfars
Section 00 45 00 - Representations and Certifications
52.204-19 Incorporation by Reference of Representations and
Certifications.
DEC 2014
252.203-7005 Representation Relating to Compensation of Former DoD Officials
NOV 2011
252.204-7008 Compliance With Safeguarding Covered Defense Information Controls
OCT 2016
252.204-7017 Prohibition on the Acquisition of Covered Defense Telecommunications Equipment or Services -- Representation
MAY 2021
52.204-8 ANNUAL REPRESENTATIONS AND CERTIFICATIONS (MAY 2022)
(a)(1) The North American Industry Classification System (NAICS) code for this acquisition is 238210.
(2) The small business size standard is $16,500,000.
(3) The small business size standard for a concern that submits an offer, other than on a construction or service acquisition, but proposes to furnish an end item that it did not itself manufacture, process, or produce is 500 employees if the acquisition--
(i) Is set aside for small business and has a value above the simplified acquisition threshold;
(ii) Uses the HUBZone price evaluation preference regardless of dollar value, unless the offeror waives the price evaluation preference; or
(iii) Is an 8(a), HUBZone, service-disabled veteran-owned, economically disadvantaged women-owned, or women-owned small business set-aside or sole-source award regardless of dollar value.
(b)(1) If the provision at 52.204-7, System for Award Management, is included in this solicitation, paragraph (d) of this provision applies.
(2) If the provision at 52.204-7, System for Award Management, is not included in this solicitation, and the Offeror has an active registration in the System for Award Management (SAM), the Offeror may choose to use paragraph (d) of this provision instead of completing the corresponding individual representations and certifications in the solicitation. The Offeror shall indicate which option applies by checking one of the following boxes:
( ) Paragraph (d) applies.
( ) Paragraph (d) does not apply and the offeror has completed the individual representations and certifications in the solicitation.
(c) (1) The following representations or certifications in SAM are applicable to this solicitation as indicated:
(i) 52.203-2, Certificate of Independent Price Determination. This provision applies to solicitations when a firm-fixed-price contract or fixed-price contract with economic price adjustment is contemplated, unless—
(A) The acquisition is to be made under the simplified acquisition procedures in Part 13;
(B) The solicitation is a request for technical proposals under two-step sealed bidding procedures; or
(C) The solicitation is for utility services for which rates are set by law or regulation.
(ii) 52.203-11, Certification and Disclosure Regarding Payments to Influence Certain Federal Transactions. This provision applies to solicitations expected to exceed $150,000.
(iii) 52.203-18, Prohibition on Contracting with Entities that Require Certain Internal Confidentiality Agreements or Statements--Representation. This provision applies to all solicitations.
(iv) 52.204-3, Taxpayer Identification. This provision applies to solicitations that do not include the provision at 52.204-7, System for Award Management.
(v) 52.204-5, Women-Owned Business (Other Than Small Business). This provision applies to solicitations that—
(A) Are not set aside for small business concerns;
(B) Exceed the simplified acquisition threshold; and
(C) Are for contracts that will be performed in the United States or its outlying areas.
(vi) 52.204-26, Covered Telecommunications Equipment or Services--Representation. This provision applies to all solicitations.
(vii) 52.209-2, Prohibition on Contracting with Inverted Domestic Corporations--Representation.
(viii) 52.209-5, Certification Regarding Responsibility Matters. This provision applies to solicitations where the contract value is expected to exceed the simplified acquisition threshold.
(ix) 52.209-11, Representation by Corporations Regarding Delinquent Tax Liability or a Felony Conviction under any Federal Law. This provision applies to all solicitations.
(x) 52.214-14, Place of Performance--Sealed Bidding. This provision applies to invitations for bids except those in which the place of performance is specified by the Government.
(xi) 52.215-6, Place of Performance. This provision applies to solicitations unless the place of performance is specified by the Government.
(xii) 52.219-1, Small Business Program Representations (Basic, Alternates I, and II). This provision applies to solicitations when the contract is for supplies to be delivered or services to be performed in the United States or its outlying areas, or when the contracting officer has applied part 19 in accordance with 19.000(b)(1)(ii).
(A) The basic provision applies when the solicitations are issued by other than DoD, NASA, and the Coast Guard.
(B) The provision with its Alternate I applies to solicitations issued by DoD, NASA, or the Coast Guard.
(C) The provision with its Alternate II applies to solicitations that will result in a multiple-award contract with more than one NAICS code assigned.
(xiii) 52.219-2, Equal Low Bids. This provision applies to solicitations when contracting by sealed bidding and the contract is for supplies to be delivered or services to be performed in the United States or its outlying areas, or when the contracting officer has applied part 19 in accordance with 19.000(b)(1)(ii).
(xiv) 52.222-22, Previous Contracts and Compliance Reports. This provision applies to solicitations that include the clause at 52.222-26, Equal Opportunity.
(xv) 52.222-25, Affirmative Action Compliance. This provision applies to solicitations, other than those for construction, when the solicitation includes the clause at 52.222-26, Equal Opportunity.
(xvi) 52.222-38, Compliance with Veterans' Employment Reporting Requirements. This provision applies to solicitations when it is anticipated the contract award will exceed the simplified acquisition threshold and the contract is not for acquisition of commercial products or commercial services.
(xvii) 52.223-1, Biobased Product Certification. This provision applies to solicitations that require the delivery or specify the use of USDA-designated items; or include the clause at 52.223-2, Affirmative Procurement of Biobased Products Under Service and Construction Contracts.
(xviii) 52.223-4, Recovered Material Certification. This provision applies to solicitations that are for, or specify the use of, EPA- designated items.
(xix) 52.223-22, Public Disclosure of Greenhouse Gas Emissions and Reduction Goals--Representation. This provision applies to solicitations that include the clause at 52.204-7.)
(xx) 52.225-2, Buy American Certificate. This provision applies to solicitations containing the clause at 52.225-1.
(xxi) 52.225-4, Buy American--Free Trade Agreements--Israeli Trade Act Certificate. (Basic, Alternates I, II, and III.) This provision applies to solicitations containing the clause at 52.225- 3.
(A) If the acquisition value is less than $25,000, the basic provision applies.
(B) If the acquisition value is $25,000 or more but is less than $50,000, the provision with its Alternate I applies.
(C) If the acquisition value is $50,000 or more but is less than $92,319, the provision with its Alternate II applies.
(D) If the acquisition value is $92,319 or more but is less than $100,000, the provision with its Alternate III applies.
(xxii) 52.225-6, Trade Agreements Certificate. This provision applies to solicitations containing the clause at 52.225-5.
(xxiii) 52.225-20, Prohibition on Conducting Restricted Business Operations in Sudan--Certification. This provision applies to all solicitations.
(xxiv) 52.225-25, Prohibition on Contracting with Entities Engaging in Certain Activities or Transactions Relating to Iran—Representation and Certification. This provision applies to all solicitations.
(xxv) 52.226-2, Historically Black College or University and Minority Institution Representation. This provision applies to solicitations for research, studies, supplies, or services of the type normally acquired from higher educational institutions.
(2) The following representations or certifications are applicable as indicated by the Contracting Officer:
[Contracting Officer check as appropriate.]
XXX (i) 52.204-17, Ownership or Control of Offeror.
(ii) 52.204-20, Predecessor of Offeror.
(iii) 52.222-18, Certification Regarding Knowledge of Child Labor for Listed End Products.
(iv) 52.222-48, Exemption from Application of the Service Contract Labor Standards to Contracts for Maintenance, Calibration, or Repair of Certain Equipment--Certification.
(v) 52.222-52 Exemption from Application of the Service Contract Labor Standards to Contracts for Certain Services--Certification.
(vi) 52.223-9, with its Alternate I, Estimate of Percentage of Recovered Material Content for EPA- Designated Products (Alternate I only).
(vii) 52.227-6, Royalty Information.
(A) Basic.
(B) Alternate I.
(viii) 52.227-15, Representation of Limited Rights Data and Restricted Computer Software.
(d) The Offeror has completed the annual representations and certifications electronically in SAM accessed through https://www.sam.gov. After reviewing the SAM information, the Offeror verifies by submission of the offer that the representations and certifications currently posted electronically that apply to this solicitation as indicated in paragraph (c) of this provision have been entered or updated within the last 12 months, are current, accurate, complete, and applicable to this solicitation (including the business size standard applicable to the NAICS code referenced for this solicitation), as of the date of this offer and are incorporated in this offer by reference (see FAR 4.1201); except for…