Section C - III(C) Tab Report Attachment.pdf
PDF 3 MB Posted
- Attached to
- Supply and Install 4 HVAC Units
- Solicitation number
- 75H71324Q00020
About this file
This test and balance report summarizes the results of testing and balancing four HVAC units at the Chemawa Indian Health Center Dental Area in Salem, Oregon. Key details include: testing and balancing was performed per NEBB standards and procedures on RTU-3 and RTU-4 to proportion outlets and inlets to within 10% of design airflow, with actual total supply airflow of 1145 CFM and 1450 CFM respectively; unit data, fan motor details, sheave configurations, and test pressures are provided for each unit; outlet and inlet summaries with design versus actual airflows are given. Deficiencies are noted but not the responsibility of the TAB firm to repair.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
- -Revision Date:
SEATTLE
5516 1 st Avenue South
Seattle, Washington 98108
Fax (206) 343-9820
Phone (206) 621-1810
PORTLAND
2501 SE Columbia Way, Suite 230
Vancouver, Washington 98661
Phone (503) 235-8924
Fax (503) 235-8925
Revision Number:
Project Completion Date:
NEUDORFER ENGINEERS INC.
TEST REPORT TYPE:
Chemawa Indian Health Center
12/30/20
BALANCE REPORT
Job Number: 2020-1153
Title Sheet 3
Report Certification 4
Terms 5
Instrument Calibration 6
Project Summary 7
TAB Data Sheets 8
Mechanical Prints 12
TABLE OF CONTENTS
Chemawa Indian Health Center
Project: Chemawa Indian Health Center
NEI Job#: 2020-1153
Mechanical Engineer:
Architect:
HVAC Contractor: Judson's
TAB Firm: Neudorfer Engineers Inc
Test Engineer:
2501 SE Columbia Way, Suite 230
Vancouver, Washington 98661
Phone (503) 235-8924
Fax (503) 235-8925
CERTIFIED TEST: BALANCE REPORT
REPORT TITLE
Philip Kuning
Fax (206) 343-9820
Phone (206) 621-1810
Seattle, Washington 98108
5516 1 st Ave South
NEBB TAB Firm:
Certification No: 3414
Expiration Date: March 31, 2021
Certification Date: March 31, 2019
(Date completed) Signed and Sealed by:
NEBB Supervisor: Mike Vawter P.E.
NEBB Supervisor: Eric Stotts
Neudorfer Engineers Inc
Submitted and Certified by:
CERTIFICATION
The data presented in this report is a record of system measurements and final adjustments that have been obtained in accordance with the current edition of the NEBB Procedural Standards for
Testing, Adjusting, and Balancing of Environmental Systems. Any variances from design quantities, which exceed NEBB tolerances, are noted in the Test-Adjust-Balance Report Project
Summary.
Significant / Noteworthy Remarks are noted on the General Remarks and General Field Notes pages. Other remarks are noted on individual test sheets.
Noted deficiencies are not the TAB firms responsibility to repair. Prior to issuance of this report, Deficiency Reports are forwarded to our contracted agent.
Warranty is limited to one year from date of this report. Within that time, any discrepancies, ambiguities, or omissions found in this report will be retested, adjusted, or balanced as needed. A written notification will be required.
Project: Chemawa Indian Health Center AC or ACU Air Conditioner or Air Conditioning Unit TDH Pressure Difference across the entering
AH or AHU Air Handler or Air Handling Unit and leaving side of a pump.
AVG Average HEPA High Efficiency Particulate Arrestance
BHP Brake Horsepower HP Horsepower
CAV Constant Air Volume HVAC Heating Ventilation and Air Conditioning
CBV Calbirated Balancing Valve HWS Heating Water Supply
(Circuit Setter) HWR Heating Water Return
CC Cooling Coil HX Heat Exchanger
CD Ceiling Diffuser HZ Hertz, cycle per second
in. inches
CFM Cubic Feet per Minute in.w.g. inches of water gauge
CH Chiller Kfactor Correction factor to the free area need to
CHWS Chilled Water Supply calculate CFM.
CHWR Chilled Water Return KW Kilowatts
LAT Leaving Air Temperature
CP Circulating Pump LWG Low Wall Grille
CR Ceiling Register LWR Low Wall Register
CRAC Computer Room Air Conditioner LWT Leaving Water Temperature
CRU Computer Room Unit MAU Make-up Air Hangling Unit
CT Cooling Tower MBH 1,000 BTUH
CU Condenser Unit N/A Not Applicable
CUH Cabinet Unit Heater OSA Outside Air
CWS Condenser Water Supply OBD Opposed Blade Damper
CWR Condenser Water Return ∆P Pressure Drop.
DAT Discharge Air Temperature PH Phase
DB Dyr Bulb PSI Pounds per Square Inch
DD Direct Drive RA Return Air
DDC Direct Digital Controls: EMS Control RAT Return Air Temperature
System for the HVAC RF Return Fan
Des. Design RH Relative Humidity
Dia. Diameter RHC Reheat Coil
Disch. Discharge RPM Revolutions per Minute
EA Exhaust Air RTU Roof Top Unit
EAT Entering Air Temperature SA Supply Air
Economizer Controls and components that allow an SAT Supply Air Temerature air handler to logically utilize outdoor air S.F. Service Factor for cooling as opposed to the use of SF Supply Fan mechanical cooling. SFD Smoke/Fire Damper
EF Exhaust Fan SP Static Pressure
EG Exhaust Grille sq.ft. square feet
EMCS Energy Management Control System Suct. Suction
ERU Energy Recovery Unit SWG Sidewall Grille
E.S.P. External Static Pressure SWR Sidewall Register
HRC Heat Recovery Coil TAB Test; Adjust; and Balance
EWT Entering Water Temperature TSP Total Static Pressure: Difference
FCU Fan Coil Unit between the entering and leaving
FD Fire Damper static pressure of a fan.
FLA Full Load Amperage: Maximum UH Unit Heater amperage a motor can draw. VAV Variable Air Volume; box that
Flow Hood Instrument that captures air and contains a motorized damper that converts the reading to CFM. modulates airflow.
FHT VD Volume Damper
FPB Fan Powered Box VFD Variable Frequency Drive
FPM Feet per Minute Velgrid Instrument that reads used to read
FR Field Report velocity in feet per minute.
FT Foot, Feet VVT Variable Volume Terminal
FTU Fan Terminal Unit WC Water Column
GPM Gallons per Minute W.G. Water Gauge
HC Heating Coil WB Wet Bulb
Fume Hood Test
TERMS AND ABBREVIATIONS
Instrument Type Air Data Meter with Flowhood Instrument Serial # M10465
Instrument Manufacturer Shortridge Calibration Date 10/17/2019
Instrument Model Number ADM 870C Calibration Due 10/16/2020
Instrument Type Differential Pressure Water Meter Instrument Serial # W10088
Instrument Manufacturer Shortridge Calibration Date 10/17/2019
Instrument Model Number HDM-250 Calibration Due 10/16/2020
Instrument Type Psychrometer Instrument Serial # 8084305
Instrument Manufacturer Extech Calibration Date 10/15/2019
Instrument Model Number RH390 Calibration Due 10/14/2020
Instrument Type Tachometer Instrument Serial # B185B5022P
Instrument Manufacturer Nidec Calibration Date 10/15/2019
Instrument Model Number MT-200 Calibration Due 10/14/2020
Instrument Type Amp Probe Instrument Serial # 33380179WS
Instrument Manufacturer Fluke Calibration Date 10/14/2019
Instrument Model Number 323 Clamp Meter Calibration Due 10/13/2020
Instrument Type Digital Thermometer Instrument Serial # 7190028
Instrument Manufacturer Fluke Calibration Date 10/14/2019
Instrument Model Number 52 Calibration Due 10/13/2020
Instrument Type Manometer Instrument Serial # M10465
Instrument Manufacturer Shortridge Calibration Date 10/17/2019
Instrument Model Number ADM 870C Calibration Due 10/16/2020
Instrument Type Thermal Anemometer Instrument Serial # AVM440742003
Instrument Manufacturer Alnor Instruments Calibration Date 10/16/2019
Instrument Model Number AVM 440 Calibration Due 10/15/2020
Instrument Type Ultrasonic Flow Meter Instrument Serial # N7G1992T
Instrument Manufacturer Fuji Calibration Date 10/16/2019
Instrument Model Number Portaflow-C Calibration Due 10/15/2020
INSTRUMENT CALIBRATIONS
Neudorfer Engineers Inc.
TEST & BALANCE REPORT SUMMARY
This project has been balanced per plans and specifications using the National Environmental Balancing
Bureau (NEBB) standards and procedures.
The fans were checked for data, operating amperage, voltage, rotation, and static pressure. All outlets and inlets were proportioned to +/- 10% of the actual total flow unless otherwise noted.
These units are constant volume. The economizer dampers actuate based on a 2-10 volt DC signal.
RTU-3 is set at 2.0 volts,. RTU-4 is set at 2.80 volts.
RTU-3
SA Design Total Flow – 1270 Actual Total Flow – 1145 (90%)
RA Design Total Flow – 1075 Actual Total Flow – 950 (88%)
RTU-4
SA Design Total Flow – 1600 Actual Total Flow – 1450 (91%)
RA Design Total Flow – 865 Actual Total Flow – 920 (106%)
Air Handling Unit
PROJECT:
LOCATION:
Chemawa Indian Health Center Dental Area COVID-19 Verification Salem, OR, 2020-1153PROJECT #:
DATE:
CONTACT:
AUTHOR:
1/18/2021 Philip Kuning Philip Kuning
Tested By: Philip Kuning Date: 1/18/2021
SYSTEM/UNIT: RTU-3
Log: RTU-3 12/14/2020 Philip Kuning (1) The volume damper is full open.
Unit Data Unit Manufacturer Carrier Unit Model Number LGA060H4BH5G Unit Serial Number 5606D12944
RTU-3/SF Filter Bank Filter Type Pleated Filter Quantity - Size 1 2 Filter Dimensions - Size 1 16x25x2
Test Data Unit SA Design Flow 1270 CFM Unit SA Actual Flow 1145 CFM RA Design Flow 1075 CFM RA Actual Flow 950 CFM
RTU-3/Supply Fan Motor Volts T1-T2 493 Volts Motor Volts T2-T3 490 Volts Motor Volts T1-T3 488 Volts Motor Amps T1 1.1 Amps Motor Amps T2 1.1 Amps Motor Amps T3 1.1 Amps
Motor Data RTU-3/Supply Fan
Drive Type Belt Drive Motor Manufacturer Emerson Motor HP 1 1/2 HP Motor RPM 1725 RPM Motor Rated Volts 200-230/460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 4.4/2.2 Amps Motor Service Factor 1.15
Sheave Data RTU-3/Supply Fan
Motor Sheave Diam. 3 3/4 OD Motor Sheave Bore 7/8 in.
Motor Sheave Type Adjustable Adj Mtr Sheave Pos Minimum Fan Sheave MFG Browning Fan Sheave Model AK58 Fan Sheave Bore 1 in.
Number of Belts 1 Belt Size AX44 Sheave Center Line 15 1/2 in.
Motor to Extend 3 in.
Motor to Retract 0 in.
Test Pressures OA Damper Pos 2.0 Volts
System/Unit Area Served Type of Reading
Outlet Type
Size LxW / D
AK Design Airflow
Prelim Airflow
Final Airflow
Final % Remarks
Outlet-01 Operatory A Flowhood CD 1.00 200 240 190 95 Outlet-02 Operatory A Flowhood CD 1.00 200 260 180 90 Outlet-03* Corridor Flowhood CD 1.00 250 175 190 76 (1) Outlet-04 Operatory C Flowhood CD 1.00 200 200 185 93 Outlet-05 Operatory C Flowhood CD 1.00 200 200 185 93 Outlet-06 Storage Flowhood CD 1.00 100 130 95 95 Outlet-07 Corridor Flowhood CD 1.00 120 130 120 100
Totals: - - - - 1270 1335 1145 90 -
RTU-3 Supply Outlet Summary
Log: RTU-3/Outlet-03 12/14/2020 Philip Kuning This diffuser is below -10% of design. The diffuser size is 6". If it were 8" or larger, it is likely it could achieve design flow.
Neudorfer Engineers, Inc.
LOCATION:
Chemawa Indian Health Center Dental Area COVID-19 Verification Salem, OR, 2020-1153PROJECT #:
DATE:
CONTACT:
AUTHOR:
1/18/2021 Philip Kuning Philip Kuning
System/Unit Area Served Type of Reading
Outlet Type
Size LxW / D
AK Design Airflow
Prelim Airflow
Final Airflow
Final % Remarks
Inlet-01 Operatory A Flowhood 1 235 135 190 81 (1) Inlet-02 Operatory A Flowhood 1 235 135 190 81 Inlet-03 Operatory C Flowhood 1 235 170 215 91 Inlet-04 Operatory C Flowhood 1 235 210 225 96 Inlet-05 Corridor Flowhood 1 135 195 130 96
Totals: - - - - 1075 845 950 88 -
RTU-3 Return Inlet Summary
LOCATION:
Chemawa Indian Health Center Dental Area COVID-19 Verification Salem, OR, 2020-1153PROJECT #:
DATE:
CONTACT:
AUTHOR:
1/18/2021 Philip Kuning Philip Kuning
Tested By: Philip Kuning Date: 1/18/2021
SYSTEM/UNIT: RTU-4
Log: RTU-4 12/14/2020 Philip Kuning (1) The volume damper is full open.
Unit Data Unit Manufacturer Carrier Unit Model Number LGA072H4BH2G Unit Serial Number 5606D12986
RTU-4/SF Filter Bank Filter Type Pleated Filter Quantity - Size 1 2 Filter Dimensions - Size 1 16x25x2
Test Data Unit SA Design Flow 1600 CFM Unit SA Actual Flow 1450 CFM RA Design Flow 865 CFM RA Actual Flow 920 CFM
RTU-4/Supply Fan Motor Volts T1-T2 493 Volts Motor Volts T2-T3 490 Volts Motor Volts T1-T3 488 Volts Motor Amps T1 1.4 Amps Motor Amps T2 1.4 Amps Motor Amps T3 1.4 Amps
Motor Data RTU-4/Supply Fan
Drive Type Belt Drive Motor Manufacturer Emerson Motor HP 1 1/2 HP Motor RPM 1725 RPM Motor Rated Volts 200-230/460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 4.4/2.2 Amps Motor Service Factor 1.15
Sheave Data RTU-4/Supply Fan
Motor Sheave Diam. 3 3/4 OD Motor Sheave Bore 7/8 in.
Motor Sheave Type Adjustable Adj Mtr Sheave Pos Minimum Fan Sheave MFG Browning Fan Sheave Model AK58 Fan Sheave Bore 1 in.
Number of Belts 1 Belt Size AX43 Sheave Center Line 15 1/2 in.
Motor to Extend 2 in.
Motor to Retract 2 in.
Test Pressures OA Damper Pos 2.80 Volts
System/Unit Area Served Type of Reading
Outlet Type
Size LxW / D
AK Design Airflow
Prelim Airflow
Final Airflow
Final % Remarks
Outlet-01 Entry Flowhood CD 1.00 150 130 150 100 Outlet-02 Operatory B Flowhood CD 1.00 200 160 180 90 Outlet-03 Operatory B Flowhood CD 1.00 200 130 170 85 (1) Outlet-04 Operatory B Flowhood CD 1.00 200 180 190 95 Outlet-05 Corridor Flowhood CD 1.00 170 160 160 94 Outlet-06 EXAM Flowhood CD 1.00 240 295 205 85 Outlet-07 EXAM Flowhood CD 1.00 240 225 210 88 Outlet-08 Storage Flowhood CD 1.00 100 85 90 90 Outlet-09 Corridor Flowhood CD 1.00 100 125 95 95
Totals: - - - - 1600 1490 1450 91 -
RTU-4 Supply Outlet Summary
LOCATION:
Chemawa Indian Health Center Dental Area COVID-19 Verification Salem, OR, 2020-1153PROJECT #:
DATE:
CONTACT:
AUTHOR:
1/18/2021 Philip Kuning Philip Kuning
System/Unit Area Served Type of Reading
Outlet Type
Size LxW / D
AK Design Airflow
Prelim Airflow
Final Airflow
Final % Remarks
Inlet-01 Operatory B Flowhood RG 1 235 265 250 106 Inlet-02 Operatory B Flowhood RG 1 235 300 255 109 Inlet-03 Operatory B Flowhood RG 1 235 355 255 109 Inlet-04 Storage Flowhood RG 1 160 160 160 100 (1)
Totals: - - - - 865 1080 920 106 -
RTU-4 Return Inlet Summary
Operatory A
Operatory C
Operatory B
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
Minimum Airflow Rates
1 2
2 3 4
| 1.pdf |
| 2.pdf |
| 3.pdf |
| 4.pdf |
| 5.pdf |
| 6.pdf |
| Chemawa Summary.pdf |
| Air Handling Unit |
| RTU-3 |
| RTU-4 |
| Chemawa TAB Prints.pdf |
| Current Configuration |
| Proposed Configuration |
| Proposed.vsdx |
| Page-1 |
| Ductwork Routing |
| Minimum Balance |
| Size and balance.vsdx |
| Page-1 |