Fire_Alarm_Annual_Inspection.xls

XLS spreadsheet 222 KB Posted

Attached to
Question and Answers Federal contract opportunity
Solicitation number
w9124c16r2011
Issued by
Department of the Army Materiel Command Mission and Installation Contracting Command Fort Jackson

About this file

List of Inspections provided by customer.

View the file

Other files for this federal contract opportunity

Other files attached to Question and Answers, newest first.
File Type Posted
FJ_Buildings_and_Systems.xlsx XLSX spreadsheet
16-R-2011_QAs_20160419.docx DOCX document
Sprinkler_Inspection.xls XLS spreadsheet
Fire_Alarm_Inspections.zip ZIP file
16-R-2011_QAs_20160412.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fire Alarm Inspections

FORT JACKSON SOUTH CAROLINA
FIRE ALARM INSPECTION LOG
FTHD - FixedTemp Heat Detector PBSA - Pull Box Single Action PSDA - Pull Box Double Action PSD - Photo Smoke Detector SPPS - Power Supply DSD - Duct Smoke Detector HD - Heat DetectorRRHD - Rate of Rise Heat Detector CSH - Combined Smoke/Heat Detector SPKR - Speaker A/V - Audio/Visual Signal Device VSIG - Visual Only Signal NAC - NAC Booster Panel ANNC - AnnunciatorHORN - Horn DHCD - Door Closer with Detector ELPR- Elevator Primary Recall ELAL - Elevator Alternate Recall SP/V - Speaker Visual RCVR - Fire Control Annunciator BELLS - BellsSSSD- Single Station Smoke Detector WF-Water Flow Detector
BLDGNAME OF BLDGALARM PANELYear# FTHD# PBSA# PBDA# PSD# SPPS# DSD#HD# RRHD# CSH# SPKR# A/V# VSIG# NAC# ANNC# HORN# DHCD# ELPR# ELAL# SP/V#RCVR# BELLS# WFTOTAL NUMBER OF DEVICES IN BUILDINGINSPECT DATE# HRSNOTES
1525USAR CenterSimplex 4100U200800111841402000113010011117002825/11/1010The batteries in one of the NAC panels failed load testing and were replaced at this time (2-12V/7.5Ahr). Because the batteries only lasted about a year and the last batteries in this panel did not last long, the Simplex tech came by to adjust the charger in this NAC panel.
1541Army Lodging Maintenance ShopFCI FC-7200500000000000100000064/30/102There were no deficiencies noted.
1542Army Lodging WarehouseFCI FC-7200100000000000100000024/30/102There were no deficiencies noted.
1698Chemical StorageMonaco Vulcan 1Passed - Voltage w/charger, voltage w/o charger, battery % of charge, battery age check, zone trouble, signal trouble, type signal circuit, AC Input voltage, Earth Detection, Lamps/LED Test, Drill Switch, Control Function(s)0No deficiencies noted.
1699HazmatMonaco M-1000000000000000000000004/13/102Battery failed load test.
1701USAR Vehicle Main ShopMonaco C-100A-12198404000000000000000000371/20/104There were no deficiencies noted.
1704HazmatMonaco M-11995Passed - Voltage w/charger, voltage w/o charger, battery % of charge, battery age check, zone trouble, signal trouble, type signal circuit, AC Input voltage, Lamps/LED Test, Drill Switch, Control Function(s)04/13/102No deficiencies noted.
1705DormitoryEdwards EST-20010300007002280000000007710/16/096Photo smoke detector on 1st floor west bay office 2 and 2nd floor east bay office 2/storage was not tested. Rate of rise heat detector on 2nd floor west bay storage room was not tested. There were no deficiencies noted.
1706DormitoryEdwards EST-20010310006002280000000007710/16/096The heat detectors on first floor showed as first floor smokes and the second floor heats showed as second floor smokes on the Monaco panel. Photo smoke detectors on 2nd floor east office/storage, 2nd floor west bay office 1 and 2nd floor west bay utility room/office 2 were not tested.
1741AdministrativeSimplex 4001199104020000100000000000042910/30/094There were no deficiencies noted.
1742AdministrativeSimplex 4001199104020000100000000000042910/30/094The two 7.5 Ahr batteries in the fire alarm panel failed load testing and were replaced at this time.
1744MaintenanceSimplex 40021991440000000000001000000910/9/092The battery in the Monaco panel failed load testing and was replaced with a new 2.3 Ahr battery. There were no deficiencies noted.
1745StorageSimplex 40021991220000000000001000000510/9/092There were no deficiencies noted.
1865PX AnnexMonaco M Series200300300223000400000000003210/9/094There were no deficiencies noted.
1867120 AGFireshield +05000002600000040000003510/9/098There were no deficiencies noted.
1867120 AGFireshield +0500000260000004000000353/23/104There were no deficiencies noted.
1872DormitoryEdwards EST-220070017790213000441200000000016710/8/0916Smoke detector on 1st floor room 136 at hall by station 6 and 2nd floor room 229 hall by station 7 were not tested. There were no deficiencies noted.
1875Dining FacilityFire Lite Sens 100019920600031300030001000000263/23/104The battery in Monaco panel failed load testing and was replaced at this time. (12V/7.5Ahr)
1877DormitoryGamewell Zans 400199212505700080000000000001410510/2/0916Smoke/heat detector in bay 4 west end failed to alarm when tested. A diode in the head was broken. The detector was replaced with another System Sensor 2WT-B and re-tested. The new device worked normal. There were four rooms which could not be accessed at this time, !st floor cadre, 2nd floor female baggage room, 2nd floor room 216 and 3rd floor commander's office.
1880DormitoryGamewell Zans 4001985112605100020000000000001510510/7/0916One pull station (bay 1) had a broken switch inside the cover and was replaced and retested at this time. Two rooms ( 3rd floor not cadre office and south cadre office) could not be accessed at this time. Two smoke detectors (2nd floor bay 6 south, 3rd floor linen room) failed to alarm and were replaced and retested normal at this time. One bell (on the 2nd floor balcony) stated alarming but quit after a minute, and needs to be replaced.
1889DormitoryGamewell Zans 4001985110075000500000000000069710/1/0916The batteries failed load testing and were replaced at this time. There was also a heat detector in the second floor laundry room (215) which failed to alarm when tested. The heat head was replaced and re-tested. All devices now testing normally.
1892DormitoryGamewell Zans 4001992125053020100000000000001510610/6/0916Smoke detector on 3rd floor east cadre office was not tested. There were no deficiencies noted.
1895120th AG HQSimplex 40011972017000000003400000000005110/16/094Pull station single action on 1st floor far left side has had a message center installed over it blocking access to the reset screw. There were no deficiencies noted.
1897DormitoryGamewell Zans 40019925250500002000000000000159710/5/0916The batteries in the fire alarm panel failed load testing and were replaced at this time (2/7.5 Ahr battery). The heat detector that failed (1st floor main supply room) was a Simplex 4098-9402-135 fixed temp.rate of rise heat. There were no replacement for this in the shop and still needs repair.
2009Vanguard GymEdwards03000000000000000000254/30/101The fire alarm panel is not operating and may need to be replaced.
2075187th Ord WH Vehicle SchoolEdwards20090200000200000000006000108/17/106There were no deficiencies
2078187th Ord WH Vehicle SchoolEdwards2009006100000010000000010000278/19/104There were no deficiencies noted.
2079187th Ord WH Vehicle SchoolEdwards20090021010100000000005000108/18/104There were no deficiencies noted.
2090187th Ord BN Motor PoolSimplex 400219907650000008050000000000942/1/108Audio Visual on 1st floor rear of bay failed inspection.
2100Applied InstructionNotifier 72 Series002800230000260000000000772/2/1012Three pull stations failed to alarm when pulled. All the pull stations are getting old and the switches are sticking. Two duct detectors failed to alarm. One as being jumped and now needs to be re-connected. The other just failed to alarm.
R2101ClassroomEdwards EST 2005000060050000000000161/5/104No deficiencies noted.
R2102Orderly RoomEdwards EST 200600002100110000000000381/6/104No deficiencies noted.
R2103ClassroomEdwards EST 2005000060050000000000161/5/104No deficiencies noted.
R2104BN HQEdwards EST 20050000600102000000000231/6/104No deficiencies noted.
R2105DormitoryEdwards EST 200418000000120000000000341/5/104The sounder base of smoke detector in the south bay, sleeping room 1 does not sound when device is in alarm. The base needs to be replaced.
R2106DormitoryEdwards EST 200418000000140000000000361/5/104There were no deficiencies noted.
R2107DormitoryEdwards EST 200418000000140000000000361/6/104The audio/visual in the south bay shower did not sound or flash when the fire alarm was set off.
R2108DormitoryEdwards EST 200314000000140000000000311/6/104There were no deficiencies noted.
2119Admin SchoolSFL 400 Notifier19910120005000000000000007242/3/1012One pull station failed to alarm when tested. Three duct detectors failed to alarm when tested.
2139Mini LaundryFCI 72 Series1984003000000000003000000069/22/102.0Two horns failed testing: First floor Office hallway and first floor outside on BLDG.
2159Exchange BranchSimplex 400219960700040190050000000000354/29/102When zone 5 goes into alarm it does not alarm zone 5 on the Monaco panel. Also there is no panel trouble on the Monaco panel. If any zone goes into trouble that zone will show a trouble on the Monaco, but a signal or panel trouble will not be reported to fire dispatch.
G2169Alpine LodgeMonaco FACP31000000200000000000175/5/102The Gentex smoke detectors did sound locally when tested but they did not pt an alarm on the fire alarm panel.
2190Applied InstructionSimplex 400119871460502000080000000000352/2/104The battery in the Monaco panel failed load testing and was replaced at this time. (12V, 2.3Ahr)
2200Storage GP InstFCI 72 Series19840110000000000005000000165/4/102The fire alarm control panel did not report troubles or alarms to the Monaco panel in Bldg. 2119.
2205DormitoryGamewell Flex 61020020801240127000121400000000017710/14/0916Photo smoke detector on 1st floor room 136, 1st floor room 138 and 1st floor room 140 were not tested. There were no deficiencies noted.
2210SSI ClassroomSimplex 40021994030002000060000000000112/4/103There were no deficiencies noted.
2210SSI ClassroomSimplex 4002030002000060000000000113/24/104There were no deficiencies noted.
2215DormitoryFCI 72 Series19860600012017600000000000910410/19/0916Twelve duct smoke detectors did not go into alarm even after heavy smoke - Two on 1st floor mechanical room, two on 2nd floor west mechanical room, two on 2nd floor east mechanical room, two on 2nd floor west mechanical room, two on 3rd floor east mechanical room and two on 3rd floor mechanical room. The four smoke detectors in rooms 221, 230, 312, 325 would not sound locally when smoked. The smoke detector in room 212 would not stop sounding locally after smoked. All five of the bad smoke/heat detectors were replaced and retested at this time. All tested normal. Room 132 could not be accessed at this time.
2225DormitoryFCI 72 Series19860601200017600000900000010410/15/0916Rooms 123, 124, 128 and 135 could not be accessed at this time. Duct smoke detector 1st floor east mechanical room went into alarm but did not alarm the panel. The batteries in the fire alarm panel failed load testing and were replaced at this time.
2230Dining FacilityEdwards 5721-B1988050003000050000000000136/8/10Batteries failed load testing and were replaced. Three DSD (Duct Smoke Detectors) failed: first floor HVAC.
2235DormitoryFCI 72 Series198606000601760000000000099810/20/0916Rooms 107 and 114 could not be accessed at this time. First floor east mechanical room duct detector failed to alarm when tested. Third floor at west stairwell pull station failed to alarm when tested. The two batteries in the fire panel failed load testing and were replaced at this time.
2245DormitoryMonaco C-100A-1219820600020010600000000000912310/28/0916Two bells failed to alarm when tested, third floor east end hall and first floor center hall.
2253DormitorySimplex 400119830601200107600000900000010410/22/0916Rooms 117 and 152 could not be accessed at this time. Third floor room 325 had one smoke/heat detector failed to sound when it was smoked. The device was replaced and retested. Tested normal. The batteries in the fire alarm failed load testing and were replaced at this time.
2255DormitoryFCI 72 Series19872600012018200000000000911210/21/0916There is one smoke detector and two duct detectors on the second floor which could not be accessed at this time (smoke room 211, ducts in north mechanical room.) There was one smoke/heat detector on the third floor, room 311 which did not sound in the room when smoked. This detector was replaced at this time and retested. Tested normal.
2265DormitoryFCI 72 Series19876600012017600000000000911010/26/0916Room 126 could not be accessed at this time. The smoke/heat detector in third floor room 322 failed to sound when smoked. Replaced and retested normal. The duct detector in first floor south mechanical room, failed to alarm when tested.
2270ClassroomSimplex 40021994030002000060000000000115/19/104When the Simplex panel has an alarm on the pull station zone (zone 1), it is not showing on the Monaco panel. Dispatch is not seeing the alarm, but when they poll the Monaco until it shows all normal. The Simplex panel is not sending the alarm on zone 1 to the Monaco panel. Zone 2 (duet detectors) worked normally.
2275DormitoryFCI 72 Series19871600012018100000900000011010/27/0916There were no deficiencies noted.
2281UnknownMonaco Vulcan 11993There is no system in this building per Rick.
2285DormitoryFCI 72 Series19870600012017600000900000010410/29/0916The smoke/heat detector in first floor room 125 failed to sound when smoked. This device was replaced at this time and retested normal. The bell on second floor center hall failed to sound when tested. All other devices tested normal.
2287HazmatMonaco M-1Passed - Voltage w/charger, voltage w/o charger, battery % of charge, battery age check, zone trouble, signal trouble, type signal circuit, AC Input voltage, Lamps/LED Test, Drill Switch, Control Function(s)04/13/102Battery failed load test.
2300AG SchoolFCI 72 Series198401200001100000000000006294/21/10 4/22/1030One of two duct detectors in room 150 does not have a detector head on the smoke. This is not showing a trouble at panel. All the bells only works intermittent. They all need to be changed out. The next day we changed out all six bells for new system sensor horns. The pull station in the east front stairwell did not alarm when tested.
2310369th Operation SecurityGamewell198902050000000000000000294/7/105There were no deficiencies noted.
23404th BDE HQGamewell2009008921070160100300002300795/27/108Two PSD (Photo Smoke Detector) was not tested: First floor bottom of elevator shaft, third floor top of elevator shaft. One of the RRHD (Rate of Rise Heat Detector) was not tested: First floor bottom of elevator shaft.
23504th BDE WarehouseGamewell20090036000000123010000000255/18/10There were no deficiencies noted.
2375USA Finance School AITSimplex 40021994060004000070000000000174/15/108There were no deficiencies noted.
2395Ivy LanesMonaco Radio Panel00000000000000000000004/23/102The battery in the Monaco panel failed load testing and was replaced at this time. (1-12V/7.5Ahr)
2400NCO AcademySimplex 4002199408025040000130010000000514/20/1016No key to elevator reset. Can reset with main breaker in equipment room off main electrical room.
2420Gat 1 ShoppetteMonaco M-11860002000061000000000334/23/104There were no deficiencies noted.
2435MEPSGamewell Multiplex0120130080170047500000000002642/17/1016The heat detectors in the attic are very high and mounted sideways which keeps the testing device from working properly. One pull station (device 1-92) failed to alarm until exercised. Needs to be replaced.
2442DormitorySimplex 40100260720600005700000000001614/9/108Pull station on 1st floor outside at room 107B had no alarm when tested.
2446DormitorySimplex 40100260720600000570000000001614/9/108There were no deficiencies noted.
2447Community BuildingSimplex 40100900040000910000000000324/5/108There were no deficiencies noted.
2449DormitorySimplex 40100260720600005700000000001613/30/10 and 4/10/1016Audio visual device floor A north stairwell failed.
2450Heavy Wheel Vehicle SchoolMonaco M-11996338022000200170000000000822/19/1014The batteries in the panel failed load testing and were replaced at this time (2 - 12V/18Ahr). There are also two audio/visual devices that failed to flash when tested (1st floor area D and E west). There was no access to duct detectors located in units on the roof.
2450DDog KennelMonaco M-110401201000020001000000304/30/104We could not access Narc room at this time. The pull station at the rear of the kennel did not alarm when tested.
2453DormitorySimplex 40100260720600005700000000001614/10/1016There were no deficiencies noted.
2460DormitorySimplex 40100260720600005700000000001613/31/10 and 4/7/1016There were no deficiencies noted.
2461DormitorySimplex 40100260720600005700000000001613/31/10 and 4/6/1016Pull station 1st floor outside by room 103 B had no alarm when tested.
2462S-4 Training CenterEdwards MD-4197800400000000000000000375/12/104The batteries failed load testing and were replaced at this time (2 - 12v/7.5aHR)
2463Community BuildingSimplex 40100904000000910000000000324/2/108One duct detector (M 1-13) did not shut down the air handler. The other three ducts operated normally. The pull stations in the basement are suppose to trip a one (some 4) on the Monaco panel. They did not trip the Monaco when alarmed.
2464DormitoryNotifier MD 4-819770120000004401200000000006810/30/098There were no deficiencies noted.
2466DormitoryEdwards1977012000000440000000000013695/13/108Three. combined smoke/heat detectors failed - 1st floor Mod 10 room B, 3rd floor Mod 6 Room C, 3rd floor Mod 9 Room B. Three bells failed - 1st floor mod 1, end floor mod 11, 3rd floor mod 6.
2467DormitorySimplex 40100260721600005700000000001623/30/10 and 4/6/1016Smoke detector on 2nd floor room 202B had no alarm when tested.
2468DormitorySimplex 40100260720600005700000000001613/30/10 and 4/6/1016Room smoke detectors are Supervisory only with local alarm. The batteries in the NAC panel were four years old and failed load testing. They were replaced at this time. (2-12V/7.7A hr)
250000000000000000000000008/5/10The battery failed load testing and was replaced at this time.
2502AAFES Maintenance ShopMonaco M-105000000000000400000009There were no deficiencies noted.
2510WarehouseTied to 2500 Monaco Radio Panel00000000000000000000006/14/10There were no deficiencies noted.
2512Clothing ClassificationTied to 2522 Monaco Radio Panel000000000000000000000008/16/101There were no deficiencies noted.
2520WarehouseTied to 250000000000000000000000008/3/10There is no fire alarm, sprinkler, or radio panel in this building at this time. There were no deficiencies noted this inspection.
2522WarehouseMonaco Radio Panel000000000000000000000008/16/101There were no deficiencies noted.
2530WarehouseTied to 250000000000000000000000008/3/10There is no fire alarm, sprinkler, or radio panel in this building at this time. There were no deficiencies noted this inspection.
2532LCI WarehouseTied to 252200000000000000000000000No deficiencies noted.
2539DLE Hazmat StorageMonaco M-11992Passed - Voltage w/charger, voltage w/o charger, battery % of charge, battery age check, zone trouble, signal trouble, type signal circuit, AC Input voltage, Lamps/LED Test, Drill Switch, Control Function(s)04/13/102No deficiencies noted.
2549DLE HazMat StorageMonaco M-100000000000000000000004/13/102No deficiencies noted.
2558Pest ControlFCI 72 Series004000004000004000000122/16/103The batteries in the panel failed load testing and were replaced at this time (2 - 12V/7.5 Ahr).
2561HazmatMonacoPassed - Voltage w/charger, voltage w/o charger, battery % of charge, battery age check, zone trouble, signal trouble, type signal circuit, AC Input voltage, Lamps/LED Test, Drill Switch, Control Function(s)0No deficiencies noted.
2562DLE AdministrativeFCI 72 Series301300000213000000000004712/18/108The batteries failed load testing and were replaced at this time (2 12V/7/5Ahr).
2563DLE EnvironmentalSimplex 40012070000151000003000002302/18/105The batteries in the fire alarm panel and in the Monaco panel failed load testing and were replaced at this time (3 - 12V/7.5 Ahr).
2567Corps of EngineersSimplex 4001004000040040000000000122/18/103There were no deficiencies noted.
2570WarehouseSimplex 400100000000000000000000008/3/10There is a sprinkler system only in this building which is monitored by a simplex 4001 fire alarm panel. All the batteries in these panels were dated 05/08 and tested 85%.
2571WarehouseMonaco Radio Panel00000000000000000000008/3/10There is a sprinkler system in this building which is monitored by a Monaco radio panel. The battery in the Monaco radio panel failed load testing and was replaced at this time.
2580WarehouseSimplex 400100000000000000000000101There were no deficiencies noted.
2584WarehouseSimplex 400100000000000000000000008/3/10The panel is only using one zone to monitor the sprinkler system.
2590WarehouseSimplex 400102000000000000000000103There were no deficiencies noted during this inspection.
2594Fuel StationAn outside contractor operates this facility and they will inspect it per Rick.
2600DLE OfficeEdwards 5721-B1993560104000000008010000254/27/106The battery in the Monaco panel failed load testing and was replaced at this time (1-12V/7.5Ahr). The batteries in the fire panel fail load testing and were replaced at this time (2-12V/18Ahr)
2601DLE ShopEdwards 5721-B199101500050000000015000000356/4/108There were no deficiencies noted.
2602DLE ShopEdwards 5721-B19910130006000000009000000286/15/106One duct detector in maintenance bay 23 failed to alarm
2603DLE ShopEdwards EST 2200702100010000000009000002426/15/1014DSD ( Duct Smoke detector) : 2 failed First floor paint prep shop bay 45 and first floor paint prep shop bay 46
2604DLE ShopEdwards 5721-B199202500080000000024000000576/15/1012Tested 8 DSD (Duct smoke detector) 1 failed: First floor South Bay 49. 1 PSSA ( Pull station-single action) not tested: First floor Northwest storage room
2605Weapons PoolEdwards 5721-B19921360404030000005000000351/20/1012The batteries in the fire alarm panel failed load testing and were replaced at this time. The four duct detectors (1st floor outside mechanical room) did not alarm when tested. They also did not put a trouble on the panel when the heads were removed. They do not seem to have any power to them.
2606DLE Motor PoolEdwards 5721-B1992550002000000004000000161/20/108There was a panel trouble on the panel on arrival, but it does not send in on the Monaco and there is no zone trouble showing. Everything on the panel worked normally even with the trouble. One of the batteries in the panel failed load testing at 35%, so both batteries were changed at this time.
2609Telephone Switch BuildingMonaco M-1 Notifier01030000001000000000165/14/104There were no deficiencies noted.
2620Navy Reserve CenterEdwards EST-2001100803002436000000000824/26/1010There were no deficiencies noted.
2785Kennedy HallGamewell IF65020020.030025600010005100000000013482/4/10 2/16/1021One smoke detector in hall by room 532 is hanging down about 1" and needs to be fixed. Five sounder bases failed to sound when smoke detector was tested (rooms 232, 316, 404 bed and living rooms., 515). Pull station at exit by room 425 did not work when first tested. Only worked after exercising switch.
3058Maintenance ShopSimplex 4001199304000000000000000000594/21/102There were no deficiencies noted.
3205DormitorySimplex 40011997This building is being renovated. We will not be doing an inspection this year per Rick.
3210Dining FacilityMonaco Vulcan 119892500011000070000000000256/4/108.0One DSD failed: Floor A South Attic.
3215DormitorySimplex 41001994411301060587000005500000020812/18/0916Combined smoke/heat detector on 1st floor room 108 was not tested. Duct smoke detector 3rd floor AHU-3 west mechanical room was not tested. Horn on 1st floor on post by mechanical room 131, on post by room 106, on post by room 124 and on post by room 127 failed due to no alarm when tested.
3220Office BuildingNotifier AFP-20019920501100000090000000000253/23/104There were no deficiencies noted.
3225DormitoryEdwards EST 220078091310200230251400000000021211/2/09 -11/4/0920First floor northeast rear exit pull station double action failed to alarm when tested. This device was replaced and retested. Tested normal. Five rooms could not be accessed at this time - Room 114, 202, 239, 240 and Closet 312. Eight fixed tem heats in attic were visual checked.
3235DormitorySimplex 40011994431300060088000006000000021012/21/0916The smoke detector in the elevator equipment room did alarm but it did not show on the fire alarm panel. Five horns failed to alarm at this time. Tow on tow. (Post at 203, 227). One on one. (Post at 117, 124, 127). Two duct detectors on AHU-1 failed to shut down air unit. One duct detector on the third floor could not be accessed.
3250HQ BuildingGamewell E3 Series05/18/104
3255Office BuildingGamewell IF6100303713011102415000000000953/25/1016All location descriptions in the panel are old (from when building was MEPS) and need to be updated for current occupants.
3265DormitorySimplex 41001994451300060088000006100000021312/21/0916Four horns failed to sound (2nd floor at room 224, 1st floor at rooms 104 and 120, and basement). One duct detector in first floor east did not shut down air unit. One duct detector on third floor could not be accessed at this time.
3270ClassroomSimplex 4100199205000000002000000000073/26/105There were no deficiencies noted.
3275DormitorySimplex 41001994431300060288000006100000021312/21/0916Could not access room 125 and smoke/heat in room 124 failed to alarm. Three duct detectors failed to shut down the air unit (2 on 1st floor west and 1 on 1st floor east) and one duct detector was missing the smoke head from the detector (3rd floor west).
3276DormitorySimplex 4100431301060087000006100000021112/21/0910There were no deficiencies noted.
3280ClassroomFirelite Sensiscan199205000000002000000000073/26/106The batteries in the fire alarm panel failed load testing and were replaced at this time. (2-12v/7.5 Ahr)
3285DormitorySimplex 4001198706000201800000000000099811/3/0916The batteries in the fire alarm panel failed load testing and were replaced at this time ( 2-12V/7.5Ahr batteries). First floor east and west mechanical rooms duct smoke detector are not wired into system.
3295DormitorySimplex 4001198716000200800000000000099811/12/0916The batteries in the fire alarm panel failed load testing and were replaced at this time (2 -7.5 Ahr). Rooms 106, 107 and 124 could not be accessed at this time.
3295DormitorySimplex 400219888/17/102
3296DormitorySimplex 400219888/17/102
3296Indoor PoolFCI Series 72198905000001002000000000085/19/102Three pull stations failed to alarm (First floor front right pool area, First floor rear left pool area, First floor rear right pool area) and the heat detector was covered for construction and painting. One RRHD ( Rate of rise heat detector) was not tested: First floor rear pool equipment room. One A/V (Audio/Visual signal device) failed: First floor rear pool area.
3301ClassroomEdwards EST 2004800030073000000000253/26/108The labels on the classrooms are reversed from the labels on those device labels in the panel.
3305Magruders PubEdwards 57121983070000020052000000000165/6/106The heat detector in the mechanical room at the fire panel failed to alarm when tested.
3330Victory Brigade HQEdwards196303000000000000000000693/24/104The pull station on the first floor has a wall built around it where it can not be reset. Could not test at this time. The bell in the south basement clacker is moving but is not making contact with the bell. No batteries in the fire alarm panel. The battery in the Monaco panel is 1.5 years old and 85% load tested.
3390Data Processing Center1030000000030000000000164/27/105There are 2 pull stations, 17 smoke detectors, and 3 bells that were connected to an old Halon system in the old computer server room which ware removed from last years inspection. The remaining bells were changed to new audio/visual devices. The panel was changed out for a Simplex 4001 panel. A few of the fix temp heat were checked by shorting the wires and putting an alarm on the panel.
3392MWREdwards6370000000000003000000735/4/102The front right wing that has been added onto the building does not have a signal and the horns in the building cannot be heard in this area.
MC3430USMC Reserve CenterEdwards EST-32008701052400010120100003600786/2/1012Changed batteries in the fire alarm panel. (2-12V/26Ahr) Changed the batteries in both NAC panels (4-12V/7.5Ahr) Changed the battery in the Monaco panel (1-12V/12Ahr). DSD (Duct smoke detector) 4 was not tested : First floor Assembly area, First floor Mechanical area, First floor new gear room, and First floor new gear room. SPPS (Power supply) 2 failed: First floor Outside mechanical room.
MC3431USMC Reserve Center Vehicle MaintenanceEdwards EST-320090032100000010000001000176/1/104The batteries in the fire alarm panel were replaced at this time. (2-12V/26Ahr)
3499BH HQSimplex 400102040001002000000000095/5/102There has been an exit door added to the rear of the building since the last inspection was done. There should be a fire alarm pull station added at this exit.
3500WarehouseTied to 2493 Monaco Radio Panel00000000000000000000008/3/10This building has a Monaco radio panel which monitors a sprinkler system. The battery in the Monaco was dated 4/08 and tested at 90%
3501WarehouseSimplex 4002000000000000000000000008/16/101There were no deficiencies noted during this inspection.
3510WarehouseSimplex 4001020000000000000000001038/16/101One PSSA ( pull station-single action) failed: First floor warehouse office exit.
3511WarehouseSimplex 400100000000000000000000008/3/10There were no deficiencies noted during this inspection.
3521WarehouseSimplex 2001710000000000000000002108/3/10There are two panels in this building. The 4001 in the front office monitors the sprinkler system and the 2001 in the center closet monitors the pull station and heat detectors.
3630Officer's ClubEdwards 5721-B1986560000000060000000000175/6/104The five heat were visual inspected because they are fixed temp. heats but the wiring was tested normal by shorting at the device. The fire alarm panel is automatically silencing the signal circuit on an alarm which also keeps the panel from alerting the Monaco panel. The fire alarm panel needs to be replaced.
3652Golf Course ClubhouseFCI 72 Series1993070005000070000000000194/26/106The batteries in the fire alarm and the Monaco panel tailed load testing and were replaced at this time. (3-12V/7.5Ahr). The A/V in the bar area failed to flash when alarmed.
3662Golf Course HazmatMonacoPassed - Voltage w/charger, voltage w/o charger, battery % of charge, battery age check, zone trouble, signal trouble, type signal circuit, AC Input voltage, Lamps/LED Test, Drill Switch, Control Function(s)0No deficiencies noted.
E3900Scorekeeper TowerEdwards 5721B18300000000300000000000248/17/108There were no deficiencies noted during this inspection.
4110Main PXNotifier AFP 40000142029000037290000000001115/3/1016SPECIAL PROVISIONS: To shut off signals… Pull bell circuit 1 & 2 from top right of power supply board in bottom of panel. Then disable module 198 & 199 in programming. To get to programming... Hit enter. Put in code 11111, enter. Pick 1, enter. it # (module) and the number, enter.
4120Gat @ ShoppetteNotifier System 50019910030020210030000000000296/7/103.0There was a programming trouble. When any fire zone on the panel went into alarm it would activate zones 1-4 on the Monaco panel.
4149Penez GymSpurling03000000000000000000364/30/101The pull station at the front entrance failed to alarm when tested.
4159VideoramaSimplex 400100300000000000300000063/29/1031st floor outside at entrance did not alarm when tested.
4169ShoppetteSpurling06000000000000000000284/29/102There were no deficiencies noted.
4200Orderly Room/SupplySpurling196401000000000000000000010205/19/104One bell in the front of section failed to alarm: First floor section one front door
4203ClassroomEdwards EST 20068000100067000000000371/29/107There were no deficiencies noted.
4204ClassroomGamewell IF602S220021000180030000000000241/29/106The batteries in the fire alarm panel failed load testing and were replaced at this time. Four rate of rise heat detectors show up on the panel as being in the wrong room. All four have the right room number listed in the report.
4205DormitorySimplex 4001198816000200800000000000099811/5/0916Third floor room 319 combined smoke/heat detector did not sound when smoked. The device was replaced and retested. Detector worked normal. Eight rooms could not be accessed at this time - Rooms 113, 122, 209, 236, 250, 309, 329, and 336. The duct detectors are not tied into the fire alarm system.
4210Dining FacilityMonaco Vulcan 119962500014000080000000000296/2/108Air Handler 7, Duct detector 1, No shut down. Air Handler 9, Duct detector 1 & 2, No shut down. Air handler8, duct detector 1&2, No alarm, head missing. Two duct detectors above ceiling in the dining area are bypassed at this time. DSD (Duct smoke detector) 3 failed: Floor A South Attic, Floor A south Attic, and floor A south attic. 2 was not tested: First floor North dinning by leaning ceiling and First floor South dining by leaning ceiling.
4215DormitorySimplex 4001198816000200800000000000099811/6/0916Two rooms could not be accessed at this time - Rooms 227 and 336. The two duct detectors are not wired into the fire alarm system.
4220Orderly Room/SupplySpurling196501000000000000000000010205/19/104Could not access the fifth unit at this time. Two PSSA (Pull Station-Single Action) was not tested : Supply Building one E Co. Front Door and Supply Building one E Co. Rear Door. Two BELL was not tested: Supply Building one E Co. Front Door and Supply Building one E Co. Rear Door.
4225DormitorySimplex 4001198816000200800000000000099811/9/0916Rooms 120, 125, 132, 138, 140, 229 and 236 could not be accessed at this time. The duct detectors are not tied into the fire alarm system.
4230ClassroomSpurling196503000000000000000000255/19/102.0There are four duct detectors in the attics (2 in north, 2 in south) which are not connected to the FACP. They were tested and three did shut down a damper. The forth is on collapsed duct work.
4235DormitorySimplex 4001196606000200760000000000099311/10/0916The duct detectors are not wired into the fire alarm system and access could not be gained at this time. Rooms 122 and 250 were locked and could not be accessed at this time.
4243DormitoryFCI1993This building is being renovated. We will not be doing an inspection this year per Rick.
4250Payroll SupportSpurling196501000000000000000000010205/4/102Drill switch had no alarm when tested. First floor office 4 front and rear pull station and bell was not tested. First floor office 2 front bell had no alarm when tested.
4255Dormitory20090140256203000119010000470002178/11/108One SP/V (Speaker Visual) failed: Third floor Bay 2 west end. One VSIG (Visual only signal) failed: Second floor West latrine south side
4265Dormitory20090140256203000119010000470002178/11/108There were no deficiencies noted during this inspection.
4270Dining FacilityThis building is being renovated. We will not be doing an inspection this year per Rick.
4275Dormitory200901402562030001190100004700008/12/108There were no deficiencies noted during this inspection.
4280Dining Facility0807040100022000000800008/13/108Two PSD ( Photo Smoke Detector) were not tested: First floor storage room 105 and First floor storage room 112B.
4282Telecommunication SwitchSimplex 20011988070900000010001000003215/14/108Any alarm on the three panels will shut off power and put the building on emergency power. Check that the tech has disabled all three panels before checking any panel.
4285Dormitory20090140256203000119010000470002178/12/108One ANNC (Annunciator) was not tested: First floor main entrance. Six SPPS (power supply) was not tested: (2) First floor outside rear electrical room, (2) second floor west electrical room, (2) third floor west electrical room.
4290Orderly Room/SupplySpurling196401000000000000000000010206/3/106There were no deficiencies noted.
4295Dormitory20090140256203000119010000470002178/13/108There were no deficiencies noted.
43105th Brig HQSpurling196403000000000000000000365/4/101The bell in the front office is getting the alarm but the bell is not ringing.
4323UnknownSimplex1965This building is being renovated. We will not be doing an inspection this year per Rick.
4325Post HeadquartersFirelite Scan 42419870013000000000000000003166/8/105There was a trouble on the panel on arrival and still there after complete, but it did not cause any problem to testing.
4330BN HQSpurling196403000000000000000000364/28/102There were no deficiencies noted.
4334HazmatMonaco M-11992Passed - Voltage w/charger, voltage w/o charger, battery % of charge, battery age check, zone trouble, signal trouble, type signal circuit, AC Input voltage, Lamps/LED Test, Drill Switch, Control Function(s)04/13/102No deficiencies noted.
4338EP2Auto Call AC197801070000001000000000093/9/104There were no deficiencies noted.
4340DOCSimplex 400103000000000000600000095/12/103There were no deficiencies noted.
4350Travel OfficeSpurling196504000000000000000000485/12/103There were no deficiencies noted.
435412020000002000000000077/8/108There were no deficiencies noted.
4380BN HQSpurling1964080102050003100000016000638/16/108There were no deficiencies noted.
4392AG MuseumMonaco M-119940502504010062000000000435/11/106There were no deficiencies noted.
4394PAO/Welcome CenterEdwards196403000000002000000000054/30/102The fire alarm panel was changed to a Simplex 4001 panel.
4400Post OfficeMonaco C-100A-1215000000000000000000392/16/102There were no deficiencies noted.
4408Museum AnnesGamewell IF6100102900020010000000001345/6/106The batteries in the fire alarm panel failed load testing and were replaced at this time (2-12V/7.5Ahr)
4416Dozier HouseSimplex 200150030000000000000000192/3/104There were no deficiencies noted.
4420Starship Soldier BarracksGamewell IF6500630140619288000104520100000006732/8/10 - 2/12/1040Annunciator in main lobby failed. Twenty heat detectors failed: 1st floor kitchen, serving area, four in laundry room utility closet, two in mechanical room, three in laundry room, 2nd floor three in mechanical room, two in electrical/storage, four in sleeping bay latrine utility closet, 3rd floor electrical/storage. Pull station 1st floor serving area 1 exit to breezeway failed. Power supply 2nd floor electrical/storage failed load test.
4420Starship Soldier BarracksGamewell IF6500630141619288000104520100000006744/12/1016One heat detector failed testing and was replaced and re-tested at this time (10-53). Now testing normal. One heat detector and one smoke detector could not be accessed at this time (RRHD 1-80, PSD 2-37)
4442Post MuseumGamewell IF6100
4464Century LanesSimplex 200119792709000100040000000000324/28/1014The two smoke detectors over the snack bar failed to alarm. The A/V by the west exit failed to flash when alarmed. The Simplex Tech (Alex) replaced the two smoke detectors over the snack bar and the bad A/V device.
4470ChapelFCI020600010010001000002136/11/104Replaced the battery in the Monaco panel at this time.
4482Coleman GymSimplex 42381974060000000000000000005115/4/102There were no deficiencies noted.
4510Warehouse04000000000000000000268/5/10There were no deficiencies noted.
4580Post ChapelADT Unimode19851094500000040000000000595/21/1016There are four devices which are too high up to be tested: Floor two Nave Center, Floor two Nave Front, Floor two Nave Rear and floor two Office Lobby. A lift would be needed to test these.
4581Scales CDCEdwards EST-219850025830002001820000000001305/7/1016There were no deficiencies noted.
4585Hood Street CDCSimplex 400119860802503030030010000000432/23/108Duct smoke detectors in room 116 and room 123 were not tested.
4600Education CenterSimplex 20011985111048000000300000110010755/20/1010Monaco radio panel for this building is located in building 4679, and tested normal. The batteries are only one year old, but are reading borderline at 80%. Eight smoke detectors failed to alarm when tested: First floor hall by B 109, First floor room B 104,First floor room B 110, Second floor room B 200, Second floor room B 203, Second floor room B 205, Second floor room B 208 and second floor room B 208.
4679Post LibrarySimplex 4208196803000000005000000000085/20/102No deficiencies noted.
4710Credit UnionAdemco Automatic198716000000000000010000000176/7/102No deficiencies noted.
4712PX Mini MallSimplex 40101972020050801200304010000000804/29/108There is a new pull station added in the new Tactical Shop which did alarm in the fire panel but it did not alarm on the Monaco panel. An alarm from this pull station would not automatically be transmitted to the fire department.
4716CommissaryADT (Firelite) Unimode 2001985170155060000176000000000665/101016The batteries in the fire alarm panel, and in the two NAC panels, failed load testing and were replaced at this time (6-12V/7.5Ajhr batteries.)
53851st Brig HDSimplex 42081978080000000000000000003113/9/104The battery in the Monaco panel failed load testing and was replaced at this time (1 - 12V/7.5Ahr)
F5400Map Reading ClassSimplex 40012680000000040000000000386/10/103NO deficiencies noted.
5421DormitoryTied to 5426504000006024000000000211/10/10See Bldg 5426NO deficiencies noted.
5422Dormitory StarshipCerberus MXL0650051813602960102560000000006783/1/10 - 3/5/1080Batteries in POD 4 NAC panel failed load testing and were replaced at this time (2 - 12V/7.5A hr). Could not access the NAC panel in POD 5. door is painted shut. There was a total of 3 combined smoke/heat detectors, 21 heat detectors, 1 visual only signal only and 1 power supply that was not tested. Combined Smoke/Heat detectors in rooms 303, 307 and 309 had no alarm when tested. Heat detector 2nd floor pod 2B side latrine supply had no alarm when tested. Power supply pod 4B side electrical room failed load test. Visual Only Signal 2nd floor pod 4A side latrine, 2nd floor pod 5A side latrine, 2nd floor pod 5B side latrine and room 307 had no alarm when tested.
5423DormitoryTied to 54265040000012028000000000311/10/10See Bldg 5426Fixed temp heat detector 1st floor drill sgt office/west storage and 1st floor eat storage was not tested. Pull station double action 1st floor east bay south had no alarm when tested.
5424DormitoryTied to 5427004700050024000000000221/10/10See Bldg 5427Rate of rise heat detector on 1st floor supply room TA-50 was not tested.
5425DormitoryTied to 5427004700050024000000000221/10/10See Bldg 5427Rate of rise heat detector on 1st floor supply room TA-50 was not tested.
5426Orderly RoomEdwards EST 2907000000050000000000211/10/108Pull station double action 1st floor southeast storage was not tested. Fixed temp heat detector 1st floor southeast storage was not tested. The batteries in the fire alarm panel failed load testing and were replaced at this time.
5427Orderly RoomEdwards EST 2008000090032000000000221/10/108Rate of rise heat detector on 1st floor supply room B side front and rear was not tested. Two pull station double action 1st floor supply room B front side and one pull station double action 1st floor supply room B side rear was not tested. Audio/Visual 1st floor supply room B side front was not tested.
5432CO HQSimplex 420802000000000000000000243/29/103There were no deficiencies noted.
5450Strom Thurmond BldgGE EST 2200700158080000380000000000695/5/109The batteries failed load testing and were replaced at this time (FACP 2-12V/12Ahr, NAC 2-12V/7.5Ahr, Monaco 1-12V/7.5Ahr). The pull station in pod 4, room 118 failed to alarm when tested. It put an open line trouble on the panel. This pull needs to be replaced with a new pull station which is addressable. The smoke detectors in the main data room and electrical room will open the pre-action system for this room.
5453DormitoryTied to 5426504000000020000000000111/10/10See Bldg 5426No deviancies noted.
5472DormitoryTied to 54265020000012017000000000271/10/10See Bldg 5426NO deficiencies noted.
5473DormitoryTied to 54270021300040025000000000261/10/10See Bldg 5427Two rate of rise heat detector 1st floor supply room was not tested.