This solicitation seeks proposals for refurbishing and recharging Halon 1301 fire suppression system cylinders for the Defense Logistics Agency Ozone Depleting Substance Reserve Program. The contractor will transport empty cylinders from Defense Depot Richmond, Virginia to their facility for cleaning, valve rebuilding, hydrostatic testing, refilling with government-furnished Halon 1301, and repainting. The contractor must then ship the completed cylinders back to Defense Depot Richmond within 365 days. The base period of performance is September 2, 2021 through September 1, 2022, with four optional one-year extensions. Pricing must be provided for the base year and all options. Proposals are due by June 21, 2021 with award based on a tradeoff evaluation. The contractor must manage cylinder warranties and provide failure analysis reports in accordance with the warranty plan.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 2021_SysCyl_SOW_ReSol.pdf | ||
| Schedule B - System Cylinders_ReSol.xlsx | XLSX spreadsheet | |
| SF1449_SP4703-21-R-0013.pdf | ||
| 2021_SysCyl_SOW_Final.pdf | ||
| FY2021_SysCyl_QASP_Final.pdf | ||
| SF1449_SP4703-21-R-0013.pdf | ||
| Past Performance Questionnaire - Template.pdf | ||
| RFP System Cylinders - 21-R-0013.pdf | ||
| System Cylinders SP4703-21-R-0013 Q and As.pdf | ||
| RFP System Cylinders - 21-R-0013.pdf | ||
| Schedule B - System Cylinders.xlsx | XLSX spreadsheet | |
| SF1449_SP4703-21-R-0013.pdf | ||
| Warranty Plan.pdf | ||
| Past Performance Questionnaire - Template.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Statement of Work
(SOW)
FY21 Halon 1301 System Cylinder Refurbishment/Re-certification DLA Aviation-VO
DoD ODS Reserve Program Office 8000 Jefferson Davis Highway
Richmond, VA 23297
INTRODUCTION:
The Defense Logistics Agency (DLA) is assigned the mission of managing the Defense Reserve of Ozone Depleting Substances (ODS) to ensure that the supplies for mission critical uses are available. DLA provides central management of ODS at the Department of Defense ODS Reserve Program Office located at DLA Aviation.
SCOPE/OBJECTIVE:
The contractor must provide all services and materials in accordance with all requirements specified in this Requirements Document and the solicitation. The contractor must make all shipping arrangements and be responsible for all shipping costs associated with the pick-up of the cylinders from the Defense Depot Richmond Virginia (DDRV) and the return shipment of all cylinders to DDRV. The government will provide resources to load and unload the contractor’s trucks at DDRV. All work, except the loading and unloading of trucks at DDRV, must be performed at the contractor’s facility.
DESCRIPTION OF WORK:
The Contractor must transport the following government Halon 1301 System Cylinders and the government-furnished cylinders containing the Halon 1301 for recharging the system cylinders from DDRV to their facility to perform refurbishment and re-certification:
Line Item NSN Make Capacity Unit of Issue Condition 0001 6830-01-171-7361 Ansul 10 lb. EA Empty (C/C “G”) 0001 6830-01-221-2192 Ansul 15 lb. EA Empty (C/C “G”) 0001 6830-01-252-2428 Ansul 60 lb. EA Empty (C/C “G”) 0001 6830-01-196-8338 Ansul 95 lb. EA Empty (C/C “G”) 0001 6830-01-140-6150 Ansul 125 lb. EA Empty (C/C “G”) 0001 6830-01-238-7035 Ansul Non-Mag 15 lb. EA Empty (C/C “G”) 0001 6830-01-059-5656 Ansul Non-Mag 60 lb. EA Empty (C/C “G”) 0001 6830-01-059-5657 Ansul Non-Mag 95 lb. EA Empty (C/C “G”)
0002 6830-01-073-6543 Kidde 10 lb. EA Empty (C/C “G”) 0002 6830-01-284-5852 Kidde 15 lb. EA Empty (C/C “G”) 0002 6830-01-294-4455 Kidde 60 lb. EA Empty (C/C “G”) 0002 6830-01-302-2555 Kidde 95 lb. EA Empty (C/C “G”) 0002 6830-01-275-1637 Kidde 125 lb. EA Empty (C/C “G”)
The government furnished Halon 1301 Type II cylinders supplied for recharging the system cylinders will be provided in 1,240 lb. cylinders under National Stock Number (NSN) 6830-01-
FY21 Halon 1301 System Cylinder Refurbishment/Re-certification
392-5017. All government furnished Halon 1301 must be properly accounted for and all empty/partially full cylinders must be returned to DDRV within 365 days from the date of contract award. The contractor must include a DD250 with each shipment of empty/partially full cylinders using the NSN shown below:
FULL EMPTY/PARTIALLY FULL
6830-01-392-5017 (1,240 lbs.) 8120-01-356-5961
The Contractor is required to coordinate the pickup of all cylinders by contacting the designated individuals in the ODS Reserve Program Office at least two weeks in advance of the initial pick up and each subsequent pick up of cylinders. The Contractor must be responsible for all shipping costs for the pickup and return of the cylinders. The government will provide resources to load trucks and unload trucks.
The designated individuals in the ODS Reserve Program Office to contact for the pickup of the Halon 1301 cylinders are as follows:
Primary Contact: To Be Provided at Time of Award Alternate Contact: To Be Provided at Time of Award
The Contractor must provide all parts (including O-rings, actuators, gauges, etc.) and all labor to remove, clean, and refurbish government valves manufactured by Ansul and Kidde, provide all labor and equipment to perform all phases of cylinder inspection and re-qualification (including inspection of exterior, preparing surface and applying primer, remove valve, inspect interior, clean interior if required, hydrostatic test, install valve, and paint), and provide all labor and equipment to fill (recharge) cylinders with government furnished Halon 1301 provided in government-owned cylinders. All O-rings, springs, hardware, software, and/or other parts provided with a rebuild kit from the cylinder manufacturer must be utilized and replaced in each valve every time a valve is rebuilt. If any additional hardware or rebuild kits are needed for the valves, they must be furnished and paid for by the Contractor. Valves that fail inspection will be replaced with additional used valves by contacting Contracting Officer’s Representative (COR).
The Contractor must make any valves deemed unrepairable available to DLA for inspection upon DLA request. All work must be performed in accordance with MIL-STD-101C, MIL-STD- 1411C, and US Navy Technical Repair Standard:
S9555-A6-TRS-010 applicable Ansul repair standards
S9555-AT-MMA-010 applicable Kidde repair standards.
Complete system cylinder assemblies must have an actuator, protective caps and anti-recoil devices, and Halon charge in accordance with above standards. Final markings must be in accordance with the latest revision of MIL-STD 129 and identified with appropriate NSN cited below, Condition Code “A” (fully refurbished, filled, and ready for issue). All return shipments must be palletized according to size as follows:
10- and 15-pound cylinders: vertically palletized 20 EA to a pallet.
60-, 95-, and 125-pound cylinder: horizontally palletized 12 EA to a pallet.
All cylinders will be packaged (banded, blocked, braced, etc.) in compliance with Department of Transportation (DOT) shipping regulations. All empty/partially filled government furnished Halon 1301 cylinders must be returned to DDRV within 365 days from the date of contract award. The Contractor must be responsible for all shipping costs for the pick-up and return of the cylinders.
The Contractor must send a DD250 with each shipment of cylinders identifying the product, NSN, and quantity of cylinders. The Contractor will also provide a Cylinder Fill Log to document data including, but not limited to: pallet reference number, individual pallet shipping weight, cylinder DOT date, cylinder serial number, cylinder tare weight, cylinder full weight, halon weight, fill date, DD250 number, batch number, and date shipped.
The government will provide resources to load trucks and unload trucks. The government will only accept cylinders that are leak-free, of correct weight, within an acceptable pressure range, and that are marked correctly. The contractor will be required to provide recovery services or adequate consideration for the recovery of product from any leaking cylinders received at
DDRV.
Refurbished/recharged/re-certified cylinders must be marked with the following NSN:
Line Item NSN Make Capacity Unit of Issue Condition 0001 6830-01-171-7361 Ansul 10 lb. EA Full (C/C “A”) 0001 6830-01-221-2192 Ansul 15 lb. EA Full (C/C “A”) 0001 6830-01-252-2428 Ansul 60 lb. EA Full (C/C “A”) 0001 6830-01-196-8338 Ansul 95 lb. EA Full (C/C “A”) 0001 6830-01-140-6150 Ansul 125 lb. EA Full (C/C “A”) 0001 6830-01-238-7035 Ansul Non-Mag 15 lb. EA Full (C/C “A”) 0001 6830-01-059-5656 Ansul Non-Mag 60 lb. EA Full (C/C “A”) 0001 6830-01-059-5657 Ansul Non-Mag 95 lb. EA Full (C/C “A”)
0002 6830-01-073-6543 Kidde 10 lb. EA Full (C/C “A”) 0002 6830-01-284-5852 Kidde 15 lb. EA Full (C/C “A”) 0002 6830-01-294-4455 Kidde 60 lb. EA Full (C/C “A”) 0002 6830-01-302-2555 Kidde 95 lb. EA Full (C/C “A”) 0002 6830-01-275-1637 Kidde 125 lb. EA Full (C/C “A”)
QUANTITIES PER YEAR:
NSN Make Capacity Expected Qty Condition 6830-01-171-7361 Ansul 10 lb. 20 Full (C/C “A”) 6830-01-221-2192 Ansul 15 lb. 20 Full (C/C “A”) 6830-01-252-2428 Ansul 60 lb. 1 Full (C/C “A”) 6830-01-196-8338 Ansul 95 lb. 48 Full (C/C “A”) 6830-01-140-6150 Ansul 125 lb. 216 Full (C/C “A”) 6830-01-238-7035 Ansul Non-Mag 15 lb. 20 Full (C/C “A”) 6830-01-059-5656 Ansul Non-Mag 60 lb. 1 Full (C/C “A”) 6830-01-059-5657 Ansul Non-Mag 95 lb. 24 Full (C/C “A”) Total: 350 6830-01-073-6543 Kidde 10 lb. 1 Full (C/C “A”) 6830-01-284-5852 Kidde 15 lb. 40 Full (C/C “A”) 6830-01-294-4455 Kidde 60 lb. 36 Full (C/C “A”) 6830-01-302-2555 Kidde 95 lb. 144 Full (C/C “A”) 6830-01-275-1637 Kidde 125 lb. 312 Full (C/C “A”) Total: 533
PERIOD OF PERFORMANCE:
Base Period: 09/02/2021 – 09/01/2022 Option Period 1: 09/02/2022 – 09/01/2023 Option Period 2: 09/02/2023 – 09/01/2024 Option Period 3: 09/02/2024 – 09/01/2025 Option Period 4: 09/02/2025 – 09/01/2026
REQUIRED DELIVERY SCHEDULE:
All cylinders must be delivered within 365 days from the date of contract award.
SHIPPING ADDRESS:
All cylinders must be returned to the following address:
Defense Depot Richmond, VA SW0400 ODS Cylinder Operations Open Shed 4 Richmond, VA 23297-5900
The contractor must coordinate all deliveries with the individuals specified below:
Primary Contact: To Be Provided at Time of Award Alternate Contact: To Be Provided at Time of Award
Carriers making deliveries will use only Gate 13, located off State Route 150, Chippenham Parkway, 1/4 mile west of U.S. Highway 1 and 301, Strathmore Road/DDRV/DSCR Exit, between 8:00 AM and 12:00 Noon, Monday through Thursday, excluding holidays. Carriers should contact To Be Provided at Time of Award upon arrival at the Depot at Cell: To Be Provided at Time of Award.
An advance copy of the DD250 must be emailed to the above individuals and the COR after the delivery appointment has been coordinated and scheduled.
INSPECTION AND ACCEPTANCE:
Inspection and acceptance must take place at destination and will begin upon shipment arrival.
System Cylinders must be allowed up to 48 hours for Acceptance to allow time to settle from shipping. Acceptance must be dependent upon compliance with leak and weight standards as described in the attached Warranty Plan for this contract. The government must make the Contractor aware of any non-conforming cylinders, which must be returned to the Contractor for repair or replacement if corrections cannot be made at the destination. The Contractor will coordinate with the government COR and will adjust the DD250 to remove the full charge for any cylinder not accepted during the inspection and acceptance process.
WARRANTY:
The Contractor must provide a prorated warranty on all refurbished system cylinders that have been received within the previous 12 months and will manage warranties in accordance with attached Warranty Plan for this contract.
The government COR must provide the Contractor with regular warranty reporting in accordance with the Warranty Plan.
The Contractor must be required to submit a Failure Analysis Report including Corrective Action Plan for each system cylinder repaired under warranty, identifying cause of failure, remedy to correct, and any additional information discovered.
PAYMENT:
All invoices must be submitted through Wide Area Workflow (WAWF) in accordance with Defense Federal Acquisition Regulation Supplement (DFARS) clauses 252.232-7003 and 252.232-7006. The following attachments should be uploaded into WAWF for every Invoice:
Shipments from DLA to Contractor:
DD250
Import Template – covers gross weight and recovered gas for each cylinder received by Contractor (Excel format if possible)
Shipments from Contractor to DLA:
DD250
Shipment Overview – specific list of everything in the shipment
Certificate of Analysis (COA) for each Ready for Issue (RFI) cylinder received Fill Log that contains COA information for each System Cylinder received (Excel format if possible)
PAY DODAAC: SL4701
WAWF Invoice Type: Combo Invoice Inspection/Acceptance Point: Destination/Destination Issue by DoDAAC: SP4703 Admin DoDAAC: SP4703 Inspect By DoDAAC: Leave Blank Acceptor DoDAAC: SC0419 DCAA Auditor DoDAAC: Leave Blank
Refer to https:\\wawf.eb.mil for additional information.
File details come from the government source that posted it. Updated .