This document provides details for a federal contract solicitation to purchase and install standby power generators at Camp Santiago Joint Training Center in Puerto Rico. The Puerto Rico Army National Guard intends to award a single firm fixed-price contract between $250,000 to $500,000 for one 60KW, two 125KW, and one 300KW standby diesel generators mounted on concrete slabs with metal/concrete bollards. The generators will have automatic and manual transfer switches and the period of performance is 120 calendar days after notice to proceed. The solicitation is set aside for Service Disabled Veteran Owned Small Businesses and requires a minimum of 15% of the work to be performed by the contractor's own employees. Questions are due by July 31, 2020 and bids will open on August 24, 2020 at Camp Santiago Joint Training Center. Firms must contact the contracting officers by August 20, 2020 to schedule a required site visit. The North American Industry Classification System code is 238210 and the solicitation will be posted on the Federal Business Opportunities website.

View the file

Other files for this federal contract opportunity

Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DP

3 # 1/0 TRXLPE IN 4''

PVC SCH. 80 CONDUIT

DP

Ø

Ø

AutoCAD SHX Text

GROUND LEVEL

AutoCAD SHX Text

NEW STANDBY POWER GENERATOR 125 KW, SINGLE PHASE, ATTENUATED ENCLOSURE

AutoCAD SHX Text

EXISTINGT CONCRETE POLE

AutoCAD SHX Text EXISTING 50 kVA SINGLE PHASE POLE MOUNTED TRANSFORMER

AutoCAD SHX Text

EXISTING 4'' DIA. GALV. STEEL RGC

AutoCAD SHX Text NEW CONCRETE PAD 16' x 8'

AutoCAD SHX Text

NEW 200A AUTOMATIC TRANSFER SWITCH NEMA- 3R

AutoCAD SHX Text

EXISTING 200A MAIN BREAKER

AutoCAD SHX Text

EXISTING DISTRIBUTION PANEL TO BUILDING 769

AutoCAD SHX Text

1# 1/ 0 AWG BARE COPPER GROND WIRE

AutoCAD SHX Text

GROUND CLAMP

AutoCAD SHX Text 5/8'' x 8' LONG COPPER WELD GROUNDING ROD NUMBER AS REQUIRED TO ACHIEVE 10 OHMS TO GROUND MAX

AutoCAD SHX Text

NEW 100A MANUAL TRANSFER SWITCH NEMA- 3R

AutoCAD SHX Text

EXISTING 100A GENERAL DUTY SAFETY SWITCH

AutoCAD SHX Text

EXISTING DISTRIBUTION PANEL TO BUILDING 770

AutoCAD SHX Text EXISTING 37.5 kVA SINGLE PHASE POLE MOUNTED TRANSFORMER

AutoCAD SHX Text

EXISTINGT CONCRETE POLE

AutoCAD SHX Text TO MDP BATTERY CHARGER 2 NO 12 AWG AND 1 12 AWG GRD IN ''Ø PVC-SCH 4034''Ø PVC-SCH 40PVC-SCH 40

AutoCAD SHX Text TWO SET OF 4 NO. 500 Kcmil RHW 1 NO. 1/0 RHW MECH. GROUND IN 4''Ø PVC SCH. 40 IN PARALLEL PVC SCH. 40 IN PARALLEL CONECTION WITH SPARE