Standby Power Generator MEDCOM 589 and 593 Layout.pdf

PDF 340 KB Posted

Attached to
CSJTC Standby Power Generators Federal contract opportunity
Solicitation number
W912LR20B0015
Issued by
Department of the Army National Guard

About this file

This document outlines requirements for a federal contract solicitation for standby power generators. The Puerto Rico Army National Guard intends to award a firm fixed-price contract for the purchase and installation of four standby power generators with automatic and manual transfer switches at Camp Santiago Joint Training Center in Puerto Rico. The work includes one 60KW, two 125KW, and one 300KW standby diesel generators to be mounted on reinforced concrete slabs and protected by metal/concrete bollards. The period of performance is 120 calendar days with a project magnitude between $250,000-$500,000. The NAICS code is 238210 and it is set aside for Service Disabled Veteran Owned Small Businesses. Offerors must perform at least 15% of the work cost, excluding materials, with their own employees. The question deadline is July 31, 2020 and bids are due by August 24, 2020. Price is the evaluation factor and award will be made without discussions.

View the file

Other files for this federal contract opportunity

Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

600A MDP600A MDP

200A

200A

150A

100A

100A

200A 200A 100A 100A 100A

3 # 1/0 TRXLPE IN 4''

PVC SCH. 80 CONDUIT

Ø

20A

400A DP

Ø

AutoCAD SHX Text

GROUND LEVEL

AutoCAD SHX Text

NEW STANDBY POWER GENERATOR 300 KW, 3 PHASE, ATTENUATED ENCLOSURE

AutoCAD SHX Text

EXISTINGT REINFORCED CONCRETE POLES

AutoCAD SHX Text EXISTING 300 kVA, 3 PHASE, MOUNTED TRANSFORMER

AutoCAD SHX Text

4'' DIA. GALV. STEEL RGC

AutoCAD SHX Text NEW CONCRETE PAD 16' x 8'

AutoCAD SHX Text

NEW 800A AUTOMATIC TRANSFER SWITCH NEMA- 3R

AutoCAD SHX Text

EXISTING 800A MDP ELECTRICAL PANEL WITH A 600A MAIN BREAKER

AutoCAD SHX Text

EXISTING EQUIPMENT BUILDING 589

AutoCAD SHX Text

EXISTING EQUIPMENT BUILDING 589

AutoCAD SHX Text

EXISTING EQUIPMENT BUILDING 589

AutoCAD SHX Text

EXISTING EQUIPMENT BUILDING 589

AutoCAD SHX Text

EXISTING EQUIPMENT BUILDING 589

AutoCAD SHX Text TWO SET OF 4 NO. 500 Kcmil RHW 1 NO. 1/0 RHW MECH. GROUND IN 4''Ø PVC SCH. 40 IN PARALLEL PVC SCH. 40 IN PARALLEL CONECTION WITH SPARE

AutoCAD SHX Text

1# 1/ 0 AWG BARE COPPER GROND WIRE

AutoCAD SHX Text

GROUND CLAMP

AutoCAD SHX Text 5/8'' x 8' LONG COPPER WELD GROUNDING ROD NUMBER AS REQUIRED TO ACHIEVE 10 OHMS TO GROUND MAX

AutoCAD SHX Text

GROUND LEVEL

AutoCAD SHX Text kVA

AutoCAD SHX Text kVA

AutoCAD SHX Text kVA

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EXISTING EQUIPMENT BUILDING 589

AutoCAD SHX Text

NEW 400A AUTOMATIC TRANSFER SWITCH NEMA- 3R

AutoCAD SHX Text

EXISTING 400A DP ELECTRICAL PANEL WITH A 400A MAIN BREAKER, 42 SPACES

AutoCAD SHX Text

EXISTING EQUIPMENT BUILDING 593

AutoCAD SHX Text TO MDP BATTERY CHARGER 2 NO 12 AWG AND 1 12 AWG GRD IN ''Ø PVC-SCH 4034''Ø PVC-SCH 40PVC-SCH 40

Sheets and Views
Layout1

File details come from the government source that posted it. Updated .