W91236-10-R-0007-0002.pdf
PDF 5 MB Posted
- Attached to
- SCOE EOD FIELD TRAINING FACILITY, AP HILL, VA Federal contract opportunity
- Solicitation number
- W91236-10-R-0007
About this file
W91236-10-R-0007 Amendment 0002
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| W91236-10-R-0007-0003.pdf | ||
| W91236-10-R-0007-0001.pdf | ||
| EOD_RTA_Drawings_4Dec part 2-1.pdf | ||
| EOD_RTA_Drawings_4Dec part 2-2.pdf | ||
| EOD_RTA_Drawings_4Dec part 3-1.pdf | ||
| EOD_RTA_Drawings_4Dec part 1-1.pdf | ||
| EOD_RTA_Drawings_4Dec part 1-2.pdf | ||
| EOD_RTA_Drawings_4Dec part 3-2.pdf | ||
| W91236-10-R-0007 SOLN.pdf | ||
| EOD_RTA_Specs_Vol2of2_4Dec.pdf | ||
| EOD_RTA_Specs_Vol1of2_4Dec.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W26GLG00067262
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
Amendment 0002 is hereby issued to add the attached documents as reference material.
Amendment Point of Contact: Sabrina Tippins, sabrina.a.tippins@usace.army.mil
1. CONTRACT ID CODE PAGE OF PAGES
J 1 56
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 02-Feb-2010
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W91236-10-R-0007
X 9B. DATED (SEE ITEM 11)
06-Jan-2010
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
02-Feb-2010
CODE
USA ENGINEER DISTRICT, NORFOLK
CONTRACTING OFFICE
803 FRONT STREET
NORFOLK VA 23510-1096
W91236 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
W91236-10-R-0007
AMENDMENT 0002
ct ld take into consideration s motorist, pedestrians, or bicy-h et the visitor to th o and c with the natural surroundings. These signs are de-signe ing g Numbers: Helvetica regular.
Helvetica Medium, case.
• ite anel backs and edges: Dark
Legibility. Sign typestyle, line spacing, color, and size all combine to create the crucial de-sign characteristics of legibility. This aspe of sign design shou users such a clists, and the relative travel speed at whic each type of user will be traveling when viewing the signs.
Types of Signs.
Information / Identification Signs. These are signs that identify entrances to the installation, ar-eas within the installation, major tenants, build-ings, and organizational or functional components.
They identify a location, and gre
Figure
Building Identification.
identify buildings eith -ing nu
St proce-at l cation. They should be compatible in scale haracter with the architecture and also blend d to include the following:
Typeface: Lettering is self-adhesive back material.
• Building Title: Helvetica Medium, Upper and lower case.
• Buildin
• Building Addresses:
Upper and lower
Color:
• Panel: Dark Brown
Lettering: Wh
• Post: Dark Brown
• Exposed p Brown
• All paint: Semi-gloss
Materials:
• Panel: Double-face 1/8” thick aluminum
• Post: Pre-treated square wood posts
• Foundation: Concrete pier or direct burial
11-20.Typical identification sign at Fort A.P. Hill.
These are signs that er by street address or build mber.
reet Addresses. The addressing dures prescribed in DoD 4525.8-M, DoD Of-ficial Mail Manual are mandatory for use by l DoD components. DoD 4525.8-M, Chap-scribes the follo al ter 3 pre wing:
y ssigned and DoD activity may de-
• -style stallation and then
" to designate the delivery
• erts t.
• and address
• All DoD address shall be assigned so the are compatible with the United States Postal Services automated delivery point sequencing.
• The DoD installation is responsible for as-signing city-style, street address on the installation.
• Street addresses shall be a used even though a liver the mail to the addressee.
Only geographically locatable civilian street address (such as 4102 Cindy Ave-nue) shall be used.
Installations shall not use one street ad-dress for the entire in use secondary unit designators such as "Building 123 addresses on the installation.
Addresses such as "Building 123 Rob Street" are not a valid address format and shall not be used.
Address Placemen
• Place addresses by the front entrance of the building so they can be seen.
Place both the street name number on the building if both the building number and street address are visible from the street.
Fort A.P. Hill Installation Design Guide 11- 9
W91236-10-R-0007
AMENDMENT 0002
http://www.dtic.mil/whs/directives/corres/html/45258m.htm
SCOE EOD Field Training Area 67973
SECTION 08 14 00
WOOD DOORS
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM E 2074 (2000e1) Standard Test Method for Fire Tests of Door Assemblies, Including Positive Pressure Testing of Side-Hinged and Pivoted Swinging Door Assemblies
ASTM E 90 (2009) Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 252 (2007) Standard Methods of Fire Tests of Door Assemblies
NFPA 80 (2010) Standard for Fire Doors and Other Opening Protectives
UNDERWRITERS LABORATORIES (UL)
UL 10B (2008; Rev thru Apr 2009) Fire Tests of Door Assemblies
WINDOW AND DOOR MANUFACTURERS ASSOCIATION (WDMA)
WDMA I.S. 1-A (1997) Architectural Wood Flush Doors
WDMA I.S. 4 (2000) Water-Repellent Preservative Non-Pressure Treatment for Millwork
WDMA TM-5 (1990) Split Resistance Test Method
WDMA TM-7 (1990) Cycle Slam Test Method
WDMA TM-8 (1990) Hinge Loading Test Method
1.2 SUBMITTALS
Submit the following in accordance with Section 01 33 00 .00 50 SUBMITTAL
PROCEDURES.
SD-02 Shop Drawings
SECTION 08 14 00 Page 1
W91236-10-R-0007
Doors ; G
Submit drawings or catalog data showing each type of door unit .
Drawings and data shall indicate door type and construction, sizes, thickness, methods of assembly, door louvers, and glazing,.
SD-03 Product Data
Doors ; G
Accessories
Sample warranty
Sound transmission class rating ; G
Fire resistance rating ; G
SD-04 Samples
Doors
Prior to the delivery of wood doors, submit a sample section of each type of door which shows the stile, rail, veneer, finish, and core construction.
Door finish colors ; G
Submit a minimum of three color selection samples for selection by the Contracting Officer.
SD-06 Test Reports
Split resistance
Cycle-slam
Hinge loading resistance
Submit split resistance test report for doors tested in accordance with WDMA TM-5, cycle-slam test report for doors tested in accordance with WDMA TM-7, and hinge loading resistance test report for doors tested in accordance with WDMA TM-8.
1.3 DELIVERY, STORAGE, AND HANDLING
Deliver doors to the site in an undamaged condition and protect against damage and dampness. Stack doors flat under cover. Support on blocking, a minimum of 4 inch thick, located at each end and at the midpoint of the door. Store doors in a well-ventilated building so that they will not be exposed to excessive moisture, heat, dryness, direct sunlight, or extreme changes of temperature and humidity. Do not store in a building under construction until concrete, masonry work, and plaster are dry. Replace defective or damaged doors with new ones.
1.4 WARRANTY
Warrant doors free of defects as set forth in the door manufacturer's standard door warranty.
SECTION 08 14 00 Page 2
W91236-10-R-0007
PART 2 PRODUCTS
2.1 DOORS
Provide doors of the types, sizes, and designs indicated.
2.1.1 Flush Doors
Conform to WDMA I.S. 1-A for flush doors. Provide doors with lock blocks and 1 inch minimum thickness hinge stile. Hardwood stile edge bands of doors receives a natural finish, compatible with face veneer. Provide mill option for stile edge of doors scheduled to be painted. No visible finger joints will be accepted in stile edge bands. When used, locate finger-joints under hardware.
2.1.1.1 Interior Flush Doors
Provide particleboard core, Type II flush doors conforming to WDMA I.S. 1-A with faces of sound grade hardwood or hardboard for painted finish .
2.1.2 Acoustical Doors
WDMA I.S. 1-A , solid core, constructed to provide Sound Transmission Class rating of 35 when tested in accordance with ASTM E 90 .
2.1.3 Composite-Type Fire Doors
Provide doors specified or indicated to have a fire resistance rating conforming to the requirements of UL 10B , ASTM E 2074 , or NFPA 252 for the class of door indicated. Affix a permanent metal label with raised or incised markings indicating testing agency's name and approved hourly fire rating to hinge edge of each door.
2.2 ACCESSORIES
2.2.1 Door Louvers
Fabricate from wood and of sizes indicated. Provide louvers with a minimum of 35 percent free air. Equip louvers with sightproof inverted vee slat type. Mount louvers in the door with flush wood moldings.
2.2.2 Door Light Openings
Provide glazed openings with the manufacturer's standard wood moldings.
Lip type moldings for flush doors.
2.2.3 Additional Hardware Reinforcement
Provide the minimum lock blocks to secure the specified hardware. The measurement of top, bottom, and intermediate rail blocks are a minimum 125 mm 5 inch by full core width. Comply with the manufacturer's labeling requirements for reinforcement blocking, but not mineral material similar to the core.
SECTION 08 14 00 Page 3
W91236-10-R-0007
2.3 FABRICATION
2.3.1 Marking
Stamp each door with a brand, stamp, or other identifying mark indicating quality and construction of the door.
2.3.2 Quality and Construction
Identify the standard on which the construction of the door was based , identify the standard under which preservative treatment was made, and identify doors having a Type I glue bond.
2.3.3 Preservative Treatment
Treat doors scheduled for restrooms, janitor closets and other possible wet locations including exterior doors with a water-repellent preservative treatment and so marketed at the manufacturer's plant in accordance with
WDMA I.S. 4 .
2.3.4 Adhesives and Bonds
WDMA I.S. 1-A . Use Type I bond for exterior doors and Type II bond for interior doors. Provide a nonstaining adhesive on doors with a natural finish.
2.3.5 Prefitting
Provide factory prefinished and factory prefitted doors for the specified hardware, door frame and door-swing indicated. Machine and size doors at the factory by the door manufacturer in accordance with the standards under which the doors are produced and manufactured. The work includes sizing, bevelling edges, mortising, and drilling for hardware and providing necessary beaded openings for glass and louvers. Provide the door manufacturer with the necessary hardware samples, and frame and hardware schedules to coordinate the work.
2.3.6 Finishes
2.3.6.1 Field Painting
Factory prime or seal doors, and field paint.
2.3.6.2 Color
Provide door finish colors as indicated .
2.4 SOURCE QUALITY CONTROL
Meet or exceed the following minimum performance criteria of stiles of "B" and "C" label fire doors utilizing standard mortise leaf hinges:
a. Split resistance : Averages of ten test samples not less than 500 pounds load when tested in accordance with WDMA TM-5.
b. Cycle-slam : 200,000 cycles with no loose hinge screws or other visible signs of failure when tested in accordance with the requirements of WDMA TM-7.
SECTION 08 14 00 Page 4
W91236-10-R-0007
c. Hinge loading resistance : Averages of ten test samples not less than 700 pounds load when tested for direct screw withdrawal in accordance with WDMA TM-8 using a No. 12, 1-1/4 inch long, steel, fully threaded wood screw. Drill 5/32 inch pilot hole, use 1-1/2 inch opening around screw for bearing surface, and engage screw full, except for last 1/8 inch . Do not use a steel plate to reinforce screw area.
PART 3 EXECUTION
3.1 INSTALLATION
Before installation, seal top and bottom edges of doors with the approved water-resistant sealer. Seal cuts made on the job immediately after cutting using approved water-resistant sealer. Fit, trim, and hang doors with a 1/16 inch minimum, 1/8 inch maximum clearance at sides and top, and a 3/16 inch minimum, 1/4 inch maximum clearance over thresholds. Provide 3/8 inch minimum, 7/16 inch maximum clearance at bottom where no threshold occurs. Bevel edges of doors at the rate of 1/8 inch in 2 inch . Door warp shall not exceed 1/4 inch when measured in accordance with WDMA I.S. 1-A .
3.1.1 Fire Doors
Install fire doors in accordance with NFPA 80 . Do not paint over labels.
-- End of Section --