WVA_FIRE_SUPPRESSION_100_pct_Submission_Combined_(compress).pdf
PDF 15 MB Posted
- Attached to
- Fire Suppression System, Various Buildings, Watervliet, NY Federal contract opportunity
- Solicitation number
- W912DS19B0019
About this file
Drawings
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Bid_Abstract.pdf | ||
| W912DS19B0019_0003.pdf | ||
| FPS001.pdf | ||
| 21_13_17.00_10.pdf | ||
| W912DS19B0019_0002.pdf | ||
| 28_31_64_00_10.pdf | ||
| 01_45_00_00_10.pdf | ||
| 21_13_13_00_10.pdf | ||
| W912DS19B0019_0001.pdf | ||
| RTA_WVA_FIRE_SUPPRESSION_Spec.pdf | ||
| W912DS19B0019.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ARCHITECTURAL:
QPK DESIGN
ARCHITECTS/ENGINEERS
450 SOUTH SALINA ST
SYRACUSE NY 13201
315-472-7806
MEP:
GHD
REMINGTON PARK DRIVE
CAZENOVIA NY 13035
315-679-5800
0' 8' 16' 64'32' 0' 6" 1'3"0' 1' 2'6"0' 2' 4'1'0' 2' 4' 8' 16'0' 4' 8' 16' 32'0' 8' 16' 32' 64'0' 4' 8' 32'16'
Q P
K D
E S
IG
N
S
O U
T H
S A
L
IN
A S
T R
E E
T S
Y R
A C
U S
E N
E W
Y O
R K
US Army Corps of Engineers
1 2 3 54
A
B
C
D
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
N E
W Y
O R
K D
IS
T
R
IC
T S
O L
IC
IT
A
T
IO
N N
O
F
IL
E N
A M
E
D W
N B
Y
C K
D B
Y
D E
S
IG
N E
D B
Y
D A
T E
F
IL
E N
U M
B E
R
S
IZ
E
S U
B M
IT
T
E D
B Y
P L O
T S
C A
L E
P
L O
T D
A T
E
C O
N T
R A
C T
N O
W
D S
-1
-D -0
-0
R
E P
A
IR
F A
C
IL
IT
IE
S D
E F
IC
IE
N C
IE
S
B
U
IL
D
IN
G
W A
T E
R V
L
IE
T A
R S
E N
A L
F Y
W
A T
E R
V L
IE
T
N
Y
WARNING: THIS DOCUMENT MAY CONTAIN SENSITIVE SECURITY INFORMATION AND THEREFORE MUST BE TREATED AS A CONFIDENTIAL DOCUMENT. THE INFORMATION CONTAINED IN THIS DOCUMENT MUST BE MAINTAINED IN A CONFIDENTIAL MANNER TO PREVENT COMPROMISING HOMELAND SECURITY AS PROVIDED IN SECTION 214 OF THE HOMELAND SECURITY ACT OF 2002. NO PART OF THIS DOCUMENT SHALL BE REPRODUCED, RELEASED OR DISTRIBUTED WITHOUT THE EXPRESS WRITTEN PERMISSION OF THE UNITED STATES ARMY CORPS OF ENGINEERS, NEW YORK DISTRICT (USACE - NYD). UNAUTHORIZED REPRODUCTION, RELEASE OR DISTRIBUTION MAY RESULT IN CIVIL PENALTY OR OTHER ACTION BY USACE-NYD.
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
A S
IN
D
IC
A
T E
D
X
/1
/2
:0
:5
P
M
G-001
J U
L Y
D e s ig n e r
C h e c k e r A u th o r
W A
T E
R V
L
IE
T A
R S
E N
A L
N
E W
Y O
R K
.0
C O
V E
R S
H E
E T
DRAWING LIST
GENERAL
G-001 COVER SHEET
ARCHITECTURAL INFORMATION
A-001 GENERAL INFORMATION
A-002 WATER DIST PLAN, AERIAL PHOTO, REPAIR DETAILS
A-003 DETAILS
A-004 BUILDING 22 REGULATORY PLANS - BSMT & 1ST FLRS
A-005 BUILDING 40-5, 40-6 REGULATORY PLAN
A-006 BUILDING 41 REGULATORY PLAN, BUILDING SECTION
A-007 BUILDING 108 REGULATORY PLAN, BUILDING SECTION
A-008 BUILDING 126 REGULATORY PLAN, BUILDING SECTION
ARCHITECTURAL
A-101 BUILDING 22 RCPS - BSMT & 1ST FLRS
A-102 BUILDING 40-05, 40-06 RCPS
A-103 BUILDING 41 RCP
A-104 BUILDING 108 RCP
A-105 BUILDING 126 RCP
FIRE PROTECTION
FPS-001 FIRE SERVICE SITE PLAN
FP-001 MISC. DETAILS
FP-002 MISC. DETAILS
FP-100 BUILDING 22 - REGULATORY PLANS - BSMT & 1ST FLRS
FP-101 BUILDING 22 - REGULATORY PLANS - ATTIC PLAN
FP-102 BUILDING 40 PARTIAL FIRST FLOOR PLAN
FP-103 BUILDING 40 PARTIAL ATTIC PLAN
FP-104 BUILDING 41 FIRST FLOOR PLAN
FP-105 BUILDING 108 FIRST FLOOR PLAN
FP-106 BUILDING 126 FIRST FLOOR PLAN
FP-107 BUILDING 126 DETAILS SHEET
FY 15 FIRE SUPPRESSION SYSTEM
VARIOUS BUILDINGS
WATERVLIET ARSENAL
WATERVLIET, NY 12189
JULY 15, 2019
W912DS-14-D-0002-0022
PROJECT
NORTH
Q P K D E S I G N
ARCHITECTURE
ENGINEERING
SITE & PLANNING
450 SO. SALINA ST. PO BOX 29
SYRACUSE, NEW YORK 13021-0029
TEL 315.472.7806 FAX 315.472.7800
I T I S A V I O L A T I O N O F T H E L A W F O R A N Y P E R S O N , U N L E S S A C T I N G U N D E R T H E D I R E C T I O N O F A L I C E N S E D A R C H I T E C T , T O A L T E R T H I S D O C U M E N T I N A N Y W A Y . I F A L T E R E D , T H E A L T E R I N G A R C H I T E C T S H A L L A F F I X T H E I R S E A L A N D T H E N O T A T I O N ' A L T E R E D B Y ' F O L L O W E D B Y T H E I R S I G N A T U R E A N D T H E D A T E O F S U C H A L T E R A T I O N , A N D A S P E C I F I C D E S C R I P T I O N O F T H E A L T E R A T I O N
S H E E T T I T L E
D A T E
P R O J E C T N U M
A
N
OT F
O R C
O
NS
TR
U
CTIO
N
2 3 4 5 6 7
B
C
D
E
F
1 2 3 4 5 6 7
A
B
C
D
E
F
Enter address here
FLOOR PLAN-
AREA 1
A-102
XX/XX/XX
Project Number
Owner
Project Name
R E V I S I O N S
N A
ROOM NAME DESIGNATION
ROOM NUMBER DESIGNATION (IF PRESENT)
ROOM AREA DESIGNATION (IF PRESENT)
PARTITION TYPE DESIGNATION. SEE
PARTITION LEGEND
DOOR NUMBER DESIGNATION
SPECIAL NOTATION (e.g. DEMO NOTE)
W1 WINDOW TYPE DESIGNATION
1T ACCESSORY ITEM- SEE ACCESSORY
SCHEDULE
DATUM POINT OR WORK POINT
BUILDING SECTION
WALL SECTION
DETAIL NUMBER
SHEET NUMBER WHERE
DETAIL IS LOCATED
DETAIL NUMBER
SHEET NUMBER WHERE
DETAIL IS LOCATED
EXTENT OF SECTION
A-XXX
A1
A2 B1
DETAIL NUMBERS
SHEET NUMBER WHERE
DETAIL IS LOCATED
ELEVATIONS
REVISION NOTE
REVISION NUMBER
EXTENT OF REVISION
A1 A2 A3 A4 A5 A6 A7
B1 B2 B3 B4 B5 B6 B7
C1 C2 C3 C4 C5 C6 C7
D1 D2 D3 D4 D5 D6 D7
E1 E2 E3 E4 E5 E6 E7
F1 F2 F3 F4 F5 F6 F7
DETAIL NUMBER DETAIL SCALE
DETAIL NAME
DETAIL NUMBER
SCALE: 1/8" = 1'-0"
AXX
View Name
ROOM NAME
00000
1500 SF
DETAIL SECTION
DETAIL NUMBER
SHEET NUMBER WHERE
DETAIL IS LOCATED
EXTENT OF SECTION
PLAN DETAIL
DETAIL
NUMBER
SHEET NUMBER
WHERE DETAIL
IS LOCATED
EXTENT
OF DETAIL
NNNL
A-XXX
A-XXX
A-XXX
A-XXX
A-XXX
CONTRACTOR WILL ASSUME ALL FLOOR TILE AND CEILING TILES ARE ASBESTOS UNTIL THEY ARE SAMPLED. CONTRACTOR SHOULD INCLUDE TESTING IN THEIR EFFORTS TO CONFIRM ASBESTOS PRESENCE/ABSENCE BEFORE CONDUCTING CONSTRUCTION ACTIVITIES. TO THE BEST OF OUR KNOWLEDGE, ALL SAMPLE RESULTS FOR MATERIALS IDENTIFIED AS VERTICAL WALL SURFACES ARE ACCURATE (THE ATTACHED REPORTS IN 02 82 13.10) ANY OTHER CONSTRUCTION RELATED ACTIVITY THAT MAY INADVERTENTLY CAUSE AS ASBESTOS DISTURBANCE, BUT IS NOT IDENTIFIED THROUGH PROVIDED SAMPLING RESULTS (NO TESTING RESULTS PROVIDED FOR A SPECIFIC AREA), WILL BE TESTED FOR THE PRESENCE OF ASBESTOS PRIOR TO CONSTRUCTION ON THAT SURFACE.
IT IS NOT INTENDED THAT ANY POSITIVELY SAMPLED AREA BE TOTALLY REMEDIATED - ONLY AREAS IMPACTED BY ATTACHMENT OR PENETRATIONS ARE TO BE
MITIGATED. ALL HAZARDOUS MATERIAL REMEDATION SHALL OCCUR DURING 2ND SHIFT.
FIRE SUPPRESSION SYSTEM
PROJECT BUILDINGS
GRAPHIC KEY
NOTES:
1. THIS KEY PLAN SHALL BE USED FOR
BUILDING LOCATION REFERENCE ONLY
AND DOES NOT DEPICT EXTENTS OF WORK
SCOPES.
2. COORDINATE FINAL LOCATIONS WITH
ARSENAL LOGISTICS AND COR.
STAGING AREA
TRAILER
ACCESS ROUTES
ARSENAL SITE
ENTRANCE
PNTD PAINTED
PR PAIR
PREFAB PREFABRICAT(D)
PT PRESSURE TREATED
PTD PAPER TOWER DISPENSER
PTN PARTITION
PVC POLYVINYL CHLORIDE
(PLASTIC)
PVG PAVING
Q
QT QUARRY TILE
QTY QUANTITY
R
R RADIUS/RISER
R RESILIENT
RB RESILIENT BASE
RBR RUBBER
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REF REFRIDGERATOR
REINF REINFORCE(D)
REQ'D REQUIRED
RESIL C RESILIENT CHANNEL
RET RETURN
REV REVISION
RM ROOM
RO ROUGH OPENING
S
SC SOLID CORE
SCHED SCHEDULE
SECT SECTION
SF SQUARE FEET
SHT SHEET
SHTHG SHEATHING
SIM SIMILAR
SLNT SEALANT
SND SANITARY NAPKIN
DISPENSER
SNDU SANITARY NAPKIN DISPOSAL
UNIT
SPEC SPECIFICATION
SPKLR SPRINKLER
SQ SQUARE
SSM SOLID SURFACE MATERIAL
SST STAINLESS STEEL
STC SOUND TRANSMISSION
CLASS
STD STANDARD
STL STEEL
STL JST STEEL JOIST
STL LNTL STEEL LINTEL
STL PLATE STEEL PLATE
STRUCT STRUCTURAL
SUSP SUSPENDED
SV SHEET VINYL
SVT SHEET VINYL FLOORING
SYMM SYMMETRICAL
T
T TREAD
T&G TONGUE AND GROOVE
TEL TELEPHONE
TEMP TEMPERATURE
TER TERRAZZO
TERM TERMINAL
THK THICKNESS
THRES THRESHOLD
TK BD TACKBOARD
TMPD TEMPERED
TO TOP OF
TOC TOP OF CONCRETE
TOS TOP OF STEEL
TOW TOP OF WALL
TRANS TRANSOM, TRANSPARENT
TYP TYPICAL
U
UC UNDERCUT
UL UNDERWRITER'S LABATORY
(TEST)
UNO UNLESS NOTED OTHERWISE
UR URINAL
V
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VNR VENEER
VP VENEER PLASTER
VR VAPOR RETARDER
VT VINYL TILE
VWC VINYL WALLCOVERING
W
W WIDE
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WOOD
WDW WINDOW
WGL WIRED GLASS
WP WATERPROOFING
WPT WORKPOINT
WS WEATHERSTRIP
WWF WELDED WIRE FABRIC
FIXT FIXTURE
FLASH FLASHING
FLG FLOORING
FLR FLOOR
FM FACTORY MUTUAL
FO FACE OF
FOF FACE OF FINISH
FOS FACE OF STUD
FP FIREPROOFING
FR FRAME
FRMG FRAMING
FRP FIBERGLASS REINFORCED
PLASTIC/PANEL
FRTW FIRE RETARDANT TREATED
WOOD
FT FOOT/FEET
FTG FOOTING
FURG FURRING
FURN FURNISHED/FURNITURE
FWC FABRIC WALL COVERING
G
GA GAUGE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GCT GLAZED CERAMIC TILE
GL GLASS/GLAZING
GWB GYPSUM WALLBOARD
GYP GYPSUM
H
HC HOLLOW CORE
HCP HANDICAPPED
HDBD HARDBOARD
HDW HARDWARE
HDWD HARDWOOD
HM HOLLOW METAL
HORIZ HORIZONTAL
HR HOUR
HT HEIGHT
HVAC HEATING/VENTILATING/AIR
CONDITIONING
I
ID INSIDE DIAMETER
INCL INCLUDE(D)(-ING)
INSUL INSULATE(D)(-ION)(-ING)
INT INTERIOR
INV INVERT
J
JAN JANITOR
JT JOINT
L
LAM LAMINATE(D)
LAV LAVATORY
LF LINEAR FEET
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LT GA LIGHT GAUGE
LTG LIGHTING
LVR LOUVER
M
MACH MACHINE
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MEMB MEMBRANE
MEZZ MEZZANINE
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MKR BD MARKER BOARD
MLDG MOULDING
MO MASONRY OPENING
MR MOISTURE RESISTANT
MTL METAL
MULL MULLION
N
NA NOT APPLICABLE
NAT NATURAL
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NPS NOMINAL PIPE SIZE
NTS NOT TO SCALE
O
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
P
PBD PARTICLE BOARD
PCT PORCELAIN CERAMIC TILE
PERIM PERIMETER
PL PROPERTY LINE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLYWD PLYWOOD
PNL PANEL
PNT PAINT
A
A/C AIR CONDITIONING
AB ANCHOR BOLT
ACC ACCESIBLE
ACS PNL ACCESS PANEL
ADDM ADDENDUM
ADJ ADJUSTABLE
AFF ABOVE FINISH FLOOR
AHR ANCHOR(AGE)
ALT ALTERNATE
ALUM ALUMINUM
ANN PNL ANNUNCIATOR PANEL
ANOD ANODIZED
APC ACOUSTICAL PANEL CEILING
APPROX APPROXIMATE
ARCH ARCHITECT(URAL)
ASB ASBESTOS
ASPH ASPHALT
ATC ACOUSTICAL TILE CEILING
B
BD BOARD
BEV BEVELED
BLDG BUILDING
BLKG BLOCKING
BLKT BLANKET
BM BEAM, BENCHMARK
BOT OF BOTTOM OF
BRG BEARING
BSMT BASEMENT
BUR BUILT-UP ROOF
C
CAB CABINET
CEM CEMENT
CH BD CHALKBOARD
CIP CAST-IN-PLACE
CJ CONTROL JOINT
CLG CEILING
CLL CONTRACT LIMIT LINE
CLO CLOSET
CLR CLEAR
CMP CORRUGATED METAL PIPE
CMPST COMPOSITE
CMT CERAMIC MOSAIC TILE
CMU CONCRETE MASONRY UNIT
COL COLUMN
COMB COMBINATION
CONC CONCRETE
CONSTR CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CORR CORRIDOR
CPRS FL COMPRESSIBLE FILLER
CPT CARPET
CR CARD READER
CRS COLD ROLLED STEEL
CT CERAMIC TILE
D
D DEPTH
DET DETAIL
DF DRINKING FOUNTAIN
DFLCT DEFLECTION
DH DOUBLE HUNG
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DL DEAD LOAD
DMPF DAMPPROOFING
DR DOOR
DWG DRAWING
E
EA EACH
EIFS EXTERIOR INSULATION AND
FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRIC(AL)
ELEV ELEVATOR
EMHO ELECTROMAGNETIC HOLD
OPEN
ENTR ENTRANCE
EP ELECTRIC PANEL
EQ EQUAL
EQUIP EQUIPMENT
EST ESTIMATE
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXIST EXISTING
EXP EXPOSED, EXPANSION
EXT EXTERIOR
F
FAAP FIRE ALARM ANNUNCIATOR
PANEL
FCU FAN COIL UNIT
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FH FIRE HYDRANT
FIN FINISH(ED)
GENERAL NOTES
NUMBER
1 NON-ARCHITECTURAL DISCIPLINE INFORMATION IF SHOWN IS FOR REFERENCE ONLY. OBJECTS AND INFORMATION SHOWN MAY NOT BE ALL INCLUSIVE.
REFER TO APPROPRIATE DISCIPLINE FOR INFORMATION.
2 ALL WORK SHALL BE DONE IN ACCORDANCE WITH ALL APPLICABLE CODES, ORDINANCES AND ACCEPTED INDUSTRY STANDARDS.
3 THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL EXISTING CONDITIONS AND ESTABLISHING THE COMPATIBILITY OF ALL NEW WORK WITH
THE EXISTING CONDITIONS.
4 ALL WORK BEING DONE IS ADJACENT TO OCCUPIED SPACE. CONTRACTOR SHALL TAKE EVERY PRECAUTION TO ELIMINATE THE TRAVEL OF WATER, DUST
AND DIRT FROM THE CONSTRUCTION AREA TO OCCUPIED SPACES.
5 SCHEDULE AND SEQUENCING OF WORK SHALL BE COORDINATED WITH CONTRACTING OFFICER'S REPRESENTATIVE PRIOR TO THE START OF WORK
6 CONTRACTOR SHALL PATCH ALL SURFACES TO REMAIN THAT ARE AFFECTED BY DEMOLITION OR REMOVAL OF EXISTING EQUIPMENT & CONSTRUCTION.
SURFACES SHALL BE FILLED, SANDED SMOOTH & FINISHED TO MATCH ADJACENT SURFACE.
7 THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROVISION AND CONTINUOUS MAINTENANCE OF ALL WORK FROM DAMAGE AND SHALL PROTECT THE OWNERS' PROPERTY FROM DAMAGE OR LOSS BY DUST, DIRT, WATER, THEFT, FIRE OR ANY OTHER PHYSICAL DAMAGE IN CONNECTION WITH THE WORK.
8 MAINTAIN EXISTING UTILITIES INDICATED TO REMAIN, KEEP IN SERVICE, AND PROTECT DAMAGE DURING ALL RENOVATION WORK. GENERAL CONTRACTOR SHALL COORDINATE CONSTRUCTION AROUND EXISTING EQUIPMENT, CONDUIT CABLING, ETC. WITH COR AS REQUIRED TO MAINTAIN CONTINUOUS
OPERATION.
9 CONTRACTOR SHALL COORDINATE EXACT LOCATION OF ALL EQUIPMENT TO BE INSTALLED IN CEILING WITH EXISTING MECHANICAL AND ELECTRICAL WORK
TO REMAIN IN PLACE.
10 ALL PENETRATIONS IN RATED ASSEMBLIES SHALL BE SEALED WITH UL/FM APPROVED MATERIAL, ASSEMBLIES, AND PROCEDURES.
11 DRAWINGS SHALL NOT BE SCALED AS A BASIS FOR ESTABLISHING DIMENSIONS OR OTHER INFORMATION.
12 REFLECTED CEILINGS INDICATE TYPE OF CEILING AND NOT NECESSARILY EXACT GRID LOCATIONS FOR EXISTING ACP.
13 INTERIOR LAYDOWN AREAS ARE NOT ANTICIPATED TO BE AVAILABLE.
SCALE: NO SCALE
A1
ABBREVIATIONS
0' 8' 16' 64'32' 0' 6" 1'3"0' 1' 2'6"0' 2' 4'1'0' 2' 4' 8' 16'0' 4' 8' 16' 32'0' 8' 16' 32' 64'0' 4' 8' 32'16'
Q P
K D
E S
IG
N
S
O U
T H
S A
L
IN
A S
T R
E E
T S
Y R
A C
U S
E N
E W
Y O
R K
US Army Corps of Engineers
1 2 3 54
A
B
C
D
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
N E
W Y
O R
K D
IS
T
R
IC
T S
O L
IC
IT
A
T
IO
N N
O
F
IL
E N
A M
E
D W
N B
Y
C K
D B
Y
D E
S
IG
N E
D B
Y
D A
T E
F
IL
E N
U M
B E
R
S
IZ
E
S U
B M
IT
T
E D
B Y
P L O
T S
C A
L E
P
L O
T D
A T
E
C O
N T
R A
C T
N O
W
D S
-1
-D -0
-0
R
E P
A
IR
F A
C
IL
IT
IE
S D
E F
IC
IE
N C
IE
S
B
U
IL
D
IN
G
W A
T E
R V
L
IE
T A
R S
E N
A L
F Y
W
A T
E R
V L
IE
T
N
Y
WARNING: THIS DOCUMENT MAY CONTAIN SENSITIVE SECURITY INFORMATION AND THEREFORE MUST BE TREATED AS A CONFIDENTIAL DOCUMENT. THE INFORMATION CONTAINED IN THIS DOCUMENT MUST BE MAINTAINED IN A CONFIDENTIAL MANNER TO PREVENT COMPROMISING HOMELAND SECURITY AS PROVIDED IN SECTION 214 OF THE HOMELAND SECURITY ACT OF 2002. NO PART OF THIS DOCUMENT SHALL BE REPRODUCED, RELEASED OR DISTRIBUTED WITHOUT THE EXPRESS WRITTEN PERMISSION OF THE UNITED STATES ARMY CORPS OF ENGINEERS, NEW YORK DISTRICT (USACE - NYD). UNAUTHORIZED REPRODUCTION, RELEASE OR DISTRIBUTION MAY RESULT IN CIVIL PENALTY OR OTHER ACTION BY USACE-NYD.
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
A S
IN
D
IC
A
T E
D
X
/1
/2
:4
:5
A
M
A-001
J U
L Y
D e s ig n e r
C h e c k e r A u th o r
W A
T E
R V
L
IE
T A
R S
E N
A L
N
E W
Y O
R K
.0
G E
N E
R A
L I N
F O
R M
A T
IO
N
SCALE: NO SCALE
D4
GENERAL NOTES
SCALE: NO SCALE
C4
EXISTING HAZARDOUS MATERIALS
SCALE: 1/4" = 1'-0"
A3
ARSENAL KEY PLAN
0' 8' 16' 64'32' 0' 6" 1'3"0' 1' 2'6"0' 2' 4'1'0' 2' 4' 8' 16'0' 4' 8' 16' 32'0' 8' 16' 32' 64'0' 4' 8' 32'16'
Q P
K D
E S
IG
N
S O
U
TH
S A
LI
N
A S
TR
E
E T
S Y
R A
C U
S E
, N E
W Y
O R
K
US Army Corps of Engineers
1 2 3 54
A
B
C
D
SO
LI
C
IT
AT
IO
N N
O
FI
LE
N
AM
E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E:
FI
LE
N U
M
BE
R
SI
ZE
SU
BM
IT
TE
D B
Y:
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
C O
N
TR
AC
T
N O
W
2D S
-1 4-
D -0
2-
FY
FI
R E
S U
P R
E S
S
IO
N S
Y S
TE
M
V A
R
IO
U S
B U
IL
D
IN
G
S W
A
TE
R V
LI
E
T A
R S
E N
A L, N E
W Y
O R
K
WARNING: THIS DOCUMENT MAY CONTAIN SENSITIVE SECURITY INFORMATION AND THEREFORE MUST BE TREATED AS A CONFIDENTIAL DOCUMENT. THE INFORMATION CONTAINED IN THIS DOCUMENT MUST BE MAINTAINED IN A CONFIDENTIAL MANNER TO PREVENT COMPROMISING HOMELAND SECURITY AS PROVIDED IN SECTION 214 OF THE HOMELAND SECURITY ACT OF 2002. NO PART OF THIS DOCUMENT SHALL BE REPRODUCED, RELEASED OR DISTRIBUTED WITHOUT THE EXPRESS WRITTEN PERMISSION OF THE UNITED STATES ARMY CORPS OF ENGINEERS, NEW YORK DISTRICT (USACE - NYD). UNAUTHORIZED REPRODUCTION, RELEASE OR DISTRIBUTION MAY RESULT IN CIVIL PENALTY OR OTHER ACTION BY USACE-NYD.
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
6/ 8/
0:
:2
A
M
A-002
JU
LY
5, D es ig ne r
C he ck er
A ut ho r
W A
TE
R
V
LI
E T
A R
S E
N A
L, N
E W
Y O
R K
.0
W
AT
ER
D
IS
T
PL
AN
, A
ER
IA
L
PH
O
TO
, R
EP
AI
R
D
ET
AI
LS
D1 NTS
CONCRETE WALK D2 NTS
ASPHALT PARKING PAVEMENT D3 NTS
ASPHALT ROAD PAVEMENT D4 NTS
ASPHALT WALK PAVEMENT D5 NTS
ASPHALT JOINT (SAWCUT)
A1 AS NOTED
EXISTING WATER DISTRIBUTION PLAN A1 AS NOTED
EXISTING AERIAL PHOTO
PAVEMENT PER PLAN
NYSDOT TYPE 2
SUBBASE
COMPACTED SUBGRADE
FIN. GR.
GRANITE CURB
SLIP SHEET AT ALL
CONCRETE WALK
LOCATIONS
3,000 PSI CONTINUOUS
CONCRETE BACKING
6" 6"
FIN. GR.
6" ± (MATCH EXISTING)
6"6"
5" ± (MATCH EXISTING)
CAST IN PLACE
4,000 P.S.I. CONCRETE CURB
PAVEMENT PER DETAIL
COMPACTED
N.Y.S.D.O.T. TYPE 2
SUBBASE MATERIAL
COMPACTED SUBGRADE
CONTINUOUS SLIP SHEET
AT ALL CONCRETE
WALK LOCATIONS
1'- 4"
6"
CURB JOINT INFORMATION:
· SAWCUT AT NEAREST EXISTING JOINTS.
· EXPANSION JOINTS @ 50' O.C. MAX.
· CONTROL JOINTS @ 6' O.C. (TYP.)
· ALIGN ALL CONCRETE CURB & WALK JOINTS
FIN. GR.
6"
12" RADIUS
6"± (MATCH EXISTING)
6"± MATCH EXISTING CURB PROFILE
4'- 0"
5'- 0"
1"
15"
3"
6" Ø SCHEDULE 40 GALV. STEEL
PIPE, COLOR: SAFETY YELLOW.
3,000 PSI CONCRETE FILLER
FINISH GRADE
1/2" EXPANSION JOINT & SEALANT
CONCRETE PAVEMENT PER DETAIL
3,000 PSI CONCRETE FOOTING,
24"Ø. AUGER OR EXCAVATE AND
USE SONOTUBE FOR SMOOTH
VERTICAL FACE.
SUBBASE MATERIAL
COMPACTED SUBGRADE
6" M
IN
2" M
IN
SPACING PER SCHEDULE
MIN. 2" MULCH
SPECIES AS PER
PLANTING PLAN & PLANT
SCHEDULE
PLANTING SOIL 6" MIN.
DEPTH.
SCARIFY SUBGRADE
1"-2" +/- DEPTH,
PERPENDICULAR TO
CONTOUR.
SUBGRADE
6" TYPICAL
BED EDGE
6" M
IN
IM
UM
T
OP
SO
IL
DE
PT
H
FO
R
LA
W
N
AR
EA
S
AD
JA
CE
NT
T O
PL
AN
T
BE
DS
MIN. 2 x ROOT BALL (TYP)
5'- 0"
(M
IN
3"
INSTALL (2) HARDWOOD STAKES PER
TREE W/ RUBBER HOSES & 14GA.
DOUBLE STRAND TIE WIRE. INSTALL
PERPENDICULAR TO PREVAILING
WINDS OR SLOPE DIRECTION (TYP).
SET FLARE OF ROOT BALL 2" ABOVE
SURROUNDING GRADE. DO NOT PLACE
OR MOUND MULCH AGAINST TREE
TRUNK (TYP).
MIN. 3" DEEP DOUBLE GROUND .
HARDWOOD MULCH (TYP).
FORM 3" SOIL SAUCER AROUND
TREE OR GATOR BAG
FINISH GRADE
PRUNE BROKEN, DAMAGED, OR
CROSSING BRANCHES (TYP).
OPTIONAL GATOR BAG
PLANTING SOIL AS SPECIFIED. TAMP
SOIL AROUND ROOT BALL USING FOOT
PRESSURE.
REMOVE BURLAP & WIRE BASKET
FROM TOP 1/3 OF ROOT BALL. REMOVE
ALL SYNTHETIC ROPES & WRAPPING
MATERIALS.
EXTEND STAKES INTO UNDISTURBED
SOIL.
3' MIN. RADIUSVARIES PER PLAN
FOR TREE BEDS FOR INDIVIDUAL TREES
MIN. 2 x ROOT BALL (TYP)
3" 5'-
0" M
IN
SET FLARE OF ROOT BALL 2" ABOVE
SURROUNDING GRADE. DO NOT PLACE
OR MOUND MULCH AGAINST TREE
TRUNK (TYP).
MIN. 3" DEEP DOUBLE GROUND .
HARDWOOD MULCH (TYP).
FORM 3" SOIL SAUCER AROUND TREE
FINISH GRADE
PRUNE BROKEN, DAMAGED, OR
CROSSING BRANCHES (TYP).
PLANTING SOIL AS SPECIFIED. TAMP
SOIL AROUND ROOT BALL USING FOOT
PRESSURE.
REMOVE BURLAP & WIRE BASKET
FROM TOP 1/3 OF ROOT BALL. REMOVE
ALL SYNTHETIC ROPES & WRAPPING
MATERIALS.
EXTEND STAKES INTO UNDISTURBED
SOIL.
INSTALL HARDWOOD STAKES, (2) PER
TREE W/ RUBBER HOSES & 14ga.
DOUBLE STRANDED TIE WIRE. INSTALL
PERPENDICULAR TO PREVAILING
WINDS OR SLOPES (TYP).
3' MIN. RADIUSVARIES PER PLAN
FOR TREE BEDS FOR INDIVIDUAL TREES
FINISH GRADE
MIN. 2 x ROOT BALL (TYP)
3"
SET FLARE OF ROOT BALL 2" ABOVE
SURROUNDING GRADE. DO NOT PLACE
OR MOUND MULCH AGAINST TREE
TRUNK (TYP).
MIN. 3" DEEP MULCH (TYP).
FORM 3" SOIL SAUCER AROUND
SHRUB OR GATOR BAG
PRUNE BROKEN, DAMAGED, OR
CROSSING BRANCHES (TYP).
PLANTING SOIL. TAMP SOIL AROUND
ROOT BALL USING FOOT PRESSURE.
REMOVE BURLAP & WIRE BASKET
FROM TOP 1/3 OF ROOT BALL. REMOVE
ALL SYNTHETIC ROPES & WRAPPING
MATERIALS.
3' MIN. RADIUSVARIES PER PLAN
FOR PLANT BEDS FOR INDIVIDUAL PLANTS
0' 8' 16' 64'32' 0' 6" 1'3"0' 1' 2'6"0' 2' 4'1'0' 2' 4' 8' 16'0' 4' 8' 16' 32'0' 8' 16' 32' 64'0' 4' 8' 32'16'
Q P
K D
E S
IG
N
S O
U
TH
S A
LI
N
A S
TR
E
E T
S Y
R A
C U
S E
, N E
W Y
O R
K
US Army Corps of Engineers
1 2 3 54
A
B
C
D
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
N
EW
Y O
R K
D
IS
TR
IC
T
SO
LI
C
IT
AT
IO
N
N O
FI
LE
N
AM
E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E:
FI
LE
N U
M
BE
R
SI
ZE
SU
BM
IT
TE
D B
Y:
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
C O
N
TR
AC
T
N O
W
2D S
-1 4-
D -0
2-
FY
FI
R E
S U
P R
E S
S
IO
N S
Y S
TE
M
V A
R
IO
U S
B U
IL
D
IN
G
S W
A
TE
R V
LI
E
T A
R S
E N
A L, N E
W Y
O R
K
WARNING: THIS DOCUMENT MAY CONTAIN SENSITIVE SECURITY INFORMATION AND THEREFORE MUST BE TREATED AS A CONFIDENTIAL DOCUMENT. THE INFORMATION CONTAINED IN THIS DOCUMENT MUST BE MAINTAINED IN A CONFIDENTIAL MANNER TO PREVENT COMPROMISING HOMELAND SECURITY AS PROVIDED IN SECTION 214 OF THE HOMELAND SECURITY ACT OF 2002. NO PART OF THIS DOCUMENT SHALL BE REPRODUCED, RELEASED OR DISTRIBUTED WITHOUT THE EXPRESS WRITTEN PERMISSION OF THE UNITED STATES ARMY CORPS OF ENGINEERS, NEW YORK DISTRICT (USACE - NYD). UNAUTHORIZED REPRODUCTION, RELEASE OR DISTRIBUTION MAY RESULT IN CIVIL PENALTY OR OTHER ACTION BY USACE-NYD.
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
AS
IN
DI
CA
TE
D
X3
6/ 8/
0:
:2
A
M
A-003
JU
LY
5, D es ig ne r
C he ck er
A ut ho r
W A
TE
R
V
LI
E T
A R
S E
N A
L, N
E W
Y O
R K
.0
D
ET
AI
LS
D5 NTS
GRANITE CURB
C5 NTS
CONCRETE CURB
B5 NTS
BOLLARD
A4 NTS
GROUND COVER PLANTING
C4 NTS
DECIDUOUS TREE PLANTING
B4 NTS
EVERGREEN TREE PLANTING
D3 NTS
SHRUB PLANTING
FPS-001
TM
T
R
TK
TM
T
W A
TE
R
V
LI
E T
A R
S E
N A
L, N
E W
Y O
R K
FI
R
E
SE
R
VI
C E
SI
TE
P
LA
N
SCALE:A1 WATER DISTRIBUTION PLAN
AS NOTED
BUILDING 40 NEW 6-INCH FIRE SERVICES
AND POST INDICATOR VALVES
BUILDING 41 NEW 6-INCH FIRE
SERVICE AND POST INDICATOR VALVE
BUILDING 108 NEW 6-INCH FIRE
SERVICE AND POST INDICATOR VALVE
BUILDING 22 NEW 6-INCH FIRE
SERVICE AND POST INDICATOR VALVE.
PROVIDE BOLLARDS.
US Army Corps of Engineers
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
1 2 3 54
A
B
C
D
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
N
EW
Y O
R K
D
IS
TR
IC
T
SO
LI
C
IT
AT
IO
N
N O
FI
LE
N
AM
E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E:
FI
LE
N U
M
BE
R
SI
ZE
SU
BM
IT
TE
D B
Y:
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
C O
N
TR
AC
T
N O
WARNING: THIS DOCUMENT MAY CONTAIN SENSITIVE SECURITY INFORMATION AND THEREFORE MUST BE TREATED AS A CONFIDENTIAL DOCUMENT. THE INFORMATION CONTAINED IN THIS DOCUMENT MUST BE MAINTAINED IN A CONFIDENTIAL MANNER TO PREVENT COMPROMISING HOMELAND SECURITY AS PROVIDED IN SECTION 214 OF THE HOMELAND SECURITY ACT OF 2002. NO PART OF THIS DOCUMENT SHALL BE REPRODUCED, RELEASED OR DISTRIBUTED WITHOUT THE EXPRESS WRITTEN PERMISSION OF THE UNITED STATES ARMY CORPS OF ENGINEERS, NEW YORK DISTRICT (USACE - NYD). UNAUTHORIZED REPRODUCTION, RELEASE OR DISTRIBUTION MAY RESULT IN CIVIL PENALTY OR OTHER ACTION BY USACE-NYD.
W
2D S
-1 4-
D -0
/4
/2
A
S S
H O
W N
"x
G H
D C on su lti ng
S er vi ce s In c.
JU
LY
5, Q P
K D
E S
IG
N
S O
U
TH
S A
LI
N
A S
TR
E
E T
S Y
R A
C U
S E
, N E
W Y
O R
K
W
2D S
-1 4-
D -0
2-
FY
F
IR
E S
U P
P R
E S
S
IO
N S
Y S
TE
M
V A
R
IO
U S
B U
IL
D
IN
G
S W
A
TE
R V
LI
E
T A
R S
E N
A L, N E
W Y
O R
K
.0
BUILDING 126 EXISTING
6-INCH FIRE SERVICE
US Army Corps of Engineers
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
1 2 3 54
A
B
C
D
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
N
EW
Y O
R K
D
IS
TR
IC
T
SO
LI
C
IT
AT
IO
N
N O
FI
LE
N
AM
E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E:
FI
LE
N U
M
BE
R
SI
ZE
SU
BM
IT
TE
D B
Y:
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
C O
N
TR
AC
T
N O
WARNING: THIS DOCUMENT MAY CONTAIN SENSITIVE SECURITY INFORMATION AND THEREFORE MUST BE TREATED AS A CONFIDENTIAL DOCUMENT. THE INFORMATION CONTAINED IN THIS DOCUMENT MUST BE MAINTAINED IN A CONFIDENTIAL MANNER TO PREVENT COMPROMISING HOMELAND SECURITY AS PROVIDED IN SECTION 214 OF THE HOMELAND SECURITY ACT OF 2002. NO PART OF THIS DOCUMENT SHALL BE REPRODUCED, RELEASED OR DISTRIBUTED WITHOUT THE EXPRESS WRITTEN PERMISSION OF THE UNITED STATES ARMY CORPS OF ENGINEERS, NEW YORK DISTRICT (USACE - NYD). UNAUTHORIZED REPRODUCTION, RELEASE OR DISTRIBUTION MAY RESULT IN CIVIL PENALTY OR OTHER ACTION BY USACE-NYD.
W
2D S
-1 4-
D -0
/4
/2
A
S S
H O
W N
"x
G H
D C on su lti ng
S er vi ce s In c.
JU
LY
5, Q P
K D
E S
IG
N
S O
U
TH
S A
LI
N
A S
TR
E
E T
S Y
R A
C U
S E
, N E
W Y
O R
K
W
2D S
-1 4-
D -0
2-
FY
F
IR
E S
U P
P R
E S
S
IO
N S
Y S
TE
M
V A
R
IO
U S
B U
IL
D
IN
G
S W
A
TE
R V
LI
E
T A
R S
E N
A L, N E
W Y
O R
K
.0
FP-001
B
0-
F P
-1
.d w g
S
TB
S
TB
R
TK
M
IS
C . D
E
TA
IL
S
WHEN DISTANCE BETWEEN
JOINT AND WALL IS LESS THAN
10 FT., THE NEXT LENGTH OF
EXTERIOR PIPE SHALL BE
ANCHORED
5'-6"MIN
STANDARD
SLEEVE
RESTRAINED
JOINT
FINISHED
GRADE
1'-0"
3/4" ALL THREAD GALVANIZED
ROD THRU WALL WITH 3"X3"
X1/4" STEEL PLATE, 2 NUTS &
WASHER-ALL WITH 2 COATS
BITUMASTIC. (TYPICAL)
MALLEABLE IRON LUGS
RESTRAINED MECHANICAL
JOINT ELBOW
TO FIRE PROTECTION SYSTEM
FINISHED FLOOR
BITUMASTIC FORMING BOARD
FLANGED CONNECTION
DUCTILE IRON PIPE
NO SCALE
FIRE SERVICE LEAD-IN
VALVE
FIRE SERVICE
FINISHED GRADE
CONDUIT AND WIRING (BY DIV.26)
POST INDICATOR VALVE
WITH TAMPER SWITCH W/
FIRE ALARM MONITOR
MODULE, WRENCH AND
LOCK.
5'-6"
36" (±)
FM
UL
OPEN
2'-0"
NO SCALE
POST INDICATOR VALVE
3/4" ALL THREAD
GALVANIZED ROD THRU
WALL WITH 3"x3"x1/4"
STEEL PLATE, 2 NUTS
AND WASHER WITH 2
COATS BITUMASTIC.
TYPICAL OF TWO.
CONCRETE GROUT
AT RODS (TYPICAL)
TO FIRE
PROTECTION
SYSTEM
FINISHED FLOOR
AS REQUIRED
MALLEABLE IRON
LUGS AT FLANGE
FINISHED FLOOR
FLANGED ELBOW
BUILDING
FOUNDATION WALL
BASE ELBOW ANCHORED
TO CONCRETE BASE
RESTRAINED JOINT
WATERPROOF SLEEVE
AND SEALING ELEMENT
FINISHED GRADE
5'-6" MIN.
4"4"
WHEN DISTANCE BETWEEN
JOINT AND WALL IS LESS
THAN 10FT. THE NEXT
LENGTH OF EXTERIOR PIPE
SHALL BE ANCHORED
NO SCALE
FIRE PROTECTION LEAD-IN
FIRE PROTECTION SYMBOL LIST
RISER CHECK VALVE
CHECK VALVE
DOUBLE CHECK VALVE BACKFLOW PREVENTER ASSEMBLY
SUPERVISED CONTROL VALVE
QUICK-RESPONSE UPRIGHT SPRINKLER
DRY PENDENT SPRINKLER
ELECTRIC WATERFLOW ALARM BELL
ELBOW DOWN
TEE CONNECTION DOWN
CAP OR PLUG
STANDARD RESPONSESR
QUICK-RESPONSE SIDEWALL SPRINKLER
SPB SPRINKLER BRANCH LINE
SM SPRINKLER MAIN
SP MISC. SPRINKLER PIPE
BALL VALVE
FLOW SWITCH
2 12" HOSE VALVE W/ ADAPTER FOR SYRACUSE THREAD
RESIDENTIAL PENDENT SPRINKLER WITH GUARD
OR RESIDENTIAL UPRIGHT (NO GUARD)
INTERMEDIATE TEMPIT
QUICK-RESPONSE UPRIGHT SPRINKLER ABOVE CEILING
WET-PIPE SPRINKLER MAINS
DRY-PIPE SPRINKLER MAINDS
DRAIND
QUICK-RESPONSE DRY SIDEWALL SPRINKLER
DS
FIRE DEPARTMENT CONNECTION
QUICK-RESPONSE PENDENT SPRINKLER
PIT SPRINKLER FEED PIPING
UPRIGHT SPRINKLER WATERFLOW ALARM
GENERAL NOTES:
A. ABOVE DRAIN DETAIL IS APPLICABLE TO BUILDING 121, 136
B. LOCATE AND ANCHOR AT COLUMN OR AT WALL
NO SCALE
DRY FIRE SYSTEM AUXILIARY DRAIN
1" BRASS PLUG
7' MAX. ABOVE
FINISHED FLOOR
1" BALL VALVE
2"x12" PIPE NIPPLE
FROM DRY SYSTEM
LOW POINT
1" BALL VALVE
1" PIPE NIPPLE
CL
24"
FINISHED
FLOOR
1" THICK 24"x24" CONCRETE
SPLASH BLOCK
1"-45° ELBOW. SMOOTH
BORE, CORROSION
RESISTANT OUTLET GIVING
FLOW EQUIVALENT TO ONE
SPRINKLER.
FINISHED
GRADE/ROOF
TEMPORARY CONNECTION
PLUG VALVE END WHEN
NOT IN USE
1"BALL VALVE
1" SIGHT GLASS
WET SYSTEM
1" VALVE NOT OVER 7'-0"
ABOVE FINISHED FLOOR
BRANCH LINE
RETURN BEND FOR DRY OR
PREACTION SYSTEM
EXTERIOR BUILDING WALL
CAULKING SEALANT
NO SCALE
INSPECTOR TEST DETAIL
DRY OR PREACTION SYSTEMS
CONNECT NEW TO EXISTING
POST INDICATOR VALVE
TAMPER SWITCH
PRESSURE SWITCH
PIV
DS
TS
PIPE SECTION
WF
PS
LOW PRESSURE SUPERVISORY ALARM SWITCHLP
AIR COMPRESSORAC
FP-001
FP-001
FP-001
FP-001 5
FP-001
NO SCALE
UTILITY TRENCH DETAIL
SCHEDULE B - LOCATOR TAPE IDENTIFICATION
SCHEDULE A - MINIMUM DEPTH OF COVER OVER UTILITY
UTILITY
GAS, OIL, ELECTRIC
WATER
SANITARY,STORM
UTILITY
GAS, OIL
WATER
ELECTRIC
SANITARY, STORM
SAND BEDDING
COMPACTED BACKFILL
DEPTH OF COVER
(SEE SCHEDULE "A")
LOCATOR TAPE
(SEE SCHEDULE "B")
DEPTH
24" 66"
AS INDICATED
TAPE COLOR
YELLOW
BLUE
RED
GREEN
6" MIN.
6" MIN.
6"6"
UNDISTURBED
EARTH
PIPE, CABLE,
OR CONDUIT.
GRADE - PAVEMENT
OR OTHER SURFACE
WHERE PAVED, SAW CUT
EXISTING PAVEMENT ALONG
STRAIGHT LINES. PATCH ALL
SURFACES TO MATCH
EXISTING.
US Army Corps of Engineers
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
1 2 3 54
A
B
C
D
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
N
EW
Y O
R K
D
IS
TR
IC
T
SO
LI
C
IT
AT
IO
N
N O
FI
LE
N
AM
E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E:
FI
LE
N U
M
BE
R
SI
ZE
SU
BM
IT
TE
D B
Y:
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
C O
N
TR
AC
T
N O
WARNING: THIS DOCUMENT MAY CONTAIN SENSITIVE SECURITY INFORMATION AND THEREFORE MUST BE TREATED AS A CONFIDENTIAL DOCUMENT. THE INFORMATION CONTAINED IN THIS DOCUMENT MUST BE MAINTAINED IN A CONFIDENTIAL MANNER TO PREVENT COMPROMISING HOMELAND SECURITY AS PROVIDED IN SECTION 214 OF THE HOMELAND SECURITY ACT OF 2002. NO PART OF THIS DOCUMENT SHALL BE REPRODUCED, RELEASED OR DISTRIBUTED WITHOUT THE EXPRESS WRITTEN PERMISSION OF THE UNITED STATES ARMY CORPS OF ENGINEERS, NEW YORK DISTRICT (USACE - NYD). UNAUTHORIZED REPRODUCTION, RELEASE OR DISTRIBUTION MAY RESULT IN CIVIL PENALTY OR OTHER ACTION BY USACE-NYD.
W
2D S
-1 4-
D -0
/4
/2
A
S S
H O
W N
"x
G H
D C on su lti ng
S er vi ce s In c.
JU
LY
5, Q P
K D
E S
IG
N
S O
U
TH
S A
LI
N
A S
TR
E
E T
S Y
R A
C U
S E
, N E
W Y
O R
K
W
2D S
-1 4-
D -0
2-
FY
F
IR
E S
U P
P R
E S
S
IO
N S
Y S
TE
M
V A
R
IO
U S
B U
IL
D
IN
G
S W
A
TE
R V
LI
E
T A
R S
E N
A L, N E
W Y
O R
K
.0
FP-002
B
0-
F P
-1
.d w g
S
TB
S
TB
R
TK
M
IS
C . D
E
TA
IL
S
NO SCALE
FIRE PROTECTION RISER DETAIL - BUILDING 22, 41 & 108
GENERAL NOTES:
A. ABOVE DETAIL IS APPLICABLE TO BUILDING 22, 41 AND 108.
B. ABOVE DETAIL IS FOR GENERAL ARRANGEMENT OF VALVES AND ASSOCIATED EQUIPMENT. REFER TO FLOOR PLANS FOR
LOCATIONS OF INCOMING SERVICES.
C. ALL POWER SUPPLIES, WIRING, AND CONNECTIONS FOR TAMPER SWITCHES, FLOW SWITCH AND ELECTRIC ALARM BELLS TO FIRE
ALARM SYSTEM SHALL BE BY DIVISION 26.
TERMINATE 2" MAIN DRAIN AT FLOOR SINK
WITHIN FIRE SERVICE ROOM
2" MAIN DRAIN (TYPICAL)
RISER CHECK VALVE (TYPICAL)
WATER PRESS. GAUGES
(TYPICAL)
CONTROL VALVE WITH TAMPER
SWITCH W/ FIRE ALARM MONITOR
MODULE (TYPICAL)
DRY PIPE VALVE WITH
TRIM (TYPICAL)
3/4"
FIRE PROTECTION TANK-MOUNTED AIR
COMPRESSOR
AIR PRESSURE GAUGE
LOW AIR PRESSURE SUPERVISORY SWITCH
W/ FIRE ALARM MONITOR MODULE (TYPICAL)
AUTO AIR MAINTENANCE
DEVICE (TYPICAL)
WATER
PRESSURE
GAUGE
WATERFLOW
PRESSURE
SWITCH W/
FIRE ALARM
MONITOR
MODULE
(TYPICAL)
FLOW SWITCH
W/ FIRE ALARM
MONITOR
MODULE(TYPICAL)
TO FIRE
DEPARTMENT
CONNECTION
FIRE SERVICE
FROM WATER
SUPPLY
DOUBLE CHECK VALVE
BACKFLOW PREVENTER
ASSEMBLY (WATTS 774
OR APPROVED EQUAL).
DRAINAGE SHALL BE
PROVIDED TO HANDLE
THE FULL CAPACITY OF
DISCHARGE.
FINISHED
GRADE
1/2" CONDUIT BY DIV. 26
TO WET
SPRINKLER
SYSTEM
TO DRY SPRINKLER
SYSTEMELECTRIC WATERFLOW
ALARM BELL
APPROX. 10' ABOVE
FINISHED GRADE
TO WALL HYDRANT
NORMALLY CLOSED
AI
R
STEEL BRAIDED
CONNECTION
COALESCING
FILTER
MANUAL
DESICCANT
DRYER
ELECTRIC WATERFLOW
ALARM BELL
APPROX. 10' ABOVE
FINISHED GRADE
GENERAL NOTES:
A. ABOVE DETAIL IS APPLICABLE TO BUILDINGS 36, 40-5, 40-6 & 126.
B. ABOVE DETAIL IS FOR GENERAL ARRANGEMENT OF VALVES AND ASSOCIATED EQUIPMENT. REFER TO
FLOOR PLANS FOR LOCATIONS OF INCOMING SERVICES.
C. ALL POWER SUPPLIES, WIRING, AND CONNECTIONS FOR TAMPER SWITCHES, FLOW SWITCH AND
ELECTRIC ALARM BELLS TO FIRE ALARM SYSTEM SHALL BE BY DIVISION 26.
TO WET
SPRINKLER
SYSTEM ZONE
TERMINATE 2" MAIN
DRAIN AT NEAREST FLOOR
DRAIN OR TO EXTERIOR
2" MAIN DRAIN (TYPICAL)
RISER CHECK
VALVE (TYPICAL)
WATER PRESS.
GAUGES (TYPICAL)
CONTROL VALVE WITH TAMPER
SWITCH W/ FIRE ALARM
MONITOR MODULE (TYPICAL)
TO WET SPRINKLER
SYSTEM ZONE
CONTINUED TO
FIRE PROTECTION
SITE WATER
SUPPLY
FLOW
SWITCH W/
FIRE ALARM
MONITOR
MODULE
(TYPICAL)
TO FIRE
DEPARTMENT
CONNECTION
1/2" CONDUIT BY DIV. 26
DOUBLE CHECK VALVE BACKFLOW
PREVENTER ASSEMBLY. DRAINAGE SHALL
BE PROVIDED TO HANDLE THE FULL
CAPACITY OF DISCHARGE.
6" CAP FOR
FUTURE
FINISHED
GRADE
NO SCALE
FIRE PROTECTION RISER DETAIL - BUILDINGS 36, 40-5, 40-6 & 1261
FP-002
FP-002
NOTES:
1. ALL VALVES AND TEES SHALL BE RESTRAINED JOINT.
2. CONTRACTOR SHALL CONFIRM EXISTING PIPE O.D. PRIOR TO
THE CUTTING OF ANY EXISTING PIPE.
24" MIN SPOOL PIECE (TYP.)
D.I.P. SOLID SLEEVE
D.I.P. SOLID SLEEVE
EXISTING D.I.P/C.I./P.V.C.
WATERMAIN
EXISTING WATERMAIN
MECHANICAL
JOINT RESTRAINT
MECHANICAL
JOINT RESTRAINT
TEE CONNECTION TO EXISTING WATER MAIN
NOT TO SCALE
24" MIN SPOOL PIECE (TYP.)
NEW FIRE SERVICE
THRUST BLOCK
GRADE
CONCRETE
THRUST BLOCK
CONCRETE
THRUST BLOCK
UNDISTURBED EARTH
UNDISTURBED EARTH
PIPELINE
TEE
TEE
POLYETHYLENE
BARRIER
PLAN SECTION
'L'
'H
'L'
'L'
HORIZONTAL THRUST BLOCK FOR TEES
NOT TO SCALE
MECHANICAL JOINT
RESTRAINT
12" 1'-4" 1'-0"
16" 4'-8"14" 4'-0" 2'-8" 2'-0"
5'-4"
8" 6"
2'-8" 2'-4" 2'-0"
UP TO 150 P.S.I. WORKING PRESSURE
H L
PLUG, CAP, TEE OR
TAP SLEEVEPIPE
SIZE
HORIZONTAL ANCHOR DIMENSIONS
FOR AVERAGE SOIL CONDITIONS
NOTES:
1. SIZES BASED ON 150 PSI PRESSURE IN PIPELINE AND 2,000 PSF SOIL BEARING STRENGTH.
2. ALL EXPOSED PORTIONS OF ANCHOR STRAPS TO RECEIVE A MINIMUM OF 2 FIELD COATS OF BITUMASTIC MATERIAL.
3. PRIOR TO PLACING CONCRETE WRAP ANCHORS & ALL FITTINGS IN 8-MIL THICK POLYTHENE.
4. ALL ANCHOR RODS SHALL BE TYPE 304 STAINLESS STEEL.
THRUST BLOCK HORIZONTAL
NOT TO SCALE
GENERAL NOTES:
1. CONTRACTOR IS REQUIRED TO OBTAIN ALL NECESSARY PERMITS BEFORE STARTING WORK.
2. CONTRACTOR IS RESPONSIBLE TO PROVIDE EROSION AND SEDIMENT CONTROL IN ACCORDANCE WITH APPROPRIATE SPECIFICATION SECTIONS. CONTRACTOR SHALL OBTAIN ANY AND ALL NECESSARY PERMITS ASSOCIATED WITH EROSION AND SEDIMENT CONTROL, AND SHALL BE RESPONSIBLE TO PAY ANY FINES ASSOCIATED WITH
IMPROPER EROSION AND SEDIMENT CONTROL.
3. THE CONTRACTOR SHALL CONDUCT THE SITE WORK IN A SAFE MANNER AND WITH MINIMUM AMOUNT OF INCONVENIENCE TO TRAFFIC.
4. THE CONTRACTOR SHALL REPAIR ALL DRIVEWAYS, DRIVEWAY PIPES, CURB AND GUTTER, SIDEWALKS AND STREETS TO EXISTING CONDITION OR BETTER.
5. ALL AREAS DISTURBED DURING CONSTRUCTION SHALL BE RESTORED TO A CONDITION EQUAL TO THAT WHICH EXISTED PRIOR TO CONSTRUCTION UNLESS NOTED
OTHERWISE.
6. CONTRACTOR SHALL PROVIDE POSITIVE SITE DRAINAGE DURING CONSTRUCTION OPERATIONS. ALL FINAL LINES AND GRADES SHALL BE CONSTRUCTED TO MAINTAIN
POSITIVE SITE DRAINAGE TO EXISTING DRAINAGE STRUCTURES.
7. CONTRACTOR SHALL COORDINATE STAGING AREAS WITH OWNER.
8. LOCATIONS OF MAINLINE UTILITIES OR INDIVIDUAL SERVICES ARE NOT SHOWN ON DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING LOCATION AND DEPTH OF ALL UTILITIES. CONTRACTOR SHALL ALSO BE RESPONSIBLE FOR DETERMINING LOCATION AND DEPTH OF INDIVIDUAL SERVICES.
9. CONTRACTOR SHALL CONTACT WATERVLIET ARSENAL DEPARTMENT OF PUBLIC WORKS WHEN EXCAVATING IN THE VICINITY OF EXISTING UTILITIES. CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY EXISTING UTILITIES DAMAGED DUE TO HIS OPERATION.
10. CONTRACTOR SHALL SUPPORT AND/OR PROTECT EXISTING SEWER, STORM, WATER MAIN, GAS, OVERHEAD POWER, OR ANY OTHER EXISTING UTILITIES WHERE
NECESSARY, IN ACCORDANCE WITH UTILITY OWNER'S REQUIREMENTS.
11. CONTRACTOR SHALL LOCATE, MARK, SAFEGUARD AND PRESERVE ALL SURVEY CONTROL, R.O.W. MONUMENTS, AND INDIVIDUAL PROPERTY CORNER PINS/MONUMENTS IN THE AREA OF CONSTRUCTION. IF DAMAGED, CONTRACTOR SHALL HAVE SURVEYED AND REPLACED BY A NEW YORK STATE SURVEYOR AT NO ADDITIONAL COST TO THE
OWNER.
12. AN AIR COMPRESSOR SHALL BE PROVIDED FOR ANY BUILDING CONTAINING A DRY PIPE SPRINKLER SYSTEM. THE AIR COMPRESSOR SHALL BE PROVIDED POWER BY THE
CLOSEST BUILDING POWER SOURCE.
13. IN AREAS THAT ARE PROVIDED WITH PENDENT OR SIDEWALL SPRINKLER HEADS, DROPPED, GYPSUM OR ACT, CEILINGS CAN BE ASSUMED TO BE PRESENT. IN AREAS THAT ARE PROVIDED WITH UPRIGHT SPRINKLER HEADS, IT CAN BE ASSUMED NO CEILING IS PRESENT.
14. AREAS THAT HAVE DROPPED, GYPSUM OR ACT, CEILINGS THAT ARE BEING PROVIDED WITH PENDENT SPRINKLERS SHALL ALSO BE PROVIDED WITH CONCEALED SPRINKLER PIPING. AREAS THAT HAVE NO CEILINGS THAT ARE BEING PROVIDED WITH UPRIGHT SPRINKLERS SHALL BE PROVIDED WITH EXPOSED SPRINKLER PIPING.
SM
SPB
SPB
SPB
SPB
SMSM
SPB
SPB
SPB
SPBSP
B
SM
SPB
SPB
SPB
SPB
SPB
SPB
SMSMSM
SPB SPB
SPB
SPB
SP
B
SMSMSMSMSMSM
SPB
SPB
SP
B
SPB
SPB
SP
B
SP
B
SPB
SP
B
SP
B
BASEMENT AREA BELOW
SPB
SM
SPBSPB
SPB
SPB
SM
SPB
SPB
SPB
SPB
SPB
SPB
SPB
SM
SM
SPB
SPB
SPB
SPB
SM
SPBSM
SM
SM
SM
PIV
US Army Corps of Engineers
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
1 2 3 54
A
B
C
D
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
N
EW
Y O
R K
D
IS
TR
IC
T
SO
LI
C
IT
AT
IO
N
N O
FI
LE
N
AM
E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E:
FI
LE
N U
M
BE
R
SI
ZE
SU
BM
IT
TE
D B
Y:
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
C O
N
TR
AC
T
N O
WARNING: THIS DOCUMENT MAY CONTAIN SENSITIVE SECURITY INFORMATION AND THEREFORE MUST BE TREATED AS A CONFIDENTIAL DOCUMENT. THE INFORMATION CONTAINED IN THIS DOCUMENT MUST BE MAINTAINED IN A CONFIDENTIAL MANNER TO PREVENT COMPROMISING HOMELAND SECURITY AS PROVIDED IN SECTION 214 OF THE HOMELAND SECURITY ACT OF 2002. NO PART OF THIS DOCUMENT SHALL BE REPRODUCED, RELEASED OR DISTRIBUTED WITHOUT THE EXPRESS WRITTEN PERMISSION OF THE UNITED STATES ARMY CORPS OF ENGINEERS, NEW YORK DISTRICT (USACE - NYD). UNAUTHORIZED REPRODUCTION, RELEASE OR DISTRIBUTION MAY RESULT IN CIVIL PENALTY OR OTHER ACTION BY USACE-NYD.
W
2D S
-1 4-
D -0
/4
/2
A
S S
H O
W N
"x
G H
D C on su lti ng
S er vi ce s In c.
JU
LY
5, Q P
K D
E S
IG
N
S O
U
TH
S A
LI
N
A S
TR
E
E T
S Y
R A
C U
S E
, N E
W Y
O R
K
W
2D S
-1 4-
D -0
2-
FY
F
IR
E S
U P
P R
E S
S
IO
N S
Y S
TE
M
V A
R
IO
U S
B U
IL
D
IN
G
S W
A
TE
R V
LI
E
T A
R S
E N
A L, N E
W Y
O R
K
.0
FP-100
B
0-
F P
-1
.d w g
TM
T
TM
T
R
TK
TRU
E
NO
RTH
0 4'-0" 16'-0"
SCALE 1/8"=1'-0" AT ORIGINAL SIZE
8'-0" 12'-0"
GENERAL NOTES:
A. PROVIDE A COMPLETE AUTOMATIC WET AND DRY PIPE SPRINKLER
SYSTEM IN ACCORDANCE WITH NFPA 13-2016 AND UFC 3-600-01 FOR
BUILDING 22.
B. PIPING AS SHOWN IS DIAGRAMMATIC, NOT ALL PIPING/FITTINGS ARE
INDICATED. CONTRACTOR IS RESPONSIBLE FOR FINAL SPRINKLER
SYSTEM PIPE SIZING/LAYOUT, SPRINKLER HYDRAULIC CALCULATIONS,
AND COORDINATION WITH LIGHTS FIXTURES/FIRE ALARM DEVICES,
DUCTWORK AND DIFFUSERS.
C. FINAL PIPE SIZING SHALL BE DETERMINED BY CONTRACTOR HYDRAULIC
CALCULATIONS SUBJECT TO APPROVAL BY ENGINEER.
D. SPRINKLER DESIGN CRITERIA IS AS FOLLOWS:
1. ORDINARY HAZARD: 0.20 GPM/SQ.FT. OVER 2500 SQ.FT., 250 GPM
HOSE STREAM DEMAND.
2. ATTIC: 0.20 GPM/SQ.FT. OVER 3250 SQ.FT., 250 GPM HOSE STREAM
DEMAND.
E. FIRE STOP ALL PENETRATIONS THROUGH RATED WALLS, FLOORS, AND
CEILINGS.
F. PIPING SHALL BE INSTALLED CONCEALED ABOVE FINISHED CEILINGS, I.E.
GYP, ACT.
G. PIPING SHALL BE INSTALLED EXPOSED ONLY IN UNFINISHED CEILING
SPACES, I.E. MECH/ELEC/STORAGE ROOMS, STAIRWELLS, ETC.
H. ALL PIPE SIZES 2" AND SMALLER SHALL BE SCHEDULE 40 BLACK STEEL
WITH THREADED FITTINGS. PIPE SIZES LARGER THAN 2" ARE PERMITTED
TO BE SCHEDULE 10 BLACK STEEL WITH ROLL-GROOVED PIPE COUPLINGS.
I. SPRINKLERS SHALL BE LOCATED A MINIMUM OF 24 INCHES FROM SIDE OF
HVAC DIFFUSERS.
J. FIRE ALARM CONTROL PANEL LOCATED IN THE BASEMENT.
STATIC PRESSURE: 54 PSI
RESIDUAL PRESSURE: 47 PSI
FLOW: 1130 GPM
DATE: 3/20/2017
HYDRANTS: NORTH OF BUILDING 135
HYDRANT FLOW
TEST INFORMATION
SCALE: 1/8" � 1'-0"A2 FLOOR PLAN - BASEMENT
B U
IL
D
IN
G
R
E G
U
LA
TO
R
Y P
LA
N
S
B S
M T
S T
FL
R
S
SCALE: 1/8" � 1'-0"C1 PARTIAL FLOOR PLAN - FIRST FLOOR
SCALE: 1/8" � 1'-0"A4 PARTIAL FLOOR PLAN - FIRST FLOOR
4" UP&DN
DOWN FROM ATTIC
DRY SPRINKLER
SYSTEM
6" CONTINUE TO
WATER MAIN
4" UP TO WET SPRINKLER ZONE
4" UP TO DRY SPRINKLER ATTIC ZONE
4" UP TO DRY SPRINKLER ATTIC ZONE
4" UP TO WET SPRINKLER ZONE
4" DN
4"
4"
4"
4"
4"
4"4"
CHASE SHALL BE
PROVIDED
4" FDC (COORDINATE FITTING
WITH FIRE DEPARTMENT)
CHASE SHALL BE
PROVIDED
4" DOUBLE CHECK VALVE
BACKFLOW PREVENTER ASSEMBLY
(SEE DETAIL 1 ON DRAWING FP-002)
6" POST INDICATOR VALVE (SEE
DETAIL 3 ON DRAWING FP-001)
WF
TSTS
4"
4" UP TO FDC
AC
TS
WATERFLOW
ALARM BELL
PS
LPTS
1" FEEDS 1 SPRINKLER
4" FEEDS 3 SPRINKLERS
2" FEEDS 5 SPRINKLERS
2" FEEDS 10 SPRINKLERS
SPRINKLER BRANCH PIPE SIZING TABLE
FOR USE IN HYDRAULIC CALCULATIONS
(UNLESS NOTED OTHERWISE)
DOWN TO INSPECTOR TEST CONNECTION & AUXILIARY
DRAIN (SEE DETAIL 5 ON DRAWING FP-001)
KEYED NOTES
PROVIDE CIRCUIT OT AIR COMPRESSOR AS FOLLOWS:
· SOURCE: NEAREST 208/120 VAC PANELBOARD, PROVIDE 20A, 1P CIRCUIT
BREAKER TO MATCH EXISTING. IF SUITABLE SPARE BREAKER EXIST, IT MAY
BE USED. NEATLY REVISE PANEL DIRECTORY TO REFLECT ADDED CIRCUIT.
· BRANCH CIRCUIT: PROVIDE 2#12, #12 GROUND IN 12" EMT CONDUIT AS
SPECIFIED. EXTEND FROM PANEL TO AIR COMPRESSOR LOCATION.
· DISCONNECT: PROVIDE 30A-2P HEAVY DUTY 208V DISCONNECT, UTILIZE 1
POLE FOR "HOT" CONDUCTOR. MOUNT ADJACENT TO COMPRESSOR.
PROVIDE NAMEPLATE, "COMPRESSOR DISCONNECT".
· TERMINATION: PROVIDE 12" SEALTIGHT FROM DISCONNECT TO
COMPRESSOR CONNECTION POINT. PROVIDE 2#12, #12 GROUND
STRANDED CONDUCTOR AND TERMINATE IN COMPRESSOR ELECTRICAL
BOX.
· CONTROL: PROVIDE SEPARATE SYSTEM FOR CONTROL FUNCTION.
SEE DETAIL 1 ON DRAWING FP-001
FOR FIRE SERVICE LEAD-IN
M
AT
CH
L
IN
E
M
AT
CH
L
IN
E
ATTIC
SMSMSMSMSMSM
SMSMSMSMSMSM
SM
SM
SM
ATTIC
M
AT
CH
L
IN
E
M
AT
CH
L
IN
E
SMSMSMSMSMSMSMSMSMSMSMSMSMSM
SMSMSMSMSMSMSMSMSMSMSMSMSMSM
SM
SM
US Army Corps of Engineers
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
1 2 3 54
A
B
C
D
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
N
EW
Y O
R K
D
IS
TR
IC
T
SO
LI
C
IT
AT
IO
N
N O
FI
LE
N
AM
E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E:
FI
LE
N U
M
BE
R
SI
ZE
SU
BM
IT
TE
D B
Y:
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
C O
N
TR
AC
T
N O
WARNING: THIS DOCUMENT MAY CONTAIN SENSITIVE SECURITY INFORMATION AND THEREFORE MUST BE TREATED AS A CONFIDENTIAL DOCUMENT. THE INFORMATION CONTAINED IN THIS DOCUMENT MUST BE MAINTAINED IN A CONFIDENTIAL MANNER TO PREVENT COMPROMISING HOMELAND SECURITY AS PROVIDED IN SECTION 214 OF THE HOMELAND SECURITY ACT OF 2002. NO PART OF THIS DOCUMENT SHALL BE REPRODUCED, RELEASED OR DISTRIBUTED WITHOUT THE EXPRESS WRITTEN PERMISSION OF THE UNITED STATES ARMY CORPS OF ENGINEERS, NEW YORK DISTRICT (USACE - NYD). UNAUTHORIZED REPRODUCTION, RELEASE OR DISTRIBUTION MAY RESULT IN CIVIL PENALTY OR OTHER ACTION BY USACE-NYD.
W
2D S
-1 4-
D -0
/4
/2
A
S S
H O
W N
"x
G H
D C on su lti ng
S er vi ce s In c.
JU
LY
5, Q P
K D
E S
IG
N
S O
U
TH
S A
LI
N
A S
TR
E
E T
S Y
R A
C U
S E
, N E
W Y
O R
K
W
2D S
-1 4-
D -0
2-
FY
F
IR
E S
U P
P R
E S
S
IO
N S
Y S
TE
M
V A
R
IO
U S
B U
IL
D
IN
G
S W
A
TE
R V
LI
E
T A
R S
E N
A L, N E
W Y
O R
K
.0
FP-101
B
0-
F P
-1
.d w g
TM
T
TM
T
R
TK
TRU
E
NO
RTH
0 4'-0" 16'-0"
SCALE 1/8"=1'-0" AT ORIGINAL SIZE
8'-0" 12'-0"
GENERAL NOTES:
A. PROVIDE A COMPLETE AUTOMATIC DRY PIPE SPRINKLER SYSTEM IN
ACCORDANCE WITH NFPA 13-2016 FOR BUILDING 22 ATTIC.
B. PIPING AS SHOWN IS DIAGRAMMATIC, NOT ALL PIPING/FITTINGS ARE
INDICATED. CONTRACTOR IS RESPONSIBLE FOR FINAL SPRINKLER
SYSTEM PIPE SIZING/LAYOUT, SPRINKLER HYDRAULIC CALCULATIONS,
AND COORDINATION WITH LIGHTS FIXTURES/FIRE ALARM DEVICES,
DUCTWORK AND DIFFUSERS.
C. FINAL PIPE SIZING SHALL BE DETERMINED BY CONTRACTOR HYDRAULIC
CALCULATIONS SUBJECT TO APPROVAL BY ENGINEER.
D. SPRINKLER DESIGN CRITERIA IS AS FOLLOWS:
1. ORDINARY HAZARD: 0.20 GPM/SQ.FT. OVER 2500 SQ.FT., 250 GPM
HOSE STREAM DEMAND.
2. ATTIC: 0.20 GPM/SQ.FT. OVER 3250 SQ.FT., 250 GPM HOSE STREAM
DEMAND.
E. FIRE STOP ALL PENETRATIONS THROUGH RATED WALLS, FLOORS, AND
CEILINGS.
F. PIPING SHALL BE INSTALLED CONCEALED ABOVE FINISHED CEILINGS, I.E.
GYP, ACT.
G. PIPING SHALL BE INSTALLED EXPOSED ONLY IN UNFINISHED CEILING
SPACES, I.E. MECH/ELEC/STORAGE ROOMS, STAIRWELLS, ETC.
H. ALL PIPE SIZES 2" AND SMALLER SHALL BE SCHEDULE 40 BLACK STEEL
WITH THREADED FITTINGS. PIPE SIZES LARGER THAN 2" ARE PERMITTED
TO BE SCHEDULE 10 BLACK STEEL WITH ROLL-GROOVED PIPE COUPLINGS.
I. SPRINKLERS SHALL BE LOCATED A MINIMUM OF 24 INCHES FROM SIDE OF
HVAC DIFFUSERS.
J. EXISTING ELECTRICAL WIRING MUST NOT BE DRAPED ON SPRINKLER
SYSTEM.
K. CONTRACTOR MAY RELOCATE BRANCH LINES AND SPRINKLERS IF
EXISTING WOOD TRUSSES ARE IN THE WAY.
STATIC PRESSURE: 54 PSI
RESIDUAL PRESSURE: 47 PSI
FLOW: 1130 GPM
DATE: 3/20/2017
HYDRANTS: NORTH OF BUILDING 135
HYDRANT FLOW
TEST INFORMATION
B U
IL
D
IN
G
R
E G
U
LA
TO
R
Y P
LA
N
S
A
TT
IC
P
LA
N
SCALE: 1/8" � 1'-0"C1 PARTIAL FLOOR PLAN - ATTIC
SCALE: 1/8" � 1'-0"A4 PARTIAL FLOOR PLAN - ATTIC
DOWN TO FIRST
FLOOR CLOSET
KEYED NOTES
SPRINKLERS SHALL BE INSTALLED AT ROOF LEVEL AND PIPE SHALL BE SLOPED TO ALLOW FOR APPROPRIATE DRAINAGE.1
4"
4"
4"
4"
4"
4"
4"
4"
4"
DOWN TO APPARATUS BAY DRY SPRINKLERS
1" FEEDS 1 SPRINKLER
4" FEEDS 3 SPRINKLERS
2" FEEDS 5 SPRINKLERS
2" FEEDS 10 SPRINKLERS
SPRINKLER BRANCH PIPE SIZING TABLE
FOR USE IN HYDRAULIC CALCULATIONS
(UNLESS NOTED OTHERWISE)
UP
UNIT 1
LOFT ACCESS
DN
UP
SPRINKLER ZONE 1
SPRINKLER ZONE 2
SM
SM
SPB
SM
SM
SPBSP
B
4"
4"
4"
4"
4"4"
4"4"
PI
V
PIV
DN
STORAGE LOFT
US Army Corps of Engineers
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
1 2 3 54
A
B
C
D
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
N
EW
Y O
R K
D
IS
TR
IC
T
SO
LI
C
IT
AT
IO
N
N O
FI
LE
N
AM
E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E:
FI
LE
N U
M
BE
R
SI
ZE
SU
BM
IT
TE
D B
Y:
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
C O
N
TR
AC
T
N O
WARNING: THIS DOCUMENT MAY CONTAIN SENSITIVE SECURITY INFORMATION AND THEREFORE MUST BE TREATED AS A CONFIDENTIAL DOCUMENT. THE INFORMATION CONTAINED IN THIS DOCUMENT MUST BE MAINTAINED IN A CONFIDENTIAL MANNER TO PREVENT COMPROMISING HOMELAND SECURITY AS PROVIDED IN SECTION 214 OF THE HOMELAND SECURITY ACT OF 2002. NO PART OF THIS DOCUMENT SHALL BE REPRODUCED, RELEASED OR DISTRIBUTED WITHOUT THE EXPRESS WRITTEN PERMISSION OF THE UNITED STATES ARMY CORPS OF ENGINEERS, NEW YORK DISTRICT (USACE - NYD). UNAUTHORIZED REPRODUCTION, RELEASE OR DISTRIBUTION MAY RESULT IN CIVIL PENALTY OR OTHER ACTION BY USACE-NYD.
W
2D S
-1 4-
D -0
/4
/2
A
S S
H O
W N
"x
G H
D C on su lti ng
S er vi ce s In c.
JU
LY
5, Q P
K D
E S
IG
N
S O
U
TH
S A
LI
N
A S
TR
E
E T
S Y
R A
C U
S E
, N E
W Y
O R
K
W
2D S
-1 4-
D -0
2-
FY
F
IR
E S
U P
P R
E S
S
IO
N S
Y S
TE
M
V A
R
IO
U S
B U
IL
D
IN
G
S W
A
TE
R V
LI
E
T A
R S
E N
A L, N E
W Y
O R
K
.0
B
U
IL
D
IN
G
P
A R
TI
A
L
FI
R S
T
FL
O O
R P
LA
N
FP-102
B
0-
F P
-1
.d w g
S
TB
S
TB
R
TK
SCALE: 1/16" � 1'-0"A1 BUILDING 40 - PARTIAL FIRST FLOOR PLAN
PROJECT
NORTH
0 8'-0" 32'-0"16'-0" 24'-0"
SCALE 1/16"=1'-0" AT ORIGINAL SIZE
KEY PLAN
NO SCALE
AREA OF
WORK
6" FIRE SERVICE CONTINUED
TO WATER MAIN
4" FDC (COORDINATE FITTING
WITH FIRE DEPARTMENT)
4" SM UP (SPRINKLER ZONE 1)
4" SM UP (ATTIC
SPRINKLER ZONE)
6" FIRE SERVICE CONTINUED
TO WATER MAIN
4" SM UP (SPRINKLER ZONE 2)
4" SM UP ( ATTIC SPRINKLER ZONE)
4" FDC (COORDINATE FITTING
WITH FIRE DEPARTMENT)
GENERAL NOTES:
A. PROVIDE A COMPLETE AUTOMATIC WET PIPE SPRINKLER SYSTEM IN ACCORDANCE WITH NFPA
13-2016 AND UFC 3-600-01 FOR THE AREA OF WORK INDICATED FOR BUILDING 40.
B. PIPING AS SHOWN IS DIAGRAMMATIC, NOT ALL PIPING/FITTINGS ARE INDICATED. CONTRACTOR IS
RESPONSIBLE FOR FINAL SPRINKLER SYSTEM PIPE SIZING/LAYOUT, FINAL NFPA SPRINKLER
HYDRAULIC CALCULATIONS, AND COORDINATION WITH LIGHTS FIXTURES/FIRE ALARM DEVICES, DUCTWORK AND DIFFUSERS.
C. PIPE SIZES WHERE INDICATED ARE MINIMUM ACCEPTABLE SIZES. FINAL PIPE SIZING SHALL BE
DETERMINED BY CONTRACTOR HYDRAULIC CALCULATIONS SUBJECT TO APPROVAL BY ENGINEER.
D. SPRINKLER DESIGN CRITERIA (WITHOUT FIRE PUMP) IS AS FOLLOWS:
1. ORDINARY HAZARD: 0.20 GPM/SQ.FT. OVER 2500 SQ.FT., 250 GPM HOSE STREAM DEMAND.
F. FIRE STOP ALL PENETRATIONS THROUGH RATED WALLS, FLOORS, AND CEILINGS.
G. PIPING SHALL BE INSTALLED CONCEALED ABOVE FINISHED CEILINGS, I.E. GYP, ACT.
H. PIPING SHALL BE INSTALLED EXPOSED ONLY IN UNFINISHED CEILING SPACES.
I. ALL PIPE SIZES 2" AND SMALLER SHALL BE SCHEDULE 40 BLACK STEEL WITH THREADED FITTINGS.
PIPE SIZES LARGER THAN 2" ARE PERMITTED TO BE SCHEDULE 10 BLACK STEEL WITH
ROLL-GROOVED PIPE COUPLINGS.
J. SPRINKLERS SHALL BE LOCATED A MINIMUM OF 24 INCHES FROM SIDE OF HVAC DIFFUSERS.
COORDINATE FINAL LOCATIONS OF SPRINKLERS WITH MECHANICAL CONTRACTOR PRIOR TO
INSTALLATION.
K. SPRINKLERS SHALL BE OF QUICK-RESPONSE TYPE IN ALL AREAS UNLESS OTHERWISE INDICATED.
1" FEEDS 1 SPRINKLER
4" FEEDS 3 SPRINKLERS
2" FEEDS 5 SPRINKLERS
2" FEEDS 10 SPRINKLERS
SPRINKLER BRANCH PIPE SIZING TABLE
FOR USE IN HYDRAULIC CALCULATIONS
(UNLESS NOTED OTHERWISE)
APPROXIMATE LOCATION OF
ELECTRICAL EQUIPMENT
TS
WF
TS
x2 x2
TSWF
TS
x2 x2
6" POST INDICATOR VALVE
6" POST INDICATOR VALVE
STATIC PRESSURE: 78 PSI
RESIDUAL PRESSURE: 58 PSI
FLOW: 1115 GPM
DATE: 3/20/2017
HYDRANTS: WEST OF BUILDING 40
HYDRANT FLOW
TEST INFORMATION
SEE DETAIL 2 ON
DRAWING FP-002
SEE DETAIL 2 ON DRAWING
FP-001 FOR FIRE SERVICE
LEAD-IN & DETAIL 2 ON
DRAWING FP-002 FOR
RISER DETAIL
TS
TS DOWN TO INSPECTOR TEST CONNECTION
(SEE DETAIL 5 ON DRAWING FP-001)
DOWN TO INSPECTOR TEST CONNECTION
(SEE DETAIL 5 ON DRAWING FP-001)
WATERFLOW ALARM BELL
WATERFLOW ALARM BELL
UP
UNIT 1
SM
SM
SM
SM
SM
4" 4"
4"4"
4"
4"
4"
4" 4"
4"
4"4"4"4"
SPRINKLER ZONE 3
SPRINKLER ZONE 4
4"
4"
DN
STORAGE LOFT
US Army Corps of Engineers
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
1 2 3 54
A
B
C
D
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
N
EW
Y O
R K
D
IS
TR
IC
T
SO
LI
C
IT
AT
IO
N
N O
FI
LE
N
AM
E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E:
FI
LE
N U
M
BE
R
SI
ZE
SU
BM
IT
TE
D B
Y:
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
C O
N
TR
AC
T
N O
WARNING: THIS DOCUMENT MAY CONTAIN SENSITIVE SECURITY INFORMATION AND THEREFORE MUST BE TREATED AS A CONFIDENTIAL DOCUMENT. THE INFORMATION CONTAINED IN THIS DOCUMENT MUST BE MAINTAINED IN A CONFIDENTIAL MANNER TO PREVENT COMPROMISING HOMELAND SECURITY AS PROVIDED IN SECTION 214 OF THE HOMELAND SECURITY ACT OF 2002. NO PART OF THIS DOCUMENT SHALL BE REPRODUCED, RELEASED OR DISTRIBUTED WITHOUT THE EXPRESS WRITTEN PERMISSION OF THE UNITED STATES ARMY CORPS OF ENGINEERS, NEW YORK DISTRICT (USACE - NYD). UNAUTHORIZED REPRODUCTION, RELEASE OR DISTRIBUTION MAY RESULT IN CIVIL PENALTY OR OTHER ACTION BY USACE-NYD.
W
2D S
-1 4-
D -0
/4
/2
A
S S
H O
W N
"x
G H
D C on su lti ng
S er vi ce s In c.
JU
LY
4, Q P
K D
E S
IG
N
S O
U
TH
S A
LI
N
A S
TR
E
E T
S Y
R A
C U
S E
, N E
W Y
O R
K
W
2D S
-1 4-
D -0
2-
FY
F
IR
E S
U P
P R
E S
S
IO
N S
Y S
TE
M
V A
R
IO
U S
B U
IL
D
IN
G
S W
A
TE
R V
LI
E
T A
R S
E N
A L, N E
W Y
O R
K
.0
0%
S U
BM
IS
SI
O
N
B U
IL
D
IN
G
P A
R
TI
A L
A
TT
IC
P
LA
N
FP-103
B
0-
F P
-1
.d w g
S
TB
S
TB
R
TK
SCALE: 1/16" � 1'-0"A1 BUILDING 40 - PARTIAL ATTIC PLAN
PROJECT
NORTH
0 8'-0" 32'-0"16'-0" 24'-0"
SCALE 1/16"=1'-0" AT ORIGINAL SIZE
KEY PLAN
NO SCALE
AREA OF
WORK
4" SM DN (ATTIC
SPRINKLER ZONE)
GENERAL NOTES:
A. PROVIDE A COMPLETE AUTOMATIC WET PIPE SPRINKLER SYSTEM IN ACCORDANCE WITH NFPA
13-2016 AND UFC 3-600-01 FOR THE AREA OF WORK INDICATED FOR BUILDING 40.
B. PIPING AS SHOWN IS DIAGRAMMATIC, NOT ALL PIPING/FITTINGS ARE INDICATED. CONTRACTOR IS
RESPONSIBLE FOR FINAL SPRINKLER SYSTEM PIPE SIZING/LAYOUT, FINAL NFPA SPRINKLER
HYDRAULIC CALCULATIONS, AND COORDINATION WITH LIGHTS FIXTURES/FIRE ALARM DEVICES, DUCTWORK AND DIFFUSERS.
C. PIPE SIZES WHERE INDICATED ARE MINIMUM ACCEPTABLE SIZES. FINAL PIPE SIZING SHALL BE
DETERMINED BY CONTRACTOR HYDRAULIC CALCULATIONS SUBJECT TO APPROVAL BY
ENGINEER.
D. SPRINKLER DESIGN CRITERIA (WITHOUT FIRE PUMP) IS AS FOLLOWS:
1. ORDINARY HAZARD: 0.20 GPM/SQ.FT. OVER 2500 SQ.FT., 250 GPM HOSE STREAM DEMAND.
F. FIRE STOP ALL PENETRATIONS THROUGH RATED WALLS, FLOORS, AND CEILINGS.
G. PIPING SHALL BE INSTALLED CONCEALED ABOVE FINISHED CEILINGS, I.E. GYP, ACT.
H. PIPING SHALL BE INSTALLED EXPOSED ONLY IN UNFINISHED CEILING SPACES.
I. ALL PIPE SIZES 2" AND SMALLER SHALL BE SCHEDULE 40 BLACK STEEL WITH THREADED FITTINGS.
PIPE SIZES LARGER THAN 2" ARE PERMITTED TO BE SCHEDULE 10 BLACK STEEL WITH
ROLL-GROOVED PIPE COUPLINGS.
J. SPRINKLERS SHALL BE LOCATED A MINIMUM OF 24 INCHES FROM SIDE OF HVAC DIFFUSERS.
COORDINATE FINAL LOCATIONS OF SPRINKLERS WITH MECHANICAL CONTRACTOR PRIOR TO
INSTALLATION.
K. SPRINKLERS SHALL BE UPRIGHT TYPE FOR ATTIC SPACE.
1" FEEDS 1 SPRINKLER
4" FEEDS 3 SPRINKLERS
2" FEEDS 5 SPRINKLERS
2" FEEDS 10 SPRINKLERS
SPRINKLER BRANCH PIPE SIZING TABLE
FOR USE IN HYDRAULIC CALCULATIONS
(UNLESS NOTED OTHERWISE)
4" SM DN (ATTIC SPRINKLER ZONE)
STATIC PRESSURE: 78 PSI
RESIDUAL PRESSURE: 58 PSI
FLOW: 1115 GPM
DATE: 3/20/2017
HYDRANTS: WEST OF BUILDING 40
HYDRANT FLOW
TEST INFORMATION
SMSM
SMSP
B
SP
BSP
B
SM SM SM SM SM
SPB
SPB
SPB
SPB
SP
B
SP
B
SP
B
SP
B
SP
B
SPB SPB SPB
SPB
SPB
SPB
SPB
SP
B
SP
B
SP
B
SP
B
SPB SPB SPB
F
SPRINKLER ZONE 1
4"4"4"
4" FDC (COORDINATE FITTING
WITH FIRE DEPARTMENT)
PIV
ELECTRIC WATERFLOW
ALARM BELL
SM
SM
SM
SM
SM
SM
SM
SM
SM
SM
SM SM SM SM SM SM
SM SM SM SM SM SM SM SM SM
SM
4" SM DN ATTIC (SPRINKLER ZONE 2)
SM SM SM
SM SM
4"
4"
4" 4"
US Army Corps of Engineers
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
1 2 3 54
A
B
C
D
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
N
EW
Y O
R K
D
IS
TR
IC
T
SO
LI
C
IT
AT
IO
N
N O
FI
LE
N
AM
E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E:
FI
LE
N U
M
BE
R
SI
ZE
SU
BM
IT
TE
D B
Y:
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
C O
N
TR
AC
T
N O
WARNING: THIS DOCUMENT MAY CONTAIN SENSITIVE SECURITY INFORMATION AND THEREFORE MUST BE TREATED AS A CONFIDENTIAL DOCUMENT. THE INFORMATION CONTAINED IN THIS DOCUMENT MUST BE MAINTAINED IN A CONFIDENTIAL MANNER TO PREVENT COMPROMISING HOMELAND SECURITY AS PROVIDED IN SECTION 214 OF THE HOMELAND SECURITY ACT OF 2002. NO PART OF THIS DOCUMENT SHALL BE REPRODUCED, RELEASED OR DISTRIBUTED WITHOUT THE EXPRESS WRITTEN PERMISSION OF THE UNITED STATES ARMY CORPS OF ENGINEERS, NEW YORK DISTRICT (USACE - NYD). UNAUTHORIZED REPRODUCTION, RELEASE OR DISTRIBUTION MAY RESULT IN CIVIL PENALTY OR OTHER ACTION BY USACE-NYD.
W
2D S
-1 4-
D -0
/4
/2
A
S S
H O
W N
"x
G H
D C on su lti ng
S er vi ce s In c.
JU
LY
5, Q P
K D
E S
IG
N
S O
U
TH
S A
LI
N
A S
TR
E
E T
S Y
R A
C U
S E
, N E
W Y
O R
K
W
2D S
-1 4-
D -0
2-
FY
F
IR
E S
U P
P R
E S
S
IO
N S
Y S
TE
M
V A
R
IO
U S
B U
IL
D
IN
G
S W
A
TE
R V
LI
E
T A
R S
E N
A L, N E
W Y
O R
K
.0
FP-104
B
0-
F P
-1
.d w g
0 4'-0" 16'-0"
SCALE 1/8"=1'-0" AT ORIGINAL SIZE
8'-0" 12'-0"
TM
T
TM
T
R
TK
SCALE: 1/8" � 1'-0"A1 BUILDING 41 - FIRST FLOOR PLAN
B U
IL
D
IN
G
FI
R
S T
FL
O
O R
P
LA
N
PROJECT
NORTH
GENERAL NOTES:
A. PROVIDE COMPLETE AUTOMATIC WET PIPE AND DRY PIPE SPRINKLER SYSTEMS IN ACCORDANCE WITH NFPA 13-2016 AND UFC 3-600-01 FOR BUILDING 41.
B. PIPING AS SHOWN IS DIAGRAMMATIC, NOT ALL PIPING/FITTINGS ARE INDICATED. CONTRACTOR IS RESPONSIBLE FOR FINAL SPRINKLER SYSTEM PIPE SIZING/LAYOUT, SPRINKLER HYDRAULIC CALCULATIONS, AND COORDINATION WITH LIGHTS FIXTURES/FIRE ALARM DEVICES, DUCTWORK AND DIFFUSERS.
C. PIPE SIZES WHERE INDICATED ARE MINIMUM ACCEPTABLE SIZES. FINAL PIPE SIZING SHALL BE DETERMINED BY CONTRACTOR HYDRAULIC CALCULATIONS SUBJECT TO
APPROVAL BY ENGINEER.
D. SPRINKLER DESIGN CRITERIA IS AS FOLLOWS:
1. COMMERCIAL SPACES (ORDINARY HAZARD - RESTAURANT SEATING AREA): 0.20 GPM/SQ.FT. OVER 2500 SQ.FT., 250 GPM HOSE STREAM DEMAND.
2. ATTIC SPACE (ORDINARY HAZARD): 0.20 GPM/SQ.FT. OVER 3250 SQ.FT., 250 GPM HOSE STREAM DEMAND.
3. CORRIDORS: 0.10 GPM/SQ.FT. OVER HYDRAULICALLY MOST REMOTE 5 SPRINKLERS, 100 GPM HOSE STREAM DEMAND.
E. FIRE STOP ALL PENETRATIONS THROUGH RATED WALLS, FLOORS, AND CEILINGS.
F. PIPING SHALL BE INSTALLED CONCEALED ABOVE FINISHED CEILINGS, I.E. GYP, ACT.
G. PIPING SHALL BE…
This is the start of the file's text. The full file is on GovTribe.