DATE BY/APP/APPREV

SIZE FSCM No.

SCALE

DWG NO.

SHEET OF

REV

TITLE

EXPLOSION PROTECTION SYSTEM

DESCRIPTION

CHKD

DRN DATE

DATE SYSD2

SYSD1 DATE

DATE

PURCHASED BY: INSTALLED AT:

DESCRIPTIONQTYITEM PART NUMBER

GENERAL NOTES:

1. PROPER OPERATION OF THIS SYSTEM IS DEPENDENT UPON THE LOCATION OF ALL SYSTEM

COMPONENTS IN ACCORDANCE WITH THIS DRAWING.

2. ANY MODIFICATION TO THE PROPOSED INSTALLATION MUST BE COMMUNICATED TO AND

APPROVED BY SSI IN WRITING, PRIOR TO INSTALLATION. ANY CHANGES MUST BE

RECORDED AS A SSI REVISED DRAWING.

3. FOR FIELD WIRING AND SPECIFIC WIRE CONNECTIONS, CONSULT SSI SHEET 1D.

4. FOR INSTALLATION STANDARDS, GENERAL INFORMATION AND SAFETY REQUIREMENTS,

REFER TO THE FOLLOWING: ANSI B31.1 - PIPING AND FITTINGS, ANSI B16.5 - FLANGES, NFPA

69, NFPA 72, FIKE SPECIFICATION E06-018 - EXPLOSION SUPPRESSION CONTAINERS

INSTALLATION AND OPERATING INSTRUCTIONS AND FIKE MOUNTING DETAILS.

5. IN THE EVENT THAT ANY DESIGN PARAMETERS CHANGE, A SYSTEM PERFORMANCE REVIEW

SHALL BE CONDUCTED BY FIKE TO DETERMINE THE EFFECT, IF ANY, OF SUCH CHANGES ON

SYSTEM PERFORMANCE.

MECHANICAL NOTES:

1. DO NOT INSTALL GAS CARTRIDGE ACTUATORS (GCA'S) UNTIL SYSTEM HAS BEEN FULLY

TESTED BY A FIKE SYSTEM TECHNICIAN OR OTHER QUALIFIED PERSONNEL. GCA'S MUST

BE HANDLED IN ACCORDANCE WITH FIKE MANUALS E06-017, E06-018 AND THE

MANUFACTURER'S RECOMMENDATIONS.

2. ALL CONDUIT AND FITTINGS FOR FIKE SYSTEM MUST BE WEATHER TIGHT.

3. WHEN ASSEMBLING, SEAL ALL PROCESS PRESSURE THREADS WITH TFE TAPE OR EQUAL.

4. THE 4" STANDARD NOZZLE ASSEMBLY IS SUPPLIED WITH

(8) STUDS, 3/4"-10 UNC-2A X 6" LONG AND (8) NUTS, 3/4"-10 UNC-2B.

5. THE SUPPRESSANT CONTAINER SHALL BE FACTORY FILLED WITH FIKE POWDER AGENT

AND PRESSURIZED WITH DRY NITROGEN AT THE JOB SITE, BY FIKE SYSTEM TECHNICIAN OR

OTHER QUALIFIED PERSONNEL.

6. WHEN RECHARGING THE SUPPRESSANT CONTAINER, THE FOLLOWING COMPONENTS ARE

REQUIRED.

ITEMS NOT SHOWN ON DRAWING: ITEM NO. 1. LOCATION TO BE DETERMINED BY OTHER THAN SSI.

LOCATE CONTROL MODULES, IN AN ELECTRICALLY CLASSIFIED NON-HAZARDOUS LOCATION.

TEMPERATURE RANGE 0° F TO 110° F. REFERENCE FIKE SPECIFICATION E06-051, E06-052 , E06-053, E06-054, E06-061 & E06-018 FOR FURTHER DETAILS.

LOCATE CAUTION SIGNS, NEAR PROCESS ACCESS DOORS AND AREAS OF FREQUENT

MAINTENANCE.

29945022-C-S

E02-0081 CAUTION SIGN

CERAMIC PRESSURE DETECTOR

RIGID MOUNT FOR CERAMIC DETECTOR

02-4134

GAS CARTRIDGE ACTUATOR (GCA)

E70-030-SBC 20 LITER HRD CONTAINER w/ 42 LB. SBC4

E10-0066 EXPLOSION PROTECTION CONTROLLER (EPC)

E10-0067 POWER SUPPLY (PSU)

E10-0068 ANNUNCIATOR MODULE (AM)

E10-0083-3 BATTERY KIT, 12V, 44AH

E10-0111 ENCLOSURE BREATHER DRAIN KIT, BRASS

02-10644 TRANSFORMER, 120/240V

10-2557 DIN RAIL KIT, 20"

10-2457 820 ohm EOL RESISTOR

10-2459 2.4V ZENER DIODE SERIES CONTACT DEVICE

E70-063 9 LOCKOUT, HRD ASSEMBLY - 4", w/SENSOR

E10-0105 DISABLE POWER SWITCH2

E61-063-1

E80-025-2

E02-0172-5

E70-0064-1

SPREADER NOZZLE COVER NEOPRENE - 4"

SPREADER NOZZLE BOLTING PAD, CS-4"

SPREADER NOZZLE ASSEMBLY w/LOCKOUT

02-9073 VERTICAL MOUNT TRI-CLOVER FERRULE

SURGE PROTECTION DEVICE

36 X 24 WINDOW KIT FOR ENCLOSURE

36 X 24 BACK PANEL FOR ENCLOSURE

ENCLOSURE, 36x24x8 NEMA 4 SST ENCLOSURE

DIN RAIL TO BE CENTERED

HORIZONTALLY IN PANEL

24"

36"

BACKING PLATE

ENCLOSURE

FIKE FIELD WIRE

ENTRANCE

PREFERRED

BREATHER (TYP.)

FIKE FIELD WIRE

ENTRANCE

ALTERNATE

SHUTDOWNS/INTERLOCKS

ENTRANCE

PREFERRED

AC INPUT

ENTRANCE

PREFERRED

SYSTEM 1 BOOTH 44 - BUILDING 350

SYSTEM DESIGN NOTES:

THE FIKE SYSTEM IS DESIGNED AND INTENDED TO LIMIT PRESSURE DEVELOPED BY THE

HEAT OF COMBUSTION AND CHEMICALLY BLOCK PROPAGATION PATHWAYS IN THE EVENT OF

AN EXPLOSION (DEFLAGRATION) WITHIN THE PROTECTED VOLUME. DURING SYSTEM

ACTIVATION, A MOMENTARY PRESSURE EXCURSION WITHIN THE DUST COLLECTOR VOLUME

NOT EXCEEDING 3.0 PSIG AND THE CYCLONE NOT EXCEEDING 4.1 PSIG CAN BE EXPECTED.

THIS VALUE IS A MAXIMUM PREDICTED IMPULSE PRESSURE BASED UPON TOTALLY

ENCLOSED VOLUMES AND WILL BE LOWER DUE TO PRESSURE EQUALIZATION THROUGH

OPEN INLET/OUTLET DUCTS AS WELL AS ANY OTHER PRESSURE RELIEF PATHS SUCH AS

EXPLOSION VENTS. ENCLOSURES NOT CAPABLE OF WITHSTANDING PREDICTED PRESSURES

SHOULD BE REINFORCED OR FITTED WITH SUFFICIENT EXPLOSION VENT AREA RELEASING

TO A SAFE AREA.

THE SUPPRESSION SYSTEMS DEFINED WITHIN THESE DRAWINGS HAVE BEEN DESIGNED

BASED ON PROCESS OPERATING PARAMETERS AS DEFINED BY CUSTOMER. FIKE ACCEPTS

NO RESPONSIBILITY AS TO THE AUTHENTICITY OR ACCURACY OF THIS SUPPLIED

INFORMATION. NOR DOES FIKE ACCEPT ANY RESPONSIBILITY FOR ANY DAMAGE RESULTING

FROM THE APPLICATION OF THE SUPPLIED INFORMATION. IT MUST BE UNDERSTOOD THAT

EACH SUPPRESSION SYSTEM IS SPECIFICALLY ENGINEERED FOR APPLICATION TO THE

RESPECTIVE PROCESS ENCLOSURE AND FUEL FOR WHICH IT WAS ORIGINALLY DESIGNED.

ANY ATTEMPT TO ALTER, CHANGE OR REAPPLY THIS SYSTEM OR FAILURE TO ADHERE TO A

FIKE FACTORY RECOMMENDED MAINTENANCE SCHEDULE COULD RESULT IN SYSTEM

MALFUNCTION AND/OR PERSONAL INJURY.

INSTALLATION NOTES:

1. DUCT MOUNTED COMPONENT LOCATION DIMENSIONS ARE FROM DUCT CENTERLINE.

2. ANY INTERCONNECTED DUCTS, (LOCATED BETWEEN THE UNITS AND THE HRD), NOT

ILLUSTRATED IN THIS DRAWING WILL BE UNPROTECTED WITH THIS SYSTEM. ANY DUCTS

NOT SHOWN ON THIS DRAWING WILL BE UNPROTECTED WITH THIS SYSTEM.

3. HRD SHALL NOT BE INSTALLED CLOSER THAN 1 PIPE DIAMETER TO UPSTREAM

BRANCHES.

4. FIKE CONTROL PANEL MUST BE DISARMED WHEN LOADING, UNLOADING, OR

PERFORMING MAINTENANCE ON PROTECTED EQUIPMENT.

5. DETECTORS EXPOSED TO TEMPERATURE BELOW 0° C (32° F) MUST BE HEATED OR

INSULATED, BY CUSTOMER.

6. DO NOT OPEN PROCESS ACCESS AREAS UNLESS THE FIKE SYSTEM IS DISABLED.

7. FIKE EQUIPMENT MUST NOT BE COVERED BY PRODUCT.

E70-064 1 LOCKOUT, HRD ASSEMBLY - 6", w/SENSOR

E70-030-SBC 20 LITER HRD CONTAINER w/ 42 LB. SBC4

E80-029-2

E80-0060-2

E80-0065-1

HYGIENIC NOZZLE COVER SST - 4"

HYGIENIC NOZZLE BOLTING PAD, SST-4"

HYGIENIC NO NOZZLE ASSEMBLY

E70-030-SBC 20 LITER HRD CONTAINER w/ 42 LB. SBC1

E80-0067-2

E80-0148

E80-0065-1

HYGIENIC TELESCOPIC NOZZLE COVER SST - 4"

HYGIENIC TELESCOPIC NOZZLE BOLTING PAD, SST-4"

HYGIENIC TELESCOPIC NOZZLE ASSEMBLY w/LOCKOUT

E70-033-SBC 50 LITER HRD CONTAINER w/ 100 LB. SBC1

E80-018-2

E80-0038

E80-0043

HYGIENIC TELESCOPIC NOZZLE COVER SST - 6"

HYGIENIC TELESCOPIC NOZZLE BOLTING PAD, SST-6"

HYGIENIC TELESCOPIC NOZZLE ASSEMBLY w/LOCKOUT

02-14426

E70-048 LOW PRESSURE SWITCH - HRD10

* INCLUDES GCA.TO REORDER GCA USE FIKE PART NO. 02-4134.

CONTAINER

SIZE

RELOAD

KITS/PART

NOZZLE

COVER

AGENT

AGENT

WEIGHT

NITROGEN CHARGE

PRESSURE @ 70°F

50 LITER E85-027 E80-0038 E85-038-50 SBC 100 LBS. 900 PSIG

20 LITER E85-005 E02-0172-5 E85-038-20 SBC 42 LBS. 900 PSIG

20 LITER E85-026 E80-0148 E85-038-20 SBC 42 LBS. 900 PSIG

20 LITER E85-029 E80-0060-2 E85-038-20 SBC 42 LBS. 900 PSIG

FIKE PROTECTION SYSTEMS EQUIPMENT SHALL BE USED. THE SYSTEM SHALL BE FURNISHED,

INSTALLED AND TESTED BY THE AUTHORIZED FIKE PROTECTION SYSTEMS DISTRIBUTOR:

(DIRECT) 610.295.5852

SUPPRESSION SYSTEMS, INC.

(PHONE) 800.360.0687

EXPLOSION SALES MANAGER: RICK SEIDEL

THE INFORMATION ON THESE DRAWINGS REFLECTS THE DESIGN OF THE EXPLOSION PROTECTION

SYSTEM PROPOSED BY SUPPRESSION SYSTEMS INC., FINAL COMMISSIONING OF THIS SYSTEM

WILL NOT OCCUR WITHOUT THESE DRAWINGS BEING APPROVED BY THE CUSTOMER / CUSTOMER

REPRESENTATIVE.

DETECTION SET PRESSURE 1.0 PSIG

MIN. STATIC WARNING -2.0 PSIG

MAX. STATIC WARNING 0.5 PSIG

DETECTION PROGRAMMING

VOLUME TOTAL

EXPLOSION HAZARD

EQUIPMENT DESIGN PRESSURE

VOLUME DIRTY (LESS FILTERS)

FILTERS

PROCESS OPERATING PRESSURE

PROCESS TEMPERATURE

AMBIENT TEMPERATURE

170°F MAX

70°F MAX

SUPPRESSANT CONCENTRATION

4.5 LBS / m

PROCESS OPERATING PARAMETERS

2350.5 FT

*WALNUT SHELL

KSt 101 bar*m/s, Pmax 7.02 BARG

1308.9 FT

168 FILTERS, Ø13-7/8" X 3' LONG

TO BE DETERMINED

VECT-AIRE COLLECTOR

VOLUME TOTAL

EXPLOSION HAZARD

EQUIPMENT DESIGN PRESSURE

PROCESS OPERATING PRESSURE

PROCESS TEMPERATURE

AMBIENT TEMPERATURE

SUPPRESSANT CONCENTRATION

4.9 LBS / m

PROCESS OPERATING PARAMETERS

1030.3 FT

CYCLONE

BOOTH 44

MODEL: SVA-168-36P4

BOOTH 44

*WALNUT SHELL

KSt 101 bar*m/s, Pmax 7.02 BARG

170°F MAX

70°F MAX

TO BE DETERMINED

ATMOSPHERIC TO -5" WC

ATMOSPHERIC TO -5" WC

*REFERENCE FIKE EXPLOSION REPORT #11152380EXP

*REFERENCE FIKE EXPLOSION REPORT #11152380EXP

12/23/14 RDS/JY/TLA ISSUED, APPROVED BY FIKE

4/10/15 RDS/JY/TLB

CYCLONE INLET DUCT SIZE CHANGE, ADDED (1) ISOLATION HRD. APPROVED BY FIKE

SCALE

DWG NO.

SHEET OF

REV

TITLE

EXPLOSION PROTECTION SYSTEM

DESCRIPTION

CHKD

DRN DATE

DATE SYSD2

SYSD1 DATE

DATE

PURCHASED BY: INSTALLED AT:

SYSTEM 1 BOOTH 44 - BUILDING 350

FIKE PROTECTION SYSTEMS EQUIPMENT SHALL BE USED. THE SYSTEM SHALL BE FURNISHED,

INSTALLED AND TESTED BY THE AUTHORIZED FIKE PROTECTION SYSTEMS DISTRIBUTOR:

(DIRECT) 610.295.5852

SUPPRESSION SYSTEMS, INC.

(PHONE) 800.360.0687

EXPLOSION SALES MANAGER: RICK SEIDEL

THE INFORMATION ON THESE DRAWINGS REFLECTS THE DESIGN OF THE EXPLOSION PROTECTION

SYSTEM PROPOSED BY SUPPRESSION SYSTEMS INC., FINAL COMMISSIONING OF THIS SYSTEM

WILL NOT OCCUR WITHOUT THESE DRAWINGS BEING APPROVED BY THE CUSTOMER / CUSTOMER

REPRESENTATIVE.

4" ASME, 6" ASME HRD'S AND DOT SRD CONTAINER DETAIL

4" ASME HRD CONTAINER AND SPREADER NOZZLE ASSEMBLY

4" ASME HRD CONTAINER AND TELESCOPIC NOZZLE ASSEMBLY

6" ASME HRD CONTAINER AND TELESCOPIC NOZZLE ASSEMBLY

4" ASME HRD CONTAINER AND NO NOZZLE ASSEMBLY

12/23/14 RDS/JY/TLA ISSUED, APPROVED BY FIKE

SCALE

DWG NO.

SHEET OF

REV

TITLE

EXPLOSION PROTECTION SYSTEM

DESCRIPTION

CHKD

DRN DATE

DATE SYSD2

SYSD1 DATE

DATE

PURCHASED BY: INSTALLED AT:

SYSTEM 1 BOOTH 44 - BUILDING 350

FIKE PROTECTION SYSTEMS EQUIPMENT SHALL BE USED. THE SYSTEM SHALL BE FURNISHED,

INSTALLED AND TESTED BY THE AUTHORIZED FIKE PROTECTION SYSTEMS DISTRIBUTOR:

(DIRECT) 610.295.5852

SUPPRESSION SYSTEMS, INC.

(PHONE) 800.360.0687

EXPLOSION SALES MANAGER: RICK SEIDEL

THE INFORMATION ON THESE DRAWINGS REFLECTS THE DESIGN OF THE EXPLOSION PROTECTION

SYSTEM PROPOSED BY SUPPRESSION SYSTEMS INC., FINAL COMMISSIONING OF THIS SYSTEM

WILL NOT OCCUR WITHOUT THESE DRAWINGS BEING APPROVED BY THE CUSTOMER / CUSTOMER

REPRESENTATIVE.

K:\Engineering\2014\14168-Letterkenny Army Depot\14168 REV A 122314\14168-1 DESIGN B 041015.dwg

12/23/14 RDS/JY/TLA ISSUED, APPROVED BY FIKE

SCALE

DWG NO.

SHEET OF

REV

TITLE

EXPLOSION PROTECTION SYSTEM

DESCRIPTION

CHKD

DRN DATE

DATE SYSD2

SYSD1 DATE

DATE

PURCHASED BY: INSTALLED AT:

SYSTEM 1 BOOTH 44 - BUILDING 350

FIKE PROTECTION SYSTEMS EQUIPMENT SHALL BE USED. THE SYSTEM SHALL BE FURNISHED,

INSTALLED AND TESTED BY THE AUTHORIZED FIKE PROTECTION SYSTEMS DISTRIBUTOR:

(DIRECT) 610.295.5852

SUPPRESSION SYSTEMS, INC.

(PHONE) 800.360.0687

EXPLOSION SALES MANAGER: RICK SEIDEL

THE INFORMATION ON THESE DRAWINGS REFLECTS THE DESIGN OF THE EXPLOSION PROTECTION

SYSTEM PROPOSED BY SUPPRESSION SYSTEMS INC., FINAL COMMISSIONING OF THIS SYSTEM

WILL NOT OCCUR WITHOUT THESE DRAWINGS BEING APPROVED BY THE CUSTOMER / CUSTOMER

REPRESENTATIVE.

K:\Engineering\2014\14168-Letterkenny Army Depot\14168 REV A 122314\14168-1 DESIGN B 041015.dwg

12/23/14 RDS/JY/TLA ISSUED, APPROVED BY FIKE

SCALE

DWG NO.

SHEET OF

REV

TITLE

EXPLOSION PROTECTION SYSTEM

DESCRIPTION

CHKD

DRN DATE

DATE SYSD2

SYSD1 DATE

DATE

PURCHASED BY: INSTALLED AT:

DESCRIPTIONQTYITEM PART NUMBER

GENERAL NOTES:

1. PROPER OPERATION OF THIS SYSTEM IS DEPENDENT UPON THE LOCATION OF ALL SYSTEM

COMPONENTS IN ACCORDANCE WITH THIS DRAWING.

2. ANY MODIFICATION TO THE PROPOSED INSTALLATION MUST BE COMMUNICATED TO AND

APPROVED BY SSI IN WRITING, PRIOR TO INSTALLATION. ANY CHANGES MUST BE

RECORDED AS A SSI REVISED DRAWING.

3. FOR FIELD WIRING AND SPECIFIC WIRE CONNECTIONS, CONSULT SSI SHEET 2D.

4. FOR INSTALLATION STANDARDS, GENERAL INFORMATION AND SAFETY REQUIREMENTS,

REFER TO THE FOLLOWING: ANSI B31.1 - PIPING AND FITTINGS, ANSI B16.5 - FLANGES, NFPA

69, NFPA 72, FIKE SPECIFICATION E06-018 - EXPLOSION SUPPRESSION CONTAINERS

INSTALLATION AND OPERATING INSTRUCTIONS AND FIKE MOUNTING DETAILS.

5. IN THE EVENT THAT ANY DESIGN PARAMETERS CHANGE, A SYSTEM PERFORMANCE REVIEW

SHALL BE CONDUCTED BY FIKE TO DETERMINE THE EFFECT, IF ANY, OF SUCH CHANGES ON

SYSTEM PERFORMANCE.

MECHANICAL NOTES:

1. DO NOT INSTALL GAS CARTRIDGE ACTUATORS (GCA'S) UNTIL SYSTEM HAS BEEN FULLY

TESTED BY A FIKE SYSTEM TECHNICIAN OR OTHER QUALIFIED PERSONNEL. GCA'S MUST

BE HANDLED IN ACCORDANCE WITH FIKE MANUALS E06-017, E06-018 AND THE

MANUFACTURER'S RECOMMENDATIONS.

2. ALL CONDUIT AND FITTINGS FOR FIKE SYSTEM MUST BE WEATHER TIGHT.

3. WHEN ASSEMBLING, SEAL ALL PROCESS PRESSURE THREADS WITH TFE TAPE OR EQUAL.

4. THE 4" STANDARD NOZZLE ASSEMBLY IS SUPPLIED WITH

(8) STUDS, 3/4"-10 UNC-2A X 6" LONG AND (8) NUTS, 3/4"-10 UNC-2B.

5. THE SUPPRESSANT CONTAINER SHALL BE FACTORY FILLED WITH FIKE POWDER AGENT

AND PRESSURIZED WITH DRY NITROGEN AT THE JOB SITE, BY FIKE SYSTEM TECHNICIAN OR

OTHER QUALIFIED PERSONNEL.

6. WHEN RECHARGING THE SUPPRESSANT CONTAINER, THE FOLLOWING COMPONENTS ARE

REQUIRED.

ITEMS NOT SHOWN ON DRAWING: ITEM NO. 1. LOCATION TO BE DETERMINED BY OTHER THAN SSI.

LOCATE CONTROL MODULES, IN AN ELECTRICALLY CLASSIFIED NON-HAZARDOUS LOCATION.

TEMPERATURE RANGE 0° F TO 110° F. REFERENCE FIKE SPECIFICATION E06-051, E06-052 , E06-053, E06-054, E06-061 & E06-018 FOR FURTHER DETAILS.

LOCATE CAUTION SIGNS, NEAR PROCESS ACCESS DOORS AND AREAS OF FREQUENT

MAINTENANCE.

29945022-C-S

E02-0081 CAUTION SIGN

CERAMIC PRESSURE DETECTOR

RIGID MOUNT FOR CERAMIC DETECTOR

02-4134

GAS CARTRIDGE ACTUATOR (GCA)

DETECTION SET PRESSURE 1.0 PSIG

MIN. STATIC WARNING -2.0 PSIG

MAX. STATIC WARNING 0.5 PSIG

DETECTION PROGRAMMING

E70-030-SBC 20 LITER HRD CONTAINER w/ 42 LB. SBC4

E10-0066 EXPLOSION PROTECTION CONTROLLER (EPC)

E10-0067 POWER SUPPLY (PSU)

E10-0068 ANNUNCIATOR MODULE (AM)

E10-0083-3 BATTERY KIT, 12V, 44AH

E10-0111 ENCLOSURE BREATHER DRAIN KIT, BRASS

02-10644 TRANSFORMER, 120/240V

10-2557 DIN RAIL KIT, 20"

10-2457 820 ohm EOL RESISTOR

10-2459 2.4V ZENER DIODE SERIES CONTACT DEVICE

* INCLUDES GCA.TO REORDER GCA USE FIKE PART NO. 02-4134.

E70-063 9 LOCKOUT, HRD ASSEMBLY - 4", w/SENSOR

SSI BP-EP BYPASS SWITCH3

VOLUME TOTAL

EXPLOSION HAZARD

EQUIPMENT DESIGN PRESSURE

VOLUME DIRTY (LESS FILTERS)

FILTERS

PROCESS OPERATING PRESSURE

PROCESS TEMPERATURE

AMBIENT TEMPERATURE

170°F MAX

70°F MAX

SUPPRESSANT CONCENTRATION

4.5 LBS / m

PROCESS OPERATING PARAMETERS

2350.5 FT

*WALNUT SHELL

KSt 101 bar*m/s, Pmax 7.02 BARG

1308.9 FT

168 FILTERS, Ø13-7/8" X 3' LONG

TO BE DETERMINED

VECT-AIRE COLLECTOR

E61-063-1

E80-025-2

E02-0172-5

E70-0064-1

SPREADER NOZZLE COVER NEOPRENE - 4"

SPREADER NOZZLE BOLTING PAD, CS-4"

SPREADER NOZZLE ASSEMBLY w/LOCKOUT

02-9073 VERTICAL MOUNT TRI-CLOVER FERRULE

SURGE PROTECTION DEVICE

36 X 24 WINDOW KIT FOR ENCLOSURE

36 X 24 BACK PANEL FOR ENCLOSURE

ENCLOSURE, 36x24x8 NEMA 4 SST ENCLOSURE

VOLUME TOTAL

EXPLOSION HAZARD

EQUIPMENT DESIGN PRESSURE

PROCESS OPERATING PRESSURE

PROCESS TEMPERATURE

AMBIENT TEMPERATURE

SUPPRESSANT CONCENTRATION

4.9 LBS / m

PROCESS OPERATING PARAMETERS

1030.3 FT

CYCLONE

BOOTH 50

DIN RAIL TO BE CENTERED

HORIZONTALLY IN PANEL

24"

36"

BACKING PLATE

ENCLOSURE

FIKE FIELD WIRE

ENTRANCE

PREFERRED

BREATHER (TYP.)

FIKE FIELD WIRE

ENTRANCE

ALTERNATE

SHUTDOWNS/INTERLOCKS

ENTRANCE

PREFERRED

AC INPUT

ENTRANCE

PREFERRED

MODEL: SVA-168-36P4

BOOTH 50

SYSTEM 2 BOOTH 50 - BUILDING 350

SYSTEM DESIGN NOTES:

THE FIKE SYSTEM IS DESIGNED AND INTENDED TO LIMIT PRESSURE DEVELOPED BY THE

HEAT OF COMBUSTION AND CHEMICALLY BLOCK PROPAGATION PATHWAYS IN THE EVENT OF

AN EXPLOSION (DEFLAGRATION) WITHIN THE PROTECTED VOLUME. DURING SYSTEM

ACTIVATION, A MOMENTARY PRESSURE EXCURSION WITHIN THE DUST COLLECTOR VOLUME

NOT EXCEEDING 3.0 PSIG AND THE CYCLONE NOT EXCEEDING 4.1 PSIG CAN BE EXPECTED.

THIS VALUE IS A MAXIMUM PREDICTED IMPULSE PRESSURE BASED UPON TOTALLY

ENCLOSED VOLUMES AND WILL BE LOWER DUE TO PRESSURE EQUALIZATION THROUGH

OPEN INLET/OUTLET DUCTS AS WELL AS ANY OTHER PRESSURE RELIEF PATHS SUCH AS

EXPLOSION VENTS. ENCLOSURES NOT CAPABLE OF WITHSTANDING PREDICTED PRESSURES

SHOULD BE REINFORCED OR FITTED WITH SUFFICIENT EXPLOSION VENT AREA RELEASING

TO A SAFE AREA.

THE SUPPRESSION SYSTEMS DEFINED WITHIN THESE DRAWINGS HAVE BEEN DESIGNED

BASED ON PROCESS OPERATING PARAMETERS AS DEFINED BY CUSTOMER. FIKE ACCEPTS

NO RESPONSIBILITY AS TO THE AUTHENTICITY OR ACCURACY OF THIS SUPPLIED

INFORMATION. NOR DOES FIKE ACCEPT ANY RESPONSIBILITY FOR ANY DAMAGE RESULTING

FROM THE APPLICATION OF THE SUPPLIED INFORMATION. IT MUST BE UNDERSTOOD THAT

EACH SUPPRESSION SYSTEM IS SPECIFICALLY ENGINEERED FOR APPLICATION TO THE

RESPECTIVE PROCESS ENCLOSURE AND FUEL FOR WHICH IT WAS ORIGINALLY DESIGNED.

ANY ATTEMPT TO ALTER, CHANGE OR REAPPLY THIS SYSTEM OR FAILURE TO ADHERE TO A

FIKE FACTORY RECOMMENDED MAINTENANCE SCHEDULE COULD RESULT IN SYSTEM

MALFUNCTION AND/OR PERSONAL INJURY.

INSTALLATION NOTES:

1. DUCT MOUNTED COMPONENT LOCATION DIMENSIONS ARE FROM DUCT CENTERLINE.

2. ANY INTERCONNECTED DUCTS, (LOCATED BETWEEN THE UNITS AND THE HRD), NOT

ILLUSTRATED IN THIS DRAWING WILL BE UNPROTECTED WITH THIS SYSTEM. ANY DUCTS

NOT SHOWN ON THIS DRAWING WILL BE UNPROTECTED WITH THIS SYSTEM.

3. HRD SHALL NOT BE INSTALLED CLOSER THAN 1 PIPE DIAMETER TO UPSTREAM

BRANCHES.

4. FIKE CONTROL PANEL MUST BE DISARMED WHEN LOADING, UNLOADING, OR

PERFORMING MAINTENANCE ON PROTECTED EQUIPMENT.

5. DETECTORS EXPOSED TO TEMPERATURE BELOW 0° C (32° F) MUST BE HEATED OR

INSULATED, BY CUSTOMER.

6. DO NOT OPEN PROCESS ACCESS AREAS UNLESS THE FIKE SYSTEM IS DISABLED.

7. FIKE EQUIPMENT MUST NOT BE COVERED BY PRODUCT.

*WALNUT SHELL

KSt 101 bar*m/s, Pmax 7.02 BARG

170°F MAX

70°F MAX

TO BE DETERMINED

E70-064 1 LOCKOUT, HRD ASSEMBLY - 6", w/SENSOR

E70-030-SBC 20 LITER HRD CONTAINER w/ 42 LB. SBC4

E80-029-2

E80-0060-2

E80-0065-1

HYGIENIC TELESCOPIC NOZZLE COVER SST - 4"

HYGIENIC TELESCOPIC NOZZLE BOLTING PAD, SST-4"

HYGIENIC NO NOZZLE ASSEMBLY w/LOCKOUT

E70-030-SBC 20 LITER HRD CONTAINER w/ 42 LB. SBC1

E80-0067-2

E80-0148

E80-0065-1

HYGIENIC TELESCOPIC NOZZLE COVER SST - 4"

HYGIENIC TELESCOPIC NOZZLE BOLTING PAD, SST-4"

HYGIENIC TELESCOPIC NOZZLE ASSEMBLY w/LOCKOUT

E70-033-SBC 50 LITER HRD CONTAINER w/ 100 LB. SBC1

E80-018-2

E80-0038

E80-0043

HYGIENIC TELESCOPIC NOZZLE COVER SST - 6"

HYGIENIC TELESCOPIC NOZZLE BOLTING PAD, SST-6"

HYGIENIC TELESCOPIC NOZZLE ASSEMBLY w/LOCKOUT

E70-048 LOW PRESSURE SWITCH - HRD10

02-14426

ATMOSPHERIC TO -5" WC

ATMOSPHERIC TO -5" WC

CONTAINER

SIZE

RELOAD

KITS/PART

NOZZLE

COVER

AGENT

AGENT

WEIGHT

NITROGEN CHARGE

PRESSURE @ 70°F

50 LITER E85-027 E80-0038 E85-038-50 SBC 100 LBS. 900 PSIG

20 LITER E85-005 E02-0172-5 E85-038-20 SBC 42 LBS. 900 PSIG

20 LITER E85-026 E80-0148 E85-038-20 SBC 42 LBS. 900 PSIG

20 LITER E85-029 E80-0060-2 E85-038-20 SBC 42 LBS. 900 PSIG

FIKE PROTECTION SYSTEMS EQUIPMENT SHALL BE USED. THE SYSTEM SHALL BE FURNISHED,

INSTALLED AND TESTED BY THE AUTHORIZED FIKE PROTECTION SYSTEMS DISTRIBUTOR:

(DIRECT) 610.295.5852

SUPPRESSION SYSTEMS, INC.

(PHONE) 800.360.0687

EXPLOSION SALES MANAGER: RICK SEIDEL

THE INFORMATION ON THESE DRAWINGS REFLECTS THE DESIGN OF THE EXPLOSION PROTECTION

SYSTEM PROPOSED BY SUPPRESSION SYSTEMS INC., FINAL COMMISSIONING OF THIS SYSTEM

WILL NOT OCCUR WITHOUT THESE DRAWINGS BEING APPROVED BY THE CUSTOMER / CUSTOMER

REPRESENTATIVE.

*REFERENCE FIKE EXPLOSION REPORT #11152380EXP

*REFERENCE FIKE EXPLOSION REPORT #11152380EXP

K:\Engineering\2014\14168-Letterkenny Army Depot\14168 REV A 122314\14168-2 DESIGN B 040915.dwg

12/23/14 RDS/JY/TLA ISSUED, APPROVED BY FIKE

SCALE

DWG NO.

SHEET OF

REV

TITLE

EXPLOSION PROTECTION SYSTEM

DESCRIPTION

CHKD

DRN DATE

DATE SYSD2

SYSD1 DATE

DATE

PURCHASED BY: INSTALLED AT:

SYSTEM 2 BOOTH 50 - BUILDING 350

FIKE PROTECTION SYSTEMS EQUIPMENT SHALL BE USED. THE SYSTEM SHALL BE FURNISHED,

INSTALLED AND TESTED BY THE AUTHORIZED FIKE PROTECTION SYSTEMS DISTRIBUTOR:

(DIRECT) 610.295.5852

SUPPRESSION SYSTEMS, INC.

(PHONE) 800.360.0687

EXPLOSION SALES MANAGER: RICK SEIDEL

THE INFORMATION ON THESE DRAWINGS REFLECTS THE DESIGN OF THE EXPLOSION PROTECTION

SYSTEM PROPOSED BY SUPPRESSION SYSTEMS INC., FINAL COMMISSIONING OF THIS SYSTEM

WILL NOT OCCUR WITHOUT THESE DRAWINGS BEING APPROVED BY THE CUSTOMER / CUSTOMER

REPRESENTATIVE.

4" ASME, 6" ASME HRD'S AND DOT SRD CONTAINER DETAIL

4" ASME HRD CONTAINER AND SPREADER NOZZLE ASSEMBLY

4" ASME HRD CONTAINER AND TELESCOPIC NOZZLE ASSEMBLY

6" ASME HRD CONTAINER AND TELESCOPIC NOZZLE ASSEMBLY

4" ASME HRD CONTAINER AND NO NOZZLE ASSEMBLY

K:\Engineering\2014\14168-Letterkenny Army Depot\14168 REV A 122314\14168-2 DESIGN B 040915.dwg

4/9/15 RDS/JY/TLB CYCLONE INLET DUCT SIZE CHANGE, ADDED (1) ISOLATION HRD. APPROVED BY FIKE

SCALE

DWG NO.

SHEET OF

REV

TITLE

EXPLOSION PROTECTION SYSTEM

DESCRIPTION

CHKD

DRN DATE

DATE SYSD2

SYSD1 DATE

DATE

PURCHASED BY: INSTALLED AT:

SYSTEM 2 BOOTH 50 - BUILDING 350

FIKE PROTECTION SYSTEMS EQUIPMENT SHALL BE USED. THE SYSTEM SHALL BE FURNISHED,

INSTALLED AND TESTED BY THE AUTHORIZED FIKE PROTECTION SYSTEMS DISTRIBUTOR:

(DIRECT) 610.295.5852

SUPPRESSION SYSTEMS, INC.

(PHONE) 800.360.0687

EXPLOSION SALES MANAGER: RICK SEIDEL

THE INFORMATION ON THESE DRAWINGS REFLECTS THE DESIGN OF THE EXPLOSION PROTECTION

SYSTEM PROPOSED BY SUPPRESSION SYSTEMS INC., FINAL COMMISSIONING OF THIS SYSTEM

WILL NOT OCCUR WITHOUT THESE DRAWINGS BEING APPROVED BY THE CUSTOMER / CUSTOMER

REPRESENTATIVE.

K:\Engineering\2014\14168-Letterkenny Army Depot\14168 REV A 122314\14168-2 DESIGN B 040915.dwg

SCALE

DWG NO.

SHEET OF

REV

TITLE

EXPLOSION PROTECTION SYSTEM

DESCRIPTION

CHKD

DRN DATE

DATE SYSD2

SYSD1 DATE

DATE

PURCHASED BY: INSTALLED AT:

SYSTEM 2 BOOTH 50 - BUILDING 350

FIKE PROTECTION SYSTEMS EQUIPMENT SHALL BE USED. THE SYSTEM SHALL BE FURNISHED,

INSTALLED AND TESTED BY THE AUTHORIZED FIKE PROTECTION SYSTEMS DISTRIBUTOR:

(DIRECT) 610.295.5852

SUPPRESSION SYSTEMS, INC.

(PHONE) 800.360.0687

EXPLOSION SALES MANAGER: RICK SEIDEL

THE INFORMATION ON THESE DRAWINGS REFLECTS THE DESIGN OF THE EXPLOSION PROTECTION

SYSTEM PROPOSED BY SUPPRESSION SYSTEMS INC., FINAL COMMISSIONING OF THIS SYSTEM

WILL NOT OCCUR WITHOUT THESE DRAWINGS BEING APPROVED BY THE CUSTOMER / CUSTOMER

REPRESENTATIVE.

12/23/14 RDS/JY/TL

A

ISSUED, APPROVED BY FIKE

4/9/15 RDS/JYB CYCLONE INLET DUCT SIZE CHANGE, ADDED (1) ISOLATION HRD. APPROVED BY FIKE

SCALE

DWG NO.

SHEET OF

REV

TITLE

EXPLOSION PROTECTION SYSTEM

DESCRIPTION

CHKD

DRN DATE

DATE SYSD2

SYSD1 DATE

DATE

PURCHASED BY: INSTALLED AT:

DESCRIPTIONQTYITEM PART NUMBER

GENERAL NOTES:

1. PROPER OPERATION OF THIS SYSTEM IS DEPENDENT UPON THE LOCATION OF ALL SYSTEM

COMPONENTS IN ACCORDANCE WITH THIS DRAWING.

2. ANY MODIFICATION TO THE PROPOSED INSTALLATION MUST BE COMMUNICATED TO AND

APPROVED BY SSI IN WRITING, PRIOR TO INSTALLATION. ANY CHANGES MUST BE

RECORDED AS A SSI REVISED DRAWING.

3. FOR FIELD WIRING AND SPECIFIC WIRE CONNECTIONS, CONSULT SSI SHEET 5C.

4. FOR INSTALLATION STANDARDS, GENERAL INFORMATION AND SAFETY REQUIREMENTS,

REFER TO THE FOLLOWING: ANSI B31.1 - PIPING AND FITTINGS, ANSI B16.5 - FLANGES, NFPA

69, NFPA 72, FIKE SPECIFICATION E06-018 - EXPLOSION SUPPRESSION CONTAINERS

INSTALLATION AND OPERATING INSTRUCTIONS AND FIKE MOUNTING DETAILS.

5. IN THE EVENT THAT ANY DESIGN PARAMETERS CHANGE, A SYSTEM PERFORMANCE REVIEW

SHALL BE CONDUCTED BY FIKE TO DETERMINE THE EFFECT, IF ANY, OF SUCH CHANGES ON

SYSTEM PERFORMANCE.

MECHANICAL NOTES:

1. DO NOT INSTALL GAS CARTRIDGE ACTUATORS (GCA'S) UNTIL SYSTEM HAS BEEN FULLY

TESTED BY A FIKE SYSTEM TECHNICIAN OR OTHER QUALIFIED PERSONNEL. GCA'S MUST

BE HANDLED IN ACCORDANCE WITH FIKE MANUALS E06-017, E06-018 AND THE

MANUFACTURER'S RECOMMENDATIONS.

2. ALL CONDUIT AND FITTINGS FOR FIKE SYSTEM MUST BE WEATHER TIGHT.

3. WHEN ASSEMBLING, SEAL ALL PROCESS PRESSURE THREADS WITH TFE TAPE OR EQUAL.

4. THE 4" STANDARD NOZZLE ASSEMBLY IS SUPPLIED WITH

(8) STUDS, 3/4"-10 UNC-2A X 6" LONG AND (8) NUTS, 3/4"-10 UNC-2B.

5. THE SUPPRESSANT CONTAINER SHALL BE FACTORY FILLED WITH FIKE POWDER AGENT

AND PRESSURIZED WITH DRY NITROGEN AT THE JOB SITE, BY FIKE SYSTEM TECHNICIAN OR

OTHER QUALIFIED PERSONNEL.

6. WHEN RECHARGING THE SUPPRESSANT CONTAINER, THE FOLLOWING COMPONENTS ARE

REQUIRED.

ITEMS NOT SHOWN ON DRAWING: ITEM NO. 1. LOCATION TO BE DETERMINED BY OTHER THAN SSI.

LOCATE CONTROL MODULES, IN AN ELECTRICALLY CLASSIFIED NON-HAZARDOUS LOCATION.

TEMPERATURE RANGE 0° F TO 110° F. REFERENCE FIKE SPECIFICATION E06-051, E06-052 , E06-053, E06-054, E06-061 & E06-018 FOR FURTHER DETAILS.

LOCATE CAUTION SIGNS, NEAR PROCESS ACCESS DOORS AND AREAS OF FREQUENT

MAINTENANCE.

29945022-C-S

E02-0081 CAUTION SIGN

CERAMIC PRESSURE DETECTOR

RIGID MOUNT FOR CERAMIC DETECTOR

02-4134

GAS CARTRIDGE ACTUATOR (GCA)

DETECTION SET PRESSURE 1.0 PSIG

MIN. STATIC WARNING -2.0 PSIG

MAX. STATIC WARNING 0.5 PSIG

DETECTION PROGRAMMING

E70-029-SBC 10 LITER HRD CONTAINER w/ 20 LB. SBC1

E10-0066 EXPLOSION PROTECTION CONTROLLER (EPC)

E10-0067 POWER SUPPLY (PSU)

E10-0068 ANNUNCIATOR MODULE (AM)

E10-0083-1 BATTERY KIT, 12V, 35AH

E10-0111 ENCLOSURE BREATHER DRAIN KIT, BRASS

02-10644 TRANSFORMER, 120/240V

10-2557 DIN RAIL KIT, 20"

10-2457 820 ohm EOL RESISTOR

10-2459 2.4V ZENER DIODE SERIES CONTACT DEVICE

E70-063 2 LOCKOUT, HRD ASSEMBLY - 4", w/SENSOR

E10-0105 DISABLE POWER SWITCH1

CONTAINER

SIZE

RELOAD

KITS/PART

GCA

NOZZLE

COVER

AGENT

AGENT

WEIGHT

NITROGEN CHARGE

PRESSURE @ 70°F

5 LITER E85-005 02-4134 E80-0172-5 E85-038-05 SBC 10 LBS. 900 PSIG

10 LITER E85-005 02-4134 E80-0172-5 E85-038-10 SBC 20 LBS. 900 PSIG

9 LITER E85-002 02-4134 E02-0164-1 E85-038-09 SBC 18 LBS. 500 PSIG

VOLUME TOTAL

EXPLOSION HAZARD

EQUIPMENT DESIGN PRESSURE

VOLUME DIRTY (LESS FILTERS)

FILTERS

PROCESS OPERATING PRESSURE

PROCESS TEMPERATURE

AMBIENT TEMPERATURE

170°F MAX

70°F MAX

SUPPRESSANT CONCENTRATION

4.0 LBS / m

PROCESS OPERATING PARAMETERS

359 FT

*QUICK STRIP PLASTIC ABRASIVE

KSt 73 bar*m/s, Pmax 6.05 BARG

218 FT

32 FILTERS, 11.4" X 14.4 OVAL X 26" LONG

TO BE DETERMINED BY CUSTOMER

DONALDSON DFO 4-32 DUST COLLECTOR

R1005

E61-063-1

E80-025-2

E02-0172-5

E70-0064-1

SPREADER NOZZLE COVER NEOPRENE - 4"

SPREADER NOZZLE BOLTING PAD, CS-4"

SPREADER NOZZLE ASSEMBLY w/LOCKOUT

02-9073 VERTICAL MOUNT TRI-CLOVER FERRULE

SURGE PROTECTION DEVICE

ENCLOSURE, 24x24x8 NEMA 4 CS ENCLOSURE

SYSTEM 5 R1005 - BUILDING 350

SYSTEM DESIGN NOTES:

THE FIKE SYSTEM IS DESIGNED AND INTENDED TO LIMIT PRESSURE DEVELOPED BY THE

HEAT OF COMBUSTION AND CHEMICALLY BLOCK PROPAGATION PATHWAYS IN THE EVENT OF

AN EXPLOSION (DEFLAGRATION) WITHIN THE PROTECTED VOLUME. DURING SYSTEM

ACTIVATION, A MOMENTARY PRESSURE EXCURSION WITHIN THE DUST COLLECTOR VOLUME

NOT EXCEEDING 3.2 PSIG CAN BE EXPECTED. THIS VALUE IS A MAXIMUM PREDICTED

IMPULSE PRESSURE BASED UPON TOTALLY ENCLOSED VOLUMES AND WILL BE LOWER DUE

TO PRESSURE EQUALIZATION THROUGH OPEN INLET/OUTLET DUCTS AS WELL AS ANY OTHER

PRESSURE RELIEF PATHS SUCH AS EXPLOSION VENTS. ENCLOSURES NOT CAPABLE OF

WITHSTANDING PREDICTED PRESSURES SHOULD BE REINFORCED OR FITTED WITH

SUFFICIENT EXPLOSION VENT AREA RELEASING TO A SAFE AREA.

THE SUPPRESSION SYSTEMS DEFINED WITHIN THESE DRAWINGS HAVE BEEN DESIGNED

BASED ON PROCESS OPERATING PARAMETERS AS DEFINED BY CUSTOMER. FIKE ACCEPTS

NO RESPONSIBILITY AS TO THE AUTHENTICITY OR ACCURACY OF THIS SUPPLIED

INFORMATION. NOR DOES FIKE ACCEPT ANY RESPONSIBILITY FOR ANY DAMAGE RESULTING

FROM THE APPLICATION OF THE SUPPLIED INFORMATION. IT MUST BE UNDERSTOOD THAT

EACH SUPPRESSION SYSTEM IS SPECIFICALLY ENGINEERED FOR APPLICATION TO THE

RESPECTIVE PROCESS ENCLOSURE AND FUEL FOR WHICH IT WAS ORIGINALLY DESIGNED.

ANY ATTEMPT TO ALTER, CHANGE OR REAPPLY THIS SYSTEM OR FAILURE TO ADHERE TO A

FIKE FACTORY RECOMMENDED MAINTENANCE SCHEDULE COULD RESULT IN SYSTEM

MALFUNCTION AND/OR PERSONAL INJURY.

INSTALLATION NOTES:

1. DUCT MOUNTED COMPONENT LOCATION DIMENSIONS ARE FROM DUCT CENTERLINE.

2. ANY INTERCONNECTED DUCTS, (LOCATED BETWEEN THE DUST COLLECTOR AND SRD),

NOT ILLUSTRATED IN THIS DRAWING WILL BE UNPROTECTED WITH THIS SYSTEM.

3. DUCT LAYOUT AND TRANSITIONS MAY NOT BE TO SCALE OR AN ACCURATE DEPICTION.

4. SRDs SHALL NOT BE INSTALLED CLOSER THAN 1 PIPE DIAMETER TO

UPSTREAM/DOWNSTREAM BRANCHES.

5. UP TO 2 BENDS/ELBOWS ≤90° CAN BE PRESENT BETWEEN PRIMARY EXPLOSION

VOLUME AND BARRIER LOCATION.

6. FIKE CONTROL PANEL MUST BE DISARMED WHEN LOADING, UNLOADING OR

PERFORMING MAINTENANCE ON PROTECTED EQUIPMENT.

7. DETECTORS EXPOSED TO TEMPERATURES BELOW 0°C (32°F) MUST BE HEATED OR

INSULATED, BY CUSTOMER.

8. DO NOT OPEN PROCESS ACCESS AREAS UNLESS THE FIKE SYSTEM IS DISABLED.

9. FIKE EQUIPMENT MUST NOT BE COVERED BY PRODUCT.

02-14426

E70-0048 LOW PRESSURE SWITCH - HRD2

E70-028-SBC 5 LITER HRD CONTAINER w/ 10 LB. SBC1

ATMOSPHERIC TO -5" WC

E70-0049 LOW PRESSURE SWITCH - SRD4

E70-035-SBC

9 LITER SRD CONTAINER w/ 18 LB. SBC4

E80-055-1 SRD HYGIENIC NOZZLE ASSY-1-1/4"TRI-CLAMP, Ni/SST COVER4

FIKE PROTECTION SYSTEMS EQUIPMENT SHALL BE USED. THE SYSTEM SHALL BE FURNISHED,

INSTALLED AND TESTED BY THE AUTHORIZED FIKE PROTECTION SYSTEMS DISTRIBUTOR:

(DIRECT) 610.295.5852

SUPPRESSION SYSTEMS, INC.

(PHONE) 800.360.0687

EXPLOSION SALES MANAGER: RICK SEIDEL

THE INFORMATION ON THESE DRAWINGS REFLECTS THE DESIGN OF THE EXPLOSION PROTECTION

SYSTEM PROPOSED BY SUPPRESSION SYSTEMS INC., FINAL COMMISSIONING OF THIS SYSTEM

WILL NOT OCCUR WITHOUT THESE DRAWINGS BEING APPROVED BY THE CUSTOMER / CUSTOMER

REPRESENTATIVE.

*REFERENCE FIKE EXPLOSIBILITY REPORT #11152375EXP

4" ASME, 6" ASME HRD'S AND DOT SRD CONTAINER DETAIL

4" ASME HRD CONTAINER AND SPREADER NOZZLE ASSEMBLY

12/23/14 RDS/JY/TLA ISSUED, APPROVED BY FIKE

3/23/15 RDS/JYB DUCT SIZE CHANGE/ADDED (2) SRD'S

5/17/19 JB/DTC GENERAL REVISIONS

6/28/19 JB/DTD MECHANICAL / ELECTRICAL AS BUILT

SCALE

DWG NO.

SHEET OF

REV

TITLE

EXPLOSION PROTECTION SYSTEM

DESCRIPTION

CHKD

DRN

DATE

DATE SYSD2

SYSD1 DATE

DATE

PURCHASED BY: INSTALLED AT:

DIN RAIL TO BE CENTERED

HORIZONTALLY IN PANEL

24"

24"

BACKING PLATE

ENCLOSURE

FIKE FIELD WIRE

ENTRANCE

PREFERRED

BREATHER (TYP.)

FIKE FIELD WIRE

ENTRANCE

ALTERNATE

SHUTDOWNS/INTERLOCKS

ENTRANCE

PREFERRED

AC INPUT

ENTRANCE

PREFERRED

SYSTEM 5 R1005 - BUILDING 350

FIKE PROTECTION SYSTEMS EQUIPMENT SHALL BE USED. THE SYSTEM SHALL BE FURNISHED,

INSTALLED AND TESTED BY THE AUTHORIZED FIKE PROTECTION SYSTEMS DISTRIBUTOR:

(DIRECT) 610.295.5852

SUPPRESSION SYSTEMS, INC.

(PHONE) 800.360.0687

EXPLOSION SALES MANAGER: RICK SEIDEL

THE INFORMATION ON THESE DRAWINGS REFLECTS THE DESIGN OF THE EXPLOSION PROTECTION

SYSTEM PROPOSED BY SUPPRESSION SYSTEMS INC., FINAL COMMISSIONING OF THIS SYSTEM

WILL NOT OCCUR WITHOUT THESE DRAWINGS BEING APPROVED BY THE CUSTOMER / CUSTOMER

REPRESENTATIVE.

K:\Engineering\2014\14168-Letterkenny Army Depot\14168-5A REV D.dwg

12/23/14 RDS/JY/TLA ISSUED, APPROVED BY FIKE

3/23/15 RDS/JYB DUCT SIZE CHANGE/ADDED (2) SRD'S

SCALE

DWG NO.

SHEET OF

REV

TITLE

EXPLOSION PROTECTION SYSTEM

DESCRIPTION

CHKD

DRN DATE

DATE SYSD2

SYSD1 DATE

DATE

PURCHASED BY: INSTALLED AT:

SYSTEM 5 R1005 - BUILDING 350

FIKE PROTECTION SYSTEMS EQUIPMENT SHALL BE USED. THE SYSTEM SHALL BE FURNISHED,

INSTALLED AND TESTED BY THE AUTHORIZED FIKE PROTECTION SYSTEMS DISTRIBUTOR:

(DIRECT) 610.295.5852

SUPPRESSION SYSTEMS, INC.

(PHONE) 800.360.0687

EXPLOSION SALES MANAGER: RICK SEIDEL

THE INFORMATION ON THESE DRAWINGS REFLECTS THE DESIGN OF THE EXPLOSION PROTECTION

SYSTEM PROPOSED BY SUPPRESSION SYSTEMS INC., FINAL COMMISSIONING OF THIS SYSTEM

WILL NOT OCCUR WITHOUT THESE DRAWINGS BEING APPROVED BY THE CUSTOMER / CUSTOMER

REPRESENTATIVE.

12/23/14 RDS/JY/TLA ISSUED, APPROVED BY FIKE

3/23/15 RDS/JYB DUCT SIZE CHANGE/ADDED (2) SRD'S

SCALE

DWG NO.

SHEET OF

REV

TITLE

EXPLOSION PROTECTION SYSTEM

DESCRIPTION

CHKD

DRN DATE

DATE SYSD2

SYSD1 DATE

DATE

PURCHASED BY: INSTALLED AT:

DESCRIPTIONQTYITEM PART NUMBER

GENERAL NOTES:

1. PROPER OPERATION OF THIS SYSTEM IS DEPENDENT UPON THE LOCATION OF ALL SYSTEM

COMPONENTS IN ACCORDANCE WITH THIS DRAWING.

2. ANY MODIFICATION TO THE PROPOSED INSTALLATION MUST BE COMMUNICATED TO AND

APPROVED BY SSI IN WRITING, PRIOR TO INSTALLATION. ANY CHANGES MUST BE

RECORDED AS A SSI REVISED DRAWING.

3. FOR FIELD WIRING AND SPECIFIC WIRE CONNECTIONS, CONSULT SSI SHEET 8C.

4. FOR INSTALLATION STANDARDS, GENERAL INFORMATION AND SAFETY REQUIREMENTS,

REFER TO THE FOLLOWING: ANSI B31.1 - PIPING AND FITTINGS, ANSI B16.5 - FLANGES, NFPA

69, NFPA 72, FIKE SPECIFICATION E06-018 - EXPLOSION SUPPRESSION CONTAINERS

INSTALLATION AND OPERATING INSTRUCTIONS AND FIKE MOUNTING DETAILS.

5. IN THE EVENT THAT ANY DESIGN PARAMETERS CHANGE, A SYSTEM PERFORMANCE REVIEW

SHALL BE CONDUCTED BY FIKE TO DETERMINE THE EFFECT, IF ANY, OF SUCH CHANGES ON

SYSTEM PERFORMANCE.

MECHANICAL NOTES:

1. DO NOT INSTALL GAS CARTRIDGE ACTUATORS (GCA'S) UNTIL SYSTEM HAS BEEN FULLY

TESTED BY A FIKE SYSTEM TECHNICIAN OR OTHER QUALIFIED PERSONNEL. GCA'S MUST

BE HANDLED IN ACCORDANCE WITH FIKE MANUALS E06-017, E06-018 AND THE

MANUFACTURER'S RECOMMENDATIONS.

2. ALL CONDUIT AND FITTINGS FOR FIKE SYSTEM MUST BE WEATHER TIGHT.

3. WHEN ASSEMBLING, SEAL ALL PROCESS PRESSURE THREADS WITH TFE TAPE OR EQUAL.

4. THE 4" STANDARD NOZZLE ASSEMBLY IS SUPPLIED WITH

(8) STUDS, 3/4"-10 UNC-2A X 6" LONG AND (8) NUTS, 3/4"-10 UNC-2B.

5. THE SUPPRESSANT CONTAINER SHALL BE FACTORY FILLED WITH FIKE POWDER AGENT

AND PRESSURIZED WITH DRY NITROGEN AT THE JOB SITE, BY FIKE SYSTEM TECHNICIAN OR

OTHER QUALIFIED PERSONNEL.

6. WHEN RECHARGING THE SUPPRESSANT CONTAINER, THE FOLLOWING COMPONENTS ARE

REQUIRED.

ITEMS NOT SHOWN ON DRAWING: ITEM NO. 1. LOCATION TO BE DETERMINED BY OTHER THAN SSI.

LOCATE CONTROL MODULES, IN AN ELECTRICALLY CLASSIFIED NON-HAZARDOUS LOCATION.

TEMPERATURE RANGE 0° F TO 110° F. REFERENCE FIKE SPECIFICATION E06-051, E06-052 , E06-053, E06-054, E06-061 & E06-018 FOR FURTHER DETAILS.

LOCATE CAUTION SIGNS, NEAR PROCESS ACCESS DOORS AND AREAS OF FREQUENT

MAINTENANCE.

29945022-C-S

E02-0081 CAUTION SIGN

CERAMIC PRESSURE DETECTOR

RIGID MOUNT FOR CERAMIC DETECTOR

02-4134

GAS CARTRIDGE ACTUATOR (GCA)

DETECTION SET PRESSURE 1.0 PSIG

MIN. STATIC WARNING -2.0 PSIG

MAX. STATIC WARNING 0.5 PSIG

DETECTION PROGRAMMING

E70-030-SBC 20 LITER HRD CONTAINER w/ 42 LB. SBC3

E10-0066 EXPLOSION PROTECTION CONTROLLER (EPC)

E10-0067 POWER SUPPLY (PSU)

E10-0068 ANNUNCIATOR MODULE (AM)

E10-0083-1 BATTERY KIT, 12V, 33AH

E10-0111 ENCLOSURE BREATHER DRAIN KIT, BRASS

02-10644 TRANSFORMER, 120/240V

10-2557 DIN RAIL KIT, 20"

10-2457 820 ohm EOL RESISTOR

10-2459 2.4V ZENER DIODE SERIES CONTACT DEVICE

* INCLUDES GCA.TO REORDER GCA USE FIKE PART NO. 02-4134.

E70-063 6 LOCKOUT, HRD ASSEMBLY - 4", w/SENSOR

E10-0105 DISABLE POWER SWITCH1

CONTAINER

SIZE

RELOAD

KITS/PART

NOZZLE

COVER

AGENT

AGENT

WEIGHT

NITROGEN CHARGE

PRESSURE @ 70°F

2.5 LITER E85-005 E80-0172-5 E85-038-2.5 SBC 5 LBS. 900 PSIG

20 LITER E85-005 E80-0172-5 E85-038-20 SBC 42 LBS. 900 PSIG

20 LITER E85-029 E80-0060-2 E85-038-20 SBC 42 LBS. 900 PSIG

E61-063-1

E80-025-2

E02-0172-5

E70-0064-1

SPREADER NOZZLE COVER NEOPRENE - 4"

SPREADER NOZZLE BOLTING PAD, CS-4"

SPREADER NOZZLE ASSEMBLY w/LOCKOUT

02-9073 VERTICAL MOUNT TRI-CLOVER FERRULE

SURGE PROTECTION DEVICE

ENCLOSURE, 24x24x8 NEMA 4 CS ENCLOSURE

SYSTEM 8 R6094 - BUILDING 57

SYSTEM DESIGN NOTES:

THE FIKE SYSTEM IS DESIGNED AND INTENDED TO LIMIT PRESSURE DEVELOPED BY THE

HEAT OF COMBUSTION AND CHEMICALLY BLOCK PROPAGATION PATHWAYS IN THE EVENT OF

AN EXPLOSION (DEFLAGRATION) WITHIN THE PROTECTED VOLUME. DURING SYSTEM

ACTIVATION, A MOMENTARY PRESSURE EXCURSION WITHIN THE DUST COLLECTOR VOLUME

NOT EXCEEDING 4.3 PSIG CAN BE EXPECTED. THIS VALUE IS A MAXIMUM PREDICTED

IMPULSE PRESSURE BASED UPON TOTALLY ENCLOSED VOLUMES AND WILL BE LOWER DUE

TO PRESSURE EQUALIZATION THROUGH OPEN INLET/OUTLET DUCTS AS WELL AS ANY OTHER

PRESSURE RELIEF PATHS SUCH AS EXPLOSION VENTS. ENCLOSURES NOT CAPABLE OF

WITHSTANDING PREDICTED PRESSURES SHOULD BE REINFORCED OR FITTED WITH

SUFFICIENT EXPLOSION VENT AREA RELEASING TO A SAFE AREA.

THE SUPPRESSION SYSTEMS DEFINED WITHIN THESE DRAWINGS HAVE BEEN DESIGNED

BASED ON PROCESS OPERATING PARAMETERS AS DEFINED BY CUSTOMER. FIKE ACCEPTS

NO RESPONSIBILITY AS TO THE AUTHENTICITY OR ACCURACY OF THIS SUPPLIED

INFORMATION. NOR DOES FIKE ACCEPT ANY RESPONSIBILITY FOR ANY DAMAGE RESULTING

FROM THE APPLICATION OF THE SUPPLIED INFORMATION. IT MUST BE UNDERSTOOD THAT

EACH SUPPRESSION SYSTEM IS SPECIFICALLY ENGINEERED FOR APPLICATION TO THE

RESPECTIVE PROCESS ENCLOSURE AND FUEL FOR WHICH IT WAS ORIGINALLY DESIGNED.

ANY ATTEMPT TO ALTER, CHANGE OR REAPPLY THIS SYSTEM OR FAILURE TO ADHERE TO A

FIKE FACTORY RECOMMENDED MAINTENANCE SCHEDULE COULD RESULT IN SYSTEM

MALFUNCTION AND/OR PERSONAL INJURY.

INSTALLATION NOTES:

1. DUCT MOUNTED COMPONENT LOCATION DIMENSIONS ARE FROM DUCT CENTERLINE.

2. ANY INTERCONNECTED DUCTS, (LOCATED BETWEEN THE DUST COLLECTOR AND THE

HRD), NOT ILLUSTRATED IN THIS DRAWING WILL BE UNPROTECTED WITH THIS SYSTEM.

ANY DUCTS NOT SHOWN ON THIS DRAWING WILL BE UNPROTECTED WITH THIS SYSTEM.

3. HRD SHALL NOT BE INSTALLED CLOSER THAN 1 PIPE DIAMETER TO UPSTREAM

BRANCHES.

4. FIKE CONTROL PANEL MUST BE DISARMED WHEN LOADING, UNLOADING, OR

PERFORMING MAINTENANCE ON PROTECTED EQUIPMENT.

5. DETECTORS EXPOSED TO TEMPERATURE BELOW 0° C (32° F) MUST BE HEATED OR

INSULATED, BY CUSTOMER.

6. DO NOT OPEN PROCESS ACCESS AREAS UNLESS THE FIKE SYSTEM IS DISABLED.

7. FIKE EQUIPMENT MUST NOT BE COVERED BY PRODUCT.

02-14426

E70-0048 LOW PRESSURE SWITCH - HRD6

E70-027-SBC 2.5 LITER HRD CONTAINER w/ 5 LB. SBC3

E80-029-2

E80-0060-2

E80-0065-1

HYGIENIC NOZZLE COVER SST - 4"

HYGIENIC NOZZLE BOLTING PAD, SST-4"

HYGIENIC NO NOZZLE ASSEMBLY

FIKE PROTECTION SYSTEMS EQUIPMENT SHALL BE USED. THE SYSTEM SHALL BE FURNISHED,

INSTALLED AND TESTED BY THE AUTHORIZED FIKE PROTECTION SYSTEMS DISTRIBUTOR:

(DIRECT) 610.295.5852

SUPPRESSION SYSTEMS, INC.

(PHONE) 800.360.0687

EXPLOSION SALES MANAGER: RICK SEIDEL

THE INFORMATION ON THESE DRAWINGS REFLECTS THE DESIGN OF THE EXPLOSION PROTECTION

SYSTEM PROPOSED BY SUPPRESSION SYSTEMS INC., FINAL COMMISSIONING OF THIS SYSTEM

WILL NOT OCCUR WITHOUT THESE DRAWINGS BEING APPROVED BY THE CUSTOMER / CUSTOMER

REPRESENTATIVE.

VOLUME TOTAL

EXPLOSION HAZARD

EQUIPMENT DESIGN PRESSURE

VOLUME DIRTY (LESS FILTERS)

FILTERS

PROCESS OPERATING PRESSURE

PROCESS TEMPERATURE

AMBIENT TEMPERATURE

170°F MAX

70°F MAX

SUPPRESSANT CONCENTRATION

6.4 LBS / m

PROCESS OPERATING PARAMETERS

551.6 FT

*QUICK STRIP PLASTIC ABRASIVE

KSt 73 bar*m/s, Pmax 6.05 BARG

314 FT

48 FILTERS, Ø14" X 23" LONG

TO BE DETERMINED

R6094 DUST COLLECTOR

ATMOSPHERIC TO -5" WC

*REFERENCE FIKE EXPLOSION REPORT #11152375EXP

4" ASME, 6" ASME HRD'S AND DOT SRD CONTAINER DETAIL

4" ASME HRD CONTAINER AND SPREADER NOZZLE ASSEMBLY

4" ASME HRD CONTAINER AND NO NOZZLE ASSEMBLY

SCALE

DWG NO.

SHEET OF

REV

TITLE

EXPLOSION PROTECTION SYSTEM

DESCRIPTION

CHKD

DRN DATE

DATE SYSD2

SYSD1 DATE

DATE

PURCHASED BY: INSTALLED AT:

DIN RAIL TO BE CENTERED

HORIZONTALLY IN PANEL

24"

24"

BACKING PLATE

ENCLOSURE

FIKE FIELD WIRE

ENTRANCE

PREFERRED

BREATHER (TYP.)

FIKE FIELD WIRE

ENTRANCE

ALTERNATE

SHUTDOWNS/INTERLOCKS

ENTRANCE

PREFERRED

AC INPUT

ENTRANCE

PREFERRED

SYSTEM 8 R6094 - BUILDING 57

FIKE PROTECTION SYSTEMS EQUIPMENT SHALL BE USED. THE SYSTEM SHALL BE FURNISHED,

INSTALLED AND TESTED BY THE AUTHORIZED FIKE PROTECTION SYSTEMS DISTRIBUTOR:

(DIRECT) 610.295.5852

SUPPRESSION SYSTEMS, INC.

(PHONE) 800.360.0687

EXPLOSION SALES MANAGER: RICK SEIDEL

THE INFORMATION ON THESE DRAWINGS REFLECTS THE DESIGN OF THE EXPLOSION PROTECTION

SYSTEM PROPOSED BY SUPPRESSION SYSTEMS INC., FINAL COMMISSIONING OF THIS SYSTEM

WILL NOT OCCUR WITHOUT THESE DRAWINGS BEING APPROVED BY THE CUSTOMER / CUSTOMER

REPRESENTATIVE.

SCALE

DWG NO.

SHEET OF

REV

TITLE

EXPLOSION PROTECTION SYSTEM

DESCRIPTION

CHKD

DRN DATE

DATE SYSD2

SYSD1 DATE

DATE

PURCHASED BY: INSTALLED AT:

SYSTEM 8 R6094 - BUILDING 57

FIKE PROTECTION SYSTEMS EQUIPMENT SHALL BE USED. THE SYSTEM SHALL BE FURNISHED,

INSTALLED AND TESTED BY THE AUTHORIZED FIKE PROTECTION SYSTEMS DISTRIBUTOR:

(DIRECT) 610.295.5852

SUPPRESSION SYSTEMS, INC.

(PHONE) 800.360.0687

EXPLOSION SALES MANAGER: RICK SEIDEL

THE INFORMATION ON THESE DRAWINGS REFLECTS THE DESIGN OF THE EXPLOSION PROTECTION

SYSTEM PROPOSED BY SUPPRESSION SYSTEMS INC., FINAL COMMISSIONING OF THIS SYSTEM

WILL NOT OCCUR WITHOUT THESE DRAWINGS BEING APPROVED BY THE CUSTOMER / CUSTOMER

SCALE

DWG NO.

SHEET OF

REV

TITLE

EXPLOSION PROTECTION SYSTEM

DESCRIPTION

CHKD

DRN DATE

DATE SYSD2

SYSD1 DATE

DATE

PURCHASED BY: INSTALLED AT:

DESCRIPTIONQTYITEM PART NUMBER

GENERAL NOTES:

1. PROPER OPERATION OF THIS SYSTEM IS DEPENDENT UPON THE LOCATION OF ALL SYSTEM

COMPONENTS IN ACCORDANCE WITH THIS DRAWING.

2. ANY MODIFICATION TO THE PROPOSED INSTALLATION MUST BE COMMUNICATED TO AND

APPROVED BY SSI IN WRITING, PRIOR TO INSTALLATION. ANY CHANGES MUST BE

RECORDED AS A SSI REVISED DRAWING.

3. FOR FIELD WIRING AND SPECIFIC WIRE CONNECTIONS, CONSULT SSI SHEET 7C.

4. FOR INSTALLATION STANDARDS, GENERAL INFORMATION AND SAFETY REQUIREMENTS,

REFER TO THE FOLLOWING: ANSI B31.1 - PIPING AND FITTINGS, ANSI B16.5 - FLANGES, NFPA

69, NFPA 72, FIKE SPECIFICATION E06-018 - EXPLOSION SUPPRESSION CONTAINERS

INSTALLATION AND OPERATING INSTRUCTIONS AND FIKE MOUNTING DETAILS.

5. IN THE EVENT THAT ANY DESIGN PARAMETERS CHANGE, A SYSTEM PERFORMANCE REVIEW

SHALL BE CONDUCTED BY FIKE TO DETERMINE THE EFFECT, IF ANY, OF SUCH CHANGES ON

SYSTEM PERFORMANCE.

MECHANICAL NOTES:

1. DO NOT INSTALL GAS CARTRIDGE ACTUATORS (GCA'S) UNTIL SYSTEM HAS BEEN FULLY

TESTED BY A FIKE SYSTEM TECHNICIAN OR OTHER QUALIFIED PERSONNEL. GCA'S MUST

BE HANDLED IN ACCORDANCE WITH FIKE MANUALS E06-017, E06-018 AND THE

MANUFACTURER'S RECOMMENDATIONS.

2. ALL CONDUIT AND FITTINGS FOR FIKE SYSTEM MUST BE WEATHER TIGHT.

3. WHEN ASSEMBLING, SEAL ALL PROCESS PRESSURE THREADS WITH TFE TAPE OR EQUAL.

4. THE 4" STANDARD NOZZLE ASSEMBLY IS SUPPLIED WITH

(8) STUDS, 3/4"-10 UNC-2A X 6" LONG AND (8) NUTS, 3/4"-10 UNC-2B.

5. THE SUPPRESSANT CONTAINER SHALL BE FACTORY FILLED WITH FIKE POWDER AGENT

AND PRESSURIZED WITH DRY NITROGEN AT THE JOB SITE, BY FIKE SYSTEM TECHNICIAN OR

OTHER QUALIFIED PERSONNEL.

6. WHEN RECHARGING THE SUPPRESSANT CONTAINER, THE FOLLOWING COMPONENTS ARE

REQUIRED.

ITEMS NOT SHOWN ON DRAWING: ITEM NO. 1. LOCATION TO BE DETERMINED BY OTHER THAN SSI.

LOCATE CONTROL MODULES, IN AN ELECTRICALLY CLASSIFIED NON-HAZARDOUS LOCATION.

TEMPERATURE RANGE 0° F TO 110° F. REFERENCE FIKE SPECIFICATION E06-051, E06-052 , E06-053, E06-054, E06-061 & E06-018 FOR FURTHER DETAILS.

LOCATE CAUTION SIGNS, NEAR PROCESS ACCESS DOORS AND AREAS OF FREQUENT

MAINTENANCE.

29945022-C-S

E02-0081 CAUTION SIGN

CERAMIC PRESSURE DETECTOR

RIGID MOUNT FOR CERAMIC DETECTOR

02-4134

GAS CARTRIDGE ACTUATOR (GCA)

DETECTION SET PRESSURE 1.0 PSIG

MIN. STATIC WARNING -2.0 PSIG

MAX. STATIC WARNING 0.5 PSIG

DETECTION PROGRAMMING

E70-030-SBC 20 LITER HRD CONTAINER w/ 42 LB. SBC3

E10-0066 EXPLOSION PROTECTION CONTROLLER (EPC)

E10-0067 POWER SUPPLY (PSU)

E10-0068 ANNUNCIATOR MODULE (AM)

E10-0083-1 BATTERY KIT, 12V, 33AH

E10-0111 ENCLOSURE BREATHER DRAIN KIT, BRASS

02-10644 TRANSFORMER, 120/240V

10-2557 DIN RAIL KIT, 20"

10-2457 820 ohm EOL RESISTOR

10-2459 2.4V ZENER DIODE SERIES CONTACT DEVICE

* INCLUDES GCA.TO REORDER GCA USE FIKE PART NO. 02-4134.

E70-063 6 LOCKOUT, HRD ASSEMBLY - 4", w/SENSOR

E10-0105 DISABLE POWER SWITCH1

CONTAINER

SIZE

RELOAD

KITS/PART

NOZZLE

COVER

AGENT

AGENT

WEIGHT

NITROGEN CHARGE

PRESSURE @ 70°F

2.5 LITER E85-005 E80-0172-5 E85-038-2.5 SBC 5 LBS. 900 PSIG

20 LITER E85-005 E80-0172-5 E85-038-20 SBC 42 LBS. 900 PSIG

20 LITER E85-029 E80-0060-2 E85-038-20 SBC 42 LBS. 900 PSIG

VOLUME TOTAL

EXPLOSION HAZARD

EQUIPMENT DESIGN PRESSURE

VOLUME DIRTY (LESS FILTERS)

FILTERS

PROCESS OPERATING PRESSURE

PROCESS TEMPERATURE

AMBIENT TEMPERATURE

170°F MAX

70°F MAX

SUPPRESSANT CONCENTRATION

6.4 LBS / m

PROCESS OPERATING PARAMETERS

551.6 FT

*QUICK STRIP PLASTIC ABRASIVE

KSt 73 bar*m/s, Pmax 6.05 BARG

314 FT

48 FILTERS, Ø14" X 23" LONG

TO BE DETERMINED

R6185 DUST COLLECTOR

E61-063-1

E80-025-2

E02-0172-5

E70-0064-1

SPREADER NOZZLE COVER NEOPRENE - 4"

SPREADER NOZZLE BOLTING PAD, CS-4"

SPREADER NOZZLE ASSEMBLY w/LOCKOUT

02-9073 VERTICAL MOUNT TRI-CLOVER FERRULE

SURGE PROTECTION DEVICE

ENCLOSURE, 24x24x8 NEMA 4 CS ENCLOSURE

SYSTEM 7 R6185 - BUILDING 37

SYSTEM DESIGN NOTES:

THE FIKE SYSTEM IS DESIGNED AND INTENDED TO LIMIT PRESSURE DEVELOPED BY THE

HEAT OF COMBUSTION AND CHEMICALLY BLOCK PROPAGATION PATHWAYS IN THE EVENT OF

AN EXPLOSION (DEFLAGRATION) WITHIN THE PROTECTED VOLUME. DURING SYSTEM

ACTIVATION, A MOMENTARY PRESSURE EXCURSION WITHIN THE DUST COLLECTOR VOLUME

NOT EXCEEDING 4.3 PSIG CAN BE EXPECTED. THIS VALUE IS A MAXIMUM PREDICTED

IMPULSE PRESSURE BASED UPON TOTALLY ENCLOSED VOLUMES AND WILL BE LOWER DUE

TO PRESSURE EQUALIZATION THROUGH OPEN INLET/OUTLET DUCTS AS WELL AS ANY OTHER

PRESSURE RELIEF PATHS SUCH AS EXPLOSION VENTS. ENCLOSURES NOT CAPABLE OF

WITHSTANDING PREDICTED PRESSURES SHOULD BE REINFORCED OR FITTED WITH

SUFFICIENT EXPLOSION VENT AREA RELEASING TO A SAFE AREA.

THE SUPPRESSION SYSTEMS DEFINED WITHIN THESE DRAWINGS HAVE BEEN DESIGNED

BASED ON PROCESS OPERATING PARAMETERS AS DEFINED BY CUSTOMER. FIKE ACCEPTS

NO RESPONSIBILITY AS TO THE AUTHENTICITY OR ACCURACY OF THIS SUPPLIED

INFORMATION. NOR DOES FIKE ACCEPT ANY RESPONSIBILITY FOR ANY DAMAGE RESULTING

FROM THE APPLICATION OF THE SUPPLIED INFORMATION. IT MUST BE UNDERSTOOD THAT

EACH SUPPRESSION SYSTEM IS SPECIFICALLY ENGINEERED FOR APPLICATION TO THE

RESPECTIVE PROCESS ENCLOSURE AND FUEL FOR WHICH IT WAS ORIGINALLY DESIGNED.

ANY ATTEMPT TO ALTER, CHANGE OR REAPPLY THIS SYSTEM OR FAILURE TO ADHERE TO A

FIKE FACTORY RECOMMENDED MAINTENANCE SCHEDULE COULD RESULT IN SYSTEM

MALFUNCTION AND/OR PERSONAL INJURY.

INSTALLATION NOTES:

1. DUCT MOUNTED COMPONENT LOCATION DIMENSIONS ARE FROM DUCT CENTERLINE.

2. ANY INTERCONNECTED DUCTS, (LOCATED BETWEEN THE DUST COLLECTOR AND THE

HRD), NOT ILLUSTRATED IN THIS DRAWING WILL BE UNPROTECTED WITH THIS SYSTEM.

ANY DUCTS NOT SHOWN ON THIS DRAWING WILL BE UNPROTECTED WITH THIS SYSTEM.

3. HRD SHALL NOT BE INSTALLED CLOSER THAN 1 PIPE DIAMETER TO UPSTREAM

BRANCHES.

4. FIKE CONTROL PANEL MUST BE DISARMED WHEN LOADING, UNLOADING, OR

PERFORMING MAINTENANCE ON PROTECTED EQUIPMENT.

5. DETECTORS EXPOSED TO TEMPERATURE BELOW 0° C (32° F) MUST BE HEATED OR

INSULATED, BY CUSTOMER.

6. DO NOT OPEN PROCESS ACCESS AREAS UNLESS THE FIKE SYSTEM IS DISABLED.

7. FIKE EQUIPMENT MUST NOT BE COVERED BY PRODUCT.

02-14426

E70-0048 LOW PRESSURE SWITCH - HRD6

E70-027-SBC 2.5 LITER HRD CONTAINER w/ 5 LB. SBC3

ATMOSPHERIC TO -5" WC

E80-029-2

E80-0060-2

E80-0065-1

HYGIENIC NOZZLE COVER SST - 4"

HYGIENIC NOZZLE BOLTING PAD, SST-4"

HYGIENIC NO NOZZLE ASSEMBLY

FIKE PROTECTION SYSTEMS EQUIPMENT SHALL BE USED. THE SYSTEM SHALL BE FURNISHED,

INSTALLED AND TESTED BY THE AUTHORIZED FIKE PROTECTION SYSTEMS DISTRIBUTOR:

(DIRECT) 610.295.5852

SUPPRESSION SYSTEMS, INC.

(PHONE) 800.360.0687

EXPLOSION SALES MANAGER: RICK SEIDEL

THE INFORMATION ON THESE DRAWINGS REFLECTS THE DESIGN OF THE EXPLOSION PROTECTION

SYSTEM PROPOSED BY SUPPRESSION SYSTEMS INC., FINAL COMMISSIONING OF THIS SYSTEM

WILL NOT OCCUR WITHOUT THESE DRAWINGS BEING APPROVED BY THE CUSTOMER / CUSTOMER

REPRESENTATIVE.

*REFERENCE FIKE EXPLOSION REPORT #11152375EXP

4" ASME, 6" ASME HRD'S AND DOT SRD CONTAINER DETAIL

4" ASME HRD CONTAINER AND SPREADER NOZZLE ASSEMBLY

4" ASME HRD CONTAINER AND NO NOZZLE ASSEMBLY

SCALE

DWG NO.

SHEET OF

REV

TITLE

EXPLOSION PROTECTION SYSTEM

DESCRIPTION

CHKD

DRN DATE

DATE SYSD2

SYSD1 DATE

DATE

PURCHASED BY: INSTALLED AT:

DIN RAIL TO BE CENTERED

HORIZONTALLY IN PANEL

24"

24"

BACKING PLATE

ENCLOSURE

FIKE FIELD WIRE

ENTRANCE

PREFERRED

BREATHER (TYP.)

FIKE FIELD WIRE

ENTRANCE

ALTERNATE

SHUTDOWNS/INTERLOCKS

ENTRANCE

PREFERRED

AC INPUT

ENTRANCE

PREFERRED

SYSTEM 7 R6185 - BUILDING 37

FIKE PROTECTION SYSTEMS EQUIPMENT SHALL BE USED. THE SYSTEM SHALL BE FURNISHED,

INSTALLED AND TESTED BY THE AUTHORIZED FIKE PROTECTION SYSTEMS DISTRIBUTOR:

(DIRECT) 610.295.5852

SUPPRESSION SYSTEMS, INC.

(PHONE) 800.360.0687

EXPLOSION SALES MANAGER: RICK SEIDEL

THE INFORMATION ON THESE DRAWINGS REFLECTS THE DESIGN OF THE EXPLOSION PROTECTION

SYSTEM PROPOSED BY SUPPRESSION SYSTEMS INC., FINAL COMMISSIONING OF THIS SYSTEM

WILL NOT OCCUR WITHOUT THESE DRAWINGS BEING APPROVED BY THE CUSTOMER / CUSTOMER

SCALE

DWG NO.

SHEET OF

REV

TITLE

EXPLOSION PROTECTION SYSTEM

DESCRIPTION

CHKD

DRN DATE

DATE SYSD2

SYSD1 DATE

DATE

PURCHASED BY: INSTALLED AT:

SYSTEM 7 R6185 - BUILDING 37

FIKE PROTECTION SYSTEMS EQUIPMENT SHALL BE USED. THE SYSTEM SHALL BE FURNISHED,

INSTALLED AND TESTED BY THE AUTHORIZED FIKE PROTECTION SYSTEMS DISTRIBUTOR:

(DIRECT) 610.295.5852

SUPPRESSION SYSTEMS, INC.

(PHONE) 800.360.0687

EXPLOSION SALES MANAGER: RICK SEIDEL

THE INFORMATION ON THESE DRAWINGS REFLECTS THE DESIGN OF THE EXPLOSION PROTECTION

SYSTEM PROPOSED BY SUPPRESSION SYSTEMS INC., FINAL COMMISSIONING OF THIS SYSTEM

WILL NOT OCCUR WITHOUT THESE DRAWINGS BEING APPROVED BY THE CUSTOMER / CUSTOMER

SCALE

DWG NO.

SHEET OF

REV

TITLE

EXPLOSION PROTECTION SYSTEM

DESCRIPTION

CHKD

DRN DATE

DATE SYSD2

SYSD1 DATE

DATE

PURCHASED BY: INSTALLED AT:

DESCRIPTIONQTYITEM PART NUMBER

GENERAL NOTES:

1. PROPER OPERATION OF THIS SYSTEM IS DEPENDENT UPON THE LOCATION OF ALL SYSTEM

COMPONENTS IN ACCORDANCE WITH THIS DRAWING.

2. ANY MODIFICATION TO THE PROPOSED INSTALLATION MUST BE COMMUNICATED TO AND

APPROVED BY SSI IN WRITING, PRIOR TO INSTALLATION. ANY CHANGES MUST BE

RECORDED AS A SSI REVISED DRAWING.

3. FOR FIELD WIRING AND SPECIFIC WIRE CONNECTIONS, CONSULT SSI SHEET 11C.

4. FOR INSTALLATION STANDARDS, GENERAL INFORMATION AND SAFETY REQUIREMENTS,

REFER TO THE FOLLOWING: ANSI B31.1 - PIPING AND FITTINGS, ANSI B16.5 - FLANGES, NFPA

69, NFPA 72, FIKE SPECIFICATION E06-018 - EXPLOSION SUPPRESSION CONTAINERS

INSTALLATION AND OPERATING INSTRUCTIONS AND FIKE MOUNTING DETAILS.

5. IN THE EVENT THAT ANY DESIGN PARAMETERS CHANGE, A SYSTEM PERFORMANCE REVIEW

SHALL BE CONDUCTED BY FIKE TO DETERMINE THE EFFECT, IF ANY, OF SUCH CHANGES ON

SYSTEM PERFORMANCE.

MECHANICAL NOTES:

1. DO NOT INSTALL GAS CARTRIDGE ACTUATORS (GCA'S) UNTIL SYSTEM HAS BEEN FULLY

TESTED BY A FIKE SYSTEM TECHNICIAN OR OTHER QUALIFIED PERSONNEL. GCA'S MUST

BE HANDLED IN ACCORDANCE WITH FIKE MANUALS E06-017, E06-018 AND THE

MANUFACTURER'S RECOMMENDATIONS.

2. ALL CONDUIT AND FITTINGS FOR FIKE SYSTEM MUST BE WEATHER TIGHT.

3. WHEN ASSEMBLING, SEAL ALL PROCESS PRESSURE THREADS WITH TFE TAPE OR EQUAL.

4. THE 4" STANDARD NOZZLE ASSEMBLY IS SUPPLIED WITH

(8) STUDS, 3/4"-10 UNC-2A X 6" LONG AND (8) NUTS, 3/4"-10 UNC-2B.

5. THE SUPPRESSANT CONTAINER SHALL BE FACTORY FILLED WITH FIKE POWDER AGENT

AND PRESSURIZED WITH DRY NITROGEN AT THE JOB SITE, BY FIKE SYSTEM TECHNICIAN OR

OTHER QUALIFIED PERSONNEL.

6. WHEN RECHARGING THE SUPPRESSANT CONTAINER, THE FOLLOWING COMPONENTS ARE

REQUIRED.

ITEMS NOT SHOWN ON DRAWING: ITEM NO. 1. LOCATION TO BE DETERMINED BY OTHER THAN SSI.

LOCATE CONTROL MODULES, IN AN ELECTRICALLY CLASSIFIED NON-HAZARDOUS LOCATION.

TEMPERATURE RANGE 0° F TO 110° F. REFERENCE FIKE SPECIFICATION E06-051, E06-052 , E06-053, E06-054, E06-061 & E06-018 FOR FURTHER DETAILS.

LOCATE CAUTION SIGNS, NEAR PROCESS ACCESS DOORS AND AREAS OF FREQUENT

MAINTENANCE.

29945022-C-S

E02-0081 CAUTION SIGN

CERAMIC PRESSURE DETECTOR

RIGID MOUNT FOR CERAMIC DETECTOR

02-4134

GAS CARTRIDGE ACTUATOR (GCA)

DETECTION SET PRESSURE 1.0 PSIG

MIN. STATIC WARNING -2.0 PSIG

MAX. STATIC WARNING 0.5 PSIG

DETECTION PROGRAMMING

E70-030-SBC 20 LITER HRD CONTAINER w/ 42 LB. SBC1

E10-0066 EXPLOSION PROTECTION CONTROLLER (EPC)

E10-0067 POWER SUPPLY (PSU)

E10-0068 ANNUNCIATOR MODULE (AM)

E10-0083-1 BATTERY KIT, 12V, 33AH

E10-0111 ENCLOSURE BREATHER DRAIN KIT, BRASS

02-10644 TRANSFORMER, 120/240V

10-2557…