Gavins_Pt_Ref_01_06_2017.pdf
PDF 31 MB Posted
- Attached to
- Gavins Point Excitation System Replacement Federal contract opportunity
- Solicitation number
- W9128F-16-T-0044
About this file
Amendment #7 Reference Drawing
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment__10_W9128F-16-T-0044.pdf | ||
| Amendment__9_W9128F-16-T-0044.pdf | ||
| Gavins_Pt_drawing_01_06_2017.pdf | ||
| Contractor_Questions-Amendment25Oct2016.pdf | ||
| Additonal_Specs.pdf | ||
| Past_Performance_Questionnaire.pdf | ||
| Amendment__7_Gavins_Point.pdf | ||
| Amendment__6_W9128F-16-T-0044.pdf | ||
| Amendment__5_W9128F-16-T-0044.pdf | ||
| Amendment__4_W9128F-16-T-0044.pdf | ||
| Amendment__2_W9128F-16-T-0044.pdf | ||
| Amendment__1_W9128F-16-T-0044.pdf | ||
| Amendment__3_W9128F-16-T-0044.pdf | ||
| Gavins_Point_reference.pdf | ||
| Gavins_Point_Exciters_Dwgs.pdf | ||
| Gavins_Point_Exciters_Dwgs.7z | 7Z file | |
| Gavins_Point_Exciters_Specs.pdf | ||
| 1442_and_clauses.pdf |
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EL. 1215.0
EL. 1211.0
EL. 1195.0
EL. 1179.5
EL. 1161.0
1O
EL. 1234.0
BROWN TRAFFIC CONTROL
SPARE
SPARE
SPARE
CROUSE HINDS TRAFFIC CONT.
CAMERA 6 SOUTH INTAKE
EXIT LIGHT
EX FAN E6 SEWAGE TREATMENT
EX FAN E5 LOCKER ROOM
BRIDGE AND INSIDE RECEPT.
BRIDGE LIGHT SOUTH
BRIDGE LIGHT NORTH
1O
COMPRESSOR ROOM LIGHTS
BREAK ROOM LIGHTS
GATE REPAIR PIT LIGHTS UPPER
GATE REPAIR PIT LIGHTS LOWER
MAINT. OFFICE AND JANITOR LIGHTS
ELEVATOR RM AND UPPER PLENUM LIGHTS
CORRIDOR LIGHTS
CORRIDOR LIGHTS
3RD FLOOR STORAGE RECEPTS
3RD FLOOR STORAGE RECEPTS
MAINT. OFFICE HEATER
SPARE
MAINT. OFFICE HEATER
GATE REPAIR PIT RECEPTS
MAIN BREAKER
MAIN BREAKER
3RD FLOOR STORAGE COVE HEATERS
3RD FLOOR STORAGE COVE HEATERS
***MAINT. OFFICE RECEPTS***
***ELEVATOR LIGHTS, ELEVATOR RM RECEPTS***
1O
1O
1O
LIGHTS-STORAGE ROOM
PANEL 1LE
HALL AND STAIRWAY LIGHTS
SOUTH CLOSET LIGHTS
GEN OFFICE WEST LIGHTS
GEN OFFICE CENTER LIGHTS
GEN OFFICE EAST LIGHTS
NO. 1 OFFICE LIGHTS
GEN OFFICE RECEPTS SOUTH
GEN OFFICE RECEPTS N,W,E AND PARTITON
COPY MACHINE NORTH WALL AND PARTITON
GEN OFFICE RECEPTS NORTH AND EAST
GEN OFFICE RECEPTS SOUTH WEST
GEN OFFICE RECEPT WEST WALL
SPARE
GEN OFFICE RECEPT WEST WALL14
PANEL 2LE PANEL 3LE
HALLWAY LIGHTS
BATHROOM LIGHTS
VAULT, BREAK ROOM, FITNESS ROOM LIGHTS
230V RECEPT IN FITNESS ROOM
FITNESS ROOM LIGHTS
230V RECEPT IN FITNESS ROOM
RECEPT IN OFFICE NO.1 AND BATHROOM
RECEPT-KITCHEN COUNTER EAST
RECEPT-KITCHEN COUNTER WEST
RECEPT-FITNESS ROOM S.E.
WOMENS BATHROOM HAND DRYER
SPARE
WOMENS BATHROOM HAND DRYER14
LIGHTS-HALLWAY AND LANDING IN STAIRWELL
LIGHTS-OFFICE #3 CLOSET
LIGHTS-OFFICE #3
CONF. ROOM FLOURESCENT LIGHTS 1
CONF. ROOM INCANDESCENT LIGHTS
CONF. ROOM FLOURESCENT LIGHTS 2
RECEPTS-OFFICE 3, HALLWAY,STORAGE RM
RECEPTS-CONF. ROOM COUNTER
ABANDONED FLOOR GUTTER STORAGE ROOM
RECEPT.- STUDY ROOM
RECEPT-CONF. ROOM COUNTER
CONF. ROOM COVE HEATERS
RECEPT-CONF. ROOM EAST
CONF. ROOM COVE HEATERS
RECEPT-CONF. ROOM WEST AND NORTH
1O
PANEL 4LD
HIGHBAY LITES - ERECTION BAY
HIGHBAY LITES - ERECTION BAY
HIGHBAY LITES - ERECTION BAY
HIGHBAY LITES - ERECTION BAY
LITES - MACHINE SHOP
HIGHBAY LITES - ERECTION BAY
HIGHBAY LITES - ERECTION BAY
LITES - MACHINE SHOP
LITES - MACHINE SHOP
LITES - MACHINE SHOP
LITES - MACHINE SHOP
LITES - WELD SHOP
LITES - ELECTRIC SHOP
LITES - ELECT. SHOP/STAIRS EL. 2015
LITES - DISPLAY ERECTION BAY
LITES - LOCKER ROOM
EXIT SIGN LITES - SOUTH AND BIG DOOR
LITES - STAIRS EL. 1195
LITES - BATHROOM EL. 1195
EMERGENCY LITES (RELAY)
RECEPTS - ERECTION BAY
EMERGENCY LITES - STARIWAY UP
EMERGENCY LITES - ELECTRIC SHOP
MAIN BREAKER 2-POLE
1O
PANEL 1LD
LIGHTS - MENS ROOM
RECEPT - FIRST AID ROOM SINK
RECEPT - FLOOR NEAR JANITORS CLOSET
PANEL 2LD
1O
PANEL 3LD
LIGHTS - BATTERY ROOM
EXHAUST FAN E-11, EMERGENCY GEN ROOM
LIGHTS - HALLWAY AND STAIRS
HIGHBAY LIGHTS - GENERATOR BAY
HIGHBAY LIGHTS - GENERATOR BAY
HIGHBAY LIGHTS - GENERATOR BAY
HIGHBAY LIGHTS - GENERATOR BAY
LIGHTS - EXC./GEN HOUSING AND UPPER GUIDE
LIGHTS - ACTUATOR CABINET
RECEPTS - GENERATOR FLOOR
RECEPTS - METER/JANITOR ROOMS
LIGHTS - JANITOR ROOM
RECEPTS - GEN HOUSING AND UPPER GUIDE
EXHAUST FAN E-3, BATTERY ROOM
EMERGENCY LIGHTING RELAY
LIGHTS - METER ROOM, EMERGENCY GEN ROOM
SPARE
SPARE - DC
EMERGENCY LIGHTS - GENERATOR FLOOR (4)
EMERGENCY LIGHTS - HALLWAY (2) SMALL ROOMS (5)
EMERGENCY LIGHTS EL. 1179.5 (5)
EMERGENCY LIGHTS - HALLWAY EL. 1211 (3)
25 SPARE - DC
1O
HIGHBAY LIGHTS - GENERATOR BAY
HIGHBAY LIGHTS - GENERATOR BAY
LIGHTS - ACTUATOR CABINET
RECEPTS - GENERATOR FLOOR
EMERGENCY LIGHTS - HALLWAY EL. 1211 (1)
SPARE - DC
EMERGENCY LIGHTING RELAY
SPARE
MAIN BREAKER 2-POLE
EMERGENCY LIGHTS - GENERATOR ROOM (4)
SPARE
SPARE
LIGHTS - EXC./GEN HOUSING,UPPER GUIDE
RECEPTS - GEN. HOUSING AND UPPER GUIDE
EMERGENCY LIGHTS - SERV. BAY EL. 1179 (5)
PANEL 2LD1
1O
RECEPTS - PPCS WORKSTATION
SPARE
CONTROL ROOM LIGHTS
CONTROL ROOM LIGHTS
CONTROL ROOM LIGHTS
SPARE
KITCHEN LIGHTS
SPARE
SPARE
RECEPTS - TAILRACE
RECEPTS - CONTROL ROOM
RECEPTS - KITCHEN
***RECORDER BOARD LIGHTS AND RECEPTS***
MAIN BREAKER 2-POLE
***CONTROL BOARD LIGHTS AND RECEPTS***
HIGHBAY LIGHTS - GENERATOR BAY
HIGHBAY LIGHTS - GENERATOR BAY
HIGHBAY LIGHTS - GENERATOR BAY
HIGHBAY LIGHTS - GENERATOR BAY
HIGHBAY LIGHTS - GENERATOR BAY
HIGHBAY LIGHTS - GENERATOR BAY
LIGHTS - EXC./GEN HOUSING, UPPER GUIDE
LIGHTS - ACTUATOR CABINET
RECEPTS - GENERATOR FLOOR
RECEPTS - MENS ROOM AND WATER COOLER
SPARE
SPARE
RECEPTS - GEN HOUSING AND UPPER GUIDE
LIGHTS - EXIT SIGNS, PA SYSTEM
SPARE
RECEPTS - WOMENS RESTROOM
LIGHTS - SECURITY, PHOTOEYE (A FLOOR)
LIGHTS - TAILRACE
EMERGENCY LIGHTS RELAY
EMERGENCY LIGHTS LOBBY
EMERGENCY LIGHTS HALLWAY EL. 1211
EMERGENCY LIGHTS SERV. BAY EL 1195
EMERGENCY LIGHTS GEN FLOOR
EMERGENCY LIGHTS GEN FLOOR
EMERGENCY LIGHTS GEN FLOOR
1O
PANEL 4LC
EMERGENCY LIGHTS RELAY
EMERGENCY LIGHTS - OIL STORAGE/PURIFICATION (3)
LIGHTS - AIR HANDLER ROOM
LIGHTS - AIR HANDLER ROOM
LIGHTS - AIR HANDLER ROOM
LIGHTS - CABLE TRAY ROOM
LIGHTS - CABLE TRAY ROOM
LIGHTS - ELECTRIC STORAGE ROOM
LIGHTS - MECH. SHOP SOUTH
LIGHTS - MECH. SHOP NORTH
LIGHTS - MECH. SHOP STORAGE ROOM
LIGHTS - AIR PLENUM/WIRE STORAGE
LIGHTS - EL. 1161
LIGHTS - EL. 1179.5
RECEPTS - S. GATE REP. PIT/STORAGE RM
RECEPTS - PA SYSTEM/SOUTH WALL
LIGHTS - A.H.U. #4
RECEPTS - MECH. SHOP CORD REELS
INTAKE DE-ICING COMP. WATER PUMP
RECEPTS - MECH SHOP DESK/COMPUTERS
EMERGENCY LIGHTS - STAIRWAY/COMMAND CENTER (5)
RECEPT - AIR COMPRESSOR DRYER
1O
RECEPT - PAINT SHAKER
PANEL 4LB
11LIGHTS - OIL STORAGE ROOM (INSULATING)
LIGHTS - OIL STORAGE ROOM (INSULATING)
LIGHTS - CO2 ROOM
LIGHTS - OIL PURIFICATION ROOM
LIGHTS - OIL STORAGE ROOM (LUBE)
LIGHTS - STORAGE ROOM
LIGHTS - SEWAGE TREATMENT PLANT
LIGHTS - HEATPUMP ROOM
LIGHTS - STORAGE ROOM
LIGHTS - E.O.C. ROOM
LIGHTS - SEWAGE TREATMENT ROOM
LIGHTS - WOOD SHOP / STORAGE
LIGHTS - WOOD SHOP / STORAGE
LIGHTS - CORRIDOR
SUMP PUMP EL. 1161.0
RECEPT - PANEL 4LB
***EMERGENCY EXH. FAN HEAT PUMP ROOM***
RECEPT - E.O.C. ROOM UPSTREAM
RECEPT -E.O.C. ROOM DOWNSTREAM/CHLORINATOR/SEWAGE
LIGHTS
RECEPTS - JANITORS CLOSET AND POP MACH.
SWITCHGEAR 38
1,3 WATER HEATER - GUARD ROOM/LOBBY
RANGE KITCHEN2,4
5,7 6,8
9,11 ABANDON CIR. - PH CONF. RM DUCT HEAT
10,12 FIRST AID ROOM / SHOWER HEATER - LOBBY
MENS RESTROOM HEATER - ADMIN
WOMENS RESTROOM HEATER - ADMIN
13,15 WOMENS RESTROOM HEATER - LOBBY
14,16 ABANDON CIR. MENS RESTROOM HEATER - LOBBY
17,19 WOMENS RESTROOM HAND DRYER - LOBBY
18,20 WATER HEATER ADMIN BREAK ROOM
21,23
WALL OUTLETS
25,27 CONTROL RM. RESTROOM HEATER
RECEPTS - SOUTH WALL
FDB-4
29,31 WATER HEATER UNDER KITCHEN SINK
RECEPTS - KITCHEN
RECEPTS - REFIGERATOR
RECEPTS - KITCHEN
35,37 WAPA CHARGER #1
39,41 WAPA CHARGER #2
1O
PANEL 1LC
LIGHTS - GENERATOR BAY CEILING S.E.
LIGHTS - GENERATOR BAY CEILING S.W.
LIGHTS - GENERATOR BAY CEILING N.E.
LIGHTS - GENERATOR BAY CEILING N.W.
LIGHTS AND RECEPTS - TURBINE PIT
LIGHTS - THRUST BEARING HOUSING
LIGHTS - SERVICE BAY CEILING
LIGHTS - SERVICE BAY WALL
RECEPTS - SERVICE BAY SS SIDE
RECEPTS - SERVICE BAY GEN SIDE
TURBINE PIT FAN
LIGHTS - UPPER TURBINE PIT AND OIL GAUGES
CONTROL POWER FOR SOUTH HEADER VALVES
RAW WATER STRAINER CONTROLS (SOUTH)
1O
PANEL 2LC
LIGHTS - GENERATOR BAY CEILING S.E.
LIGHTS - GENERATOR BAY CEILING S.W.
LIGHTS - GENERATOR BAY CEILING N.E.
LIGHTS - GENERATOR BAY CEILING N.W.
LIGHTS AND RECEPTS - TURBINE PIT
LIGHTS - THRUST BEARING HOUSING
LIGHTS - SERVICE BAY WALL
TURBINE PIT FAN
RECEPTS - TURBINE PIT, OIL FLOW LIGHTS,PA SYSTEM
RECEPTS - TURBINE FLOOR
MAIN BREAKER 2-POLE
LIGHTS - VOLTAGE REG. AND EXCITER CAB. U1&U2
MAIN BREAKER 2-POLE
LIGHTS - UPPER TURBINE PIT
1O
PANEL 3LC
LIGHTS - GENERATOR BAY CEILING S.E.
LIGHTS - GENERATOR BAY CEILING S.W.
LIGHTS - GENERATOR BAY CEILING N.E.
LIGHTS - GENERATOR BAY CEILING N.W.
LIGHTS AND RECEPTS - TURBINE PIT
RECEPTS - GENERATOR BAY
LIGHTS - THRUST BEARING HOUSING/TURBINE PIT UPPER
LIGHTS - SPILLWAY STAIRS
LIGHTS - SPILLWAY STAIRS/EXIT SIGN A FLOOR TUNNEL
RECEPTS - WATER QUALITY AND DISTILLER
LIGHTS - WALL AND EXIT SIGN
LIGHTS - OIL SIGHT GAUGES
LIGHTS - STAIRWAY AND HALL E. RECEPTS SERV BAY/TELE CAB.
LIGHTS - VOLTAGE REG. & EXCITER CABINET U3
RAW WATER STRAINER (NORTH)
WATER HEATER
WATER HEATER
TURBINE PIT FAN
LIGHTS - STORAGE ROOM UPSTREAM
LIGHTS - STORAGE ROOM DOWNSTREAM
LIGHTS - DRAFT TUBE
LIGHTS - STAIRWAY
RECEPTS - EL. 1134
RECEPTS - COMPUTER RM LIGHTS - COMPRESSOR RM
RECEPTS - COMPUTER RM LIGHTS - COMPRESSOR RM
LIGHTS - STORAGE ROOM SOUTH
LIGHTS - STORAGE ROOM NORTH
LIGHTS - SOUTH CORRIDOR
LIGHTS - NORTH CORRIDOR
LIGHTS - EL. 1134.0
1O LIGHTS - EL. 1134.0
LIGHTS - EL. 1134.0
LIGHTS - EL. 1134.0
LIGHTS - EL.1134
LIGHTS - EL.1134
LIGHTS - DRAFT TUBE
LIGHTS - COMPUTER ROOM
RECEPTS - EL. 1161
EMERGENCY LIGHTS RELAY
LIGHTS AND RECEPTS - PRINT STORAGE ROOM
DC EMERGENCY LIGHTS - EL. 1161.0
DC EMERGENCY LIGHTS - EL. 1134.0
CONTROL RM. RESTROOM & KITCHEN EX. FAN
RECEPT-HALLWAY,VAULT,FITNESS,BREAK RM
S.S. BUS #2
VOLT
REG.
MAIN LIGHTING DISTRIBUTION PANEL - 7DCB
NOTES :
BREAKERS MUST BE TAGGED***
1. ***CIRCUITS MARKED WITH ASTERIKS ARE SEMI - CRITICAL,
1,2 3,4
PANEL 38-A
RANGE - ADMIN. KITCHEN
WATER HEATER - CONTROL ROOM RESTROOM
( SEE NOTE 2 )
( SEE NOTE 2 ) ( SEE NOTE 2 ) ( SEE NOTE 2 )
ERECTION BAY GEN BAY 1 GEN BAY 2 GEN BAY 3
BKR#
BKR#
BKR#
BKR#
BKR#
BKR#
BKR# BKR#
BKR# BKR#
BKR#
BKR#
BKR# BKR#
BKR#
BKR#
BKR#
BKR#
4TDE
4TF
2TCDD1E 2TB 3TCDE
CONTROL RELAY - BRIDGE LIGHTS
LIGHTS/RECEPTS - JANITORS CLOSET
DURAPHONE
2. ALL TRANSFORMERS FEEDING LIGHTING PANELS ARE 460V/120-240V
AND ARE LOCATED ON A FLOOR - EL. 1179.5
8DCB 8DCB
PANEL 4LF
US Army Corps of Engineers
Omaha District
PANEL 4LE
SWGR #7 CONTROL ROOM EL. 1195
ADMIN
S.S. BUS #1
PANEL 2LB
XFMR
1TCDE
XFMR
SWGR 384TCB
XFMRXFMR
3RD FLOOR
2ND FLOOR
1ST FLOOR
A FLOOR
B FLOOR
XFMR
XFMR XFMR XFMR
Designed by:
Drawn by:
Checked by:
Reviewed by:
Submitted by:
Chief:
Contract No.:
Drawing Code:
Date:Scale:
As Shown
Plot Scale Ratio:
Design File:
Revisions
DACW 45
Missouri River
Gavins Point Project-Lewis and Clark Lake
Sect.
DEVICE.DGN
CONVERTED TO
CADD 8-93
JUNE 1998
MGOPN-83E232A
DateDescriptions APPROVEDMADE
GENERAL REVISIONS
POWER HOUSE
LIGHTING PANEL SCHEDULES
A.K.
AND RISER DIAGRAM
11-19-12
Gavins Point Project-Lewis and Clark Lake
M.R.E.
Negative Phase Sequence Relay
121T
Gen. Status/ Alarm Relay
Transformer Status/Alarm relay74T
Line Breaker or Relay operation Alarm Relay 74L
1UC
Excitation Start/Stop Relay1E
Alarm Cutout Relay-Control Room
63GBX
Gen. Thrust Bearing Cooling Water Flow Aux Relay
IS Interlock Switch
Turbine Blade Tilt Solenoid65BT
BT Turbine Blade Tilt
6PS-1 Pressure Switch DC Turbine Bearing Oil Pump 6PS-2 Pressure Switch Turbine Bearing Permissive
33N Null Switch
Gen Turbine Bearing Oil Pressure Aux Relay
63Q Governor Low Oil Pressure Switch
TH Thermostat
Packing Gland
BF
CS
Breaker Failure
Control Switch
63TB
63GX,Y
Gen. Thrust Brg. Oil Level Switch
63TX,Y
Gen. Air Brake Intermittent Timer
Reclosure Aux. Relay
Gen. Packing Gland Flow Aux Relay63PGX,Y
79 Reclosing Relay
94 Tripping Relay
78 Out of Step Relay
3G Partial Shutdown Aux Relay
Manual Excitation Control Sw.
Speed Switch Aux Relay
Intake Gate Emergency Close Solenoids
Volts per Hertz Relay
27T Transfer Bus Undervoltage Relay
Exciter Field Circuit Breaker Trip Coil 42 Motor Starter
51N Neutral Overcurrent Relay
Generator Overcurrent Relay-Voltage Supervised
27 Under Voltage Relay
32 Directional/Reverse Power relay
38 Bearing Thermal Relay
Exciter Field Circuit Breaker Close Coil 41E
50 Instantaneous Overcurrent Relay
Instantaneous/Time Overcurrent Relay
Breaker Cutoff Relay Anti-Pump
Intake Hydraulic Gate Emergency Close Solenoid
Time Delay Overcurrent Relay
51Y
Breaker Close Coil
59FY Sustained Field Overvolatge-DC rag. (voltage mode) 59FZ Sustained Field Overvolatge-TRIP. (current mode)
59GZ Generator at Rated Voltage
52GCL Unit Breaker Position Status
52GY Unit Breaker Position Status
Excitation on Permissive 3E
Unit Aux. Master Relay
4E Excitation Master Start Stop Relay Excitation Master Start Stop AUX. Relay4EX
31F Field Flashing Contactor
86B1,B2 Exciter Bridge Lockout Relays
80BX
80BY Exciter Bridge Low Air Flow
Exciter Bridge Low Air Flow
70CV-CS Exciter Current/Voltage Adjust Control Switch
Bus Differential Lockout Relay
CTO Cutout
C,NAC Closed, Normally After Closed
CSA Control Switch Auxilliary
A
B
C
D
A
B
C
5 4 3 2 1
5 4 3 2 1
Breaker Failure Cutout Sw. (1BF2, etc.)
Emergency Shutdown Sw.
Generator Breaker Control Sw.
Generator Aux. Control Sw.
Gate Limit Control Sw.
Gate Servo Lock Selector Sw.
Partial Shutdown Reset Sw.
Sta. Serv. Transformer 13.8KV ACB Control Sw.
Speed Adjust Motor Control Sw.
Gen. Synchronizing Sw.
Line Synchronizing Sw.
Sta. Serv. 480V ACB Control Sw.
Transformer Aux. Control Sw.
Gen. Aux. Control Sw.
Gen. Start-Stop Control Sw.
Draft Tube Water Depression Control Sw.
Starting Time Delay Relay Code Call Timer Relay Fisherman's Horn Time Relay Synchronizing Timer Turbine Pit Warning Horn
Starting Time Delay Aux. Relay
Unit Master Start-Stop Relay
Automatic Synchronizer Power Supply Relay Transformer Aux. Master Relay Auto Master Start Stop Relay
Complete Shutdown Relay Complete Shutdown Aux. Relay Emergency Shutdown Relay Mechanical Shutdown Relay Partial Shutdown Relay
AC Turbine Bearing Oil Pump DC Turbine Bearing Oil Pump
Draft Tube Depression Compressor Sel. Sw.
Station Air Compressor Seq. Sw.
Over Speed Switch
Speed Switch
Under Speed Switch
Auto Speed Matching Relay
Speed Matching Aux. Relay
Solenoid Valves Control Air Sol. Valve (To Filters)
Gen. Air Brake Valve Solenoid Pneumatic Press. Tank Air Supply Sol. Valve
Draft Tube Depressor Aux. Air Supply Sol. Oper. Valve Draft Tube Dash Pot Depressor Switch
Draft Tube Depressor Aux. Relay Draft Tube Depressor Interlock Relay
Gate Servo Lock Solenoid Make Up Air Control Sol. Valve
Sta. Sevr. Air Compr. Aftercooler Cooling Water Sol. Valve
Sta. Serv. Air Compr. Cooling Water Valve Time Delay
De-icing Air Compr. Cooling Water Valve
Aux. Relay (20 Sec TD)
Turbine Runner Seals Water Motor Oper. Valve
Transformer Cooling Water Motor Oper. Valve
Unit Cooling Water Supply Motor Oper. Valve Unit Cooling Water Valve Local Aux. Relay
Automatic Sychronizer
1BF1
1ES
1G
1GA
1GL
1GSL
1PSR
1S
1SAM
1SG
1SL
1SS
1TA
1UA
1WD
1V
2CC
2FH
2S
2TPWH
2X
4S 4X 4Z
5C
5CX
5E 5M 5P
6QAC
6QDC
10DA
10SA
13X
15R, 15L
15RX
15LX
20AF
20AI
20AS
20AV
20A,B,C
20DA
20DCS
20DM
20DX
20DY
20EC
20GSL
20MA
20SAAW
20SAW
20SDW
20SDWX
20T
20TR
20TW
20U
20UR
Automatic Synchronizing Lockout Relay Automatic Synchronizing Control Aux. Relay Automatic Synchronizing Selecting Relay
Thermal Device Thermal Aux. Relay
Bus Voltage Check Relay
Generator Lower Guide Brg. Thermal Relay Generator Thrust Brg. Thermal Relay Generator Upper Guide Brg. Thermal Relay
Generator Oil Head Thermal Relay Generator Upper Stuffing Box Thermal Relay Generator Middle Stuffing Box Thermal Relay Generator Lower Stuffing Box Thermal Relay Turbine Guide Brg. Thermal Relay
Generator Loss of Field Relay
Exciter Field Circuit Breaker
Exciter Field Circuit Breaker Control Sw.
Auto Transformer Air Handling
Generator Cooling Water Pump Starter Station Drainage Pump Domestic Water Pump Oil Room Exh. Fan (F - fast, S - slow) Fire Pumps Gen. Thrust Brg. HP Lub. Oil Pump Generator Heater Starter Gov. Oil Pump Gov. Air Compressor Generator Heater Gen. Thrust Brg. HP Lub. Oil Pump Starter Hydraulic Jack Oil Pump Starter Battery Charger Motor Unwatering Sump Drainage Pump Oil Purifier Purifier Motor Purifier Pump
Surge Tank De-icing Air Compressor Turbine Sump Pump AC Motor Starter Transformer Oil Pump Oil Transfer Pump Unwatering Pump
Gen. Air Brake Auto Transfer Sw.
Air Brake Control Sw.
Unit Master Control Sw.
Unit Master Control Aux. Relay - Local Auto Unit Master Control Aux. Relay - Local Manual
Unit Master Control Aux. Relay - Remote Auto
Gen. Air Brake Hand Transfer Sw.
Pump Starting Sequence Selector Sw.
Voltage Regulator Transfer Sw.
Reclosing Cutout & Transfer Sw.
Local-Remote Switch AT OCB PNLS
Three Phase Undervoltage and Phase Sequence Relay
Incomplete Starting Sequence Timing Relay Incomplete Starting Sequence Lockout Relay
Thermal Relay Auto Transformer Thermal Relay
Generator Stator Temp. Relay Generator Stator Temp. Aux. Relay Temperature Recorder Alarm
Transformer Thermal Relay Transformer Winding Thermal Aux. Relay
Transformer Thermal Aux. Relay
Auto Transformer Neutral Overcurrent Relay Ground Transformer Overcurrent Relay Ground Transformer Grd. Overcurrent Aux. Relay
Generator Overcurrent Relay
Transformer Neutral Overcurrent Relay
Transformer Neutral Overcurrent Aux. Relay
Overcurrent Aux. Relay Voltage Restrained Overcurrent Relay 3 Phase O.C. Relay - Voltage Supervised
Gen. Breaker Control Switch
Breaker Trip Coil Breaker Closure Air Valve Breaker Trip Free Coil Control Valve
Breaker Closure Aux. Relay Breaker Aux. Relay
Exciter Field Flashing Relay Exciter Field Flashing Time Delay Relay
Gen. Voltage Relay Gen. Voltage Control Aux. Relay Gen. Instantaneous Overvoltage Aux. Relay
Gen. Field Overvoltage Relay
Generator Overvoltage Relay
Essential AC Normal Supply Overvoltage Relay
Potential Indicator Relay
Generator Overvoltage Aux. Relay
Auto Voltage Matching Relay - Raise Auto Voltage Matching Relay - Lower
Normal Shutdown Time Relay Transformer Oil Pump Time Delay Aux. Relay Pendulum Relay Backup Relay Breaker Failure Timer. 2, 3, etc.
Gen. Time Delay Closing Relay Gen. Neutral Overvoltage Timer Complete Shutdown Relay
Gen. Neutral Overvoltage Timer Partial Shutdown Relay
Transformer Oil Flow Timer Transformer Oil Flow Time Aux. Relay Transformer Oil Flow Time Aux. Relay
Air Brake Pressure Applied Air Brake Cylinder Pressure Switch Gen. Brake Air Supply Pressure Switch Brake Cylinder Pressure Aux. Relay
Clearwell Low Level Float Switch Clearwell Low Level Aux. Relay
Sta. Drainage & Unwatering Sump Float Switch
High Sump Alarm Aux. Relay
Draft Tube Depressor Air Header Press. Sw.
Draft Tube Pressure Switch Draft Tube Float Switch Draft Tube Depressor Low Water Level Aux. Sw.
Tailwater Float Switch
Tailwater Float Switch Aux. Relay Governor Air Pressure Switch
Gen. Thrust Brg. Oil Pressure Switch
Governor Sump Level Switch
Gen. Cooling Water Flow Aux. Relay
Gen. Packing Gland Flow Switch
Governor Oil Pressure Switch Turbine Guide Brg. Oil Flow Switch Turbine Brg. Oil High Level Switch Turbine Brg. Oil Low Level Switch Turbine Guide Brg. Oil Pump Pressure Sw.
Governor Low Oil Pressure Aux.
Sta. Air Pressure Switch
Shear Pin Failure Pressure Switch
Transformer Oil Flow Switch Transformer Oil Flow Aux. Switch Transformer Sudden Press. Rise Relay Transformer Sudden Pressure Rise Aux. Relay
Transformer Sudden Pressure Rise Relay Cutout
Transformer Water Flow Switch
Sump Control Level Switch
Generator Air Cooling Water Flowmeter
Turbine Guide Brg. Water Low Flow Sw.
A
ACR
ACS
AR
AS
CGCS
CGX
DAX
DCA
EA
ECX
F
FR
FS
FWH
FWHAX
FWR
FWS
GL
GP
GPC
GS
GSL
HR
HRA
L
LDC
LF
LS
LTS
M
MOD
R
OL
OSC
PB
PF
PG
PS
PSX
RTD
S
SS
SCS
T
TC
TD
TRC
TS
TCX
TY
UA
UC
URX
UV
V
VA
VAR
VAR
VR
VS
VT
W W
WH
WVT
WT
X,Y,Z
Alarm Cutout Switch Aux. Relay Ammeter Switch
Cylinder Gate Control Switch
Intake Emerg. & Cylinder Control Sw. Aux. Relay
Auxiliary Time Delay Relay Generator Field DC Ammeter Exciter DC Ammeter Intake Gate Emerg. Control Switch Emerg. Gate Closing Relay Frequency Indicator
Frequency Recorder Float Switch Fisherman's Warning Horn Fisherman's Warning Horn Auxiliary Relay Fisherman's Warning Horn Relay Fisherman's Warning Horn Switch Gate Servo Lock-On Light Gate Limit & Position Indicator Gate Limit & Position Converter Generator Symbol Gate Servo Lock Hand Reset Actuator Horn Reset Relay
Lamp Line Drop Compensation Load Frequency
Limit Switch Annunciator Light Test Switch Motor Motor Operated Disconnect
Receiver - Carrier
Remote
Overload Oscillograph Jack
Pushbutton Power Factor Meter
Pressure Switch Pressure Aux. Relay
Resistance Temperature Detector
Synchroscope
Synchronizing Switch Sync. Cutout Sw.
Transmitter - Receiver Carrier Thermal Converter Time Delay Relay
Throw Over Contactor
Trip Coil Aux. Relay Energizer Lockout Relay Unit Auxiliary Control Switch Gen. Auto Start Stop Control Switch Unit Run Aux. Relay
Voltmeter Synchronizing Voltage Adjust Transformer Varmeter Var. Recorder Voltage Regulator Voltage Switch Var. Transducer Wattmeter Watt Recorder Watthour Meter Watt Var. Transducer Watt Transducer Auxiliary
Auto Transformer Neutral Overcurrent Relay
Auto Transformer Neutral Overcurrent Aux. Relay
DC Bus Ground Relay
Essential AC Ground Relay
Exciter Field Ground Detector Relay
Gen. Neutral Ground Overcurrent Relay Gen. Neutral Ground Overcurrent Aux. Relay Gen. Neutral Overvoltage Timer Complete Shutdown Relay
Gen. Neutral Overvoltage Timer Partial Shutdown Relay Gen. Neutral Ground Overcurrent Aux. Relay Gen. Ground Time Delay Aux. Relay Gen. Ground Time Delay Aux. Relay
Station Service Swgr. Bus Grd. Relay Station Service Swgr. Bus Grd. Aux. Relay
Transformer Neutral Overcurrent Relay Transformer Neutral Overcurrent Aux. Relay
Gov. Dashpot Bypass Valve Control Sw.
Gov. Automatic Local Control - Lower
Turbine Gate Limit Control Motor Turbine Gate Limit Adjustment Control Sw.
Gov. Dashpot Bypass Valve Solenoid Speed Level Adjustment Control Switch Gov. Speed Level Limit Switch Gov. Speed Level Control Motor Gov. Bypass Time Delay Relay Gov. Bypass Time Delay Relay Gov. Automatic Load Control - Raise
Gov. Shutdown Solenoid Gov. Speed No Load Solenoid Gov. Transfer Valve Switch
Circuit Breaker Permissive Relay
Motor Operated Exciter Field Rheostat
Exciter Field Rheostat Control Switch
Exciter Field Rheostat Motor Preposition Relay, Type SG, Voltage Regulator
Exciter Field Rheo. No-Load Lower Prepositioning Relay Exciter Field Rheo. No-Load Raise Prepositioning Relay
Battery Charger Gen. DC Contactor Battery Changer Contactor Aux. Relay Emergency Lighting Feeder Contactor Inverter Set Motor Turbine Sump Pump DC Motor Starter
Main ACB Overcurrent Alarm Aux. Relay Station Serv. Fdr. 3 Overcurrent Alarm Aux. Relay Intake Feeder Overcurrent Alarm Aux. Relay Outlet & Spillway Fdr. Overcurrent Alarm Aux. Relay Grounding xfmr. Overcurrent Alarm Aux. Relay
Ann. Alarm Relay
Water Depression Alarm Relay
Ann. Horn Timer Relay Ann. Horn Timer Aux. Relay
Gen. Breaker Oper. Mechanism Position Contacts
Abnormal Freq. Contact of Freq. Recorder Abnormal Freq. Aux. Relay Voltage Regulator Freq. Relay
Voltage Reg. Amplidyne Cut in Contactor
Essential AC Throw Over Contactor Emerg. Supply Essential AC Throw Over Contactor Normal Supply
Volt. Reg. PT's. Amplidyne PM Alter. Cut in Relay Volt. Reg. Motor Starting Voltage Control Relay Volt. Reg. Norm Voltage Control Relay
Lockout Relay
Gen. Differential Lockout Relay Breaker Failure Lockout Relay. 2-3, etc.
Transformer & Line Lockout Relay
Auto Transformer Differential Relay Bus Differential Relay Bus Differential Relay Bus Differential Aux. Relay Gen. Differential Relay Gen. Differential Aux. Relay Transformer Differential Relay Transformer Differential Aux. Relay
Field Reducing Contactor
Directional Distance Timer Trip Bypass Relay Reclosure Blocking Timing Relay
Directional Distance Relay Directional Distance Out-of-Step Blocking Relay Directional Distance Carrier Start Relay
Directional Distance Timer Relay
Synchronizing Check Relay
115KV Bus Voltage Relay Line Voltage Relay
Motor Operated Line Disconnect
OCB Reclosure Cutout Switch OCB Reclosure Cutout Aux. Relay
Directional Distance Fault Detector Relay Fault Detector Relay
Line Breaker Line Breaker Aux. Contacts Line Breaker Trip Coil Line Breaker Anti-pump Relay
Carrier Directional Ground Overcurrent Relay Line Directional Ground Overcurrent Relay Backup Directional Ground Overcurrent Relay Directional Ground Backup Relay Pilot Directional Ground Overcurrent Relay Directional Ground Backup Relay Carrier Directional Ground Relay Transfer OCB Directional Ground Overcurrent Relay
Directional Distance Out-of-Step Blocking Relay
Reclosing Relay Reclosing Blocking Relay Reclosure Permissive Relay Reclosure Cutoff Switch Reclosure Delay Relay Reclosure Motor Relay Reclosure Initiation Relay
Carrier Receiver & Aux. Relay
Transfer Trip Aux. Relay Carrier Aux. Relay Dir. Distance Out-of-Step Blocking Aux. Relay
Line Differential Relay
Line Differential Overcurrent Relay Line Differential Overcurrent Aux. Relay
MOD Control Switch
Tripping Relay Transfer Tripping Aux. Relay Tripping Aux. Relay Transfer OCB Tripping Aux. Relay Line Tripping Relay
Auto Transformer Thermal Relay
Gen. Thrust Brg. Cooling Water Flowmeter
Complete Prime Pressure Switch Turbine Packing Box Water Flow Switch
Turbine Packing Box Water Flow Aux. Relay
Permissive Start Relay
DEVICE DESCRIPTION DEVICE DESCRIPTION DEVICE DESCRIPTION DEVICE DESCRIPTION DEVICE DESCRIPTION DEVICE DESCRIPTION
Ammeter
115KV Bus Differential Lockout Relay86BD 86G
86BF1
86T
87AT
87B
87BD
87BX
87G
87GX
87T
87TX
102RC
121B
121CX
121X
127B
143X
150B
152aa-x
152TC
152Y
167CG
167G
167GB
167GR
167PG
167-1 167-2 167G
179AT
179AX
179CO
179D 179M 179X 179Y
185T 185X 185Y
187L
187LX
189CS
194A,B,C 194L 194T 194X
64B
64E
64F
64G
64GX
64G 64G
64GX
64GY
64GZ
64S
64SX
64T
64TX
65BVCS
65L
65ML
65MLCS
65MSBP
65MSCS
65MSLS
65MS
65MSX
65MSY
65R
65SD
65SNL
65TV
70CS
70M
70PX
70RC
70XL
70XR
70Y 70Z
72GB
72EL
72M
72SP
74AT1
74AT2
74AT3
74AT4
74AT5
74C
74D 74G
74HT
74HTX
75G
81FR
81FRX
81R
83A
83IE
83IN
83X 83Y 83Z
86B
52G-CS
52TC
52V-CO
52VT
52X 52Y 52Y
53C
53TD
59A
59AX,2
59-1X
59F
59G
59N
59NX
59ST
59X
62BF1
62G
62GY
62GY
62T
62TX
62TY
63ABA
63AB
63ABS
63ABX
63C
63CWLU
63CWX
63D
63DX
63DH
63DT
63DW
63DWX
63DY
63DYX
63GA
63GQ
63GS
63PG
63QG
63QTG
63QTH
63QTPS
63QX
63SA
63SPF
63TO
63TOX
63TP
63TPX
63TP-CO
63TW
63U
63WA
63WB
CO Discharge Pressure Switch2
63WG
63WP
63WT
63WTA
63X
64AT
64ATX
25LO
25X,Y,Z 25K1,K2
26A
27B
38GLG
38GT
38GUG
38OH
38USB
38MSB
38LSB
38TG
41CC
41CS
41TC
42AT
42AH
42CWP
42DP
42DW
42F 42F 42G
42GH
42GP
42GR
42H
42HP
42J 42M
42MP
42OP
42PM
42PP
42SD
42SP
42T
42TP
42UP
43A
43AB
43C
43LAX
43LMX
43RAX
43H
43P 43R
43RC
43T
46Q
47H
48A
49AT
49ATT
49G
49GX
49RA
49T 49T1X 49T2X
49TX
50-51
50-51ATN
50-51GT
51G
51TN
51TNX
51V
49T3X
Essential AC Normal Supply Overvoltage Aux. Relay
51X 51-27
52CC
50-51GTNX
Draft Tube Depressor Aux. Air Supply Sol. Oper. Valve
Sta. Serv. Air Compr. Cooling Water Sol. Valve
Turbine Runner Seals Water Valve Local Aux. Relay
127L
Exciter Field Rheo Lower Prepositioning Relay Exciter Field Rheo Raise Prepositioning Relay
RX
LX
Test Switch
Magnetic Unloader Valve
RE
EC
Legend
63QTL
87L A-C Pilot Wire Relay
63GSX,Y Governor Sump Aux. Cutout Relay
43GSA Gov Sump Aux-Pump Cutout Control Transfer Relay
PAX Phone Ann. Aux Relay
Offset MHO Distance Relay121Z
Directional Distance Timer Relay
Wicket Gate Position Sw.
Unit Aux. Master Relay
4A 4B
Designed by:
Drawn by:
Checked by:
Reviewed by:
Submitted by:
Chief:
Contract No.:
Drawing Code:
Date:Scale:
As Shown
Plot Scale Ratio:
Design File:
Revisions
DateDescriptions
$$ - THINK VALUE ENGINEERING - $$
U.S. ARMY ENGINEER DISTRICT
CORPS OF ENGINEERS
OMAHA, NEBRASKA
DACW 45
Missouri River
Gavins Point Project-Lewis and Clark Lake
US Army Corps of Engineers
Omaha District
Sect.
DEVICE SCHEDULE
APPROVEDMADE
M.R.E. GENERAL REVISIONS
DEVICE.DGN
CONVERTED TO
CADD 8-93
JUNE 1998
MGOPN-83E300.7
M.R.E. GENERAL REVISIONS 3-10
4-91
GENERAL REVISIONSM.R.E. 8-12
M.R.E. GENERAL REVISIONS 1-13
Designed by:
Drawn by:
Checked by:
Reviewed by:
Submitted by:
Chief:
Spec. No.:
Contract No.:
Drawing Code:
Date:Scale:
As Shown
Plot Scale Ratio:
Design File:
Revisions
MADEDescriptions
$$ - THINK VALUE ENGINEERING - $$
OMPUTER
IDED
ESIGN &
RAFTINGD
D A
C
U.S. ARMY ENGINEER DISTRICT
CORPS OF ENGINEERS
OMAHA, NEBRASKA
DACW 45
DACW 45Sect.
DATE APPR'D
MISSOURI RIVER
GAVINS POINT DAM-LEWIS AND CLARK LAKE
PAB
MAY 2001
SINGLE LINE
125V DC & 115V AC
DIAGRAMS
9-14-85 New drawing added ENK CLC
2 3 4
20 21
27 28
30 20
49 5044
100100100100 30
52 53
20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35
15 16
3 4 5
6 7 8 9
12 13
14 1 2
175 175 100 100 100 100 100 100
PNL.7 DCB PNL.8 DCB
PNL.5 DCB PNL.6 DCB
PNL.4 DCB
PNL.1 DCB
PNL.2 DCB
PNL.3 DCB
125V DC BUS
125V DC BUS
115V AC 10 BUS
125V DC BUS
14 15 16 17 18
125V DC BUS
14 15
125V DC BUS
C o n t r o l
P w e r
U n i t
H e a t r
D C
C o n t r o l
A u
S a r t
S t o p
S p a r e
B R
N C
J
L u m p
T r b i n e
S u m p m p r b i n e
C CUnit No.1-Swgr.11
Same as Shown for
UNIT NO.2 AUX.PANEL
SWGR.NO.12 125V DC
UNIT NO.1 AUX.PANEL
SWGR.NO.11 125V DC
C o n t r o l
A C
B c n t r o l
U n i
R l a y
S w g r
F e d e r
R e l a y s
U n i
X f m r
S S n t r o l
S t a
S e r v
X f m r
S y n c h r o n i z e r
A u t o m a t i c
S p a r e
B u s
G r d
F a u l a y
S p a r e
P
A T
U S
E q u i p m e n t
C a r r i r r e n t
S p a r e
W A
U
E l e c t
M a i n
V p p l y c e p t s n t r o l
U n l a y
S w g r e d e r
S p a r e
R e l a y s
U n m r
S p a r e
L i n l a y s
S p i r
M u n d
S p a r e
S p a r e
T r i p
V o g u l a t o r
R e c e p t
E l e c t r h o p
C r a i p
P o w a n t
S w g r i p
P o w e r
O s c i l l o g r a p h
C o n t r o m
A n n u n c i a t o r s
A u d i b a r m
O n t r o l
O o m s
R e l a y s
B l o o m f i e d n e
C o n t r o l
G e
UNIT NO.3 AUX.PANEL
SWGR.NO.13 125V DC
C C
F F
Sump Pump
DC Turbine
Bearing Oil Pump
DC TurbineS p a r e
A
V
VS
#1
Charger
A
V
VS
#2
Charger
A
V
60 cell
Batteries
Station
Note 1
Note 1
Note 2
A
V F W
Supply
Normal
Note 4
115VAC
INVERTER
115V
460V
Xfr
Bypass
25KVA
70A Bkr.#6
From 7DCB, n t r o l
U n l a y
S w g r e d e r
S p a r e
S p a r e
R e l a y s
U n m r
C o n t r o l
P C
B
M O
D
S p a r e
S p a r e
S p a r e
S p a r e
S p a r e
C o n t r o l
W a t t h o t e r
C a b
D
E m e g
C a
D
E m e g
C a
D
E m e g
C a
D
E m e g
C a
C
E m e g
C a
B
E m e g
P C
B n t r o l
S t a r v
P C
B n t r o l
S t r v
C h a r g i g t o r
P C
B
C h a r g i t o r
P C
B
L e v c o r d e r
H e
W t e r
L e v c o r d e r
T a t e r
S p a r e
S e l s y n s
U n i t
S e l s y n s
U n e l s y n s
U n l o c k s
S t a t i o n
T r a n s d u c e r s
R e c o r d e r s
M o n i t o r s
V i b r a t i o n
S p a r e
S p a r e
S p a r e
S p a r e
W e a t h a t i o n
A b o v e
C o n t i n u o m
C o n t i n u
B l o w
Battery Charger and Inverter (1989), Misc. Changes MRE
4. 225A Breaker located on A FLoor behind Inverter.
furnished by the Government.
with equipment as indicated and detailed drawing are detailed drawing and switchgear Nos.11, 12, and 13
3. Switchboards with equipment as indicated and
"E" Frame, 2P.
2. All 115V AC Feeder Circuit Breakers to be 100A.
2 Pole, except Battery Breaker to be 225A, 2P, as shown.
1. All 125V DC Circuit Breakers to be 100A. "F" Frame, NOTES:
Control
Auto Start-Stop
Control Power
Unit Heater DC
Note 3
5-15-01
U n
E x c i t e r
F i e a s h i n g
U n c i t e r
F i e a s h i n g
U n c i t e r
F i e a s h i n g
FIELD FLASHING and INVERTER SUPPLY
2-21-13 MRE
C o n t r o l
U n c i t e r
C o n t r o l
P C
B
D
C o n t r o l
P C
B
D
C o n t r o l
P C
B
D
C o n t r o l
S t a
S e r v
S S
C o n t r o l
S t a
S e r v
V
R e l a y s
H a r t i n g t n e
L i l a y s
Y a n k t o n
J u n c t i o n
P C
B n t r o l
S p a r e
C o n t r o l
V
C o n t r o l
U n c i t e r
C o n t r o l
P C
B
D
S e r v n t r o l
V a
S n t r o l
S t a
S e r v
X f m r
C o n t r o l
P C
B
D
C o n t r o l
P C
B
D
C o n t r o l
V C
B
C o n t r o l
U n c i t e r
C a b
A
C a b
C a b
F e e d i p
S p i l l w y
G a t h a t i o n
C l i m a t r o n i s
A u a l e r
S i e s m i c
S p a r e
S p a r e
V n e l
T e l e p h o o m
V n e l
T e l e p h o o m
O u t l e t
I
B
B a t t e h a r g e r
E m e r g e n n e r a t o r
W a r n i r n
F i s h e r m a n
X f m r
I n v e r t p a s s
F d g
F d g
S y n c h r o n i z e r
A u t o m a t i c
F
R I
L
S p a r e
F
R I
L
S p a r e
V a l v e
U d u l a t i l v e d u l a t i m i n g
L i c l o s i n g
P o w p p l y a t u s
M e t w l v d u l a t i n g
F
R I
B
T B I
R
S p a r e
R
R I
B
O u t l e t a t
M e t e r o w
M e t e r o w a t u s l t
C o n t r
C
X m p
5DCB and 6DCB Revised
MG-OPN83E2101.3
L t
T C
D E
L t
T C
D E
L t
T B
C
L t
T D
E
L t
T F
L t
T B
L t
T C
D D n g e
P n
R S
V
R E
G
150A 150A
#14
From MCC #14
From MCC
3-11-15 MRENew 150 Amp Battery Chargers
T e p s p l a y s
W a t
T
E R
S
N P
V E
N U
E
BY-PASS
AC
OUTPUT
AC
"A" FL
DC INPUT
SUPPLY BKR
5DCB ESS. AC
63SX
31F
BATTERY
STATION
125VDC
86T1
HR
71QL
A
B
HR
EXC.
64F
ANN
FIELD
V
V
A
387E
387E
WHM
63SX
71QL
5C
ANN
5C
HR
T2
GCB 362
5P ANN
HR
PCB 462
65SNL
A
GSB
S P
A R
E
VGR
41E
TRANSFORMER
POTENTIAL
POWER
378,1300ADC MAX
250VDC,793ADC NORMAL
B R
A K
E
G E
N
IG
H T
C R
E E
P
13.8KV/320V
600KVA
A
300G
B
300G
B
A A
B
A
B
A
B transfer PCB current transformers are connected to differential bus PCB must be in open position before disconnects can be
5. Line grounding switches, line PCB isolating disconnects and
24 Volts per Hertz Relay
27 Undrevoltage Relay
41E
Time Overcurrent Relay
Instantaneous Overcurrent Relay50
51V
Voltage Supervised Time Overcurrent Relay
78 Out of Step Relay
81 Frequency Relay
W/V Watt / Var Transducer
HARTINGTON
Transformer Protective Relay
ES
GCB Generator Circuit Breaker
RTD-Resistance Temperature Detector
RES Remote Synch
13 Synchronous Speed Switch
Gen. Air Brake Intermittent Timer
33-7
VCB322
WIL WIL WIL WIL
VCB226
UNIT VCB'S
VCB224
VCB222
33-7
PCB462
T3
TLM
DIGITAL
TLM TELEMETERING
46.419 MVA
V
TDTD
R E
S
ANN
SS-2
TRIP
IN PARALLEL
13.8KV, 97KA
1-2000/5
5/6
800/5
75 RPM
0.95 PF
ISOLATING
LINKS
13.8KV/480V
1000KVA
STA. SERV.STA. SERV.
TRANSF.TRANSF.
NO.1NO.2
ANN
3-2000/5
3-2000/5/5
3-2000/5
3-100/5
SS
R I
I.C.
N
WH
N
3-2.5/5
WH
W
TD
W
51X
ACB226AS
49T 49T
UNITUNIT
ANN
SS-1
TRIP
SD
5C
1-2000/5
0.19
800/5
5/6
A
33-7X
63C
86T1
ES
HR ANN
65SD
5C
63QTL ANN
0.19
SS
R I
3-2000/5/5
3-2000/5
2 2
13.8KV13.8KV
49TX
59ST
1-200/5 1-200/5
TO EXTERIOR
STA. SERV. SWG.
(SH,2)
3-400/5
69-165
SEE
NOTE 3
115KV MAIN BUS
L L
S
V V
F F
SS
MAIN BUS VOLTAGE
115KV TRANSFER BUS
VVF
3-400/5
SS
RES7RES6
(SH,2)(SH,2)
SEE
NOTE 3
69-265
INCOMING
M M
SYN
BUS
49TX
UNIT
SD
5C
1-2000/5
0.19
800/5
5/6
33-7X
63C
86T1
ES
HR
ANN
65SD
GCB362
5C
63QTL ANN
3-2000/5/5
3-2000/5
20AI
CO
1-200/5
3-400/5
M
DFR
A0
363 263
49TX
VCB362
ANN
13.8KV
T
ANN
65SD
FBM
SISI
RP
SNL 13
30X
95X
PMG
S N
L
A N
N
A C
T U
A T
O R
O N
IN
S T
R
B D
WVAR
TS
TS
3G
W/V
TD
W
TDTD
VAR
WVARPFASA
V
VS
V
TD
PS
SS
SSSS
RES4
(SH,2)
VS
W/V
TD
DFR
TS (METERING)
(RELAYING)
69-165 69-265
69-365
27T
DFR
RES5
(SH,2)
NOTE 3
A0
SEE
NOTE
69-365
SCS
25X3
25X1
25X2
M
W
VAR
TS
SS
DIGITAL
TLM
NPPD
RES3
(SH,2)
VS
W/V
TD
DFR
M
W
VAR
TS
SS
RES2
(SH,2)
VS
W/V
TD
DFR
M
W
VAR
TS
LINE
YANKTON
JUNCTION
LINE
SPIRIT
MOUND
LINE
SS
VS
DFR
M
W
VAR
TS
761861
108 KHz
RELAYING
T
R
A0
A0
BLOOMFIELD
LINE
RES1
(SH,2)
WH
3 ELEMENT, 4
WIRE, GRD Y
METRING
DEVICE
20AI
RUNNING
TSTSTS
Complete Shutdown
Partial Shutdown
Exciter Field Ground Relay
Governor Shutdown Solenoid
Bus Differential Relay
Generator Differential Relay
Emergency Shutdown
Temperature Relay Bulb
Thermostat
Ammeter
Frequency Indicator
Fly Ball Motor
Lamp-Synchronizing
Motor Operator
Permanent Magnet Generator
Phase Shifter
Synchroscope
Speed Indicator
Voltmeter
VARmeter
Wattmeter
Watthour Meter
White Indicating Lamp
Watt Transducer
Var Transducer
Volt Transducer
Ammeter Switch
Receiver-Carrier
Rectifier Pack
Synchronizing Switch
Transmitter-Carrier
Transfer Switch
Voltage Regulator
Voltmeter Switch
Frequency Recorder
Temperature Recorder
Voltage Recorder
VAR Recorder
Watt Recorder
Unit Bearing
Temperature Recorder
5C
5P
PF
W/V
TD
A
F
FBM
L
M
DFR
PMG
PS
S
SI
V
VAR
W
WH
WIL
W
TD
VAR
TD
TD
V
AS
R
RP
SS
T
TS
VR
VS
F
T
V
VAR
W
UBT
TD
LEGEND:
relays when permissive switch is operated.
permissive switches so that only one disconnect can be closed at permits closing of grounding switches only when the associated
Power Factor Meter
Watt/VAR Transducer
63QG
63QG
14400/120 V
14400/120 V
MAIN BUS
IN
C
O M
IN
G
R U
N N
IN
G
86T3
300G
300G
300G
300G
40 27
300G
Lock-Out Relay
300G
387E
387E
HR
HR
387E
86T2
387E
VR
ANN
387E
51V
64F51N
NOTES:
1. Generators No. 1 and 2 are identical to generator No 3.
Connections differ only where indicated
2. REMOVED
3. Transfer switches for transformer differential relaying are combined with permissive switches for MOD operation so that
4. Transfer bus motor operated disconnects are interlocked by a time. Operation of disconnects is interlocked so that transfer closed or opened.
disconnects are open and in turn closing of isolating and motor operated disconnects only when grounding switch is open.
line motor operated disconnects have key type interlock which
Overspeed Switch
Underspeed Switch
20AI
Auto Synchronizer
Wicket Gate Position Switch
Bearing Thermal Relay
Loss of Excitation Relay
Exciter Field Breaker
46Q Negative Sequence/Time O.C. Relay
49T
Transformer Thermal Relay
51N Neutral Overcurrent Relay
59ST Potential Indicator
59 Overvoltage Relay
63C CO Pressure Switch
63QG Governor Low Oil Press. Sw.
63QTL Turb. Guide Brg. Low Oil Press. Sw.
64F
65SD
65SNL Governor Speed No Load Solenoid
Permissive Switch
87B
87G
87T Transformer Differential Relay
Generator Protective Relay
387E
HR Hand Reset
SCS Auto Sync. Cutout Switch
7X
NPPD
HR
7X
Y
37.5/50 MVA
Y
TRANSF 2
Y
TRANSF. 1
37.5/50 MVA
WH
L E
A S
IN
E
DFR
F
S
H ,2
TB
59ST
MB
59ST
59ST
2T 1T
59ST
SYNC. VOLT.
CORR. TRANSF.
SYNC. VOLT.
CORR. TRANSF.
Digital Fault Recorder
311L
M
67G
BFI
M
67G
311C
I A,B,C
V A,B,C,N
V A,N
I A,B,C
BF829CS 311L
M
67G
M
67G
311C
I A,B,C
I A,B,C
BF729CS
M
67G
M
67G
I A,B,C
I A,B,C
311L
M
67G
M
67G
311C
I A,B,C
V A,B,C,N
V A,N
I A,B,C
BFI T0
87B115
7979 7979
21-8A
W
VAR
A
W
VAR
A
W/V
TD
V
VS
25L
21 Distance Element
25L Sync Check
32 Directional/Reverse Power Relay
50BF Breaker Failure
67G Directional Ground Element
86B115 Bus Differnetial Lock-Out Relay
86BF115 Breaker Failure Lock-Out Relay
79 Auto Reclose
DCB Directional Comparison Blocking
311L Line Protective Relay
311C Line Protective Relay
487B Bus Differential/Breaker Failure Relay
29 Breaker Failure Cut-Out Switch
Metering (V,A,W,VAR)M
BFI
DCB
V A,B,C,N
TRIP
PCB
DCB
BFI BFI
POTT POTT
BFI T0
87B115
TRIP
PCB
TRIP
PCB
87B115-1/2
TO
MIRRORED
BITS
RELAYS
OTHER
END
TO
87B115-1/2
87B115-1/2
TO
87B
87B115-1
86B115
ALL PCB'S
ANN
86BF115
50BF
87B
50BF
CURRENTS FROM BKRS
162,262,362,462, 562,662,762,862
87B115-1: A/B PHASE
87B115-2: C PHASE
87B115-2
ALL PCB'S
ALL 65SNL
ANN
POTT Potential Overreach Transfer Trip
DTT Direct Transfer Trip
21-7A 21-6A 21-5A
V A,B,C,N
V A,N
V A,B,C,N
V A,N 311L
67G
67G
311C
I A,B,C
I A,B,C
BF629CSBFI BFI
POTT POTT
TRIP
PCB
TRIP
PCB
V A,B,C,N
V A,N
V A,B,C,N
V A,N
MIRRORED
BITS
RELAYS
OTHER
END
Line Differential Element87L
TRIP
PCB
TRIP
PCB
V A,B,C,N
V
A,B,C,N311L 311CV
A,N V
A,N
BF529CSBFIBFI
TRIP
PCB
TRIP
PCB
BFI BFI
V A,B,C,N
V A,N
BF429CS
TRIP
PCB
BFI FROM BKRS
462,562,662,762,862 programmed to work for the Yankton Line
11. POTT/BFDTT scheme in transfer breaker relays only relays 87B115-1 and 87B115-2 individually.
10. Breaker failure tripping function shall be performed by both handles C Phase currents.
9. 87B115-1 handles A Phase and B Phase currents, 87B115-2
See AC control diagram for additional details.
8. All line relay fuses/switches not depicted on this drawings.
See schematic for additional details.
7. All line relay inputs/outputs not depicted on this drawing.
one permissive switch can be closed at one time.
potentials from each line to transfer breaker line relays. Only
6. Permissive switches for MOD operation used to transfer
TS
DFR
DFRDFRDFRDFR
I A,B,C
25L
25L
M25L87L
CURRENTS
OTHER
END
25L
487B 487B
21-7B 21-7A 87L-6B 21-6A 21-5B 21-5A 21-4B
A
21-8B 21-8A
TO
87B115-1/2
TO
87B115-1/2
TO
87B115-1/2
TO
87B115-1/2
TO
87B115-1/2
BFI T0
87B115
BFI T0
87B115
BFI T0
87B115
Q Y
D
Y
A
Q Y
C
Y
A
Q Y
A
Y
A
Q Y
D
Y
A
Q Y
C
Y
A
Q Y
A
Y
A
Q Y
D
Y
A
Q Y
C
Y
A
Q Y
A
Y
A
Q Y
D
Y
A
Q Y
C
Y
A
Q Y
A
Y
A
Q Y
C
Y
A
Q Y
D
Y
A
Q Y
B
Y
QY4A
3Y-1200
400:5A
Q Y
A
Y
A
Q Y
A
Y
A
Q Y
A
Y
A
V Y
A
Y
,0
V
V Y
A
Y
,0
V
V Y
A
Y
,0
V
V Y
A
Y
,0
V
V P
B
A
,0
V
V P
B
A
,0
V
MIRRORED
BITS
RELAYS
OTHER
END
POTTBFDTT
21-4A
Z
C S
Z
C S
W
VAR
A
W
VAR
A
W
VAR
A
V V V V
W/V
TD
VAR
W
TS
BFDTTBFDTTBFDTTBFDTT
Designed by:
Drawn by:
Checked by:
Reviewed by:
Submitted by:
Chief:
Spec. No.:
Contract No.:
Drawing Code:
Date:Scale:
As Shown
Plot Scale Ratio:
Design File:
MADEDescriptions
U.S. ARMY ENGINEER DISTRICT
CORPS OF ENGINEERS
OMAHA, NEBRASKA
DACW 45
DACW 45Sect.
DATE APPR'D
MISSOURI RIVER
GAVINS POINT DAM-LEWIS AND CLARK LAKE
3-8-90
FEBRUARY 1999
PAB
SHEET 1
MRE
NEUTRAL C.T. AND GENERATOR RELAY CHANGES MRE
CJW
$$ - THINK VALUE ENGINEERING - $$
Revisions
CMS
SINGLE LINE DIAGRAM
MG-OPN83E301.16
3-1200A POLES
I.C.
13.8 KV-3 PHASE
KV, 50KA
ONAN/ONAF
T.S.
T.S.
TS
TS
V
F
T1
PCB262
ANN
PCB462
5C
VCB228
5P
HR
VCB224
65SNL
ANN
ONAN/ONAF
37.5/50 MVA
ONAN/ONAF
63SX
71QL
5C
T3
3000A, 13.8
13-30
13-95
(B O)
1-16-11 ECHO
2-28-13 GENERATOR AND REGULATOR REVISIONS
NEW SEL WATT HOUR METERS
AS-BUILTS SEL 300G and 387E
4-13-15
2-15-16 REV 8: AS-BUILT RELAY REPLACEMENT BY ECHO POWER
AS
WH
W
WTD
1SQA5
1SQA4
1SQA3
1SQC3
1SQC5
1SQC4
T .S
0.25 MF
25X3
25X3
12KV
R
B V
C
R
B V
B O
25X1
Ground
Running Incoming
59ST
R
B V
C
R
B V
B O
GSB
1TNQ
T.S.
W H
M
200/5A
200/5A200/5A
3TNQ
2TNQ
T.S.
T.S.
25X2
M
V A
M
V A
M
V A
SCS
AUTO
SYNC
R
B V
A
R
B V
A
R
B V
A
H1
51C
51B
51A
E
Q O
E
Q C
E
Q B
E
Q A
13,800/480V
1000KVA, 3PH,
Transf. No.2
To Sta. Serv.
R W
V T
P F
V A
R
W
M
Q C
M
Q C
M
Q C
M
Q C
M
Q C
M
Q A
W V
T
M
Q A
M
Q A
M
Q A
M
Q A
M
Q A
W H
M
M
Q A
A S
A
M
Q C
M
Q C
M
Q A
M
Q B
M
Q B
M
Q B
M
Q B
M Q
M
Q
R
B V
A
L L Lamps
Synchroscope
F
F
V
V
H2 H3
X2 X3
97KV A B C
S
Q B
O
V
F
R
R
1MVA1
1MVB0
R
2000/5A
3MQO
3MQA
3MQC
0.25 MF
2MVC
2MVBO
2MVA
B
A
2GQO
2GQC
2GQB
2GQA
C B
A{
E
Q O
Designed by:
Drawn by:
Checked by:
Reviewed by:
Submitted by:
Chief:
Spec. No.:
Contract No.:
Drawing Code:
Date:Scale:
As Shown
Plot Scale Ratio:
Design File:
MADEDescriptions
OMPUTER
IDED
ESIGN &
RAFTINGD
D A
C
U.S. ARMY ENGINEER DISTRICT
CORPS OF ENGINEERS
OMAHA, NEBRASKA
DACW 45
DACW 45Sect.
DATE APPR'D
MISSOURI RIVER
GAVINS POINT DAM-LEWIS AND CLARK LAKE
3-8-90
FEBRUARY 1999
PAB THREE LINE DIAGRAM
SHEET 1
3GQ0
2000/5A
3GNQ
3GNQ0
3GNQA
3GNQB
3GNQC
5/6A 800/5A
2GQ0
2000/5A
2GNQ
2GNQ0
2GNQA
2GNQB
2GNQC
5/6A 800/5A
1GQ0
2000/5A
1GNQ
5/6A 800/5A
G
Q A
G
Q B
G
Q C
G
Q
1GNQA
1GNQB
1GNQC
1GNQ0
T
T
T
T
T
T
T
T
T
T
T
T
A B C
T
T
T
T
T
T
T
T
T
T
T
T
A B C
T
T
T
T
T
T
T
T
T
T
T
T
A B C
0.25 MF
12 KV
12 KV
2RVC
2RVBO
2RVA
A
B
C
3RVC
3RVBO
3RVA
1RVC
1RVA
1RVBO
C
3MQB
3MQO
2000/5A
2MQB
2MQO
2000/5A
14400/120 V
3MVC
3MVBO
3MVA
14400/120 V C
B
A
2000/5A
2MQO
2MQA
2MQC
3TQO
2000/5/5A
3GQO
3GQC
3GQB
3GQA
5 4
3 2 1
T
Q O
T
Q C
T
Q B
T
Q A
V O
H1 H2 H3
X1 X2 X3
A B C
97KV A B C
T
Q C
B
T
Q B
A
T
Q A
C
3TQC
3TQB
3TQA
R
B V
A
R
B V
B O
R
B V
C
B
A
C
V S
1MVC1
W V
T
T D
V
S T
W P F
M C
V
T.S. 14,400/120V
V O
2000/5/5A
2TQC
2TQB
2TQA
2TQO
2000/5/5A
1TQC
1TQB
1TQA
1TQO
C B
A
1GQO
1GQC
1GQB
1GQA
2000/5/5A
2000/5A
T
Q O
T
Q A
T
Q B
T
Q C
1TQC
1TQB
1TQA
1TQO
1TQO
1TQA
1TQB
1TQC
T
Q C
B T
Q C
B
T
Q B
A T
Q B
A
T
Q A
C T
Q A
C
S
Q A
S
Q B
S
Q C
100/5A
S
Q A
S
Q C
S
Q A
S
Q C
1RBVA
SS
M B
V A
V O
R B
V A
S B
V A
M in s lt a g e
G r o u n d
R u n n in g
In c o m in g
VO
RBVA
SBVA
127 225 227
2EVA
2EVBO
2EVC
1EVA1
2MQA
2MQB
2MQC
2MQO
W H
25/5
1MQA
1MQB
1MQC
1MQO
NORTH BANK SOUTH BANK
CONTINUED ON SHEET 2
51N
0.19
NEUTRAL REACTOR
0.19
NEUTRAL REACTOR
0.19
NEUTRAL REACTOR
tranformer correcting voltage
Synchronizing
5/5A
2000/
5A
2.5
M
Q C
A
387E-3-A
387E-3-B
387E-1-A
387E-1-B
300G-1-A
300G-1-B
1MVC
1MVBO
1MVA
W W W
MRE
T
Q O
T
Q A
T
Q B
T
Q C
S
Q O
S
Q A
S
Q B
S
Q C
2000/5A 50/5A
100/5A
226 228
E
Q A
E
Q B
E
Q C
100/5
500 KVA 3PH 13.8/12.47KV
TRANSFORMER T4
EXTERIOR STATION SERVICE
13,800/12,470V
500KVA, 3PH,
XFMR #T5
To Sta. Serv.
Exterior
0.95 PF-75 RPM
46.419 MVA,13.8KV,3PH
GENERATOR NO.3
0.95 PF-75 RPM
46.419 MVA,13.8KV,3PH
GENERATOR NO.2
H1 H2 H3
X1 X2 X3
A B C
97KV A B C
CURRENT JACKSCURRENT JACKS
CURRENT JACKS
A
13,800/480V
1000KVA, 3PH,
Transf. No.1
To Sta. Serv.
W T
D
W
M
Q C
M
Q B
M
Q A
M
Q
2000/5
1MVC1
1MVA1
T.S. 14,400/120V
1EVC1
M
Q A
M
Q A
A S
M
Q B
M
Q C
M
Q C
T.S.
1MQA1
1MQB1
1MQC1
1MQO1
M
Q B
A
M
Q A
A
1EVA
1EVBO
1EVC
1EVB0
NEUTRAL C.T. AND GENERATOR RELAY CHANGES MRE
CJW
S
Q
3PH 13.2-66.4/115KV
37.5/50MVA ONAN/ONAF
TRANSF. NO.1
3PH 13.2-66.4/115KV
37.5/50MVA ONAN/ONAF
TRANSF. NO.2
3PH 13.2-66.4/115KV
37.5/50MVA ONAN/ONAF
TRANSF. NO.3
B C
97KA I.C.
Poles in parallel 13.8KV
Neutral ACB's 3-1200A A
S
Q O
2 4 531 R
B V
A transformer voltage correcting
Synchronizing
R
B V
A
X1
T .S
S
Q C
A
S
Q A
A
S
Q B
S
Q O
M
V A
$$ - THINK VALUE ENGINEERING - $$
Revisions
CMS
14,400/120 V 14,400/120 V
MG-OPN83E304.10
1MVB0
1MVC2
1MVA2
1MVB0
R W
V T
100/5
2000/5
Regulator
Voltage
1-16-11 ECHO
2-28-13 GENERATOR AND REGULATOR REVISIONS
0.95 PF-75 RPM
46.419 MVA,13.8KV,3PH
GENERATOR NO.1
NEW SEL WATT HOUR METERS
AS-BUILTS SEL 300G and 387E
4-13-15
2-15-16 REV 8: AS-BUILT RELAY REPLACEMENT BY ECHO POWER
14,400/120 V
WH
WTD
W
R
B V
1:12
C2
8E-BP
a
IN CONTRACT.
3 NOT SUPPLIED UNLESS SPECIFIED
2 REMOTE MOUNTING NOT RECOMMENDED
1 MUST BE MOUNTED IN ONE LOCATION ONLY
SYMBOLS:
OPERATION INPUT SIGNAL
& UNIT LOCKOUT RELAY
GENERATOR DIFFERENTIAL
C
B
A
VDC
PANEL
CONVERTER
DC/DC
BALANCE
REGULATOR
24VDC
CURRENT TRIP
LOSS OF FIELD
CURRENT COMPENSATION
DIFFERENTIAL REACTIVE
CURRENT REGULATOR
TRANSFER TO FIELD
FAILURE AUTOMATIC
VOLTAGE REGULATOR
COMPENSATION
LINE DROP
AUTOMATIC TRACKING
V/HZ LIMIT
PF/VAR REGULATOR
NULL BALANCE
PARALLELING
REACTIVE DROOP
OVEREXCITATION LIMIT
INSTANTANEOUS
LIMIT
TIMED OVEREXCITATION
LIMIT (TWO LINE)
MINIMUM EXCITATION
LIMIT (STRAIGHT LINE)
MINIMUM EXCITATION
FIELD CURRENT REG
STATOR VOLTAGE REG
FUNCTIONS PROVIDED
=40VA
BURDEN
INPUT
SIGNAL
CT
CURRENT)
(FIELD
SETTER (DC)
REFERENCE
VOLTAGE)
(STATOR
SETTER (AC)
REFERENCE
REGULATOR OUTPUTS
REGULATOR INPUTS
INTERFACE
PT & CT =5VA
SENSING BURDEN
CURRENT INPUT
VOLTAGE & SIGNAL
STATOR PT
+24VDC
CBA
BREAKER
UNIT
13,800V, 3PH, 60HZ
MAIN BUS
C
B
A
G
LOCKOUT RELAY
TO UNIT
TRIP SIGNAL
EXCITER FAULT
DEVICE
GROUNDING
52G
(RN)
CT-G
2000:5
CTOCTI
MODE OFF-TEST
MAINTENANCE
PSS RESET
41E TRIP - CLOSE
LEAD-LAG
BRIDGE LOCKOUT
CONT.PWR.INPUT
+/-24VDC
CONT.PWR.INPUT
125VDC
MOUNTED
REMOTE
MOUNTED
CUBICLE
CONTROL SWITCHES & PUSH BUTTONS
CONTROL LOGIC
SELECTION
BRIDGE
RAISE - LOWER
REF. SETTER
ON - OFF
SELECTION
REGUL. MODE
MODE SELECTION
LOCAL - REMOTE
DESCRIPTION
C1
BC
PF = 1.0
VP02/P03
V (STATOR)
CTI
C1/C2
I
V
C.T. CURRENTS.
P.T. VOLTAGE AND
STATOR VOLTAGE,
RELATIONSHIP OF
VECTOR
PF = ZERO
ANV
CTI
C1/C2
I
V
AB
VP01/P02
V (STATOR)
CA
VP03/P01
V (STATOR)
ROTATION
OF PHASE
DIRECTION
FU
AUXILIARY
POWER
320 VAC
GATE SYNC
SUPPLY
115 VAC
FAN
SUPPLY
(N)
(RN)
(RN)
(R) (R)
CONTROL POWER
125VDC 1 AMP NOMINAL
(R)
VDC
REGULATOR NULL BALANCE
METER 1 -0- 1 SCALE
1-0-1 MA MOVEMENT
(RN)
EXCITER
(N) NOT SUPPLIED BY SIEMENS POWER CORP.
(R) REMOTE MOUNTED.
(RN) REMOTE MOUNTED NOT SUPPLIED BY
SIEMENS POWER CORP.
FIELD CONNECTION
(86C)
SW
P02 P03P01
2 PT'S
14,400-120V
(RN)
FAN SELECTION
ISOL-B1
BAM
10-0-10VDC
1-0-1 SCALE
CROSS CURRENT
COMPENSATION
CRITICAL &
NON-CRITICAL
CONTACT
OUTPUTS.
ANN
ANNUNCIATOR
AN-3196
0-18KV
STATOR
VOLTS
ANNUNCIATOR
PUSHBUTTONS
120VAC
LIGHTS, RECEPTACLES &
(RN)
GENERATOR DATA:
46,419 KVA
0.95 PF
13,800 VAC
75 RPM
3 PHASE
60 HERTZ
IRVA IRVBD IRVC
320 VAC
FANS
CURRENT
GATING
AUX. FAN POWER
FIELD
59F
31F
0-500V
2000:5A
CT1/CT2
V
NEMA 1 NEMA 12
REDUNDANT BRIDGES
REDUNDANT FANS
FAN COOLED
CONVECTION COOLED
VDC CEILING
VDC NOMINAL
ADC FORCING
ADC MAX CONT.
ADC NOMINAL
POWER CONVERTER
X3
X2
X1 o
PRI TAPS
PRI BIL KV
C RISE
% IMP
SEC VOLTS
PRI VOLTS
KVA
SEC CONN.
PRI CONN.
DRY TYPE - CLASS AA
SUPPRESSOR
VOLTAGE
TRANSIENT
RELAY
OVERVOLTAGE
FIELD
GENERATOR FIELD
RESISTOR
FLASHING
FIELD
125 VDC
FIELD FLASH SUPPLY
POWER POTENTIAL TRANSFORMER
H1
H2
H3
CL FUSES
A
B
C
41E
SHAFT VOLTAGE
SUPPRESSION
(10 SEC)
(R)
41F
(R)
SEC. TIME AT CEILING
13.8 KV
6.5
4- 8€2 1/2%
DISCHARGE
RESISTOR
0.128 AT 25 C
1300A MAX. CONTINUOUS
250 VOLTS RATED
1600A
600VAC
CT1
CT2
CT3
PHASE BALANCE RELAY-46E
AND OVERCURRENT RELAY-50/51E
49T1 49T2
50/5
INSULATION CLASS H 220 C
DR
FIELD VOLT
0-500 VDC
(R)
FIELD
0-1500A
SH
1500A
320 VAC
GATING
CURRENT
FANS
o
METER
EXCITER
STATIC EXCITATION SYSTEM
THREE LINE DIAGRAM
R.T.L.
R.T.L.
K.R.T.
gp06307.dgn
COMPUTER
IDEDA
DESIGN &
RAFTINGD
Designed by:
Drawn by:
Checked by:
Reviewed by:
Submitted by:
Chief: Section Contract No.:
Plot Scale Ratio:
Design File:
Date:
Drawing Code:
Symbol Date Approved
Revisions
Descriptions
U.S. ARMY ENGINEER DISTRICT
CORPS OF ENGINEERS
OMAHA, NEBRASKA
A
B
C
D
12345
D
C
B
A
5 4 3 2 1
ELECTRICAL
MISSOURI RIVER
GAVINS POINT DAM - LEWIS AND CLARK LAKE
MG-OPN-83E
SEPT 1996
DACW45-94-C-0168
Manufacturer:
Siemens Power Corp.
UNIT 1 - EXCITATION SYSTEM
1:12
320A
R C
A C
A C
A C
R
W
.0
M
S
.0
M S
C U
R R
E
E D
B A
K
A L I N
G
.2
C
M
C
F R
C I T
A T I
W E
R
P O
T E
N T I
A N
S F
O R
M E
R
A
B
C
A
B
C
C T
X
X
C T
X
X
:5
A
:5
T H
Y
F
U
F U
F
U
D
E
T Y
A
V A
C
L
L
L
A B
C
P
V
A
B
C
A
E
D
NOTES:
1. SEE LINE 04 FOR DETAILS OF BRIDGE
T H
Y
F
U
F U
F
U
D
T H
Y
F
U
F U
F
U
D C
N
M
D C
P D
C N
M
C
2. NO CONNECTION ON THIS END IN
EXCITER - CONNECTS TO BUS
IN TRANSFORMER CUBICLE
DURING INSTALLATION.
INTERNALS.
E A
R T
H
G N
D
C U
B I C
L E
G N
D
G
G
G N
D
S H I E
L D
G N
D
B U
S
B R
D C
N
D C
P
F S
F S
P E
R
F S
F S
L E
D
P E
R
L E
D
S N
S N
PP
<R> K
G
<R> <W> G
K
<W>
S
S
G A
T E
S C
R
G A
T E
S C
R
P
P
S C
R
S C
R
F S
F S
F S
F S
L E
D
L E
D
S N
S N
PP
<R>G
K 2<W> S
S
G A
T E
S C
R
<W>G A
T E
S C
R
G
K
P
<R>
P
S N
S N
S C
R
S C
R
F S
F S
L E
D
L E
D
F S
F S
S N
S N
PPS
S
<R> K
G
<W>
G A
T E
S C
R
P
G A
T E
S C
R
P 1 <W> G
K
<R>
G A
T I
U B
B
.C
B O
A R
D
S C
H E
M A
T
G A
T I
U B
B
.C
B O
A R
D
S C
H E
M A
T
S C
R
S C
R 1 P E
R
L E
D
L E
D
P E
R
A S
S E
M B
L Y
T H
Y R I S
T O
R
N E
G A
T I V
E
N
T H
Y
A S
S E
M B
L Y
T H
Y R I S
T O
R
P O
S I T I V
E
P
T
Y
4FU
1FU
3FU
6FU
5FU
2FU
C
I N
P
W
A
B
C
T P
U T
NOTES:
1. BR2 IS SAME AS BR1.
2. PREFIX ON DEVICES SHOWN
FOR BR1. CHANGE THE PREFIX
TO 2 FOR BR2.
B R
B R
E 3 3
3. OVERTEMP SWITCH MOUNTED
ON HEATSINK - OPENS AT
92•C.
4. 1FU-6FU 1250A,700V.
T S
T S
N
G F
M
T S
T S
P
G F
M
T H
Y
F
U
F U
F
U
D C
P
AC/DC MAIN POWER CIRCUITS
R.T.L.
K.R.T.
gp06320a.dgn
COMPUTER
IDEDA
DESIGN &
RAFTINGD
Designed by:
Drawn by:
Checked by:
Reviewed by:
Submitted by:
Chief: Section Contract No.:
Plot Scale Ratio:
Design File:
Date:
Drawing Code:
Symbol Date Approved
Revisions
Descriptions
U.S. ARMY ENGINEER DISTRICT
CORPS OF ENGINEERS
OMAHA, NEBRASKA
A
B
C
D
12345
D
C
B
A
5 4 3 2 1
ELECTRICAL
MISSOURI RIVER
GAVINS POINT DAM - LEWIS AND CLARK LAKE
MG-OPN-83E
SEPT 1996
DACW45-94-C-0168
1:12
320B
A
K
F U
A
C R
C
S
C
K
R
W
M
R
W
M
A
K T
K
F U
A
K T
K
F U
V D
C
F I E
E R
V O
L T
A
L A
Y
(3
D C
P D
C N
P
N
A
K
F U
A
C
C
F
A
A
(D M
T
H
A P
P L
D A
V
T R
A N
S D
U C
E R
D C
N
D C
H
2 3
A
M V
A
A
M V
D B
F I E
L D
A M
P S
R
B
K
.0
W
R
A
K
.0
W
C
A
V m f d
A
B
E
F
A
B
G
C
D
E
(D M
(R
C
V
C T
B
C T
B
F I E
L T
M E
T E
R
F V
M
F I E
L T
M E
T E
R
F V
M
M
C O
M
A
K
F U
B
A
K
F U
B
C
R
A
S E
C
.5
M S
S
.9
M S
F N
Q
R
F U
V S
F N
Q
R
F U
V S
V S
W
M S
V S
W
M S
(R
N E
R A
T
E
L D
T Y
P E
F
1 5
A
B
C
D
(R
V D
C
F I E
L D
F L
A S
H
S U
P P
L Y
D C
N
A ,6
V m f d
V m f d
V
A ,6
V
P
D
N T
B F
D
P T
B
E
,G
E A
.1
M S
N T I N
U O
U S
T O
T
S I S
T A
N
M S
R
C
D C
P
R
V S
R
V S
.5
M
W
.5
M
F 2 M
V
S T
F 1 M
V
S T
F F
P N
F I E
A S
H I
N E
L
F
A
B
C
D
E
F
G
H J
K
N O
T E
S
R E
V E
R
L A
R I
N E
R A
T
E
I T
C H I N
R
A
C
.5
M S
A
B
(S
X
C L
A M
P I
S E
M B
L Y
X
C O
P P
S
X
C O
P P
S
M
N
D C
N -
B G
N
S T
A L
L
A
F F I C I E
B L
T P
N N
E C
T I O
N
A C
K
B L
E S
L
2 2 R
R
R E
S I S
T O
R
A S
S E
M B
L Y
F F
R
R
C
S
.9
M
A C
R S
P
H
A C
R S
P
H
M
R
C
D R
A S
S E
M B
L Y
R E
S I S
T O
R R
R
2 2
U N I T
H
A S
I N
D I V I D
U
S I S
T O
S H
O W
N
R I
H E
M A
T I C U
N I T
S
S I S
T
S E
M B
L I
R
A
O
G
E
S C
H E
M A
T
A
G R
A M
D C
P
A D
C N
DC POWER CIRCUITS
K.R.T.
gp06320b.dgn
COMPUTER
IDEDA
DESIGN &
RAFTINGD
Designed by:
Drawn by:
Checked by:
Reviewed by:
Submitted by:
Chief: Section Contract No.:
Plot Scale Ratio:
Design File:
Date:
Drawing Code:
Symbol Date Approved
Revisions
Descriptions
U.S. ARMY ENGINEER DISTRICT
CORPS OF ENGINEERS
OMAHA, NEBRASKA
A
B
C
D
12345
D
C
B
A
5 4 3 2 1
ELECTRICAL
MISSOURI RIVER
GAVINS POINT DAM - LEWIS AND CLARK LAKE
MG-OPN-83E
SEPT 1996
DACW45-94-C-0168
1:12
320E
X
UNIT 1 - EXCITATION SYSTEM
1:12
SCTB
SCTB
SCTB
SCTB
CUBGND
FROM EXCITER
POWER TRANSFORMER
PRIMARY C.T.'S
CTHA
CTHB
CTHC
CTHA1
CTHB1
CTHC1
CTHN
P125
N125
GND
GND
J18A
J18B
CAT. # 443T2241
TIME RANGE: 1.5 - 6A
INST. RANGE: 2-20 TIMES
0.1 - 0.4A TAP RANGE
0.5 - 4 SEC. DEFINITE TIME
SET AT 0.1A TAP
0.5 SEC. TIME
CAT. # 427Q4170
3X 2.5A 1
INSTANT TAP T.L.
50/51E
OVERCURRENT RELAY SETTINGS
NOTE: CT WIRING TO BE 10 AWG,
50:5 CT RATIO
ABB TYPE 51Y
50/51E
G
ABB TYPE ITE46D
46E
G
(DM)
(DM)
125VDC
TAP SETTING
<G>
<G>
NOTE:
1. SEE SYSTEM THREE LINE DIAGRAM
FOR CORRECT POLARITY AND PHASE.
PROTECTIVE RELAYS
K.R.T.
R.T.L.
gp06320e.dgn
GEN SENSING PCB
6.6VAC
5A@
AUX CT
5A/0.264A
5W
AUX PT'S
120V/29.7V
GSB
CT1
CT0
X140
24VDC
(RN)
FROM STATOR PT'S
120V, 3 PH, 60 HZ
(RN)
FROM STATOR CT
PHASE B
2000 PRI/5A SEC
T
T
CTB3
CTB3
CTB3
CTB3
CTB3
CTB3
T
T
BAM
GND
V
10-0-10VDC MOVEMENT
1-0-1 SCALE
NULL
BALANCE
METER
ABB TYPE
ITE-59
P01
P02
P03
CAT.#410C1175
SHLDBUS
SHLD
TB-X140
CA
P24
C24
N24
NOTE:
1. SEE SYSTEM THREE LINE DIAGRAM
CAT. # 7007 SC-BA-GB
INPUT:10-0-10VDC
OUTPUT:1-0-1mA
CTB3
SHLDBUS
SHLD
CTB3
25SH
25A
25B
26K
26L
TO LINE 26
(120VAC)
GND <G/W>
TO REMOTE
1-0-1mA
1-0-1SCALE
(R)
P125
N125
SVM
0-18KV SCALE
0-150VAC MOVEMENT
V
SCIENTIFIC COLUMBUS
ISOL-B1
25C
25D
SCHEMATIC AC-301-346-404
24A
24B
24C
24D
24E
(DM)
(DM)
(DM)
T
SHLD
<G>
<G>
RANGE-100-150V
TIME DIAL-1-6
SET TO
P.U. AT 110VAC
TERM VOLTS.
SET TIME DIAL AT 2
FOR CORRECT POLARITY AND PHASE.
<W>
<BK> <BK>
<W>
<G/W>
1E31
1NMN
1NMP
BALANCE METER
SEE DRAWING MG-OPN-83E307.
COMPUTER
IDEDA
DESIGN &
RAFTINGD
Designed by:
Drawn by:
Checked by:
Reviewed by:
Submitted by:
Chief: Section Contract No.:
Plot Scale Ratio:
Design File:
Date:
Drawing Code:
Symbol Date Approved
Revisions
Descriptions
U.S. ARMY ENGINEER DISTRICT
CORPS OF ENGINEERS
OMAHA, NEBRASKA
A
B
C
D
12345
D
C
B
A
5 4 3 2 1
ELECTRICAL
MISSOURI RIVER
GAVINS POINT DAM - LEWIS AND CLARK LAKE
MG-OPN-83E
SEPT 1996
DACW45-94-C-0168
320F
REDUNDANT POWER SUPPLIES
K.R.T.
R.T.L.
gp06320f.dgn
2A,600V
FU26A
6A,600V
FU26B
T26
H2
X2
H1
X1
320 VAC
GATE SYNC SUPPLY
PRIMARY : 320 VAC
SEC. : 120VAC
1 KVA
TBX140
REGULATOR SUPPLY
24 VDC RELAY SUPPLY
& AIRFLOW SWITCH
ISOLATOR
2A, 600V
FU27
CONTROL POWER
125 VDC
8E-BP
L1 L2
A B
CTB1
CTB1
125 VDC STATION
BATTER…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .