S02-Attachment 1 M23125 Sub-Base Needs.docx

DOCX document 16 KB Posted

Attached to
J047--Bldg 200 Sub-Basement Mechanical Repairs Federal contract opportunity
Solicitation number
36C25223Q0927
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 12

About this file

This document outlines mechanical repair needs for the sub-basement of Building 200 at a Department of Veterans Affairs medical center. Key repair and replacement needs include relieving leaking steam station valves, replacing leaking unions on steam and condensate lines, eliminating leaking unions, removing abandoned conveyor equipment, and replacing sump pumps. The related federal contract opportunity is solicitation number 36C25223Q0927 from the VA Veterans Health Administration VISN 12 for mechanical repairs to meet the sub-basement needs described in the attachment. The solicitation seeks bids for repairs to address leaking, clogged, and faulty steam, condensate and plumbing systems, including replacing valves, unions, lines and pumps.

View the file

Other files for this federal contract opportunity

Other files attached to J047--Bldg 200 Sub-Basement Mechanical Repairs, newest first.
File Type Posted
36C25223Q0927 0003.docx DOCX document
S02-Attachment 3 M23125 Site Plan.pdf PDF
S02-Attachment 4 Kitchen Drains (8).pdf PDF
36C25223Q0927 0002.docx DOCX document
S02-ATTACHMENT 6 -bldg 200 sec C stone space.pdf PDF
36C25223Q0927 0001.docx DOCX document
P07 - Cook County WD 2015-5017 (Rev-24) dated 07.07.2023.pdf PDF
S02-ATTACHMENT 4 -2-7-2-1754 Basement Part Plan C.pdf PDF
S02-ATTACHMENT 2-Basement Part Plan A.pdf PDF
36C25223Q0927.docx DOCX document
S02-ATTACHMENT 3-2-7-2-1753 Basement Part Plan B.pdf PDF
S02-ATTACHMENT 5 -2-7-2-1755 Basement Part Plan D.pdf PDF
S02-Attachment 1 M23125.docx DOCX document
Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COLUMN

(match to As Builts)

DESCRIPTION
CLIN
A-10
REPLACE RELIEF VALVE @ STEAM STATION - LEAKING / WEAK SPRING
1
L-12
LEAK @ UNION ON PUMPING TRAP / REPLACE SIGHT GLASS (2)
1
D-10
1-1/2" UNION LEAK HP STEAM TO AC100 HUM.
1
G-3
REPLACE RELIEF VALVE @ STEAM STATION - LEAKING / WEAK SPRING
1
L-3
RECONNECT BROKEN CONDENSATE LINE AFTER TRAPSET
1
J-3 / J-4
PINHOLE LEAK@ LP CONDENSATE RETURN ( AB ON PIPE)
1
M-7
1-1/4" UNION LEAK (LP COND RETURN) ELIMINATE UNION
1
M-7
REMOVE OLD HW BOOSTER AND PUMPIMG TRAP (DEAD EQUIPMENT)
3
Hallway separating quadrant D-C
REMOVE 120’ OF ABANDONED CONVEYOR SYSTEM
3
N-7
1-1/4" UNION LEAK (LP COND RETURN) ELIMINATE UNION
1
Q-8
HOT WATER LEAK @ CAP
2
R-3
REPLACE / REPIPE SUMP PUMP
2
½ hp; 110 volts; cast iron body; integral float switch
Q-2
REPLACE/REPIPE DUAL PUMP WITH SINGLE 2" GRINDER AND NEW LID
2
½ hp; 110 volts; cast iron body; integral float switch
L-3
REPLACE/ REPIPE SUMP PUMP
2
½ hp; 110 volts; cast iron body; integral float switch
K-6
REPLACE/ REPIPE SUMP PUMP
2
½ hp; 110 volts; cast iron body; integral float switch
CONV TUNNEL
REPLACE/ REPIPE SUMP PUMP
2
½ hp; 110 volts; cast iron body; integral float switch
B-8
CLOGGED OPEN SITE DRAIN / REPLACE LINE (not in kitchen area)
2
D-8
REPAIR STEAM LINE DRIP LEG
1
D-8
REPAIR CONDENSATE LINE
1
K-6
REPLACE CONDENSATE VALVES
1
R-4/R-5
REPLACE CONDENSATE LINE
1

Under Kitchen & Lab S-10 to J-10 through S-3 to J-3