S02 - Attachment 01 - Drawings Replace Plumbing (68 pages).pdf

PDF 15 MB Posted

Attached to
J045--Replace Plumbing Systems in Bldg. 64 Federal contract opportunity
Solicitation number
36C24822R0194
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8

About this file

This document outlines a federal solicitation to replace plumbing systems in Building 64 at the Lake City Veterans Affairs Medical Center in Lake City, Florida. The solicitation seeks to remove and replace the existing overhead horizontal sanitary mains and branches in the basement level ceiling space to address problems caused by the poor condition of the existing piping. Work must be completed according to the provided specifications and construction drawings and minimize downtime. A mandatory site visit is scheduled for October 18, 2022 at 10:00 AM EST where attendees will park in the visitors lot and meet in Conference Room B11-19 of Building 19. The solicitation is issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8.

View the file

Other files for this federal contract opportunity

Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VA PROJECT NO. 573A4-18-600

REPLACE PLUMBING SYSTEMS IN BUILDING 64

LAKE CITY

VETERANS AFFAIRS MEDICAL CENTER

PROJECT LOCATION MAP

VICINITY MAP

PROJECT LOCATION

VICINITY MAP

LAKE CITY, FL

NOT TO SCALE

VAMC

PROJECT

LOCATION

247 N www.abovegroupinc.com COA/CA Lic. No. 31120

305 East Dr. Suite H, Melbourne, Florida 32904

PH: 321.345.9026

LAKE CITY VA MEDICAL CENTER

619 S MARION AVE, LAKE CITY, FL 32025

DESIGNED FOR: DESIGNED BY:

K

LE DA

IV

S

P R

O F

ESS ION A L ENG

I N

E E

R

L I CENSE

F

LO R I D A

STATE OF

No. 84275

Y J.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

C U s e rs \a z g o d a \D o c u m e n ts \0

R e p la c e

P lu m b in g

S y s te m s B ld g

P

R a z g o d a .R

V T

/2

/2

:0

:4

P

M

CS-001

COVER SHEET

REPLACE PLUMBING

SYSTEMS IN BLDG. 64

Lake City, Florida

573A4-18-600

PAUL DRAKE

08/27/2021 KJD JAR

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

KYLE J. DAVIS, P.E.

FL License #84275

INDEX OF DRAWINGS

Sheet

Discipline

Sheet

Number Sheet Name

GENERAL CS-001 COVER SHEET

ARCHITECTURE G101 LIFE SAFETY & PHASING PLANS

ARCHITECTURE G102 LIFE SAFETY & PHASING PLANS

ARCHITECTURE G103 LIFE SAFETY & PHASING PLANS

ARCHITECTURE G104 LIFE SAFETY & PHASING PLANS

ARCHITECTURE G105 LIFE SAFETY & PHASING PLANS

ARCHITECTURE G106 LIFE SAFETY & PHASING PLANS

ARCHITECTURE G107 LIFE SAFETY & PHASING PLANS

ARCHITECTURE G108 LIFE SAFETY & PHASING PLANS

ARCHITECTURE G109 LIFE SAFETY & PHASING PLANS

ARCHITECTURE G110 LIFE SAFETY & PHASING PLANS

ARCHITECTURE G111 LIFE SAFETY & PHASING PLANS

PLUMBING PL-001 PLUMBING LEGENDS, NOTES, SPECIFICATIONS & SYMBOLS

PLUMBING PL-101 BLDG. 64 UNIT A SANITARY - OVERALL DEMO

PLUMBING PL-102 BLDG. 64 UNIT B SANITARY - OVERALL DEMO

PLUMBING PL-201 BLDG. 64 UNIT A SANITARY - PHASE 1

PLUMBING PL-202 BLDG. 64 UNIT A SANITARY - PHASE 1 PHOTOS

PLUMBING PL-203 BLDG. 64 UNIT A SANITARY - PHASE 2

PLUMBING PL-204 BLDG. 64 UNIT A SANITARY - PHASE 2 PHOTOS

PLUMBING PL-205 BLDG. 64 UNIT A SANITARY - PHASE 3

PLUMBING PL-206 BLDG. 64 UNIT A SANITARY - PHASE 3 PHOTOS

PLUMBING PL-207 BLDG. 64 UNIT A SANITARY - PHASE 4

PLUMBING PL-208 BLDG. 64 UNIT A SANITARY - PHASE 4 ISOMETRIC

PLUMBING PL-209 BLDG. 64 UNIT A SANITARY - PHASE 4 PHOTOS

PLUMBING PL-210 BLDG. 64 UNIT A SANITARY - PHASE 5

PLUMBING PL-211 BLDG. 64 UNIT A SANITARY - PHASE 5 PHOTOS

PLUMBING PL-212 BLDG. 64 UNIT A SANITARY - PHASE 6

PLUMBING PL-213 BLDG. 64 UNIT A SANITARY - PHASE 6 PHOTOS

PLUMBING PL-214 BLDG. 64 UNIT B SANITARY - PHASE 7

PLUMBING PL-215 BLDG. 64 UNIT B SANITARY - PHASE 7 PHOTOS

PLUMBING PL-216 BLDG. 64 UNIT B SANITARY - PHASE 8

PLUMBING PL-217 BLDG. 64 UNIT B SANITARY - PHASE 8 PHOTOS

PLUMBING PL-218 BLDG. 64 UNIT B SANITARY - PHASE 9

PLUMBING PL-219 BLDG. 64 UNIT B SANITARY - PHASE 9 PHOTOS

PLUMBING PL-220 BLDG. 64 UNIT B SANITARY - PHASE 10

PLUMBING PL-221 BLDG. 64 UNIT B SANITARY - PHASE 10 PHOTOS

PLUMBING PL-222 BLDG. 64 UNIT B SANITARY - PHASE 11

PLUMBING PL-223 BLDG. 64 UNIT B SANITARY - PHASE 11 PHOTOS

PLUMBING PL-224 RISER SCHEDULES

PLUMBING PL-225 RISER SCHEDULES

PLUMBING PL-226 RISER SCHEDULES

PLUMBING PL-227 RISER SCHEDULES

PLUMBING PL-228 RISER SCHEDULES

PLUMBING PL-301 BLDG. 64 - BASEMENT - UNIT A ROOMS AFFECTED BY PHASE

PLUMBING PL-302 BLDG. 64 - FIRST FLOOR - UNIT A ROOMS AFFECTED BY PHASE

PLUMBING PL-303 BLDG. 64 - SECOND FLOOR - UNIT A ROOMS AFFECTED BY PHASE

PLUMBING PL-304 BLDG. 64 - THIRD FLOOR - UNIT A ROOMS AFFECTED BY PHASE

PLUMBING PL-305 BLDG. 64 - FOURTH FLOOR - UNIT A ROOMS AFFECTED BY PHASE

PLUMBING PL-306 BLDG. 64 - BASEMENT - UNIT B ROOMS AFFECTED BY PHASE

PLUMBING PL-307 BLDG. 64 - SECOND FLOOR - UNIT B ROOMS AFFECTED BY PHASE

PLUMBING PL-308 BLDG. 64 - THIRD FLOOR - UNIT B ROOMS AFFECTED BY PHASE

PLUMBING PL-309 BLDG. 64 - FOURTH FLOOR - UNIT B ROOMS AFFECTED BY PHASE

PLUMBING PL-310 BLDG. 64 UNIT A SANITARY - OVERALL DEMO PHASE 1

PLUMBING PL-311 BLDG. 64 UNIT A SANITARY - OVERALL DEMO PHASE 2

PLUMBING PL-312 BLDG. 64 UNIT A SANITARY - OVERALL DEMO PHASE 3

PLUMBING PL-313 BLDG. 64 UNIT A SANITARY - OVERALL DEMO PHASE 4

PLUMBING PL-314 BLDG. 64 UNIT A SANITARY - OVERALL DEMO PHASE 5

PLUMBING PL-315 BLDG. 64 UNIT A SANITARY - OVERALL DEMO PHASE 6

PLUMBING PL-316 BLDG. 64 UNIT B SANITARY - OVERALL DEMO PHASE 7

PLUMBING PL-317 BLDG. 64 UNIT B SANITARY - OVERALL DEMO PHASE 8

PLUMBING PL-318 BLDG. 64 UNIT B SANITARY - OVERALL DEMO PHASE 9

PLUMBING PL-319 BLDG. 64 UNIT B SANITARY - OVERALL DEMO PHASE 10

PLUMBING PL-320 BLDG. 64 UNIT B SANITARY - OVERALL DEMO PHASE 11

PLUMBING PL-401 PLUMBING DETAILS

PLUMBING PL-501 PLUMBING SCHEDULES

ELECTRICAL E-001 ELECTRICAL LEGEND AND GENERAL NOTES

ELECTRICAL EP-101 BLDG . 64 - BASEMENT - UNIT A ELECTRICAL PLAN

ELECTRICAL EP-102 BLDG . 64 - BASEMENT - UNIT B ELECTRICAL PLAN

Revisions: Date:

AB24

AB03

P-1/64

P-2/64

S-4/64

S-3/64

C B

AB22B

AB21 AB13

AB19

ABO8B

ABO5C

ABO5E

ABO5D

ABO5B

C B

AB28

AB29

AB22D

AB23

AB22C

AB23A

AB21B

AB27

AB22

AB26

AB22A

AB21A

AB21C AB21D

AB18B

AB18C AB18D

AB18A

AB16

AB14

AB15

AB17

AB19A

AB17A

AB12

AB11

AB25ABO5A

ABO5

ABO8A ABO8

ABO6ABO7A

ABO7

ABO4

ABO2

ABO1

ABO9

AB10

ABO6A

ABO9A

AB11A

AB12A

AB12B

C B

CB-4

CB-3

CB-3

C B

AB28

AB29

BB03A

C B

AB28A

C15

C8

C7A

C7

MECH.

RM.

STAIR

STAIR

STAIR

F.A.C.

UTIL.

TUNNEL/AREAWAY

OFC.

LINEN

CHUTE

GAS

STERILE & NON-STERILE

STORAGE

PREP. &

STERILIZATION

SOILED

RECIEVING

DECONTAMINATION

STOR.

TISSUE

STOR.

SPDFEM.

TOIL.

MORT.

REFRIG.

HAC

STORAGE

S.TOIL.

ELEC.

TECH. COMP.

SPEC.

LEAD.

SPEC.

CORRIDOR

LINEN

CHUTE

IRMS

STOR.

EMS

STOR.

EMS.

SUPRINT

DEC.

SUPR.

MECH.

RM.

EMS

STOR.

PATIENT

CLOTHINGROOM

F.A.C.

EL.CL.

SPD

MALETOIL

S V C E L E V

L O B B Y

AUTOPSY

ROOM

MECH

RM.

MECH. EQUIP.

RM.

A/C

SHOP LINEN

FORMS

FIRE ALARM

SYSTEMENG.

STORAGE

EMS

STOR.

CONFERANCE

ROOM

EMS

STOR.

MECH.

ROOM

FORMS

STORAGE

EMS

STOR. SUPR.

OFC.

EMS

STORAGESIGN

SHOP

DISPATCH

EMS

STOR.

CHUTE

MECH.

STOR.

CORRIDOR

CORRIDOR

STEAM

ROOM

STORAGE

MASONRY

SHOP

C O R R

ID

O R

P A S S .E L E V

L O B B Y

C O R R

ID

O R

DISPATCH

CHIEF

SPD CLERICAL

SPD

C O R R

ID

O R

RECIEVING

SPD

CLEAN

STORAGE

SPD STERILE & NON

STERILE

STAIR

SUPR.

0-HR Smoke Partition - NFPA 101 - 8.4

1-HR Smoke Barrier - NFPA 101 - 8.5

1-HR Fire Barrier - NFPA 101 - 8.3

2-HR Fire Barrier - NFPA 101 - 8.3

Means of Egress

Existing Wall to Remain

Proposed Temporary Wall Location - Wall Type T1.0

CODE LEGEND

T1.0

9.21

9.02

9.80

9.45

4 1/4"

STRUCTURE ABOVE

FIN. CEILING

FLOOR SLAB

9.45

CONSTRUCTION SIDE CLEAN SIDE

JOHN

A.

POE

IO

HO

FOET

A T

S

R E G I S

E T

R

ED RA

C H

TI

E C T

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

VA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management www.abovegroupinc.com COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

/2

/2

:4

:1

P

M

REPLACE PLUMBING

SYSTEMS IN BLDG. 64

08/27/2021

LIFE SAFETY& PHASING PLANS

G101

NSJR

573A4-18-600

Lake City, Florida

PAUL DRAKE

100% CONSTRUCTION

DOCUMENTS

N Scale: 1/8" = 1'-0"

CODE PLAN - PHASE 1

GENERAL PHASING NOTES

A. Temporary partition to structural deck above. If temporary partition cannot be built to deck due to utilities above the ceiling a fire retardant plastic may be used from the suspended ceiling to the structural deck to seal up construction area and enable a negative air construction zone.

B. Coordinate all work involving the generation of excessive noise so as to occur during non-peak operating hours, 1000 to 1600 daily.

Activities to occur during this time include, but are not limited to saw cutting, jack hammering, hammer drilling and core drilling. If there is any question as to whether an operation should occur during this time the Contractor will contact the COR.

C. Coordinate phase completion with requirements as set for by COR to maintain daily operations to near as normal as possible.

D. Coordinate access to all phases of construction, deliveries, and debris removal with the COR. See General Requirements.

E. Temporary door locations and sizes are as required by the General Contractor. Doors will interfere with daily operations as little as possible. All temporary doors shall be accessible to maintenance personnel to gain access to maintenance rooms inside construction areas. Coordinate final door locations with COR.

F. All existing doors to surrounding a construction phase must be sealed to prevent the passage of smoke. Install plastic zipper walls at all entrances to construction phases.

G. Existing utilities shall remain in operation during construction.

H. Provide and maintain negative air pressure inside construction zone.

I. All marked exits shall be maintained throughout construction. If an exit is required to be blocked temporary signage must be installed to direct to the nearest exit. Coordinate closing of exits with COR.

J. Verify proper fire stopping is installed at penetrations of rated walls.

Scale: 1" = 1'-0"

TEMPORARY PARTITION TYPE

9.02 3 5/8" non-structural metal framing @ 16" o.c.

9.21 5/8" Type X gypsum board.

9.45 Flame-retardant plastic sheeting sealed to create negative air pressure inside work zone.

9.80 Acoustic insulation

NOTES

Revisions Date

P-1/64

P-2/64

S-4/64

S-3/64

C B

AB22B

AB21 AB13

AB19

ABO8B

ABO5C

ABO5E

ABO5D

ABO5B

C B

AB28

AB29

AB22D

AB23

AB22C

AB23A

AB21B

AB27

AB22

AB26

AB22A

AB21A

AB21C AB21D

AB18B

AB18C AB18D

AB18A

AB16

AB14

AB15

AB17

AB19A

AB17A

AB12

AB11

AB25ABO5A

ABO5

ABO8A ABO8

ABO6ABO7A

ABO7

ABO4

ABO2

ABO1

ABO9

AB10

ABO6A

ABO9A

AB11A

AB12A

AB12B

C B

CB-4

CB-3

CB-3

C B

AB28

AB29

BB03A

C B

AB28A

C15

C8

C7A

C7

AB20B

MECH.

RM.

STAIR

STAIR

STAIR

F.A.C.

UTIL.

TUNNEL/AREAWAY

OFC.

LINEN

CHUTE

GAS

STERILE & NON-STERILE

STORAGE

PREP. &

STERILIZATION

SOILED

RECIEVING

DECONTAMINATION

STOR.

TISSUE

STOR.

SPDFEM.

TOIL.

MORT.

REFRIG.

HAC

STORAGE

S.TOIL.

ELEC.

TECH. COMP.

SPEC.

LEAD.

SPEC.

CORRIDOR

LINEN

CHUTE

IRMS

STOR.

EMS

STOR.

EMS.

SUPRINT

DEC.

SUPR.

MECH.

RM.

EMS

STOR.

PATIENT

CLOTHINGROOM

F.A.C.

EL.CL.

SPD

MALETOIL

S V C E L E V

L O B B Y

AUTOPSY

ROOM

MECH

RM.

MECH. EQUIP.

RM.

A/C

SHOP LINEN

FORMS

FIRE ALARM

SYSTEMENG.

STORAGE

EMS

STOR.

CONFERANCE

ROOM

EMS

STOR.

MECH.

ROOM

FORMS

STORAGE

EMS

STOR. SUPR.

OFC.

EMS

STORAGESIGN

SHOP

DISPATCH

EMS

STOR.

CHUTE

MECH.

STOR.

CORRIDOR

CORRIDOR

STEAM

ROOM

STORAGE

MASONRY

SHOP

C O R R

ID

O R

P A S S .E L E V

L O B B Y

C O R R

ID

O R

DISPATCH

CHIEF

SPD CLERICAL

SPD

C O R R

ID

O R

RECIEVING

SPD

CLEAN

STORAGE

SPD STERILE & NON

STERILE

STAIR

RECPT.

EMS.

ASST.CHIEF

SUPR.

0-HR Smoke Partition - NFPA 101 - 8.4

1-HR Smoke Barrier - NFPA 101 - 8.5

1-HR Fire Barrier - NFPA 101 - 8.3

2-HR Fire Barrier - NFPA 101 - 8.3

Means of Egress

Existing Wall to Remain

Proposed Temporary Wall Location - Wall Type T1.0

CODE LEGEND

JOHN

A.

POE

IO

HO

FOET

A T

S

R E G I S

E T

R

ED RA

C H

TI

E C T

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

VA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management www.abovegroupinc.com COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

/2

/2

:4

:1

P

M

REPLACE PLUMBING

SYSTEMS IN BLDG. 64

08/27/2021

LIFE SAFETY& PHASING PLANS

G102

NSJR

573A4-18-600

Lake City, Florida

PAUL DRAKE

100% CONSTRUCTION

DOCUMENTS

N Scale: 1/8" = 1'-0"

CODE PLAN - PHASE 2

GENERAL PHASING NOTES

A. Temporary partition to structural deck above. If temporary partition cannot be built to deck due to utilities above the ceiling a fire retardant plastic may be used from the suspended ceiling to the structural deck to seal up construction area and enable a negative air construction zone.

B. Coordinate all work involving the generation of excessive noise so as to occur during non-peak operating hours, 1000 to 1600 daily.

Activities to occur during this time include, but are not limited to saw cutting, jack hammering, hammer drilling and core drilling. If there is any question as to whether an operation should occur during this time the Contractor will contact the COR.

C. Coordinate phase completion with requirements as set for by COR to maintain daily operations to near as normal as possible.

D. Coordinate access to all phases of construction, deliveries, and debris removal with the COR. See General Requirements.

E. Temporary door locations and sizes are as required by the General Contractor. Doors will interfere with daily operations as little as possible. All temporary doors shall be accessible to maintenance personnel to gain access to maintenance rooms inside construction areas. Coordinate final door locations with COR.

F. All existing doors to surrounding a construction phase must be sealed to prevent the passage of smoke. Install plastic zipper walls at all entrances to construction phases.

G. Existing utilities shall remain in operation during construction.

H. Provide and maintain negative air pressure inside construction zone.

I. All marked exits shall be maintained throughout construction. If an exit is required to be blocked temporary signage must be installed to direct to the nearest exit. Coordinate closing of exits with COR.

J. Verify proper fire stopping is installed at penetrations of rated walls.

P-1/64

P-2/64

S-4/64

S-3/64

C B

AB22B

AB21 AB13

AB19

ABO8B

ABO5C

ABO5E

ABO5D

ABO5B

C B

AB28

AB29

AB22D

AB28A

AB23

AB22C

AB23A

AB21B

AB27

AB22

AB26

AB22A

AB21A

AB21C AB21D

AB18B

AB18C AB18D

AB18A

AB16

AB14

AB15

AB17

AB19A

AB17A

AB12

AB11

AB25ABO5A

ABO5

ABO8A ABO8

ABO6ABO7A

ABO7

ABO4

ABO2

ABO1

ABO9

AB10

ABO6A

ABO9A

AB11A

AB12A

AB12B

C B

CB-4

CB-3

CB-3

C B

AB28

AB29

BB03A

BB03

C B

AB28B

BB06

AB28A

C B

C15

C8

CB-3 CB-3

C7A

C7

AB20B

MECH.

RM.

STAIR

STAIR

STAIR

F.A.C.

UTIL.

TUNNEL/AREAWAY

OFC.

LINEN

CHUTE

GAS

STERILE & NON-STERILE

STORAGE

PREP. &

STERILIZATION

SOILED

RECIEVING

DECONTAMINATION

STOR.

TISSUE

STOR.

SPDFEM.

TOIL.

MORT.

REFRIG.

HAC

STORAGE

S.TOIL.

ELEC.

TECH. COMP.

SPEC.

LEAD.

SPEC.

CORRIDOR

LINEN

CHUTE

IRMS

STOR.

EMS

STOR.

EMS.

SUPRINT

DEC.

SUPR.

MECH.

RM.

EMS

STOR.

PATIENT

CLOTHINGROOM

F.A.C.

EL.CL.

SPD

MALETOIL

S V C E L E V

L O B B Y

AUTOPSY

ROOM

MECH

RM.

MECH. EQUIP.

RM.

A/C

SHOP LINEN

FORMS

FIRE ALARM

SYSTEMENG.

STORAGE

EMS

STOR.

CONFERANCE

ROOM

EMS

STOR.

MECH.

ROOM

FORMS

STORAGE

EMS

STOR. SUPR.

OFC.

EMS

STORAGESIGN

SHOP

DISPATCH

EMS

STOR.

CHUTE

MECH.

STOR.

CORRIDOR

CORRIDOR

STEAM

ROOM

STORAGE

MASONRY

SHOP

C O R R

ID

O R

P A S S .E L E V

L O B B Y

C O R R

ID

O R

DISPATCH

CHIEF

SPD CLERICAL

SPD

C O R R

ID

O R

RECIEVING

SPD

CLEAN

STORAGE

SPD STERILE & NON

STERILE

STAIR

CORRIDOR CORRIDOR

RECPT.

EMS.

ASST.CHIEF

SUPR.

0-HR Smoke Partition - NFPA 101 - 8.4

1-HR Smoke Barrier - NFPA 101 - 8.5

1-HR Fire Barrier - NFPA 101 - 8.3

2-HR Fire Barrier - NFPA 101 - 8.3

Means of Egress

Existing Wall to Remain

Proposed Temporary Wall Location - Wall Type T1.0

CODE LEGEND

JOHN

A.

POE

IO

HO

FOET

A T

S

R E G I S

E T

R

ED RA

C H

TI

E C T

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

VA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management www.abovegroupinc.com COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

/2

/2

:4

:1

P

M

REPLACE PLUMBING

SYSTEMS IN BLDG. 64

08/27/2021

LIFE SAFETY& PHASING PLANS

G103

NSJR

573A4-18-600

Lake City, Florida

PAUL DRAKE

100% CONSTRUCTION

DOCUMENTS

N Scale: 1/8" = 1'-0"

CODE PLAN - PHASE 3

GENERAL PHASING NOTES

A. Temporary partition to structural deck above. If temporary partition cannot be built to deck due to utilities above the ceiling a fire retardant plastic may be used from the suspended ceiling to the structural deck to seal up construction area and enable a negative air construction zone.

B. Coordinate all work involving the generation of excessive noise so as to occur during non-peak operating hours, 1000 to 1600 daily.

Activities to occur during this time include, but are not limited to saw cutting, jack hammering, hammer drilling and core drilling. If there is any question as to whether an operation should occur during this time the Contractor will contact the COR.

C. Coordinate phase completion with requirements as set for by COR to maintain daily operations to near as normal as possible.

D. Coordinate access to all phases of construction, deliveries, and debris removal with the COR. See General Requirements.

E. Temporary door locations and sizes are as required by the General Contractor. Doors will interfere with daily operations as little as possible. All temporary doors shall be accessible to maintenance personnel to gain access to maintenance rooms inside construction areas. Coordinate final door locations with COR.

F. All existing doors to surrounding a construction phase must be sealed to prevent the passage of smoke. Install plastic zipper walls at all entrances to construction phases.

G. Existing utilities shall remain in operation during construction.

H. Provide and maintain negative air pressure inside construction zone.

I. All marked exits shall be maintained throughout construction. If an exit is required to be blocked temporary signage must be installed to direct to the nearest exit. Coordinate closing of exits with COR.

P-1/64

P-2/64

S-4/64

S-3/64

C B

AB22B

AB21 AB13

AB19

ABO8B

ABO5C

ABO5E

ABO5D

ABO5B

C B

AB28

AB29

AB22D

AB28A

AB23

AB22C

AB23A

AB21B

AB27

AB22

AB26

AB22A

AB21A

AB21C AB21D

AB18B

AB18C AB18D

AB18A

AB16

AB14

AB15

AB17

AB19A

AB17A

AB12

AB11

AB25ABO5A

ABO5

ABO8A ABO8

ABO6ABO7A

ABO7

ABO4

ABO2

ABO1

ABO9

AB10

ABO6A

ABO9A

AB11A

AB12A

AB12B

C B

CB-4

CB-3

CB-3

C B

AB28

AB29

BB03A

BB03

C B

AB28B

BB06

AB28A

C B

C15

C8

CB-3 CB-3

C7A

C7

AB20B

MECH.

RM.

STAIR

STAIR

STAIR

F.A.C.

UTIL.

TUNNEL/AREAWAY

OFC.

LINEN

CHUTE

GAS

STERILE & NON-STERILE

STORAGE

PREP. &

STERILIZATION

SOILED

RECIEVING

DECONTAMINATION

STOR.

TISSUE

STOR.

SPDFEM.

TOIL.

MORT.

REFRIG.

HAC

STORAGE

S.TOIL.

ELEC.

TECH. COMP.

SPEC.

LEAD.

SPEC.

CORRIDOR

LINEN

CHUTE

IRMS

STOR.

EMS

STOR.

EMS.

SUPRINT

DEC.

SUPR.

MECH.

RM.

EMS

STOR.

PATIENT

CLOTHINGROOM

F.A.C.

EL.CL.

SPD

MALETOIL

S V C E L E V

L O B B Y

AUTOPSY

ROOM

MECH

RM.

MECH. EQUIP.

RM.

A/C

SHOP LINEN

FORMS

FIRE ALARM

SYSTEMENG.

STORAGE

EMS

STOR.

CONFERANCE

ROOM

EMS

STOR.

MECH.

ROOM

FORMS

STORAGE

EMS

STOR. SUPR.

OFC.

EMS

STORAGESIGN

SHOP

DISPATCH

EMS

STOR.

CHUTE

MECH.

STOR.

CORRIDOR

CORRIDOR

STEAM

ROOM

STORAGE

MASONRY

SHOP

C O R R

ID

O R

P A S S .E L E V

L O B B Y

C O R R

ID

O R

DISPATCH

CHIEF

SPD CLERICAL

SPD

C O R R

ID

O R

RECIEVING

SPD

CLEAN

STORAGE

SPD STERILE & NON

STERILE

STAIR

CORRIDOR CORRIDOR

RECPT.

EMS.

ASST.CHIEF

SUPR.

0-HR Smoke Partition - NFPA 101 - 8.4

1-HR Smoke Barrier - NFPA 101 - 8.5

1-HR Fire Barrier - NFPA 101 - 8.3

2-HR Fire Barrier - NFPA 101 - 8.3

Means of Egress

Existing Wall to Remain

Proposed Temporary Wall Location - Wall Type T1.0

CODE LEGEND

JOHN

A.

POE

IO

HO

FOET

A T

S

R E G I S

E T

R

ED RA

C H

TI

E C T

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

VA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management www.abovegroupinc.com COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

/2

/2

:4

:1

P

M

REPLACE PLUMBING

SYSTEMS IN BLDG. 64

08/27/2021

LIFE SAFETY & PHASING PLANS

G104

NSJR

573A4-18-600

Lake City, Florida

PAUL DRAKE

100% CONSTRUCTION

DOCUMENTS

N Scale: 1/8" = 1'-0"

CODE PLAN - PHASE 4

GENERAL PHASING NOTES

A. Temporary partition to structural deck above. If temporary partition cannot be built to deck due to utilities above the ceiling a fire retardant plastic may be used from the suspended ceiling to the structural deck to seal up construction area and enable a negative air construction zone.

B. Coordinate all work involving the generation of excessive noise so as to occur during non-peak operating hours, 1000 to 1600 daily.

Activities to occur during this time include, but are not limited to saw cutting, jack hammering, hammer drilling and core drilling. If there is any question as to whether an operation should occur during this time the Contractor will contact the COR.

C. Coordinate phase completion with requirements as set for by COR to maintain daily operations to near as normal as possible.

D. Coordinate access to all phases of construction, deliveries, and debris removal with the COR. See General Requirements.

E. Temporary door locations and sizes are as required by the General Contractor. Doors will interfere with daily operations as little as possible. All temporary doors shall be accessible to maintenance personnel to gain access to maintenance rooms inside construction areas. Coordinate final door locations with COR.

F. All existing doors to surrounding a construction phase must be sealed to prevent the passage of smoke. Install plastic zipper walls at all entrances to construction phases.

G. Existing utilities shall remain in operation during construction.

H. Provide and maintain negative air pressure inside construction zone.

I. All marked exits shall be maintained throughout construction. If an exit is required to be blocked temporary signage must be installed to direct to the nearest exit. Coordinate closing of exits with COR.

P-1/64

P-2/64

S-4/64

S-3/64

C B

AB22B

AB21 AB13

AB19

ABO8B

ABO5C

ABO5E

ABO5D

ABO5B

C B

AB28

AB29

AB22D

AB28A

AB23

AB22C

AB23A

AB21B

AB27

AB22

AB26

AB22A

AB21A

AB21C AB21D

AB18B

AB18C AB18D

AB18A

AB16

AB14

AB15

AB17

AB19A

AB17A

AB12

AB11

AB25ABO5A

ABO5

ABO8A ABO8

ABO6ABO7A

ABO7

ABO4

ABO2

ABO1

ABO9

AB10

ABO6A

ABO9A

AB11A

AB12A

AB12B

C B

CB-4

CB-3

CB-3

C B

AB28

AB29

BB03A

BB03

C B

AB28B

BB06

AB28A

C B

C15

C8

CB-3 CB-3

C7A

C7

AB20B

MECH.

RM.

STAIR

STAIR

STAIR

F.A.C.

UTIL.

TUNNEL/AREAWAY

OFC.

LINEN

CHUTE

GAS

STERILE & NON-STERILE

STORAGE

PREP. &

STERILIZATION

SOILED

RECIEVING

DECONTAMINATION

STOR.

TISSUE

STOR.

SPDFEM.

TOIL.

MORT.

REFRIG.

HAC

STORAGE

S.TOIL.

ELEC.

TECH. COMP.

SPEC.

LEAD.

SPEC.

CORRIDOR

LINEN

CHUTE

IRMS

STOR.

EMS

STOR.

EMS.

SUPRINT

DEC.

SUPR.

MECH.

RM.

EMS

STOR.

PATIENT

CLOTHINGROOM

F.A.C.

EL.CL.

SPD

MALETOIL

S V C E L E V

L O B B Y

AUTOPSY

ROOM

MECH

RM.

MECH. EQUIP.

RM.

A/C

SHOP LINEN

FORMS

FIRE ALARM

SYSTEMENG.

STORAGE

EMS

STOR.

CONFERANCE

ROOM

EMS

STOR.

MECH.

ROOM

FORMS

STORAGE

EMS

STOR. SUPR.

OFC.

EMS

STORAGESIGN

SHOP

DISPATCH

EMS

STOR.

CHUTE

MECH.

STOR.

CORRIDOR

CORRIDOR

STEAM

ROOM

STORAGE

MASONRY

SHOP

C O R R

ID

O R

P A S S .E L E V

L O B B Y

C O R R

ID

O R

DISPATCH

CHIEF

SPD CLERICAL

SPD

C O R R

ID

O R

RECIEVING

SPD

CLEAN

STORAGE

SPD STERILE & NON

STERILE

STAIR

CORRIDOR CORRIDOR

RECPT.

EMS.

ASST.CHIEF

SUPR.

0-HR Smoke Partition - NFPA 101 - 8.4

1-HR Smoke Barrier - NFPA 101 - 8.5

1-HR Fire Barrier - NFPA 101 - 8.3

2-HR Fire Barrier - NFPA 101 - 8.3

Means of Egress

Existing Wall to Remain

Proposed Temporary Wall Location - Wall Type T1.0

CODE LEGEND

JOHN

A.

POE

IO

HO

FOET

A T

S

R E G I S

E T

R

ED RA

C H

TI

E C T

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

VA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management www.abovegroupinc.com COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

/2

/2

:4

:1

P

M

REPLACE PLUMBING

SYSTEMS IN BLDG. 64

08/27/2021

LIFE SAFETY & PHASING PLANS

G105

NSJR

573A4-18-600

Lake City, Florida

PAUL DRAKE

100% CONSTRUCTION

DOCUMENTS

GENERAL PHASING NOTES

A. Temporary partition to structural deck above. If temporary partition cannot be built to deck due to utilities above the ceiling a fire retardant plastic may be used from the suspended ceiling to the structural deck to seal up construction area and enable a negative air construction zone.

B. Coordinate all work involving the generation of excessive noise so as to occur during non-peak operating hours, 1000 to 1600 daily.

Activities to occur during this time include, but are not limited to saw cutting, jack hammering, hammer drilling and core drilling. If there is any question as to whether an operation should occur during this time the Contractor will contact the COR.

C. Coordinate phase completion with requirements as set for by COR to maintain daily operations to near as normal as possible.

D. Coordinate access to all phases of construction, deliveries, and debris removal with the COR. See General Requirements.

E. Temporary door locations and sizes are as required by the General Contractor. Doors will interfere with daily operations as little as possible. All temporary doors shall be accessible to maintenance personnel to gain access to maintenance rooms inside construction areas. Coordinate final door locations with COR.

F. All existing doors to surrounding a construction phase must be sealed to prevent the passage of smoke. Install plastic zipper walls at all entrances to construction phases.

G. Existing utilities shall remain in operation during construction.

H. Provide and maintain negative air pressure inside construction zone.

I. All marked exits shall be maintained throughout construction. If an exit is required to be blocked temporary signage must be installed to direct to the nearest exit. Coordinate closing of exits with COR.

J. Verify proper fire stopping is installed at penetrations of rated walls.

N Scale: 1/8" = 1'-0"

CODE PLAN - PHASE 5

P-1/64

P-2/64

S-4/64

S-3/64

C B

AB22B

AB21 AB13

AB19

ABO8B

ABO5C

ABO5E

ABO5D

ABO5B

C B

AB28

AB29

AB22D

AB28A

AB23

AB22C

AB23A

AB21B

AB27

AB22

AB26

AB22A

AB21A

AB21C AB21D

AB18B

AB18C AB18D

AB18A

AB16

AB14

AB15

AB17

AB19A

AB17A

AB12

AB11

AB25ABO5A

ABO5

ABO8A ABO8

ABO6ABO7A

ABO7

ABO4

ABO2

ABO1

ABO9

AB10

ABO6A

ABO9A

AB11A

AB12A

AB12B

C B

CB-4

CB-3

CB-3

C B

AB28

AB29

BB03A

BB03

C B

AB28B

BB06

AB28A

C8

CB-3 CB-3

C7A

C7

AB18G

AB20B AB20 AB20A

AB18

AB

18F

MECH.

RM.

STAIR

STAIR

STAIR

F.A.C.

UTIL.

TUNNEL/AREAWAY

OFC.

LINEN

CHUTE

GAS

STERILE & NON-STERILE

STORAGE

PREP. &

STERILIZATION

SOILED

RECIEVING

DECONTAMINATION

STOR.

TISSUE

STOR.

SPDFEM.

TOIL.

MORT.

REFRIG.

HAC

STORAGE

S.TOIL.

ELEC.

TECH. COMP.

SPEC.

LEAD.

SPEC.

CORRIDOR

LINEN

CHUTE

IRMS

STOR.

EMS

STOR.

EMS.

SUPRINT

DEC.

SUPR.

MECH.

RM.

EMS

STOR.

PATIENT

CLOTHINGROOM

F.A.C.

EL.CL.

SPD

MALETOIL

S V C E L E V

L O B B Y

AUTOPSY

ROOM

MECH

RM.

MECH. EQUIP.

RM.

LINEN

FORMS

FIRE ALARM

SYSTEMENG.

STORAGE

EMS

STOR.

CONFERANCE

ROOM

EMS

STOR.

MECH.

ROOM

FORMS

STORAGE

EMS

STOR. SUPR.

OFC.

EMS

STORAGESIGN

SHOP

DISPATCH

EMS

STOR.

CHUTE

MECH.

STOR.

CORRIDOR

CORRIDOR

STEAM

ROOM

STORAGE

MASONRY

SHOP

C O R R

ID

O R

P A S S .E L E V

L O B B Y

C O R R

ID

O R

DISPATCH

CHIEF

SPD CLERICAL

SPD

C O R R

ID

O R

RECIEVING

SPD

CLEAN

STORAGE

SPD STERILE & NON

STERILE

CORRIDOR CORRIDOR

CLASS

ROOM

CHIEF

EMS

RECPT.

EMS.

ASST.CHIEF SECT./RECPT.

SUPR.

0-HR Smoke Partition - NFPA 101 - 8.4

1-HR Smoke Barrier - NFPA 101 - 8.5

1-HR Fire Barrier - NFPA 101 - 8.3

2-HR Fire Barrier - NFPA 101 - 8.3

Means of Egress

Existing Wall to Remain

Proposed Temporary Wall Location - Wall Type T1.0

CODE LEGEND

JOHN

A.

POE

IO

HO

FOET

A T

S

R E G I S

E T

R

ED RA

C H

TI

E C T

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

VA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management www.abovegroupinc.com COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

/2

/2

:4

:1

P

M

REPLACE PLUMBING

SYSTEMS IN BLDG. 64

08/27/2021

LIFE SAFETY & PHASING PLANS

G106

NSJR

573A4-18-600

Lake City, Florida

PAUL DRAKE

100% CONSTRUCTION

DOCUMENTS

N Scale: 1/8" = 1'-0"

CODE PLAN - PHASE 6

GENERAL PHASING NOTES

A. Temporary partition to structural deck above. If temporary partition cannot be built to deck due to utilities above the ceiling a fire retardant plastic may be used from the suspended ceiling to the structural deck to seal up construction area and enable a negative air construction zone.

B. Coordinate all work involving the generation of excessive noise so as to occur during non-peak operating hours, 1000 to 1600 daily.

Activities to occur during this time include, but are not limited to saw cutting, jack hammering, hammer drilling and core drilling. If there is any question as to whether an operation should occur during this time the Contractor will contact the COR.

C. Coordinate phase completion with requirements as set for by COR to maintain daily operations to near as normal as possible.

D. Coordinate access to all phases of construction, deliveries, and debris removal with the COR. See General Requirements.

E. Temporary door locations and sizes are as required by the General Contractor. Doors will interfere with daily operations as little as possible. All temporary doors shall be accessible to maintenance personnel to gain access to maintenance rooms inside construction areas. Coordinate final door locations with COR.

F. All existing doors to surrounding a construction phase must be sealed to prevent the passage of smoke. Install plastic zipper walls at all entrances to construction phases.

G. Existing utilities shall remain in operation during construction.

H. Provide and maintain negative air pressure inside construction zone.

I. All marked exits shall be maintained throughout construction. If an exit is required to be blocked temporary signage must be installed to direct to the nearest exit. Coordinate closing of exits with COR.

A O V

AB28A

BB25

CB-14

BB27

BB28

BB29

BB26

BB24

BB23BB22

BB26A

BB03A

BB03

CB-7

BB02

BB01

BB04 BB05

BB16

BB07

BB16A

BB20

BB19

BB21 BB21C

BB18

BB17

BB18A

C B

C B

C B

F-5/64

AB28B

BB06

BB14

BB14A

BB15

BB13

BB11A

C B

BB12B

CB-10

BB12

BB11

BB12A

BB10

BB09

BB09A

CB-10

BB10A

BB08

AB30

C B

C10B

C10

C10

C9A

C B A

C9

C9

C9CC9B

C9D

C B

CB-3

C6E C6D C6C

C6B

C6F

C6

C6G

CB-3

C7A

C5

C6A C6

C4

C1

CB-1

C2

C6K

C6H C6J

STAIR

CORRIDOR

M.

TOILET

WELLNESS

CENTER

F.

TOILET

R.M.S.

STORAGE

R.M.S.

STORAGE

H.A.C.F.A.C.

MECH.

ROOM

(UNEXCAVATED)

MECH.

ROOM

CHIEF

SPD CLERICAL

SPD

CORRIDOR

MALE

TOIL,

CL.

LINEN

FEM.

TOIL,

HAC

SPD

STORAGE

T.M.E.R.

SHOP

T.M.E.R.

SHOP

SPD

STORAGE

FREEZER #

M.A.S.

STOR.

E.M.S.

STOR.

ENG.

DIETETICS

STORAGE

D

IE

T E L E V

L O B B Y

C O R R

ID

O R

C O R R

ID

O R

HAC

RECIEVING

SPD

CLEAN

HVAC

MECH.

ROOM

REFRIG.

MECH.

ROOM

EMS

EQUIP.

CLEANING

FREEZER #

C O R R

ID

O R

MEDICAL

MEDIACAMERA

ROOM

CORRIDOR

M.M.

OFC

REFRIG #

PROCESS

ROOM

M.M.

FILM

ILLUS.

RM.

M.M.

REFRIG, #

CORRIDOR

M.M.

EQ.

STOR.DIETETIC

COOLER #

MECH.

RM.

HVAC

STORAGE

SPD STERILE & NON

STERILE

C O R R

ID

O R

C

ORRIDOR

C O R R

ID

O R

CORRIDOR CORRIDOR

C B

C O R R

ID

O R

ELEV.

LOBBY

PASS.

0-HR Smoke Partition - NFPA 101 - 8.4

1-HR Smoke Barrier - NFPA 101 - 8.5

1-HR Fire Barrier - NFPA 101 - 8.3

2-HR Fire Barrier - NFPA 101 - 8.3

Means of Egress

Existing Wall to Remain

Proposed Temporary Wall Location - Wall Type T1.0

CODE LEGEND

JOHN

A.

POE

IO

HO

FOET

A T

S

R E G I S

E T

R

ED RA

C H

TI

E C T

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

VA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management www.abovegroupinc.com COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

/2

/2

:4

:1

P

M

REPLACE PLUMBING

SYSTEMS IN BLDG. 64

08/27/2021

LIFE SAFETY & PHASING PLANS

G107

NSJR

573A4-18-600

Lake City, Florida

PAUL DRAKE

100% CONSTRUCTION

DOCUMENTS

N Scale: 1/8" = 1'-0"

CODE PLAN - PHASE 7

GENERAL PHASING NOTES

A. Temporary partition to structural deck above. If temporary partition cannot be built to deck due to utilities above the ceiling a fire retardant plastic may be used from the suspended ceiling to the structural deck to seal up construction area and enable a negative air construction zone.

B. Coordinate all work involving the generation of excessive noise so as to occur during non-peak operating hours, 1000 to 1600 daily.

Activities to occur during this time include, but are not limited to saw cutting, jack hammering, hammer drilling and core drilling. If there is any question as to whether an operation should occur during this time the Contractor will contact the COR.

C. Coordinate phase completion with requirements as set for by COR to maintain daily operations to near as normal as possible.

D. Coordinate access to all phases of construction, deliveries, and debris removal with the COR. See General Requirements.

E. Temporary door locations and sizes are as required by the General Contractor. Doors will interfere with daily operations as little as possible. All temporary doors shall be accessible to maintenance personnel to gain access to maintenance rooms inside construction areas. Coordinate final door locations with COR.

F. All existing doors to surrounding a construction phase must be sealed to prevent the passage of smoke. Install plastic zipper walls at all entrances to construction phases.

G. Existing utilities shall remain in operation during construction.

H. Provide and maintain negative air pressure inside construction zone.

I. All marked exits shall be maintained throughout construction. If an exit is required to be blocked temporary signage must be installed to direct to the nearest exit. Coordinate closing of exits with COR.

V

AB28A

BB25

CB-14

BB27

BB28

BB29

BB26

BB24

BB23BB22

BB26A

BB03A

BB03

CB-7

BB02

BB01

BB04 BB05

BB16

BB07

BB16A

BB20

BB19

BB21 BB21C

BB18

BB17

BB18A

C B

C B

C B

F-5/64

AB28B

BB06

BB14

BB14A

BB15

BB13

BB11A

C B

BB12B

CB-10

BB12

BB11

BB12A

BB10

BB09

BB09A

CB-10

BB10A

BB08

AB30

C B

C10B

C10

C10

C9A

C B A

C9

C9

C9CC9B

C9D

C B

CB-3

C6E C6D C6C

C6B

C6F

C6

C6G

CB-3

C5

C6A C6

C4

C1

CB-1

C2

C6K

C6H C6J

STAIR

CORRIDOR

M.

TOILET

WELLNESS

CENTER

F.

TOILET

R.M.S.

STORAGE

R.M.S.

STORAGE

H.A.C.F.A.C.

MECH.

ROOM

(UNEXCAVATED)

MECH.

ROOM

SPD

CORRIDOR

MALE

TOIL,

CL.

LINEN

FEM.

TOIL,

HAC

SPD

STORAGE

T.M.E.R.

SHOP

T.M.E.R.

SHOP

SPD

STORAGE

FREEZER #

M.A.S.

STOR.

E.M.S.

STOR.

ENG.

DIETETICS

STORAGE

D

IE

T E L E V

L O B B Y

C O R R

ID

O R

C O R R

ID

O R

HAC

SPD

HVAC

MECH.

ROOM

REFRIG.

MECH.

ROOM

EMS

EQUIP.

CLEANING

FREEZER #

C O R R

ID

O R

MEDICAL

MEDIACAMERA

ROOM

CORRIDOR

M.M.

OFC

REFRIG #

PROCESS

ROOM

M.M.

FILM

ILLUS.

RM.

M.M.

REFRIG, #

CORRIDOR

M.M.

EQ.

STOR.DIETETIC

COOLER #

MECH.

RM.

HVAC

SPD STERILE & NON

C O R R

ID

O R

C

ORRIDOR

C O R R

ID

O R

CORRIDOR CORRIDOR

C B

C O R R

ID

O R

ELEV.

LOBBY

PASS.

0-HR Smoke Partition - NFPA 101 - 8.4

1-HR Smoke Barrier - NFPA 101 - 8.5

1-HR Fire Barrier - NFPA 101 - 8.3

2-HR Fire Barrier - NFPA 101 - 8.3

Means of Egress

Existing Wall to Remain

Proposed Temporary Wall Location - Wall Type T1.0

CODE LEGEND

JOHN

A.

POE

IO

HO

FOET

A T

S

R E G I S

E T

R

ED RA

C H

TI

E C T

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

VA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management www.abovegroupinc.com COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

/2

/2

:4

:1

P

M

REPLACE PLUMBING

SYSTEMS IN BLDG. 64

08/27/2021

LIFE SAFETY & PHASING PLANS

G108

NSJR

573A4-18-600

Lake City, Florida

PAUL DRAKE

100% CONSTRUCTION

DOCUMENTS

N Scale: 1/8" = 1'-0"

CODE PLAN - PHASE 8

GENERAL PHASING NOTES

A. Temporary partition to structural deck above. If temporary partition cannot be built to deck due to utilities above the ceiling a fire retardant plastic may be used from the suspended ceiling to the structural deck to seal up construction area and enable a negative air construction zone.

B. Coordinate all work involving the generation of excessive noise so as to occur during non-peak operating hours, 1000 to 1600 daily.

Activities to occur during this time include, but are not limited to saw cutting, jack hammering, hammer drilling and core drilling. If there is any question as to whether an operation should occur during this time the Contractor will contact the COR.

C. Coordinate phase completion with requirements as set for by COR to maintain daily operations to near as normal as possible.

D. Coordinate access to all phases of construction, deliveries, and debris removal with the COR. See General Requirements.

E. Temporary door locations and sizes are as required by the General Contractor. Doors will interfere with daily operations as little as possible. All temporary doors shall be accessible to maintenance personnel to gain access to maintenance rooms inside construction areas. Coordinate final door locations with COR.

F. All existing doors to surrounding a construction phase must be sealed to prevent the passage of smoke. Install plastic zipper walls at all entrances to construction phases.

G. Existing utilities shall remain in operation during construction.

H. Provide and maintain negative air pressure inside construction zone.

I. All marked exits shall be maintained throughout construction. If an exit is required to be blocked temporary signage must be installed to direct to the nearest exit. Coordinate closing of exits with COR.

V

AB29

AB22D

AB28A

BB25

CB-14

BB27

BB28

BB29

BB26

BB24

BB23BB22

BB26A

AB29

BB03A

BB03

CB-7

C B

BB02

BB01

BB04 BB05

BB16

BB07

BB16A

BB20

BB19

BB21 BB21C

BB18

BB17

BB18A

C B

C B

C B

F-5/64

AB28B

BB06

BB14

BB14A

BB15

BB13

BB11A

C B

BB12B

CB-10

BB12

BB11

BB12A

BB10

BB09

BB09A

CB-10

BB10A

BB08

AB30

AB28A

C B

C10B

C10

C10

C9A

C B A

C9

C9

C9CC9B

C9D

C B

C15

C8

CB-3

C6E C6D C6C

C6B

C6F

C6

C6G

CB-3

C7A

C5

C6A C6

C4

C1

CB-1

C2

C6K

C6H C6J

C7

LINEN

CHUTE

GAS

STERILE & NON-STERILE

STORAGE

STOR.

STAIR

CORRIDOR

M.

TOILET

WELLNESS

CENTER

F.

TOILET

R.M.S.

STORAGE

R.M.S.

STORAGE

H.A.C.F.A.C.

MECH.

ROOM

(UNEXCAVATED)

MECH.

ROOM

CHIEF

SPD CLERICAL

SPD

CORRIDOR

C O R R

ID

O R

MALE

TOIL,

CL.

LINEN

FEM.

TOIL,

HAC

SPD

STORAGE

T.M.E.R.

SHOP

T.M.E.R.

SHOP

SPD

STORAGE

FREEZER #

M.A.S.

STOR.

E.M.S.

STOR.

ENG.

DIETETICS

STORAGE

D

IE

T E L E V

L O B B Y

C O R R

ID

O R

C O R R

ID

O R

HAC

RECIEVING

SPD

CLEAN

HVAC

MECH.

ROOM

REFRIG.

MECH.

ROOM

EMS

EQUIP.

CLEANING

FREEZER #

C O R R

ID

O R

MEDICAL

MEDIACAMERA

ROOM

CORRIDOR

M.M.

OFC

REFRIG #

PROCESS

ROOM

M.M.

FILM

ILLUS.

RM.

M.M.

REFRIG, #

CORRIDOR

M.M.

EQ.

STOR.DIETETIC

COOLER #

MECH.

RM.

HVAC

STORAGE

SPD STERILE & NON

STERILE

C O R R

ID

O R

C

ORRIDOR

C O R R

ID

O R

STAIR

CORRIDOR CORRIDOR

C B

C O R R

ID

O R

ELEV.

LOBBY

PASS.

0-HR Smoke Partition - NFPA 101 - 8.4

1-HR Smoke Barrier - NFPA 101 - 8.5

1-HR Fire Barrier - NFPA 101 - 8.3

2-HR Fire Barrier - NFPA 101 - 8.3

Means of Egress

Existing Wall to Remain

Proposed Temporary Wall Location - Wall Type T1.0

CODE LEGEND

JOHN

A.

POE

IO

HO

FOET

A T

S

R E G I S

E T

R

ED RA

C H

TI

E C T

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

VA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management www.abovegroupinc.com COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

/2

/2

:4

:1

P

M

REPLACE PLUMBING

SYSTEMS IN BLDG. 64

08/27/2021

LIFE SAFETY & PHASING PLANS

G109

NSJR

573A4-18-600

Lake City, Florida

PAUL DRAKE

100% CONSTRUCTION

DOCUMENTS

N Scale: 1/8" = 1'-0"

CODE PLAN - PHASE 9

GENERAL PHASING NOTES

A. Temporary partition to structural deck above. If temporary partition cannot be built to deck due to utilities above the ceiling a fire retardant plastic may be used from the suspended ceiling to the structural deck to seal up construction area and enable a negative air construction zone.

B. Coordinate all work involving the generation of excessive noise so as to occur during non-peak operating hours, 1000 to 1600 daily.

Activities to occur during this time include, but are not limited to saw cutting, jack hammering, hammer drilling and core drilling. If there is any question as to whether an operation should occur during this time the Contractor will contact the COR.

C. Coordinate phase completion with requirements as set for by COR to maintain daily operations to near as normal as possible.

D. Coordinate access to all phases of construction, deliveries, and debris removal with the COR. See General Requirements.

E. Temporary door locations and sizes are as required by the General Contractor. Doors will interfere with daily operations as little as possible. All temporary doors shall be accessible to maintenance personnel to gain access to maintenance rooms inside construction areas. Coordinate final door locations with COR.

F. All existing doors to surrounding a construction phase must be sealed to prevent the passage of smoke. Install plastic zipper walls at all entrances to construction phases.

G. Existing utilities shall remain in operation during construction.

H. Provide and maintain negative air pressure inside construction zone.

I. All marked exits shall be maintained throughout construction. If an exit is required to be blocked temporary signage must be installed to direct to the nearest exit. Coordinate closing of exits with COR.

V

AB28A

BB25

CB-14

BB27

BB28

BB29

BB26

BB24

BB23BB22

BB26A

AB29

BB03A

BB03

CB-7

C B

BB02

BB01

BB04 BB05

BB16

BB07

BB16A

BB20

BB19

BB21 BB21C

BB18

BB17

BB18A

C B

C B

C B

F-5/64

AB28B

BB06

BB14

BB14A

BB15

BB13

BB11A

C B

BB12B

CB-10

BB12

BB11

BB12A

BB10

BB09

BB09A

CB-10

BB10A

BB08

AB30

AB28A

C B

C10B

C10

C10

C9A

C B A

C9

C9

C9CC9B

C9D

C B

C8

CB-3

C6E C6D C6C

C6B

C6F

C6

C6G

CB-3

C7A

C5

C6A C6

C4

C1

CB-1

C2

C6K

C6H C6J

C7

LINEN

CHUTE

STERILE & NON-STERILE

STORAGE

STAIR

CORRIDOR

M.

TOILET

WELLNESS

CENTER

F.

TOILET

R.M.S.

STORAGE

R.M.S.

STORAGE

H.A.C.F.A.C.

MECH.

ROOM

(UNEXCAVATED)

MECH.

ROOM

CHIEF

SPD CLERICAL

SPD

CORRIDOR

C O R R

ID

O R

MALE

TOIL,

CL.

LINEN

FEM.

TOIL,

HAC

SPD

STORAGE

T.M.E.R.

SHOP

T.M.E.R.

SHOP

SPD

STORAGE

FREEZER #

M.A.S.

STOR.

E.M.S.

STOR.

ENG.

DIETETICS

STORAGE

D

IE

T E L E V

L O B B Y

C O R R

ID

O R

C O R R

ID

O R

HAC

RECIEVING

SPD

CLEAN

HVAC

MECH.

ROOM

REFRIG.

MECH.

ROOM

EMS

EQUIP.

CLEANING

FREEZER #

C O R R

ID

O R

MEDICAL

MEDIACAMERA

ROOM

CORRIDOR

M.M.

OFC

REFRIG #

PROCESS

ROOM

M.M.

FILM

ILLUS.

RM.

M.M.

REFRIG, #

CORRIDOR

M.M.

EQ.

STOR.DIETETIC

COOLER #

MECH.

RM.

HVAC

STORAGE

SPD STERILE & NON

STERILE

C O R R

ID

O R

C

ORRIDOR

C O R R

ID

O R

STAIR

CORRIDOR CORRIDOR

C B

C O R R

ID

O R

ELEV.

LOBBY

PASS.

0-HR Smoke Partition - NFPA 101 - 8.4

1-HR Smoke Barrier - NFPA 101 - 8.5

1-HR Fire Barrier - NFPA 101 - 8.3

2-HR Fire Barrier - NFPA 101 - 8.3

Means of Egress

Existing Wall to Remain

Proposed Temporary Wall Location - Wall Type T1.0

CODE LEGEND

JOHN

A.

POE

IO

HO

FOET

A T

S

R E G I S

E T

R

ED RA

C H

TI

E C T

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

VA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management www.abovegroupinc.com COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

/2

/2

:4

:1

P

M

REPLACE PLUMBING

SYSTEMS IN BLDG. 64

08/27/2021

LIFE SAFETY & PHASING PLANS

G110

NSJR

573A4-18-600

Lake City, Florida

PAUL DRAKE

100% CONSTRUCTION

DOCUMENTS

N Scale: 1/8" = 1'-0"

CODE PLAN - PHASE 10

GENERAL PHASING NOTES

A. Temporary partition to structural deck above. If temporary partition cannot be built to deck due to utilities above the ceiling a fire retardant plastic may be used from the suspended ceiling to the structural deck to seal up construction area and enable a negative air construction zone.

B. Coordinate all work involving the generation of excessive noise so as to occur during non-peak operating hours, 1000 to 1600 daily.

Activities to occur during this time include, but are not limited to saw cutting, jack hammering, hammer drilling and core drilling. If there is any question as to whether an operation should occur during this time the Contractor will contact the COR.

C. Coordinate phase completion with requirements as set for by COR to maintain daily operations to near as normal as possible.

D. Coordinate access to all phases of construction, deliveries, and debris removal with the COR. See General Requirements.

E. Temporary door locations and sizes are as required by the General Contractor. Doors will interfere with daily operations as little as possible. All temporary doors shall be accessible to maintenance personnel to gain access to maintenance rooms inside construction areas. Coordinate final door locations with COR.

F. All existing doors to surrounding a construction phase must be sealed to prevent the passage of smoke. Install plastic zipper walls at all entrances to construction phases.

G. Existing utilities shall remain in operation during construction.

H. Provide and maintain negative air pressure inside construction zone.

I. All marked exits shall be maintained throughout construction. If an exit is required to be blocked temporary signage must be installed to direct to the nearest exit. Coordinate closing of exits with COR.

V

AB28A

BB25

CB-14

BB27

BB28

BB29

BB26

BB24

BB23BB22

BB26A

BB03A

BB03

CB-7

BB02

BB01

BB04 BB05

BB16

BB07

BB16A

BB20

BB19

BB21 BB21C

BB18

BB17

BB18A

C B

C B

C B

F-5/64

AB28B

BB06

BB14

BB14A

BB15

BB13

BB11A

C B

BB12B

CB-10

BB12

BB11

BB12A

BB10

BB09

BB09A

CB-10

BB10A

BB08

AB30

C B

C10B

C10

C10

C9A

C B A

C9

C9

C9CC9B

C9D

C B

CB-3

C6E C6D C6C

C6B

C6F

C6

C6G

CB-3

C7A

C5

C6A C6

C4

C1

CB-1

C2

C6K

C6H C6J

STAIR

CORRIDOR

M.

TOILET

WELLNESS

CENTER

F.

TOILET

R.M.S.

STORAGE

R.M.S.

STORAGE

H.A.C.F.A.C.

MECH.

ROOM

(UNEXCAVATED)

MECH.

ROOM

CHIEF

SPD CLERICAL

SPD

CORRIDOR

MALE

TOIL,

CL.

LINEN

FEM.

TOIL,

HAC

SPD

STORAGE

T.M.E.R.

SHOP

T.M.E.R.

SHOP

SPD

STORAGE

FREEZER #

M.A.S.

STOR.

E.M.S.

STOR.

ENG.

DIETETICS

STORAGE

D

IE

T E L E V

L O B B Y

C O R R

ID

O R

C O R R

ID

O R

HAC

RECIEVING

SPD

CLEAN

HVAC

MECH.

ROOM

REFRIG.

MECH.

ROOM

EMS

EQUIP.

CLEANING

FREEZER #

C O R R

ID

O R

MEDICAL

MEDIACAMERA

ROOM

CORRIDOR

M.M.

OFC

REFRIG #

PROCESS

ROOM

M.M.

FILM

ILLUS.

RM.

M.M.

REFRIG, #

CORRIDOR

M.M.

EQ.

STOR.DIETETIC

COOLER #

MECH.

RM.

HVAC

STORAGE

SPD STERILE & NON

STERILE

C O R R

ID

O R

C

ORRIDOR

C O R R

ID

O R

CORRIDOR CORRIDOR

C B

C O R R

ID

O R

ELEV.

LOBBY

PASS.

0-HR Smoke Partition - NFPA 101 - 8.4

1-HR Smoke Barrier - NFPA 101 - 8.5

1-HR Fire Barrier - NFPA 101 - 8.3

2-HR Fire Barrier - NFPA 101 - 8.3

Means of Egress

Existing Wall to Remain

Proposed Temporary Wall Location - Wall Type T1.0

CODE LEGEND

JOHN

A.

POE

IO

HO

FOET

A T

S

R E G I S

E T

R

ED RA

C H

TI

E C T

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

VA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management www.abovegroupinc.com COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

/2

/2

:4

:1

P

M

REPLACE PLUMBING

SYSTEMS IN BLDG. 64

08/27/2021

LIFE SAFETY & PHASING PLANS

G111

NSJR

573A4-18-600

Lake City, Florida

PAUL DRAKE

100% CONSTRUCTION

DOCUMENTS

N Scale: 1/8" = 1'-0"

CODE PLAN - PHASE 11

GENERAL PHASING NOTES

A. Temporary partition to structural deck above. If temporary partition cannot be built to deck due to utilities above the ceiling a fire retardant plastic may be used from the suspended ceiling to the structural deck to seal up construction area and enable a negative air construction zone.

B. Coordinate all work involving the generation of excessive noise so as to occur during non-peak operating hours, 1000 to 1600 daily.

Activities to occur during this time include, but are not limited to saw cutting, jack hammering, hammer drilling and core drilling. If there is any question as to whether an operation should occur during this time the Contractor will contact the COR.

C. Coordinate phase completion with requirements as set for by COR to maintain daily operations to near as normal as possible.

D. Coordinate access to all phases of construction, deliveries, and debris removal with the COR. See General Requirements.

E. Temporary door locations and sizes are as required by the General Contractor. Doors will interfere with daily operations as little as possible. All temporary doors shall be accessible to maintenance personnel to gain access to maintenance rooms inside construction areas. Coordinate final door locations with COR.

F. All existing doors to surrounding a construction phase must be sealed to prevent the passage of smoke. Install plastic zipper walls at all entrances to construction phases.

G. Existing utilities shall remain in operation during construction.

H. Provide and maintain negative air pressure inside construction zone.

I. All marked exits shall be maintained throughout construction. If an exit is required to be blocked temporary signage must be installed to direct to the nearest exit. Coordinate closing of exits with COR.

GENERAL NOTES

1. THE PLUMBING INSTALLATION SHALL COMPLY

WITH ALL CURRENT STATE AND LOCAL

CODES.

2. PROVIDE ALL OFFSETS AND FITTINGS AND

MAKE CONNECTION TO SITE UTILITIES.

3. CONCEAL PIPING ABOVE CEILINGS, WITHIN

WALLS OR CHASES EXCEPT IN MECHANICAL

ROOMS OR AS SPECIFICALLY NOTED.

4. PROVIDE ACCESS PANELS FOR ALL VALVES

CONCEALED IN WALLS OR ABOVE NON-

ACCESSIBLE CEILINGS.

5. SLEEVE AND/OR FIRESTOP ALL PENETRATIONS

THROUGH RATED WALLS, CEILINGS, AND

FLOORS WITH U/L LISTED ASSEMBLIES.

FIRESTOP ASSEMBLIES SHALL BE EQUAL TO

OR EXCEED THE RATING OF THE WALL,

CEILING OR FLOOR. SEE ARCHITECTURAL

DRAWINGS FOR FINAL FINISHES.

6. PROVIDE AN AIR GAP, WHEN REQUIRED BY

CODE, SERVING INDIVIDUAL FIXTURES,

DEVICES, APPLIANCES AND APPARATUS.

7. PROVIDE CLEANOUTS AS REQUIRED BY CODE

OR IN ADDITION TO THOSE SHOWN ON PLAN

IF AN ALTERNATE ROUTE IS CHOSEN BY

CONTRACTOR. INSTALL CLEANOUT WITH COVER

FLUSH TO FINISHED SURFACE

8. CONTRACTOR TO PROVIDE ALL

APPURTENANCES TO COMPLETE INSTALLATION

AND CONNECTIONS IN ITS ENTIRETY TO

FIXTURES AND EQUIPMENT.

9. LEAK TEST TO BE PERFORMED ON SANITARY

PIPING PER SPECIFICATION SECTION

22 13 00, 3.5 TESTS.

10. WHEN SUMP PUMP AND TEMPORARY PIPING

IS REMOVED AFTER A PHASE IS COMPLETED,

THE WYE FITTING IS TO BE CAPPED AT THE

MAIN AS A CLEANOUT.

11. CONTRACTOR TO SUBMIT AN APPROXIMATE

TIMELINE OF SHUTDOWNS FOR THE PROJECT

WHEN SUBMITTING A BID. BEFORE ANY WORK

BEGINS, THE CONTRACTOR MUST RECEIVE VA

COR APPROVAL ON A SCHEDULE FOR

SHUTDOWNS. AFTER APPROVAL, ANY

DEVIATION FROM THIS SCHEDULE NEEDS TO

BE COMMUNICATED WITH THE VA COR AND

RECEIVE THE VA COR APPROVAL.

PLUMBING VALVE SYMBOLS

BALL VALVE

GATE VALVE WITH 3/4 " HOSE ADAPTER

CHECK VALVE

ANGLE GLOBE VALVE

BUTTERFLY VALVE

MODULATING CONTROL VALVE

TWO POSITION CONTROL VALVE

THREE-WAY MODULATING CONTROL VALVE

AUTOMATIC FLOW CONTROL VALVE

PRESSURE RELIEF VALVE

GATE VALVE

MANUAL AIR VENT

TEST PLUG

(PRESSURE/TEMPERATURE)

GLOBE VALVE

PRESSURE REGULATING VALVE

THREE-WAY TWO POSITION CONTROL VALVE

AUTOMATIC AIR VENTAV

GENERAL PLUMBING SYMBOLS

LIMIT OF DEMOLITION

ANCHOR

REDUCER OR INCREASER

DIRECTION OF FLOW

SIDE…