222 North Center Street Bonham, TX 75418
(903) 583-8097
ACT COMMUNICATIONS, INC. CONTACT US
www.act-communications.com | sales@act-communications.com
ACT Surge Stryker 455 LT Family 7-Mode Hardwired Primary AC Surge Protection Device
RECOMMENDED LOCATION
• Type 2 Location
• Cell Sites, Well Pumps / Cat C
• Distribution Equipment / Cat B
• Branch Panels / Cat B
• Point of Use / Cat A
• Residential / Cat C
The Surge Stryker LT Family is a high performance surge protector designed for critical panel locations.
The SPD incorporates high-energy MOVs with the best performing AC !lter on the market to provide protection against transients originating from induced lightning strikes, utility switching and facility power noise.
Real-time diagnostics include LED fault indicators for each phase, as well as an optional alarm that includes red LED, dual Form C dry contacts for remote indication.
Housed in a rugged resin NEMA 12/4X enclosure, these devices are suitable for harsh indoor or outdoor applications. The ACT 455 LT Family is available for all voltages and con!gurations up to 480Vac.
EXAMPLE: ACT455-277Y-100-LT-R
Wall mounted protector at 100kA/mode with remote alarm relay.
AC PANEL PROTECTION
• Available in 050, 080, 100 kA per modes
• All modes of protection
• 200 kAIC Fault Current Rating
• Advanced EMI/RFI Noise Filtering (-45dB) 3kHz - 1MHz
• 2-year warranty (5-year optional)
• 3rd Party Tested - 15,000 (C3 20 kV/10 kA)
CHARACTERISTICS
Surge Handling (Imax) Up to 100 kA/mode
200 kA/phase
All Mode Protection (10 modes) L-N, L-G, N-G, L-L
Response Time <5 nanoseconds MOV Technology
Green LED Indicators Yes
EMI/RFI Noise Rejection (option) -45dB
Optional Alarms
Red LED Yes
Remote Signalling Form C dry contacts – NC & NO
STANDARDS & GUIDELINES
Lis ted by ETL for UL 1449 3rd edition USA
ANSI/IEEE C62.41 USA
Listed by ETL for UL 1283 Power Filters USA
3rd Party to IEC61643-11 CE Mark International
FEATURES
Surge Rating (kA) by Mode: 050, 080, 100
Surge Rating (kA) by Phase: 100, 160, 200
Enclosure Type: Resin NEMA 12/4X –
Standard no option code
Optional Alarms Alarm LED, Remote Relay – R
Optional Filter -45 dB EMI / Noise Filter – F
Optional Mounting Top Feed – T
A C
T
LT
: 1
ACT COMMUNICATIONS, INC. CONTACT US
www.act-communications.com | sales@act-communications.com
ACT Surge Stryker 455 LT Family 7-Mode Hardwired Primary AC Surge Protection Device
Part Number Con!guration MCOV
VPR (Voltage Protection Rating)
IEEE C62 – UL 3rd Edition
L-N L-G N-G L-L
455-120S-XXX-RF 120/240 Vac 3W+G 150V 700 700 700 1000
455-120Y-XXX-RF 120/208 Vac 4W+G 150V 700 700 700 1000
455-277Y-XXX-RF 277/480 Vac 4W+G 320V 1000 1000 1000 1800
455-240D-XXX-RF 240 Vac 3W+G, delta 320V - 1000 - 1800
455-240H-XXX-RF 120/240 Vac 4W+G, delta HL PHB 150V/320V 700/1000 700/1000 1000 1000/1800
455-480D-XXX-RF 480 Vac 3W+G, delta 600V - 1800 - 3000
TECHNICAL INFORMATION
ELECTRICAL SPECIFICATIONS
Connection Method Parallel
Discrete Protection Modes (7) L-N, L-G, N-G
Protection Modes (10 Modes) L-N, L-G, L-L, N-G
Pre-Wired 30” Stranded #10 AWG
Status Indicators Green LED
Optional EMI Filter -45 dB Noise Reduction
Optional Alarm Relay Contacts Form C NC & NO
Optional Red LED Indicates Red when unit is in alarm
MECHANICAL SPECIFICATIONS
Weight 10 lbs
Standard Enclosure Resin NEMA 12 / 4X
Operating Temp -40C to +65C
Non-condensing Humidity 5% to 95%
Bottom Fed is Standard – Top Fed is Option Code – T
100% Sanded for Increased Safety
7 Mode 455 Model Numbers
Model No. System Voltage Service Con�guration
455-120-XXX 120 VAC 1 PHASE, 2 WIRE, W/GROUND
455-240-XXX 240 VAC 1 PHASE, 2 WIRE, W/GROUND
455-120S-XXX 120/240 VAC 1 PHASE, 3 WIRE SPLIT PHASE, W/GROUND
455-120Y-XXX 120/208 VAC 3 PHASE, 4 WIRE WYE, W/GROUND
455-220Y-XXX 220/380 VAC 3 PHASE, 4 WIRE WYE, W/GROUND
455-277Y-XXX 277/480 VAC 3 PHASE, 4 WIRE WYE, W/GROUND
455-240H-XXX 120/240 VAC
B PHASE IS 208V 3 PHASE, HIGH-LEG DELTA, W/GROUND
455-240D-XXX 240VAC 3 PHASE, 3 WIRE DELTA, W/GROUND
455-380D-XXX 380 VAC 3 PHASE, 3 WIRE DELTA, W/GROUND
455-480D-XXX 480 VAC 3 PHASE, 3 WIRE DELTA, W/GROUND
DIMENSIONAL SPECIFICATIONS
Dim ACT 455 – 50, 80, 100, 125, 160, 200
H3 10.00 (254)
W1 8.00 (203.2)
D 6.00 (154.2)
Single Phase, 3-Wire (with neutral) 3-Phase, 4-Wire WYE