WSTI Questions and Answers.pdf
PDF 62 KB Posted
- Attached to
- THERMAL SECURITY CAMERA
- Solicitation number
- W50S8R-20-R-0022
View the file
Other files
| File | Type | Posted |
|---|---|---|
| WSTI Questions and Answers Rev 1.pdf | ||
| Attachment 02 Statement of Requirement_REV 1.pdf | ||
| Attachment 03 Line Items Listing.xlsx | XLSX spreadsheet | |
| Attachment 01 - Provisions and Clauses.pdf | ||
| Attachment 02 Statement of Requirement.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WSTI Questions and Answers:
Q1. What type and size of conduit for the hangar roof?
A1. Size of conduit to be per NEC based off wire size required to operate camera. Conduit to be rigid or intermediate conduit listed for exterior installation. May use liquid tight flexible to make for a maximum of 10 ft to make final connection to camera.
Q2. Are PVC, UL rated conduit/connectors acceptable?
A2. Yes. As long as they are rated for exterior installation.
Q3. What are the requirements for fastening the conduit to the hangar roof?
A3. No penetrations. Mount conduit on rubber base with internal strut to allow conduit to be fastened to block.
Q4. What are the requirements for the grounding of the conduit?
A4. Grounded per NEC requirements.
Q5. We want to confirm that we only need single mode fiber patch cables with SC APC connectors for building 422 and 164. We did not go into all buildings and need to confirm the length of fiber patch cables.
A5. Task Cable directly plug in, run through BLDG#'s 422-164 to 300, use same model we have in place which is standard. (no old cables are reusable).
Q6. Statement of requirement 3.1.3 states that the contractor will furnish a desktop server and purchase a milestone camera license.
A6 We will use the Pelco for the “desktop”, the milestone does need purchased.
Q7. Is the existing system Milestone, or will we need to install Milestone on the server?
A7. The Pelco Control Point Software and yes
Q8. If the requirement is a new server, please provide specifications needed for the server.
A8. Independent, scalable, recording capable able to be moved and integrated into the new firehouse when building is finished.
Q9. What type of cabling is installed for the current camera?
A9. Multi mode jumper Optic
Q10. What is the datacom that is in place (i.e. Ethernet, fiber-optic, etc.)?
A10. Proprietary/Fiber Optic Multi Mode
Q11. Is there a power source for the camera at the site of installation (i.e. standard 120v outlet)?
A11. Yes, 120V standard power source
Q12. What is the height of the Hangar?
A12. 37FT to Thermal Camera Location.
Q13. What field of view is desired?
A13. FOV-for Thermal Camera:24degrees(H) to 6degrees(H)
FOV-for Visable Camera:63.7 wide,to 2.3 tele
Q14. What does BDOC stand for?
A14. Base Defense Operations Center
Q15. What does remote refer to? Camera can be controlled/viewed anywhere on your intranet by pulling up the webpage on the camera or do you want a NVR/VMS connection with a joystick?
A15. joystick with NVR/VMS will be needed for security reasons, being able to pull up the page on the internet is a unnecessary risk.
File details come from the government source that posted it. Updated .