Specifications.pdf
PDF 6 MB Posted
- Attached to
- J073--Kitchen Hood Cleaning and Maintenance
- Solicitation number
- 36C25924Q0834
About this file
This document is a Request for Quote (RFQ) for kitchen hood cleaning and maintenance services. The solicitation number is 36C25924Q0834, and the North American Industry Classification System (NAICS) code is 561720 with a small business size standard of $22.0 Million.
The government is seeking a firm-fixed-price contract for quarterly kitchen hood cleaning and maintenance services. The contract includes a base year and four option years. Offerors are required to submit technical and price proposals. Technical capability and price will be the evaluation factors, with the government reserving the right to select a proposal that provides additional benefits beyond the minimum requirements. Quotes are due by 12:00pm MT on 09/24/2024 and should be submitted via email to Eric.Adusei@va.gov. The Department of Veterans Affairs, Veterans Health Administration, Veterans Integrated Service Network 19 is the procuring agency.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25924Q0834 0001.docx | DOCX document | |
| Kitchen Hoods and Fans.pdf | ||
| SOW Kitchen Hood Cleaning and Maintenance Updated.docx | DOCX document | |
| Wage Determination 2015-5419 REV 27 Dated 07-22-2024.pdf | ||
| 36C25924Q0834.docx | DOCX document | |
| SOW_Kitchen Suppression Hood Cleaning and Maintenance.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UPDN
DN
UP
BS
BS
BS
MAINT.
ACCESS
MAINT.
ACCESS
MAINT.
ACCESS
HSU-101
VEST
04-SV1-V1
HSU-102
VEST
04-SV1-V2
HSU-ST2
STAIR
04-SV1-ST2
HE-S01
ELEV
04-SV1-SE3
HE-S02
ELEV
04-SV1-SE4HE-P02
ELEV
04-SV1-PE4
HE-P01
ELEV
04-SV1-PE3
HSU-ST1
STAIR
04-SV1-ST1
HE-S03
ELEV
04-SV1-SE17
HSU-100
MECH
04-SV1-A1-M1
04-SV-F3-05
BIOMED REPAIR
HS-100
RECEIVING
04-SV-A1-03
HS-152
OFFICE
04-SV-F1-03
HS-105
AUTOPSY
04-SV-B3-04
HS-109
ISO/AUTOPSY
04-SV-B3-01
HS-107A
STAFF TLT
04-SV-B3-03
HS-113
RECEIVING
04-SV-B3-05
HS-157
STAFF
LOUNGE/LOCKERS
04-SV-G3-04
04-SV-C3-01
OFFICE
HS-121
OFFICE
04-SV-C3-03HS-115
OFFICE
04-SV-C3-02
04-SV-G1-06
STAFF TLT
HS-111
MORTUARY REFR
04-SV-A3-01
HS-149C
BIOMED STOR
04-SV-G3-02
HS-149B
RECEIVING/CLEANING
04-SV-G3-01
HS-149A
OFFICE
04-SV-F3-02
HS-125
STOR
04-SV-D3-0304-SV-C3-06
CLEAN LINEN
HOLD
04-SV-C3-05
CLEAN LINEN
CART STOR
HS-131
DISTRIBUTION/DISPATCH
04-SV-E3-02
04-SV-E3-04
SUPPLY STOR
HS-133
UNIFORM
04-SV-E3-01
04-SV-E3-03
LINEN STOR
HS-123
CLEAN LINEN
DISTRIBUTION
04-SV-C3-04
04-SV-E3-05
OFFICE
04-SV-H1-04
FEMALE
TLT/SHOWER
HS-100A
NON-FOOD STOR
04-SV-A2-01
HS-100B
DRY FOOD STOR
04-SV-A1-02
HS-124A
REFR AND
FROZEN FOOD
STOR
04-SV-B2-01
HS-124C
BLAST CHILLED
FOOD STOR
04-SV-B1-02 04-SV-D1-01
TRAY ASSEMBLY
04-SV-D1-03
TRAY CART
CLEAN
HS-130
POT WASH 2
04-SV-D1-02 04-SV-E1-01
POT WASH 1
HS-132B
CART WASH
04-SV-E2-01
HS-132
DISHWASH
04-SV-E1-03
04-SV-E2-03
HAZ SUPPLIES
STORHS-132A
HAC
04-SV-E2-02
04-SV-A1-04
RECYCLING
HS-150
CONF
04-SV-G1-01
HS-148D
OFFICE
04-SV-F1-04
HS-148B
OFFICE
04-SV-F1-09
HS-154
OFFICE
04-SV-F1-02
HS-126A
COMMUNICATIONS/FOOD
SERVICE
04-SV-D2-01
HS-148A
SECR/WAIT
04-SV-F2-02
04-SV-E3-08
OFFICE
04-SV-E3-10
OFFICE
04-SV-E3-07
OFFICE
HS-143
OFFICE
04-SV-E3-06
HS-124D
BLAST CHILLED
FOOD STOR
04-SV-B1-01
HS-139
OFFICE
04-SV-E3-11
HS-141
OFFICE
04-SV-E3-09
HS-135
SECR/WAIT
04-SV-E3-13
04-SV-F3-04
BED REPAIR
SHOP
HS-149
ELECTRONICS
04-SV-F3-03
HS-129
HAC
04-SV-D3-01
04-SV-F1-06
OFFICE
04-SV-F1-05
OFFICE
HS-130B
CLEANING
SUPPLY STOR
04-SV-E1-02
04-SV-G1-07
MALE
TLT/SHOWER
04-SV-F1-01
OFFICE
04-SV-H1-06
LOCKERS
04-SV-G1-03
LOCKERS
04-SV-H1-05
STAFF LOCKERS
04-SV-G3-03
STAFF LOUNGE
04-SV-H1-03
STAFF TLT04-SV-G1-05
STAFF TLT
04-SV-H1-02
STAFF TLT
HS-156
STAFF
LOUNGE/LOCKERS
04-SV-G1-02
HS-101
HAC
04-SV-A3-03
04-SV-H3-01
STAFF LOUNGE
HS-134
WASTE PULPER
04-SV-F2-01
HS-130A
STAFF TLT
04-SV-D2-02
HS-158
FEMALE
TLT/SHOWER
04-SV-H1-01
04-SV-G1-04
MALE
TLT/SHOWER
HS-107
STAFF LOCKERS
04-SV-B3-02
HS-145
RECEIVING/CLEANING
04-SV-F3-01
04-SV-G2-01
VEST
04-SV-H2-02
VEST
HS-137
CONSULT
04-SV-E3-12
04-SV-F1-07
OFFICE
HS-148C
OFFICE
04-SV-F1-08
04-SV-A3-06
CLOSET
HS-C02
CORRIDOR
04-SV-B2-02
HS-103
CORRIDOR
04-SV-A3-02
HS-124B
CIRC
04-SV-B1-03
04-SV-E3-14
CIRC
HS-102
CART DEPOT
04-SV-A2-02
HS-C01
CORRIDOR
04-SV-A3-04
HS-C03
CORRIDOR
04-SV-D3-02
HS-C04
CORRIDOR
04-SV-E3-15
HS-126
FOOD PREP
04-SV-C2-01
HS-124
NOURISH
04-SV-C1-01
INTERSTITIAL ACCESS WALKWAY
4 - TU1 - 0.2
4 - TU2 - 0.1
4 - TU2 - 0.3
4 - TU2 - 0.4
4 - TU2 - 0.5
4 - TU2 - 0.6 4 - TU2 - 0.7
4 - TU2 - 0.8
4 - TU2 - 0.9
4 - TU3 - 0.1
4 - TU3 - 0.2
4 - TU3 - 0.3
4 - TU3 - 0.6
4 - TU3 - 0.7
4 - TU3 - 0.8
4 - TU3 - 0.9
4 - TU3 - 0.10
4 - TU3 - 0.11
4 - TU3 - 0.15
4 - TU3 - 0.16
4 - TU3 - 0.17
4 - TU3 - 0.18 4 - TU3 - 0.19
4 - TU3 - 0.44 - TU3 - 0.13
"x
28"x20"
4 - TU2 - 0.11
4 - TU1 - 0.1
4 - TU2 - 0.10
FIRE DAMPER
IN VERTICAL
(TYP)
4 - TU1 - 0.3
4 - TU1 - 0.4
4 - TU1 - 0.5
4 - TU2 - 0.12
A
B
C
D
E
F
G
H
J
K
R1
R2
RJ
RF
RE
RD
RC
RB
RA
4 - TU2 - 0.2
4 - TU3 - 0.12
4 - TU3 - 0.5
20"x18"
14"x14"
"x
"x
24"x18" 20"x18"
"x
22"x18"30"x18" 30"x18"
20"x18"
"x
24"x18"
24"x26" 16"x16"
24"x18" 18"x16"
18"x18"
"x
" 16"x10"
"x
"x
36"x30"30"x26"
26"x26" 22"x20"
20"x16"
32"x22"24"x22"
"x
30"x26"
24"x18"
30"x20" 16"x18"
"x
"x
16"x20"
14"x16" 14 "x
"x
14"x16"
"x
12"x10"12"x14"
16"x14"
14"x16"14 "x
30"x28"
30"x20"
20"x16"
8"ø
"x
14"x14"
"x
G 880 CFM
18 / 12C 880 CFM
18 / 12
"x
"x
"x
C 880 CFM
18 / 12G 880 CFM
18 / 12
"x
16"x14"
"x
14"x14"
14"x14"
14"x14"
10"x14"
10"ø
"x
FIRE
DAMPER IN
VERTICAL
(TYP)16"ø
CONNECT TO
HOOD (TYP-5)
20"x18"
20"x18"
36"x24"
40"x20"
"x
36"x24"
14"ø
700 CFM TO
CART
WASH
750 CFM TO
DISH WASH
10"x16"
"x
04-ETU-0.1
14"x16"
"x
8"
4 - TU1 - 0.6
4 - TU2 - 0.13
04-MH-301
RG
RH
"x
20"x20"
"x
30"x20"
10"x12"
04-FCU-14
24"x18"
20"x20"
20"x20"
8"ø
10"ø
"ø
10"x12"
"x
MH.X086
MH.X086
MH.X048
04-MH-100
8" EA DOWN
MH.X243
MH.X243
8" ø
11 12 08 09 13
03040506
Drawing Number
Building Number
Project NumberProject Title
Location
Date Checked Drawn
Drawing Title
Approved: Project Director
Key PlanCONSULTANTS:
DateRevisions
1 2 3 4 5 6 7 8 9 10 11 12
D
C
B
A
554-501REPLACEMENT MEDICAL CENTER
FACILITY, EASTERN COLORADO
HEALTH CARE SYSTEM
AURORA, COLORADO
N
C O
N
R
ES
D
AT
IB
S
IB
N
EN
C
C
LC
C
BN
C
BC
C
BS
PS
N
PV
N
PV
S
13 14
1 2 3 4 5 6 7 8 9 10 11 12 13 14
E
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
ARCHITECT/ENGINEERS:Professional Seal
6/
/2
3:
:4
PM
C :\U se rs
\C
AD
U se r 2 \D oc um en ts
\M H
-IB
S_ ch ar lo tte
.b la ck w oo d.
rv t
04-MH-100-1
SERVICE LEVEL INTERSTITIAL HVAC
PLAN
INPATIENT BUILDING (SOUTH)
08/31/2012
0' 4' 8' 16' 32'0' 4' 8' 16' 32'
NORTH
1/8" = 1'-0"1
SERVICE LEVEL INTERSTITIAL
HVAC PLAN
UP
DN
UP
DN
R R D
H
C
48/2448/2448/24
D D
C
BS
BS
BS
HS-112
CONDENSATE
LIFT / STORM &
SAN
04-SV-A2-H3
HS-117
ELEC
04-SV-C3-E2 HS-119
DATA /
TELECOMM
04-SV-C3-T2
HE-S02
ELEV
04-SV-SE4
HE-S01
ELEV
04-SV-SE3
HS-147
ELEC
04-SV-F3-E1
HS-100D
ELEV MACH RM
04-SV-A1-V17
HE-S03
ELEV
04-SV-SE17
HE-P01
ELEV
04-SV-PE3
HE-P02
ELEV
04-SV-PE4
HS-127
CHUTE
04-SV-D3-H1
HS-ST1
STAIR
04-SV-ST1
HS-ST2
STAIR
04-SV-ST2
04-SV-V2
VEST
04-SV-F3-05
BIOMED REPAIR
HS-100
RECEIVING
04-SV-A1-03
HS-152
OFFICE
04-SV-F1-03
HS-105
AUTOPSY
04-SV-B3-04
HS-109
ISO/AUTOPSY
04-SV-B3-01
HS-107A
STAFF TLT
04-SV-B3-03
HS-113
RECEIVING
04-SV-B3-05
HS-157
STAFF
LOUNGE/LOCKERS
04-SV-G3-04
04-SV-C3-01
OFFICE
HS-121
OFFICE
04-SV-C3-03HS-115
OFFICE
04-SV-C3-02
04-SV-G1-06
STAFF TLT
HS-111
MORTUARY REFR
04-SV-A3-01
HS-149C
BIOMED STOR
04-SV-G3-02
HS-149B
RECEIVING/CLEANING
04-SV-G3-01
HS-149A
OFFICE
04-SV-F3-02
HS-125
STOR
04-SV-D3-0304-SV-C3-06
CLEAN LINEN
HOLD
04-SV-C3-05
CLEAN LINEN
CART STOR
HS-131
DISTRIBUTION/DISPATCH
04-SV-E3-02
04-SV-E3-04
SUPPLY STOR
HS-133
UNIFORM
04-SV-E3-01
04-SV-E3-03
LINEN STOR
HS-123
CLEAN LINEN
DISTRIBUTION
04-SV-C3-04
04-SV-E3-05
OFFICE
04-SV-H1-04
FEMALE
TLT/SHOWER
HS-100A
NON-FOOD STOR
04-SV-A2-01
HS-100B
DRY FOOD STOR
04-SV-A1-02
HS-124A
REFR AND
FROZEN FOOD
STOR
04-SV-B2-01
HS-124C
BLAST CHILLED
FOOD STOR
04-SV-B1-02 04-SV-D1-01
TRAY ASSEMBLY
04-SV-D1-03
TRAY CART
CLEAN
HS-130
POT WASH 2
04-SV-D1-02 04-SV-E1-01
POT WASH 1
HS-132B
CART WASH
04-SV-E2-01
HS-132
DISHWASH
04-SV-E1-03
04-SV-E2-03
HAZ SUPPLIES
STORHS-132A
HAC
04-SV-E2-02
04-SV-A1-04
RECYCLING
HS-150
CONF
04-SV-G1-01
HS-148D
OFFICE
04-SV-F1-04
HS-148B
OFFICE
04-SV-F1-09
HS-154
OFFICE
04-SV-F1-02
HS-126A
COMMUNICATIONS/FOOD
SERVICE
04-SV-D2-01
HS-148A
SECR/WAIT
04-SV-F2-02
04-SV-E3-08
OFFICE
04-SV-E3-10
OFFICE
04-SV-E3-07
OFFICE
HS-143
OFFICE
04-SV-E3-06
HS-124D
BLAST CHILLED
FOOD STOR
04-SV-B1-01
HS-139
OFFICE
04-SV-E3-11
HS-141
OFFICE
04-SV-E3-09
HS-135
SECR/WAIT
04-SV-E3-13
04-SV-F3-04
BED REPAIR
SHOP
HS-149
ELECTRONICS
04-SV-F3-03
HS-129
HAC
04-SV-D3-01
04-SV-F1-06
OFFICE
04-SV-F1-05
OFFICE
HS-130B
CLEANING
SUPPLY STOR
04-SV-E1-02
04-SV-G1-07
MALE
TLT/SHOWER
04-SV-F1-01
OFFICE
04-SV-H1-06
LOCKERS
04-SV-G1-03
LOCKERS
04-SV-H1-05
STAFF LOCKERS
04-SV-G3-03
STAFF LOUNGE
04-SV-H1-03
STAFF TLT04-SV-G1-05
STAFF TLT
04-SV-H1-02
STAFF TLT
HS-156
STAFF
LOUNGE/LOCKERS
04-SV-G1-02
HS-101
HAC
04-SV-A3-03
04-SV-H3-01
STAFF LOUNGE
HS-134
WASTE PULPER
04-SV-F2-01
HS-130A
STAFF TLT
04-SV-D2-02
HS-158
FEMALE
TLT/SHOWER
04-SV-H1-01
04-SV-G1-04
MALE
TLT/SHOWER
HS-107
STAFF LOCKERS
04-SV-B3-02
HS-145
RECEIVING/CLEANING
04-SV-F3-01
04-SV-G2-01
VEST
04-SV-H2-02
VEST
HS-137
CONSULT
04-SV-E3-12
04-SV-F1-07
OFFICE
HS-148C
OFFICE
04-SV-F1-08
04-SV-A3-06
CLOSET
HS-C02
CORRIDOR
04-SV-B2-02
HS-103
CORRIDOR
04-SV-A3-02
HS-124B
CIRC
04-SV-B1-03
04-SV-E3-14
CIRC
HS-102
CART DEPOT
04-SV-A2-02
HS-C01
CORRIDOR
04-SV-A3-04
HS-C03
CORRIDOR
04-SV-D3-02
HS-C04
CORRIDOR
04-SV-E3-15
HS-126
FOOD PREP
04-SV-C2-01
HS-124
NOURISH
04-SV-C1-01
A
B
C
D
E
F
G
H
J
K
R1
R2
RJ
RF
RE
RD
RC
RB
RA
A 220 CFM
8" A 360 CFM
12"
A 240 CFM
10"
(TYP-2)
A 200 CFM
8"
A 70 CFM
8"
A 220 CFM
8"
A 300 CFM
10" A 300 CFM
10"
E 480 CFM
14"
A 350 CFM
10"
A 350 CFM
12" A 270 CFM
12" E 110 CFM
8"
A 375 CFM
10"
A 375 CFM
10"
A 300 CFM
10"A 200 CFM
8"
J 320 CFM
10"
(TYP-3)
E 340 CFM
12"
(TYP-2)
A 200 CFM
8"
E 200 CFM
8"
E 100 CFM
8"
A 100 CFM
8"
A 300 CFM
10"
J 70 CFM
8"
A 390 CFM
12"
A 390 CFM
12"
B 170 CFM
8"
B 130 CFM
8"
J 100 CFM
8"
J 100 CFM
8"
A 305 CFM
10"
(TYP-6)
J 80 CFM
8"
A 300 CFM
10"
A 200 CFM
8'
(TYP-3)
E 690 CFM
14"
E 600 CFM
14"
(TYP-4)
A 80 CFM
8"
A 80 CFM
8"
A 110 CFM
8"
A 200 CFM
8"
A 80 CFM
8"
E 440 CFM
14"
J 190 CFM
8"
A 200 CFM
8" A 200 CFM
8"
E 200 CFM
8"
E 200 CFM
8"
E 120 CFM
8"
A 120 CFM
8"
A 300 CFM
10"
A 100 CFM
8" A 80 CFM
8"
A 260 CFM
10"
E 260 CFM
10"E 80 CFM
8"
H 260 CFM
10"
(TYP-5)
B 260 CFM
10"
(TYP-5)
E 200 CFM
8" E 350 CFM
8" J 210 CFM
10"
(TYP-4)
B 270 CFM
10"
(TYP-3)
A 300 CFM
10"
E 650 CFM
14"E 675 CFM
14"
A 260 CFM
10"
(TYP-4)
A 365 CFM
10"
(TYP-5)
A 240 CFM
10"
E 1180 CFM
16" E 1180 CFM
16"
A 140 CFM
8"
E 80 CFM
8"J 150 CFM
8"
(TYP-2)
J 190 CFM
8"
E 600 CFM
14"
(TYP-2)
(TYP-4)
F 1000 CFM
14"
K 500 CFM
12"
F 1000 CFM
14"
K 500 CFM
12"
(TYP-4)
(TYP-21)
E 600 CFM
14"
J 120 CFM
8"
E 250 CFM
8"
J 100 CFM
8"
14/14 EA UP & DN
G 1250 CFM
24 / 12
DUCT AND GRILLE
LOCATED IN PIPE
BASEMENT LEVEL
C 1250 CFM
18 / 12
14x14 SA UP & DN
DUCT AND GRILLE
LOCATED IN PIPE
BASEMENT LEVEL
CONNECT 14"
DIA TO DISH
WASH
CONNECT
14" DIA TO
CART
WASH
750 CFM
700 CFM
22 / 10S 770 CFM
22 / 10S 770 CFM
8" DIA. DN TO 6" BELOW
CEILING, CONNECT TO SINK
EXHAUST OUTLET WITH FLEX
PROVIDED BY EQUIPMENT
MFGR TO ACCOMMODATE
ADJUSTABLE SINK HEIGHT,
(300 CFM) (TYP-6)
10x4 DUCT DN TO 10x6 GRILLE TYPE
"G" AT 7"A.F.F.,
BALANCE TO 100
CFM (TYP-3).
10" DIA EA UP & DN
10" STUB UP
TO 2" A.F.F.,
BALANCE TO
350 CFM
14"x14"
"x
FIRE DAMPER
IN VERTICAL
A 320 CFM
10"
E 960 CFM
16"
(TYP-3)
A 80 CFM
8"
A 100 CFM
8"
04-MH-301
RG
RG
RH
RH
E 480 CFM
14"
(TRANSFER)
(TRANSFER)
A 250 CFM
8"
REFER TO EQUIPMENT DRAWINGS
FOR CFM TO EXHAUST HOOD
CONNECTIONS . TOTAL EXHAUST
CFM TO BE 6,960 CFM.
C 1600 CFM
20 / 20
G 1600 CFM
20 / 20
MH.X086
MH.X048
B 280 CFM
10"
10"ø
PROVIDE FIVE 4"
DROPS DOWN TO
STORAGE
CABINETS AND
BALANCE TO 40
CFM EACH.
8" DUCT ABOVE
CEILING
8" DUCT UP TO
INTERSTITIAL
LEVEL
04-MH-100
MH.X243
6" EXHAUST
FROM
MORTUARY
REFRIGERATOR,
EXHAUST FAN
PROVIDED WITH
MORTUARY
REFRIGERATOR
MH.X243
S 75 CFM
22/10
SERV LEVEL
-20' - 0"
SERV INT
-8' - 6"
8"ø
4"ø
11 12 08 09 13
03040506
Drawing Number
Building Number
Project NumberProject Title
Location
Date Checked Drawn
Drawing Title
Approved: Project Director
Key PlanCONSULTANTS:
DateRevisions
1 2 3 4 5 6 7 8 9 10 11 12
D
C
B
A
554-501REPLACEMENT MEDICAL CENTER
FACILITY, EASTERN COLORADO
HEALTH CARE SYSTEM
AURORA, COLORADO
N
C O
N
R
ES
D
AT
IB
S
IB
N
EN
C
C
LC
C
BN
C
BC
C
BS
PS
N
PV
N
PV
S
13 14
1 2 3 4 5 6 7 8 9 10 11 12 13 14
E
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
ARCHITECT/ENGINEERS:Professional Seal
6/
/2
3:
:3
PM
C :\U se rs
\C
AD
U se r 2 \D oc um en ts
\M H
-IB
S_ ch ar lo tte
.b la ck w oo d.
rv t
04-MH-100
SERVICE LEVEL HVAC PLAN
INPATIENT BUILDING (SOUTH)
08/31/2012
0' 4' 8' 16' 32'0' 4' 8' 16' 32'
NORTH
1/8" = 1'-0"1 SERVICE LEVEL HVAC PLAN
1/8" = 1'-0"2
SECTION AT AUTOPSY STORAGE
CABINETS
M
AI
N T.
AC
C
ES
S
M
AI
N T.
AC
C
ES
S
M
H1U-101
VEST
04-11-V1
H1U-ST1
STAIR
04-11-ST1
HE-P02
ELEV
04-11-PE4
HE-P01
ELEV
04-11-PE3
HE-S03
ELEV
04-11-SE17
HE-S02
ELEV
04-11-SE4
HE-S01
ELEV
04-11-SE3
H1U-ST2
STAIR
04-11-ST2
H1U-102
VEST
04-11-V2
H1U-100
MECH
04-11-A1-M1
01-01-PGE4
ELEV
01-01-PGE3
ELEV
IBS H
INTERSTITIAL ACCESS WALKWAY
4 - TU2 - 1.16
4 - TU2 - 1.15
4 - TU2 - 1.14
4 - TU2 - 1.13
4 - TU2 - 1.12
4 - TU2 - 1.10 4 - TU2 - 1.7 4 - TU2 - 1.6 4 - TU2 - 1.3 4 - TU2 - 1.1
4 - TU2 - 1.11 4 - TU2 - 1.9
4 - TU2 - 1.8
4 - TU2 - 1.4
4 - TU2 - 1.5
4 - TU2 - 1.38
4 - TU2 - 1.31
4 - TU2 - 1.30
4 - TU2 - 1.29
4 - TU2 - 1.28
4 - TU2 - 1.27
4 - TU2 - 1.26
4 - TU2 - 1.18
4 - TU2 - 1.20
4 - TU2 - 1.21
4 - TU2 - 1.23
4 - TU2 - 1.24
4 - TU2 - 1.17
4 - TU2 - 1.19
4 - TU2 - 1.22
4 - TU2 - 1.25
4 - TU3 - 1.1
4 - TU3 - 1.3 4 - TU3 - 1.4
4 - TU3 - 1.5
4 - TU3 - 1.6 4 - TU3 - 1.7 4 - TU3 - 1.8
4 - TU3 - 1.9
4 - TU3 - 1.10 4 - TU3 - 1.11
4 - TU3 - 1.12 4 - TU3 - 1.13
4 - TU3 - 1.15
4 - TU3 - 1.16
4 - TU3 - 1.17
4 - TU3 - 1.18
4 - TU3 - 1.19
4 - TU3 - 1.20
4 - TU3 - 1.21
4 - TU3 - 1.22
4 - TU3 - 1.26
4 - TU3 - 1.27
4 - TU3 - 1.28
4 - TU3 - 1.25
4 - TU3 - 1.23
4 - TU3 - 1.29
4 - TU3 - 1.30
4 - TU3 - 1.33
4 - TU3 - 1.31
4 - TU3 - 1.34
4 - TU3 - 1.35
4 - TU3 - 1.36
4 - TU3 - 1.37
4 - TU3 - 1.38
4 - TU3 - 1.39
4 - TU3 - 1.40
4 - TU3 - 1.41
4 - TU3 - 1.42
4 - TU3 - 1.43
4 - TU3 - 1.44
4 - TU3 - 1.45
4 - TU3 - 1.46
4 - TU3 - 1.47
4 - TU3 - 1.48
4 - TU3 - 1.49
4 - TU3 - 1.24
4 - TU3 - 1.32
4 - TU2 - 1.32
4 - TU2 - 1.33
4 - TU2 - 1.2
4 - TU2 - 1.34
4 - TU3 - 1.14
RJ
RJ
RH
RH
RG
RG
RF
RF
RD
RD
RC
RC
RB
RB
AA
AA
BB
BB
A
B
C
D
E
F
G
H
J
J
K
R1
R2
RA
42"x28"
"x
"x
"x
26"x26"
20"x20"
20"x14"
36"x16"
20"x20"
16"x20"20"x12"
14"x12"
"x
"x
16"x14"
14"x16"
14"x16"
20"x20"
10"x14"
14"x16"
14"x14"
"x
"x
10"x14"
"x
"x
24"x26"
20"x20" 18"x18" 18"x16"
12"x12"
8"x12"
"x
14"x14"
8" ø
12"ø
18"x16" 16"x16" 16"x14"
12"x14" 10"x12"
16"x14"16"x16"
"x
"x
22"x20"22"x20"
"x
"x
26"x24"
26"x24"
28"x24"
"x
14"x14"
18"x16"
16"x16"
18"x16"
14"x16"
14"x16"
30"x26"
"x
"x
"x
G 880 CFM
18 / 12 C 880 CFM
18 / 12
12"x14"
"x
C 875 CFM
18 / 12 G 875 CFM
18 / 12
"x
"x
"x
32"x30"
28"x24"
28"x24"
"x
"x
24"x20"
"x
"10
"ø
04-MH-403
04-MH-403
04-MH-404
FIRE
DAMPER IN
VERTICAL
(TYP)
FIRE
DAMPER IN
VERTICAL
(TYP)
K 550 CFM
12"
(TYP-4)
F 1100 CFM
14"
(TYP-2)
24"x26"
4-ETU-1.1
4-ETU 1.2
"x
"x
"x
"x
14"ø
10"ø
10"x10"
8"x12"
10"x12"
14"x16"
14"x16"
12"ø
8"x12"
40"x24"
4-CUH-4
14"ø
4 - TU3 - 1.50
REFER TO BUILDING
O5-IBN FOR
CONTIUNATION
"ø
14"ø
"x
"x
12"x14"
22"x20"
22"x20"
14"ø
20"x20"
12"x12"
14"x14"
30"x30"
4" DRYER
EXH DN
4" DRYER
EXH UP
8"x14"
"ø
10"ø
10"ø
16"x14"
12"x10" 12"x14"
16"x16"
"x
8"
8"x14"
4 - TU3 - 1.2
10"ø
12"ø
12"ø
10"ø
8"ø
11 12 08 09 13
03040506
Drawing Number
Building Number
Project NumberProject Title
Location
Date Checked Drawn
Drawing Title
Approved: Project Director
Key PlanCONSULTANTS:
DateRevisions
1 2 3 4 5 6 7 8 9 10 11 12
D
C
B
A
554-501REPLACEMENT MEDICAL CENTER
FACILITY, EASTERN COLORADO
HEALTH CARE SYSTEM
AURORA, COLORADO
N
C O
N
R
ES
D
AT
IB
S
IB
N
EN
C
C
LC
C
BN
C
BC
C
BS
PS
N
PV
N
PV
S
13 14
1 2 3 4 5 6 7 8 9 10 11 12 13 14
E
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
ARCHITECT/ENGINEERS:Professional Seal
6/
/2
3:
:3
PM
C :\U se rs
\C
AD
U se r 2 \D oc um en ts
\M H
-IB
S_ ch ar lo tte
.b la ck w oo d.
rv t
04-MH-101-1
LEVEL 1 INTERSTITIAL HVAC PLAN
INPATIENT BUILDING (SOUTH)
08/31/2012
0' 4' 8' 16' 32'0' 4' 8' 16' 32'
NORTH
1/8" = 1'-0"1
LEVEL 1 INTERSTITIAL HVAC
PLAN
UP
UP
M
M
M
M
M
M
M
A
A
B
B
C
C
D
D
E
E
F
F
G
G
H
H
J
J
RE
RF
RG
RH
RJ
RC
RB
RA
R1
R1
K
K
R2
R2
RD
HP-104
ELEV MACH RM
04-PH-D3-V4
HP-101
ELEV MACH RM
04-PH-A3-V4
HP-105
ELEC
04-PH-C1-E1
HP-107
ELEC
04-PH-D1-E2
HP-100
MECH
04-PH-A1-01
HP-103
HEATING EQUIP
RM
04-PH-B1-M1
MV SWITCHING
PV INVERTERMV
TRANSFORMERS
HP-102
VEST
04-PH-V1
HP-ST1
STAIR
04-PH-ST1
HE-S02
ELEV
04-PH-SE4
HP-ST2
STAIR
04-PH-ST2
/8 " C
LE
AR
M
AC
HI
NE
R
OO
M
2" C
LE
AR
M
AC
HI
NE
R
OO
M
8' - 7" CLEAR 6"
9' - 1"
ELEV. SE4 ELEV. SE3
04-AHU-6
04-AHU-4
04-FCU-1204-FCU-11
04-FCU-10
04-ERU-1
04-AHU-3
04-EF-07
04-FCU-9
4-AHU-5
04-AHU-2
04-FCU-8
04-AHU-1
04-EF-1
04-HWP-1
04-HWP-2
04-GWP-1
04-GWP-2
04-GPP-1
04-GPP-2
4-SWHX-1&2
4-SWHX-3&4
4-FCU-6
04-FCU-7
56"x20"
38"x34"
36"x48"
"x
36"x12"
"x
90"x30"
2" x3 6"
92"x27"
38"x48"36"x48"
"x
82"x3 6"
42"x28"
"x
2" x3 6"
"x
"x
50"x30"
18"x16"
30"x36"
30"x36"
"x
30"x28"
30"x36"
78"x36"
58"x42"
78"x36" 40 "x
56"x42"
36"x36"
126"x48"
40"x28"
132"x36"
"x
32"x36"
30"x142" 132"x142"
130"x50"
150"x42"
130"x50"
150"x42"
INSULATED PLENUM AT LOUVER.
SLOPED TOWARDS LOUVER, TYP.
MINIMUM 24" DEEP OR AS
NEEDED
FOR SIDE CONNECTION.
132"x142"
84"x142"
4" DRYER EXH
TO WALL CAP
4"ø
4" DRYER
EXH TO
WALL
CAP
04-EF-6
04-EF-5
04-EF-3
04-EF-4
4" DRYER EXH UP TO
ROOF, COORDINATE WITH
PV PANELS. PROVIDE
ELBOW WITH CAP AT
DISCHARGE.
TERMINATE DRYER CAP AT 2'-6"
ABOVE FINISHED ROOF IN RIB
OF PANEL SYSTEM, TYP.
04-EF-2
04-EF-8
22"ø
34"ø
04-HEPA1
22"ø
22"ø
18"ø
18"ø
04-HEPA2
20"ø
20"ø
18"x24"
SMOKE DAMPER
04-HEPA304-EF-10
04-EF-11 20"Ø
20"Ø
NORTH
11 12 08 09 13
03040506
Drawing Number
Building Number
Project NumberProject Title
Location
Date Checked Drawn
Drawing Title
Approved: Project Director
Key PlanCONSULTANTS:
DateRevisions
1 2 3 4 5 6 7 8 9 10 11 12
D
C
B
A
554-501REPLACEMENT MEDICAL CENTER
FACILITY, EASTERN COLORADO
HEALTH CARE SYSTEM
AURORA, COLORADO
N
C O
N
R
ES
D
AT
IB
S
IB
N
EN
C
C
LC
C
BN
C
BC
C
BS
PS
N
PV
N
PV
S
13 14
1 2 3 4 5 6 7 8 9 10 11 12 13 14
E
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
ARCHITECT/ENGINEERS:Professional Seal
/1
6/
:1 0:
P
M C
:\U se rs \C
AD
U se r 2
\D oc um en ts \M
H
-IB
S_ ch ar lo tte .b la ck w oo d.
rv t
04-MH-104
PENTHOUSE LEVEL HVAC PLAN
INPATIENT BUILDING (SOUTH)
08/03/2012
1/8" = 1'-0"1 PENTHOUSE LEVEL HVAC PLAN
0' 4' 8' 16' 32'0' 4' 8' 16' 32'
PLAN ISSUED TO INDICATE COIL CONNECTIONS TO AHU'S ONLY.
SEE MECHANICAL SCHEDULE SHEETS FOR EQUIPMENT
INCLUDED IN CDI NO. 11.
THIS ENTIRE DRAWING
HAS BEEN MODIFIED AS
PART OF CD NO. 12
| 01.MH.100-D Subcontractor As-built |
| 01.MH.100-D_JSI041 |
| 01.MH.101-D Subcontractor As-built |
| 01.MH.101-D_CD12 |
| 01.MH.102-D_CD12 |
| 04.MH.100.1 Subcontrator As-built (1) |
| 04.MH.100.1 |
| Sheets: 04-MH-100-1 - SERVICE LEVEL INTERSTITIAL HVAC PLAN |
| 04.MH.100 |
| Sheets: 04-MH-100 - SERVICE LEVEL HVAC PLAN |
| 04.MH.101.1 |
| Sheets: 04-MH-101-1 - LEVEL 1 INTERSTITIAL HVAC PLAN |
| 04.MH.104 Subcontrator As-built (1) |
| 04.MH.104 |
| Sheets: 04-MH-104 - PENTHOUSE LEVEL HVAC PLAN |
05.MH.101.1 Subcontractor As-built
File details come from the government source that posted it. Updated .