Sample_Door_Typicals.pdf
PDF 947 KB Posted
- Attached to
- Hastings Branch Office Expansion Phase 2
- Solicitation number
- 2026-IFB-LM-0470
- Issued by
- Los Angeles County, California
About this file
This document is a technical specification sheet for door installation typicals prepared by Convergint Technologies LP for access control and security hardware integration. The file provides detailed installation guidelines for three standard door configurations: single doors with electrified lever locks, single doors with electrified panic hardware, and double doors with electrified panic hardware. Each typical includes plan and elevation views showing mounting locations, conduit routing, electrical box placement, and component specifications for the Hastings Branch Office Expansion Phase 2 project in Pasadena, California. The specifications establish minimum standards for conduit sizing (3/4 inch minimum), cable routing methods, junction box placement at accessible ceiling heights (42 inches above finished floor), and integration of components including card readers, door position switches, electrified locks, request-to-exit switches, and alarm contacts sourced from various contractors (S.C., E.C., D.H.C.).
The general notes and cable routing notes contained within the specifications require contractors to field-verify all conditions prior to installation, maintain fire ratings on fire-rated doors, coordinate mounting locations with building owners, and route cables through either free-air plenum-rated methods or minimum 1-inch conduit to access control panels. The document emphasizes that conduit and boxes shall be mounted on the secured side of portals unless otherwise noted and that conduit shall be concealed except where specifically indicated. All hardware shown is for reference purposes only, with actual hardware types subject to variation based on project requirements. The specifications are proprietary to Convergint Technologies LP and require written authorization for reproduction, with revision tracking fields for project engineer, project manager, and approval documentation.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIN. FLOOR
6 x 6 x 3 BOX W/ COVER
MOUNT ON SECURE SIDE
AT SERVICEABLE SPACE
(P.B.O.)
1" STUB OUT
W/ BUSHING
RUN CABLES TO
TERMINATION POINT
UTILIZING FREE-AIR
METHOD (U.N.O.)
CEILING
RECESSED
ALARM CONTACTS
PROVIDED BY S.C.
3/4" CONDUIT (P.B.O)
4"
18"
(8" MIN.)
3/4" CONDUIT
TYP. (P.B.O.)
CARD READER PROVIDED
BY S.C.O/ 4" SQ. BOX W/
SINGLE GANG TRIM (P.B.O.)
AT NON-SECURE SIDE
12"
" A
FF
MAX
CR
DPS
EL
REX
EPT
JB
SECURE SIDE
PLAN VIEW ELEVATION VIEW
TO ACP
CABLE ROUTED
THROUGH DOOR
POWER TRANSFER
DEVICE (P.B.O.)
3/4" CONDUIT
TYP. (P.B.O.)
ELECTRIFIED LOCK
W/ INTEGRATED RX
(P.B.O.)
4"
6"
ROUTE CONDUIT
INSIDE FRAME
CR
DPS
EL
JB
EPT
REX
CARD READER
DOOR POSITION SWITCH
ELECTRIC LOCK
JUNCTION BOX
ELECTRONIC POWER TRANSFER
REQUEST TO EXIT (IN HARDWARE)
SYMBOL LEGEND
CABLES TO TERMINATION
POINT UTILIZING CONDUIT
GENERAL NOTES:
1. VIEW SHOWN IS FROM SECURED SIDE OF PORTAL.
2. CONDUIT, BOXES SHALL BE MOUNTED ON SECURED
SIDE OF PORTAL, UNLESS OTHERWISE NOTED.
3. CONDUIT SHALL BE CONCEALED UNLESS
OTHERWISE NOTED
4. DOOR HARDWARE SHOWN FOR REFERENCE ONLY.
TYPE OF HARDWARE MAY VARY.
5. ALL CONDUIT SHALL BE 3/4" MINIMUM UNLESS
NOTED OTHERWISE
6. DETAIL REPRESENTS TYPICAL INSTALLATION. FIELD
VERIFY ALL CONDITIONS PRIOR TO INSTALLATION
7. DOOR SWING MAY DIFFER, FIELD VERIFY ACTUAL
CONDITION.
8. WORK PERFORMED AT FIRE RATED DOOR, TO
MAINTAIN FIRE RATING.
CABLE ROUTING NOTES:
1.A. PROVIDE 1" STUB-OUT W/ BUSHING FROM J-BOX
ABOVE DOOR FOR PLENUM RATED CABLES RUN
USING "FREE AIR" METHODS TO ACCESS CONTROL
PANEL. REFER TO PLANS FOR CABLE
TERMINATION POINTS.
1.B. PROVIDE MINIMUM 1" CONDUIT FROM J-BOX ABOVE
DOOR TO ACCESS CONTROL PANEL, NEAREST
DISTRIBUTION BOX, OR CABLE TRAY. REFER TO
PLANS FOR CABLE TERMINATION POINTS.
CABLE ROUTE OPTION
NON-SECURE
SIDE
***This document and the information/depictions contained/shown is the exclusive property of Convergint Technologies LP and shall be handled as proprietary and confidential information and must be returned upon request. This document cannot be reproduced by any means without the written authorization of Convergint Technologies LP.
JOB NUMBER:
PROJECT ENGINEER:
PROJECT MANAGER:
SCALE:
DRAWN BY:
REV DESCRIPTION APPROVEDDATE
DRAWING:CUSTOMER:
20 Centerpointe Dr. #120 La Palma, CA 90623 Phone: 714-546-2780 Fax: 714-546-2457
DATE:
TYPICAL SINGLE DOOR
DETAIL WITH ELECTRIFIED
LEVER
GENERAL NOTES:
1. VIEW SHOWN IS FROM SECURED SIDE OF PORTAL.
CONDUIT, BOXES AND EQUIPMENT SHALL BE
MOUNTED ON SECURED SIDE OF PORTAL, UNLESS
OTHERWISE NOTED.
2. CONDUITS MAY BE COMBINED. IF COMBINED,
CONTRACTOR SHALL ENSURE CONDUIT IS SIZED TO
ACCEPT REQUIRED CONDUCTORS.
3. COORDINATE MOUNTING LOCATIONS, ROUGH-IN
AND FINISHES WITH THE OWNER.
4. CONDUIT SHALL BE CONCEALED UNLESS
OTHERWISE NOTED
5. DOOR HARDWARE SHOWN FOR REFERENCE ONLY.
TYPE OF HARDWARE MAY VARY.
6. INTEGRAL REX SWITCH SHALL BYPASS DOOR ALARM
ONLY.
7. PROVIDE CONDUIT IN WALL ONLY WHERE WIRING
CANNOT BE ROUTED IN DOOR FRAME.
8. USE 3/4" CONDUIT FROM J-BOX TO DEVICE.
9. EXISTING BUILDINGS: SURVEY EA. LOCATION AND
VERIFY CONDITION AND UTILIZATION OF CABLES AT
EACH DEVICE.
ECB CRASH BAR W/ ELECTRIC LOCK
CABLE ROUTING NOTES:
1.A. PROVIDE 1" STUB-OUT W/ BUSHING FROM J-BOX ABOVE
DOOR FOR PLENUM RATED CABLES RUN USING "FREE
AIR" METHODS TO ACCESS CONTROL PANEL. REFER TO
PLANS FOR CABLE TERMINATION POINTS.
1.B. PROVIDE MINIMUM 1" CONDUIT FROM J-BOX ABOVE DOOR
TO ACCESS CONTROL PANEL, NEAREST DISTRIBUTION
BOX, OR CABLE TRAY. REFER TO PLANS FOR CABLE
TERMINATION POINTS.
CABLES TO TERMINATION
POINT UTILIZING CONDUIT
FINISHED FLOOR
6"x6"x4" J-BOX IN
ACCESSIBLE CEILING
SECURE SIDE
(PROVIDED BY E.C.)
3/4" CONDUIT
(PROVIDED BY E.C.)
3/4" CONDUIT
(PROVIDED BY E.C.)
ELECTRIC LOCK WITH
INTEGRATED RX
(PROVIDED BY D.H.C.)
CARD READER PROVIDED BY S.C.
OVER 4" SQ. BOX W/ SINGLE
GANG TRIM RING PROVIDED
(PROVIDED BY E.C.)
MAINTAIN FIRE RATING OF
WALL ASSEMBLY.
NON-SECURE SIDE
RECESSED
DOOR POSITION SENSOR
PROVIDED BY S.C.
" A
FF
8"
4"
FINISHED CEILING
TRANSFER HINGE
(PROVIDED BY D.H.C.)
ROUTE CONDUIT TO
6" ABOVE TRANSFER
HINGE
(PROVIDED BY D.H.C.)
3/4" CONDUIT
(PROVIDED BY E.C.)
TO ACP AS SCHEDULED
CR
DPS
EPT
JB
SECURE SIDE
PLAN VIEW
TO ACP
CR
DPS
JB
EPT
REX
CARD READER
DOOR POSITION SWITCH
JUNCTION BOX
ELECTRONIC POWER TRANSFER
REQUEST TO EXIT (IN HARDWARE)
SYMBOL LEGEND
NON-SECURE
SIDE
ECB
REX
ELECTRIFIED
CRASH BAR (P.B.O.)
ELEVATION VIEW
***This document and the information/depictions contained/shown is the exclusive property of Convergint Technologies LP and shall be handled as proprietary and confidential information and must be returned upon request. This document cannot be reproduced by any means without the written authorization of Convergint Technologies LP.
JOB NUMBER:
PROJECT ENGINEER:
PROJECT MANAGER:
SCALE:
DRAWN BY:
REV DESCRIPTION APPROVEDDATE
DRAWING:CUSTOMER:
20 Centerpointe Dr. #120 La Palma, CA 90623 Phone: 714-546-2780 Fax: 714-546-2457
DATE:
TYPICAL SINGLE DOOR
PANIC HARDWARE
RECESSED
ALARM CONTACTS
PROVIDED BY S.C.
4"
ELECTRIFIED
CRASH BAR (P.B.O.)FINISHED
FLOOR
6"x6"x4" J-BOX IN
ACCESSIBLE CEILING
(P.B.O) AT SECURE SIDE
3/4" CONDUIT
(P.B.O.)
3/4" CONDUIT
(P.B.O.)
CARD READER PROVIDED BY S.C.
OVER 4" SQ. BOX W/ SINGLE
GANG TRIM RING PROVIDED (P.B.O.).
NON-SECURE SIDE
RECESSED ALARM CONTACTS
PROVIDED BY S.C.
" A
FF
FINISHED CEILING
ROUTE CONDUIT TO
6" ABOVE TRANSFER
HINGE (P.B.O.)
TRANSFER HINGE
(P.B.O.)8"
4"
ALL CABLES TO
ACCESS CONTROL PANEL
THROUGH CONDUIT (P.B.O.)
ROUTE CONDUIT TO
6" ABOVE TRANSFER
HINGE
PATHWAY FROM JUNCTION
BOX TO HEADER
REQUIRED FOR ALARM
CONTACTS
TRANSFER HINGE
(P.B.O.)
CR
DPS
JB
SECURE SIDE
TO ACP
DPS
ECB
REX
EPT EPT
ECB
REX
ELEVATION VIEW
GENERAL NOTES:
1. VIEW SHOWN IS FROM SECURED SIDE OF PORTAL.
CONDUIT, BOXES AND EQUIPMENT SHALL BE
MOUNTED ON SECURED SIDE OF PORTAL, UNLESS
OTHERWISE NOTED.
2. CONDUITS MAY BE COMBINED. IF COMBINED,
CONTRACTOR SHALL ENSURE CONDUIT IS SIZED TO
ACCEPT REQUIRED CONDUCTORS.
3. COORDINATE MOUNTING LOCATIONS, ROUGH-IN
AND FINISHES WITH THE OWNER.
4. CONDUIT SHALL BE CONCEALED UNLESS
OTHERWISE NOTED
5. DOOR HARDWARE SHOWN FOR REFERENCE ONLY.
TYPE OF HARDWARE MAY VARY.
6. INTEGRAL REX SWITCH SHALL BYPASS DOOR ALARM
ONLY.
7. PROVIDE CONDUIT IN WALL ONLY WHERE WIRING
CANNOT BE ROUTED IN DOOR FRAME.
8. USE 3/4" CONDUIT FROM J-BOX TO DEVICE.
9. EXISTING BUILDINGS: SURVEY EA. LOCATION AND
VERIFY CONDITION AND UTILIZATION OF CABLES AT
EACH DEVICE.
CR
DPS
JB
EPT
REX
CARD READER
DOOR POSITION SWITCH
JUNCTION BOX
ELECTRONIC POWER TRANSFER
REQUEST TO EXIT (IN HARDWARE)
SYMBOL LEGEND
ECB CRASH BAR W/ ELECTRIC LOCK
CABLE ROUTING NOTES:
1.A. PROVIDE 1" STUB-OUT W/ BUSHING FROM J-BOX ABOVE
DOOR FOR PLENUM RATED CABLES RUN USING "FREE
AIR" METHODS TO ACCESS CONTROL PANEL. REFER TO
PLANS FOR CABLE TERMINATION POINTS.
1.B. PROVIDE MINIMUM 1" CONDUIT FROM J-BOX ABOVE DOOR
TO ACCESS CONTROL PANEL, NEAREST DISTRIBUTION
BOX, OR CABLE TRAY. REFER TO PLANS FOR CABLE
TERMINATION POINTS.
CABLES TO TERMINATION
POINT UTILIZING CONDUIT
3/4" CONDUIT
(P.B.O.)
***This document and the information/depictions contained/shown is the exclusive property of Convergint Technologies LP and shall be handled as proprietary and confidential information and must be returned upon request. This document cannot be reproduced by any means without the written authorization of Convergint Technologies LP.
JOB NUMBER:
PROJECT ENGINEER:
PROJECT MANAGER:
SCALE:
DRAWN BY:
REV DESCRIPTION APPROVEDDATE
DRAWING:CUSTOMER:
20 Centerpointe Dr. #120 La Palma, CA 90623 Phone: 714-546-2780 Fax: 714-546-2457
DATE:
TYPICAL DOUBLE DOOR
PANIC HARDWARE
| Sheets and Views |
| 2024.02.14 Door Det-A1-ELK SINGLE |
| 2024.02.14 Door Det-G1-PANIC SINGLE |
| 2024.02.14 Door Det-H1-PANIC DBL |
File details come from the government source that posted it. Updated .