W91236-10-R-0007-0002.pdf

PDF 5 MB Posted

Attached to
SCOE EOD FIELD TRAINING FACILITY, AP HILL, VA Federal contract opportunity
Solicitation number
W91236-10-R-0007
Issued by
Department of the Army Corps of Engineers Engineering District Norfolk

About this file

W91236-10-R-0007 Amendment 0002

View the file

Other files for this federal contract opportunity

Other files attached to SCOE EOD FIELD TRAINING FACILITY, AP HILL, VA, newest first.
File Type Posted
W91236-10-R-0007-0003.pdf PDF
W91236-10-R-0007-0001.pdf PDF
EOD_RTA_Drawings_4Dec part 2-1.pdf PDF
EOD_RTA_Drawings_4Dec part 2-2.pdf PDF
EOD_RTA_Drawings_4Dec part 3-1.pdf PDF
EOD_RTA_Drawings_4Dec part 1-1.pdf PDF
EOD_RTA_Drawings_4Dec part 1-2.pdf PDF
EOD_RTA_Drawings_4Dec part 3-2.pdf PDF
W91236-10-R-0007 SOLN.pdf PDF
EOD_RTA_Specs_Vol2of2_4Dec.pdf PDF
EOD_RTA_Specs_Vol1of2_4Dec.pdf PDF
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

W26GLG00067262

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print)

30-105-04EXCEPTION TO SF 30

APPROVED BY OIRM 11-84

STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA

FAR (48 CFR) 53.243

Amendment 0002 is hereby issued to add the attached documents as reference material.

Amendment Point of Contact: Sabrina Tippins, sabrina.a.tippins@usace.army.mil

1. CONTRACT ID CODE PAGE OF PAGES

J 1 56

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

16C. DATE SIGNED

BY 02-Feb-2010

16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR

(Signature of Contracting Officer)(Signature of person authorized to sign)

8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W91236-10-R-0007

X 9B. DATED (SEE ITEM 11)

06-Jan-2010

10B. DATED (SEE ITEM 13)

9A. AMENDMENT OF SOLICITATION NO.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.

Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:

(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN

REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

10A. MOD. OF CONTRACT/ORDER NO.

2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)

6. ISSUED BY

3. EFFECTIVE DATE

02-Feb-2010

CODE

USA ENGINEER DISTRICT, NORFOLK

CONTRACTING OFFICE

803 FRONT STREET

NORFOLK VA 23510-1096

W91236 7. ADMINISTERED BY (If other than item 6)

4. REQUISITION/PURCHASE REQ. NO.

CODE

See Item 6

FACILITY CODECODE

EMAIL:TEL:

W91236-10-R-0007

AMENDMENT 0002

ct ld take into consideration s motorist, pedestrians, or bicy-h et the visitor to th o and c with the natural surroundings. These signs are de-signe ing g Numbers: Helvetica regular.

Helvetica Medium, case.

• ite anel backs and edges: Dark

Legibility. Sign typestyle, line spacing, color, and size all combine to create the crucial de-sign characteristics of legibility. This aspe of sign design shou users such a clists, and the relative travel speed at whic each type of user will be traveling when viewing the signs.

Types of Signs.

Information / Identification Signs. These are signs that identify entrances to the installation, ar-eas within the installation, major tenants, build-ings, and organizational or functional components.

They identify a location, and gre

Figure

Building Identification.

identify buildings eith -ing nu

St proce-at l cation. They should be compatible in scale haracter with the architecture and also blend d to include the following:

Typeface: Lettering is self-adhesive back material.

• Building Title: Helvetica Medium, Upper and lower case.

• Buildin

• Building Addresses:

Upper and lower

Color:

• Panel: Dark Brown

Lettering: Wh

• Post: Dark Brown

• Exposed p Brown

• All paint: Semi-gloss

Materials:

• Panel: Double-face 1/8” thick aluminum

• Post: Pre-treated square wood posts

• Foundation: Concrete pier or direct burial

11-20.Typical identification sign at Fort A.P. Hill.

These are signs that er by street address or build mber.

reet Addresses. The addressing dures prescribed in DoD 4525.8-M, DoD Of-ficial Mail Manual are mandatory for use by l DoD components. DoD 4525.8-M, Chap-scribes the follo al ter 3 pre wing:

y ssigned and DoD activity may de-

• -style stallation and then

" to designate the delivery

• erts t.

• and address

• All DoD address shall be assigned so the are compatible with the United States Postal Services automated delivery point sequencing.

• The DoD installation is responsible for as-signing city-style, street address on the installation.

• Street addresses shall be a used even though a liver the mail to the addressee.

Only geographically locatable civilian street address (such as 4102 Cindy Ave-nue) shall be used.

Installations shall not use one street ad-dress for the entire in use secondary unit designators such as "Building 123 addresses on the installation.

Addresses such as "Building 123 Rob Street" are not a valid address format and shall not be used.

Address Placemen

• Place addresses by the front entrance of the building so they can be seen.

Place both the street name number on the building if both the building number and street address are visible from the street.

Fort A.P. Hill Installation Design Guide 11- 9

W91236-10-R-0007

AMENDMENT 0002

http://www.dtic.mil/whs/directives/corres/html/45258m.htm

SCOE EOD Field Training Area 67973

SECTION 08 14 00

WOOD DOORS

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.

ASTM INTERNATIONAL (ASTM)

ASTM E 2074 (2000e1) Standard Test Method for Fire Tests of Door Assemblies, Including Positive Pressure Testing of Side-Hinged and Pivoted Swinging Door Assemblies

ASTM E 90 (2009) Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 252 (2007) Standard Methods of Fire Tests of Door Assemblies

NFPA 80 (2010) Standard for Fire Doors and Other Opening Protectives

UNDERWRITERS LABORATORIES (UL)

UL 10B (2008; Rev thru Apr 2009) Fire Tests of Door Assemblies

WINDOW AND DOOR MANUFACTURERS ASSOCIATION (WDMA)

WDMA I.S. 1-A (1997) Architectural Wood Flush Doors

WDMA I.S. 4 (2000) Water-Repellent Preservative Non-Pressure Treatment for Millwork

WDMA TM-5 (1990) Split Resistance Test Method

WDMA TM-7 (1990) Cycle Slam Test Method

WDMA TM-8 (1990) Hinge Loading Test Method

1.2 SUBMITTALS

Submit the following in accordance with Section 01 33 00 .00 50 SUBMITTAL

PROCEDURES.

SD-02 Shop Drawings

SECTION 08 14 00 Page 1

W91236-10-R-0007

Doors ; G

Submit drawings or catalog data showing each type of door unit .

Drawings and data shall indicate door type and construction, sizes, thickness, methods of assembly, door louvers, and glazing,.

SD-03 Product Data

Doors ; G

Accessories

Sample warranty

Sound transmission class rating ; G

Fire resistance rating ; G

SD-04 Samples

Doors

Prior to the delivery of wood doors, submit a sample section of each type of door which shows the stile, rail, veneer, finish, and core construction.

Door finish colors ; G

Submit a minimum of three color selection samples for selection by the Contracting Officer.

SD-06 Test Reports

Split resistance

Cycle-slam

Hinge loading resistance

Submit split resistance test report for doors tested in accordance with WDMA TM-5, cycle-slam test report for doors tested in accordance with WDMA TM-7, and hinge loading resistance test report for doors tested in accordance with WDMA TM-8.

1.3 DELIVERY, STORAGE, AND HANDLING

Deliver doors to the site in an undamaged condition and protect against damage and dampness. Stack doors flat under cover. Support on blocking, a minimum of 4 inch thick, located at each end and at the midpoint of the door. Store doors in a well-ventilated building so that they will not be exposed to excessive moisture, heat, dryness, direct sunlight, or extreme changes of temperature and humidity. Do not store in a building under construction until concrete, masonry work, and plaster are dry. Replace defective or damaged doors with new ones.

1.4 WARRANTY

Warrant doors free of defects as set forth in the door manufacturer's standard door warranty.

SECTION 08 14 00 Page 2

W91236-10-R-0007

PART 2 PRODUCTS

2.1 DOORS

Provide doors of the types, sizes, and designs indicated.

2.1.1 Flush Doors

Conform to WDMA I.S. 1-A for flush doors. Provide doors with lock blocks and 1 inch minimum thickness hinge stile. Hardwood stile edge bands of doors receives a natural finish, compatible with face veneer. Provide mill option for stile edge of doors scheduled to be painted. No visible finger joints will be accepted in stile edge bands. When used, locate finger-joints under hardware.

2.1.1.1 Interior Flush Doors

Provide particleboard core, Type II flush doors conforming to WDMA I.S. 1-A with faces of sound grade hardwood or hardboard for painted finish .

2.1.2 Acoustical Doors

WDMA I.S. 1-A , solid core, constructed to provide Sound Transmission Class rating of 35 when tested in accordance with ASTM E 90 .

2.1.3 Composite-Type Fire Doors

Provide doors specified or indicated to have a fire resistance rating conforming to the requirements of UL 10B , ASTM E 2074 , or NFPA 252 for the class of door indicated. Affix a permanent metal label with raised or incised markings indicating testing agency's name and approved hourly fire rating to hinge edge of each door.

2.2 ACCESSORIES

2.2.1 Door Louvers

Fabricate from wood and of sizes indicated. Provide louvers with a minimum of 35 percent free air. Equip louvers with sightproof inverted vee slat type. Mount louvers in the door with flush wood moldings.

2.2.2 Door Light Openings

Provide glazed openings with the manufacturer's standard wood moldings.

Lip type moldings for flush doors.

2.2.3 Additional Hardware Reinforcement

Provide the minimum lock blocks to secure the specified hardware. The measurement of top, bottom, and intermediate rail blocks are a minimum 125 mm 5 inch by full core width. Comply with the manufacturer's labeling requirements for reinforcement blocking, but not mineral material similar to the core.

SECTION 08 14 00 Page 3

W91236-10-R-0007

2.3 FABRICATION

2.3.1 Marking

Stamp each door with a brand, stamp, or other identifying mark indicating quality and construction of the door.

2.3.2 Quality and Construction

Identify the standard on which the construction of the door was based , identify the standard under which preservative treatment was made, and identify doors having a Type I glue bond.

2.3.3 Preservative Treatment

Treat doors scheduled for restrooms, janitor closets and other possible wet locations including exterior doors with a water-repellent preservative treatment and so marketed at the manufacturer's plant in accordance with

WDMA I.S. 4 .

2.3.4 Adhesives and Bonds

WDMA I.S. 1-A . Use Type I bond for exterior doors and Type II bond for interior doors. Provide a nonstaining adhesive on doors with a natural finish.

2.3.5 Prefitting

Provide factory prefinished and factory prefitted doors for the specified hardware, door frame and door-swing indicated. Machine and size doors at the factory by the door manufacturer in accordance with the standards under which the doors are produced and manufactured. The work includes sizing, bevelling edges, mortising, and drilling for hardware and providing necessary beaded openings for glass and louvers. Provide the door manufacturer with the necessary hardware samples, and frame and hardware schedules to coordinate the work.

2.3.6 Finishes

2.3.6.1 Field Painting

Factory prime or seal doors, and field paint.

2.3.6.2 Color

Provide door finish colors as indicated .

2.4 SOURCE QUALITY CONTROL

Meet or exceed the following minimum performance criteria of stiles of "B" and "C" label fire doors utilizing standard mortise leaf hinges:

a. Split resistance : Averages of ten test samples not less than 500 pounds load when tested in accordance with WDMA TM-5.

b. Cycle-slam : 200,000 cycles with no loose hinge screws or other visible signs of failure when tested in accordance with the requirements of WDMA TM-7.

SECTION 08 14 00 Page 4

W91236-10-R-0007

c. Hinge loading resistance : Averages of ten test samples not less than 700 pounds load when tested for direct screw withdrawal in accordance with WDMA TM-8 using a No. 12, 1-1/4 inch long, steel, fully threaded wood screw. Drill 5/32 inch pilot hole, use 1-1/2 inch opening around screw for bearing surface, and engage screw full, except for last 1/8 inch . Do not use a steel plate to reinforce screw area.

PART 3 EXECUTION

3.1 INSTALLATION

Before installation, seal top and bottom edges of doors with the approved water-resistant sealer. Seal cuts made on the job immediately after cutting using approved water-resistant sealer. Fit, trim, and hang doors with a 1/16 inch minimum, 1/8 inch maximum clearance at sides and top, and a 3/16 inch minimum, 1/4 inch maximum clearance over thresholds. Provide 3/8 inch minimum, 7/16 inch maximum clearance at bottom where no threshold occurs. Bevel edges of doors at the rate of 1/8 inch in 2 inch . Door warp shall not exceed 1/4 inch when measured in accordance with WDMA I.S. 1-A .

3.1.1 Fire Doors

Install fire doors in accordance with NFPA 80 . Do not paint over labels.

-- End of Section --

SECTION 08 14 00 Page 5

W91236-10-R-0007