Sprinkler_Inspection.xls

XLS spreadsheet 103 KB Posted

Attached to
Question and Answers Federal contract opportunity
Solicitation number
w9124c16r2011
Issued by
Department of the Army Materiel Command Mission and Installation Contracting Command Fort Jackson

About this file

List of Inspections provided by customer.

View the file

Other files for this federal contract opportunity

Other files attached to Question and Answers, newest first.
File Type Posted
FJ_Buildings_and_Systems.xlsx XLSX spreadsheet
16-R-2011_QAs_20160419.docx DOCX document
Fire_Alarm_Inspections.zip ZIP file
Fire_Alarm_Annual_Inspection.xls XLS spreadsheet
16-R-2011_QAs_20160412.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Inspections

FORT JACKSON SOUTH CAROLINA
Annual Sprinkler Inspection
BLDGNAME OF BLDGTYPE OF SYSTEMTYPE OF HEADRED/YELLOW/GREEN TAGINSPECT DATE# OF HOURS TO INSPECTNOTES
1525USAR CenterWet (System #1) Wet (System #2)Green Green2/8/2010 2/8/20104System 1 - FDC sign missing System 2 - No deficiencies noted
1895120th AG HQWet (System #1) Wet (System #2)Yellow Yellow1/19/2010 1/19/104System 1 - Hydraulic name plate missing. Boys side of building has upright sprinklers above ceiling and no sprinklers below ceiling. System #2 - Hydraulic name plate missing.
2100Applied InstructionWetGreen1/6/101FDC is behind bushes not visible or accessible. Hydraulic plate missing.
2100 NorthApplied InstructionWetGreen1/6/101FDC is behind bushes not visible or accessible. Hydraulic plate missing.
2179IOCBuilding under construction per Donald at Midland.
23404th BDE HQWestGreen8/3/104No deficiencies noted
23504th BDE WarehouseWetPass8/3/104No deficiencies noted
2395Ivy LanesWetAutoGreen1/19/092Hydraulic name plate missing. Foreign materials on fire sprinklers through out the building. Fire Sprinkler in back storage room may be to far off the wall.
2435MEPSWet DryGreen Green2/18/2010 2/1/20104System 1 -Some foreign materials on fire sprinkler throughout the building. System 2 - Strap on Riser mount compressor broken.
2442DormitoryWetCentralGreen10/26/091Hydraulic name plate is missing
2446DormitoryWetCentralGreen10/26/092No deficiencies noted
2447Community BuildingWetCentralYellow10/26/091Water motor alarm is not working
2449DormitoryWetCentralGreen10/26/092No deficiencies noted
2450 A, B, CHeavy Wheel Vehicle SchoolWetGemGreen10/28/094No deficiencies noted
2453DormitoryWetCentralGreen10/26/092Hydraulic name plate is missing
2460DormitoryWetCentralGreen10/26/092No deficiencies noted
2461DormitoryWetCentralGreen10/26/092No deficiencies noted
2462S-4 Training CenterWetAutoYellow11/16/092Hydraulic name plate missing.
2463Community BuildingWetCentralGreen10/26/091No deficiencies noted
2467DormitoryWetCentralGreen10/26/091No deficiencies noted
2468DormitoryWetCentralGreen10/26/091No deficiencies noted
2502AAFES Maintenance ShopDryCentralGreen11/16/094Hydraulic name plate missing. Alarm did not sound in building.
2510WarehouseDryGreen12/7/092Hydraulic name plate missing. No head in riser room.
2512Clothing ClassificationDryYellow2/8/103Hydraulic name plate missing, no alarms in building. 2" drain rusted out and water motor alarm needs to be cleaned. ****Ft. Jackson central did receive Flow Alarm****
2522WarehouseDryCentralYellow11/16/094Hydraulic name plate missing.
2558Pest ControlDryCentralGreen12/7/092Hydraulic name plate missing. Electric alarm did not sound in building.
2570WarehouseDryCentralGreen12/7/092Hydraulic name plate missing. EDC cap missing. It appears office in building is not sprinkled.
2571WarehouseDryGreen12/7/092Hydraulic name plate missing. No alarm in building. It appears small room in back of building by rollup door not sprinklered.
2572WarehouseDryYellow1/5/104Hydraulic name plate missing. FDC sign missing. Fire sprinklers are missing in office area, upright sprinkler used for pendent 2" drain rusted. Water motor alarm and electric alarm are not working.
2580WarehouseDryGreen12/7/092Hydraulic name plate missing.
2584WarehouseDryGreen12/7/092Hydraulic name plate missing.
2590WarehouseDryVikingGreen1/5/104Hydraulic name plate missing. FDC cap missing.
2601DLE ShopWetGlobeYellow12/9/09212/9/09 It appears there are offices throughout building that are not sprinklered. They have sprinklers above ceiling but not below.
2602DLE ShopWetGlobeGreen12/9/092No deficiencies noted
2603DLE ShopWet (System #1) Wet (System #2)GlobeGreen Green12/9/2009 12/9/20094System 1 - No deficiencies noted. System 2 - No deficiencies noted.
2604DLE ShopWet (System #1) Wet (System #2)Globe GlobeGreen Green12/9/2009 12/9/20094System 1 - No deficiencies noted. System 2 - No deficiencies noted.
2605Weapons PoolWetGlobeGreen1/5/102No deficiencies noted
2609Telephone Switch BuildingPre ActionGreen2/23/103No deficiencies noted
2620Navy Reserve CenterWet (System 1) Wet (System 2)Green Green12/8/2009 12/8/20094System 1 - No deficiencies noted. System 2 - No deficiencies noted.
2785Kennedy HallWetVikingGreen2/17/104Hydraulic name plate missing. Foreign materials on some fire sprinkler through out building.
3058Maintenance ShopWetGreen1/6/101Hydraulic name plate missing. It appears that there are offices in the bldg that are not sprinkled.
3215 (1st, 2nd, and 3rd Floors)DormitoryDM WetStockGreen10/26/091No deficiencies noted
3235 (1st, 2nd, and 3rd Floors)DormitoryDM WetGlobeGreen10/26/091No deficiencies noted
3255Office BuildingWetGreen12/8/092No deficiencies noted
3265 (1st, 2nd, and 3rd Floors)DormitoryDM WetGreen10/26/091It appears cover is missing on 1st floor flow switch
3275 (1st, 2nd, and 3rd Floors)DormitoryDM WetGlobeGreen10/26/091No deficiencies noted
3276 (1st, 2nd, and 3rd Floors)DormitoryDM WetGreen10/26/091No deficiencies noted
3305Magruder PubWetVikingGreen10/26/092No deficiencies noted
3390Data Processing CenterWetD (Pre Action)Green12/8/092Hydraulic name plate is missing.
MC3430USMC Reserve CenterWetGreen2/1/102Strap on riser mount compressor broken.
MC3431USMC Reserve Center Vehicle MaintenanceWetGreen8/10/102No deficiencies noted
3500WarehouseDryGemGreen12/7/092Hydraulic name plate missing. It appears office in warehouse in not sprinkled. Fire sprinklers in office are not properly oriented.
3501WarehouseBuilding to be torn down per Donald at Midland
3510WarehouseDryGreen1/5/104Hydraulic name plate missing. FDC cap missing. Bell line psi switch is leaking when water is flowed to set alarms off but it is working.
3511WarehouseWetASCOAGreen11/16/092Hydraulic name plate missing.
3521WarehouseWetASCOAGreen11/16/092Hydraulic name plate missing.
3630Officer's ClubWetStockGreen11/17/094Hydraulic name plate missing. Cannot locate inspectors test.
3652Golf Course ClubhouseDryGlobeGreen11/16/092Hydraulic name plate missing. Sprinkler in janitors closet may be blocked by shelves.
4110Main PXWet (Zone 1) Wet (Zone 2) Wet (Zone 3) Wet (Zone 4) Wet (Zone 5)Green Green Green Green Green12/9/2009 12/9/2009 12/9/2009 12/9/2009 12/9/200910Zone 1 - Some foreign materials on fire sprinklers throughout store. Zone 2 - Some foreign materials on fire sprinklers throughout store. Zone 3 - Some foreign materials on fire sprinklers throughout store. Zone 4 - Some foreign materials on fire sprinklers throughout store. Zone 5 - No deficiencies noted.
4255DormitoryWetGreen8/10/102No deficiencies noted
4265DormitoryWetGreen8/10/102No deficiencies noted
4275DormitoryWetGreen8/10/102No deficiencies noted
4280WetGreen8/12/102No deficiencies noted
4282Telecommunication SwitchWet (System 1) Wet (System 2)Stock StockYellow Green1/19/2010 1/19/104System # 1 - Hydraulic name plate missing. Drain is clogged and over flows when testing, value trim on PreAction valve has corrosion on it. System #2 - Hydraulic name plate missing.
4285DormitoryWetGreen8/10/102No deficiencies noted
4295DormitoryWetGreen8/10/102No deficiencies noted
4380WetGreen8/12/102No deficiencies noted
4392AG MuseumDryCentralGreen12/8/092No deficiencies noted
4408Museum AnnesWetASCOAGreen12/8/092Hydraulic name plate missing. Electric alarm not working.
4442Post MuseumWetGrinnellYellow1/11/106Hydraulic name plate missing. Foreign materials on fire sprinklers through out building. Alarm test valve not working on dry valve. Alarm not sounding in building. Hangers are missing on 3" main.
4510WarehouseDryGrinnellYellow1/11/106Hydraulic name plate missing. 2" draining rusted out. FDC check valve leaking. Foreign materials on fire sprinklers. Swivels/couplings need lubing. Paint on Fire sprinklers through out the building. Leaking dry pendent sprinkler.
4581Scales CDCCopper SystemYello6/24/104Alarm would not sound. Heads in mechanical room too far down from ceiling. Heads in kitchen too far off walls.
4585Hood Street CDCWetCentralGreen10/28/092Fire sprinklers have foreign material on them. It appears riser has corrosion caused by a leak at the base.
4679Post LibraryWetGreen2/23/102Hydraulic name plate missing. Alarm does not sound in building during water flow test.
4712APX Mini MallWetGrinnellYellow1/11/104Hydraulic name plate missing. Inspectors test seems to be clogged. Alarm is not sounding when water is flowed.
4712BPX Mini MallWetGrinnellYellow1/11/104Hydraulic name plate missing. Coolers not sprinkle red in ABC Store.
4716CommissaryWet (System 1) Wet (System 2) Wet (System 3)Rasco RascoYellow Yellow11/17/094System 1 - Some foreign materials on heads. FDC caps missing. Water flow switch or alarms did not sound when inspectors test was at activated. System 2 - Foreign materials on heads through out store. Some heads have paint on them. Coolers not sprinkle red. Could not find inspectors to flow alarm. System 3 - Foreign materials on heads through out store. Some heads have paint on them. Elevator lobby does not have sprinkler heads.
5450Strom Thurmond BldgWet (System #1) Pre Action (System #2)VikingGreen Red12/9/094System 1 - No deficiencies noted. System 2 - System out of service upon arrival. Air compressor not working.
5499Emergency Service CenterDry WetASCOAGreen11/16/094System 1 - Hydraulic name plate missing. It appears water motor alarm not working. System 2 - Hydraulic name plate missing. It appears water motor alarm not working.
5615Hood Street SchoolBuilding under construction per Donald at Midland.
5670Burger King4" CopperASCOAGreen10/28/092Hydraulic name plate is missing
5671Recycle CenterDryCentralYellow1/7/104Hydraulic name plate missing. FDC not visible or accessible because of fence and trees. FDC caps missing.
5900CC Pickney School1 1/2" CopperGreen6/24/104Small cooper system feeling 8 fire sprinklers. System has no psi gauges to take flow or psi readings.
5975Youth Activity CenterGreenVikingGreen1/19/102Hydraulic name plate missing. Foreign materials on fire sprinklers through out the building.
6000Palmetto LodgeDM Wet (System 1) Wet (System 2) Wet (System 3)StockGreen Green12/8/2009 12/8/20096System 1 - Electric alarm not working System 2 - Hydraulic name plate missing. FDC sign missing. System 3 - No deficiencies noted.
D6271Reserve CenterWetCentralGreen1028/20092FDC sign not visible. FDC is missing.
6510Community Activity CenterWetGlobeGreen11/17/094No deficiencies noted
7540DOD Polygraph InstituteWetGreen6/24/106It appears fire sprinklers in mechanical room have paint on them.
9470CEP 4WetGreen2/8/102FDC sign missing.
10000SSIWet (Zone 1) Wet (Zone 2) Wet (Zone 4) Wet (Zone 5) Wet (Zone 6) Wet (Zone 7) Wet (Zone 8) Wet (Zone 9) Wet (Zone 10) Wet (Zone 11) Wet (Zone 12) Wet (Zone 13) Wet (Zone 14) Wet (Zone 15) Wet (Zone 16) Pre-Action (Zone 1 in Mech. Room)Green Green Green Green Green Green Green Green Green Green Green Green Green Green Green Green -2/24/2010 2/24/2010 2/24/2010 2/24/2010 2/242010 2/242010 2/24/2010 2/24/2010 2/24/2010 2/24/2010 2/24/2010 2/24/2010 2/24/2010 2/24/2010 2/24/2010 2/24/2010 -16On all zones the hydraulic signs are missing
10100Chaplains SchoolDry Wet DryGreen Green Green2/24/2010 2/24/2010 2/24/20104Hydraulic sign missing. Drain needs to be piped to mop sink to perform drain test. Hydraulic sign missing. 48" duct in mech room not sprinklered under, foreign material on fire sprinkler through out the bldg Hydraulic sign missing. Some corrosion on priming line from old leak.
10300Dozier HallWetStar/SGGreen12/8/096Some foreign materials on fire sprinklers, throughout building.
10400BN HQWetGreen10/27/092No deficiencies noted
10401 (A and B)Dining FacilityWet (A) Dry (B)ASCOA ASCOAGreen10/27/093On system B fire sprinklers in kitchen have foreign material on them.
10402 (1st, 2nd and 3rd Floor)DormitoryWetASCOAGreen10/27/093On 3rd floor, 48" and larger duct is not sprinkled below
10404 (1st, 2nd and 3rd Floor)DormitoryWetASCOAGreen10/27/093On 3rd floor, 48" and larger duct is not sprinkled below
10405 (1st, 2nd and 3rd Floor)DormitoryWetASCOAGreen10/27/093No deficiencies noted
10406DormitoryWetASCOAGreen10/27/093On 3rd floor, 48" and larger duct is not sprinkled below
10407DormitoryWetASCOAGreen10/27/093On 3rd floor, 48" and larger duct is not sprinkled below
10620DormitoryWetGreen1/6/101FDC sign is missing.
10621DormitoryWetGreen1/6/101FDC sign is missing.
10622DormitoryWetGreen1/6/101FDC sign missing. Hydraulic name plate missing.
10623DormitoryWetGreen1/6/101FDC sign missing. Hydraulic name plate missing.
10626DormitoryWetGreen1/6/101FDC sign missing.
10629DormitoryWetGreen1/6/101FDC sign missing. Hydraulic name plate missing.
10630HQWetGreen1/6/101FDC sign missing.
10631HQWetGreen1/6/101FDC sign missing.
10632HQWetGreen1/6/101FDC sign missing.
10633ClassroomWetGreen1/6/101FDC sign missing.
10634ClassroomWetGreen1/6/101FDC sign missing.
10791Dining FacilityWetGreen1/6/101Hydraulic name plate missing. It appears there is corrosion on sprinklers in kitchen, some part B esc, are missing through out building.
12600Miles WarehouseDryGreen1/7/102Hydraulic name plate missing.
12625TASC WarehouseWetYellow1/7/102FDC caps missing. Water motor alarm not working. Heads from old paint need to be removed to close to overhead sprinkler.
12650TASCWetGreen1/7/102Fire sprinkler at read loading dock outside of building have corrosion on them, FDC caps missing.
12656WarehouseDryGreen1/7/104Hydraulic name plate missing.
13000108th Reserve CenterDry WetGreen Green11/17/09 11/17/09611/17/09 Dry System - Hydraulic name plate missing. Retard Chamber on Dry Ssytem needs to be removed. 11/17/09 Wet System - Hydraulic name plate missing. It appears that some heads in mechanics room are painted.
13100108th Motor PoolDryCentralGreen11/17/094Hydraulic name plate missing. Retard Chamber on Dry System needs to be removed from Bell line.
13200108th Res StorageDrySGGreen11/17/094Hydraulic name plate missing.

File details come from the government source that posted it. Updated .