Inspections
| FORT JACKSON SOUTH CAROLINA | |||||||
| Annual Sprinkler Inspection | |||||||
| BLDG | NAME OF BLDG | TYPE OF SYSTEM | TYPE OF HEAD | RED/YELLOW/GREEN TAG | INSPECT DATE | # OF HOURS TO INSPECT | NOTES |
| 1525 | USAR Center | Wet (System #1) Wet (System #2) | Green Green | 2/8/2010 2/8/2010 | 4 | System 1 - FDC sign missing System 2 - No deficiencies noted | |
| 1895 | 120th AG HQ | Wet (System #1) Wet (System #2) | Yellow Yellow | 1/19/2010 1/19/10 | 4 | System 1 - Hydraulic name plate missing. Boys side of building has upright sprinklers above ceiling and no sprinklers below ceiling. System #2 - Hydraulic name plate missing. | |
| 2100 | Applied Instruction | Wet | Green | 1/6/10 | 1 | FDC is behind bushes not visible or accessible. Hydraulic plate missing. | |
| 2100 North | Applied Instruction | Wet | Green | 1/6/10 | 1 | FDC is behind bushes not visible or accessible. Hydraulic plate missing. | |
| 2179 | IOC | Building under construction per Donald at Midland. | |||||
| 2340 | 4th BDE HQ | West | Green | 8/3/10 | 4 | No deficiencies noted | |
| 2350 | 4th BDE Warehouse | Wet | Pass | 8/3/10 | 4 | No deficiencies noted | |
| 2395 | Ivy Lanes | Wet | Auto | Green | 1/19/09 | 2 | Hydraulic name plate missing. Foreign materials on fire sprinklers through out the building. Fire Sprinkler in back storage room may be to far off the wall. |
| 2435 | MEPS | Wet Dry | Green Green | 2/18/2010 2/1/2010 | 4 | System 1 -Some foreign materials on fire sprinkler throughout the building. System 2 - Strap on Riser mount compressor broken. | |
| 2442 | Dormitory | Wet | Central | Green | 10/26/09 | 1 | Hydraulic name plate is missing |
| 2446 | Dormitory | Wet | Central | Green | 10/26/09 | 2 | No deficiencies noted |
| 2447 | Community Building | Wet | Central | Yellow | 10/26/09 | 1 | Water motor alarm is not working |
| 2449 | Dormitory | Wet | Central | Green | 10/26/09 | 2 | No deficiencies noted |
| 2450 A, B, C | Heavy Wheel Vehicle School | Wet | Gem | Green | 10/28/09 | 4 | No deficiencies noted |
| 2453 | Dormitory | Wet | Central | Green | 10/26/09 | 2 | Hydraulic name plate is missing |
| 2460 | Dormitory | Wet | Central | Green | 10/26/09 | 2 | No deficiencies noted |
| 2461 | Dormitory | Wet | Central | Green | 10/26/09 | 2 | No deficiencies noted |
| 2462 | S-4 Training Center | Wet | Auto | Yellow | 11/16/09 | 2 | Hydraulic name plate missing. |
| 2463 | Community Building | Wet | Central | Green | 10/26/09 | 1 | No deficiencies noted |
| 2467 | Dormitory | Wet | Central | Green | 10/26/09 | 1 | No deficiencies noted |
| 2468 | Dormitory | Wet | Central | Green | 10/26/09 | 1 | No deficiencies noted |
| 2502 | AAFES Maintenance Shop | Dry | Central | Green | 11/16/09 | 4 | Hydraulic name plate missing. Alarm did not sound in building. |
| 2510 | Warehouse | Dry | Green | 12/7/09 | 2 | Hydraulic name plate missing. No head in riser room. | |
| 2512 | Clothing Classification | Dry | Yellow | 2/8/10 | 3 | Hydraulic name plate missing, no alarms in building. 2" drain rusted out and water motor alarm needs to be cleaned. ****Ft. Jackson central did receive Flow Alarm**** | |
| 2522 | Warehouse | Dry | Central | Yellow | 11/16/09 | 4 | Hydraulic name plate missing. |
| 2558 | Pest Control | Dry | Central | Green | 12/7/09 | 2 | Hydraulic name plate missing. Electric alarm did not sound in building. |
| 2570 | Warehouse | Dry | Central | Green | 12/7/09 | 2 | Hydraulic name plate missing. EDC cap missing. It appears office in building is not sprinkled. |
| 2571 | Warehouse | Dry | Green | 12/7/09 | 2 | Hydraulic name plate missing. No alarm in building. It appears small room in back of building by rollup door not sprinklered. | |
| 2572 | Warehouse | Dry | Yellow | 1/5/10 | 4 | Hydraulic name plate missing. FDC sign missing. Fire sprinklers are missing in office area, upright sprinkler used for pendent 2" drain rusted. Water motor alarm and electric alarm are not working. | |
| 2580 | Warehouse | Dry | Green | 12/7/09 | 2 | Hydraulic name plate missing. | |
| 2584 | Warehouse | Dry | Green | 12/7/09 | 2 | Hydraulic name plate missing. | |
| 2590 | Warehouse | Dry | Viking | Green | 1/5/10 | 4 | Hydraulic name plate missing. FDC cap missing. |
| 2601 | DLE Shop | Wet | Globe | Yellow | 12/9/09 | 2 | 12/9/09 It appears there are offices throughout building that are not sprinklered. They have sprinklers above ceiling but not below. |
| 2602 | DLE Shop | Wet | Globe | Green | 12/9/09 | 2 | No deficiencies noted |
| 2603 | DLE Shop | Wet (System #1) Wet (System #2) | Globe | Green Green | 12/9/2009 12/9/2009 | 4 | System 1 - No deficiencies noted. System 2 - No deficiencies noted. |
| 2604 | DLE Shop | Wet (System #1) Wet (System #2) | Globe Globe | Green Green | 12/9/2009 12/9/2009 | 4 | System 1 - No deficiencies noted. System 2 - No deficiencies noted. |
| 2605 | Weapons Pool | Wet | Globe | Green | 1/5/10 | 2 | No deficiencies noted |
| 2609 | Telephone Switch Building | Pre Action | Green | 2/23/10 | 3 | No deficiencies noted | |
| 2620 | Navy Reserve Center | Wet (System 1) Wet (System 2) | Green Green | 12/8/2009 12/8/2009 | 4 | System 1 - No deficiencies noted. System 2 - No deficiencies noted. | |
| 2785 | Kennedy Hall | Wet | Viking | Green | 2/17/10 | 4 | Hydraulic name plate missing. Foreign materials on some fire sprinkler through out building. |
| 3058 | Maintenance Shop | Wet | Green | 1/6/10 | 1 | Hydraulic name plate missing. It appears that there are offices in the bldg that are not sprinkled. | |
| 3215 (1st, 2nd, and 3rd Floors) | Dormitory | DM Wet | Stock | Green | 10/26/09 | 1 | No deficiencies noted |
| 3235 (1st, 2nd, and 3rd Floors) | Dormitory | DM Wet | Globe | Green | 10/26/09 | 1 | No deficiencies noted |
| 3255 | Office Building | Wet | Green | 12/8/09 | 2 | No deficiencies noted | |
| 3265 (1st, 2nd, and 3rd Floors) | Dormitory | DM Wet | Green | 10/26/09 | 1 | It appears cover is missing on 1st floor flow switch | |
| 3275 (1st, 2nd, and 3rd Floors) | Dormitory | DM Wet | Globe | Green | 10/26/09 | 1 | No deficiencies noted |
| 3276 (1st, 2nd, and 3rd Floors) | Dormitory | DM Wet | Green | 10/26/09 | 1 | No deficiencies noted | |
| 3305 | Magruder Pub | Wet | Viking | Green | 10/26/09 | 2 | No deficiencies noted |
| 3390 | Data Processing Center | Wet | D (Pre Action) | Green | 12/8/09 | 2 | Hydraulic name plate is missing. |
| MC3430 | USMC Reserve Center | Wet | Green | 2/1/10 | 2 | Strap on riser mount compressor broken. | |
| MC3431 | USMC Reserve Center Vehicle Maintenance | Wet | Green | 8/10/10 | 2 | No deficiencies noted | |
| 3500 | Warehouse | Dry | Gem | Green | 12/7/09 | 2 | Hydraulic name plate missing. It appears office in warehouse in not sprinkled. Fire sprinklers in office are not properly oriented. |
| 3501 | Warehouse | Building to be torn down per Donald at Midland | |||||
| 3510 | Warehouse | Dry | Green | 1/5/10 | 4 | Hydraulic name plate missing. FDC cap missing. Bell line psi switch is leaking when water is flowed to set alarms off but it is working. | |
| 3511 | Warehouse | Wet | ASCOA | Green | 11/16/09 | 2 | Hydraulic name plate missing. |
| 3521 | Warehouse | Wet | ASCOA | Green | 11/16/09 | 2 | Hydraulic name plate missing. |
| 3630 | Officer's Club | Wet | Stock | Green | 11/17/09 | 4 | Hydraulic name plate missing. Cannot locate inspectors test. |
| 3652 | Golf Course Clubhouse | Dry | Globe | Green | 11/16/09 | 2 | Hydraulic name plate missing. Sprinkler in janitors closet may be blocked by shelves. |
| 4110 | Main PX | Wet (Zone 1) Wet (Zone 2) Wet (Zone 3) Wet (Zone 4) Wet (Zone 5) | Green Green Green Green Green | 12/9/2009 12/9/2009 12/9/2009 12/9/2009 12/9/2009 | 10 | Zone 1 - Some foreign materials on fire sprinklers throughout store. Zone 2 - Some foreign materials on fire sprinklers throughout store. Zone 3 - Some foreign materials on fire sprinklers throughout store. Zone 4 - Some foreign materials on fire sprinklers throughout store. Zone 5 - No deficiencies noted. | |
| 4255 | Dormitory | Wet | Green | 8/10/10 | 2 | No deficiencies noted | |
| 4265 | Dormitory | Wet | Green | 8/10/10 | 2 | No deficiencies noted | |
| 4275 | Dormitory | Wet | Green | 8/10/10 | 2 | No deficiencies noted | |
| 4280 | Wet | Green | 8/12/10 | 2 | No deficiencies noted | ||
| 4282 | Telecommunication Switch | Wet (System 1) Wet (System 2) | Stock Stock | Yellow Green | 1/19/2010 1/19/10 | 4 | System # 1 - Hydraulic name plate missing. Drain is clogged and over flows when testing, value trim on PreAction valve has corrosion on it. System #2 - Hydraulic name plate missing. |
| 4285 | Dormitory | Wet | Green | 8/10/10 | 2 | No deficiencies noted | |
| 4295 | Dormitory | Wet | Green | 8/10/10 | 2 | No deficiencies noted | |
| 4380 | Wet | Green | 8/12/10 | 2 | No deficiencies noted | ||
| 4392 | AG Museum | Dry | Central | Green | 12/8/09 | 2 | No deficiencies noted |
| 4408 | Museum Annes | Wet | ASCOA | Green | 12/8/09 | 2 | Hydraulic name plate missing. Electric alarm not working. |
| 4442 | Post Museum | Wet | Grinnell | Yellow | 1/11/10 | 6 | Hydraulic name plate missing. Foreign materials on fire sprinklers through out building. Alarm test valve not working on dry valve. Alarm not sounding in building. Hangers are missing on 3" main. |
| 4510 | Warehouse | Dry | Grinnell | Yellow | 1/11/10 | 6 | Hydraulic name plate missing. 2" draining rusted out. FDC check valve leaking. Foreign materials on fire sprinklers. Swivels/couplings need lubing. Paint on Fire sprinklers through out the building. Leaking dry pendent sprinkler. |
| 4581 | Scales CDC | Copper System | Yello | 6/24/10 | 4 | Alarm would not sound. Heads in mechanical room too far down from ceiling. Heads in kitchen too far off walls. | |
| 4585 | Hood Street CDC | Wet | Central | Green | 10/28/09 | 2 | Fire sprinklers have foreign material on them. It appears riser has corrosion caused by a leak at the base. |
| 4679 | Post Library | Wet | Green | 2/23/10 | 2 | Hydraulic name plate missing. Alarm does not sound in building during water flow test. | |
| 4712A | PX Mini Mall | Wet | Grinnell | Yellow | 1/11/10 | 4 | Hydraulic name plate missing. Inspectors test seems to be clogged. Alarm is not sounding when water is flowed. |
| 4712B | PX Mini Mall | Wet | Grinnell | Yellow | 1/11/10 | 4 | Hydraulic name plate missing. Coolers not sprinkle red in ABC Store. |
| 4716 | Commissary | Wet (System 1) Wet (System 2) Wet (System 3) | Rasco Rasco | Yellow Yellow | 11/17/09 | 4 | System 1 - Some foreign materials on heads. FDC caps missing. Water flow switch or alarms did not sound when inspectors test was at activated. System 2 - Foreign materials on heads through out store. Some heads have paint on them. Coolers not sprinkle red. Could not find inspectors to flow alarm. System 3 - Foreign materials on heads through out store. Some heads have paint on them. Elevator lobby does not have sprinkler heads. |
| 5450 | Strom Thurmond Bldg | Wet (System #1) Pre Action (System #2) | Viking | Green Red | 12/9/09 | 4 | System 1 - No deficiencies noted. System 2 - System out of service upon arrival. Air compressor not working. |
| 5499 | Emergency Service Center | Dry Wet | ASCOA | Green | 11/16/09 | 4 | System 1 - Hydraulic name plate missing. It appears water motor alarm not working. System 2 - Hydraulic name plate missing. It appears water motor alarm not working. |
| 5615 | Hood Street School | Building under construction per Donald at Midland. | |||||
| 5670 | Burger King | 4" Copper | ASCOA | Green | 10/28/09 | 2 | Hydraulic name plate is missing |
| 5671 | Recycle Center | Dry | Central | Yellow | 1/7/10 | 4 | Hydraulic name plate missing. FDC not visible or accessible because of fence and trees. FDC caps missing. |
| 5900 | CC Pickney School | 1 1/2" Copper | Green | 6/24/10 | 4 | Small cooper system feeling 8 fire sprinklers. System has no psi gauges to take flow or psi readings. | |
| 5975 | Youth Activity Center | Green | Viking | Green | 1/19/10 | 2 | Hydraulic name plate missing. Foreign materials on fire sprinklers through out the building. |
| 6000 | Palmetto Lodge | DM Wet (System 1) Wet (System 2) Wet (System 3) | Stock | Green Green | 12/8/2009 12/8/2009 | 6 | System 1 - Electric alarm not working System 2 - Hydraulic name plate missing. FDC sign missing. System 3 - No deficiencies noted. |
| D6271 | Reserve Center | Wet | Central | Green | 1028/2009 | 2 | FDC sign not visible. FDC is missing. |
| 6510 | Community Activity Center | Wet | Globe | Green | 11/17/09 | 4 | No deficiencies noted |
| 7540 | DOD Polygraph Institute | Wet | Green | 6/24/10 | 6 | It appears fire sprinklers in mechanical room have paint on them. | |
| 9470 | CEP 4 | Wet | Green | 2/8/10 | 2 | FDC sign missing. | |
| 10000 | SSI | Wet (Zone 1) Wet (Zone 2) Wet (Zone 4) Wet (Zone 5) Wet (Zone 6) Wet (Zone 7) Wet (Zone 8) Wet (Zone 9) Wet (Zone 10) Wet (Zone 11) Wet (Zone 12) Wet (Zone 13) Wet (Zone 14) Wet (Zone 15) Wet (Zone 16) Pre-Action (Zone 1 in Mech. Room) | Green Green Green Green Green Green Green Green Green Green Green Green Green Green Green Green - | 2/24/2010 2/24/2010 2/24/2010 2/24/2010 2/242010 2/242010 2/24/2010 2/24/2010 2/24/2010 2/24/2010 2/24/2010 2/24/2010 2/24/2010 2/24/2010 2/24/2010 2/24/2010 - | 16 | On all zones the hydraulic signs are missing | |
| 10100 | Chaplains School | Dry Wet Dry | Green Green Green | 2/24/2010 2/24/2010 2/24/2010 | 4 | Hydraulic sign missing. Drain needs to be piped to mop sink to perform drain test. Hydraulic sign missing. 48" duct in mech room not sprinklered under, foreign material on fire sprinkler through out the bldg Hydraulic sign missing. Some corrosion on priming line from old leak. | |
| 10300 | Dozier Hall | Wet | Star/SG | Green | 12/8/09 | 6 | Some foreign materials on fire sprinklers, throughout building. |
| 10400 | BN HQ | Wet | Green | 10/27/09 | 2 | No deficiencies noted | |
| 10401 (A and B) | Dining Facility | Wet (A) Dry (B) | ASCOA ASCOA | Green | 10/27/09 | 3 | On system B fire sprinklers in kitchen have foreign material on them. |
| 10402 (1st, 2nd and 3rd Floor) | Dormitory | Wet | ASCOA | Green | 10/27/09 | 3 | On 3rd floor, 48" and larger duct is not sprinkled below |
| 10404 (1st, 2nd and 3rd Floor) | Dormitory | Wet | ASCOA | Green | 10/27/09 | 3 | On 3rd floor, 48" and larger duct is not sprinkled below |
| 10405 (1st, 2nd and 3rd Floor) | Dormitory | Wet | ASCOA | Green | 10/27/09 | 3 | No deficiencies noted |
| 10406 | Dormitory | Wet | ASCOA | Green | 10/27/09 | 3 | On 3rd floor, 48" and larger duct is not sprinkled below |
| 10407 | Dormitory | Wet | ASCOA | Green | 10/27/09 | 3 | On 3rd floor, 48" and larger duct is not sprinkled below |
| 10620 | Dormitory | Wet | Green | 1/6/10 | 1 | FDC sign is missing. | |
| 10621 | Dormitory | Wet | Green | 1/6/10 | 1 | FDC sign is missing. | |
| 10622 | Dormitory | Wet | Green | 1/6/10 | 1 | FDC sign missing. Hydraulic name plate missing. | |
| 10623 | Dormitory | Wet | Green | 1/6/10 | 1 | FDC sign missing. Hydraulic name plate missing. | |
| 10626 | Dormitory | Wet | Green | 1/6/10 | 1 | FDC sign missing. | |
| 10629 | Dormitory | Wet | Green | 1/6/10 | 1 | FDC sign missing. Hydraulic name plate missing. | |
| 10630 | HQ | Wet | Green | 1/6/10 | 1 | FDC sign missing. | |
| 10631 | HQ | Wet | Green | 1/6/10 | 1 | FDC sign missing. | |
| 10632 | HQ | Wet | Green | 1/6/10 | 1 | FDC sign missing. | |
| 10633 | Classroom | Wet | Green | 1/6/10 | 1 | FDC sign missing. | |
| 10634 | Classroom | Wet | Green | 1/6/10 | 1 | FDC sign missing. | |
| 10791 | Dining Facility | Wet | Green | 1/6/10 | 1 | Hydraulic name plate missing. It appears there is corrosion on sprinklers in kitchen, some part B esc, are missing through out building. | |
| 12600 | Miles Warehouse | Dry | Green | 1/7/10 | 2 | Hydraulic name plate missing. | |
| 12625 | TASC Warehouse | Wet | Yellow | 1/7/10 | 2 | FDC caps missing. Water motor alarm not working. Heads from old paint need to be removed to close to overhead sprinkler. | |
| 12650 | TASC | Wet | Green | 1/7/10 | 2 | Fire sprinkler at read loading dock outside of building have corrosion on them, FDC caps missing. | |
| 12656 | Warehouse | Dry | Green | 1/7/10 | 4 | Hydraulic name plate missing. | |
| 13000 | 108th Reserve Center | Dry Wet | Green Green | 11/17/09 11/17/09 | 6 | 11/17/09 Dry System - Hydraulic name plate missing. Retard Chamber on Dry Ssytem needs to be removed. 11/17/09 Wet System - Hydraulic name plate missing. It appears that some heads in mechanics room are painted. | |
| 13100 | 108th Motor Pool | Dry | Central | Green | 11/17/09 | 4 | Hydraulic name plate missing. Retard Chamber on Dry System needs to be removed from Bell line. |
| 13200 | 108th Res Storage | Dry | SG | Green | 11/17/09 | 4 | Hydraulic name plate missing. |