This document is an amendment to a solicitation for the supply and installation of five vertical lift module storage systems at a Defense Logistics Agency Distribution facility in Japan. The amendment provides responses to contractor questions to clarify requirements. The solicitation seeks a firm-fixed price contract for vertical lift modules measuring approximately 15 feet wide by 10 feet deep with tray capacities up to 1,540 pounds. Contractors must visit the site and are responsible for installing all electrical wiring from the building source to each unit. Insurance requirements include workers compensation, general liability, and automobile liability. The contract will be awarded by April 28, 2020 to the responsible contractor submitting a technically acceptable quote with fair and reasonable pricing.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
1. CONTRACT ID CODE
2. AMENDMENT/MODIFICAITON NO. 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQ. NO. 5. PROJECT NO. (If applicble)
7. ADMINISTERED BY (If other than Item 6) CODE
STANDARD FORM 30 (REV. 10-83)
Prescribed by GSA FAR (48 CFR) 53.243
FACILITY CODE
9A. AMENDMENT OF SOLICIATION NO.
9B. DATED (SEE ITEM 11)
10A. MODIFICATION OF CONTRACT/ORDER NO.
10B. DATED (SEE ITEM 11)
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended, is not extended.
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
(a)By completing items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment your desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPIRATION DATA (If required)
13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER
NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15C. DATE SIGNED
15A. NAME AND TITLE OF SIGNER (Type or print)
16C. DATE SIGNED
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
PAGE OF PAGES
6. ISSUED BY CODE
8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code) (X)
CODE
15B. CONTRACTOR/OFFEROR
(Signature of person authorized to sign)
16B. UNITED STATES OF AMERICA
(Signature of Contracting Officer)
NSN 7540-01-152-8070
Previous edition unusable
SP3300-20-Q-5015
AMENDMENT 0001
The purpose of this amendment is to answer contractor questions and incorporate a revised Statement of Work.
1. Question: Your very detailed and specific description in the solicitation for dual tray delivery is specific to one manufacturer, which is Modula. This renders the solicitation effectively a brand name only procurement, even though you have not labeled the Solicitation as so. In order to conduct a brand name only procurement, you are required to establish a Justification and Approval document providing detailed information about why the government must purchase from Modula and not any other vendor, which the government has not done in this case. Will you be either providing the J&A document for public review very soon or revising the solicitation (and your very Modula-specific description for dual tray delivery) to make this procurement brand name or equal? And, in establishing a BNOE procurement, DLA revise its descriptions to only require the salient physical, functional, and performance characteristics that are truly required by DLA?
1. Answer: The Government has performed extensive market research and there exist several companies that manufacture external, dual tray delivery system configurations. This type of delivery system is not unique to one manufacturer. DLA Distribution has a need for a VLM that provides the external dual tray delivery systems as these types of systems allow the operators to pick or stow from more than one tray at a time.
This feature provides ergonomic and unobstructed overhead access to the trays leading to a more efficient and safer workplace environment for workers.
2. Question: Your very detailed and specific description in the solicitation for tray dimensions is specific to one manufacturer, which is Modula. This renders the solicitation effectively a brand name only procurement, even though you have not labeled the Solicitation as so. In order to conduct a brand name only procurement, you are required to establish a Justification and Approval document providing detailed information about why the government must purchase from Modula and not any other vendor, which the government has not done in this case. Will you be either providing the J&A document for public review very soon or revising the solicitation (and your very Modula-specific description for tray dimensions) to make this procurement brand name or equal? And, in establishing a BNOE procurement, DLA revise its descriptions to only require the salient physical, functional, and performance characteristics that are truly
2. Answer: Tray dimensions have been revised. See revised SOW.
3. Question: Your very detailed and specific description in the solicitation for a "green device" is specific to one manufacturer, which is Modula. This renders the solicitation effectively a brand name only procurement, even though you have not labeled the Solicitation as so. In order to conduct a brand name only procurement, you are required to establish a Justification and Approval document providing detailed information about why the government must purchase from Modula and not any other vendor, which the government has not done in this case. Will you be either providing the J&A document for public review very soon or revising the solicitation (and your very Modula-specific description for a green device) to make this procurement brand name or equal? And, in establishing a BNOE procurement, DLA revise its descriptions to only require the salient physical, functional, and performance characteristics that are truly
3. Answer: DLA’s market research indicates that the vast majority of VLM manufacturers offer “Green Energy” features. DLA’s SOW directs vendors to propose energy efficient equipment as it is a best industry practice. See revised SOW.
4. Question: SOW 3.2.2.1 states tray depth of 34”. 3.2.2.6 states tray depth no less that 33”. Our tray depth is 33.74”. Acceptable?
4. Answer: Yes.
5. Question: SOW 3.2.2.6 states tray height should be 5”. Our tray height is 4.72” high. Acceptable?
5. Answer: Yes. See revised SOW.
6. Question: SOW 3.4: Is the requirement for the contractor to wire from the building source to the VLM locations? This is usually managed by the customer because of their familiarity with the facility. If you do require the contractor to do this, can you please indicate on the drawing where the building power source is and a recommended path for conduit?
6. Answer: Yes, the contractor is required to install all the necessary wiring and conduits from the building power source to each of the five (5) VLMs. There are no drawing available that show distribution panel locations for Building 1907. However, the distribution panel from which the contractor is to install the wiring and conduits from is approximately four hundred feet from where the VLMs are to be installed.
Conduits are to be installed in the ceiling.
7. Question: In order to determine the electrical SOW and the extent to which we will have to install electrical power distribution equipment, breakers, transformers, etc. how do we determine if the building has sufficient power and amperage to meet the 5 each VLMs prior to submitting our bid?
7. Answer: The power requirements for the VLMs have already been verified. The Navy Facilities Engineering department is currently installing a new distribution panel specifically for the VLMs.
8. Question: Is the owner to supply a source of power in close proximity to the VLM installation and the contractor then making a connection to a breaker box then to an emergency cutoff and then to the VLM?
8. Answer: Yes.
9. Question: Is it the intent that the contractor determine if the facility can accommodate the power requirements of the VLMs and then responsible for pulling power from the ‘outside line’ if necessary?
9. Answer: No. It is not the intent that the contractor determine if the facility can accommodate the power requirements of the VLMs. The power requirements for the VLMs have already been verified. The Navy Facilities Engineering department is currently installing a new distribution panel specifically for the VLMs.
The contractor is required to install all the necessary wiring and conduits from the building power source to each of the five (5) VLMs.
10. Question: In order for the structural engineer to determine if the existing slab is sufficient or requires modification to accommodate the seismic anchoring solution, we need know existing slab details, such as whether the floor is slab on grade, concrete PSI, and concrete depth- will these be made available and with sufficient time to allow for a structural engineer to evaluate?
10. Answer: All of the information requested is not available. The floor is slab on grade. Building 1907 was constructed to meet seismic zone 4 requirements. We previously had three (3) VLMs installed on the second floor for a number of years and had no issues.
11. Question: Is a 13’2.4” tray width x 32” tray depth acceptable, if the VLM external dimensions are 15’ width x 10’2” deep?
11. Answer: Yes.
12. Question: Does the owner require a 5” deep tray? A VLM tray can accommodate taller items, for example a 12” cardboard box can still be stored on a 4” deep tray.
12. Answer: The Government prefers a 5” deep tray. However, if the offeror is asking if a 4” deep tray is acceptable, the answer is yes. See revised SOW.
13. Question: Is a 5” deep metal tray required or is a 4” deep tray with 5” deep plastic or metal bins acceptable?
13. Answer: A 4” deep tray is acceptable. However, plastic or metal bins are not acceptable. See revised
SOW.
14. Question: Does the owner require a ‘kevlar reinforced toothed belt drive system’ or is a metal gear drive a suitable alternative for vertical tray movement in the central elevating corridor?
14. Answer: The Government prefers Kevlar reinforced toothed belt drive system. However, per the SOW, all vertical tray movement is to be accomplished through the use of steel or Kevlar® reinforced toothed belt drive system.
15. Question: Does the owner require external tray delivery for every tray delivery evolution? The Schaefer LOGIMAT VLM offers dual tray delivery INTERNAL to the sheet metal machine enclosure, however, an individual tray CAN BE delivered to an external cart if the user wishes to incorporate an overhead crane or hoist to remove objects from the tray. IF ergonomics and access to the bins/ back of the trays is the reason for external tray delivery; the LOGIMAT VLM offers trays that tilt towards the user to allow access to all areas of the tray.
15. Answer: Yes. The Government’s requirement is for an external, dual tray delivery system. Reference SOW Paragraph 3.2.2.3 EXTERNAL TRAY DELIVERY SYSTEM and 3.3.2.4 DUAL TRAY DELIVERY
16. Question: Is a maximum tray capacity of 1,540 lbs acceptable?
16. Answer: Yes. See revised SOW.
17. Question: Are durable, lightweight plastic dividers an acceptable replacement for heavier metal dividers?
17. Answer: No.
END OF AMENDMENT 0001
| Amend 0001 SP330016B0016 for FBO |
| SP3300-15-R-5004 0003 page 1 |
Amend 0001 Page 2
| IDCode: |
| Page: 1 |
| Pages: 4 |
| Text4: AMENDMENT/MODIFICATION NO. |
| AmendNo: 0001 |
| ReqNo: |
| ProjNo: |
| IssCode: SP3300 |
| IssuedBy: DLA Distribution |
Acquisition Operations, J-7 Mifflin Avenue, Bldg 430 New Cumberland, PA 17070
| AdmCode: |
| AdminBy: POC: Benjamin Bailey |
717-770-5390 (P) Benjamin.Bailey@DLA.MIL
| ContName: |
| ContStrt: |
| ContCnty: |
| ContSt: |
| ContZIP: |
| Code: |
| FacCode: |
| SolChgYs: Yes |
| SolChgNo: Off |
| SolAmdNo: SP3300-20-Q-5015 |
| AmendDate: 04/06/20 |
| ModNo: |
| ModDate: |
| NoCopies: 1 |
| Amended: Yes |
| OffrExt: Off |
| OffrNoEx: No |
| ChgeOrd: Off |
| ChgeOrder: |
| Modify: Off |
| SuppAgre: Off |
| SuppAuth: |
| ModOthr: Off |
| OthrSpec: |
| NoReq: Off |
| Require: Off |
| Copies: |
| Descript: SEE CONTINUATION PAGE(s) |
| SignName: |
| SignTitl: |
| ContDate: |
| CoName: |
| CoTitle: |
| CODate: |
| Text1: 28 April 2020 |
| Text2: |
| Text3: |