S02-Attachment 1 M23125.docx
DOCX document 15 KB Posted
- Attached to
- J047--Bldg 200 Sub-Basement Mechanical Repairs Federal contract opportunity
- Solicitation number
- 36C25223Q0927
About this file
This document contains an attachment to a federal contract solicitation for mechanical repairs at Building 200. The attachment lists specific mechanical systems in need of repair, including replacing leaking relief valves, unions, sight glasses, and condensate lines. It also lists removing old piping, equipment, and sealing building penetrations. The related solicitation is for mechanical repairs in the sub-basement of Building 200 and involves replacing approximately 100 feet of 4-inch drain line with fittings, 400 feet of 3-inch cast iron pipe with fittings, 600 feet of 2-inch cast iron pipe with fittings, and adding cleanouts. It also involves replacing approximately 400 feet of 6-inch cast iron sanitary line with fittings, 800 feet of 4-inch cast iron pipe with fittings, and adding cleanouts. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 12.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| S02-Attachment 3 M23125 Site Plan.pdf | ||
| S02-Attachment 1 M23125 Sub-Base Needs.docx | DOCX document | |
| 36C25223Q0927 0003.docx | DOCX document | |
| S02-Attachment 4 Kitchen Drains (8).pdf | ||
| 36C25223Q0927 0002.docx | DOCX document | |
| S02-ATTACHMENT 6 -bldg 200 sec C stone space.pdf | ||
| 36C25223Q0927 0001.docx | DOCX document | |
| P07 - Cook County WD 2015-5017 (Rev-24) dated 07.07.2023.pdf | ||
| S02-ATTACHMENT 4 -2-7-2-1754 Basement Part Plan C.pdf | ||
| S02-ATTACHMENT 3-2-7-2-1753 Basement Part Plan B.pdf | ||
| S02-ATTACHMENT 2-Basement Part Plan A.pdf | ||
| 36C25223Q0927.docx | DOCX document | |
| S02-ATTACHMENT 5 -2-7-2-1755 Basement Part Plan D.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COLUMN
DESCRIPTION
| A-10 |
| REPLACE RELIEF VALVE @ STEAM STATION - LEAKING / WEAK SPRING |
| L-12 |
| LEAK @ UNION ON PUMPING TRAP / REPLACE SIGHT GLASS (2) |
| D-10 |
| 1-1/2" UNION LEAK HP STEAM TO AC100 HUM. |
| G-3 |
| REPLACE RELIEF VALVE @ STEAM STATION - LEAKING / WEAK SPRING |
| L-3 |
| RECONNECT BROKEN CONDENSATE LINE AFTER TRAPSET |
| J-3 / J-4 |
| PINHOLE LEAK@ LP CONDENSATE RETURN ( AB ON PIPE) |
| M-7 |
| 1-1/4" UNION LEAK (LP COND RETURN) ELIMINATE UNION |
| M-7 |
| REMOVE OLD HW BOOSTER AND PUMPIMG TRAP (DEAD EQUIPMENT) |
| N-7 |
| 1-1/4" UNION LEAK (LP COND RETURN) ELIMINATE UNION |
| C-10 |
| REMOVE OLD PIPING FOR "50" BUILDINGS SEAL PENETRATIONS |
| Q-8 |
| HOT WATER LEAK @ CAP |
| R-3 |
| REPLACE / REPIPE SUMP PUMP |
| Q-2 |
| REPLACE/REPIPE DUAL PUMP WITH SINGLE 2" GRINDER AND NEW LID |
| L-3 |
| REPLACE/ REPIPE SUMP PUMP |
| K-6 |
| REPLACE/ REPIPE SUMP PUMP |
| CONV TUNNEL |
| REPLACE/ REPIPE SUMP PUMP |
| B-8 |
| CLOGGED OPEN SITE DRAIN / REPLACE LINE (not in kitchen area) |
| D-8 |
| REPAIR STEAM LINE DRIP LEG |
| D-8 |
| REPAIR CONDENSATE LINE |
| Under Kitchen & Lab |
| Demo/Replace Drain line 100' x 4" cast w/ (15) 4" fittings; |
400' x 3" cast w/ (45) 3" fittings;
600' x 2" cast w/ (160) 2" fittings;
Add cleanouts
| Bldg 200 Main Sanitary Line |
| 400' x 6" cast w/ (65) 6" fittings; 800' x 4" cast w/ (85) 4" fittings; add cleanouts |
File details come from the government source that posted it. Updated .