28_31_64_00_10.pdf
PDF 81 KB Posted
- Attached to
- Fire Suppression System, Various Buildings, Watervliet, NY Federal contract opportunity
- Solicitation number
- W912DS19B0019
About this file
Section 28 31 13 64 10: Fire Detection and Alarm System
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Bid_Abstract.pdf | ||
| W912DS19B0019_0003.pdf | ||
| FPS001.pdf | ||
| 21_13_17.00_10.pdf | ||
| W912DS19B0019_0002.pdf | ||
| 01_45_00_00_10.pdf | ||
| 21_13_13_00_10.pdf | ||
| W912DS19B0019_0001.pdf | ||
| WVA_FIRE_SUPPRESSION_100_pct_Submission_Combined_(compress).pdf | ||
| RTA_WVA_FIRE_SUPPRESSION_Spec.pdf | ||
| W912DS19B0019.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WVA Multiple Building Fire Protection 2162942
SECTION 28 31 64.00 10
FIRE DETECTION AND ALARM SYSTEM, ADDRESSABLE
08/09
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ACOUSTICAL SOCIETY OF AMERICA (ASA)
ASA S3.41 (2015) Audible Emergency Evacuation Signal
(ASA 96)
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE C62.41.1 (2002; R 2008) Guide on the Surges Environment in Low-Voltage (1000 V and Less) AC Power Circuits
IEEE C62.41.2 (2002) Recommended Practice on Characterization of Surges in Low-Voltage (1000 V and Less) AC Power Circuits
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2017) National Electrical Code
NFPA 72 (2016) National Fire Alarm and Signaling Code
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submittals with an "S" are for inclusion in the Sustainability Notebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Detail Drawings
SD-03 Product Data
Testing
SD-06 Test Reports
Testing
SD-07 Certificates
SECTION 28 31 64.00 10 Page 1 amendment 1.
09 SEP 2019
Equipment
Qualifications
SD-10 Operation and Maintenance Data
Operating and Maintenance Instructions; G
1.3 QUALITY ASSURANCE
1.3.1 Qualifications
Submit proof of qualifications for required personnel. The installer shall submit proof of experience for the Professional Engineer, fire alarm technician, and the installing company.
1.3.1.1 Engineer and Technician
a. Registered Professional Engineer with verification of experience and at least 4 years of current experience in the design of the fire protection and detection systems.
b. National Institute for Certification in Engineering Technologies (NICET) qualifications as an engineering technician in fire alarm systems program with verification of experience and current NICET certificate.
c. The Registered Professional Engineer may perform all required items under this specification. The NICET Fire Alarm Technician shall perform only the items allowed by the specific category of certification held.
1.3.1.2 Installer
The installing Contractor shall provide the following: NICET Fire Alarm Technicians to perform the installation of the system. A NICET Level 3 Fire Alarm Technician shall supervise the installation of the fire alarm system. NICET Level 2 or higher Fire Alarm Technician shall install and terminate fire alarm devices, cabinets and panels. An electrician or NICET Level 1 Fire Alarm Technician shall install conduit for the fire alarm system. The Fire Alarm technicians installing the equipment shall be factory trained in the installation, adjustment, testing, and operation of the equipment specified herein and on the drawings.
1.3.1.3 Fire Protection Engineer
Installations needing designs or modifications of fire detection, fire alarm, or fire suppression systems require the services and review of a qualified fire protection engineer. For the purposes of meeting this requirement, a qualified fire protection engineer is defined as an individual meeting one of the following conditions:
a. An engineer having a Bachelor of Science or Masters of Science Degree in Fire Protection Engineering from an accredited university engineering program, plus a minimum of 2 years' work experience in fire protection engineering.
b. A registered professional engineer (P.E.) in fire protection
SECTION 28 31 64.00 10 Page 2 engineering.
c. A registered PE in a related engineering discipline and member grade status in the National Society of Fire Protection Engineers.
d. An engineer with a minimum of 10 years' experience in fire protection engineering and member grade status in the National Society of Fire Protection Engineers.
1.3.2 Detail Drawings
Submit detail drawings consisting of a complete list of equipment and material, including manufacturer's descriptive and technical literature, catalog cuts, and installation instructions. Diagram shall include connections between system devices, appliances, control panels, supervised devices, and equipment that is activated or controlled by the panel.
1.4 DELIVERY, STORAGE, AND HANDLING
Protect equipment delivered and placed in storage from the weather, humidity and temperature variation, dirt, dust, and any other contaminants.
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
The existing fire alarm systems in Building Nos. 22, 36, 40, 41, 108 and 126 are Simplex IJCI. The scope of work is to provide addressable initiating device circuits modules for monitor, new fire sprinkler system, sprinkler waterflow and pressure switches, valve tamper supervisory switches and high/low air pressure switches. Wiring and conduit shall be provided from the initiating device circuits modules and connected to existing circuits. Programming of fire alarm systems and testing shall be provided.
2.1.1 Operation
Activate the existing system into the alarm mode by actuation of any alarm initiating device. The system will remain in the alarm mode until the initiating device is reset and the fire alarm control panel is reset and restored to normal. Alarm and supervisory initiating devices shall be individually addressable. Alarm initiating devices shall be connected to existing signal line circuits (SLC), in accordance with NFPA 72 .
a. Individual identity of each addressable device for the following conditions: alarm; trouble; open; short; and appliances missing/failed remote detector - sensitivity adjustment from the panel for smoke detectors.
b. Capability of each addressable device being individually disabled or enabled from the panel.
2.1.2 Alarm Functions
An alarm condition on a circuit shall automatically initiate the following functions:
a. Transmission of signals over the station existing fire reporting system. The signals shall be as follows:
SECTION 28 31 64.00 10 Page 3
b. Visual indications of the alarmed devices on the fire alarm control panel display.
c. Continuous sounding or operation of alarm notification appliances throughout the building as required by ASA S3.41 .
2.1.3 Interface With Existing Fire Alarm Equipment
The equipment specified herein shall operate as an extension to an existing configuration. Submit certified copies of current approvals or listings issued by an independent test lab if not listed by UL, FM or other nationally recognized testing laboratory, showing compliance with specified NFPA standards. The new equipment shall be connected to an existing control panel in the existing part of the building. Existing monitoring equipment shall be expanded, modified, or supplemented as necessary to extend the existing monitoring functions to the new points or zones. New components shall be capable of merging with the existing configuration without degrading the performance of either system. The scope of the acceptance tests of paragraph Testing shall include aspects of operation that involve combined use of both new and existing portions of the final configuration.
2.2 STANDARD PRODUCTS
Provide material and equipment which are the standard products of a manufacturer regularly engaged in the manufacture of the products for at least 2 years prior to bid opening. Equipment shall be supported by a service organization that can provide service within 24 hours of notification.
2.3 CONTROL PANEL
2.3.1 System Expansion and Modification Capabilities
Provide, as part of this contract, any equipment and software needed by qualified technicians to implement future changes to the fire alarm system.
2.3.2 Addressable Initiating Device Circuits Module
Configure the initiating device being monitored as a Class A initiating device circuits. The system shall be capable of defining any module as an alarm module and report alarm trouble, loss of polling, or as a supervisory module, and reporting supervisory short, supervisory open or loss of polling. The module shall be UL listed as compatible with the control panel. The monitor module shall provide address setting means compatible with the control panel's SLC supervision and store an internal identifying code. Monitor module shall contain an integral LED that flashes each time the monitor module is polled. Pull stations with a monitor module in a common backbox are not required to have an LED. Existing fire alarm system initiating device circuits shall be connected to a single module to power and supervise the circuit.
PART 3 EXECUTION
3.1 EXAMINATION
After becoming familiar with details of the work, verify dimensions in the field and advise the Contracting Officer of any discrepancy before
SECTION 28 31 64.00 10 Page 4 performing the work.
3.2 INSTALLATION
Install all work as shown, in accordance with NFPA 70 and NFPA 72 , and in accordance with the manufacturer's diagrams and recommendations, unless otherwise specified. Smoke detectors shall not be installed until construction is essentially complete and the building has been thoroughly cleaned.
3.2.1 Wiring
Conduit size for wiring shall be in accordance with NFPA 70 . Wiring for the fire alarm system shall not be installed in conduits, junction boxes, or outlet boxes with conductors of lighting and power systems. Not more than two conductors shall be installed under any device screw terminal.
The wires under the screw terminal shall be straight when placed under the terminal then clamped in place under the screw terminal. The wires shall be broken and not twisted around the terminal. Circuit conductors entering or leaving any mounting box, outlet box enclosure, or cabinet shall be connected to screw terminals with each terminal and conductor marked in accordance with the wiring diagram. Connections and splices shall be made using screw terminal blocks. The use of wire nut type connectors in the system is prohibited. Wiring within any control equipment shall be readily accessible without removing any component parts. The fire alarm equipment manufacturer's representative shall be present for the connection of wiring to the control panel.
3.2.2 Addressable Initiating Device Circuits Module
The initiating device circuits module shall be used to connect supervised conventional initiating devices (water flow switches, water pressure switches, manual fire alarm stations, high/low air pressure switches, and tamper switches). The module shall mount in an electrical box adjacent to or connected to the device it is monitoring and shall be capable of Style B supervised wiring to the initiating device. In order to maintain proper supervision, there shall be no T-taps allowed on style B lines.
Addressable initiating device circuits modules shall monitor only one initiating device each. Contacts in suppression systems and other fire protection subsystems shall be connected to the fire alarm system to perform supervisory and alarm functions as specified in Section 21 13 13.00 10 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION and 21 13 17.00 10 DRY PIPE SPRINKLER SYSTEM, FIRE PROTECTION, as indicated on the drawings and as specified herein.
3.3 OVERVOLTAGE AND SURGE PROTECTION
3.3.1 Power Line Surge Protection
All equipment connected to alternating current circuits shall be protected from surges in accordance with IEEE C62.41.1 / IEEE C62.41.2 B3 combination waveform and NFPA 70 . Fuses shall not be used for surge protection. The surge protector shall be rated for a maximum let thru voltage of 350 Volts ac (line-to-neutral) and 350 Volt ac (neutral-to-ground).
3.3.2 Signal Line Circuit Surge Protection
All SLC cables/conductors, except fiber optics, shall have surge protection/isolation circuits installed at each point where it exits or
SECTION 28 31 64.00 10 Page 5 enters a building. The circuit shall be protected from surges in accordance with IEEE C62.41.1 / IEEE C62.41.2 B3 combination waveform and NFPA 70 . The surge protector/isolator shall be rated to protect the equipment.
3.4 GROUNDING
Grounding shall be provided by connecting to building ground system.
3.5 TRAINING
Submit lesson plans, operating instructions, maintenance procedures, and training data, furnished in manual format, for the training courses. The operations training shall familiarize designated government personnel with proper operation of the fire alarm system. Conduct the course in the building where the system is installed or as designated by the Contracting Officer.
a. The instructions shall cover items contained in the operating and maintenance instructions. In addition, training shall be provided on performance of expansions or modifications to the fire detection and alarm system. The training period for system expansions and modifications shall consist of at least 4 training days (2 hours per day) and shall start after the system is functionally completed but prior to final acceptance tests. Sessions shall be separated by one week intervals to accommodate the rotation schedule of the fire department.
3.6 TESTING
Notify the Contracting Officer at least 10 days before the preliminary and acceptance tests are to be conducted. Perform the tests in accordance with the approved test procedures in the presence of the Contracting Officer.
The control panel manufacturer's representative shall be present to supervise tests. Furnish instruments and personnel required for the tests.
a. Submit detailed test procedures, prepared and signed by a Registered Professional Engineer or a NICET Level 4 Fire Alarm Technician, for the fire detection and alarm system 60 days prior to performing system tests.
b. Submit test reports, in booklet form, showing field tests performed to prove compliance with the specified performance criteria, upon completion and testing of the installed system. Each test report shall document readings, test results and indicate the final position of controls. Include the NFPA 72 Certificate of Completion and NFPA 72 Inspection and Testing Form, with the appropriate test reports.
3.6.1 Preliminary Tests
Upon completion of the installation, subject the system to functional and operational performance tests including tests of each installed initiating and notification appliance, when required. Tests shall include the meggering of system conductors to determine that the system is free from grounded, shorted, or open circuits. Conduct the megger test prior to the installation of fire alarm equipment. If deficiencies are found, corrections shall be made and the system shall be retested to assure that it is functional. After completing the preliminary testing complete and submit the NFPA 72 , Certificate of Completion and Testing Form.
SECTION 28 31 64.00 10 Page 6
3.6.2 Acceptance Test
Acceptance testing shall not be performed until the Contractor has completed and submitted the Certificate of Completion. Conduct testing in accordance with NFPA 72 . The recommended tests in NFPA 72 are considered mandatory and shall verify that previous deficiencies have been corrected.
The Fire alarm Technician supervising the installation of the fire alarm system shall attend the testing of the system. The test shall include all requirements of NFPA 72 and the following:
a. Test of each function of the control panel.
b. Test of each circuit in both trouble and normal modes.
c. Tests of each alarm initiating devices in both normal and trouble conditions.
d. Tests of each control circuit and device.
e. Visual inspection of wiring connections.
f. Opening the circuit at each alarm initiating device and notification appliance to test the wiring supervisory feature.
g. Ground fault.
h. Short circuit faults.
-- End of Section --
SECTION 28 31 64.00 10 Page 7
File details come from the government source that posted it.