Tuttle Creek Tainter Gate Controls
Solicitation number
W912DQ18B1010
Issued by

About this file

question from contractor

View the file

Other files

File Type Posted
Bid_sheet.pdf PDF
Bid_opening_Sign_in_sheet.pdf PDF
Site-Visit_Signin_sheet.pdf PDF
TC_TGC_E-102O.PDF PDF
TC_TGC_E-102.pdf PDF
Amendment_0001.pdf PDF
A.07.23_TC_TGC_16_May_2018.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

*Section 35 20 20, paragraph 2.4.2.1 calls for an SPD. The drawing E-601, control schematic does not indicate where this is located in the circuit. Will the SPD need to be in 480VAC load side of the breakers or will be on the 120VAC off the transformer?

Answer: The SPD's shall be on the load side of the 480VAC breakers.