FOR CONSTRUCTION 04/25/2016

NO. TYPE MATERIAL WIDTH HEIGHT THICKNESS TYPE MATERIAL JAMB HEAD SILL

*1A 1 HM 3'‐0" 6'‐8" 1 3/4" A HM J‐1 H‐1 ‐ TH‐1 1 1 HR.

*2A 2 WOOD PR 2'‐6" * 6'‐8" 1 3/4" A HM J‐1 H‐1 ‐ ‐ 2 ‐

*4A 2 WOOD 2'‐0" 6'‐8" 1 3/4" A HM J‐1 H‐1 ‐ ‐ 3 ‐

*5A 1 WOOD 3'‐0" 6'‐8" 1 3/4" A HM J‐1 H‐1 ‐ ‐ 4 ‐

*6A 1* WOOD 2'‐4" 6'‐8" 1 3/4" A HM J‐1 H‐1 ‐ MARBLE 5 ‐

*7A 2 WOOD 2'‐0" 6'‐8" 1 3/4" A HM J‐1 H‐1 ‐ ‐ 3 ‐

*8A 1 WOOD 3'‐0" 6'‐8" 1 3/4" A HM J‐1 H‐1 ‐ ‐ 4 ‐

*9A 1* WOOD 2'‐4" 6'‐8" 1 3/4" A HM J‐1 H‐1 ‐ MARBLE 5 ‐

S1A 3 HM 3'‐0" 7'‐0" 1 3/4" E HM ‐ ‐ ‐ TH‐1 6 ‐

S1B 3 HM 3'‐0" 7'‐0" 1 3/4" E HM ‐ ‐ ‐ TH‐1 6 ‐

S1C 5 HM 3'‐0" 7'‐0" 1 3/4" D HM ‐ ‐ ‐ ‐ 7 20 MIN

S4A 1 HM PR 2'‐4" 7'‐0" 1 3/4" G HM ‐ ‐ ‐ TH‐1 8 ‐

S5A 1 HM 3'‐0" 7'‐0" 1 3/4" A HM ‐ ‐ ‐ MARBLE 9 ‐

S6A 1 HM 3'‐0" 7'‐0" 1 3/4" C HM ‐ ‐ ‐ ‐ 10 ‐

S7A 1 HM 3'‐0" 6'‐8" 1 3/4" F HM J‐2 H‐2 ‐ TH‐1 11 ‐

S8A 1 HM 3'‐0" 7'‐0" 1 3/4" C HM ‐ ‐ ‐ ‐ 10

S9A 1 HM 3'‐0" 6'‐8" 1 3/4" F HM ‐ ‐ ‐ TH‐1 12 ‐

A101 4 ALUM 3'‐0" 7'‐4" 1 3/4" * ALUM ‐ ‐ ‐ TH‐1 * ‐

A102 5 HM 3'‐0" 7'‐0" 1 3/4" B HM ‐ ‐ ‐ TH‐1 * 45 MIN

A103 5 HM 3'‐0" 7'‐0" 1 3/4" B HM ‐ ‐ ‐ TH‐1 *

B101 4 ALUM 3'‐0" 7'‐4" 1 3/4" * ALUM ‐ ‐ ‐ TH‐1 * ‐

B102 5 HM 3'‐0" 7'‐0" 1 3/4" B HM ‐ ‐ ‐ TH‐1 * 45 MIN

B103 5 HM 3'‐0" 7'‐0" 1 3/4" B HM ‐ ‐ ‐ TH‐1 *

C101 4 ALUM 3'‐0" 7'‐4" 1 3/4" * ALUM ‐ ‐ ‐ TH‐1 * ‐

C102 5 HM 3'‐0" 7'‐0" 1 3/4" B HM ‐ ‐ ‐ TH‐1 * 45 MIN

C103 5 HM 3'‐0" 7'‐0" 1 3/4" B HM ‐ ‐ ‐ TH‐1 *

D101 4 ALUM 3'‐0" 7'‐4" 1 3/4" * ALUM ‐ ‐ ‐ TH‐1 * ‐

D102 5 HM 3'‐0" 7'‐0" 1 3/4" C HM J‐3 H‐3 TH‐1 13 1 HR

D103 5 HM 3'‐0" 7'‐0" 1 3/4" B HM J‐3 H‐3 TH‐1 13 ‐

E101 4 ALUM 3'‐0" 7'‐4" 1 3/4" * ALUM ‐ ‐ ‐ TH‐1 * ‐

E102 5 HM 3'‐0" 7'‐0" 1 3/4" B HM ‐ ‐ ‐ TH‐1 * 45 MIN

E103 5 HM 3'‐0" 7'‐0" 1 3/4" B HM ‐ ‐ ‐ TH‐1 * ‐

F101 4 ALUM 3'‐0" 7'‐4" 1 3/4" * ALUM ‐ ‐ ‐ TH‐1 * ‐

F102 5 HM 3'‐0" 7'‐0" 1 3/4" B HM ‐ ‐ ‐ TH‐1 * 45 MIN

F103 5 HM 3'‐0" 7'‐0" 1 3/4" B HM ‐ ‐ ‐ TH‐1 * ‐

A201 5 HM 3'‐0" 7'‐0" 1 3/4" B HM ‐ ‐ ‐ TH‐1 * 45 MIN

B201 5 HM 3'‐0" 7'‐0" 1 3/4" B HM ‐ ‐ ‐ TH‐1 * 45 MIN

C201 5 HM 3'‐0" 7'‐0" 1 3/4" B HM ‐ ‐ ‐ TH‐1 * 45 MIN

D201 5 HM 3'‐0" 7'‐0" 1 3/4" B HM ‐ ‐ ‐ TH‐1 * 45 MIN

E201 5 HM 3'‐0" 7'‐0" 1 3/4" B HM ‐ ‐ ‐ TH‐1 * 45 MIN

F201 5 HM 3'‐0" 7'‐0" 1 3/4" B HM ‐ ‐ ‐ TH‐1 * 45 MIN

A301 5 HM 3'‐0" 7'‐0" 1 3/4" B HM ‐ ‐ ‐ TH‐1 * 45 MIN

A302 1 HM 2'‐0" 4'‐0" 1 3/4" H HM ‐ ‐ ‐ ‐ * ‐

B301 5 HM 3'‐0" 7'‐0" 1 3/4" B HM ‐ ‐ ‐ TH‐1 * 45 MIN

B302 1 HM 2'‐0" 4'‐0" 1 3/4" H HM ‐ ‐ ‐ ‐ * ‐

C301 5 HM 3'‐0" 7'‐0" 1 3/4" B HM ‐ ‐ ‐ TH‐1 * 45 MIN

C302 1 HM 2'‐0" 4'‐0" 1 3/4" H HM ‐ ‐ ‐ ‐ * ‐

D301 5 HM 3'‐0" 7'‐0" 1 3/4" B HM ‐ ‐ ‐ TH‐1 * 45 MIN

D302 1 HM 2'‐0" 4'‐0" 1 3/4" H HM ‐ ‐ ‐ ‐ 14 ‐

E301 5 HM 3'‐0" 7'‐0" 1 3/4" B HM ‐ ‐ ‐ TH‐1 * 45 MIN

E302 1 HM 2'‐0" 4'‐0" 1 3/4" H HM ‐ ‐ ‐ ‐ 14 ‐

F301 5 HM 3'‐0" 7'‐0" 1 3/4" B HM ‐ ‐ ‐ TH‐1 * 45 MIN

F302 1 HM 2'‐0" 4'‐0" 1 3/4" H HM ‐ ‐ ‐ ‐ 14 ‐

EXISTING DOOR, FRAME,THRESHOLD & HRDWR.

EXISTING DOOR, FRAME / NEW HRDWR.

EXISTING DOOR, FRAME & HRDWR. / PROVIDE NEW PASSAGE LOCKSET

EXISTING DOOR, FRAME / NEW HRDWR.

EXISTING DOOR, FRAME & HRDWR. / PROVIDE NEW PASSAGE LOCKSET

EXISTING DOOR, FRAME / NEW HRDWR.

EXISTING DOOR, FRAME & HRDWR. / PROVIDE NEW HINGE STOP

EXISTING DOOR, FRAME & HRDWR.

EXISTING DOOR, FRAME & HRDWR. / PROVIDE NEW HINGE STOP

EXISTING DOOR, FRAME & HRDWR.

STAIR AND CORRIDOR ‐ THIRD FLOOR

EXISTING DOOR, FRAME & HRDWR. / PROVIDE NEW PASSAGE LOCKSET

EXISTING DOOR, FRAME & HRDWR. / PROVIDE NEW HINGE STOP

EXISTING DOOR, FRAME,THRESHOLD & HRDWR.

EXISTING DOOR, FRAME & HRDWR. / PROVIDE NEW PASSAGE LOCKSET

EXISTING DOOR, FRAME & HRDWR. / PROVIDE NEW PASSAGE LOCKSET

EXISTING DOOR, FRAME,THRESHOLD & HRDWR.

EXISTING DOOR, FRAME,THRESHOLD & HRDWR.

EXISTING DOOR, FRAME,THRESHOLD & HRDWR.

STAIR AND CORRIDOR ‐ SECOND FLOOR

EXISTING DOOR, FRAME,THRESHOLD & HRDWR.

EXISTING DOOR, FRAME & HRDWR. / PROVIDE NEW PASSAGE LOCKSET

EXISTING DOOR, FRAME,THRESHOLD & HRDWR.

EXISTING DOOR, FRAME,THRESHOLD & HRDWR.

STAIR AND CORRIDOR ‐ FIRST FLOOR

EXISTING DOOR, FRAME,THRESHOLD & HRDWR.

EXISTING DOOR, FRAME & HRDWR. / PROVIDE NEW PASSAGE LOCKSET

EXISTING DOOR, FRAME & HRDWR. / PROVIDE NEW PASSAGE LOCKSET

EXISTING DOOR, FRAME,THRESHOLD & HRDWR.

NEW DOOR, FRAME & HRDWR.

NEW DOOR, FRAME & HRDWR.

EXISTING DOOR, FRAME,THRESHOLD & HRDWR.

EXISTING DOOR, FRAME & HRDWR. / PROVIDE NEW PASSAGE LOCKSET

EXISTING DOOR, FRAME & HRDWR. / PROVIDE NEW PASSAGE LOCKSET

EXISTING DOOR, FRAME,THRESHOLD & HRDWR.

EXISTING DOOR, FRAME & HRDWR. / PROVIDE NEW PASSAGE LOCKSET

EXISTING DOOR, FRAME,THRESHOLD & HRDWR.

EXISTING DOOR, FRAME & HRDWR. / PROVIDE NEW PASSAGE LOCKSET

EXISTING DOOR, FRAME,THRESHOLD & HRDWR.

SERVICE MODULE

DOORS SCHEDULE

* PROVIDE FL 2412

EXISTING FRAME / NEW DOORS & HRDWR.

EXISTING DOOR, FRAME,THRESHOLD/ NEW HRDWR.

EXISTING DOOR, FRAME,THRESHOLD/ NEW HRDWR.

NEW DOOR, FRAME & HRDWR.

EXISTING FRAME / NEW DOORS & HRDWR.

EXISTING FRAME / NEW DOORS & HRDWR.

EXISTING DOOR, FRAME / NEW HRDWR.

NEW DOOR, FRAME & HRDWR.

EXISTING FRAME / NEW DOORS & HRDWR.

DOORS FRAME THRESHOLD

TYPE

* BI‐FOLD DOORS

HARDWARE

SET

FIRE

RATING

REMARKS

TYPICAL LIVING UNIT

* PROVIDE FL 2412

DESIGNATION DESCRIPTION MANUFACTURER MODEL NUMBER REMARKS

GB‐36 GRAB BAR X 36" BOBRICK B‐5806.99 X 36 PEENED

GB‐42 GRAB BAR X 42" BOBRICK B‐5806.99 X 42 PEENED

M‐1 MIRROR ‐ 24" W X 60" H BOBRICK B‐165 / 2460

MC MEDICINE CABINET PACE SOC‐2430

MH ‐ 24 MOP HOLDER ‐ 24" LONG BOBRICK B‐223 X 24

RH ROBE HOOK BOBRICK B‐212

SDH SOAP DISH HOLDER LENAPE LEN‐1803 COLOR: M766 MATTE ELEMENTAL TAN

SSD SLIDING SHOWER DOOR KOHLER K‐R709062‐L‐SHP BRIGHT POLISHED SILVER

TB ‐ 18 TOWEL BAR ‐ 18" BOBRICK B‐530

TB ‐ 24 TOWEL BAR ‐ 24" BOBRICK B‐530

TBH TOOTH BRUSH HOLDER LENAPE LEN‐1883 COLOR: M766 MATTE ELEMENTAL TAN

TTD‐D TOILET TISSUE DISPENSER ‐ DOUBLE BOBRICK B‐2888 SURFACE MOUNT

TTD‐S TOILET TISSUE DISPENSER ‐ SINGLE BOBRICK B‐2730 SURFACE MOUNT

WC WALL CABINET PACE CAL‐249

WC/ PTD WALL CABINET / PAPER TOWEL DISPENSER AMERICAN SPECIALTIES MODEL 0436

TOILET ROOM ACCESSORIES SCHEDULE

NOTES:

1. MANUFACTURER MODEL NUMBERS INDICATED ARE TO SET STANDARD OF QUALITY, MATERIAL, COLOR AND FINISH. EQUAL PRODUCTS FROM OTHER MANUFACTURERS ARE ACCEPTABLE.

NO. NAME MATERIAL COLOR MATERIAL COLOR MATERIAL COLOR MATERIAL COLOR HEIGHT DOOR FRAME

*1 FOYER VCT F‐1 RUBBER B‐1 PAINT W‐1 ACT C‐1 7'‐4" D‐1 FR‐1

* 2 LAUNDRY VCT F‐1 RUBBER B‐1 PAINT W‐1 ACT C‐1 6'‐8" D‐1 FR‐1

*3 KITCHEN VCT F‐1 RUBBER B‐1 PAINT W‐1 PAINT C‐2 8'‐0" D‐1 FR‐1

*4 CLOSET VCT F‐1 RUBBER B‐1 PAINT W‐1 ACT C‐1 7'‐4" D‐1 FR‐1

*5 BEDROOM VCT F‐1 RUBBER B‐1 PAINT W‐1 PAINT C‐2 8'‐0" D‐1 FR‐1

*6 BATH CT F‐4 CT B‐2 CT W‐2 PAINT C‐2 8'‐0" D‐1 FR‐1

*7 CLOSET VCT F‐1 RUBBER B‐1 PAINT W‐1 ACT C‐1 7'‐4" D‐1 FR‐1

*8 BEDROOM VCT F‐1 RUBBER B‐1 PAINT W‐1 PAINT C‐2 8'‐0" D‐1 FR‐1

*9 BATH CT F‐4 CT B‐2 CT W‐2 PAINT C‐2 8'‐0" D‐1 FR‐1

S1 ACTIVITY VCT F‐1,F‐2,F‐3 RUBBER B‐1 PAINT W‐1 PAINT C‐2 8'‐0" D‐1 FR‐1

S2 CORRIDOR VCT F‐1 RUBBER B‐1 PAINT W‐1 PAINT C‐2 7'‐8" D‐1 FR‐1

S3 LOBBY VCT F‐1 RUBBER B‐1 PAINT W‐1 PAINT C‐2 7'‐8" D‐1 FR‐1

S4 MECHANICAL CONC ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ D‐1 FR‐1

S5 TOILET CT F‐4 CT B‐2 CT W‐2 ACT C‐1 7'‐4" D‐1 FR‐1

S6 JANITOR VCT F‐1 RUBBER B‐1 PAINT W‐1 PAINT C‐2 8'‐0" D‐1 FR‐1

S7 SPRINKLER EPOXY F‐5 ‐ ‐ PAINT W‐1 PAINT C‐2 8'‐0" * FR‐1

S8 ELECTRICAL EPOXY F‐5 ‐ ‐ PAINT W‐1 PAINT C‐2 8'‐0" D‐1 FR‐1

S9 ELECTRICAL EPOXY F‐5 ‐ ‐ PAINT W‐1 PAINT C‐2 8'‐0" * FR‐1

A100 STAIR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 VARIES D‐1 FR‐1

A101 CORRIDOR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

COURT YARD A‐B EPOXY F‐5 ‐ ‐ ‐ ‐ ‐ ‐ ‐ D‐1 FR‐1

B100 STAIR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 VARIES D‐1 FR‐1

B101 CORRIDOR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

C100 STAIR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 VARIES D‐1 FR‐1

C101 CORRIDOR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

COURT YARD C‐D EPOXY F‐5 ‐ ‐ ‐ ‐ ‐ ‐ ‐ D‐1 FR‐1

D100 STAIR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 VARIES D‐1 FR‐1

* CORRIDOR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

E100 STAIR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 VARIES D‐1 FR‐1

E101 CORRIDOR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

COURT YARD E‐F EPOXY F‐5 ‐ ‐ ‐ ‐ ‐ ‐ ‐ D‐1 FR‐1

F100 STAIR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 VARIES D‐1 FR‐1

F101 CORRIDOR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

A200 STAIR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 VARIES D‐1 FR‐1

A201 CORRIDOR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

B200 STAIR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 VARIES D‐1 FR‐1

B201 CORRIDOR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

C200 STAIR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 VARIES D‐1 FR‐1

C201 CORRIDOR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

D200 STAIR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 VARIES D‐1 FR‐1

D201 CORRIDOR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

E200 STAIR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 VARIES D‐1 FR‐1

E201 CORRIDOR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

F200 STAIR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 VARIES D‐1 FR‐1

F201 CORRIDOR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

A300 STAIR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

A301 CORRIDOR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

B300 STAIR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

B301 CORRIDOR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

C300 STAIR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

C301 CORRIDOR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

D300 STAIR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

D301 CORRIDOR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

E300 STAIR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

E301 CORRIDOR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

F300 STAIR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

F301 CORRIDOR EPOXY F‐5 RUBBER B‐1 PAINT W‐1, * PAINT C‐2 8'‐0" D‐1 FR‐1

STAIR AND CORRIDOR ‐ THIRD FLOOR

* 7, 8

* 7

* 7, 8

* 7

* 7, 8

* 7

* 7, 8

* 7

* 7, 8

* 7

* 7, 8

* 7

STAIR AND CORRIDOR ‐ SECOND FLOOR

* 7, 8

* 7

* 7, 8

* 7

* 7, 8

* 7

* 7, 8

* 7

* 7, 8

* 7

* 7

* 7, 8

* 7

* 6

* 1

* 2,3

* 2

* 7, 8

* 7

* 7

* 7

* 7, 8

* 7

* 7, 8

* 7

* 7, 8

* 7, 8

* 7, 8

* 4

* 2

* 4

* 5

SERVICE MODULE

STAIR AND CORRIDOR ‐ FIRST FLOOR

* 1,4

* 6

ROOM FINISH SCHEDULE

REMARKSROOMS FLOOR BASE WALLS CEILING DOOR

TYPICAL LIVING UNIT

APPLICABLE CODES / REGULATIONS

UFC 1-200-01: General Building Requirements, Change 2, 1 Nov 2014

UFC 1-200-02: High Performance & Sustainable Building Requirements, Change 3, 7 Nov

UFC 3-600-01: Design: Fire Protection Engineering for Facilities, with Change 3, 1 March 2013

IBC 2012: International Building Code except as modified by UFC 1-200-01

IBC 2012: International Mechanical Code

NFPA 101, 2012: Life Safety Code, except as modified in UFC 3-600-01

NFPA 10, 2013: Standard for Portable Fire Extinguishers

NFPA 13, 2013: Standard for Installation of Sprinkler Systems

NFPA 20, 2013: Standard for the Installation of Stationary Pumps for Fire Protection

NFPA 30, 2012: Flammable and Combustible Liquids Code

NFPA 70, 2011: National Electrical Code (NEC)

NFPA 80, 2013: Standard for Fire Doors and Other Opening Protectives

NFPA 72, 2013: National Fire Alarm and Signaling Code

NFPA 90A, 2012: Standard Installation of Air Conditioning & Ventilation Systems

NFPA 291, 2013: Recommended Practice for Fire Flow Testing and Marking of Hydrants

ABA (Architectural Barriers Act) Accessibility Standards for DoD Facilities

Factory Mutual Global Property Loss Prevention Data Sheet 3-26, dated July 2011

USE AND OCCUPANCY CLASSIFICATION

IBC Chapter 3, 310.4 Residential Group R-2 IBC Chapter 3, 303.1.2 Small Assembly Space – Classify as Group B

Occupancy or as part of that (primary) Occupancy.

UFC 3-600-01 Personnel Housing

NFPA 101, 3.3.36.3, Apartment Building

NFPA 101, 6.1.8.2 Apartment Building

GENERAL BUILDING HEIGHT AND AREAS

IBC Chapter 5 Allowable Heights & Areas Table 503 Allowed Proposed

Height 55’ 40’

Stories 4 STY 3 STY

Area 16,000 SF 32,316 SF

IBC Chapter 5, 506.3 Automatic Sprinkler System Increase – Table

503 area limitation can be increased by 200% - Building Area allowed = 48,000 SF > 32,316 SF

CONSTRUCTION CLASSIFICATION

Type IIB Noncombustible, Unprotected

Table 601 Fire - Resistance Rating Requirements for Building Elements (Hours)

Building Element Rating

Primary Structural Frame 0

Bearing Walls Exterior Interior

Nonbearing Walls Exterior

See Table 602

Nonbearing Walls Interior

Floor Construction and Associated Secondary Members 0

Roof Construction and Associated Secondary Members 0

Table 602 Fire - Resistance Rating Requirements for Exterior Walls Based on Fire Separation

Fire Separation Distance X in Feet Rating

X < 5’ 1

5 ≤ X < 10 0

10 ≤ X < 30 0

X ≥ 30 0

FIRE AND SMOKE PROTECTION FEATURES

IBC Chapter 7, 708 & 711 Fire Partitions / Horizontal Assemblies - Dwelling

Units shall have 1/2 hour separation rating.

IBC Chapter 7, 717 Ducts & Air Transfer Openings – dampers not required at penetrations if fire resistance rating is 1 hour or less and building is protected by automatic sprinkler system.

NFPA 101 30.3.6.2.1 & 30.3.6.2.3 Doors that open onto exit access corridor shall have not less than 20 minute rating, be self-closing and self-latching.

INTERIOR FINISHES

IBC Table 803.9 Interior Wall and Ceiling Finish Requirements

R – 2 Sprinklered Class

Interior exit stairways, interior exit ramps and exit passageways C

Corridors and enclosure for exit access stairways and exit access ramps C

Rooms and enclosed spaces C

UFC 3-600-01, 2.6 Refers to NFPA 101 NFPA 101, 30.3.3.2 & 10.2 Exit Enclosures – A

Lobbies and Corridors – Class A or B Other Spaces – Class A, B or C

FIRE PROTECTION SYSTEMS

Use IBC Chapter 7 and UFC 3-600-01

UFC 3-600-01, Chapter 5 Fire Alarm Systems

UFC 3-600-01, 6 – 2.1 Complete Automatic Sprinkler System per NFPA 101 13 or 13R

UFC 3-600-01, 6 – 2.2 Smoke Detection Provide per NFPA 101, 30.3.4, 9.6

MEANS OF EGRESS

Use UFC 3-600-01 and NFPA 101

OCCUPANT LOAD (NFPA 101 TABLE 7.3.1.2)

Use Area SF / Person Occupant Load

First Floor:

Assembly 664 SF 15 SF / Person 45 Occupants

Residential 10,108 SF 200 SF / Person 51 Occupants

Second Floor 10,772 SF 200 SF / Person 54 Occupants

Third Floor 10,772 SF 200 SF / Person 54 Occupants

TOTALS 32, 316 SF 204 Occupants

NFPA 101, 30.2.1.2 Means of Egress Requirements Comply with NFPA 24.2 – requires a primary and secondary means of escape except if dwelling unit is protected by automatic sprinkler system.

NFPA 101, 30.2.2 Means of Egress Components

Building protected by automatic sprinkler – exit enclosures and doors shall be 1 hr. rated.

NFPA 101, 30.2.3 & Table 7.3.3.1 Capacity of Means of Egress

Corridors with required capacity of 50 or more – 44” min. width

Stairs width / person = 0.3”

Level Components and Ramps width / person = 0.2”

NFPA 101, 30.2.4 Number of Means of Egress Every dwelling unit shall have access to at least two separate exits. Single exit allowed if conditions of Paragraph 30.2.4.6 are met.

NFPA 101, 30.2.5, 30.2.6 & Table A7.6 Travel Distance

Common Path Limit = 50’

Dead-End Limit = 50’

Travel Distance Limit = 325’

Travel Distance from dwelling unit to a corridor door = 125’

Travel Distance from dwelling entrance door to nearest exit = 200’

NFPA 101, 30.2.8 Illumination of Means of Egress

Means of Egress shall be illuminated in accordance with Section 7.8.

ACCESSIBILITY

Use ABA Accessibility Standards for Department of Defense Facilities

Per 2012 Memo in regard to UEPH standards – comply with ADA and ADAAG standards;

requirement is only for access to the building lobby area.

LOUVER SCHEDULE

TAG DESCRIPTION LOCATION VOLUME VELOCITY W x H x D AREA FREE AREA NOTES

CFM FPM FT2 FT2

LV-1 INTAKE COURTYARD 5,940 ,000 32 x 48 x 3 10.67 6.04 1, NOTES

1. NEW LOUVER IN EXISTING WALL OPENING.

FAN SCHEDULE

EQUIPMENT LOCATION AREA SERVICE TYPE MFR MODEL No. CFM ESP ("WC) FAN MAX DAMPER POWER DISC STARTER NOTES

NUMBER RPM SONES TYPE CRTL-VOLT CRTL-VOLT HP V/PH/HZ FLA WATTS BY BY

EF-1 ATTIC STACK "A-F" DRYER EXH CENTRIFUGAL S & P PV-315X 525 0.90 1,950 12.3 B'DRAFT 0.75 115/1/60 13.8 1,2,3,4,5 EF-2 ATTIC STACK "A-F" KIT. HOOD CENTRIFUGAL GREENHECK USF-312-10-BI-4 525 0.90 1725 11.6 B'DRAFT 0.25 208/1/60 3.2 1,2,4,5

1. PROVIDE VFD CONTROL

2.BOOSTER FAN

3. DRYER EXHAUST BOOSTER FAN SHALL BE UL LISTED 705, FOR DRYER EXHAUST.

4. BACKDRAFT DAMPER - GREENHECK MODEL HBR-050.

5. PROVIDE DISCONNECT AND STARTER UNDER DIVISION 15-MECHANICAL AND TURN OVER TO ELECTRICAL FOR INSTALLATION AND WIRING.

GRILLES , REGISTERS & DIFFUSERS

ID TYPE ABBREVIATION SERVICE FACE/ NECK MAX MAX MAX DAMPER MATERIAL MFR & MODEL REMARKS/NOTES

TYPE LOCATION PANEL SIZE CFM PRESS NC

SIZE DROP

SWG-1 SIDE WALL GRILLE SWG LIVING MODULE SUPPLY 12 x 4 176 0.065 20 N ALUMINUM TITUS - CT-541-12 SWG-2 SIDE WALL GRILLE SWG LIVING MODULE SUPPLY 18 x 4 373 0.043 25 N ALUMINUM TITUS - CT-541-12

DG-1 DOOR GRILLE DG TOIL LIVING MOD TRANSFER 3,

CRG-1 CEILING RETURN CRG LIVING MODULE RETURN 12x12 230 0.018 20 N ALUMINUM TITUS - 350FL-F1 1,2, EG-1 TOILET EXHAUST EG LVG UNIT TOILETS EXHAUST 8 x 6 125 0.024 10 OBD ALUMINUM TITUS - 50F EG-2 TOILET EXHAUST EG 1ST FL TOILET EXHAUST 8X8 100 0.013 20 N ALUMINUM TITUS - 50F

CGR-2 CEILING RETURN CRG LIVING MODULE RETURN 8X8 100 0.013 20 N ALUMINUM TITUS - 50F

1. PROVIDE WITH 1" REPLACEABLE FILTER, MERV 8.

2. 2x2 LAY IN CLG.

3. BY ARCHITECTURAL.

12/7/2015 NEW UNIT FAN COIL SCHEDULE

EXISTING PROJECT COOLING HEATING

OR AREA SUPPLY OA RETURN EXT TOTAL SENSIBLE EAT EAT LAT LAT CHWS EWT LWT COIL PD BTUH EAT LAT HHS EWT LWT DESIGN BASIS TAG/ID NEW SERVED CFM CFM AIR SP BTUH BTUH DB WB DB WB GPM FT (MAX) °F °F GPM °F °F MODEL NOTES FCU-1A NEW LIVING UNIT VOLAR BARRACKS 1+1 RENOVATION 725 495 230 0.25 31,395 20,080 80.3 67.3 55 53.2 6.3 45 55 8.0 37,304 53.22 100 3.7 180 160 CARRIER 42CAA10H 1,2,3,8,9,10,11,12 FCU-2A NEW 1ST FL ACTIVITY ROOM VOLAR BARRACKS 1+1 RENOVATION 256 0 256 0.25 6,700 6,050 79 64.5 57 55.7 1.3 45 55 8.0 5,062 69 88.1 0.53 180 160 CARRIER 42CBG03D 1,3,9,12 FCU-3A NEW 1ST FL LOBBY VOLAR BARRACKS 1+1 RENOVATION 220 0 220 0.2 7,600 5,200 78.7 67.1 56.9 55.9 1.5 45 55 8.0 11,206 69.1 99.8 0.73 180 160 CARRIER 42CGB03D 1,2,3,9,12 FCU-4 EXISTING OLD LAUNDRY DEMO DEMO THIS UNIT NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 6,7 FCU-5 EXISTING VESTIBULES EXISTING TO REMAIN 120 0 120 0.2 5,200 4,200 80 55 1.0 45 55 8.0 7,600 62.5 90.0 0.55 180 160 CARRIER 42CBG03D 3,4,5,6 FCU-6 EXISTING 3rd FLOOR STAIRWELLS EXISTING TO REMAIN 370 0 370 0.2 15,400 12,200 80.0 55.0 3.1 45 55 8.0 13,500 62.5 90.0 0.98 180 160 CARRIER 42CGB03D 3,4,5,6

1. MAXIMUM FACE VELOCITY = 500 FPM.

2. HORIZONTAL FURRED-IN CONCELAED UNIT WITH IN FULLY INSULATED CEILING CAVITY, REAR OA INTAKE & RETURN.

3. 120V/1PH/60HZ

4. STANDARD FILTER, BOTTOM ACCESS.

5. EXISITNG FCU TO REMAIN IN SERVICE

6. HORIZONTAL CEILING MOUNTED

7. DEMO THIS UNIT

8. DIMENSIONAL SIZE LIMITATIONS :

9. HEATING COIL IN REHEAT POSITION.

10. FCU AND ALL ACCESSRIES MUST FIT WITHIN THE CONFINED SPACE ABOVE THE WASHER AND DRYER; 5'-11" x 3'-1" x 12" HIGH. VALVE PACKAGE MAY BE MOUNTED REMOTELY OVER THE CLOSET.

11. UNIT SHALL NOT ALLOW DEW POINT TEMPERATURES IN THE CONCEALED SPACE TO BE REACHED AND PROVIDE A SOURCE FOR MOLD TO GROW.

12. SEE SEQUNCE OF CONTROLS IN SPECIFICATIONS 15-900.

5/12/2016 3/18/2016 1/14/2016

ENERGY RECOVERY VENTILATOR (ERV)

OA SUPPLY SUPPLY SUPPLY EXHAUST EXHAUST SUPPLY EXHAUST

MARK NAME Qty LOCATION AREA DESIGN BASIS VOLUME (EXT) SP MINIMUM EXHAUST (EXT) SP Efficiency SIZE SIZE VOLTAGE POWER PHASE MCA MOP ENCL NOTES

MODEL CFM in. wg Efficiency % (CFM) in. wg MIN % (IN) (IN) HZ ERV-1- A 1 ATTIC STACK "A" CARRIER ERV-55-15H 5,940 1.2 65 3,000 0.75 65 BY MFR BY MFR 208 60 3 29.6 45 ODP 1,2,3,4, 5,6 ERV-2- D 1 ATTIC STACK "D" CARRIER ERV-55-15H 5,940 1.3 65 2,750 1.2 65 BY MFR BY MFR 208 60 3 28.7 45 ODP 1,2,3,4,6, ERV-3- E 1 ATTIC STACK "E" CARRIER ERV-55-15H 5,445 1.3 65 3,000 1.2 65 BY MFR BY MFR 208 60 3 29.6 45 ODP 1,2,3,4,5,6

NOTES

1. PRE-FILTERS MERV 8; FINAL FILTERS MERV 13.

2. UNIT 1 STACK A; UNIT 2 STACK D; UNIT 3 STACK E. SEE DRAWINGS FOR STACK DESIGNATIONS.

3. EXTERNAL STATIC PRESSURE INCLUDES INTAKE AND DISCHARGE SIDE OF FAN.

4. NO HEATING OR COOLING COILS, ONLY ENERGY RECOVERY FROM OUTSIDE AIR AND EXHAUST AIR.

5. DESIGN BASIS : GREENHECK MODEL ERV-55-15H

6. PROVIDE EXHAUST FANS WITH VFD CONTROL CAPABILITY. SEE SEQUENCE OF CONTROL IN SPEC 15-900 HVAC Controls.

FIRE PROTECTION SPRINLKLER SCHEDULE

ASR FIRE AREA NAME HAZARD AREA MAX MIN. No. HYDRAULIC DATA TYPE TYPE HEAD

RISER No. ZONE SQ. FT SQ. FT OF HEADS DENSITY AREA SYSTEM STYLE FINISH TEMP ORIFICE NOTES PER HEAD GPM/FT2 APPLICATION RATING oF SIZE

1 1-1 BARRACKS STACK A&B LIGHT 12,245 225 55 0.15 1,500 WET SWS CHROME 155 1/2' 2,3,4,5,6,7 1 1-1 CLOSET LIGHT 54 225 1 0.15 ENTIRE AREA WET PEND(C), WHITE 155 1/2" 3,4,5,6,7 1 1-1 COMMON LIGHT 142 225 2 0.15 ENTIRE AREA WET PEND(C) & SWS WHITE/CHROME 155 1/2" 3,4,5,6,7

1 1-1 WASHER,DRYER LIGHT 18 225 1 0.15 ENTIRE AREA WET PEND, CHROME 3,4,5,6,7

1 1-1 ATRIUM LIGHT 250 225 3 0.15 ENTIRE AREA WET UPRIGHT CHROME 155 1/2" 3,4,5,6,7 1 1-2 BARRACKS STACK C&D LIGHT 12,245 225 55 0.15 1,500 WET SWS CHROME 155 1/2" 2,3,4,5,6,7 1 1-2 CLOSET LIGHT 54 225 1 0.15 ENTIRE AREA WET PEND(C), WHITE 155 1/2" 3,4,5,6,7 1 1-2 COMMON LIGHT 142 225 2 0.15 ENTIRE AREA WET PEND(C) & SWS WHITE/CHROME 155 1/2" 3,4,5,6,7

1 1-2 WASHER,DRYER LIGHT 18 225 1 0.15 ENTIRE AREA WET PEND, CHROME 3,4,5,6,7

1 1-2 ATRIUM LIGHT 250 225 3 0.15 ENTIRE AREA WET UPRIGHT CHROME 155 1/2" 3,4,5,6,7 1 1-3 BARRACKS STACK E&F LIGHT 12,245 225 55 0.15 1,500 WET SWS CHROME 155 1/2' 2,3,4,5,6,7 1 1-3 CLOSET LIGHT 54 225 1 0.15 ENTIRE AREA WET PEND(C), WHITE 155 1/2" 3,4,5,6,7 1 1-3 COMMON LIGHT 142 225 2 0.15 ENTIRE AREA WET PEND(C) & SWS WHITE/CHROME 155 1/2" 3,4,5,6,7 1 1-3 WASHER,DRYER LIGHT 18 225 1 0.15 ENTIRE AREA WET PEND, CHROME 155 1/2" 3,4,5,6,7 1 1-3 ATRIUM LIGHT 250 225 3 0.15 ENTIRE AREA WET UPRIGHT CHROME 155 1/2" 3,4,5,6,7

#DIV/0!

NS 1-4 ATTIC NS NS NS #VALUE! NS NS NS NS NS NS NS 1,

#DIV/0!

#DIV/0!

#DIV/0!

#DIV/0!

#DIV/0!

#DIV/0!

#DIV/0!

#DIV/0!

#DIV/0!

#DIV/0!

#DIV/0!

#DIV/0!

#DIV/0!

#DIV/0!

#DIV/0!

#DIV/0!

#DIV/0!

#DIV/0!

#DIV/0!

#DIV/0!

#DIV/0!

#DIV/0!

1. AREA NOT SPRINKLED

2. TOILET ROOMS SHALL BE SPRINKLED

3. INSTALL SPRINKLER HEADS SYMETRICALLY AND IN STRAIGHT LINES

4. INSTALL HEADS IN CENTER-CENTER OF LAY-IN CEILING TILES PER ARCHITECTURAL DRAWINGS.

5. MINIMUM NUMBER OF HEADS FOR REFERENCE ONLY

6. PEND = PENDANT ; PEND(C) = PENDANT CONCEALED ; SWS = SIDE WALL, UPR = UPRIGHT

7. SEE FLOOR PLANS FOR TYPE OF SPRINKLER HEAD.

CKT# AMPS POLES DESCRIPTION LOAD PH. 1 PH. 2 LOAD DESCRIPTION POLES AMPS CKT#

1 20 1 BEDRM/CLOS. LIGHTS/REC* 1,000 2500 1,500 WASHER 1 20 2

3 20 1 BEDRM/CLOS. LIGHTS/REC* 1,000 2500 1,500 MICROWAVE 1 20 4

5 20 1 BEDRM/CLOS. LIGHTS/REC* 590 890 300 RANGE HOOD 1 20 6

7 20 1 KITCHEN RECEPTACLES 540 1040 500 HVAC FAN COIL UNIT 1 20 8

9 20 1 BATHROOM LIGHTS/REC 600 2400 1,800 GARGAGE DISPOSAL 1 20 10

11 30 2 DRYER 2,500 3700 1,200 REF/FREEZ 1 20 12

2,500 6500 4,000 ELECTRIC RANGE 2 50 14

15 20 1 SPARE* 4000 4,000

17 20 1 SPARE* SPACE 1 18

19 20 1 SPARE* SPACE 1 20

21 1 SPACE SPACE 1 22

23 1 SPACE SPACE 1 24

CONNECTED LOAD/PHASE 12,290 11,240

TOTAL CONNECTED LOAD (VA) 24,580

DEMAND LOAD (AMPS) ‐ NEC OPTIONAL METHOD TABLE 2 78

1. INDICATED 20 AMPERE, 1 POLE BREAKERS SHALL BE ARC FAULT INTERRUPTER TYPE IN ACCORDANCE WITH NFPA 70, ARTICLE 210.112(A).

ARC FAULT BREAKERS ARE INDICATED BY AN ASTERISK (*).

2. SEE ELECTRICAL RISER DIAGRAM FOR PHASING ASSIGNMENTS, EG. 1 AND 2.

3. REFER TO NEW ELECTRICAL PLANS FOR PANEL DESIGNATIONS FOR EACH UNIT.

PANEL: XX VOLTAGE: 208V PHASE: 1 WIRE: 3 TYPE: 100A MLO TRIM: FLUSH AIC: 10,000 AMPS

MARK MANUF MODEL NUMBER DESCRIPTION MOUNTING OPTICS / LENSING FINISH VOLTAGE LAMPING

TEXAS FLUOR CV800F40W4000LDMV40KWH

LITHONIA MLRS5-48-F-MW-PIA-45L40K-1-DV-PEL

VISIONEERING LVG48-LED840K044LUNV

TEXAS FLUOR PUF-22L-H36W3250L-DMV-40K

LITHONIA 2TLX2-33L-FW-A12-LP840

LUMAX SULED-31L-4K-22-9-FARS

TEXAS FLUOR PUF-14L-F48W4500L-DMV-40K

LITHONIA SBL4-48L-EOHN-LP840

LUMAX WNLED-61L-4K-48-9-CFSA

TEXAS FLUOR BKV-MW-36L-R36W3600-LDMV-40K

BROWNLEE 5010-36-H25LED-WEC-40K-BAC-ES

LUMAX SUN2LED-31L-4K-48-9-FAR

TEXAS FLUOR 207A448LF48W4800LDMV40K

LITHONIA FEM4LED-6L-41K-IMAFL

LUMAX VWBTLED-70L-4K-48-9FAR

TEXAS FLUOR TFC14LW1800D120WH40K

BROWNLEE 2050-19-WH-B12LED-WA-40K-BAC

INCON 11411-12LED-40K

NOTES:

1. ALL FIXTURES SHALL COMPLY WITH THE "BUY AMERICAN ACT".

2. ALTERNATIVE FIXTURES WILL BE CONSIDERED BY PRIOR-APPROVAL ONLY.

3. FLUORESCENT FIXTURE ALTERNATIVES (SEE NOTE 2) WILL NOT BE ACCEPTABLE UNDER ANY CIRCUMSTANCES.

ACRYLIC FROSTED WHITE ENAMEL

4,000 LUMEN

DRIVER (MIN),

4000K COLOR

1,500 LUMEN

DRIVER (MIN),

4000K COLOR

120/277V, 1

PH,

UNIVERSAL

120/277V, 1

PH,

UNIVERSAL

WHITE ENAMEL

4500 LUMEN

DRIVER (MIN),

4000K COLOR

ACRYLIC FROSTED WHITE ENAMEL

3,000 LUMEN

DRIVER (MIN),

4000K COLOR

ACRYLIC FROSTED WHITE ENAMEL

BATHROOM VANITY LIGHT

FIXTURE LED

1' X 4' WRAPAROUND UTILITY

LIGHT FIXTURE,VAPORTIGHT

LED

ROUND DORM LIGHT FIXTURE

LED

4000 LUMEN

DRIVER (MIN),

4000K COLOR

ACRYLIC FROSTED WHITE ENAMEL

ACRYLIC FROSTED WHITE ENAMEL

3000 LUMEN

DRIVER (MIN),

4000K COLOR

ACRYLIC FROSTED

K

SURFACE,

WALL

SURFACE,

CEILING

SURFACE,

CEILING

WALL,

SURFACE

SURFACE,

STRUCTURE

SURFACE,

CEILING

HALLWAY LIGHT FIXTURE LED

VANDAL RESISTANT

2' X 2' DORM LIGHT FIXTURE

LED

1' X 4' DORM LIGHT FIXTURE LED

LIGHTING FIXTURE SCHEDULE

A

B1

B2

C

D

120/277V, 1

PH,

UNIVERSAL

120/277V, 1

PH,

UNIVERSAL

120/277V, 1

PH,

UNIVERSAL

120/277V, 1

PH,

UNIVERSAL

3783-01-REV3
3783-02 (CD-1)-REV3
3783-03 (C-1)-REV3
3783-04 (AD-1)-REV3
3783-05 (AD-2) - REV3
3783-06 (AD-3) - REV3
3783-07 (AD-4) - REV3
3783-08 (A-1)-REV3
3783-09 (A-2)-REV3
3783-10 (A-3)-REV3
3783-11 (A-4)-REV3
3783-12 (A-5)-REV3
3783-13 (A-6)-REV3
3783-14 (A-7)-REV3
3783-15 (A-8)-REV3
3783-16 (A-9)-REV3
3783-17 (A-10)-REV3
3783-18 (A-11)-REV3
3783-19 (F-1)-REV3
3783-20 (S-1)-REV3
3783-21 (MD-1)-REV3
3783-22 (MD-2) REV 3
3783-23 (MD-3) 1st Fl HVAC Demo Rev3
3783-24 (MD-4) Pipimg Riser Diagram Rev3
3783-25 (M-1)-REV3
3783-26 (M-2)-REV3 Attic Duct Plan
3783-27 (M-2A)-REV3 Attic PIPING Plan
3783-28 (M-3)-REV3 3rd FL PLAN
3783-29 (M-4)-REV3 2nd FL PLAN
3783-30 (M-5)-REV3 1ST FL PLAN
3783-31 (M-6)-REV3 Composite Plan
3783-32 (M-7)-REV3 HVAC Piping Riser
3783-33 (M-8)-REV3 Typical Mech Rm (revised 7-22-16)
3783-34 (M-9)-REV3 HVAC Sections
3783-35 (M-10)-REV3 Seismic Details
3783-36 (M-11)-REV3 Mech Schedules
3783-37 (M-12)-REV3 Add Chilled Water Flow Sheet
3783-38 (M-13)-REV3 Add Heating Hot Water Flow Sheet
3783-39 (PD-1)-REV3
3783-40 (PD-2)-REV3
3783-41 (PD-3)-REV3
3783-42 (PD-4)-REV3
3783-43 (PD-5)-REV3
3783-44 (P-1)-REV3
3783-45 (P-2)-REV3
3783-46 (P-3)-REV3
3783-47 (P-4)-REV3
3783-48 (P-5)-REV3
3783-49 (P-6)-REV3
3783-50 (FP-1)-REV3
3783-51 (FP-2)-REV3
3783-52 (FP-3)-REV3
3783-53 (FP-4)-REV3
3783-54 (FP-5)-REV3
3783-55 (E-1)-REV3
3783-56 (E-2)-REV3
3783-57 (E-3)-REV3
3783-58 (E-4)-REV3
3783-59 (E-5)-REV3
3783-60 (E-6)-REV3
3783-61 (E-7)-REV3
3783-62 (E-8)-REV3
3783-63 (E-9)-REV3
3783-64 (E-10)-REV3
3783-65 (E-11)-REV3
3783-66 (E-12)-REV3
3783-67 (E-13)-REV3
3783-68 (E-14)-REV3
3783-69 (E-15)-REV3
3783-70 (E-16)-REV3