RFI-Chiller Replacement
| 1. Air cooled or water cooled chiller? | Air Cooled | ||
| 2. Photos of existing unit | Added to solicitation | ||
| 3. Is the chiller closely accessible for a crane to remove and set | Yes |
the new unit.
| 4. Is the existing chiller a 30 or 40 ton chiller? | 40 Ton | ||
| 5. What is the voltage of the chiller? | See Data Plate Pic | ||
| 6. What is the ampacity of the existing breaker, disconnect, and wiring? | See Data Plate Pic |
7. Will the existing circuit handle the electrical load for the new 40 ton chiller? If the existing electrical is not sufficient for the new chiller, is the contractor responsible for replacing Yes electrical service to the new unit?
8. Please clarify the P O P of 30 days. Is this 30 days after the arrival of the chiller? Delivery of the chiller could be approx 4 to 6 weeks
| depending on factory availability, after approved submittals? | POP is 30 days from award | |
| 9. Can you provide a photo of the existing Trane NamePlate | Photo added |
which will show Make, Model, etc?