Fire Alarm Inspections
| FORT JACKSON SOUTH CAROLINA | |||||||||||||||||||||||||||||
| FIRE ALARM INSPECTION LOG | |||||||||||||||||||||||||||||
| FTHD - FixedTemp Heat Detector PBSA - Pull Box Single Action PSDA - Pull Box Double Action PSD - Photo Smoke Detector SPPS - Power Supply DSD - Duct Smoke Detector HD - Heat Detector | RRHD - Rate of Rise Heat Detector CSH - Combined Smoke/Heat Detector SPKR - Speaker A/V - Audio/Visual Signal Device VSIG - Visual Only Signal NAC - NAC Booster Panel ANNC - Annunciator | HORN - Horn DHCD - Door Closer with Detector ELPR- Elevator Primary Recall ELAL - Elevator Alternate Recall SP/V - Speaker Visual RCVR - Fire Control Annunciator BELLS - Bells | SSSD- Single Station Smoke Detector WF-Water Flow Detector | ||||||||||||||||||||||||||
| BLDG | NAME OF BLDG | ALARM PANEL | Year | # FTHD | # PBSA | # PBDA | # PSD | # SPPS | # DSD | #HD | # RRHD | # CSH | # SPKR | # A/V | # VSIG | # NAC | # ANNC | # HORN | # DHCD | # ELPR | # ELAL | # SP/V | #RCVR | # BELLS | # WF | TOTAL NUMBER OF DEVICES IN BUILDING | INSPECT DATE | # HRS | NOTES |
| 1525 | USAR Center | Simplex 4100U | 2008 | 0 | 0 | 11 | 18 | 4 | 14 | 0 | 2 | 0 | 0 | 0 | 113 | 0 | 1 | 0 | 0 | 1 | 1 | 117 | 0 | 0 | 282 | 5/11/10 | 10 | The batteries in one of the NAC panels failed load testing and were replaced at this time (2-12V/7.5Ahr). Because the batteries only lasted about a year and the last batteries in this panel did not last long, the Simplex tech came by to adjust the charger in this NAC panel. | |
| 1541 | Army Lodging Maintenance Shop | FCI FC-72 | 0 | 0 | 5 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 6 | 4/30/10 | 2 | There were no deficiencies noted. | ||
| 1542 | Army Lodging Warehouse | FCI FC-72 | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 2 | 4/30/10 | 2 | There were no deficiencies noted. | ||
| 1698 | Chemical Storage | Monaco Vulcan 1 | Passed - Voltage w/charger, voltage w/o charger, battery % of charge, battery age check, zone trouble, signal trouble, type signal circuit, AC Input voltage, Earth Detection, Lamps/LED Test, Drill Switch, Control Function(s) | 0 | No deficiencies noted. | ||||||||||||||||||||||||
| 1699 | Hazmat | Monaco M-1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 4/13/10 | 2 | Battery failed load test. | |
| 1701 | USAR Vehicle Main Shop | Monaco C-100A-12 | 1984 | 0 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 3 | 7 | 1/20/10 | 4 | There were no deficiencies noted. | |
| 1704 | Hazmat | Monaco M-1 | 1995 | Passed - Voltage w/charger, voltage w/o charger, battery % of charge, battery age check, zone trouble, signal trouble, type signal circuit, AC Input voltage, Lamps/LED Test, Drill Switch, Control Function(s) | 0 | 4/13/10 | 2 | No deficiencies noted. | |||||||||||||||||||||
| 1705 | Dormitory | Edwards EST-2 | 0 | 0 | 10 | 30 | 0 | 0 | 0 | 7 | 0 | 0 | 22 | 8 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 77 | 10/16/09 | 6 | Photo smoke detector on 1st floor west bay office 2 and 2nd floor east bay office 2/storage was not tested. Rate of rise heat detector on 2nd floor west bay storage room was not tested. There were no deficiencies noted. | ||
| 1706 | Dormitory | Edwards EST-2 | 0 | 0 | 10 | 31 | 0 | 0 | 0 | 6 | 0 | 0 | 22 | 8 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 77 | 10/16/09 | 6 | The heat detectors on first floor showed as first floor smokes and the second floor heats showed as second floor smokes on the Monaco panel. Photo smoke detectors on 2nd floor east office/storage, 2nd floor west bay office 1 and 2nd floor west bay utility room/office 2 were not tested. | ||
| 1741 | Administrative | Simplex 4001 | 1991 | 0 | 4 | 0 | 20 | 0 | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 4 | 29 | 10/30/09 | 4 | There were no deficiencies noted. | |
| 1742 | Administrative | Simplex 4001 | 1991 | 0 | 4 | 0 | 20 | 0 | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 4 | 29 | 10/30/09 | 4 | The two 7.5 Ahr batteries in the fire alarm panel failed load testing and were replaced at this time. | |
| 1744 | Maintenance | Simplex 4002 | 1991 | 4 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 9 | 10/9/09 | 2 | The battery in the Monaco panel failed load testing and was replaced with a new 2.3 Ahr battery. There were no deficiencies noted. | |
| 1745 | Storage | Simplex 4002 | 1991 | 2 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 5 | 10/9/09 | 2 | There were no deficiencies noted. | |
| 1865 | PX Annex | Monaco M Series | 2003 | 0 | 0 | 3 | 0 | 0 | 2 | 23 | 0 | 0 | 0 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 32 | 10/9/09 | 4 | There were no deficiencies noted. | |
| 1867 | 120 AG | Fireshield + | 0 | 5 | 0 | 0 | 0 | 0 | 0 | 26 | 0 | 0 | 0 | 0 | 0 | 0 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 35 | 10/9/09 | 8 | There were no deficiencies noted. | ||
| 1867 | 120 AG | Fireshield + | 0 | 5 | 0 | 0 | 0 | 0 | 0 | 26 | 0 | 0 | 0 | 0 | 0 | 0 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 35 | 3/23/10 | 4 | There were no deficiencies noted. | ||
| 1872 | Dormitory | Edwards EST-2 | 2007 | 0 | 0 | 17 | 79 | 0 | 2 | 13 | 0 | 0 | 0 | 44 | 12 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 167 | 10/8/09 | 16 | Smoke detector on 1st floor room 136 at hall by station 6 and 2nd floor room 229 hall by station 7 were not tested. There were no deficiencies noted. | |
| 1875 | Dining Facility | Fire Lite Sens 1000 | 1992 | 0 | 6 | 0 | 0 | 0 | 3 | 13 | 0 | 0 | 0 | 3 | 0 | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 26 | 3/23/10 | 4 | The battery in Monaco panel failed load testing and was replaced at this time. (12V/7.5Ahr) | |
| 1877 | Dormitory | Gamewell Zans 400 | 1992 | 1 | 25 | 0 | 57 | 0 | 0 | 0 | 8 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 14 | 105 | 10/2/09 | 16 | Smoke/heat detector in bay 4 west end failed to alarm when tested. A diode in the head was broken. The detector was replaced with another System Sensor 2WT-B and re-tested. The new device worked normal. There were four rooms which could not be accessed at this time, !st floor cadre, 2nd floor female baggage room, 2nd floor room 216 and 3rd floor commander's office. | |
| 1880 | Dormitory | Gamewell Zans 400 | 1985 | 11 | 26 | 0 | 51 | 0 | 0 | 0 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 15 | 105 | 10/7/09 | 16 | One pull station (bay 1) had a broken switch inside the cover and was replaced and retested at this time. Two rooms ( 3rd floor not cadre office and south cadre office) could not be accessed at this time. Two smoke detectors (2nd floor bay 6 south, 3rd floor linen room) failed to alarm and were replaced and retested normal at this time. One bell (on the 2nd floor balcony) stated alarming but quit after a minute, and needs to be replaced. | |
| 1889 | Dormitory | Gamewell Zans 400 | 1985 | 1 | 10 | 0 | 75 | 0 | 0 | 0 | 5 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 6 | 97 | 10/1/09 | 16 | The batteries failed load testing and were replaced at this time. There was also a heat detector in the second floor laundry room (215) which failed to alarm when tested. The heat head was replaced and re-tested. All devices now testing normally. | |
| 1892 | Dormitory | Gamewell Zans 400 | 1992 | 1 | 25 | 0 | 53 | 0 | 2 | 0 | 10 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 15 | 106 | 10/6/09 | 16 | Smoke detector on 3rd floor east cadre office was not tested. There were no deficiencies noted. | |
| 1895 | 120th AG HQ | Simplex 4001 | 1972 | 0 | 17 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 34 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 51 | 10/16/09 | 4 | Pull station single action on 1st floor far left side has had a message center installed over it blocking access to the reset screw. There were no deficiencies noted. | |
| 1897 | Dormitory | Gamewell Zans 400 | 1992 | 5 | 25 | 0 | 50 | 0 | 0 | 0 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 15 | 97 | 10/5/09 | 16 | The batteries in the fire alarm panel failed load testing and were replaced at this time (2/7.5 Ahr battery). The heat detector that failed (1st floor main supply room) was a Simplex 4098-9402-135 fixed temp.rate of rise heat. There were no replacement for this in the shop and still needs repair. | |
| 2009 | Vanguard Gym | Edwards | 0 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 2 | 5 | 4/30/10 | 1 | The fire alarm panel is not operating and may need to be replaced. | ||
| 2075 | 187th Ord WH Vehicle School | Edwards | 2009 | 0 | 2 | 0 | 0 | 0 | 0 | 0 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 6 | 0 | 0 | 0 | 10 | 8/17/10 | 6 | There were no deficiencies |
| 2078 | 187th Ord WH Vehicle School | Edwards | 2009 | 0 | 0 | 6 | 10 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 10 | 0 | 0 | 0 | 27 | 8/19/10 | 4 | There were no deficiencies noted. |
| 2079 | 187th Ord WH Vehicle School | Edwards | 2009 | 0 | 0 | 2 | 1 | 0 | 1 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 5 | 0 | 0 | 0 | 10 | 8/18/10 | 4 | There were no deficiencies noted. |
| 2090 | 187th Ord BN Motor Pool | Simplex 4002 | 1990 | 76 | 5 | 0 | 0 | 0 | 0 | 0 | 0 | 8 | 0 | 5 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 94 | 2/1/10 | 8 | Audio Visual on 1st floor rear of bay failed inspection. | |
| 2100 | Applied Instruction | Notifier 72 Series | 0 | 0 | 28 | 0 | 0 | 23 | 0 | 0 | 0 | 0 | 26 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 77 | 2/2/10 | 12 | Three pull stations failed to alarm when pulled. All the pull stations are getting old and the switches are sticking. Two duct detectors failed to alarm. One as being jumped and now needs to be re-connected. The other just failed to alarm. | ||
| R2101 | Classroom | Edwards EST 2 | 0 | 0 | 5 | 0 | 0 | 0 | 0 | 6 | 0 | 0 | 5 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 16 | 1/5/10 | 4 | No deficiencies noted. | ||
| R2102 | Orderly Room | Edwards EST 2 | 0 | 0 | 6 | 0 | 0 | 0 | 0 | 21 | 0 | 0 | 11 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 38 | 1/6/10 | 4 | No deficiencies noted. | ||
| R2103 | Classroom | Edwards EST 2 | 0 | 0 | 5 | 0 | 0 | 0 | 0 | 6 | 0 | 0 | 5 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 16 | 1/5/10 | 4 | No deficiencies noted. | ||
| R2104 | BN HQ | Edwards EST 2 | 0 | 0 | 5 | 0 | 0 | 0 | 0 | 6 | 0 | 0 | 10 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 23 | 1/6/10 | 4 | No deficiencies noted. | ||
| R2105 | Dormitory | Edwards EST 2 | 0 | 0 | 4 | 18 | 0 | 0 | 0 | 0 | 0 | 0 | 12 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 34 | 1/5/10 | 4 | The sounder base of smoke detector in the south bay, sleeping room 1 does not sound when device is in alarm. The base needs to be replaced. | ||
| R2106 | Dormitory | Edwards EST 2 | 0 | 0 | 4 | 18 | 0 | 0 | 0 | 0 | 0 | 0 | 14 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 36 | 1/5/10 | 4 | There were no deficiencies noted. | ||
| R2107 | Dormitory | Edwards EST 2 | 0 | 0 | 4 | 18 | 0 | 0 | 0 | 0 | 0 | 0 | 14 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 36 | 1/6/10 | 4 | The audio/visual in the south bay shower did not sound or flash when the fire alarm was set off. | ||
| R2108 | Dormitory | Edwards EST 2 | 0 | 0 | 3 | 14 | 0 | 0 | 0 | 0 | 0 | 0 | 14 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 31 | 1/6/10 | 4 | There were no deficiencies noted. | ||
| 2119 | Admin School | SFL 400 Notifier | 1991 | 0 | 12 | 0 | 0 | 0 | 5 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 7 | 24 | 2/3/10 | 12 | One pull station failed to alarm when tested. Three duct detectors failed to alarm when tested. | |
| 2139 | Mini Laundry | FCI 72 Series | 1984 | 0 | 0 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 6 | 9/22/10 | 2.0 | Two horns failed testing: First floor Office hallway and first floor outside on BLDG. |
| 2159 | Exchange Branch | Simplex 4002 | 1996 | 0 | 7 | 0 | 0 | 0 | 4 | 0 | 19 | 0 | 0 | 5 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 35 | 4/29/10 | 2 | When zone 5 goes into alarm it does not alarm zone 5 on the Monaco panel. Also there is no panel trouble on the Monaco panel. If any zone goes into trouble that zone will show a trouble on the Monaco, but a signal or panel trouble will not be reported to fire dispatch. | |
| G2169 | Alpine Lodge | Monaco FACP | 3 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 7 | 5/5/10 | 2 | The Gentex smoke detectors did sound locally when tested but they did not pt an alarm on the fire alarm panel. | ||
| 2190 | Applied Instruction | Simplex 4001 | 1987 | 14 | 6 | 0 | 5 | 0 | 2 | 0 | 0 | 0 | 0 | 8 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 35 | 2/2/10 | 4 | The battery in the Monaco panel failed load testing and was replaced at this time. (12V, 2.3Ahr) | |
| 2200 | Storage GP Inst | FCI 72 Series | 1984 | 0 | 11 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 5 | 0 | 0 | 0 | 0 | 0 | 0 | 16 | 5/4/10 | 2 | The fire alarm control panel did not report troubles or alarms to the Monaco panel in Bldg. 2119. | |
| 2205 | Dormitory | Gamewell Flex 610 | 2002 | 0 | 8 | 0 | 124 | 0 | 12 | 7 | 0 | 0 | 0 | 12 | 14 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 177 | 10/14/09 | 16 | Photo smoke detector on 1st floor room 136, 1st floor room 138 and 1st floor room 140 were not tested. There were no deficiencies noted. | |
| 2210 | SSI Classroom | Simplex 4002 | 1994 | 0 | 3 | 0 | 0 | 0 | 2 | 0 | 0 | 0 | 0 | 6 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 11 | 2/4/10 | 3 | There were no deficiencies noted. | |
| 2210 | SSI Classroom | Simplex 4002 | 0 | 3 | 0 | 0 | 0 | 2 | 0 | 0 | 0 | 0 | 6 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 11 | 3/24/10 | 4 | There were no deficiencies noted. | ||
| 2215 | Dormitory | FCI 72 Series | 1986 | 0 | 6 | 0 | 0 | 0 | 12 | 0 | 1 | 76 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 9 | 104 | 10/19/09 | 16 | Twelve duct smoke detectors did not go into alarm even after heavy smoke - Two on 1st floor mechanical room, two on 2nd floor west mechanical room, two on 2nd floor east mechanical room, two on 2nd floor west mechanical room, two on 3rd floor east mechanical room and two on 3rd floor mechanical room. The four smoke detectors in rooms 221, 230, 312, 325 would not sound locally when smoked. The smoke detector in room 212 would not stop sounding locally after smoked. All five of the bad smoke/heat detectors were replaced and retested at this time. All tested normal. Room 132 could not be accessed at this time. | |
| 2225 | Dormitory | FCI 72 Series | 1986 | 0 | 6 | 0 | 12 | 0 | 0 | 0 | 1 | 76 | 0 | 0 | 0 | 0 | 0 | 9 | 0 | 0 | 0 | 0 | 0 | 0 | 104 | 10/15/09 | 16 | Rooms 123, 124, 128 and 135 could not be accessed at this time. Duct smoke detector 1st floor east mechanical room went into alarm but did not alarm the panel. The batteries in the fire alarm panel failed load testing and were replaced at this time. | |
| 2230 | Dining Facility | Edwards 5721-B | 1988 | 0 | 5 | 0 | 0 | 0 | 3 | 0 | 0 | 0 | 0 | 5 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 13 | 6/8/10 | Batteries failed load testing and were replaced. Three DSD (Duct Smoke Detectors) failed: first floor HVAC. | ||
| 2235 | Dormitory | FCI 72 Series | 1986 | 0 | 6 | 0 | 0 | 0 | 6 | 0 | 1 | 76 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 9 | 98 | 10/20/09 | 16 | Rooms 107 and 114 could not be accessed at this time. First floor east mechanical room duct detector failed to alarm when tested. Third floor at west stairwell pull station failed to alarm when tested. The two batteries in the fire panel failed load testing and were replaced at this time. | |
| 2245 | Dormitory | Monaco C-100A-12 | 1982 | 0 | 6 | 0 | 0 | 0 | 2 | 0 | 0 | 106 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 9 | 123 | 10/28/09 | 16 | Two bells failed to alarm when tested, third floor east end hall and first floor center hall. | |
| 2253 | Dormitory | Simplex 4001 | 1983 | 0 | 6 | 0 | 12 | 0 | 0 | 1 | 0 | 76 | 0 | 0 | 0 | 0 | 0 | 9 | 0 | 0 | 0 | 0 | 0 | 0 | 104 | 10/22/09 | 16 | Rooms 117 and 152 could not be accessed at this time. Third floor room 325 had one smoke/heat detector failed to sound when it was smoked. The device was replaced and retested. Tested normal. The batteries in the fire alarm failed load testing and were replaced at this time. | |
| 2255 | Dormitory | FCI 72 Series | 1987 | 2 | 6 | 0 | 0 | 0 | 12 | 0 | 1 | 82 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 9 | 112 | 10/21/09 | 16 | There is one smoke detector and two duct detectors on the second floor which could not be accessed at this time (smoke room 211, ducts in north mechanical room.) There was one smoke/heat detector on the third floor, room 311 which did not sound in the room when smoked. This detector was replaced at this time and retested. Tested normal. | |
| 2265 | Dormitory | FCI 72 Series | 1987 | 6 | 6 | 0 | 0 | 0 | 12 | 0 | 1 | 76 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 9 | 110 | 10/26/09 | 16 | Room 126 could not be accessed at this time. The smoke/heat detector in third floor room 322 failed to sound when smoked. Replaced and retested normal. The duct detector in first floor south mechanical room, failed to alarm when tested. | |
| 2270 | Classroom | Simplex 4002 | 1994 | 0 | 3 | 0 | 0 | 0 | 2 | 0 | 0 | 0 | 0 | 6 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 11 | 5/19/10 | 4 | When the Simplex panel has an alarm on the pull station zone (zone 1), it is not showing on the Monaco panel. Dispatch is not seeing the alarm, but when they poll the Monaco until it shows all normal. The Simplex panel is not sending the alarm on zone 1 to the Monaco panel. Zone 2 (duet detectors) worked normally. | |
| 2275 | Dormitory | FCI 72 Series | 1987 | 1 | 6 | 0 | 0 | 0 | 12 | 0 | 1 | 81 | 0 | 0 | 0 | 0 | 0 | 9 | 0 | 0 | 0 | 0 | 0 | 0 | 110 | 10/27/09 | 16 | There were no deficiencies noted. | |
| 2281 | Unknown | Monaco Vulcan 1 | 1993 | There is no system in this building per Rick. | |||||||||||||||||||||||||
| 2285 | Dormitory | FCI 72 Series | 1987 | 0 | 6 | 0 | 0 | 0 | 12 | 0 | 1 | 76 | 0 | 0 | 0 | 0 | 0 | 9 | 0 | 0 | 0 | 0 | 0 | 0 | 104 | 10/29/09 | 16 | The smoke/heat detector in first floor room 125 failed to sound when smoked. This device was replaced at this time and retested normal. The bell on second floor center hall failed to sound when tested. All other devices tested normal. | |
| 2287 | Hazmat | Monaco M-1 | Passed - Voltage w/charger, voltage w/o charger, battery % of charge, battery age check, zone trouble, signal trouble, type signal circuit, AC Input voltage, Lamps/LED Test, Drill Switch, Control Function(s) | 0 | 4/13/10 | 2 | Battery failed load test. | ||||||||||||||||||||||
| 2300 | AG School | FCI 72 Series | 1984 | 0 | 12 | 0 | 0 | 0 | 0 | 11 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 6 | 29 | 4/21/10 4/22/10 | 30 | One of two duct detectors in room 150 does not have a detector head on the smoke. This is not showing a trouble at panel. All the bells only works intermittent. They all need to be changed out. The next day we changed out all six bells for new system sensor horns. The pull station in the east front stairwell did not alarm when tested. | |
| 2310 | 369th Operation Security | Gamewell | 1989 | 0 | 2 | 0 | 5 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 2 | 9 | 4/7/10 | 5 | There were no deficiencies noted. | |
| 2340 | 4th BDE HQ | Gamewell | 2009 | 0 | 0 | 8 | 9 | 2 | 1 | 0 | 7 | 0 | 16 | 0 | 10 | 0 | 3 | 0 | 0 | 0 | 0 | 23 | 0 | 0 | 79 | 5/27/10 | 8 | Two PSD (Photo Smoke Detector) was not tested: First floor bottom of elevator shaft, third floor top of elevator shaft. One of the RRHD (Rate of Rise Heat Detector) was not tested: First floor bottom of elevator shaft. | |
| 2350 | 4th BDE Warehouse | Gamewell | 2009 | 0 | 0 | 3 | 6 | 0 | 0 | 0 | 0 | 0 | 0 | 12 | 3 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 25 | 5/18/10 | There were no deficiencies noted. | ||
| 2375 | USA Finance School AIT | Simplex 4002 | 1994 | 0 | 6 | 0 | 0 | 0 | 4 | 0 | 0 | 0 | 0 | 7 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 17 | 4/15/10 | 8 | There were no deficiencies noted. | |
| 2395 | Ivy Lanes | Monaco Radio Panel | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 4/23/10 | 2 | The battery in the Monaco panel failed load testing and was replaced at this time. (1-12V/7.5Ahr) | ||
| 2400 | NCO Academy | Simplex 4002 | 1994 | 0 | 8 | 0 | 25 | 0 | 4 | 0 | 0 | 0 | 0 | 13 | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 51 | 4/20/10 | 16 | No key to elevator reset. Can reset with main breaker in equipment room off main electrical room. | |
| 2420 | Gat 1 Shoppette | Monaco M-1 | 18 | 6 | 0 | 0 | 0 | 2 | 0 | 0 | 0 | 0 | 6 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 33 | 4/23/10 | 4 | There were no deficiencies noted. | ||
| 2435 | MEPS | Gamewell Multiplex | 0 | 12 | 0 | 130 | 0 | 8 | 0 | 17 | 0 | 0 | 47 | 50 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 264 | 2/17/10 | 16 | The heat detectors in the attic are very high and mounted sideways which keeps the testing device from working properly. One pull station (device 1-92) failed to alarm until exercised. Needs to be replaced. | ||
| 2442 | Dormitory | Simplex 4010 | 0 | 26 | 0 | 72 | 0 | 6 | 0 | 0 | 0 | 0 | 57 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 161 | 4/9/10 | 8 | Pull station on 1st floor outside at room 107B had no alarm when tested. | ||
| 2446 | Dormitory | Simplex 4010 | 0 | 26 | 0 | 72 | 0 | 6 | 0 | 0 | 0 | 0 | 0 | 57 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 161 | 4/9/10 | 8 | There were no deficiencies noted. | ||
| 2447 | Community Building | Simplex 4010 | 0 | 9 | 0 | 0 | 0 | 4 | 0 | 0 | 0 | 0 | 9 | 10 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 32 | 4/5/10 | 8 | There were no deficiencies noted. | ||
| 2449 | Dormitory | Simplex 4010 | 0 | 26 | 0 | 72 | 0 | 6 | 0 | 0 | 0 | 0 | 57 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 161 | 3/30/10 and 4/10/10 | 16 | Audio visual device floor A north stairwell failed. | ||
| 2450 | Heavy Wheel Vehicle School | Monaco M-1 | 1996 | 3 | 38 | 0 | 22 | 0 | 0 | 0 | 2 | 0 | 0 | 17 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 82 | 2/19/10 | 14 | The batteries in the panel failed load testing and were replaced at this time (2 - 12V/18Ahr). There are also two audio/visual devices that failed to flash when tested (1st floor area D and E west). There was no access to duct detectors located in units on the roof. | |
| 2450D | Dog Kennel | Monaco M-1 | 10 | 4 | 0 | 12 | 0 | 1 | 0 | 0 | 0 | 0 | 2 | 0 | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 30 | 4/30/10 | 4 | We could not access Narc room at this time. The pull station at the rear of the kennel did not alarm when tested. | ||
| 2453 | Dormitory | Simplex 4010 | 0 | 26 | 0 | 72 | 0 | 6 | 0 | 0 | 0 | 0 | 57 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 161 | 4/10/10 | 16 | There were no deficiencies noted. | ||
| 2460 | Dormitory | Simplex 4010 | 0 | 26 | 0 | 72 | 0 | 6 | 0 | 0 | 0 | 0 | 57 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 161 | 3/31/10 and 4/7/10 | 16 | There were no deficiencies noted. | ||
| 2461 | Dormitory | Simplex 4010 | 0 | 26 | 0 | 72 | 0 | 6 | 0 | 0 | 0 | 0 | 57 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 161 | 3/31/10 and 4/6/10 | 16 | Pull station 1st floor outside by room 103 B had no alarm when tested. | ||
| 2462 | S-4 Training Center | Edwards MD-4 | 1978 | 0 | 0 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 3 | 7 | 5/12/10 | 4 | The batteries failed load testing and were replaced at this time (2 - 12v/7.5aHR) | |
| 2463 | Community Building | Simplex 4010 | 0 | 9 | 0 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 9 | 10 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 32 | 4/2/10 | 8 | One duct detector (M 1-13) did not shut down the air handler. The other three ducts operated normally. The pull stations in the basement are suppose to trip a one (some 4) on the Monaco panel. They did not trip the Monaco when alarmed. | ||
| 2464 | Dormitory | Notifier MD 4-8 | 1977 | 0 | 12 | 0 | 0 | 0 | 0 | 0 | 0 | 44 | 0 | 12 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 68 | 10/30/09 | 8 | There were no deficiencies noted. | |
| 2466 | Dormitory | Edwards | 1977 | 0 | 12 | 0 | 0 | 0 | 0 | 0 | 0 | 44 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 13 | 69 | 5/13/10 | 8 | Three. combined smoke/heat detectors failed - 1st floor Mod 10 room B, 3rd floor Mod 6 Room C, 3rd floor Mod 9 Room B. Three bells failed - 1st floor mod 1, end floor mod 11, 3rd floor mod 6. | |
| 2467 | Dormitory | Simplex 4010 | 0 | 26 | 0 | 72 | 1 | 6 | 0 | 0 | 0 | 0 | 57 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 162 | 3/30/10 and 4/6/10 | 16 | Smoke detector on 2nd floor room 202B had no alarm when tested. | ||
| 2468 | Dormitory | Simplex 4010 | 0 | 26 | 0 | 72 | 0 | 6 | 0 | 0 | 0 | 0 | 57 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 161 | 3/30/10 and 4/6/10 | 16 | Room smoke detectors are Supervisory only with local alarm. The batteries in the NAC panel were four years old and failed load testing. They were replaced at this time. (2-12V/7.7A hr) | ||
| 2500 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 8/5/10 | The battery failed load testing and was replaced at this time. | |||||
| 2502 | AAFES Maintenance Shop | Monaco M-1 | 0 | 5 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 9 | There were no deficiencies noted. | |||
| 2510 | Warehouse | Tied to 2500 Monaco Radio Panel | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 6/14/10 | There were no deficiencies noted. | |||
| 2512 | Clothing Classification | Tied to 2522 Monaco Radio Panel | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 8/16/10 | 1 | There were no deficiencies noted. | |
| 2520 | Warehouse | Tied to 2500 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 8/3/10 | There is no fire alarm, sprinkler, or radio panel in this building at this time. There were no deficiencies noted this inspection. | |||
| 2522 | Warehouse | Monaco Radio Panel | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 8/16/10 | 1 | There were no deficiencies noted. | |
| 2530 | Warehouse | Tied to 2500 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 8/3/10 | There is no fire alarm, sprinkler, or radio panel in this building at this time. There were no deficiencies noted this inspection. | |||
| 2532 | LCI Warehouse | Tied to 2522 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | No deficiencies noted. | |||
| 2539 | DLE Hazmat Storage | Monaco M-1 | 1992 | Passed - Voltage w/charger, voltage w/o charger, battery % of charge, battery age check, zone trouble, signal trouble, type signal circuit, AC Input voltage, Lamps/LED Test, Drill Switch, Control Function(s) | 0 | 4/13/10 | 2 | No deficiencies noted. | |||||||||||||||||||||
| 2549 | DLE HazMat Storage | Monaco M-1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 4/13/10 | 2 | No deficiencies noted. | ||
| 2558 | Pest Control | FCI 72 Series | 0 | 0 | 4 | 0 | 0 | 0 | 0 | 0 | 4 | 0 | 0 | 0 | 0 | 0 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 12 | 2/16/10 | 3 | The batteries in the panel failed load testing and were replaced at this time (2 - 12V/7.5 Ahr). | ||
| 2561 | Hazmat | Monaco | Passed - Voltage w/charger, voltage w/o charger, battery % of charge, battery age check, zone trouble, signal trouble, type signal circuit, AC Input voltage, Lamps/LED Test, Drill Switch, Control Function(s) | 0 | No deficiencies noted. | ||||||||||||||||||||||||
| 2562 | DLE Administrative | FCI 72 Series | 30 | 13 | 0 | 0 | 0 | 0 | 0 | 21 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 4 | 71 | 2/18/10 | 8 | The batteries failed load testing and were replaced at this time (2 12V/7/5Ahr). | ||
| 2563 | DLE Environmental | Simplex 4001 | 2 | 0 | 7 | 0 | 0 | 0 | 0 | 15 | 1 | 0 | 0 | 0 | 0 | 0 | 3 | 0 | 0 | 0 | 0 | 0 | 2 | 30 | 2/18/10 | 5 | The batteries in the fire alarm panel and in the Monaco panel failed load testing and were replaced at this time (3 - 12V/7.5 Ahr). | ||
| 2567 | Corps of Engineers | Simplex 4001 | 0 | 0 | 4 | 0 | 0 | 0 | 0 | 4 | 0 | 0 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 12 | 2/18/10 | 3 | There were no deficiencies noted. | ||
| 2570 | Warehouse | Simplex 4001 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 8/3/10 | There is a sprinkler system only in this building which is monitored by a simplex 4001 fire alarm panel. All the batteries in these panels were dated 05/08 and tested 85%. | |||
| 2571 | Warehouse | Monaco Radio Panel | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 8/3/10 | There is a sprinkler system in this building which is monitored by a Monaco radio panel. The battery in the Monaco radio panel failed load testing and was replaced at this time. | |||
| 2580 | Warehouse | Simplex 4001 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 1 | There were no deficiencies noted. | |||
| 2584 | Warehouse | Simplex 4001 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 8/3/10 | The panel is only using one zone to monitor the sprinkler system. | |||
| 2590 | Warehouse | Simplex 4001 | 0 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 3 | There were no deficiencies noted during this inspection. | |||
| 2594 | Fuel Station | An outside contractor operates this facility and they will inspect it per Rick. | |||||||||||||||||||||||||||
| 2600 | DLE Office | Edwards 5721-B | 1993 | 5 | 6 | 0 | 1 | 0 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 8 | 0 | 1 | 0 | 0 | 0 | 0 | 25 | 4/27/10 | 6 | The battery in the Monaco panel failed load testing and was replaced at this time (1-12V/7.5Ahr). The batteries in the fire panel fail load testing and were replaced at this time (2-12V/18Ahr) | |
| 2601 | DLE Shop | Edwards 5721-B | 1991 | 0 | 15 | 0 | 0 | 0 | 5 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 15 | 0 | 0 | 0 | 0 | 0 | 0 | 35 | 6/4/10 | 8 | There were no deficiencies noted. | |
| 2602 | DLE Shop | Edwards 5721-B | 1991 | 0 | 13 | 0 | 0 | 0 | 6 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 9 | 0 | 0 | 0 | 0 | 0 | 0 | 28 | 6/15/10 | 6 | One duct detector in maintenance bay 23 failed to alarm | |
| 2603 | DLE Shop | Edwards EST 2 | 2007 | 0 | 21 | 0 | 0 | 0 | 10 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 9 | 0 | 0 | 0 | 0 | 0 | 2 | 42 | 6/15/10 | 14 | DSD ( Duct Smoke detector) : 2 failed First floor paint prep shop bay 45 and first floor paint prep shop bay 46 | |
| 2604 | DLE Shop | Edwards 5721-B | 1992 | 0 | 25 | 0 | 0 | 0 | 8 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 24 | 0 | 0 | 0 | 0 | 0 | 0 | 57 | 6/15/10 | 12 | Tested 8 DSD (Duct smoke detector) 1 failed: First floor South Bay 49. 1 PSSA ( Pull station-single action) not tested: First floor Northwest storage room | |
| 2605 | Weapons Pool | Edwards 5721-B | 1992 | 13 | 6 | 0 | 4 | 0 | 4 | 0 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 5 | 0 | 0 | 0 | 0 | 0 | 0 | 35 | 1/20/10 | 12 | The batteries in the fire alarm panel failed load testing and were replaced at this time. The four duct detectors (1st floor outside mechanical room) did not alarm when tested. They also did not put a trouble on the panel when the heads were removed. They do not seem to have any power to them. | |
| 2606 | DLE Motor Pool | Edwards 5721-B | 1992 | 5 | 5 | 0 | 0 | 0 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 16 | 1/20/10 | 8 | There was a panel trouble on the panel on arrival, but it does not send in on the Monaco and there is no zone trouble showing. Everything on the panel worked normally even with the trouble. One of the batteries in the panel failed load testing at 35%, so both batteries were changed at this time. | |
| 2609 | Telephone Switch Building | Monaco M-1 Notifier | 0 | 1 | 0 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 6 | 5/14/10 | 4 | There were no deficiencies noted. | ||
| 2620 | Navy Reserve Center | Edwards EST-2 | 0 | 0 | 11 | 0 | 0 | 8 | 0 | 3 | 0 | 0 | 24 | 36 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 82 | 4/26/10 | 10 | There were no deficiencies noted. | ||
| 2785 | Kennedy Hall | Gamewell IF650 | 2002 | 0.0 | 30 | 0 | 256 | 0 | 0 | 0 | 10 | 0 | 0 | 51 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 348 | 2/4/10 2/16/10 | 21 | One smoke detector in hall by room 532 is hanging down about 1" and needs to be fixed. Five sounder bases failed to sound when smoke detector was tested (rooms 232, 316, 404 bed and living rooms., 515). Pull station at exit by room 425 did not work when first tested. Only worked after exercising switch. | |
| 3058 | Maintenance Shop | Simplex 4001 | 1993 | 0 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 5 | 9 | 4/21/10 | 2 | There were no deficiencies noted. | |
| 3205 | Dormitory | Simplex 4001 | 1997 | This building is being renovated. We will not be doing an inspection this year per Rick. | |||||||||||||||||||||||||
| 3210 | Dining Facility | Monaco Vulcan 1 | 1989 | 2 | 5 | 0 | 0 | 0 | 11 | 0 | 0 | 0 | 0 | 7 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 25 | 6/4/10 | 8.0 | One DSD failed: Floor A South Attic. | |
| 3215 | Dormitory | Simplex 4100 | 1994 | 41 | 13 | 0 | 1 | 0 | 6 | 0 | 5 | 87 | 0 | 0 | 0 | 0 | 0 | 55 | 0 | 0 | 0 | 0 | 0 | 0 | 208 | 12/18/09 | 16 | Combined smoke/heat detector on 1st floor room 108 was not tested. Duct smoke detector 3rd floor AHU-3 west mechanical room was not tested. Horn on 1st floor on post by mechanical room 131, on post by room 106, on post by room 124 and on post by room 127 failed due to no alarm when tested. | |
| 3220 | Office Building | Notifier AFP-200 | 1992 | 0 | 5 | 0 | 11 | 0 | 0 | 0 | 0 | 0 | 0 | 9 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 25 | 3/23/10 | 4 | There were no deficiencies noted. | |
| 3225 | Dormitory | Edwards EST 2 | 2007 | 8 | 0 | 9 | 131 | 0 | 2 | 0 | 0 | 23 | 0 | 25 | 14 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 212 | 11/2/09 -11/4/09 | 20 | First floor northeast rear exit pull station double action failed to alarm when tested. This device was replaced and retested. Tested normal. Five rooms could not be accessed at this time - Room 114, 202, 239, 240 and Closet 312. Eight fixed tem heats in attic were visual checked. | |
| 3235 | Dormitory | Simplex 4001 | 1994 | 43 | 13 | 0 | 0 | 0 | 6 | 0 | 0 | 88 | 0 | 0 | 0 | 0 | 0 | 60 | 0 | 0 | 0 | 0 | 0 | 0 | 210 | 12/21/09 | 16 | The smoke detector in the elevator equipment room did alarm but it did not show on the fire alarm panel. Five horns failed to alarm at this time. Tow on tow. (Post at 203, 227). One on one. (Post at 117, 124, 127). Two duct detectors on AHU-1 failed to shut down air unit. One duct detector on the third floor could not be accessed. | |
| 3250 | HQ Building | Gamewell E3 Series | 0 | 5/18/10 | 4 | ||||||||||||||||||||||||
| 3255 | Office Building | Gamewell IF610 | 0 | 3 | 0 | 37 | 1 | 3 | 0 | 1 | 11 | 0 | 24 | 15 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 95 | 3/25/10 | 16 | All location descriptions in the panel are old (from when building was MEPS) and need to be updated for current occupants. | ||
| 3265 | Dormitory | Simplex 4100 | 1994 | 45 | 13 | 0 | 0 | 0 | 6 | 0 | 0 | 88 | 0 | 0 | 0 | 0 | 0 | 61 | 0 | 0 | 0 | 0 | 0 | 0 | 213 | 12/21/09 | 16 | Four horns failed to sound (2nd floor at room 224, 1st floor at rooms 104 and 120, and basement). One duct detector in first floor east did not shut down air unit. One duct detector on third floor could not be accessed at this time. | |
| 3270 | Classroom | Simplex 4100 | 1992 | 0 | 5 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 7 | 3/26/10 | 5 | There were no deficiencies noted. | |
| 3275 | Dormitory | Simplex 4100 | 1994 | 43 | 13 | 0 | 0 | 0 | 6 | 0 | 2 | 88 | 0 | 0 | 0 | 0 | 0 | 61 | 0 | 0 | 0 | 0 | 0 | 0 | 213 | 12/21/09 | 16 | Could not access room 125 and smoke/heat in room 124 failed to alarm. Three duct detectors failed to shut down the air unit (2 on 1st floor west and 1 on 1st floor east) and one duct detector was missing the smoke head from the detector (3rd floor west). | |
| 3276 | Dormitory | Simplex 4100 | 43 | 13 | 0 | 1 | 0 | 6 | 0 | 0 | 87 | 0 | 0 | 0 | 0 | 0 | 61 | 0 | 0 | 0 | 0 | 0 | 0 | 211 | 12/21/09 | 10 | There were no deficiencies noted. | ||
| 3280 | Classroom | Firelite Sensiscan | 1992 | 0 | 5 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 7 | 3/26/10 | 6 | The batteries in the fire alarm panel failed load testing and were replaced at this time. (2-12v/7.5 Ahr) | |
| 3285 | Dormitory | Simplex 4001 | 1987 | 0 | 6 | 0 | 0 | 0 | 2 | 0 | 1 | 80 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 9 | 98 | 11/3/09 | 16 | The batteries in the fire alarm panel failed load testing and were replaced at this time ( 2-12V/7.5Ahr batteries). First floor east and west mechanical rooms duct smoke detector are not wired into system. | |
| 3295 | Dormitory | Simplex 4001 | 1987 | 1 | 6 | 0 | 0 | 0 | 2 | 0 | 0 | 80 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 9 | 98 | 11/12/09 | 16 | The batteries in the fire alarm panel failed load testing and were replaced at this time (2 -7.5 Ahr). Rooms 106, 107 and 124 could not be accessed at this time. | |
| 3295 | Dormitory | Simplex 4002 | 1988 | 8/17/10 | 2 | ||||||||||||||||||||||||
| 3296 | Dormitory | Simplex 4002 | 1988 | 8/17/10 | 2 | ||||||||||||||||||||||||
| 3296 | Indoor Pool | FCI Series 72 | 1989 | 0 | 5 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 0 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 8 | 5/19/10 | 2 | Three pull stations failed to alarm (First floor front right pool area, First floor rear left pool area, First floor rear right pool area) and the heat detector was covered for construction and painting. One RRHD ( Rate of rise heat detector) was not tested: First floor rear pool equipment room. One A/V (Audio/Visual signal device) failed: First floor rear pool area. | |
| 3301 | Classroom | Edwards EST 2 | 0 | 0 | 4 | 8 | 0 | 0 | 0 | 3 | 0 | 0 | 7 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 25 | 3/26/10 | 8 | The labels on the classrooms are reversed from the labels on those device labels in the panel. | ||
| 3305 | Magruders Pub | Edwards 5712 | 1983 | 0 | 7 | 0 | 0 | 0 | 0 | 0 | 2 | 0 | 0 | 5 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 16 | 5/6/10 | 6 | The heat detector in the mechanical room at the fire panel failed to alarm when tested. | |
| 3330 | Victory Brigade HQ | Edwards | 1963 | 0 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 6 | 9 | 3/24/10 | 4 | The pull station on the first floor has a wall built around it where it can not be reset. Could not test at this time. The bell in the south basement clacker is moving but is not making contact with the bell. No batteries in the fire alarm panel. The battery in the Monaco panel is 1.5 years old and 85% load tested. | |
| 3390 | Data Processing Center | 10 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 16 | 4/27/10 | 5 | There are 2 pull stations, 17 smoke detectors, and 3 bells that were connected to an old Halon system in the old computer server room which ware removed from last years inspection. The remaining bells were changed to new audio/visual devices. The panel was changed out for a Simplex 4001 panel. A few of the fix temp heat were checked by shorting the wires and putting an alarm on the panel. | |||
| 3392 | MWR | Edwards | 63 | 7 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 73 | 5/4/10 | 2 | The front right wing that has been added onto the building does not have a signal and the horns in the building cannot be heard in this area. | ||
| MC3430 | USMC Reserve Center | Edwards EST-3 | 2008 | 7 | 0 | 10 | 5 | 2 | 4 | 0 | 0 | 0 | 1 | 0 | 12 | 0 | 1 | 0 | 0 | 0 | 0 | 36 | 0 | 0 | 78 | 6/2/10 | 12 | Changed batteries in the fire alarm panel. (2-12V/26Ahr) Changed the batteries in both NAC panels (4-12V/7.5Ahr) Changed the battery in the Monaco panel (1-12V/12Ahr). DSD (Duct smoke detector) 4 was not tested : First floor Assembly area, First floor Mechanical area, First floor new gear room, and First floor new gear room. SPPS (Power supply) 2 failed: First floor Outside mechanical room. | |
| MC3431 | USMC Reserve Center Vehicle Maintenance | Edwards EST-3 | 2009 | 0 | 0 | 3 | 2 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 10 | 0 | 0 | 17 | 6/1/10 | 4 | The batteries in the fire alarm panel were replaced at this time. (2-12V/26Ahr) | |
| 3499 | BH HQ | Simplex 4001 | 0 | 2 | 0 | 4 | 0 | 0 | 0 | 1 | 0 | 0 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 9 | 5/5/10 | 2 | There has been an exit door added to the rear of the building since the last inspection was done. There should be a fire alarm pull station added at this exit. | ||
| 3500 | Warehouse | Tied to 2493 Monaco Radio Panel | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 8/3/10 | This building has a Monaco radio panel which monitors a sprinkler system. The battery in the Monaco was dated 4/08 and tested at 90% | |||
| 3501 | Warehouse | Simplex 4002 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 8/16/10 | 1 | There were no deficiencies noted during this inspection. | |
| 3510 | Warehouse | Simplex 4001 | 0 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 3 | 8/16/10 | 1 | One PSSA ( pull station-single action) failed: First floor warehouse office exit. | |
| 3511 | Warehouse | Simplex 4001 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 8/3/10 | There were no deficiencies noted during this inspection. | |||
| 3521 | Warehouse | Simplex 2001 | 7 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 2 | 10 | 8/3/10 | There are two panels in this building. The 4001 in the front office monitors the sprinkler system and the 2001 in the center closet monitors the pull station and heat detectors. | |||
| 3630 | Officer's Club | Edwards 5721-B | 1986 | 5 | 6 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 6 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 17 | 5/6/10 | 4 | The five heat were visual inspected because they are fixed temp. heats but the wiring was tested normal by shorting at the device. The fire alarm panel is automatically silencing the signal circuit on an alarm which also keeps the panel from alerting the Monaco panel. The fire alarm panel needs to be replaced. | |
| 3652 | Golf Course Clubhouse | FCI 72 Series | 1993 | 0 | 7 | 0 | 0 | 0 | 5 | 0 | 0 | 0 | 0 | 7 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 19 | 4/26/10 | 6 | The batteries in the fire alarm and the Monaco panel tailed load testing and were replaced at this time. (3-12V/7.5Ahr). The A/V in the bar area failed to flash when alarmed. | |
| 3662 | Golf Course Hazmat | Monaco | Passed - Voltage w/charger, voltage w/o charger, battery % of charge, battery age check, zone trouble, signal trouble, type signal circuit, AC Input voltage, Lamps/LED Test, Drill Switch, Control Function(s) | 0 | No deficiencies noted. | ||||||||||||||||||||||||
| E3900 | Scorekeeper Tower | Edwards 5721B | 18 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 24 | 8/17/10 | 8 | There were no deficiencies noted during this inspection. | |
| 4110 | Main PX | Notifier AFP 400 | 0 | 0 | 14 | 2 | 0 | 29 | 0 | 0 | 0 | 0 | 37 | 29 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 111 | 5/3/10 | 16 | SPECIAL PROVISIONS: To shut off signals… Pull bell circuit 1 & 2 from top right of power supply board in bottom of panel. Then disable module 198 & 199 in programming. To get to programming... Hit enter. Put in code 11111, enter. Pick 1, enter. it # (module) and the number, enter. | ||
| 4120 | Gat @ Shoppette | Notifier System 500 | 1991 | 0 | 0 | 3 | 0 | 0 | 2 | 0 | 21 | 0 | 0 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 29 | 6/7/10 | 3.0 | There was a programming trouble. When any fire zone on the panel went into alarm it would activate zones 1-4 on the Monaco panel. | |
| 4149 | Penez Gym | Spurling | 0 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 3 | 6 | 4/30/10 | 1 | The pull station at the front entrance failed to alarm when tested. | ||
| 4159 | Videorama | Simplex 4001 | 0 | 0 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 6 | 3/29/10 | 3 | 1st floor outside at entrance did not alarm when tested. | ||
| 4169 | Shoppette | Spurling | 0 | 6 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 2 | 8 | 4/29/10 | 2 | There were no deficiencies noted. | ||
| 4200 | Orderly Room/Supply | Spurling | 1964 | 0 | 10 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 10 | 20 | 5/19/10 | 4 | One bell in the front of section failed to alarm: First floor section one front door | |
| 4203 | Classroom | Edwards EST 2 | 0 | 0 | 6 | 8 | 0 | 0 | 0 | 10 | 0 | 0 | 6 | 7 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 37 | 1/29/10 | 7 | There were no deficiencies noted. | ||
| 4204 | Classroom | Gamewell IF602S22 | 0 | 0 | 2 | 1 | 0 | 0 | 0 | 18 | 0 | 0 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 24 | 1/29/10 | 6 | The batteries in the fire alarm panel failed load testing and were replaced at this time. Four rate of rise heat detectors show up on the panel as being in the wrong room. All four have the right room number listed in the report. | ||
| 4205 | Dormitory | Simplex 4001 | 1988 | 1 | 6 | 0 | 0 | 0 | 2 | 0 | 0 | 80 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 9 | 98 | 11/5/09 | 16 | Third floor room 319 combined smoke/heat detector did not sound when smoked. The device was replaced and retested. Detector worked normal. Eight rooms could not be accessed at this time - Rooms 113, 122, 209, 236, 250, 309, 329, and 336. The duct detectors are not tied into the fire alarm system. | |
| 4210 | Dining Facility | Monaco Vulcan 1 | 1996 | 2 | 5 | 0 | 0 | 0 | 14 | 0 | 0 | 0 | 0 | 8 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 29 | 6/2/10 | 8 | Air Handler 7, Duct detector 1, No shut down. Air Handler 9, Duct detector 1 & 2, No shut down. Air handler8, duct detector 1&2, No alarm, head missing. Two duct detectors above ceiling in the dining area are bypassed at this time. DSD (Duct smoke detector) 3 failed: Floor A South Attic, Floor A south Attic, and floor A south attic. 2 was not tested: First floor North dinning by leaning ceiling and First floor South dining by leaning ceiling. | |
| 4215 | Dormitory | Simplex 4001 | 1988 | 1 | 6 | 0 | 0 | 0 | 2 | 0 | 0 | 80 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 9 | 98 | 11/6/09 | 16 | Two rooms could not be accessed at this time - Rooms 227 and 336. The two duct detectors are not wired into the fire alarm system. | |
| 4220 | Orderly Room/Supply | Spurling | 1965 | 0 | 10 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 10 | 20 | 5/19/10 | 4 | Could not access the fifth unit at this time. Two PSSA (Pull Station-Single Action) was not tested : Supply Building one E Co. Front Door and Supply Building one E Co. Rear Door. Two BELL was not tested: Supply Building one E Co. Front Door and Supply Building one E Co. Rear Door. | |
| 4225 | Dormitory | Simplex 4001 | 1988 | 1 | 6 | 0 | 0 | 0 | 2 | 0 | 0 | 80 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 9 | 98 | 11/9/09 | 16 | Rooms 120, 125, 132, 138, 140, 229 and 236 could not be accessed at this time. The duct detectors are not tied into the fire alarm system. | |
| 4230 | Classroom | Spurling | 1965 | 0 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 2 | 5 | 5/19/10 | 2.0 | There are four duct detectors in the attics (2 in north, 2 in south) which are not connected to the FACP. They were tested and three did shut down a damper. The forth is on collapsed duct work. | |
| 4235 | Dormitory | Simplex 4001 | 1966 | 0 | 6 | 0 | 0 | 0 | 2 | 0 | 0 | 76 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 9 | 93 | 11/10/09 | 16 | The duct detectors are not wired into the fire alarm system and access could not be gained at this time. Rooms 122 and 250 were locked and could not be accessed at this time. | |
| 4243 | Dormitory | FCI | 1993 | This building is being renovated. We will not be doing an inspection this year per Rick. | |||||||||||||||||||||||||
| 4250 | Payroll Support | Spurling | 1965 | 0 | 10 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 10 | 20 | 5/4/10 | 2 | Drill switch had no alarm when tested. First floor office 4 front and rear pull station and bell was not tested. First floor office 2 front bell had no alarm when tested. | |
| 4255 | Dormitory | 2009 | 0 | 14 | 0 | 25 | 6 | 2 | 0 | 3 | 0 | 0 | 0 | 119 | 0 | 1 | 0 | 0 | 0 | 0 | 47 | 0 | 0 | 0 | 217 | 8/11/10 | 8 | One SP/V (Speaker Visual) failed: Third floor Bay 2 west end. One VSIG (Visual only signal) failed: Second floor West latrine south side | |
| 4265 | Dormitory | 2009 | 0 | 14 | 0 | 25 | 6 | 2 | 0 | 3 | 0 | 0 | 0 | 119 | 0 | 1 | 0 | 0 | 0 | 0 | 47 | 0 | 0 | 0 | 217 | 8/11/10 | 8 | There were no deficiencies noted during this inspection. | |
| 4270 | Dining Facility | This building is being renovated. We will not be doing an inspection this year per Rick. | |||||||||||||||||||||||||||
| 4275 | Dormitory | 2009 | 0 | 14 | 0 | 25 | 6 | 2 | 0 | 3 | 0 | 0 | 0 | 119 | 0 | 1 | 0 | 0 | 0 | 0 | 47 | 0 | 0 | 0 | 0 | 8/12/10 | 8 | There were no deficiencies noted during this inspection. | |
| 4280 | Dining Facility | 0 | 8 | 0 | 7 | 0 | 4 | 0 | 1 | 0 | 0 | 0 | 22 | 0 | 0 | 0 | 0 | 0 | 0 | 8 | 0 | 0 | 0 | 0 | 8/13/10 | 8 | Two PSD ( Photo Smoke Detector) were not tested: First floor storage room 105 and First floor storage room 112B. | ||
| 4282 | Telecommunication Switch | Simplex 2001 | 1988 | 0 | 7 | 0 | 9 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 3 | 21 | 5/14/10 | 8 | Any alarm on the three panels will shut off power and put the building on emergency power. Check that the tech has disabled all three panels before checking any panel. | |
| 4285 | Dormitory | 2009 | 0 | 14 | 0 | 25 | 6 | 2 | 0 | 3 | 0 | 0 | 0 | 119 | 0 | 1 | 0 | 0 | 0 | 0 | 47 | 0 | 0 | 0 | 217 | 8/12/10 | 8 | One ANNC (Annunciator) was not tested: First floor main entrance. Six SPPS (power supply) was not tested: (2) First floor outside rear electrical room, (2) second floor west electrical room, (2) third floor west electrical room. | |
| 4290 | Orderly Room/Supply | Spurling | 1964 | 0 | 10 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 10 | 20 | 6/3/10 | 6 | There were no deficiencies noted. | |
| 4295 | Dormitory | 2009 | 0 | 14 | 0 | 25 | 6 | 2 | 0 | 3 | 0 | 0 | 0 | 119 | 0 | 1 | 0 | 0 | 0 | 0 | 47 | 0 | 0 | 0 | 217 | 8/13/10 | 8 | There were no deficiencies noted. | |
| 4310 | 5th Brig HQ | Spurling | 1964 | 0 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 3 | 6 | 5/4/10 | 1 | The bell in the front office is getting the alarm but the bell is not ringing. | |
| 4323 | Unknown | Simplex | 1965 | This building is being renovated. We will not be doing an inspection this year per Rick. | |||||||||||||||||||||||||
| 4325 | Post Headquarters | Firelite Scan 424 | 1987 | 0 | 0 | 13 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 3 | 16 | 6/8/10 | 5 | There was a trouble on the panel on arrival and still there after complete, but it did not cause any problem to testing. | |
| 4330 | BN HQ | Spurling | 1964 | 0 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 3 | 6 | 4/28/10 | 2 | There were no deficiencies noted. | |
| 4334 | Hazmat | Monaco M-1 | 1992 | Passed - Voltage w/charger, voltage w/o charger, battery % of charge, battery age check, zone trouble, signal trouble, type signal circuit, AC Input voltage, Lamps/LED Test, Drill Switch, Control Function(s) | 0 | 4/13/10 | 2 | No deficiencies noted. | |||||||||||||||||||||
| 4338 | EP2 | Auto Call AC | 1978 | 0 | 1 | 0 | 7 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 9 | 3/9/10 | 4 | There were no deficiencies noted. | |
| 4340 | DOC | Simplex 4001 | 0 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 6 | 0 | 0 | 0 | 0 | 0 | 0 | 9 | 5/12/10 | 3 | There were no deficiencies noted. | ||
| 4350 | Travel Office | Spurling | 1965 | 0 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 4 | 8 | 5/12/10 | 3 | There were no deficiencies noted. | |
| 4354 | 1 | 2 | 0 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 7 | 7/8/10 | 8 | There were no deficiencies noted. | ||||
| 4380 | BN HQ | Spurling | 1964 | 0 | 8 | 0 | 1 | 0 | 2 | 0 | 5 | 0 | 0 | 0 | 31 | 0 | 0 | 0 | 0 | 0 | 0 | 16 | 0 | 0 | 0 | 63 | 8/16/10 | 8 | There were no deficiencies noted. |
| 4392 | AG Museum | Monaco M-1 | 1994 | 0 | 5 | 0 | 25 | 0 | 4 | 0 | 1 | 0 | 0 | 6 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 43 | 5/11/10 | 6 | There were no deficiencies noted. | |
| 4394 | PAO/Welcome Center | Edwards | 1964 | 0 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 5 | 4/30/10 | 2 | The fire alarm panel was changed to a Simplex 4001 panel. | |
| 4400 | Post Office | Monaco C-100A-12 | 1 | 5 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 3 | 9 | 2/16/10 | 2 | There were no deficiencies noted. | ||
| 4408 | Museum Annes | Gamewell IF610 | 0 | 1 | 0 | 29 | 0 | 0 | 0 | 2 | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 34 | 5/6/10 | 6 | The batteries in the fire alarm panel failed load testing and were replaced at this time (2-12V/7.5Ahr) | ||
| 4416 | Dozier House | Simplex 2001 | 5 | 0 | 0 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 9 | 2/3/10 | 4 | There were no deficiencies noted. | ||
| 4420 | Starship Soldier Barracks | Gamewell IF650 | 0 | 63 | 0 | 140 | 6 | 19 | 288 | 0 | 0 | 0 | 104 | 52 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 673 | 2/8/10 - 2/12/10 | 40 | Annunciator in main lobby failed. Twenty heat detectors failed: 1st floor kitchen, serving area, four in laundry room utility closet, two in mechanical room, three in laundry room, 2nd floor three in mechanical room, two in electrical/storage, four in sleeping bay latrine utility closet, 3rd floor electrical/storage. Pull station 1st floor serving area 1 exit to breezeway failed. Power supply 2nd floor electrical/storage failed load test. | ||
| 4420 | Starship Soldier Barracks | Gamewell IF650 | 0 | 63 | 0 | 141 | 6 | 19 | 288 | 0 | 0 | 0 | 104 | 52 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 674 | 4/12/10 | 16 | One heat detector failed testing and was replaced and re-tested at this time (10-53). Now testing normal. One heat detector and one smoke detector could not be accessed at this time (RRHD 1-80, PSD 2-37) | ||
| 4442 | Post Museum | Gamewell IF610 | 0 | ||||||||||||||||||||||||||
| 4464 | Century Lanes | Simplex 2001 | 1979 | 2 | 7 | 0 | 9 | 0 | 0 | 0 | 10 | 0 | 0 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 32 | 4/28/10 | 14 | The two smoke detectors over the snack bar failed to alarm. The A/V by the west exit failed to flash when alarmed. The Simplex Tech (Alex) replaced the two smoke detectors over the snack bar and the bad A/V device. | |
| 4470 | Chapel | FCI | 0 | 2 | 0 | 6 | 0 | 0 | 0 | 1 | 0 | 0 | 1 | 0 | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 2 | 13 | 6/11/10 | 4 | Replaced the battery in the Monaco panel at this time. | ||
| 4482 | Coleman Gym | Simplex 4238 | 1974 | 0 | 6 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 5 | 11 | 5/4/10 | 2 | There were no deficiencies noted. | |
| 4510 | Warehouse | 0 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 2 | 6 | 8/5/10 | There were no deficiencies noted. | ||||
| 4580 | Post Chapel | ADT Unimode | 1985 | 1 | 0 | 9 | 45 | 0 | 0 | 0 | 0 | 0 | 0 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 59 | 5/21/10 | 16 | There are four devices which are too high up to be tested: Floor two Nave Center, Floor two Nave Front, Floor two Nave Rear and floor two Office Lobby. A lift would be needed to test these. | |
| 4581 | Scales CDC | Edwards EST-2 | 1985 | 0 | 0 | 25 | 83 | 0 | 0 | 0 | 2 | 0 | 0 | 18 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 130 | 5/7/10 | 16 | There were no deficiencies noted. | |
| 4585 | Hood Street CDC | Simplex 4001 | 1986 | 0 | 8 | 0 | 25 | 0 | 3 | 0 | 3 | 0 | 0 | 3 | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 43 | 2/23/10 | 8 | Duct smoke detectors in room 116 and room 123 were not tested. | |
| 4600 | Education Center | Simplex 2001 | 1985 | 1 | 11 | 0 | 48 | 0 | 0 | 0 | 0 | 0 | 0 | 3 | 0 | 0 | 0 | 0 | 0 | 1 | 1 | 0 | 0 | 10 | 75 | 5/20/10 | 10 | Monaco radio panel for this building is located in building 4679, and tested normal. The batteries are only one year old, but are reading borderline at 80%. Eight smoke detectors failed to alarm when tested: First floor hall by B 109, First floor room B 104,First floor room B 110, Second floor room B 200, Second floor room B 203, Second floor room B 205, Second floor room B 208 and second floor room B 208. | |
| 4679 | Post Library | Simplex 4208 | 1968 | 0 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 5 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 8 | 5/20/10 | 2 | No deficiencies noted. | |
| 4710 | Credit Union | Ademco Automatic | 1987 | 16 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 17 | 6/7/10 | 2 | No deficiencies noted. |
| 4712 | PX Mini Mall | Simplex 4010 | 1972 | 0 | 20 | 0 | 5 | 0 | 8 | 0 | 12 | 0 | 0 | 30 | 4 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 80 | 4/29/10 | 8 | There is a new pull station added in the new Tactical Shop which did alarm in the fire panel but it did not alarm on the Monaco panel. An alarm from this pull station would not automatically be transmitted to the fire department. | |
| 4716 | Commissary | ADT (Firelite) Unimode 200 | 1985 | 17 | 0 | 15 | 5 | 0 | 6 | 0 | 0 | 0 | 0 | 17 | 6 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 66 | 5/1010 | 16 | The batteries in the fire alarm panel, and in the two NAC panels, failed load testing and were replaced at this time (6-12V/7.5Ajhr batteries.) | |
| 5385 | 1st Brig HD | Simplex 4208 | 1978 | 0 | 8 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 3 | 11 | 3/9/10 | 4 | The battery in the Monaco panel failed load testing and was replaced at this time (1 - 12V/7.5Ahr) | |
| F5400 | Map Reading Class | Simplex 4001 | 26 | 8 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 38 | 6/10/10 | 3 | NO deficiencies noted. | ||
| 5421 | Dormitory | Tied to 5426 | 5 | 0 | 4 | 0 | 0 | 0 | 0 | 0 | 6 | 0 | 2 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 21 | 1/10/10 | See Bldg 5426 | NO deficiencies noted. | ||
| 5422 | Dormitory Starship | Cerberus MXL | 0 | 65 | 0 | 0 | 5 | 18 | 136 | 0 | 296 | 0 | 102 | 56 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 678 | 3/1/10 - 3/5/10 | 80 | Batteries in POD 4 NAC panel failed load testing and were replaced at this time (2 - 12V/7.5A hr). Could not access the NAC panel in POD 5. door is painted shut. There was a total of 3 combined smoke/heat detectors, 21 heat detectors, 1 visual only signal only and 1 power supply that was not tested. Combined Smoke/Heat detectors in rooms 303, 307 and 309 had no alarm when tested. Heat detector 2nd floor pod 2B side latrine supply had no alarm when tested. Power supply pod 4B side electrical room failed load test. Visual Only Signal 2nd floor pod 4A side latrine, 2nd floor pod 5A side latrine, 2nd floor pod 5B side latrine and room 307 had no alarm when tested. | ||
| 5423 | Dormitory | Tied to 5426 | 5 | 0 | 4 | 0 | 0 | 0 | 0 | 0 | 12 | 0 | 2 | 8 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 31 | 1/10/10 | See Bldg 5426 | Fixed temp heat detector 1st floor drill sgt office/west storage and 1st floor eat storage was not tested. Pull station double action 1st floor east bay south had no alarm when tested. | ||
| 5424 | Dormitory | Tied to 5427 | 0 | 0 | 4 | 7 | 0 | 0 | 0 | 5 | 0 | 0 | 2 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 22 | 1/10/10 | See Bldg 5427 | Rate of rise heat detector on 1st floor supply room TA-50 was not tested. | ||
| 5425 | Dormitory | Tied to 5427 | 0 | 0 | 4 | 7 | 0 | 0 | 0 | 5 | 0 | 0 | 2 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 22 | 1/10/10 | See Bldg 5427 | Rate of rise heat detector on 1st floor supply room TA-50 was not tested. | ||
| 5426 | Orderly Room | Edwards EST 2 | 9 | 0 | 7 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 5 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 21 | 1/10/10 | 8 | Pull station double action 1st floor southeast storage was not tested. Fixed temp heat detector 1st floor southeast storage was not tested. The batteries in the fire alarm panel failed load testing and were replaced at this time. | ||
| 5427 | Orderly Room | Edwards EST 2 | 0 | 0 | 8 | 0 | 0 | 0 | 0 | 9 | 0 | 0 | 3 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 22 | 1/10/10 | 8 | Rate of rise heat detector on 1st floor supply room B side front and rear was not tested. Two pull station double action 1st floor supply room B front side and one pull station double action 1st floor supply room B side rear was not tested. Audio/Visual 1st floor supply room B side front was not tested. | ||
| 5432 | CO HQ | Simplex 4208 | 0 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 2 | 4 | 3/29/10 | 3 | There were no deficiencies noted. | ||
| 5450 | Strom Thurmond Bldg | GE EST 2 | 2007 | 0 | 0 | 15 | 8 | 0 | 8 | 0 | 0 | 0 | 0 | 38 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 69 | 5/5/10 | 9 | The batteries failed load testing and were replaced at this time (FACP 2-12V/12Ahr, NAC 2-12V/7.5Ahr, Monaco 1-12V/7.5Ahr). The pull station in pod 4, room 118 failed to alarm when tested. It put an open line trouble on the panel. This pull needs to be replaced with a new pull station which is addressable. The smoke detectors in the main data room and electrical room will open the pre-action system for this room. | |
| 5453 | Dormitory | Tied to 5426 | 5 | 0 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 11 | 1/10/10 | See Bldg 5426 | No deviancies noted. | ||
| 5472 | Dormitory | Tied to 5426 | 5 | 0 | 2 | 0 | 0 | 0 | 0 | 0 | 12 | 0 | 1 | 7 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 27 | 1/10/10 | See Bldg 5426 | NO deficiencies noted. | ||
| 5473 | Dormitory | Tied to 5427 | 0 | 0 | 2 | 13 | 0 | 0 | 0 | 4 | 0 | 0 | 2 | 5 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 26 | 1/10/10 | See Bldg 5427 | Two rate of rise heat detector 1st floor supply room was not tested. |