A02._PLAN_SET_DRAWINGS-2016-03-22-_Lock_18_Aux_-_OPTION_C.pdf

PDF 9 MB Posted

Attached to
LD 15, 16, 18, 22 Bulkhead Recesses
Solicitation number
W912EK-16-R-0006
Issued by

About this file

Plan set drawings- Lock 18 Aux.- Option C

View the file

Other files

File Type Posted
PLAN_SET_AMENDMENT-2016-05-18-AMD0004.pdf PDF
AMD0004_SPECS_2016-05-19.pdf PDF
W912EK-16-R-0006-0004.pdf PDF
Small_business_samples.pdf PDF
W912EK-16-R-0006-0003.pdf PDF
PLAN_SET_AMENDMENT-2016-04-29-AMD0003.pdf PDF
AMD0003_SPECS_2016-05-03.pdf PDF
Appendix_D_PPQ.pdf PDF
A22._AMD0002_PLANS_SPECS_2016-04-20.pdf PDF
W912EK-16-R-0006-0002.pdf PDF
W912EK-16-R-0006-0001.pdf PDF
MR169_AMD0001_SPECS_2016-04-14.pdf PDF
MR169_AMD_0001_PLANS_2016-04-14.pdf PDF
PPQ.pdf PDF
A02._PLAN_SET_DRAWINGS-2016-03-22-_Lock_22_Aux_-_OPTION_D.pdf PDF
A02._PLAN_SET_DRAWINGS-2016-03-22-_Lock_16_Main_-_BASE_BID.pdf PDF
A02._REFERENCE_DRAWINGS_Lock_16.pdf PDF
A02._PLAN_SET_DRAWINGS-2016-03-22-_Lock_22_THU_-_BASE_BID.pdf PDF
W912EK-16-R-0006_FINAL_SOLICITATION.pdf PDF
A02._PHOTOS_Lock_16_Aux.pdf PDF
A02._PLAN_SET_DRAWINGS-2016-03-22-_Lock_16_Aux_-_OPTION_B.pdf PDF
A02._REFERENCE_DRAWINGS_Lock_18.pdf PDF
A02._PLAN_SET_DRAWINGS-2016-03-22-_Lock_15_Main_-_BASE_BID.pdf PDF
A02._PHOTOS_Lock_15_Aux.pdf PDF
A02._PHOTOS_Lock_22_THU.pdf PDF
A02._PHOTOS_Lock_18_Aux.pdf PDF
A02._PHOTOS_Lock_16_Main.pdf PDF
A02._REFERENCE_DRAWINGS_Lock_15.pdf PDF
A02._PLAN_SET_DRAWINGS-2016-03-22-_Lock_15_Aux_-_OPTION_A.pdf PDF
A02._PHOTOS_Lock_22_Aux.pdf PDF
A02._PHOTOS_Lock_15_Main.pdf PDF
A02._REFERENCE_DRAWINGS_Lock_22.pdf PDF
Show all 32

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A N

S I

D m v r-a p p w p lt \P

W iC

S S h a re

\3

\4

\M

R -E

X X

X .d g n

:5

:1

A

M

M V

R -A

P P

W P

L T

D

A T

E

R O

C K I S

L A

N D

IL

L

IN

O

IS

R O

C K I S

L A

N D D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

S

M

-E

X X

X .d g n

K W

K

B M

A

A S S

H O

W N

G L

W

F

J

C

V E

R S

H E

E T

E000

L

C K

S

A N

D

M

IS

S

IS

S

IP

P I

R

IV

E R B

A S

IN

M R

C K

A

U X

IL

IA

R Y

DRAWINGS (E)

UPSTREAM AUXILIARY LOCK

LOCK 18

OPTION C

/0

/2

W E

K -1

-R -0

IL

L

IN

O

IS

IO

W A

A N

D M

IS

S

O U

R I

L O

C K C

H A

M B

E R B

U L

K H

E A

D R

E C

E S

S

FINAL

ID

Sheet

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

D A

T E

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps of Engineers

US Army Corps

P R

O J E

C T C

O D

STRUCTURAL NOTES

CLEARANCE DIAGRAM FOR BULKHEAD RECESS

REACTION ROLLER

BULKHEAD RECESS ASSEMBLY

GUIDE ROLLER

LOCK BULKHEAD

BEAM SIDE.

REACTION ROLLER

ROLLER AGAINST

WITH REACTION

" CLEARANCE2

BUFFER

C L

O F L

O C

K W

A L L

F A

C E T

O F

A C

L L E

R B

E A

M

C /L R

E A

C T

IO

N

-8

-2

4-1" *

"8 52-9 *

-1

-0

4'202

SCALE: IN FEET

WASHERS AND NUTS.

U-BOLTS WHICH WRAP AROUND THE LADDER RUNGS AND ASSOCIATED

" DIAMETER2

1 CONTRACTOR SHALL ASSUME HARDWARE CONSISTS OF FOUR

AND PROVIDE NEW STAINLESS STEEL HARDWARE TO REINSTALL THESE.

NEW LADDERS. CONTRACTOR SHALL DRILL FOUR NEW HOLES IN EACH DEVICE

THE CONTRACTOR SHALL REMOVE AND REINSTALL THESE DEVICES ON THE

THE EXISTING LADDERS ON BOTH THE INTERMEDIATE WALL AND RIVER WALL.

8. THERE ARE TWO EXISTING LADDER EXTENSION DEVICES ATTACHED TO

DRAWINGS FOR DETAILS.

REINFORCING IS NOT SHOWN ON REMOVAL DRAWINGS, SEE REFERENCE

7. REINFORCING IN EXISTING WALLS IS UNKNOWN IN SIZE AND LOCATION.

AS SPECIFIED IN AWS D1.1.

6. WELD SIZES NOT CALLED OUT SHALL MEET MINIMUM REQUIREMENTS

THE RECESS FRAMES FOR THE FULL HEIGHT OF THE RECESS.

BETWEEN THE ENDS OF THE BULKHEADS AND THE INSIDE WALL OF

" GAP2

1 5. IT IS INTENDED TO POSITION RECESS TO ACHIEVE A 1

".2

1 MORE THAN

4. BULKHEAD RECESS SHALL NOT VARY IN ALIGNMENT WITH ONE ANOTHER

IN 10'-0".

"16

1 3. BULKHEAD RECESS SHALL NOT VARY FROM PLUMB MORE THAN

AND FABRICATION OF MATERIAL.

SHOWN ON THE DRAWINGS PRIOR TO SHOP DRAWING PREPARATION

2. CONTRACTOR IS RESPONSIBLE FOR CONFIRMING ALL DIMENSIONS

RESOLUTION IF ANY ALIGNMENT PROBLEMS ARE ENCOUNTERED.

CONTRACTOR SHALL REPORT THE FINDINGS, AND PROPOSED

EQUAL CLEARANCE ON EACH END OF THE BULKHEAD. THE

AND THE REACTION ROLLER BEAMS ARE IN ALIGNMENT WITH

CENTERLINES OF THE REACTION ROLLERS ON THE BULKHEAD

DIMENSIONS MAY HAVE TO BE ADJUSTED SO THAT THE

AT THE MIDPOINT OF THESE TWO ELEVATIONS. THE 2'-10"

WALL ELEVATION, (1) AT THE SILL ELEVATION, AND (1)

THE VERTICAL FACE OF THE WALL: (1) AT THE TOP OF

MEASUREMENTS SHALL BE TAKEN AT THREE LOCATIONS ALONG

THE 2'-10" AND 1'-2" DIMENSIONS SHOWN ON THE CLEARANCE DIAGRAM.

FACE TO FACE OF LOCKWALLS IN CONJUNCTION WITH MAINTAINING

FABRICATION, VERIFY THE 110'-0" DIMENSION BETWEEN

B. DURING THE DIVE INSPECTION BUT PRIOR TO EMBEDDED STEEL

FACE OF RECESS SHALL BE 115'-8".

LOCK MEASUREMENT FROM INSIDE FACES OF RECESS TO INSIDE

". FINAL4

1 THE BEARING SURFACES ARE MAINTAINED AT +

THE CLEARANCES SHOWN BETWEEN THE BULKHEADS AND

A. ALIGN VERTICAL SURFACES OF THE RECESSES SUCH THAT

NECESSARILY LIMITED TO THE FOLLOWING:

SUCH FIT. THESE PRECAUTIONS SHOULD INCLUDE, BUT ARE NOT

THE CONTRACTOR SHALL TAKE THE NECESSARY PRECAUTIONS TO ASSURE

CRITICAL FOR OPERATIONAL FIT OF THE BULKHEADS IN THE RECESSES.

1. THE DIMENSIONS ANNOTATED BY ASTERISK (*) ON THIS SHEET ARE

ACCUMULATIONS IN THESE AREAS, SEE SPECIFICATIONS FOR DETAILS.

CONCRETE CONDITIONS FOR SEALING COFFERDAM, AND SILT/DEBRIS

9. THE CONTRACTOR SHALL PERFORM AN INITIAL DIVE INSPECTION TO VERIFY

A N

S I

D m v r-a p p w p lt \P

W iC

S S h a re

\3

\4

\M

R S -E

X X

X .d g n

:5

:3

A

M

M V

R -A

P P

W P

L T

D

A T

C K I S

L A

N D

IL

L

IN

O

IS

R O

C K I S

L A

N D D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

S -E

X X

X .d g n

C H J

B

S

H O

W N

J C

Q

F

C K

A

U X

IL

IA

Y

C K

S

A N

D

M

IS

S

IS

S

IP

P I

R

IV

E R B

A S

IN

M R

SE001

G E

N E

R A

L N

O T

E S

/0

/2

W E

K -1

-R -0

IL

L

IN

O

IS

IO

W A

A N

D M

IS

S

O U

R I

L O

C K C

H A

M B

E R B

U L

K H

E A

D R

E C

E S

S

Sheet

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

D A

T E

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps of Engineers

US Army Corps

P R

O J E

C T C

O D

Sheet

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

D A

T E

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps of Engineers

US Army Corps

P R

O J E

C T C

O D

SEE ELECTRICAL DRAWINGS

EXISTING LIGHT POLE,

LADDER AND GAGE

REMOVE EXISTING

MITER GATE MACHINERY

C/L

CHAMBER

LOCK

MAIN

T O R

E M

A

IN

E X

IS

T

IN

G H

A N

D R

A

IL

T O R

E M

A

IN

E X

IS

T

IN

G H

A N

D R

A

IL

N

0 4' 16'8'SCALE : 1/8"=1'-0"

EXISTING FILLING CULVERT

STA. 670.0A

EXISTING CHECKPOST

FILLING CULVERT

EXISTING

SEE ELECTRICAL DRAWINGS

ELECTRICAL DUCTBANK

EXISTING EMBEDDED

F L

O W

SE101

C1

SE101

C3

A N

S I

D m v r-a p p w p lt \P

W iC

S S h a re

\3

\4

\M

R S -E

X X

X .d g n

:5

:1

A

M

M V

R -A

P P

W P

L T

D

A T

C K I S

L A

N D

IL

L

IN

O

IS

R O

C K I S

L A

N D D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

S -E

X X

X .d g n

C H J

B

S

H O

W N

J C

Q

F

U P

S T

R E

A M L

O C

K E

N L

A R

G E

D P

L A

N

L O

C K

A

U X

IL

IA

C K

S

A N

D

M

IS

S

IS

S

IP

P I

R

IV

E R B

A S

IN

M R

EXISTING LADDER

REMOVE

SE100

STA. 707.6A

MONOLITH JOINT

STA. 680.6A

MONOLITH JOINT

SEE ELECTRICAL DRAWINGS

EXISTING LIGHT POLE

EXISTING MANHOLE NO. C6

ELECTRICAL DRAWINGS

DUCTBANK SEE

EXISTING ELECTRICAL

PINTLE STA. 590.0A

C/L

EXISTING MITER GATES

STA. 687.0A

MONOLITH JOINT

MANHOLE NO. C8

EXISTING

ELECTRICAL DRAWINGS

DUCTBANK SEE

EXISTING ELECTRICAL

INSTALLATION

BULKHEAD RECESS

CONCRETE FOR

REMOVE AND REPLACE

STA. 660.5A

LADDER

C/L EXISTING

STA. 660.5A

LADDER

C/L EXISTING

T O R

E M

A

IN

E X

IS

T

IN

G H

A N

D R

A

IL

T O R

E M

A

IN

E X

IS

T

IN

G H

A N

D R

A

IL

INSTALLATION

BULKHEAD RECESS

CONCRETE FOR

REMOVE AND REPLACE

INSTALLATION

BULKHEAD RECESS

CONCRETE FOR

REMOVE AND REPLACE

H A

N D

R A

IL

R E

P L

A C

E E

X

IS

T

IN

G

H A

N D

R A

IL

R E

P L

A C

E E

X

IS

T

IN

G

A1

AUXILIARY LOCK PLAN

/0

/2

W E

K -1

-R -0

IL

L

IN

O

IS

IO

W A

A N

D M

IS

S

O U

R I

L O

C K C

H A

M B

E R B

U L

K H

E A

D R

E C

E S

S

0 2' 4' 8'SCALE : 1/4"=1'-0"

SE102

C3

SE102

C1

SE102

A1

EL. 509.5

EL. 523.0

EL. 537.5

LOCKWALL

TOP OF

C /L

0 2' 4' 8'SCALE : 1/4"=1'-0"

HANDRAIL, SEE SHEET SD250

REPLACE EXISTING

REMOVE LADDER

FLOW

SEE ELECTRICAL DRAWINGS

EXISTING LIGHT POLE,

0 2' 4' 8'SCALE : 1/4"=1'-0"

SE103

C3

SE103

A1

SE103

C1

C /L

S T

A .0

G A

G E

S T

A .0

C H

E C

K P

O S

T

0 2' 4' 8'SCALE : 1/4"=1'-0"

TO REMAIN

CHECKPOST

EXISTING

FLOW

REMOVE LADDER

NO WORK REQUIRED

GATE MACHINERY

EXISTING MITER

SEE ELECTRICAL DRAWINGS

EXISITNG LIGHT POLE,

SEE SHEET SD250

REPLACE EXISTING HANDRAIL,

C /L

S T

A .0

L

IN

E H

O O

K S

S T

A .0

C H

E C

K P

O S

T C /L

C /L

S T

A .0

L

IN

E H

O O

K S

EL. 523.0

EL. 509.5

TO REMAIN

EXISTING CHECKPOST

S T

A .5

A

R E

C E

S S

M

IT

E R G

A T

E

S T

A .0

A

J O

IN

T

M O

N O

L

IT

H

S T

A .5

A

R E

C E

S S

M

IT

E R G

A T

E

REMOVE GAGE

LINE HOOK

REMOVE

ELECTRICAL DRAWINGS

MANHOLE SEE

EXISTING ELECTRICAL

SEE ELECTRICAL DRAWINGS

ELECTRICAL DUCTBANK

EXISTING EMBEDDED

SEE ELECTRICAL DRAWINGS

ELECTRICAL DUCTBANK

EXISTING EMBEDDED

ELECTRICAL DRAWINGS

MANHOLE SEE

EXISTING ELECTRICAL

A N

S I

D m v r-a p p w p lt \P

W iC

S S h a re

\3

\4

\M

R S -E

X X

X .d g n

:5

:1

A

M

M V

R -A

P P

W P

L T

D

A T

C K I S

L A

N D

IL

L

IN

O

IS

R O

C K I S

L A

N D D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

S -E

X X

X .d g n

C H J

B

S

H O

W N

J C

Q

F

D

M O

L

IT

IO

N P

L A

N S A

N D E

L E

V A

T

IO

N S

L O

C K

A

U X

IL

IA

C K

S

A N

D

M

IS

S

IS

S

IP

P I

R

IV

E R B

A S

IN

M R

EL. 537.5

LOCKWALL

TOP OF

MONOLITH 7

MONOLITH 7

MONOLITH 29

MONOLITH 29

SE101

S T

A .5

L A

D D

E R

LINE HOOK

REMOVE

S T

A .5

L A

D D

E R

C1

PLAN - RIVER WALL

C3

PLAN - INTERMEDIATE WALL

A3

ELEVATION - INTERMEDIATE WALL

A1

ELEVATION - RIVER WALL

/0

/2

W E

K -1

-R -0

IL

L

IN

O

IS

IO

W A

A N

D M

IS

S

O U

R I

L O

C K C

H A

M B

E R B

U L

K H

E A

D R

E C

E S

S

Sheet

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

D A

T E

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps of Engineers

US Army Corps

P R

O J E

C T C

O D

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

D A

T E

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps of Engineers

US Army Corps

P R

O J E

C T C

O D

E

0 1' 2' 4'SCALE : 1/2"=1'-0"

S T

A .5

A

M

IT

E R G

A T

E R

E C

E S

S

S T

A .5

A

E X

IS

T

IN

G L

A D

D E

R C /L

0 1' 2' 4'SCALE : 1/2"=1'-0"

1'-6"

S T

A .5

A

M

IT

E R G

A T

E R

E C

E S

S

S T

A .5

A

E X

IS

T

IN

G L

A D

D E

R C /L

2'-10"

4'-0"

R E

M O

V E E

X

IS

T

IN

G W

A L L A

R M

O R

0 1' 2' 4'SCALE : 1/2"=1'-0"

B3

4'-1"

RECESS ASSEMBLY

C/L BULKHEAD

POIREE DAM FOUNDATION

TOP OF EXISTING CONCRETE

DASHED LINE INDICATES

0 1' 2' 4'SCALE : 1/2"=1'-0"

GENERAL NOTES

SEE NOTE 12'-5"

S

P A

C E

S

"2 114'-10

C O

N C

R E

T E R

E M

O V

A L

L

IM

IT

O

F

"2 114'-10

BULKHEAD RECESS STEEL

REMOVE CONCRETE WITHIN

FILLING CULVERT

BULKHEAD RECESS

BULKHEAD RECESS STEEL

REMOVE CONCRETE WITHIN

A N

S I

D m v r-a p p w p lt \P

W iC

S S h a re

\3

\4

\M

R S -E

X X

X .d g n

:0

:4

A

M

M V

R -A

P P

W P

L T

D

A T

C K I S

L A

N D

IL

L

IN

O

IS

R O

C K I S

L A

N D D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

S -E

X X

X .d g n

C H J

B

S

H O

W N

J C

Q

F

IV

E R

W A

L L D

E M

O L

IT

IO

N S

E C

T

IO

N S

L O

C K

A

U X

IL

IA

C K

S

A N

D

M

IS

S

IS

S

IP

P I

R

IV

E R B

A S

IN

M R

EL. 509.5

SE102

VARIES

FILLING CULVERT

EL. 537.5 TO EL. 532.0

EL. 537.5 TO EL. 532.0

THIS AREA IS FROM

CONCRETE REMOVAL IN

C O

N C

R E

T E R

E M

O V

A L

L

IM

IT

O

F

EL. 504.0 TO EL. 508.0

EL. VARIES FROM

CONSTRUCTION OF LOCK 18 IN THE MID 1930's MAY HAVE AN AFFECT ON THIS DIMENSION.

REPRESENT AS-BUILT CONDITIONS. CONCRETE DETERIORATION SINCE THE

THESE DRAWINGS ARE BASED ON ORIGINAL CONTRACT DRAWINGS AND MAY NOT

AND NOTE PROXIMITY TO WORK UNDER THIS CONTRACT. DIMENSIONS SHOWN ON

1. THE CONTRACTOR SHALL NOTE THE LOCATION OF THE EXISTING FILLING CULVERT

EL. 516.5 TO EL. 522.0

EL. VARIES FROM

EL. 537.5

8'0"

8'-0"

EL. 532.0 TO EL. 509.5

C1

SECTION

C3

SECTION

B3

SECTION

A1

SECTION

/0

/2

W E

K -1

-R -0

IL

L

IN

O

IS

IO

W A

A N

D M

IS

S

O U

R I

L O

C K C

H A

M B

E R B

U L

K H

E A

D R

E C

E S

S

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

D A

T E

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps of Engineers

US Army Corps

P R

O J E

C T C

O D

E

0 1' 2' 4'SCALE : 1/2"=1'-0"

EL. 504.0

EL. 516.5 TO

FILLING CULVERT

S T

A .5

A

M

IT

E R G

A T

E R

E C

E S

S

C /L

0 1' 2' 4'SCALE : 1/2"=1'-0"

4'-6"

90°

S T

A .0

A

E X

IS

T

IN

G G

A G

E

S T

A .5

A

E X

IS

T

IN

G L

A D

D E

R

S T

A .5

A

M

IT

E R G

A T

E R

E C

E S

S

C /L

C /L

0 1' 2' 4'SCALE : 1/2"=1'-0"

VARIES

S

P A

C E

S

W A

L L A

R M

O R

R E

M O

V E E

X

IS

T

IN

G

4'-0"

EL. 516.5

FILLING CULVERT

EL. 509.5

2'-10"

B3

POIREE DAM FOUNDATION

TOP OF EXISTING CONCRETE

DASHED LINE INDICATES

RECESS ASSEMBLY

C/L BULKHEAD

4'-1"

0 1' 2' 4'SCALE : 1/2"=1'-0"

GENERAL NOTES

SEE NOTE 12'-5"

EL. 537.5

C O

N C

R E

T E R

E M

O V

A L

L

IM

IT

O

F

"2 114'-10

"2 13'-4 3'-6" 8'-0"

"2 114'-10

C O

N C

R E

T E R

E M

O V

A L

L

IM

IT

O

F

BULKHEAD RECESS STEEL

REMOVE CONCRETE WITHIN

BULKHEAD RECESS STEEL

REMOVE CONCRETE WITHIN

BULKHEAD RECESS

A N

S I

D m v r-a p p w p lt \P

W iC

S S h a re

\3

\4

\M

R S -E

X X

X .d g n

:0

:1

A

M

M V

R -A

P P

W P

L T

D

A T

C K I S

L A

N D

IL

L

IN

O

IS

R O

C K I S

L A

N D D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

S -E

X X

X .d g n

C H J

B

S

H O

W N

J C

Q

F

I- W

A L L D

E M

O L

IT

IO

N S

E C

T

IO

N S

L O

C K

A

U X

IL

IA

C K

S

A N

D

M

IS

S

IS

S

IP

P I

R

IV

E R B

A S

IN

M R

8'-0"3'-6""2 13'-4

S T

A .0

A

E X

IS

T

IN

G G

A G

E C /L

EL. 537.5 TO EL. 529.5

SE103

EL. 504.0

S T

A .5

A

E X

IS

T

IN

G L

A D

D E

R

DIMENSION.

CONSTRUCTION OF LOCK 18 IN THE MID 1930's MAY HAVE AN AFFECT ON THIS

REPRESENT AS-BUILT CONDITIONS. CONCRETE DETERIORATION SINCE THE

THESE DRAWINGS ARE BASED ON ORIGINAL CONTRACT DRAWINGS AND MAY NOT

AND NOTE PROXIMITY TO WORK UNDER THIS CONTRACT. DIMENSIONS SHOWN ON

1. THE CONTRACTOR SHALL NOTE THE LOCATION OF THE EXISTING FILLING CULVERT

EL. 529.5 TO EL. 509.5

EL. 529.5

SEE ELECTRICAL SHEETS

ELECTRICAL DUCTBANK

EXISTING EMBEDDED

C1

SECTION

C3

SECTION

B3

SECTION

A1

SECTION

/0

/2

W E

K -1

-R -0

IL

L

IN

O

IS

IO

W A

A N

D M

IS

S

O U

R I

L O

C K C

H A

M B

E R B

U L

K H

E A

D R

E C

E S

S

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

D A

T E

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps of Engineers

US Army Corps

P R

O J E

C T C

O D

E

0 2' 4' 8'SCALE : 1/4"=1'-0" 0 2' 4' 8'SCALE : 1/4"=1'-0"

0 2' 4' 8'SCALE : 1/4"=1'-0" 0 2' 4' 8'SCALE : 1/4"=1'-0"

NEW LADDER

NEW BULKHEAD RECESS

FLOW

SE151

C3

SE151

A1

SE151

C1

SE152

A1

SE151

C1

SE152

C3

NEW BULKHEAD RECESS

NEW LADDER

EXISTING CHECKPOST

NO WORK REQUIRED

GATE MACHINERY

EXISTING MITER

ARMOR (TYP)

GRIND EXISTING

S T

A .9

L A

D D

E R

C /L

C /L

S T

A .5

A

R E

C E

S S

M

IT

E R G

A T

E

S T

A .9

A

N E

W L

A D

D E

R

S T

A .0

A

C H

E C

K P

O S

T C /L

C /L

C /L

ARMOR (TYP)

GRIND EXISTING

FLOW

MK SE801-A1

NEW CORNER CAP

EXISTING CHECKPOST

S T

A .0

A

C H

E C

K P

O S

T C /L

S T

A .5

A

R E

C E

S S

M

IT

E R G

A T

E

S T

A .5

A

R E

C E

S S

B U

L K

H E

A D

S T

A .0

A

J O

IN

T

M O

N O

L

IT

H

S T

A .5

A

R E

C E

S S

B U

L K

H E

A D

MK SE801-A1

NEW CORNER CAP

ELECTRICAL DRAWINGS

MANHOLE SEE

EXISTING ELECTRICAL

SEE ELECTRICAL DRAWINGS

ELECTRICAL DUCTBANK

EXISTING EMBEDDED

SEE ELECTRICAL DRAWINGS

EXISTING LIGHT POLE

DRAWINGS

SEE ELECTRICAL

ELECTRICAL DUCTBANK

EXISTING EMBEDDED

ELECTRICAL DRAWINGS

MANHOLE SEE

EXISTING ELECTRICAL

A N

S I

D m v r-a p p w p lt \P

W iC

S S h a re

\3

\4

\M

R S -E

X X

X .d g n

:5

:0

A

M

M V

R -A

P P

W P

L T

D

A T

C K I S

L A

N D

IL

L

IN

O

IS

R O

C K I S

L A

N D D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

S -E

X X

X .d g n

C H J

B

S

H O

W N

J C

Q

F

W W

O R

K P

L A

N S A

N D E

L E

V A

T

IO

N S

L O

C K

A

U X

IL

IA

C K

S

A N

D

M

IS

S

IS

S

IP

P I

R

IV

E R B

A S

IN

M R

DRAWINGS

SEE ELECTRICAL

EXISTING LIGHT POLE

EL. 537.5

LOCKWALL

TOP OF

MONOLITH 7

EL. 537.5

LOCKWALL

TOP OF

MONOLITH 7

MONOLITH 29

MONOLITH 29

SE150

SE800-C1

CORNER ARMOR

NEW HORIZONTAL

SE801-B1

NEW CORNER CAP

SE801-B3

CORNER ARMOR

NEW VERTICAL

SD802-B4

CORNER ARMOR

NEW VERTICAL

SE801-B1

NEW CORNER CAP SE801-B1

CAP

NEW CORNER

SE801-B1

NEW CORNER CAP

SE800-C1

CORNER ARMOR

NEW HORIZONTAL

SE801-B3

CORNER ARMOR

NEW VERTICAL

SE802-B4

CORNER ARMOR

NEW VERTICAL

C1

PLAN - RIVERWALL

C3

PLAN - INTERMEDIATE WALL

A3

ELEVATION - INTERMEDIATE WALL

A1

ELEVATION - RIVERWALL

/0

/2

W E

K -1

-R -0

IL

L

IN

O

IS

IO

W A

A N

D M

IS

S

O U

R I

L O

C K C

H A

M B

E R B

U L

K H

E A

D R

E C

E S

S

0 1' 2' 4'SCALE : 1/2"=1'-0"

T

A .5

A

M

IT

E R G

A T

E R

E C

E S

S

S T

A .5

A

B U

L K

H E

A D R

E C

E S

S C /L

#6 @ 12 #6B @ 12 #6 @ 12

#6B @ 12

4 SP @ 1'-0" 2'-6" 3'-6" 2 SP @

#6 @ 12

1'-0"

S T

A .5

A

M

IT

E R G

A T

E R

E C

E S

S

S T

A .5

A

B U

L K

H E

A D R

E C

E S

S

S T

A .9

A

L A

D D

E R

C /L C /L

#6 @ 12

#6B @ 12

VERT.

#6B @ 12

#6 @ 12

1'-0"

#6B @ 12

4 SP @ 1'-0" 2'-6" 2 SP @3'-6"

0 1' 2' 4'SCALE : 1/2"=1'-0"

0 1' 2' 4'SCALE : 1/2"=1'-0"

A3

B3

BULKHEAD RECESS

4'-1"

1'-0"1'-0"

LOCK WALL

FACE OF

"2 16 #6 @ 12

PLACEMENT

WALL CONCRETE

R E

C E

S S

B U

L K

H E

A D

DAM FOUNDATION

CONCRETE POIREE

TOP OF EXISTING

DASHED LINE INDICATES

PLACEMENT

WALL CONCRETE

LOCKWALL

#6B ANCHORS

C/L BULKHEAD RECESS ASSEMBLY

BULKHEAD RECESS

4'-1"

C L

0 1' 2' 4'SCALE : 1/2"=1'-0"

0 1' 2' 4'SCALE : 1/2"=1'-0"

4'-0"

2'-10"

#6B ANCHORS

EL. 537.5

"2 15'-58'-0"

"2 114'-10

PLACEMENT

SILL CONCRETE

PLACEMENT

SILL CONCRETE

FILLING CULVERT

EXISTING

C O

N C

R E

T E R

E M

O V

A L

L

IM

IT

O

F

"2 114'-10

"2 16'-108'-0"

C O

N C

R E

T E R

E M

O V

A L

L

IM

IT

O

F

A N

S I

D m v r-a p p w p lt \P

W iC

S S h a re

\3

\4

\M

R S -E

X X

X .d g n

:5

:5

A

M

M V

R -A

P P

W P

L T

D

A T

C K I S

L A

N D

IL

L

IN

O

IS

R O

C K I S

L A

N D D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

S -E

X X

X .d g n

C H J

B

S

H O

W N

J C

Q

F

E R

W A

L L N

E W W

O R

K S

E C

T

IO

N S

L O

C K

A

U X

IL

IA

C K

S

A N

D

M

IS

S

IS

S

IP

P I

R

IV

E R B

A S

IN

M R

EL. VARIES

EMPTYING CULVERT

EL. 509.5

EL. VARIES

EL. VARIES

EL. 537.5 TO EL. 532.0

INSTALLED FROM

THIS ANCHOR NOT

LAYOUT AND SIZE

SEE SE153 FOR ANCHOR

NOTE:

LAYOUT AND SIZE

SEE SE153 FOR ANCHOR

NOTE:

SE151

TOP OF WALL.

CONDUIT AT 1'-9" BELOW

BLOCK OUT CENTERED ON

IN CONCRETE FOR CONDUIT.

18"x12"x4'-0" BLOCK OUT

12"

BLOCKOUT

BELOW

ABOVE AND

3-#6B @ 12

C1

SECTION

C3

SECTION

B3

SECTION

A3

SECTION

A1

SECTION

/0

/2

W E

K -1

-R -0

IL

L

IN

O

IS

IO

W A

A N

D M

IS

S

O U

R I

L O

C K C

H A

M B

E R B

U L

K H

E A

D R

E C

E S

S

Sheet

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

D A

T E

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps of Engineers

US Army Corps

P R

O J E

C T C

O D

0 1' 2' 4'SCALE : 1/2"=1'-0"

S T

A .5

A

B U

L K

H E

A D R

E C

E S

S

S T

A .5

A

M

IT

E R G

A T

E R

E C

E S

S

C /L

#6 @ 12 #6B @ 12 #6 @ 12

#6B @ 12

#6 @ 12

1'-0"

3'-6"2 SP @ 4 SP @ 1'-0"2'-6"

0 1' 2' 4'SCALE : 1/2"=1'-0"

PLACEMENT

WALL CONCRETE

R E

C E

S S

B U

L K

H E

A D

LOCK WALL

FACE OF

#6 @ 12

BULKHEAD RECESS

4'-1"

1'-0"1'-0"

"2

A3

0 1' 2' 4'SCALE : 1/2"=1'-0"

DAM FOUNDATION

CONCRETE POIREE

TOP OF EXISTING

DASHED LINE INDICATES

LOCKWALL

#6B ANCHORS

PLACEMENT

WALL CONCRETE

C/L BULKHEAD RECESS ASSEMBLY

C L

BULKHEAD RECESS

4'-1"

#6B ANCHORS

2'-10"

4'-0"

VARIES

B3

0 1' 2' 4'SCALE : 1/2"=1'-0"

"2 15'-5• 7'-11"

#6 @ 12#6B @ 12

#6B @ 12

#8 TYP

#6B @ 12 VERT.

#6B @ 12 VERT.

#6 @ 12

7 SP

1'-0

0 1' 2' 4'SCALE : 1/2"=1'-0"

S T

A .9

A

L A

D D

E R

C /L

S T

A .5

A

B U

L K

H E

A D R

E C

E S

S C /L S T

A .5

A

M

IT

E R G

A T

E R

E C

E S

S

EL. 509.5

EL. 537.5

FILLING CULVERT

EXISTING

PLACEMENT

SILL CONCRETE

PLACEMENT

SILL CONCRETE

C O

N C

R E

T E R

E M

O V

A L

L

IM

IT

O

F

"2 114'-10

8'-0""2 16'-10

C O

N C

R E

T E R

E M

O V

A L

L

IM

IT

O

F

ELECTRICAL DUCTBANK

EXISTING EMBEDDED

A N

S I

D m v r-a p p w p lt \P

W iC

S S h a re

\3

\4

\M

R S -E

X X

X .d g n

:5

:5

A

M

M V

R -A

P P

W P

L T

D

A T

C K I S

L A

N D

IL

L

IN

O

IS

R O

C K I S

L A

N D D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

S -E

X X

X .d g n

C H J

B

S

H O

W N

J C

Q

F

I-

A L L N

E W W

O R

K S

E C

T

IO

N S

L O

C K

A

U X

IL

IA

C K

S

A N

D

M

IS

S

IS

S

IP

P I

R

IV

E R B

A S

IN

M R

EL. 516.5

LAYOUT AND SIZE

SEE SE153 FOR ANCHOR

NOTE:

EL. 537.5 TO EL. 529.5

LAYOUT AND SIZE

SEE SE153 FOR ANCHOR

NOTE:

SE152

EL. 504.0

EL. 516.5 TO

EMPTYING CULVERT

EL. 529.5 TO EL. 509.5

AREA

IN REMOVAL

DUCTBANK

ELECTRICAL

NEW EMBEDDED

EL. 529.5

"2 114'-10

TOP OF WALL.

CONDUIT AT 1'-9" BELOW

BLOCK OUT CENTERED ON

IN CONCRETE FOR CONDUIT.

18"x12"x4'-0" BLOCK OUT

C1

SECTION

C3

SECTION

B3

SECTION

A3

SECTION

A1

SECTION

/0

/2

W E

K -1

-R -0

IL

L

IN

O

IS

IO

W A

A N

D M

IS

S

O U

R I

L O

C K C

H A

M B

E R B

U L

K H

E A

D R

E C

E S

S

Sheet

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

D A

T E

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps of Engineers

US Army Corps

P R

O J E

C T C

O D

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

D A

T E

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps of Engineers

US Army Corps

P R

O J E

C T C

O D

E

0 1' 2' 4'SCALE : 1/2"=1'-0" 0 1' 2' 4'SCALE : 1/2"=1'-0"

EL. 537.5

S

P A

C E

S

S

P A

C E

S

A

N C

H O

R S

B A

N C

H O

R S

B A

N C

H O

R S

B A

N C

H O

R S

B A

N C

H O

R S

S

P A

C E

S

S

P A

C E

S

B A

N C

H O

R S

EL. 537.5

S

P A

C E

S

B A

N C

H O

R S

A N

S I

D m v r-a p p w p lt \P

W iC

S S h a re

\3

\4

\M

R S -E

X X

X .d g n

:0

:1

A

M

M V

R -A

P P

W P

L T

D

A T

C K I S

L A

N D

IL

L

IN

O

IS

R O

C K I S

L A

N D D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

S -E

X X

X .d g n

C H J

B

S

H O

W N

J C

Q

F

C H

O R L

A Y

O U

T E

L E

V A

T

IO

N S

L O

C K

A

U X

IL

IA

C K

S

A N

D

M

IS

S

IS

S

IP

P I

R

IV

E R B

A S

IN

M R

P A

C E

S

S

P A

C E

S

SE153

FILLING

CULVERT

FILLING

CULVERT

(3

B A

N C

H O

R S

A1

RIVERWALL ELEVATION - ANCHOR LAYOUT

A3

INTERMEDIATE WALL ELEVATION - ANCHOR LAYOUT

/0

/2

W E

K -1

-R -0

IL

L

IN

O

IS

IO

W A

A N

D M

IS

S

O U

R I

L O

C K C

H A

M B

E R B

U L

K H

E A

D R

E C

E S

S

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

D A

T E

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps of Engineers

US Army Corps

P R

O J E

C T C

O D

SCALE : NO SCALE

SCALE : NO SCALE

SCALE : NO SCALE SCALE : NO SCALE SCALE : NO SCALE

NEW

CONCRETE

EXISTING

CONCRETE

EPOXY GROUT

EMBED IN

#6 BAR x 3'-0"

1'-6" MIN

NEW

CONCRETE

EXISTING

CONCRETE

EPOXY GROUT

EMBED IN

INSTALLATION)

(BEND PRIOR TO

STANDARD HOOK

#6, #8 BAR WITH

#6B,#8B ANCHOR -

1'-6" MIN

3'-0"

"4

EXISTING CONCRETE NEW CONCRETE

JOINT SEALANT

JOINT MATERIAL

EXPANSION

PREMOLDED

EXISTING CONCRETE NEW CONCRETE

JOINT SEALANT

"2

JOINT SEALANT

JOINT

MATERIAL

EXPANSION JOINT

BACKER ROD OR

" FOR EXPANSION JOINTS2

AND CONSTRUCTION JOINTS

" FOR CONTRACTION4

M

IN

A N

S I

D m v r-a p p w p lt \P

W iC

S S h a re

\3

\4

\M

R S -E

X X

X .d g n

:5

:3

A

M

M V

R -A

P P

W P

L T

D

A T

C K I S

L A

N D

IL

L

IN

O

IS

R O

C K I S

L A

N D D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

S -E

X X

X .d g n

C H J

B

S

H O

W N

J C

Q

F

W W

O R

K D

E T

A

IL

S

L O

C K

A

U X

IL

IA

C K

S

A N

D

M

IS

S

IS

S

IP

P I

R

IV

E R B

A S

IN

M R

SE200

C1

JOINT DETAIL - NEW/EXISTING CONCRETE

C2

JOINT DETAIL AT EXPANSION/MONOLITH JOINT

C4

JOINT DETAIL

#6B & #8B ANCHOR DETAIL

B4

A2

#6 ANCHOR DETAIL

/0

/2

W E

K -1

-R -0

IL

L

IN

O

IS

IO

W A

A N

D M

IS

S

O U

R I

L O

C K C

H A

M B

E R B

U L

K H

E A

D R

E C

E S

S

SCALE : 3/4"=1'-0" 0 1' 2' 3'

FITTINGS (TYP)

CAST ALUMINUM

S E

E N

O T

E

E Q

U A

L E

Q U

A L

SCALE : 3/4"=1'-0" 0 1' 2' 3'

W

IT

H C

A S

T A

L U

M

IN

U M F

IT

T

IN

G S

N E

W G

A L

V A

N

IZ

E D H

A N

D R

A

IL

S T

A .0

A

C H

E C

K P

O S

T

S T

A .9

A

L A

D D

E R

S T

A .5

A

B U

L K

H E

A D S

L O

T

C /L

C /L

C /L

4'-6"2'-10""2 1106'-6"3'-8"

NEW GALVANIZED HANDRAIL WITH CAST ALUMINUM FITTINGS

RAIL FOR LADDER ACCESS

INSTALL NEW CUSTOM REMOVABLE

EXISTING HANDRAIL

A N

S I

D m v r-a p p w p lt \P

W iC

S S h a re

\3

\4

\M

R S -E

X X

X .d g n

:0

:4

A

M

M V

R -A

P P

W P

L T

D

A T

C K I S

L A

N D

IL

L

IN

O

IS

R O

C K I S

L A

N D D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

S -E

X X

X .d g n

C H J

B

S

H O

W N

J C

Q

F

E R

W A

L L H

A N

D R

A

IL

L O

C K

A

U X

IL

IA

C K

S

A N

D

M

IS

S

IS

S

IP

P I

R

IV

E R B

A S

IN

M R

SE250

EXISTING HANDRAIL

LADDER SAFETY DEVICES

REINSTALL EXISTING

MATCH EXISTING.

3. FIELD VERIFY EXISTING HANDRAIL HEIGHT. NEW HANDRAIL HEIGHT SHALL

WIRE ROPE FROM FAIRLEAD TO PASS OVER.

CONTINUOUS SECTION OF HANDRAIL BETWEEN WALL AND MITER GATE TO ALLOW

2. CONTRACTOR SHALL CUSTOM FABRICATE HANDRAIL SECTION WHICH PROVIDES

LAYOUT BY ACTUAL FIELD MEASUREMENTS AND SUBMIT FOR APPROVAL.

OF NEW HANDRAIL REQUIREMENTS. CONTRACTOR SHALL DETERMINE HANDRAIL

1. HANDRAIL LAYOUT SHOWN IS TO GIVE THE CONTRACTOR A GENERAL IDEA

NOTES:

C1

RIVERWALL HANDRAIL-PLAN

A1

RIVERWALL HANDRAIL-ELEVATION

/0

/2

W E

K -1

-R -0

IL

L

IN

O

IS

IO

W A

A N

D M

IS

S

O U

R I

L O

C K C

H A

M B

E R B

U L

K H

E A

D R

E C

E S

S

Sheet

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

D A

T E

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps of Engineers

US Army Corps

P R

O J E

C T C

O D

SCALE : 3/4"=1'-0" 0 1' 2' 3'

INTERMEDIATE WALL OPPOSITE HAND

GALVANIZED PIPE (TYP)

NEW 2" DIA. X-STRONG

FITTINGS (TYP)

CAST ALUMINUM

S E

E N

O T

E

E Q

U A

L E

Q U

A L

SAFETY DEVICES

EXISTING LADDER

SCALE : 3/4"=1'-0" 0 1' 2' 3'

W

IT

H C

A S

T A

L U

M

IN

U M F

IT

T

IN

G S

N E

W G

A L

V A

N

IZ

E D H

A N

D R

A

IL

H A

N D

R A

IL

E X

IS

T

IN

G

INTERMEDIATE WALL OPPOSITE HAND

S T

A .0

A

C H

E C

K P

O S

T

S T

A .9

A

L A

D D

E R

S T

A .5

A

B U

L K

H E

A D S

L O

T

C /L

C /L

C /L

MATCH EXISTING.

3. FIELD VERIFY EXISTING HANDRAIL HEIGHT. NEW HANDRAIL HEIGHT SHALL

WIRE ROPE FROM FAIRLEAD TO PASS OVER.

CONTINUOUS SECTION OF HANDRAIL BETWEEN WALL AND MITER GATE TO ALLOW

2. CONTRACTOR SHALL CUSTOM FABRICATE HANDRAIL SECTION WHICH PROVIDES

LAYOUT BY ACTUAL FIELD MEASUREMENTS AND SUBMIT FOR APPROVAL.

OF NEW HANDRAIL REQUIREMENTS. CONTRACTOR SHALL DETERMINE HANDRAIL

1. HANDRAIL LAYOUT SHOWN IS TO GIVE THE CONTRACTOR A GENERAL IDEA

NOTES:

EXISTING HANDRAIL NEW GALVANIZED HANDRAIL WITH CAST ALUMINUM FITTINGS

A N

S I

D m v r-a p p w p lt \P

W iC

S S h a re

\3

\4

\M

R S -E

X X

X .d g n

:0

:1

A

M

M V

R -A

P P

W P

L T

D

A T

C K I S

L A

N D

IL

L

IN

O

IS

R O

C K I S

L A

N D D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

I- W

A L L H

A N

D R

IL

S -E

X X

X .d g n

C H J

B

S

H O

W N

J C

Q

F

C K

A

U X

IL

IA

C K

S

A N

D

M

IS

S

IS

S

IP

P I

R

IV

E R B

A S

IN

M R

LADDER ACCESS

REMOVABLE RAIL FOR

INSTALL NEW CUSTOM

4'-6" 2'-10" "2 110 6'-6" 3'-8"

SE251

C1

I-WALL HANDRAIL-PLAN

A1

I-WALL HANDRAIL-ELEVATION

/0

/2

W E

K -1

-R -0

IL

L

IN

O

IS

IO

W A

A N

D M

IS

S

O U

R I

L O

C K C

H A

M B

E R B

U L

K H

E A

D R

E C

E S

S

Sheet

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

D A

T E

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps of Engineers

US Army Corps

P R

O J E

C T C

O D

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

D A

T E

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps of Engineers

US Army Corps

P R

O J E

C T C

O D

0 1" 2" 3" 4"SCALE : 6"=1'-0"

8"

M

IN

NEOPRENE GASKET

TOP OF LOCK WALL

GALVANIZED PIPE (TYP)

2" DIA. X-STRONG

NEW HANDRAIL BASE

" ANCHORS2

1NEW

HOLE IN EACH BASE

" DRAIN2

1DRILL

C/L HANDRAIL

SECTION

PLAN

0 6" 1' 2'SCALE : 1"=1'-0"

E Q

U A

L E

Q U

A L

6'-0" (MAX)

TOP OF LOCK WALL

DETAIL THIS SHEET

FLANGE, SEE

HANDRAIL BASE

GALVANIZED PIPE (TYP)

2" DIA. X-STRONG

(F

IE

L D V

E R

IF

Y

NEW CORNER ARMOR

EXISTING AND/OR

GALVANIZED PIPE (TYP)

2" DIA. X-STRONG

HANDRAIL CENTERLINE

MATCH EXISTING

SECTIONELEVATION

0 1' 2' 4'SCALE : 1/2"=1'-0"

BREAKS AT MONOLITHS

CONTINUOUS WITH

HANDRAIL SHALL BE

SCREWS (TYP)

STEEL SET

STAINLESS

TO BE CONTINUOUS

VERTICAL POSTS

"L" FITTING

FITTING

"CROSS"

GENERAL NOTES

CHECK POSTS.

6. NEW POSTS SHALL BE A MINIMUM 3'-0" FROM CENTERLINE OF

PLATE AND CONCRETE.

PLATE. THE GASKET SHALL BE INSTALLED BETWEEN THE BASE

NEOPRENE GASKET MATCHING THE FOOTPRINT OF THE BASE

5. ALL NEW HANDRAIL SHALL BE REINSTALLED/ INSTALLED WITH A

SPLICES.

JOINTS, WITH CONNECTION SPECIFICATIONS DESIGNED FOR

4. HANDRAIL SHALL HAVE EXPANSION SPLICES AT ALL MONOLITH

C. VERTICAL POSTS CONTINUOUS TO TOP RAIL

B. MAXIMUM POST SPACING = 6'-0"

A. MAXIMUM TOP RAIL LENGTH = 30'-0"

CRITERIA SHALL BE APPLIED:

JOINTS AND LOCK APPURTENANCES). THE FOLLOWING

SUBMIT FOR APPROVAL (LAYOUT MUST SHOW MONOLITH

3. CONTRACTOR SHALL FIELD VERIFY HANDRAIL LAYOUT AND

SHALL BE GALVANIZED.

AND 6000 LB ULTIMATE SHEAR. ALL ANCHOR BOLTS AND NUTS

GROUT TO A DEPTH TO PROVIDE 4000 LB ULTIMATE PULLOUT,

" DIA., EMBEDDED IN EPOXY2

1 NEW BASE PLATES SHALL BE

2. ALL ANCHOR BOLTS SHALL BE REPLACED. ANCHOR BOLTS FOR

ALUMINUM FITTINGS.

CONSIST OF GALVANIZED STEEL RAILS AND POSTS WITH CAST

MANUFACTURER'S RECOMMENDATIONS. ALL HANDRAIL SHALL

1. ALL HANDRAIL/FENCING SHALL BE INSTALLED PER

A N

S I

D m v r-a p p w p lt \P

W iC

S S h a re

\3

\4

\M

R S -E

X X

X .d g n

:0

:4

A

M

M V

R -A

P P

W P

L T

D

A T

C K I S

L A

N D

IL

L

IN

O

IS

R O

C K I S

L A

N D D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

S -E

X X

X .d g n

K W

K

B

S

H O

W N

G L

W

F

H

N D

R A

IL

D

E T

A

IL

S

L O

C K

A

U X

IL

IA

C K

S

A N

D

M

IS

S

IS

S

IP

P I

R

IV

E R B

A S

IN

M R

SE252

0 3" 6" 9" 12"SCALE : 3"=1'-0"

SLIDES INTO HANDRAIL

" LONG8

7GALVAINED PIPE x 11

" DIA X-STRONG2

SLIDING PAST FITTING

PREVENTS PIPE FROM

" DIA ROUND STOCK8

1"

SLIDE RAIL TO LOCK INTO

NOTCH PIPE TO ALLOW

2" DIA. X-STRONG PIPE.

1"

OF FITTING

CENTERLINE

EXTENSION TO

EXTEND 2" PIPE

OPEN POSITION

CLOSED POSITION

2"

TOP OF LOCK WALL

SCALE : NO SCALE

" (TYP.)2

EXISTING HANDRAILNEW HANDRAIL

EXTENSIONS

RAIL

D1

TYPICAL HANDRAIL ELEVATION/SECTION

D3

TYPICAL HANDRAIL SLIP-ON CONNECTION DETAILS

B3

TYPICAL LADDER ACCESS RAIL DETAILS

B1

HANDRAIL EXTENSION

A1

TYPICAL HANDRAIL BASE DETAILS

/0

/2

W E

K -1

-R -0

IL

L

IN

O

IS

IO

W A

A N

D M

IS

S

O U

R I

L O

C K C

H A

M B

E R B

U L

K H

E A

D R

E C

E S

S

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

D A

T E

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps of Engineers

US Army Corps

P R

O J E

C T C

O D

E ƒ" PL

SCALE : NO SCALE

AT ASSEMBLY WITH GRATING.

RECOMMENDATION. LOCATED

PER GRATING MANUFACTURER'S

CLIP FASTENERS. SIZE AS

STUD BOLT FOR ATTACHING

1 X 2

1L2 X 1

CUT TO

1L2 X 2 X

0 6" 1' 2'SCALE : 1"=1'-0"

MAKE 1 AS SHOWN MAKE 1 OPPOSITE HAND

7" ANGLE LEG

CUT AND BEND

C/L BULKHEAD RECESS STA. 660.5A

5L7 x 4 x

HP 14 x 73

EL. 537.5

" 8

4'-1"

*"8 52'-94"

S

P A

C E

S

T Y

P S

P A

C

IN

G

X

A N

C H

B

R S

A L L S

ID

E S

F O

R A

GENERAL NOTES

AND SAWCUT AFTER CONCRETE PLACEMENT.

7. CONTRACTOR MAY STITCH WELD THIS JOINT FOR INSTALLATION

OF THE RECESS FRAMES FOR THE FULL HEIGHT OF THE RECESS.

BETWEEN THE ENDS OF THE BULKHEADS AND THE INSIDE WALL

" GAP2

1 6. IT IS INTENDED TO POSITION RECESS TO ACHIEVE A 1

".2

1 ANOTHER MORE THAN

5. BULKHEAD RECESS SHALL NOT VARY IN ALIGNMENT WITH ONE

IN 10'-0".

"16

1 4. BULKHEAD RECESS SHALL NOT VARY FROM PLUMB MORE THAN

STEEL AFTER FABRICATION.

" O.C. CROSS BARS @ 4" O.C. GALVANIZED 16

3" x 3" @ 14

1 BARS 1

3. GRATING SHALL BE BEARING BAR GRATING WITH TYPE 1, BEARING

INSTALLATION.

2. BULKHEAD RECESS ASSEMBLIES SHALL BE FABRICATED BEFORE

BULKHEADS.

1. DIMENSIONS NOTED ARE CRITICAL FOR OPERATIONAL FIT OF

SE501

D3

" PLATE4

"6

1'-6"

"4 18 "2

12'-3

1L2 x 2 x

SE501

D3

0 6" 1' 2'SCALE : 1/2"=1'-0"

"4

" PLATE4

"2 12'-3

1L2 x 2 x

POCKET

BEAM

HP 14 x 73

HP 14 x 73

TOP OF

8'-1"

2'-0"4'-1"2'-0" *

6"

1'-6"

1'-0"

2"

T Y

P

TYP

T Y

P

T Y

P

2-6

TYP.

SEE NOTE 7

(FULL LENGTH)

BETWEEN ARMOR

PROVIDE JOINT

WELDED STUDS

" DIA. X 8"4

ANCHOR

TYP EA.

TYP.

2-6

2-62-6

5L7 x 4 X

W 5 x 16 x 2 TYP 8

ANCHOR BAR

HP 14 x 73

WELDED STUDS

" DIA. x 84 x 2 TYP 8

ANCHOR BAR

R

"8 52'-9 *

0 6" 1' 2'SCALE : 1"=1'-0"

0 6" 1' 2'SCALE : 1"=1'-0"0 6" 1' 2'SCALE : 1"=1'-0"

5'-6"

7"4'-4"7"

GRATING SPAN

" C.C.16

3BAR @ 1

" BEARING4

1" X 4

NOTE: GRATING AND BANDING TO BE GALVANIZED

C R

O S

S B

A R

C C

" BAR4

1" X 4

BAND EDGES WITH

STEEL GRATING

" GALV.4

11 3

"2 12'-"2

12'-

4'-5"

T Y

P

1WELD TO L 2 x 1

" END PLATE4

5L 7 x 4 X

PER FRAME

TYP OF (4)

STUD BOLT,

FLOW

G

TYP.

SE501

D1

A1

B4

D4

B1

1 x 2

CUT TO L2 X

1L 2 x 2 x

0 6" 1' 2'SCALE : 1"=1'-0"

EL. 537.5

ALL SIDES

" PL4

3TYP

A N

S I

D m v r-a p p w p lt \P

W iC

S S h a re

\3

\4

\M

R S -E

X X

X .d g n

:0

:1

A

M

M V

R -A

P P

W P

L T

D

A T

C K I S

L A

N D

IL

L

IN

O

IS

R O

C K I S

L A

N D D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

R E

C E

S S A

S S

E M

B

S -E

X X

X .d g n

C H J

B

S

H O

W N

J C

Q

F

C K

A

U X

IL

IA

C K

S

A N

D

M

IS

S

IS

S

IP

P I

R

IV

E R B

A S

IN

M R

SE500

D

IA

X

W E

L D

E D S

T U

D S

S

P A

C E

S

F

D1

STEEL GRATING

D2

PLAN BULKHEAD RECESS ASSEMBLY

D4

SECTION

B4

ELEVATION

A2

ELEVATION-BULKHEAD RECESS ASSEMBLY

A1

SECTION

B1

ELEVATION

/0

/2

W E

K -1

-R -0

IL

L

IN

O

IS

IO

W A

A N

D M

IS

S

O U

R I

L O

C K C

H A

M B

E R B

U L

K H

E A

D R

E C

E S

S

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

D A

T E

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps of Engineers

US Army Corps

P R

O J E

C T C

O D

E

0 6" 1' 2'SCALE : 1 1/2"=1'-0"

1 x 2

1L 2 x 1

1 x 2

1L 2 x 1

BEAM POCKET

" PLATE4

1 x 2

1L 2 x 1

BEAM POCKET

TYP

TYP

D2

"4 16"4

"4

0 6" 1' 2'SCALE : 1 1/2"=1'-0"

"8

"8

"2 1"2

"8 5X 8 X 8

"2

1PLATE

"8 5 X 84

1X 6

"2

1PLATE

"2 1 X 74

1X 6

"2

1PLATE

" PLATE2

"2

"4

"4

" PLATE2

"4

"4

"2

0 6" 1' 2'SCALE : 1 1/2"=1'-0"

A N

S I

D m v r-a p p w p lt \P

W iC

S S h a re

\3

\4

\M

R S -E

X X

X .d g n

:5

:4

A

M

M V

R -A

P P

W P

L T

D

A T

C K I S

L A

N D

IL

L

IN

O

IS

R O

C K I S

L A

N D D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

S -E

X X

X .d g n

C H J

B

S

H O

W N

J C

Q

F

C E

S S A

S S

E M

B L

Y D

E T

A

IL

S

L O

C K

A

U X

IL

IA

C K

S

A N

D

M

IS

S

IS

S

IP

P I

R

IV

E R B

A S

IN

M R

SE501

D1

BEAM POCKET DETAIL

D2

SECTION

D3

BEAM POCKET DETAIL

/0

/2

W E

K -1

-R -0

IL

L

IN

O

IS

IO

W A

A N

D M

IS

S

O U

R I

L O

C K C

H A

M B

E R B

U L

K H

E A

D R

E C

E S

S

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

D A

T E

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps of Engineers

US Army Corps

P R

O J E

C T C

O D

E

0 3" 6" 9" 12"SCALE : 3"=1'-0"

A3

EXISTING ARMOR

0 6" 1' 2'SCALE : 1 1/2"=1'-0"

6"

CAPS FOR THE OPPOSITE WALL SHALL BE OPPOSITE HAND.

THE INTERMEDIATE WALL OR THE RIVER WALL. CORNER

9. CORNER CAPS ARE SHOWN IN THE ORIENTATION OF EITHER

PROFILE ON DETAIL.

8. GRINDING PROFILE OF EXISTING ARMOR SHALL MATCH

WHERE REQUIRED.

7. THE CONTRACTOR SHALL PROVIDE MONOLITH JOINTS

STRAP ANCHORS.

" FILLET WELDS FOR4

1 THE PROTECTION ARMOR. USE

6. ALL ANCHOR STRAPS AND STUDS SHALL BE WELDED TO

SMOOTH) TO VERTICAL AND HORIZONTAL ARMOR.

5. CORNER CAPS SHALL BE GROOVE WELDED (AND GROUND

" THICK ASTM A36.4

3 FROM

4. UNLESS OTHERWISE SHOWN ARMOR SHALL BE FABRICATED

VERTICAL ARMOR AND AT FREE ENDS.

3. ENDS OF THE WALL ARMOR ARE TO BE CHAMFERED AT

ALONG ITS LENGTH AND WIDTH.

INCH4

1 AND DOES NOT DEVIATE IN ANY PLANE MORE THAN

2. ARMOR SHALL BE FABRICATED SUCH THAT IT IS STRAIGHT

AFTER FABRICATION MAY BE REQUIRED.

1. ARMOR SHALL BE TRUE AND STRAIGHT. STRAIGHTENING

GENERAL ARMOR NOTES (APPLIES TO ALL ARMOR):

GENERAL NOTES

0 3" 6" 9" 12"SCALE : 3"=1'-0"

8"

2"

2""

ANCHOR BAR

2" WIDE

x 8" STUD

" DIA4

3" R

B3

ELEVATION

MAX.

MAX.

9"9" ANCHOR BARS @ 12" C.C. - STAGGERED

STUDS @ 12" C.C. - STAGGERED 9" 9"

0 6" 1' 2'SCALE : 1/2"=1'-0"

ARMOR

CORNER

VERTICAL

NEW

CONTRACT

INSTALLED UNDER THIS

TYPICAL FOR ALL ARMOR

ARMOR CONNECTIONS ARE

NOTE:

CORNER ARMOR

EXISTING

CORNER ARMOR

EXISTING

CORNER ARMOR

NEW HORIZONTAL

CORNER ARMOR

NEW HORIZONTAL

WALL ARMOR

EXISTING

WALL ARMOR

EXISTING

CAP

CORNER

NEW

G

G

TYP

G

TYP

G

G

G

0 6" 1' 2'SCALE : 1 1/2"=1'-0"

RECESS ARMOR

BULKHEAD

8"

A N

S I

D m v r-a p p w p lt \P

W iC

S S h a re

\3

\4

\M

R S -E

X X

X .d g n

:5

:4

A

M

M V

R -A

P P

W P

L T

D

A T

C K I S

L A

N D

IL

L

IN

O

IS

R O

C K I S

L A

N D D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

A R

M O

R D

E T

A

IL

I

S -E

X X

X .d g n

C H J

B

S

H O

W N

J C

Q

F

C K

A

U X

IL

IA

C K

S

A N

D

M

IS

S

IS

S

IP

P I

R

IV

E R B

A S

IN

M R

SE800

(TYP.)

NEW BULKHEAD RECESS ARMOR

GRIND EXISTING ARMOR

C1

SE800-C1 HORIZONTAL CORNER ARMOR

C3

TYPICAL ARMOR CONNECTION DETAILS

B3

SECTION

A3

SECTION

A1

EXISTING ARMOR GRINDING DETAIL

/0

/2

W E

K -1

-R -0

IL

L

IN

O

IS

IO

W A

A N

D M

IS

S

O U

R I

L O

C K C

H A

M B

E R B

U L

K H

E A

D R

E C

E S

S

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

D A

T E

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps of Engineers

US Army Corps

P R

O J E

C T C

O D

E

2'-0"

4"1'-0"8"

1'-0"

9"

3"

ANCHOR STUD

" DIA. X 8"4

ANCHOR STUD

" DIA. X 8"4

3"R

SIDE VIEWELEVATION

8"

8" 2"

"4

3" R

ANCHORS

2" WIDE STRAP

x 8" STUD

" DIA4

2"

0 3" 6" 9" 12"SCALE : 3"=1'-0"

A3

S T

R A

P S

C .C S

T A

G G

E R

E D

S T

U D

S

C .C S

T A

G G

E R

E D

M A

X

M A

X

0 3" 6" 9" 12"SCALE : 3"=1'-0"

ELEVATION

8"

8"

2""4

2"

R3

R x8" STUD

" DIA.4

0 6" 1' 2'SCALE : 1 1/2"=1'-0"

0 6" 1' 2'SCALE : 1 1/2"=1'-0"

A N

S I

D m v r-a p p w p lt \P

W iC

S S h a re

\3

\4

\M

R S -E

X X

X .d g n

:5

:4

A

M

M V

R -A

P P

W P

L T

D

A T

C K I S

L A

N D

IL

L

IN

O

IS

R O

C K I S

L A

N D D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

S -E

X X

X .d g n

C H J

B

S

H O

W N

J C

Q

F

M O

R D

E T

A

IL

S I I

L O

C K

A

U X

IL

IA

C K

S

A N

D

M

IS

S

IS

S

IP

P I

R

IV

E R B

A S

IN

M R

SE801

B1

SE801-B1 CORNER CAP

B3

SE801-B3 VERTICAL ARMOR

A3

SECTIONSE801-A1 BULKHEAD RECESS CORNER CAP

A1

/0

/2

W E

K -1

-R -0

IL

L

IN

O

IS

IO

W A

A N

D M

IS

S

O U

R I

L O

C K C

H A

M B

E R B

U L

K H

E A

D R

E C

E S

S

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

D A

T E

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps of Engineers

US Army Corps

P R

O J E

C T C

O D

E

0 3" 6" 9" 12"SCALE : 3"=1'-0" SCALE : NO SCALE

A4

A

B

D

ELEVATIONSECTION A

SECTION B

"2 11'-7

1'-6"

11"

"4 3 "4

"4

TYP

TYP

" PLATE8

C O

U P

L

IN

G N

U T S

F O

R S

P A

C

IN

G O

F

" PLATE8

" PLATE8

LOCKWASHER

(CRES) WITH

" DIA. BOLT4

HOLE IN PLATE

" DIA.16

HEX COUPLING NUT

" TAP SIZE4

PLUG END

"4

MIN.

" PLATE8

"2

SECTION D

ELEVATION

STUD ANCHOR

" DIA X 8"4

STUD ANCHOR

" DIA X 4"4

8"

2"

""4

3 "R

TYP

(NOT TO SCALE)

M A

X

"2 11'-18"

S T

U D A

N C

H O

R S

S T

U D A

N C

H O

R S

8" "2 11'-1

STRAP ANCHOR

x2x1'-0"8

R 3

R

SEE DETAIL A4

COUPLING NUT,

0 3" 6" 9" 12"SCALE : 3"=1'-0"

0 6" 1' 2'SCALE : 1 1/2"=1'-0"

A N

S I

D m v r-a p p w p lt \P

W iC

S S h a re

\3

\4

\M

R S -E

X X

X .d g n

:0

:5

A

M

M V

R -A

P P

W P

L T

D

A T

C K I S

L A

N D

IL

L

IN

O

IS

R O

C K I S

L A

N D D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

S -E

X X

X .d g n

C H J

B

S

H O

W N

J C

Q

F

M O

R D

E T

A

IL

S I

II

L O

C K

A

U X

IL

IA

C K

S

A N

D

M

IS

S

IS

S

IP

P I

R

IV

E R B

A S

IN

M R

SE802

N S

H E

E T S

E

S E

E L

A D

D E

R D

E T

A

IL

S

SE802-C1

SE802-B4

C1

SE802-C1 LADDER CORNER CAP

B4

SE802-B4 LADDER ARMOR

A4

DETAIL

A1

LADDER ARMOR DETAILS

/0

/2

W E

K -1

-R -0

IL

L

IN

O

IS

IO

W A

A N

D M

IS

S

O U

R I

L O

C K C

H A

M B

E R B

U L

K H

E A

D R

E C

E S

S

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

D A

T E

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps of Engineers

US Army Corps

P R

O J E

C T C

O D

E

SCALE : NO SCALE

SCALE : NO SCALE

SCALE : NO SCALE

0 6" 1' 2'SCALE : 1"=1'-0"

A3

B3

C3

LADDER NOTES

C/L RAIL

" BAR2

1x 2

"2

1RAIL -

"2 1" x 4" x 8" x 0'-22

1L

BRACKET,

"2

" DIA.16

13"2

1" x 4" x 8" x 0'-22 1L

BRACKET,

DIA. HOLE

"16

1TYP. 1

" BAR2

1x 2

"2

1RAIL -

6"

7"

1'-5"

" (TYP)4

1R 1

" BAR2

1x 2

"2

1RAIL -

"2 1x 8" x 0'-2

" x 4"2

1BRACKET, L

EL. 537.5

TOP OF WALL

"4

LADDER RUNG

"2 11" x 17

LADDER RUNG

"2 11" x 17

ROUND BAR

"2 1RUNG - 1" x 17

OF TWO LADDERS. (LENGTHS AS SHOWN)

5. THERE IS ONE LADDER FOR EACH WALL FOR A TOTAL

ON FIELD ELEVATIONS.

DETERMINE ACTUAL LADDER DIMENSIONS BASED

NOMINAL AND THE CONTRACTOR SHALL

4. DIMENSIONS SHOWN ON LADDER ELEVATION ARE

SECTIONS.

" GAP IS REQUIRED BETWEEN LADDER2

13. A

IN ACCORDANCE WITH SPECIFICATIONS.

2. ALL STEEL SHALL BE PAINTED AFTER FABRICATION

".4

11. ALL FILLET WELDS SHALL BE

A N

S I

D m v r-a p p w p lt \P

W iC

S S h a re

\3

\4

\M

R S -E

X X

X .d g n

:5

:2

A

M

M V

R -A

P P

W P

L T

D

A T

C K I S

L A

N D

IL

L

IN

O

IS

R O

C K I S

L A

N D D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

L A

D D

E R D

E T

A

S -E

X X

X .d g n

C H J

B

S

H O

W N

J C

Q

F

C K

A

U X

IL

IA

C K

S

A N

D

M

IS

S

IS

S

IP

P I

R

IV

E R B

A S

IN

M R

TOP OF WALL

SE875

ARMOR EL. 523.0

BOTTOM CORNER

S

P A

C E

S

A1

LADDER ELEVATION

C3

DETAIL

B3

DETAIL

A3

DETAIL

/0

/2

W E

K -1

-R -0

IL

L

IN

O

IS

IO

W A

A N

D M

IS

S

O U

R I

L O

C K C

H A

M B

E R B

U L

K H

E A

D R

E C

E S

S

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

D A

T E

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps of Engineers

US Army Corps

P R

O J E

C T C

O D

E

0 4' 16'8'SCALE : 1/8"=1'-0"

RIVER WALL (R-WALL) INTERMEDIATE WALL (I-WALL)

STA. 687.0A

MONOLITH JOINT

(SEE SHEET EE002)

AND NEW LADDER

BULKHEAD RECESS

WORK FOR NEW

OF CONCRETE

APPROX. AREA

STA. 706.0A

MONOLITH JOINT

CHAMBER

MAIN LOCK

STA. 679.0A

MONOLITH JOINT

C/L AUXILIARY LOCK CHAMBER

F L

O W

MACHINERY

MITER GATE NO. 4

MAIN LOCK

RECONNECTED.

SHALL BE REINSTALLED IN THE DUCT BANKS AND CONDUITS AND

TEMPORARY CABLES SHALL BE REMOVED AND THE STORED LOCK CABLES

BULKHEAD RECESSES. AFTER COMPLETION OF CONSTRUCTION, ALL

AS REQUIRED TO FACILITATE CONSTRUCTION AND INSTALLATION OF THE

AND LOADS. DUCT BANK AND CONDUITS SHALL BE REPAIRED AND RELOCATED

CONSTRUCTION AREA TO MAINTAIN POWER TO NECESSARY LOCK CONTROLS

POSSIBLE. TEMPORARY CABLES SHALL BE INSTALLED AND ROUTED CLEAR OF

ALL TIMES AND TEMPORARILY STORED IN ADJACENT MANHOLES AS MUCH AS

CONCRETE WILL BE REMOVED. PERMANENT CABLES SHALL BE PROTECTED AT

ELECTRICAL CABLES FROM DUCT BANK AND CONDUITS IN THE AREAS WHERE

CONDUITS PRIOR TO BEGINNING WORK. CONTRACTOR SHALL REMOVE ALL

CONTRACTOR SHALL LOCATE AND MARK EXISTING DUCT BANK AND EMBEDDED

ELECTRICAL SCOPE OF WORK:

A N

S I

D m v r-a p p w p lt \P

W iC

S S h a re

\3

\4

\M

R E -E

X X

X .d g n

:5

:4

A

M

M V

R -A

P P

W P

L T

D

A T

C K I S

L A

N D

IL

L

IN

O

IS

R O

C K I S

L A

N D D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

E -E

X X

X .d g n

B G

R

R

S

H O

W N

D D

J

C E

S S E

L E

C T

R

IC

A L P

L

C K

S

A N

D

M

IS

S

IS

S

IP

P I

R

IV

E R B

A S

IN

M R

EE001

SHEET SE102 & SE103)

RECESS AND NEW LADDER (SEE

WORK FOR NEW BULKHEAD

APPROX. AREA OF CONCRETE

EE003.

SEE DETAILED SEQUENCE OF WORK AND GENERAL NOTES ON SHEETS EE002 AND 4.

WALL F1 LIGHT POLE AT STATION 662.0 A IN THE AREAS OF CONSTRUCTION.

REMOVE BOTH INTERMEDIATE WALL (I-WALL) F2 LIGHT POLE AT STA. 662.0 A AND RIVER 3.

OPEN.

12 HOUR LOCK CLOSURE. THE REMAINING CABLES CAN BE REROUTED WHILE LOCK IS

MAIN LOCK MITER GATE NO. 4 OPERATION FIRST (HIGH PRIORITY) DURING SCHEDULED

OUTSIDE OF CONSTRUCTION AREA WITH TEMPORARY CABLES. REROUTE CABLES FOR

REMOVE ALL IDENTIFIED EXISTING CABLES FROM DUCT BANKS AND REROUTE 2.

CONSTRUCTION.

LOCATE AND MARK DUCT BANK AND EMBEDDED CONDUITS LOCATION IN AREA OF 1.

PRE-CONSTRUCTION NOTES:

SEE DETAILED SEQUENCE OF WORK AND GENERAL NOTES ON SHEETS EE002 AND EE003.6.

REINSTALL LIGHT POLES REMOVED DURING PRE-CONSTRUCTION.5.

REMAINING CABLES CAN BE RE-TERMINATED WHILE LOCK IS OPEN.

OPERATION FIRST (HIGH PRIORITY) DURING SCHEDULED 12 HOUR LOCK CLOSURE. THE

PRIOR TO CONSTRUCTION. RE-TERMINATE CABLES FOR MAIN LOCK MITER GATE NO. 4

REMOVE ALL TEMPORARY CABLES AND RE-TERMINATE EXISTING CABLES REMOVED 4.

CLEAN DUCT BANK DUCTS AND EMBEDDED CONDUITS WHERE CABLES WERE REMOVED.3.

SHEET EE005.

REMOVED OR DAMAGED DUE TO CONCRETE REMOVAL DURING CONSTRUCTION. SEE

REPLACE DUCT BANK OR EMBEDDED CONDUIT IN AREA WHERE DUCT BANK WAS 2.

CONCRETE REMOVAL. SEE DUCT BANK REPAIR DETAILS ON SHEET ED005.

RELOCATE AND RECONSTRUCT DUCT BANK AND EMBEDDED CONDUIT IN AREA OF 1.

POST-CONSTRUCTION NOTES:

(NON-OPERATIONAL)

MITER GATES

EXISTING AUXILIARY

PINTLE STA. 590.0A

C/L

L941 - 2" CONDUIT

EC 1 - 2" CONDUIT

L93 L9A 2 - 2" CONDUITS

C4F C4H C4L

C4T

C4B C4C C4D

C4I

CBI

C4A

P41

L43

P45P42 P46

2 - 2" CONDUITS

1 - 2" CONDUIT

MAIN LOCK CHAMBER HANDRAIL

EC

CB

CONTROL STAND

TO MANHOLE C4,

L44

EMBEDDED CONDUIT

EXISTING CONCRETE

INDICATES

PROTECT POLE ANCHOR

LOCATED AT STA. 662.0A

POLE AND BASE SHROUD "F1"

REMOVE AND REINSTALL LIGHT

NOTES ON SHEET E-D003.

EMBEDDED CONDUITS LOCATION

CABLES. SEE DUCT BANK AND

CONDUITS PRIOR TO PULLING

MARK DUCT BANK AND EMBEDDED

CONTRACTOR SHALL LOCATE AND

DRAWINGS)

REFERENCE

(SEE

DUCT BANK

EXISTING

F L

O W

"F2" LOCATED AT STA. 662.0A

POLE AND BASE SHROUD

AND REINSTALL LIGHT

POLE ANCHOR REMOVE

MAINTAIN AND PROTECT

ON SHEET ED002.

EMBEDDED CONDUITS LOCATION NOTES

PULLING CABLES. SEE DUCT BANK AND

BANK AND EMBEDDED CONDUIT PRIOR TO

CONTRACTOR SHALL LOCATE AND MARK DUCT

(SEE REFERENCE DRAWINGS)

EXISTING DUCT BANK

EXISTING GUARD WALL

L9AL9

C4B C4C C4E

C4I

P42 P45 P46

C4D

C4T

P41

DB-U

C4A

C4H

P64 GND

C4L CBI CB

L41

A1

L/D 18 - UPSTREAM AUXILIARY LOCK BULKHEAD RECESSES PLAN

MANHOLE MH-C8

EXISTING

EC

MANHOLE MH-C6

EXISTING

4.2. KEEPING MANHOLES PUMPED OUT AND DRY AND PERHAPS HEATED.

RE-INSTALLED DURING WARM WEATHER WHEN ICE CANNOT FORM.

4.1. SCHEDULE WORK SO THAT PERMANENT CABLES ARE REMOVED AND

PREVENTATIVE ACTIONS MAY BE:

PLACE. EXAMPLES OF AVOIDING FROZEN DUCTS AND MANHOLES AND TAKING

FORMATION DOES NOT OCCUR AND CABLES DO NOT BECOME FROZEN IN

CONTRACTOR IS ENCOURAGED TO TAKE PREVENTATIVE ACTION SO THAT ICE

MAY BE FROZEN WITH ICE DURING CERTAIN TIMES OF THE YEAR. THE

CONDUITS WHICH CONTAIN CABLES THAT ARE REQUIRED TO BE REMOVED

WIRES, AND ICE. THE CONTRACTOR SHALL CONSIDER THAT THE DUCTS AND

BEEN KNOWN TO CONTAIN GENERAL DIRT AND DEBRIS, ABANDONED PULL

EXISTING DUCT BANK DUCTS, EMBEDDED CONDUITS, AND MANHOLES HAVE 4.

RE-CONNECTED AT ALL DURING CONSTRUCTION.

REMOVAL AND TEMPORARY CABLING OR ARE NOT REQUIRED TO BE

LOW PRIORITY CABLES ARE THOSE CABLES THAT DO NOT REQUIRE IMMEDIATE 3.

RESTORED TO THESE "HIGH PRIORITY" LOADS AS SOON AS POSSIBLE.

INSTALLED AS TEMPORARY FIRST (AND VICE VERSA). POWER MUST BE

HIGH PRIORITY CABLES ARE THOSE CABLES THAT SHALL BE REMOVED AND 2.

INCH RGS COUPLING AND PLUG TO SEAL ENDS OF EMPTY CONDUITS.

LESS THAN 2 INCHES (I.E. 2 INCHES EXPOSED OUT OF CONCRETE). INSTALL 2

EXTENDED OUT OF NEW CONCRETE FACE IN DOWNSTREAM DIRECTION NOT

"EC" MEANS "EMPTY CONDUIT". THESE 2 INCH RGS EMPTY CONDUITS SHALL BE 1.

GENERAL NOTES:

L O

C K

U

S A

U X

IL

IA

R Y

/0

/2

W E

K -1

-R -0

IL

L

IN

O

IS

IO

W A

A N

D M

IS

S

O U

R I

L O

C K C

H A

M B

E R B

U L

K H

E A

D R

E C

E S

S

NOTE 13.

FOLLOWING THE PROCEDURES SIMILAR TO THAT OF GENERAL

OR GROUNDS, AND INSTALL TEMPORARY CABLES AS REQUIRED

DE-ENERGIZE ANY POWER TO CABLES, PULL REMAINING CABLES

CONTRACTING OFFICER TO ASSESS THE CIRCUIT DUTY.

THERE ARE ANY CABLES OR GROUNDS REMAINING, CONTACT

CONNECTING MANHOLE C8 AND THE BASE OF LIGHT POLE F1. IF

REMOVED FROM THE DUCT BANK OR EMBEDDED CONDUITS

CHECK THAT ALL CABLES AND GROUNDING CONDUCTORS ARE 5.

10.

TO PREVENT WATER INTRUSION INTO CABLE. SEE GENERAL NOTE

CONDUCTOR END OF CABLE AND SPLICE CAP ENTIRE CABLE END

FOR STORAGE IN MANHOLE C8. ELECTRICALLY SPLICE CAP EACH

PULL CABLE L94 AND GROUND BACK TO MANHOLE C8. COIL CABLE 4.

FOR REINSTALLATION. SEE GENERAL NOTE 17.

REMOVE LIGHT POLE F1 AT STA. 662.0A AND CAREFULLY STORE 3.

CUTTING ANY MORE CABLE THAN NECESSARY.

THE F1 LIGHT POLE. DISASSEMBLE SPLICES IN A WAY TO AVOID

ASSOCIATED LIGHT POLE 120 VOLT RECEPTACLE AT THE BASE OF

DISCONNECT ELECTRICAL CABLE L94 TO LIGHT F1, AND THE 2.

ALL ASSOCIATED RECEPTACLES. SEE GENERAL NOTE 4.

PANELBOARD LP. CONFIRM THAT POWER IS OFF TO LIGHT F1, AND

AND LIGHT POLE 120 VOLT RECEPTACLE. CIRCUITS ARE LOCATED IN

PERSONNEL TURN OFF POWER TO LIGHT POLE F1 AT STA. 662.0A

COORDINATE WITH CONTRACTING OFFICER TO HAVE LOCK 1.

RIVER WALL (R-WALL) CABLE REROUTING SEQUENCE OF WORK:

CABLE AS A CONDUCTOR FOR THE CABLE LOCATION EQUIPMENT.

EMPTY CONDUITS (EC) SHALL BE LOCATED VIA CONTRACTOR PULLING IN A TEST 8.

ANCHORAGES.

DUCT BANK LOCATION IN RELATION TO MH-C6 OR MH-C8, AND TO THE GATE

LOCK WALL. EMPHASIS SHALL BE PLACED ON TAKING PHOTOS OF THE PAINTED

ASPECTS CLEARLY SHOWING THE PAINED DUCT BANK LOCATION ON TOP OF THE

IN THE AREA. INCLUDE A MINIMUM OF 4 PHOTOS TAKEN FROM DIFFERENT

LOCATION OF THE DUCT BANK PRIOR TO THE BEGINNING OF ANY CONSTRUCTION

SPECIFYING THE DETAILS OF HOW THE DUCT BANK WAS LOCATED AND THE

THE CONTRACTOR SHALL SUBMIT, FOR GOVERNMENT APPROVAL, A TRANSMITTAL 7.

EXCAVATION.

WILL BE VISIBLE TO THE CONTRACTOR PERFORMING THE CONCRETE

LOCATION WITH AN ENVIRONMENTALLY FRIENDLY BRIGHT MARKING PAINT WHICH

MARK THE OUTER BOUNDARIES OF THE DUCT BANK AND EMBEDDED CONDUIT 6.

MH-C8 IN THE AREA OF CONCRETE REMOVAL.

LOCATION SHALL BE THE TOP OF THE LOCK WALL DOWNSTREAM OF MH-C6 OR

BANK. THE AREA TO BE SCANNED FOR THE DUCT BANK AND EMBEDDED CONDUIT

SIGNAL. APPLY SIGNALS TO THE TWO OUTERMOST UPPER CABLES IN THE DUCT

VARY SIGNAL FREQUENCIES AS REQUIRED TO ACHIEVE OPTIMUM LOCATING 5.

CHECK THAT THE LOCATOR IS IN FACT DETECTING THE CABLES.

CABLES AND TO VERIFY DUCT BANK AND EMBEDDED CONDUITS LOCATION AS A

THE ADJACENT MANHOLE (MH-C6 OR MH-C8) SHALL BE OPENED TO ACCESS THE 4.

ONE OF THE CONDUCTORS IN EACH CABLE TO BE LOCATED.

THEIR POWER SOURCE, AND DIRECTLY CONNECTING THE SIGNAL SOURCE TO

METHOD. THIS ENTAILS DISABLING POWER, DISCONNECTING THE CABLES FROM

THE MORE RELIABLE METHOD IS THE “APPLICATION OF SIGNAL, DIRECT CONNECT” 3.

DURING THIS PROCEDURE.

CONDUCTORS. THE CABLE CAN BE LEFT CONNECTED TO ITS SOURCE AND LOAD

LOCATOR, CLAMPS AROUND CABLE TO INDUCE A SIGNAL IN THE CABLE

COUPLER” METHOD WHERE THE INDUCTIVE COUPLER, ASSOCIATED WITH

ONE OF TWO METHODS. THE LEAST INTRUSIVE METHOD IS THE “INDUCTIVE

LOCATE DUCT BANK AND EMBEDDED CONDUITS IN AREA OF CONSTRUCTION BY

CONTRACTOR SHALL USE A COMMERCIALLY AVAILABLE LOCATING DEVICE TO 2.

UTILITIES USING MAGNETIC SIGNATURE LOCATION EQUIPMENT.

SHALL HAVE A MINIMUM OF 5 YEARS EXPERIENCE WITH LOCATING BURIED

THE DUCT BANK (CABLE) AND EMBEDDED CONDUITS LOCATION CONTRACTOR 1.

DUCT BANK AND EMBEDDED CONDUITS LOCATION PROCEDURE:

A N

S I

D m v r-a p p w p lt \P

W iC

S S h a re

\3

\4

\M

R E -E

.d g n

:0

:3

A

M

M V

R -A

P P

W P

L T

D

A T

C K I S

L A

N D

IL

L

IN

O

IS

R O

C K I S

L A

N D D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

E -E

.d g n

B G

R

R

S

H O

W N

D D

J

C K

S

A N

D

M

IS

S

IS

S

IP

P I

R

IV

E R B

A S

IN

M R

EE002

SEE REFERENCE DRAWING L&D 18, EL64, FOR LIGHT POLE DETAIL.17.

SIDE AND COVERED WITH TARP.

COILED AND STORED ADJACENT TO THE MANHOLE ON THE DOWNSTREAM

WITHOUT RISK OF DAMAGE. ANY CABLES WHICH WILL NOT FIT SHALL BE

STORED IN THESE MANHOLES TO THE MAXIMUM EXTENT POSSIBLE

EXISTING CABLES IN THE VICINITY OF MANHOLES C6 OR C8 SHALL BE 16.

ARRANGEMENT. SEE GENERAL NOTE 12.

FOR LIMITED INFORMATION ON DUCT BANK SIZE, EMBEDDED CONDUITS, AND

ORIGINALLY INSTALLED. SEE REFERENCE DRAWINGS L&D 18, M-L 18 20/13,

CABLES IN SAME DUCT BANK DUCT LOCATIONS IN WHICH THEY WERE

CONTROL STAND TERMINAL BOARD INTERCONNECTION DIAGRAM. INSTALL

BOARDS OR PANELBOARD. SEE REFERENCE DRAWING L&D 18, EL53, FOR

RE-TERMINATE CABLES TO THEIR RESPECTIVE CONTROL STAND TERMINAL 15.

FROM MANHOLE C6 OR C8.

CABLE(S) (IN MANHOLE C6 OR C8). PULL TEMPORARY CABLE OUT AWAY

DISASSEMBLE SPLICE BETWEEN EXISTING CABLE(S) AND TEMPORARY 14.

2000 POUND TOTAL LOAD OR 1000 POUND SINGLE AXLE LOAD.

CABLE PATHWAY BRIDGES SHALL BE ABLE TO WITHSTAND NOT LESS THAN

TRAVERSE THEM WITHOUT GETTING IMPEDED ("HUNG UP"). TEMPORARY

PROPER RAMP PITCH TO ALLOW EXISTING LOCK CUSHMAN CARTS TO

ACROSS CABLES. TEMPORARY CABLE PATHWAY BRIDGE SHALL BE WITH

A TEMPORARY RAMPED PROTECTIVE BRIDGE TYPE CROSSING INSTALLED

LESS THAN 8 FEET OR AT ANOTHER ELEVATION IF APPROVED OR SHALL BE

PATHWAY CABLE CROSSINGS SHALL BE EITHER OVERHEAD TYPE AT NOT

FOR THE SAFE ROUTING OF TEMPORARY ELECTRICAL CABLES. TEMPORARY

INSTALLED IN ACCORDANCE WITH EM 385-1-1, NFPA 70, AND IEEE/ANSI C2

TEMPORARY PATHWAY CABLE CROSSINGS SHALL BE PROVIDED AND

CUSHMAN TUG CARTS CAN HAVE A TOTAL MAXIMUM LOAD OF 2,000 POUNDS.

PEDESTRIAN TRAFFIC AND FROM LOADED CUSHMAN TUG TYPE CARTS.

TEMPORARY CABLES ARE PHYSICALLY PROTECTED FROM BOTH

ROUTE TEMPORARY ELECTRICAL CABLES ACROSS PATHWAYS SO THAT

AND BACK INTO DUCT BANK DUCT AS REQUIRED. THE CONTRACTOR SHALL

HANDRAIL POSTS, AND INTO MANHOLE C4, CONTROL STAND TERMINATIONS,

OF LOCK WALL, ALONG MAIN LOCK CHAMBER HANDRAIL, SECURING TO

LOCK CHAMBER HANDRAIL. ROUTE TEMPORARY CABLE UPSTREAM, ON TOP

SURFACE ROUTE TEMPORARY CABLE OUT OF MANHOLE C6 OR C8 TO MAIN

SPLICE TEMPORARY CABLE TO EXISTING CABLE IN MANHOLE C6 OR C8. 13.

SAME DUCTS FROM WHICH THEY WERE ORIGINALLY REMOVED.

FROM WHICH IT WAS REMOVED. RE-INSTALL ALL PERMANENT CABLES IN THE

RECORDED SO THAT EACH CABLE IS RE-INSTALLED IN THE SAME DUCT

DEMOLISHING ANY CONCRETE. DUCTS AND CONDUITS SHALL BE NOTED AND

LOCATION OF EACH CABLE PRIOR TO REMOVING ANY CABLES OR

THE CONTRACTOR SHALL VERIFY DUCT AND EMBEDDED CONDUITS 12.

CONTRACTOR'S EXPENSE

CABLE SOURCE TO THE LOAD AND WILL BE REPLACED AT THE

SHALL REPLACE THE ENTIRE CABLES CONTINUOUS LENGTH FROM THE

ORIGINAL CABLE TAP SPLICES. IF A CABLE IS DAMAGED THE CONTRACTOR

CABLE WILL NOT BE ALLOWED OTHER THAN SPECIFIED TO RESTORE

SPLICED CABLE AND RE-TERMINATE. PERMANENT SPLICES IN EXISTING

INSULATION. EXCESS CABLE SLACK MAY BE INADEQUATE TO CUT OUT

AS TO PREVENT DAMAGE TO THE EXISTING CABLE AND CONDUCTOR

SPLICES AND SPLICE CAPS SHALL BE CAREFULLY REMOVED IN SUCH A WAY 11.

NON-TERMINATED CABLE.

SPLICE CAPS SHALL BE INSTALLED TO PROTECT THE END OF A

TO PROTECT THE CABLE AND CONDUCTOR ENDS FROM WATER INTRUSION.

CONDUCTORS AND CABLE END TO INSULATE FROM ELECTRIC SHOCK AND

MATERIAL WHICH CAN BE PLACED OVER THE END OF THE BARE

A SPLICE CAP IS A TERM USED TO DESCRIBE BLIND ENDED SHRINK 10.

ENTIRETY FROM SOURCE TO LOAD AT THE CONTRACTOR'S EXPENSE.

ANY CABLES DAMAGED BY THE CONTRACTOR SHALL BE REPLACED IN 9.

SHALL BE REPAIRED AT CONTRACTOR'S EXPENSE.

ANY DAMAGE TO DUCT BANK OR EMBEDDED CONDUITS BY CONTRACTOR 8.

WILL BE ALLOWED TO BE EXPOSED ON THE LOCK WALL.

SHALL BE MADE IN THE MANHOLES AND ONLY THE TEMPORARY CABLES

LOCK WALL OR SECURED TO THE HANDRAILS. TEMPORARY CABLE SPLICES

OR DUCT BANKS AND SHALL NOT BE BROUGHT OUT TO BE EXPOSED ON THE

EXISTING CABLES SHALL BE PROTECTED BY REMAINING IN THE MANHOLES 7.

TEMPORARY WIRES TO MAINTAIN SYSTEM OPERABILITY.

MAINTAIN TEMPORARY WIRES AND SHALL PROVIDE REPAIRS TO DAMAGED

CABLE INSULATION OR ROPE BREAKAGE. THE CONTRACTOR SHALL

PHYSICAL LOADS PLACED ON THE ROPE WITHOUT THE ROPE DAMAGING THE

TO HANDRAIL POSTS BY NYLON ROPE LARGE ENOUGH TO SUPPORT THE

ALONG HANDRAIL, ADEQUATELY PROTECTED FROM ALL TRAFFIC, SECURED

TEMPORARY CABLES SHALL BE ROUTED ON TOP OF LOCK WALL ROUTED 6.

BANKS.

AND DUCT CLEANING PRIOR TO RE-INSTALLATION OF CABLES IN DUCT

SEE SPECIFICATION SECTION 33 70 02 FOR SPLICES OF TEMPORARY CABLES 5.

EM 385-1-1 DATED NOVEMBER 30, 2015, SECTION 12.

IN ACCORDANCE WITH THE SAFETY AND HEALTH REQUIREMENTS MANUAL

CONTRACTOR SHALL ADHERE TO PROPER LOCKOUT/TAG OUT PROCEDURES 4.

385-1-1 DATED NOVEMBER 30, 2015, SECTION 11, SUBSECTION J.

ACCORDANCE WITH THE SAFETY AND HEALTH REQUIREMENTS MANUAL EM

CONTRACTOR SHALL PROVIDE PROTECTION FROM OPEN MANHOLES IN 3.

THE CONTRACTING OFFICER PRIOR TO ANY ELECTRICAL POWER OUTAGES.

CONTRACTOR SHALL COORDINATE WITH AND RECEIVE APPROVAL FROM 2.

EL60 AND EL61, FOR EXISTING CABLE SIZES.

WITH CABLE TIES OR NYLON ROPE. SEE REFERENCE DRAWINGS L&D 18,

CONDUCTORS OF EACH CABLE SHALL BE BUNDLED AND TIED TOGETHER

CONDUCTORS OF THE PERMANENT CABLE BEING SPLICED TO. THE

DEGREE COPPER. CONDUCTOR SIZE SHALL NOT BE LESS THAN THE

TEMPORARY CABLES SHALL BE SINGLE CONDUCTOR 600 VAC, THWN 90 1.

GENERAL NOTES:

OPERATING CORRECTLY.

CORRECTED UNTIL ALL SYSTEMS ARE PROVEN TO BE FULLY OPERATIONAL AND

ALL POWER, LIGHTING, AND CONTROL SYSTEMS SHALL BE TESTED AND 10.

REQUIRED FOLLOWING THE PROCEDURES OF GENERAL NOTE 13.

REMAINING CABLE OR GROUND, AND INSTALL TEMPORARY CABLE AS

ACCESS THE CIRCUIT DUTY. DE-ENERGIZE ANY POWER TO CABLE, PULL

ANY CABLES OR GROUNDS REMAINING, CONTACT CONTRACTING OFFICER TO

THE DUCT BANK CONNECTING MANHOLES MH-C6 AND MH-C4. IF THERE ARE

CHECK THAT ALL CABLES AND GROUNDING CONDUCTORS ARE REMOVED FROM 9.

FULLY OPERATIONAL AND PROPER PHASE ROTATION HAS BEEN MAINTAINED.

CABLES LISTED IN TABLES 1 AND 2. VERIFY THE MITER GATE EQUIPMENT IS

ON POWER TO I-WALL MITER GATE MACHINERY POWER CABLES AND CONTROL

COORDINATE WITH CONTRACTING OFFICER TO HAVE LOCK PERSONNEL…

This is the start of the file's text. The full file is on GovTribe.