TYS RTR Construction Drawings.pdf
PDF 2 MB Posted
- Attached to
- Tower Replacement Knoxville TN Federal contract opportunity
- Solicitation number
- 6973GH-21-R-00037
About this file
This solicitation seeks proposals for a tower replacement project located in Knoxville, Tennessee. The Federal Aviation Administration requires all labor, materials, equipment, transportation, insurance, notifications, licenses, permits, fees, and supervision to remove four existing guyed antenna towers and replace them with three new 90-foot free standing towers including installation of new fiberglass junction boxes, conduits, cabling, and grounding systems. Interested contractors must be registered in the System for Award Management and submit all required forms by January 18, 2021 to be eligible for consideration. The FAA will award a firm-fixed-price construction contract and anticipates holding a pre-bid site visit. All questions must be submitted in writing by January 8th.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Knoxville Amendment 0002.pdf | ||
| Blount County WD.pdf | ||
| Knoxville QA II.pdf | ||
| Knoxville RTR Questions Answers (002).pdf | ||
| Knoxville Amendment 0001.pdf | ||
| Trench Detail.pdf | ||
| RCF TOWER 8 Mount.pdf | ||
| Contractor Release Form.doc | DOC document | |
| Payment Bond.pdf | ||
| 6973GH-21-R-00037.pdf | ||
| Knox County WD.pdf | ||
| TYS RTR Specs.pdf | ||
| Performance Bond.pdf | ||
| Experience Information Form.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
P ty s -1
-c
.d g n
/0
/2
:1
:2
M lo tt e d b y S
R V
C -C
A E
G -E
D
O
B
F
H
8 7 6 5 4 3 2 1
12345678
REVDRAWING NO
DATE JCN
APPROVED BY
ISSUED BY
CHECKED
DRAWN
DESIGNED
SUBMITTED BY
REVIEWED BY
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV
DATE
APPROVED
DESCRIPTION JCN
REDLINE
APVD
NOT TO SCALE
C001
N
°3 8'
"E
.9
°3
.0
S67°61' 17"E, 170.08'
°0
W
N81°01' 12"W, 165.98'
°2
"W
IR
BA
SE
RD
CALLAHAN
IG
T S
Y
L
Y
S
LD
N T O R
LOCATION MAP
PARKING AREA
GRAVEL
TERMINAL POLE
OVERHEAD SERVICE BY
BLOUNT ELECTRIC CO.
P.O.B.(EXISTING
CONCRETE MARKER)
FUEL TANK
#4/0 AWG BARE STRANDED
COPPER COUNTERPOISE
(TYP FOR ALL 4 TOWERS)
16' WIDE x 6" DEEP
GRAVEL ACCESS ROAD
90' GUYED TOWER 3
90' GUYED
TOWER 2
90' GUYED TOWER 4
90' GUYED TOWER 1
CONCRETE MARKER
N36°21' 17"W, 5.0'
FENCE
IRON PIN
CALL
AHAN
GROUND ROD
RT
EQUIP.
RM.
GUY ANCHOR (TYP)
7-RG-333/U
1#6
BSDC D.E.B.
20' 40'020'
SCALE: 1" = 20'
TYS RTR
IS
U
TN
RC
MB 06/11/2020 1704443
TYS-1704443-C001
IO
ENGINEERING SERVICES
COMMUNICATIONS
RTR
MC GHEE TYSON AIRPORTKNOXVILLE
PROJECT ENGINEER MGR: ENGINEERING - CENTER A
THIS DRAWING PRODUCED ON ASO REGION MICROSTATION SYSTEM
ATO - TECHNICAL OPERATIONS EASTERN SERVICE AREA
1-#6 BSDC
1-100 PR. #19A
1-100 PR. #19A,
3#2 THW, 1#6 GND,
IN 2" RIDGED CONDUIT
17'-6" WIDE DOUBLE LEAF
GATE IN EXISTING FENCE
EXISTING PLOT LAYOUT
TOWER REPLACEMENT EXISTING PLOT LAYOUT
tys-1704443-c001
2020-09-21T09:32:03-0400
STACEY L RAINES
2020-09-10T14:35:44-0400
MICHAEL ALEXANDER BUFF
lo tt e
NOTES
C002
°3 8'
.9
°3
S67°61' 17"E, 170.08'
°0
N81°01' 12"W, 165.98'
°2
"W
PARKING AREA
GRAVEL
TERMINAL POLE
OVERHEAD SERVICE BY
BLOUNT ELECTRIC CO.
P.O.B.(EXISTING
CONCRETE MARKER)
FUEL TANK
3#2 THW, 1#6 GND,
IN 2" RIDIG CONDUIT
16' WIDE x 6" DEEP
GRAVEL ACCESS ROAD
EXIST TOWER TO
BE REMOVED
CONCRETE MARKER
IRON PIN
CALL
AHAN
RT
EQUIP.
RM.
GUY ANCHOR (TYP)
20' 40'020'
SCALE: 1" = 20'
NEW 90' ANTENNA
TOWER 1
TOWER 2
TOWER 3
2 EACH 4" O PVC
WITH 17 EACH 1/2"
HELIAX CABLES
2 EACH 4" O PVC
WITH 17 EACH 1/2"
HELIAX CABLES
MB 06/11/2020
TYS-1704443-C002
MC GHEE TYSON AIRPORT
1704443
KNOXVILLE
PLOT LAYOUT AND NEW TOWERS
TOWER REPLACEMENT
N36°21' 17"W, 5.0'
INSTALL 30"x 24"x 10" GFM
FIBERGLASS BOX WITH
5'x 5'x 6" CONCRETE PAD
17'-6" WIDE DOUBLE LEAF
GATE IN EXISTING FENCE
PLOT LAYOUT
INSTALL 30"x 24"x 10" GFM
FIBERGLASS BOX WITH
5'x 5'x 6" CONCRETE PAD
GRAVEL OVER THE DISTURBED CONSTRUCTION AREA.
STONE OR EQUAL TO RE-ESTABLISH A MINIMUM OF THREE INCHES OF
EXPECTED TO FURNISH AND INSTALL A MAXIMUM OF 30 TONS OF #57
UNDERGROUND WORK IS COMPLETED. THE CONTRACTOR WILL BE
AROUND THE AREA OF CONSTRUCTION AND RESPREAD AFTER ALL
6. THE CONTRACTOR MUST REMOVE AND SALVAGE THE GRAVEL IN AND
WITH FLOOR AND SEAL OPENING WITH GROUT OR EQUAL.
BUILDING, REMOVE CABLES FROM BUILDING, CUT CONDUITS OFF FLUSH
OPERATION CONTRACTOR MUST UNCOVER RF CABLES OUTSIDE
THE THREE NEW TOWERS ARE IN OPERATION. AFTER NEW TOWERS ARE IN
ABANDONED IN PLACE. THIS WORK CAN ONLY BE ACCOMPLISHED AFTER
CABLES AND CONDUITS MUST BE CUT OFF ONE FOOT BELOW GRADE AND
TOWERS INCLUDING THE THREE GUY ANCHORS PER TOWER.
5. CONTRACTOR MUST REMOVE THE EXISTING FOUR GUYED ANTENNA
TYS-1704443-E001, E002 & E003 FOR DETAILS.
BOX AT THE TOP OF ANTENNA TOWER 1. SEE DRAWING
ON SOUTH WALL OF EXISTING BUILDING AND THE FIBERGLASS JUNCTION
CABLE (GFM) BETWEEN THE FIBERGLASS JUNCTION BOX (GFM) INSTALLED
TOP OF ANTENNA TOWERS 2 & 3. INSTALL 17 RUNS OF 1/2" HELIAX
EXISTING BUILDING AND THE FIBERGLASS JUNCTION BOX AT THE
FIBERGLASS JUNCTION BOXES (GFM) INSTALLED ON SOUTH WALL OF
4. INSTALL 17 RUNS OF 1/2" HELIAX CABLE (GFM) BETWEEN THE
PRIOR TO CONSTRUCTION.
TOWERS. THE CONTRACTOR SHALL LOCATE UNDERGROUND UTILITIES
UTILITIES WHEN INSTALLING THE CABLE DUCTBANK FOR THE ANTENNA
THE CONTRACTOR IS EXPECTED TO ENCOUNTER UNDERGROUND
THE BUILDING COUNTERPOISE WHICH SHOULD BE 24" BELOW GRADE.
GRADE. THE CONTRACTOR IS EXPECTED TO HAND DIG UNTIL CLEAR OF
THE PVC DUCTBANK. THE PVC MUST BE INSTALLED 24" BELOW FINISHED
THE BUILDING OUT APPROXIMATELY 10 FEET FOR THE INSTALLATION OF
3. CONTRACTOR MUST EXPECT TO HAND DIG FROM JUNCTION BOX ON
JUNCTION BOX 2'-6" ABOVE FINISH GRADE TO BOTTOM OF BOX.
BUILDING ON SOUTH WALL TO THE CENTER OF THE BOX. INSTALL THE
JUNCTION BOX. APPROXIMATELY 6'-0" FROM EAST END OF THE
TO BOTTOM OF BOX. INSTALL ONE GFM 30"x 24"x 10" FIBERGLASS
OF THE BOX. INSTALL THE JUNCTION BOX 2'-6" ABOVE FINISH GRADE
FROM WEST END OF THE BUILDING ON SOUTH WALL TO THE CENTER
GFM 30"x 24"x 10" FIBERGLASS JUNCTION BOX APPROXIMATELY 2'-6"
BOX 2'-6" ABOVE FINISH GRADE TO BOTTOM OF BOX. INSTALL ONE
WEST WALL TO THE CENTER OF THE BOX. INSTALL THE JUNCTION
APPROXIMATELY 2'-6" FROM SOUTH END OF THE BUILDING ON
2. INSTALL ONE GFM 30"x 24"x 10" FIBERGLASS JUNCTION BOX
SOUTH AND WEST WALLS OF THE EXISTING BUILDING.
WHILE HAND DIGGING FROM THE NEW JUNCTION BOXES INSTALLED ON THE
COUNTERPOISE. THE BUILDING COUNTERPOISE MUST BE UNCOVERED
CONNECTED INTO THE EXISTING 4/0 BARE COPPER BUILDING
THE NEW COUNTERPOISE FOR ANTENNA TOWER'S MUST BE
WORK IN ACCORDANCE WITH DETAILS SHOWN ON OTHER DRAWINGS.
AND FIBERGLASS JUNCTION BOX. CONTRACTOR MUST PERFORM ALL
ANTENNA MOUNTS, SAFETY RAIL, LIGHTNING PROTECTION, CABLING
FREE STANDING ANTENNA SUPPORT TOWER COMPLETE, INCLUDING
1. INSTALL THREE 90 FEET
tys-1704443-c002
2020-09-21T09:32:48-0400
STACEY L RAINES
2020-09-10T14:37:21-0400
MICHAEL ALEXANDER BUFF
2 1/4"
6'-8"
1 1/4"
1'-6"
12"
1 3/4" EACH
RELIEF AT
17 STRAIN
-e
:3 lo tt e
4" PVC CONDUIT
TO JUNCTION BOX
ON BUILDING
1 1/4" PVC FOR GROUND
INTO JUNCTION BOX
1 1/4" PVC FOR GROUND
INTO JUNCTION BOX
INTERMEDIATE CONDUIT SUPPORT
BEAM CLAMP
AND STRUT
SS CLAMPS
JUNCTION BOX ELEVATION1
E001
TOWER CONDUIT ELEVATION
NON SHRINK GROUT
BOX
STAHLIN
ON FABRIC
3" GRAVEL
2 EA - 4" DIA PVC
TO RTR SHELTER
4/0 GROUND
1 1/4" PVC FOR
TOWER WITH BEAM CLAMPS
1 5/8"x 1 5/8" ATTACH TO
STAINLESS STEEL UNISTRUT
SCHEDULE 40 PVC
4" NOMINAL
2 JUNCTION BOX ELEVATION
PLATFORM JUNCTION BOX HOLE LAYOUT6
STRAIN RELIEF FOR
GROUND CABLE
(TYP OF 2)
TOWER LEG
OPPOSING SIDES
(2) EACH TYPICALLY
COUNTERPOISE
TO GROUND ROD
WITH 4/0 BARE
1 1/4" PVC
(2) EACH
TO GROUND ROD
SCHED 80
INSIDE 1 1/4" PVC
4/0 BARE
4 TOWER CONDUIT SECTION
NOT TO SCALEE001
(TYPICAL OF 2 EACH)
4/0 GROUND
1 1/4" PVC FOR
SEE NOTE 3
JUNCTION BOX
INSTALLED FIBERGLASS
FROM EACH BOX
EVERY 10' -0" AND AT 3' -0"
SUPPORTED CONDUITS
SEE NOTE 2
JUNCTION BOX,
SEE NOTE 3
STAINLESS STEEL
UNISTRUT FRAME
TRANSITION FROM 1" PVC
TO 1" RGS. SUPPORT FROM
TOE BOARD, MID-RAIL, AND TOP RAIL
WITH SS UBOLTS AND HARDWARE
SEE NOTE 5
SEE NOTE 10
SUPPORTED EVERY 10'
CU THHN: (HOT, NEUTRAL, GROUND)
1" PVC FOR (3) #10 AWG
LIGHT SHALL BE CROUSE HINDS 12004-860-1R01-002 OR EQUAL.
11. THE CONTRACTOR SHALL INSTALL ONE OBSTRUCTION LIGHT ON EACH TOWER. THE OBSTRUCTION
#10 AWG FROM SHELTER TO TOP OF RGS (COLORS: RED, WHITE, GREEN).
SUPPORTED ON THE TOP RAIL, MID RAIL, AND TOE BOARD WITH SS U-BOLTS. PULL IN (3)
SUPPORTED EVERY 10'. TRANSITION FROM 1" PVC TO 1" RGS AT CAGE BASE. RGS IS
10. CONTRACTOR SHALL INSTALL 1" PVC FROM FOUNDATION TO BASE OF TOWER CAGE,
TO TOWER LEG ON OPPOSING LEGS.
9. FOR EACH TOWER INSTALL 2-#4/0 FROM COUNTERPOISE THROUGH 1 1/4" PVC AND CAD WELD
8. NOT USED
DETAIL 9/E001.
STAINLESS STEEL. INSTALL 17 EACH 1/2" HELIAX, ANDREW P/N LDF4-50A (GFM), SEE
UNISTRUT WITH STAINLESS STEEL PIPE CLAMPS. ALL MOUNTING HARDWARE SHALL BE
HORIZONTAL ANGLES MARK 9535. THE 2 EACH 4"O CONDUITS ARE THEN FASTENED TO THE
IN LENGTH TO THE ANTENNA TOWER AT THE PREFABRICATED ANTENNA TOWER
7. CONTRACTOR SHALL FURNISH AND INSTALL 1 5/8"x 1 5/8" STAINLESS STEEL UNISTRUT 36"
COLD GALVANIZED.
6. ALL CUT EDGES, CORNERS DRILLED HOLES AND OTHER ABRAIDED AREAS
THE THOMPSON 28R FROM THE TOWER LOOP.
5. CONTRACTOR SHALL INSTALL 2 EACH 3/4" DIA STRAIN RELIEF CONNECTOR (GFM) FOR
JUNCTION BOX.
(GFM) (T&B 2673) FOR CABLE INSTALLED BY OTHERS, IN THE BOTTOM OF THE TOP
4. CONTRACTOR SHALL INSTALL 17 EACH 3/4" DIA WATER TIGHT STRAIN RELIEF CONNECTORS
ENGINEER.
(P1000) FRAME AND STAINLESS STEEL BOLTS. VERIFY BOX LOCATION WITH FAA RESIDENT
(FIBER-GLASS, NEMA 4X, ATTACH TO TOWER USING A STAINLESS STEEL UNISTRUT
TOWER AND 30"x 24"x 10" JUNCTION BOX ON BOTTOM OF THE TOWER (GFM)
3. CONTRACTOR SHALL INSTALL A 36"x 30"x 10" JUNCTION BOX (GFM) ON TOP OF THE
UP TO JUNCTION BOX. ALL CUT EDGES MUST BE COLD GALVANIZED.
2. CUT SECTION OF EXPANDED METAL GRATING AS REQUIRED TO ROUTE CONDUITS
1. THE 1/2" HELIAX CABLE MUST NOT BE BENT CLOSER THAN A 5" RADIUS.
5 CONDUIT SUPPORT SECTION
TOWER DIAGONAL
SS LOCKWASHERS
AND NUTS
4" DIAMETER
PVC SCH 40
SS
PIPE CLAMP
SS UNISTRUT 1/2" DIAMETER
HELIAX CABLE
SEE DETAIL 9/E001
TYS-1704443-E001
1" RGS THREADED
FOR OBSTRUCTION
LIGHT. THE
OBSTRUCTION LIGHT
SHALL BE INSTALLED
2' ABOVE THE RAIL.
SEE NOTE 11.
TOWER CABLES SECTIONS AND DETAILS
1' 2'01'
SCALE: 1" = 1'-0"
SCALE: 3" = 1'-0"
9"6"3"3" 0 tys-1704443-e001
2020-09-21T09:33:19-0400
STACEY L RAINES
2020-09-10T14:38:05-0400
MICHAEL ALEXANDER BUFF
:5 lo tt e
CONDUIT, RIGID PLASTIC 3/4"
PIPE CLAMP, THOMPSON #240X OR EQUAL
CABLE CLAMP, THOMPSON #142 OR EQUAL
U-BOLT, 2" WITH SELF LOCKING NUTS, GALV
SEE NOTE 4
7 8
PARALLEL CLAMP, THOMPSON #4248 OR EQUAL
SET SCREW CLAMP, THOMPSON #701 OR EQUAL
GROUND ROD, COPPER CLAD 3/4" DIA x 10'
4 5
4 5
LEGEND
4/0 AWG BARE COPPER, 28 STRANDS, WT 660 LBS/1000 FT
STANDARD STEEL PIPE, GALV 2"x 21 FEET LONG (WATER PIPE)
AIR TERMINAL, 5/8"x 3', THOMPSON #667 OR EQUAL
VERTICAL CONNECTOR, THOMPSON #690 OR EQUAL10
L
IN
IN
E002
JUNCTION BOX SECTION
DOWN CONDUCTOR, 28 STRANDS,
WT 375 LBS/1000'. THOMPSON 28R OR EQUAL
ON BUILDING
TO JUNCTION BOX
4" PVC CONDUIT
4 TOWER CONDUIT SECTION
GROUNDING INTO
1 1/4" DIA PVC FOR
GROUNDING INTO
1 1/4" DIA PVC FOR
SEE DRAWING C002
TIE TO BUILDING
4/0
U-BOLTS
2" DIA SS
4TOWER LEGS
ON DIAGONAL
EACH INSTALLED
TYPICAL OF 2
JUNCTION BOX ELEVATION
J-BOX
FIBERGLASS
36"x 30"x 10"
AIR TERMINAL ASSEMBLY
CAP
PIPE
OR EQUAL
THOMPSON NO 690
ELECT CONNECTOR
E002 NOT TO SCALE
2 TOWER CONDUIT ELEVATION
NOT TO SCALEE002
STAHLIN
CORNERS
TYPICAL OPPOSITE
TO COUNTERPOISE
INSIDE JUNCTION BOX
LEAVE 3' COILED
IN 1 1/4" PVC
4/0 BARE
SEE NOTE 5
FIBERGLASS
30"x 24"x 10"
TOWER WITH BEAM CLAMPS
1 5/8"x 1 5/8" ATTACH TO
STAINLESS STEEL UNISTRUT
UNISTRUT FRAME
STAINLESS STEEL
GALV WATER PIPE
2"x 21'
7. 4/0 AWG JUMPER FROM THOMPSON 28R CADWELDED TO TOWER FRAME
6. ALL COUNTERPOISE IS PLACED 18-24" AWAY FROM CONCRETE FOUNDATIONS
EXOTHERMIC WELD.
EQUAL TO SECURE DOWN CONDUCTOR T0 4/0, A MINIMUM OF 6" BELOW THE
2 EACH,(TYPICALLY OPPOSING LEGS). USE PARALELL CLAMP THOMPSON #4248 OR
5. EXOTHERMIC WELD 4/0 AWG TO TOWER LEG A MINIMUM OF 18" ABOVE FOUNDATION,
4. INSTALLED JUNCTION BOX AT 90^ FROM HATCH OPENING DIRECTION.
3. ALL GROUNDING CONNECTIONS BELOW GRADE BY EXOTHERMIC WELD.
2. INSTALLED DOWN CONDUCTOR WITH AN MINIMUM OF BENDS.
REMAIN TIGHT BETWEEN CLAMPS
WITH THOMPSON CABLE CLAMP #142 OR APPROVED EQUAL. CONDUCTOR SHALL
AROUND THE PERIMETER OF THE PLATFORM, AND DOWN THE TOWER LEG
1. SUPPORTED THE DOWN CONDUCTOR AT A MINIMUM OF 2'-0" SPACING
INSIDE J-BOX
GROUNDBAR
CONNECTED TO
THOMPSON 28R
2 EACH
TYS-1704443-E002
MB
06/11/2020 1704443
X
ANTENNA TOWER LIGHTNIING PROTECTION
tys-1704443-e002
2020-09-21T09:33:59-0400
STACEY L RAINES
2020-09-10T14:38:48-0400
MICHAEL ALEXANDER BUFF
:0 lo tt e
NEW BULKHEAD
PLATE BY OTHERS
NEW FIBERGLASS J-BOX SEE
DWG TYS-1704443-E001 &
C002 FOR DETAILS AND
OTHER INFORMATION
NEW BULKHEAD
PLATE BY OTHERS
TYS-1704443-E003
E003
A/C
BULKHEAD PLATE
DEMARC
A/C
EMERGENCY SWITCH
EMERGENCY SWITCH
A/C CONTROL
FLOOR PLAN
FLOOR PLAN
02' 2' 6'4'
SCALE: 1" = 2'-0"
tys-1704443-e003
2020-09-21T09:34:30-0400
STACEY L RAINES
2020-09-10T14:39:28-0400
MICHAEL ALEXANDER BUFF
lo tt e
THE CURVE TO ITS ASYMPTOTIC VALUE.
E) THE TRUE VALUE OF RESISTANCE CAN BE ESTIMATED BY EXTRAPOLATING
POSITIONS AS NECESSARY TO DETERMINE WHERE THE CURVE LEVELS OFF.
RESISTANCE READINGS VERSUS THE CORRESPONDING C2 PROBE
D) PLOT ON A GRAPH SIMILAR TO FIG. 3 AS MANY RECORDED
POINTS TO ACCURATELY DETERMINE WHERE THE CURVE LEVELS OFF.
IT MAY NOT BE NECESSARY TO PLOT THE FULL 500'. PLOT ENOUGH
(NOTE THAT THE P2 POSITIONS ARE 62% OF THE C2 POSITIONS).
RECORD THE METER READINGS FOR EACH C2 & P2 PROBE POSITION.
C) POSITION THE C2 PROBE AT DISTANCES AS SHOWN IN FIG. 1.
THE C2 PROBE LINE SHALL RUN 90 DEGREES TO THE A.L.S.
FI. 1. KEEP C2 AND P2 LEADS SEPARATED AS FAR AS POSSIBLE.
AS FAR AS POSSIBLE FROM THESE METALS AS ILLUSTRATED IN
LOCATION OF ALL SUCH BURIED METALS. THEN LOCATE THE PROBE
THE ELECTRODE SYSTEM FOR THE FACILITY AND DETERMINE THE
FOR PLACEMENT OF THE C2 PROBE, EXAMINE THE CONFIGURATION
SIGNAL CABLES, FUEL TANKS, ETC. IN CHOOSING THE DIRECTION
OTHER BURIED METALS SUCH AS UTILITY PIPES, POWER AND
THE DISTANCE FROM THE ELECTRODE UNDER TEST AND FROM
B) POSITION THE C2 PROBE ALONG A LINE WHICH MAXIMIZES
THEM TO THE ELECTRODE UNDER TEST.
A) CONNECT THE TERMINALS MARKED C1 AND P1 TOGETHER AND CONNECT
(SUCH AS THE BIDDLE NULL BALANCE EARTH TESTER). PROCEED AS FOLLOWS :
DESIGNED FOR THE PURPOSE OF USING THE FALL OF POTENTIAL METHOD
MEASURE THE RESISTANCE OF THE ELECTRODE SYSTEM WITH AN INSTRUMENT
3. NEW AND EXISTING FACILITIES-
FIELDS.
MEASUREMENT WORKSHEET (FIG. 2) WILL BECOME PART OF THE PERMANENT FACILITY
SIMILAR TO THAT SHOWN IN FIG. 1. THIS SKETCH TOGETHER WITH THE RESISTANCE
EACH SECTOR OFFICE SHALL PREPARE A NEAT SKETCH OF THE FACILITY GROUND SYSTEM
2. EXISTING FACILITIES-
PROJECT ENGINEER IN THE REGIONAL OFFICE.
PROVIDE THE ORIGINAL TO THE FACILITIES CHIEF WITH A COPY TO THE
SHALL BECOME PART OF THE PERMANENT FACILITY FILE. THE COR SHALL
THIS SKETCH TOGETHER WITH THE RESISTANCE MEASUREMENT WORKSHEET (FIG. 2)
AND GROUND SYSTEM OF THE NEW FACILITY SIMILAR TO THAT SHOWN IN FIG. 1.
BY THE CONTRACTOR, SHALL PREPARE A NEAT SKETCH OF THE FACILITY
THE COR, WITH THE ASSISTANCE OF A QUALIFIED ELECTRICIAN FURNISHED
1. NEW FACILITIES-
EARTH RESISTANCE MEASUREMENT AT A TYPICAL FACILITY
2 RESISTANCE MEASUREMENT WORKSHEET
RESISTANCE MEASUREMENT WORKSHEET
SAMPLE OF A COMPLETE
POWER
INCOMING
CABLE, TYPICAL
EXISTING COAXIAL
TOWER "C"
EL. = 319'-0"
PREFAB BLDG
16'x 40'
EXISTING
POSTS
GUARD
RESISTANCE TEST ROUTE
PROBE C2 LOCATION
FIG.2
RESISTANCE =
DEPTH OF REFERENCE RODS
3.6
PROBE C2 LOCATION
FIG. 3
THREW ON 08/11/09
RESISTANCE =
DEPTH OF REFERENCE RODS
0.7
8"
WHERE CURVE LEVELS OFF.
POINTS TO ACCURATELY DETERMINE
THE FULL 500 FEET PLOT ENOUGH
IT MAY NOT BE NECESSARY TO PLOT
NOTE:
93'
31'
62'
124'
155'
186'
217'
248'
279'
50'
100'
150'
200'
250'
300'
350'
450'
500'
C2 POSITIONS
400'
310'
P2 POSITIONS
CL
E004
100 125
25'
75'
125'
175'
15'
36'
93'
108'
DISTANCE
PROBE
C2
.62x C2
READING
METER
RESISTANCE
7.2
5.4
3.8
3.7
25 75
250'
300'
350'
400'
450'
500'
31'
154'
186'
217'
248'
279'
310'
.62x C2
READING
METER
RESISTANCE
1.6
0.9
2.0
1.5
1.0
X X
I S
CL
50' 31'
77'
15050
93' 0.7
0.7
0.5
50 100 150 200
X X
TYS-1704443-E004
EARTH GROUND RESISTANCE TEST METHOD B
tys-1704443-e004
2020-09-21T09:35:00-0400
STACEY L RAINES
2020-09-10T14:40:07-0400
MICHAEL ALEXANDER BUFF
lo tt e
3/4" STRAIN RELIEF
LMR-400 THROUGH
LMR-400 THROUGH
4/0 AWG
TOWER
TO
TO SITE
TO TOP BOX
36" x 30" x 10"
TOP BOX
ON THE JUNCTION BOX.
4. PENETRATIONS AT THE TOP OF JUNCTION BOXES ARE TO HAVE BELLS TOUCHING
AND SHALL NOT BE GLUED.
3. ALL CONDUITS GOING UP THE TOWER ARE TO HAVE THE BELLS FACING DOWN,
2. CONTRACTOR SHALL VERIFY ALL PENETRATIONS WITH RE
AND BUILDINGS.
1. CONTRACTOR SHALL INSTALL ALL PENETRATIONS THROUGH JUNCTION BOXES,
E005
FRONT VIEW
TOP OF TOWER JUNCTION BOX
30" x 24" x 10"
BOTTOM BOX
TOP OF TOWER JUNCTION BOX
BOTTOM VIEW
BOTTOM OF TOWER JUNCTION BOX
BOTTOM VIEW 5
TOP VIEW
BOX ON SHELTER (SITE BOX)
BOX ON SHELTER (SITE BOX)
BOTTOM VIEW
STRAIN RELIEF
THROUGH 3/4"
STRAIN RELIEF
THROUGH 3/4"
30" x 24" x 10"
(ON SHELTER)
SITE BOX
TYS-1704443-E005
TO GROUNDING RING
W/ THOMPSON 28R
SIDES
GROUT WALL ON BOTH
LOCATION APPROVED BY RE
THROUGH BUILDING WALL.
4" PVC PENETRATED
TO GROUNDING RING
W/ THOMPSON 28R
NOT TO SCALE NOT TO SCALE
NOT TO SCALENOT TO SCALE
NOT TO SCALE NOT TO SCALE
JUNCTION BOX PENETRATION DIAGRAM
SILICONE TO THE
SEALED WITH
ON BOTTOM JUNCTION BOX
DOWN. BOTTOM BELL DIRECTLY
BELLS OF PIPE FACING
tys-1704443-e005
2020-09-21T09:35:37-0400
STACEY L RAINES
2020-09-10T14:40:51-0400
MICHAEL ALEXANDER BUFF
-g
:3 lo tt e
REV. DATE DESCRIPTION
RTR - TOWER CABLES SECTIONS AND DETAILS
TYS-1704443-G001
TYS-1704443-C001
TYS-1704443-C002
TYS-1704443-S001
TYS-1704443-E001
TYS-1704443-E002
TYS-1704443-E003
AVIA
LA
TRAT
SI
NI
T OF TRANSPO
T A
IC
OF
STATES
IT
P A
TM
EN
RTR - EXISTING PLOT LAYOUT
RTR - PLOT LAYOUT AND NEW TOWERS
RTR - ANTENNA TOWER FOUNDATION DETAILS
RTR - ANTENNA TOWER LIGHTNING PROTECTION
RTR - FLOOR PLAN
TYS-1704443-E004
TYS-1704443-E005
RTR - EARTH GROUND RESISTANCE TEST METHOD B
RTR - JUNCTION BOX PENETRATION DIAGRAM
TYS-1704443-G001
-g
DRAWING NO.
06/11/2020
RTR - COVER SHEET AND INDEX
DRAWING INDEX
REMOTE TRANSMITTER/RECEIVER (RTR)
TYS/RTR - KNOXVILLE, TENNESSEE
COVER SHEET AND INDEX
tys-1704443-g001
2020-09-21T09:36:09-0400
STACEY L RAINES
2020-09-10T14:41:39-0400
MICHAEL ALEXANDER BUFF
0'
10'
30'
SQUARE
6-8"
70'
90'
-s
:4 lo tt e
TOP VIEW
TO EQUIPMENT BUILDING
IN EQUIPMENT BUILDING
TO POWER PANEL
(52 TOTAL)
TOP AND BOTTOM
EQUALLY SPACED
EACH WAY
HORIZONTAL BARS
(13) #8 X 17'-0" GR60
FOUNDATION NOTE
TYS-1704443-S001
-s
(16) REQUIRED PER TOWER
(4) REQUIRED PER TOWER LEG
7/8 ASTM A325 X 36" WITH 6" HOOK
ANCHOR BOLTS (GFM)
MAT AROUND PERIMETER
BETWEEN TOP AND BOTTOM
RANDOMLY SPACED
VERTICAL BARS
(64) #6 3'-6" GR60
S001 NOT TO SCALE
SECTION
FOUNDATION DETAIL
TOP AND BOTTOM REBAR MAT DETAIL
TOWER 50 FEET
BY THE TOWER MANUFACTURER.
BE DETERMINED
TOWER. THE FOUNDATION SIZE WILL
THE CONTRACTOR WILL PROVIDE THE
ESTIMATING ONLY.
FOUNDATION DESIGN IS FOR 1.
FILL MATERIAL OR SAND.
7. THE CONTRACTOR SHALL BACKFILL PVC DUCTBANK WITH CLEAN
PER TOWER.
6. CONTRACTOR MUST INSTALL ONE SAFETY CLIMBING RAIL
SOIL.
5. BASE OF EXCAVATION MUST BE CLEAN OF ALL DEBRIS AND LOOSE
BEARING OF 2300PSF.
4. THIS FOUNDATION REQUIRES A MINIMUM ALLOWABLE GROSS
TO THE ASTM A615 GRADE SHOWN.
3. ALL REBAR HAS 3" MINIMUM CONCRETE COVER AND SHALL CONFORM
2 ANCHOR BOLTS SHALL BE 7/8" O ASTM A325.
1 CONCRETE MUST BE A MINIMUM 3000 PSI @ 28 DAYS STRENGTH.
18'-0"
6'-6"
17'-6"
17'-6"
S001
ANTENNA TOWER FOUNDATION DETAILS
tys-1704443-s001
2020-09-21T09:36:33-0400
STACEY L RAINES
2020-09-10T14:42:13-0400