S02 2021-08-09 VAC2001 Bid Set.pdf

PDF 8 MB Posted

Attached to
Z1DA--528A5-19-515 PROVIDE AC IN SWITCH ROOMS
Solicitation number
36C24222B0030
Issued by

About this file

This document is a solicitation for project number 585A5-19-515 to provide air conditioning in switch rooms at the Canandaigua VA Medical Center in Canandaigua, New York. The scope of work includes installing ductless mini-split AC units in eight switch rooms to provide adequate cooling for VA communications infrastructure. Electrical and demolition work is required. Specifications and drawings are provided. The total project duration is 120 days from submittal approval to final punch list completion. Bidders must comply with all applicable codes and VA standards.

View the file

Other files

File Type Posted
36C24222B0030 0001.docx DOCX document
VAC2001 100percent Review Spec Book.pdf PDF
36C24222B0030_2.docx DOCX document
P07 - WAGE DETERMINATION.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PARKING

PARKING

PARKING

WATER TOWER

CAMPUS SITE PLAN

VAMC Canandaigua

RAMP

1355 TITUS AVE « ROCHESTER, NY 14622

(585) 448- 0686

P TRIOT

DESIGN & CONSULTING

STILL SERVING

DEPARTMENT OF VETERANS AFFAIRS

PROJECT NO. 528A5-19-515

CANANDAIGUA, NY

SCALE: NONE

SITE MAP

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date:

NOTE:

USERS OF THESE DRAWINGS ARE RESPONSIBLE FOR

VERIFYING EXISTING DIMENSIONS AND CONDITIONS

IN THE FIELD

o n e e ig h th in ch o n e f o o t th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t

SCALE: NONE

SITE LOCATION

AC SWITCH ROOM

G-001 1 OF 20 COVER SHEET

M-001 2 OF 20 MECHANICAL COVER SHEET

M-101 3 OF 20 BUILDING 5 MECHANICAL FLOOR PLAN

M-102 4 OF 20 BUILDING 6 MECHANICAL FLOOR PLAN

M-103 5 OF 20 BUILDING 7 MECHANICAL FLOOR PLAN

M-104 6 OF 20 BUILDING 8 MECHANICAL FLOOR PLAN

M-105 7 OF 20 BUILDING 36 MECHANICAL FLOOR PLAN

M-106 8 OF 20 BUILDING 37 MECHANICAL BASEMENT FLOOR PLAN

M-107 9 OF 20 BUILDING 37 MECHANICAL FIRST FLOOR PLAN

M-108 10 OF 20 BUILDING 118 MECHANICAL FLOOR PLAN

M-201 11 OF 20 MECHANICAL DETAILS

E-001 12 OF 20 ELECTRICAL COVER SHEET

E-101 13 OF 20 BUILDING 5 ELECTRICAL FLOOR PLAN

E-102 14 OF 20 BUILDING 6 ELECTRICAL FLOOR PLAN

E-103 15 OF 20 BUILDING 7 ELECTRICAL FLOOR PLAN

E-104 16 OF 20 BUILDING 8 ELECTRICAL FLOOR PLAN

E-105 17 OF 20 BUILDING 36 ELECTRICAL FLOOR PLAN

E-106 18 OF 20 BUILDING 37 ELECTRICAL BASEMENT FLOOR PLAN

E-107 19 OF 20 BUILDING 37 ELECTRICAL FIRST FLOOR PLAN

E-108 20 OF 20 BUILDING 118 ELECTRICAL FLOOR PLAN

DRAWING NO. SHEET NO. TITLE

LIST OF DRAWINGS:

GENERAL NOTES:

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

BTU BRITISH THERMAL UNITS

COND CONDENS-, ER, ATE, ATION

CFM CUBIC FEET PER MINUTE

D DRAIN LINE

DD DELEGATED DESIGN

DN DOWN

EA EXHAUST AIR

EDB ENTERING DRY BULB

EF EXHAUST FAN

ETR EXISTING TO REMAIN

F FARENHEIT

FPM FEET PER MINUTE

FT FEET

HP HORSEPOWER

HZ HERTZ

KW KILOWATTS

LB POUNDS

LDB LEAVING DRY BULB

MAX MAXIMUM

MBH THOUSAND BTUS PER HOUR

MCA MINIMUM CURRENT AMPACITY

MIN MINIMUM

MOP MAX ALLOWABLE CIRCUIT BREAKER

PH PHASE

RG REFRIGERANT GAS

RL REFRIGERANT LIQUID

RPM REVOLUTIONS PER MINUTE

SA SUPPLY AIR

S.P STATIC PRESSURE

TYP TYPICAL

V VOLT

1. THE SYSTEM DESIGN, INSTALLATION AND MATERIALS SHALL CONFORM TO THE 2020

INTERNATIONAL MECHANICAL CODE AND AUTHORITIES HAVING JURISDICTION. IN CASE OF

CONFLICTS WITH CODES, DRAWINGS, OR SPECIFICATIONS, THE MOST STRINGENT SHALL

PREVAIL.

2. BEFORE COMMENCEMENT OF WORK, THE CONTRACTOR SHALL VERIFY THE EXACT

LOCATIONS, ELEVATIONS AND CHARACTERISTICS OF ALL EQUIPMENT, UTILITIES AND

PIPING, AND SHALL IMMEDIATELY NOTIFY THE ARCHITECT OF ANY DISCREPANCIES.

3. THE DRAWINGS WERE PREPARED WITH THE BEST STRUCTURAL AND ARCHITECTURAL

INFORMATION AVAILABLE. IT IS UNDERSTOOD THAT EQUIPMENT LOCATIONS AND ROUTING

OF PIPING MAY VARY FROM THAT SHOWN ON THE PLANS AS CONSTRUCTION PROCEEDS. IT

IS THE CONTRACTORS RESPONSIBILITY TO:

a. NOTIFY THE ENGINEER OF CONSTRUCTION RESTRAINTS WHICH MAKE VARIATIONS

FROM THE PLANS NECESSARY.

b. COMPLETE ALL WORK INCLUDING THE VARIATIONS WITHOUT CHARGING EXTRAS TO

THE BID CONTRACT. COMPLETION OF WORK MEANS THE JOB IS WORKING AND AN

COMPLETE TO THE SATISFACTION OF THE COR.

4. THESE DRAWINGS DO NOT INCLUDE ALL NECESSARY SAFETY REQUIREMENTS.

CONTRACTOR TO COMPLY TO THE SAFETY REQUIREMENTS SET FORTH BY THE LOCAL

AUTHORITIES HAVING JURISDICTION.

5. THESE DRAWINGS ARE FOR BIDDING PURPOSES ONLY. THEY ARE ESSENTIALLY

DIAGRAMMATIC TO THE EXTENT THAT MANY OFFSETS, BONDS, UNIONS, SPECIFIC FITTINGS

AND EXACT LOCATIONS ARE NOT INDICATED.

6. PATCH AND /OR REPAIR EXISTING DUCTWORK AND PIPING INSULATION DAMAGED OR

DISTURBED DUE TO CONSTRUCTION WORK.

7. ALL EXTERIOR FLOOR AND WALL PENETRATIONS MUST BE SEALED WATERTIGHT.

8. ALL FLOOR AND WALL PENETRATIONS FIRE THROUGH RATED WALLS MUST BE SEALED

FIRESTOPPED.

9. THE CONTRACTOR SHALL VISIT THE JOB SITE PRIOR TO SUBMITTING BID. THE

CONTRACTORS SHALL FAMILIARIZE THEMSELVES WITH ALL EXISTING CONDITIONS AND

FUTURE WORK TO BE DONE. THEY SHALL INCLUDE ALL SITE INFORMATION AND CONDITIONS

WITHIN THE BASE BID. THEY SHALL BE RESPONSIBLE FOR COMPLETE AND FULLY

FUNCTIONING SYSTEMS.

10. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE EQUIPMENT

MANUFACTURER'S RECOMMENDATIONS AND APPLICABLE CODES, PROVIDE ALL FITTINGS,

VALVES, AND OTHER DEVICES REQUIRED FOR A COMPLETE WORKABLE INSTALLATION.

11. MAINTENANCE LABEL SHALL BE AFFIXED TO ALL EQUIPMENT AND A MAINTENANCE MANUAL

SHALL BE PROVIDED TO OWNER'S REPRESENTATIVE.

12. COORDINATE WITH ELECTRICAL TRADE PRIOR TO ORDERING ELECTRICALLY OPERATED

EQUIPMENT FOR AVAILABLE VOLTAGES AT EQUIPMENT LOCATIONS.

13. THESE PLANS INDICATE APPROXIMATE ROUGH-INS ONLY FOR EQUIPMENT. EXACT ROUGH-IN

DIMENSIONS MUST BE OBTAINED FROM THE EQUIPMENT MANUFACTURER.

14. ALL NEW PENETRATIONS MUST BE CUT WITH WET SAW.

ABBREVATIONS SYMBOLS

POINT OF CONNECTION

THERMOSTAT

POINT OF REMOVAL

T

AIR FLOW DESIGNATION

1355 EAST TITUS AVENUE « ROCHESTER, NY 14622

(585) 448 - 0686 « www.Patriot-DC.com

P TRIOT

DESIGN & CONSULTING

STILL SERVING

ISSUED FOR BID

ASBESTOS AWARENESS NOTES

1. A PRE-RENOVATION SURVEY AND DOCUMENT REVIEW WAS PERFROMED BY WATTS

ARCHITECTURE & ENGINEERING IN NOVEMBER 2020 AND HAS BEEN INCLUDED IN THE

CONTRACT DOCUMENTS. ASBESTOS-CONTAINING MATERIALS (ACM) HAVE BEEN CONFIRMED

TO BE PRESENT IN SOME OF THE AREAS SCHEDULED FOR RENOVATION.

2. ASBESTOS-CONTAINING PIPE INSULATION, MUD FITTING INSULATION, 12” X 12” FLOOR TILES

(VARIOUS COLORS), 9” X 9” FLOOR TILES (VARIOUS COLORS), ASSOCIATED MASTIC AND

WINDOW GLAZING COMPOUND ARE LOCATED IN VARIOUS AREAS THROUGHOUT THE

BUILDINGS.

3. ALL CONTRACTORS ARE RESPONSIBLE FOR MAKING THEMSELVES AND THEIR EMPLOYEES

AWARE OF THE PRESENCE, LOCATION, AND QUANTITY OF EXISTING ASBESTOS-CONTAINING

BUILDING MATERIALS, AND TO WARN THEIR EMPLOYEES OF THE POTENTIAL DANGERS OF

EXPOSURE TO ASBESTOS. ANY DISTURBANCE OF ASBESTOS-CONTAINING MATERIALS SHALL

BE PERFORMED BY A LICENSED ASBESTOS ABATEMENT CONTRACTOR EMPLOYING CERTIFIED

WORKERS.

LEAD AWARENESS NOTES:

1. CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH OSHA 29 CFR 1926.62: LEAD

EXPOSURE IN CONSTRUCTION: INTERIM FINAL RULE FOR ALL ACTIVITIES DURING WHICH AN

EMPLOYEE MAY BE OCCUPATIONALLY EXPOSED TO LEAD. ALL CONTRACTORS SHALL ENSURE

THAT THEIR EMPLOYEES WEAR PROPER PERSONAL PROTECTIVE EQUIPMENT AND/OR UTILIZE

APPROPRIATE WORK METHODS TO PREVENT ELEVATED BLOOD LEAD LEVELS OR EXPOSURE

ABOVE THE PERMISSIBLE EXPOSURE LIMIT.

LO

OP

BVAVSYSTEM COMPONENT:

JOB: -

VARIABLE REFRIGERANT SYSTEM

VA CANANDAIGUA

SYSTEM:

BUILDING:

AI BIAO BO AL

AR

M

TR

EN

DI

NG

SC

HE

DU

LE

REMARKS

HARDWARE

POINTS

SYSTEM SOFTWARE/CONTROL

Zone Temperature Zone Temperature Setpoint

Zone Setpoint Adjust Zone Override Zone Humidity Zone Humidity Setpoint Zone WB Temperature Zone WB Temperature Setpoint Fan Status Fan Speed Operation Mode Compressor Status Pre-Filter Status Unit Alarm Schedule

SOFTWARE

POINTS

SH

OW

O N

GR

AP

HI

CS

NOTES:

1. PROVIDE BACNET MS/TP AND IP COMPATIBLE CONTROLS INTERFACE . TIE INTO EXISTING

LOGICAL CONTROL SOLUTIONS, INC BMS SYSTEM.

2. RUN A CAT 6 CABLE IN 3/4” CONDUIT FROM THE CONTROLS CONNECTION AT THE CONDENSER

TO THE NEAREST BMS CONTROL PANEL WHICH MAY BE LOCATED IN THE SERVER ROOM OR

MECHANICAL ROOM.

BMS CONTROL POINT SCHEDULE

INDOOR COOLING UNIT

UNIT BUILDING ROOM

LIQUID PIPE

SIZE (IN)

GAS PIPE

SIZE (IN)

HOSE

CONNECTION

SIZE (IN)

DRAIN PIPE

SIZE (IN) QUANTITY AIRFLOW H/M/L

(CFM)

COOLING CAPACITY

(BTU/HR) REFRIGERANT

POWER

OUTPUT

(WATTS)

NOMINAL

CURRENT

(AMP)

TYPE INDOOR MODEL MANUFACTURER OR

APPROVED EQUAL WEIGHT (LB) DIMENSIONS (WXHXD) ACCESORIES NOTES

AC-05 5 6 3/8" 5/8" 1" 1-1/4" 1 1007/865/742 36,000 410A 97 0.56 CEILING HUNG

CASSETTE AM036RN4DCH SAMSUNG 13 33 1/16 X 11 3/8 X 33 1/16 WIRELESS THERMOSTAT, MOUNTING RACK AND

HARDWARE, REFRIGERANT Y CONNECTION 1-4, 5, 8

AC-06A/B 6 1B 3/8" 5/8" 1" 1-1/4" 2 865/706/583 24,000 410A 65 0.45 CEILING HUNG

CASSETTE AM024RN4DCH SAMSUNG 13 33 1/16 X 8 1/32 X 33 1/16 WIRELESS THERMOSTAT, MOUNTING RACK AND

HARDWARE, REFRIGERANT Y CONNECTION 1-4, 5, 8

AC-07 7 14B 3/8" 5/8" 1" 1-1/4" 1 1007/865/742 36,000 410A 97 0.56 CEILING HUNG

CASSETTE AM036RN4DCH SAMSUNG 13 33 1/16 X 8 1/32 X 33 1/16 WIRELESS THERMOSTAT, MOUNTING RACK AND

HARDWARE, REFRIGERANT Y CONNECTION 1-4, 5, 8

AC-08A/B 8 1A 3/8" 5/8" 1" 1-1/4" 2 593/530/466 24,000 410A 27 0.40 WALL MOUNTED

UNIT AM024TNVDCH SAMSUNG 28 41 1/2 X 11 3/4 X 9 WIRELESS THERMOSTAT, MOUNTING RACK AND

HARDWARE, REFRIGERANT Y CONNECTION 1-4, 6, 8

AC-B37-A 37 1A 3/8" 5/8" 1" 1-1/4" 1 593/530/466 24,000 410A 27 0.40 WALL MOUNTED UNIT AM024TNVDCH SAMSUNG 28 41 1/2 X 11 3/4 X 9 WIRELESS THERMOSTAT, MOUNTING RACK AND

HARDWARE, REFRIGERANT Y CONNECTION 1-4, 6, 8

AC-B37-B/C 37 20 1/4" 1/2" 1" 1-1/4" 2 547/494/424 12,000 410A 65 0.40 CEILING HUNG CASSETTE AM012RN4DCH SAMSUNG 13 33 1/16 X 8 1/32 X 33 1/16 WIRELESS THERMOSTAT, MOUNTING RACK AND

HARDWARE, REFRIGERANT Y CONNECTION 1-4, 5, 8

AC-37-1 37 137 3/8" 5/8" 1" 1-1/4" 1 830/752/699 36,000 410A 58 0.90 WALL MOUNTED UNIT AC036MNTDCH SAMSUNG 28 50 3/8 X 13 9/16 X 10 WIRELESS THERMOSTAT, MOUNTING RACK AND

HARDWARE, REFRIGERANT Y CONNECTION 1-4, 6, 8

AC-118 118 9 3/8" 5/8" 1" 1-1/4" 1 830/752/699 36,000 410A 58 0.90 WALL MOUNTED

UNIT AC036MNTDCH SAMSUNG 28 50 3/8 X 13 9/16 X 10 WIRELESS THERMOSTAT, MOUNTING RACK AND

HARDWARE, REFRIGERANT Y CONNECTION 1-4, 6, 8

AC-36 36 13 3/8" 5/8" 1" 1-1/4" 1 635/705/775 24,000 410A 40 0.3 WALL MOUNTED

UNIT PUYA24NHA7 MITSUBISHI 46 14 38 X 46 1/16 X 11 5/8 WIRELESS THERMOSTAT, MOUNTING RACK AND

HARDWARE, REFRIGERANT Y CONNECTION 6, 7, 8

OUTDOOR CONDENSER UNIT

UNIT BUILDING

LIQUID PIPE

SIZE (IN)

GAS PIPE

SIZE (IN) QUANTITY AIRFLOW

(CFM)

NORMINAL CAPACITY

(BTU/HR) ø / V / Hz MAX CIRCUIT

BREAKER

MCA (A) TYPE OUTDOOR MODEL MANUFACTURER OR

APPROVED EQUAL WEIGHT (LB) DIMENSION ACCESORIES NOTES

CU-05 5 3/8" 5/8" 1 3,885 36,000 1 / 208-230 / 60 40 23 TWIN BLDC ROTARYX1 AM036TXMDCH SAMSUNG 220 34 5/8 X 25 1/8 X 12 3/16 DISCONNECT SWITCH AND

NEMA 4X ENCLOSURE 1-3, 5

CU-06 6 3/8" 5/8" 1 3,885 48,000 1 / 208-230 / 60 50 29 TWIN BLDC ROTARYX1 AM048TXMDCH SAMSUNG 220 37 X 47 5/8 X 13 DISCONNECT SWITCH AND

NEMA 4X ENCLOSURE 1-3, 5

CU-07 7 3/8" 5/8" 1 3,885 36,000 1 / 208-230 / 60 40 23 TWIN BLDC ROTARYX1 AM036TXMDCH SAMSUNG 220 34 5/8 X 25 1/8 X 12 3/16 DISCONNECT SWITCH AND

NEMA 4X ENCLOSURE 1-3, 5

CU-08 8 3/8" 5/8" 1 3,885 48,000 1 / 208-230 / 60 50 29 TWIN BLDC ROTARYX1 AM048TXMDCH SAMSUNG 220 37 X 47 5/8 X 13 DISCONNECT SWITCH AND

NEMA 4X ENCLOSURE 1-3, 5

CU-B37 37 3/8" 5/8" 1 3,885 48,000 1 / 208-230 / 60 50 29 TWIN BLDC ROTARYX1 AM048TXMDCH SAMSUNG 220 37 X 47 5/8 X 13 DISCONNECT SWITCH AND

NEMA 4X ENCLOSURE 1-3, 5

CU-37-1 37 3/8" 5/8" 1 2,754 36,000 1 / 208-230 / 60 30 24 TWIN BLDC ROTARYX1 AM036MXSCCC SAMSUNG 160 37 X 39 11/16 X 13 DISCONNECT SWITCH AND

NEMA 4X ENCLOSURE 1-3, 5

CU-118 118 3/8" 5/8" 1 2,754 36,000 1 / 208-230 / 60 30 24 TWIN BLDC ROTARYX1 AM036MXSCCC SAMSUNG 160 37 X 39 11/16 X 13 DISCONNECT SWITCH AND

NEMA 4X ENCLOSURE 1-3, 5

CU-36 36 3/8" 5/8" 1 1,940 24,000 1 / 208-230 / 60 25 19 - PUYA24NHA7 MITSUBISHI 151 37 1/8 X 37 13/32 X 13 13/16 DISCONNECT SWITCH AND

NEMA 4X ENCLOSURE 2, 4, 5

NOTES:

1. PROVIDE WIND BAFFLES.

2. PROVIDE WALL MOUNT BRACKETS FOR OUTDOOR UNIT. MOUNT OUTDOOR UNIT 36” OR MORE ABOVE GRADE.

3. PROVIDE OUTDOOR UNIT WITH DISCONNECT SWITCH AND NEMA4X ENCLOSURE TO BE PROVIDED BY EC.

4. EXISTING UNIT AND ACCESSORIES TO BE RELOCATED FROM BUILDING 37 TO BUILDING 36. NEW REFRIGERANT PIPING AND VALVES SHALL BE PROVIDED BY THE CONTRACTOR.

5. CONTRACTOR RESPONSIBLE FOR ALL TESTING AND COMMISSIONING NEEDED.

NOTES:

1. UNITS TO INCLUDE CONDENSATE PUMP AND FASCIA PANELS. CONTRACTOR TO FIELD INSTALL.

2. PROVIDE 10 YEAR MANUFACTURERS WARRANTY ON COMPRESSOR AS WELL AS PARTS & DEFECTS, WITH ONE YEAR LABOR WARRANTY.

3. LOW-AMBIENT COOLING TO -40°F

4. PROVIDE EXTERNAL CONTACT CONTROL INTERFACE FOR CONNECTION TO THE BUILDING MANAGEMENT SYSTEM TO REPORT STATUS / ALARM.

5. PROVIDE CEILING HANGERS FOR INSTALLATION OF INDOOR UNIT.

6. PROVIDE WALL MOUNT BRACKET FOR INSTALLATION OF INDOOR UNIT.

7. EXISTING UNIT AND ACCESSORIES TO BE RELOCATED FROM BUILDING 37 TO BUILDING 36. NEW REFRIGERANT PIPING AND VALVES WILL BE PROVIDED BY THE CONTRACTOR.

8. CONTRACTOR RESPONSIBLE FOR ALL START UP TESTING, AND COMMISSIONING.

SRVC.RM

# 06

EXISTING

CONDENSER

UNIT (ETR)

EXISTING

EXHAUST FAN

SERVER RACK #1

PROVIDE 3 TON CONDENSER

UNIT AND WALL MOUNTED

SUPPORTS FOR CONDENSER.

PROVIDE 36,000 BTU

CEILING HUNG

CASSETTE UNIT

PROVIDE

3/8" RL,

5/8" RG, AND

1-1/4" DRAIN

AC-05

CU-05

CONNECT 1-1/4"

DRAIN INTO

STORM LINE

T

PROVIDE

THERMOSTAT

1355 EAST TITUS AVENUE « ROCHESTER, NY 14622

(585) 448 - 0686 « www.Patriot-DC.com

P TRIOT

DESIGN & CONSULTING

STILL SERVING

ISSUED FOR BID

SCALE: 1/2" = 1'-0"

BUILDING 5 ROOM 6 SWITCH ROOM MECHANICAL PLAN

NORTH

SCALE: NONE

BUILDING 5 KEYPLAN

PLAN KEYNOTES:

1. SEAL EXTERIOR WALL PENETRATIONS WATERTIGHT. PROVIDE ESCUTCHEONS ON INTERIOR AND

ZINC PLATED STEEL WALL PLATE ON EXTERIOR.

2. CONTRACTOR SHALL PROTECT ALL EXISTING SERVERS, ELECTRONICS, AND ACCESSORIES FROM CONTAMINATION. PROVIDE TEMPORARY ICRA BARRIER. USE DURING ALL WORK THAT WILL CREATE DUST, DIRT, FUMES, OR OTHER AIR-BORNE PARTICLES. COORDINATE ALL DUST CONTROL MEASURES WITH COR PRIOR TO COMMENCING WORK. CONTRACTOR IS REQUIRED TO RUN HEPA VAC WHILE ALL WORK TAKES PLACE TO CAPTURE FUMES, DUST, & DEBRIS.REFER TO SPECIFICATION 01 35 26

SECTION 1.12.

3. PROVIDE OUTDOOR PIPE WRAP ON ALL EXTERIOR INSULATION. REFER TO SPECIFICATION 230711, HVAC INSULATION.

4. EXTEND A BMS (CAT 6) CONNECTION FROM THE INDOOR UNIT TO THE EXISTING BMS GATEWAY

LOCATED IN THE SERVER RACK. REFER TO DWG M-001 FOR BMS CONTROL POINT SCHEDULE.

X

GENERAL NOTES:

1. PROVIDE CONTROL WIRING AND RACEWAY TO WALL-MOUNT ROOM THERMOSTAT FROM INDOOR UNIT, OR FROM MASTER INDOOR UNIT FOR MULTI-UNIT SYSTEMS. MOUNT THERMOSTAT NEAR THE BACK OF THE SERVER RACK TO ENSURE THAT THERMOSTAT EFFECTIVELY READS THE HIGH TEMPERATURES

EXPELLED FROM EQUIPMENT ON SERVER RACK.

2. REFER TO ELECTRICAL DRAWINGS FOR POWER WIRING TO OUTDOOR CONDENSING UNITS AND

POWER & CONTROL WIRING FROM OUTDOOR UNIT TO INDOOR EVAPORATOR UNITS.

LINEN

WOMEN

1B

14A

EBX1

SERVER RACK #1

EXISTING

EXHAUST FAN

PROVIDE 3/8" RL,

5/8" RG, AND

1-1/4" DRAIN

PROVIDE 24,000

BTU CEILING HUNG

CASSETTE UNIT

PROVIDE 3/8" RL,

5/8" RG, AND

1-1/4" DRAIN

PROVIDE 4 TON CONDENSER

UNIT AND WALL MOUNTED

SUPPORTS FOR CONDENSER.

AC-06B

CU-06

PROVIDE 3/8" RL,

5/8" RG, AND

1-1/4" DRAIN

PROVIDE REFRIGERANT

Y-CONNECTORS WHERE

PIPING BRANCHES OFF

AC-06A

CO

T

PROVIDE

THERMOSTAT

1355 EAST TITUS AVENUE « ROCHESTER, NY 14622

(585) 448 - 0686 « www.Patriot-DC.com

P TRIOT

DESIGN & CONSULTING

STILL SERVING

ISSUED FOR BID

SCALE: 1/2" = 1'-0"

BUILDING 6 ROOM 1B SWITCH ROOM MECHANICAL PLAN

SCALE: NONE

BUILDING 6 KEYPLAN

NORTH

PLAN KEYNOTES:

1. SEAL EXTERIOR WALL PENETRATIONS WATERTIGHT. PROVIDE ESCUTCHEONS ON INTERIOR AND ZINC

PLATED STEEL WALL PLATE ON EXTERIOR.

2. CONTRACTOR SHALL PROTECT ALL EXISTING SERVERS, ELECTRONICS, AND ACCESSORIES FROM CONTAMINATION. PROVIDE TEMPORARY ICRA BARRIER. USE DURING ALL WORK THAT WILL CREATE DUST, DIRT, FUMES, OR OTHER AIR-BORNE PARTICLES. COORDINATE ALL DUST CONTROL MEASURES WITH COR PRIOR TO COMMENCING WORK. CONTRACTOR IS REQUIRED TO RUN HEPA VAC WHILE ALL WORK TAKES PLACE TO CAPTURE FUMES, DUST, & DEBRIS.REFER TO SPECIFICATION 01 35 26 SECTION 1.12.

3. PROVIDE OUTDOOR PIPE WRAP ON ALL EXTERIOR INSULATION. REFER TO SPECIFICATION 230711, HVAC

INSULATION.

4. EXTEND A BMS (CAT 6) CONNECTION FROM THE INDOOR UNIT TO THE EXISTING BMS GATEWAY LOCATED IN

THE SERVER RACK. REFER TO DWG M-001 FOR BMS CONTROL POINT SCHEDULE.

5. PROVIDE CONTROLS INTERFACE BETWEEN EACH INDOOR UNIT (CAT 6 OR MANUFACTURE'S ALTERNATIVE)

6. PROVIDE CONCRETE SPLASH BLOCK.

X

GENERAL NOTES:

1. PROVIDE CONTROL WIRING AND RACEWAY TO WALL-MOUNT ROOM THERMOSTAT FROM INDOOR UNIT, OR FROM MASTER INDOOR UNIT FOR MULTI-UNIT SYSTEMS. MOUNT THERMOSTAT NEAR THE BACK OF THE SERVER RACK TO ENSURE THAT THERMOSTAT EFFECTIVELY READS THE HIGH TEMPERATURES

EXPELLED FROM EQUIPMENT ON SERVER RACK.

14A 14

14B-EBX2

SOILED LINENEQUIP

IT ROOM

SERVER

RACK #2

SE

R

VE

R

R

AC

K #1

EXISTING

EXHAUST FAN

PROVIDE 36,000

BTU CEILING

HUNG UNIT

PROVIDE 3 TON CONDENSER UNIT

AND WALL MOUNTED SUPPORTS

FOR CONDENSER.

CU-07

AC-07

PROVIDE 3/8" RL,

5/8" RG, AND

1-1/4" DRAIN

T

PROVIDE

THERMOSTAT

1355 EAST TITUS AVENUE « ROCHESTER, NY 14622

(585) 448 - 0686 « www.Patriot-DC.com

P TRIOT

DESIGN & CONSULTING

STILL SERVING

ISSUED FOR BID

SCALE: 1/2" = 1'-0"

BUILDING 7 ROOM 14B SWITCH ROOM MECHANICAL PLAN

SCALE: NONE

BUILDING 7 KEYPLAN NORTH

PLAN KEYNOTES:

1. SEAL EXTERIOR WALL PENETRATIONS WATERTIGHT. PROVIDE ESCUTCHEONS ON INTERIOR AND

ZINC PLATED STEEL WALL PLATE ON EXTERIOR.

2. CONTRACTOR SHALL PROTECT ALL EXISTING SERVERS, ELECTRONICS, AND ACCESSORIES FROM CONTAMINATION. PROVIDE TEMPORARY ICRA BARRIER. USE DURING ALL WORK THAT WILL CREATE DUST, DIRT, FUMES, OR OTHER AIR-BORNE PARTICLES. COORDINATE ALL DUST CONTROL MEASURES WITH COR PRIOR TO COMMENCING WORK. CONTRACTOR IS REQUIRED TO RUN HEPA VAC WHILE ALL WORK TAKES PLACE TO CAPTURE FUMES, DUST, & DEBRIS.REFER TO SPECIFICATION 01 35 26

SECTION 1.12.

3. PROVIDE OUTDOOR PIPE WRAP ON ALL EXTERIOR INSULATION. REFER TO SPECIFICATION 230711, HVAC INSULATION.

4. EXTEND A BMS (CAT 6) CONNECTION FROM THE INDOOR UNIT TO THE EXISTING BMS GATEWAY

LOCATED IN THE SERVER RACK. REFER TO DWG M-001 FOR BMS CONTROL POINT SCHEDULE.

5. PROVIDE CONCRETE SPLASH BLOCK.

X

GENERAL NOTES:

1. PROVIDE CONTROL WIRING AND RACEWAY TO WALL-MOUNT ROOM THERMOSTAT FROM INDOOR UNIT, OR FROM MASTER INDOOR UNIT FOR MULTI-UNIT SYSTEMS. MOUNT THERMOSTAT NEAR THE BACK OF THE SERVER RACK TO ENSURE THAT THERMOSTAT EFFECTIVELY READS THE HIGH TEMPERATURES

EXPELLED FROM EQUIPMENT ON SERVER RACK.

CBX1

SERV. RM

NURSNG

NOOK

2A

EBX1

SERVER

RACK #2

SERVER

RACK #1

EXISTING

EXHAUST FAN

PROVIDE 24,000

BTU WALL

MOUNTED UNIT

PROVIDE 4 TON CONDENSER

UNIT AND WALL MOUNTED

SUPPORTS FOR CONDENSER.

CU-08

AC-08B

AC-08A

PROVIDE REFRIGERANT

Y-CONNECTOR WHERE

PIPING BRANCHES OFF.

PROVIDE Y CONNECTION

AND CLEAN OUT ON

DRAIN LINE.

PROVIDE 3/8" RL,

5/8" RG, AND

1-1/4" DRAIN

PROVIDE 24,000

BTU WALL

MOUNTED UNIT

PROVIDE 3/8" RL,

5/8" RG, AND

1-1/4" DRAIN

PROVIDE 3/8" RL,

5/8" RG, AND

1-1/4" DRAIN

T

PROVIDE

THERMOSTAT

1355 EAST TITUS AVENUE « ROCHESTER, NY 14622

(585) 448 - 0686 « www.Patriot-DC.com

P TRIOT

DESIGN & CONSULTING

STILL SERVING

ISSUED FOR BID

SCALE: 1/2" = 1'-0"

BUILDING 8 ROOM 1A SWITCH ROOM MECHANICAL PLAN

SCALE: NONE

BUILDING 8 KEYPLAN NORTH

PLAN KEYNOTES:

1. SEAL EXTERIOR WALL PENETRATIONS WATERTIGHT. PROVIDE ESCUTCHEONS ON INTERIOR AND ZINC

PLATED STEEL WALL PLATE ON EXTERIOR.

2. CONTRACTOR SHALL PROTECT ALL EXISTING SERVERS, ELECTRONICS, AND ACCESSORIES FROM CONTAMINATION. PROVIDE TEMPORARY ICRA BARRIER. USE DURING ALL WORK THAT WILL CREATE DUST, DIRT, FUMES, OR OTHER AIR-BORNE PARTICLES. COORDINATE ALL DUST CONTROL MEASURES WITH COR PRIOR TO COMMENCING WORK. CONTRACTOR IS REQUIRED TO RUN HEPA VAC WHILE ALL WORK TAKES PLACE TO CAPTURE FUMES, DUST, & DEBRIS.REFER TO SPECIFICATION 01 35 26 SECTION 1.12.

3. PROVIDE OUTDOOR PIPE WRAP ON ALL EXTERIOR INSULATION. REFER TO SPECIFICATION 230711, HVAC

INSULATION.

4. EXTEND A BMS (CAT 6) CONNECTION FROM THE INDOOR UNIT TO THE EXISTING BMS GATEWAY LOCATED IN

THE SERVER RACK. REFER TO DWG M-001 FOR BMS CONTROL POINT SCHEDULE.

5. PROVIDE CONTROLS INTERFACE BETWEEN EACH INDOOR UNIT (CAT 6 OR MANUFACTURE'S ALTERNATIVE)

6. PROVIDE CONCRETE SPLASH BLOCK.

X

GENERAL NOTES:

1. PROVIDE CONTROL WIRING AND RACEWAY TO WALL-MOUNT ROOM THERMOSTAT FROM INDOOR UNIT, OR FROM MASTER INDOOR UNIT FOR MULTI-UNIT SYSTEMS. MOUNT THERMOSTAT NEAR THE BACK OF THE SERVER RACK TO ENSURE THAT THERMOSTAT EFFECTIVELY READS THE HIGH TEMPERATURES

EXPELLED FROM EQUIPMENT ON SERVER RACK.

D O

W N

13EB-2

IS/IT

SVC. RM VRC

SUPPT COORD

SERVER

RACK #1

PROVIDE 3/8" RL,

5/8" RG, AND

1-1/4" DRAIN

INSTALL 24,000 BTU

WALL MOUNTED UNIT.

INSTALL 2 TON CONDENSER UNIT.

PROVIDE WALL MOUNTED

SUPPORTS FOR CONDENSER.

AC-36

CU-36

INSTALL

CONDENSATE

PUMP

T

PROVIDE

THERMOSTAT

1355 EAST TITUS AVENUE « ROCHESTER, NY 14622

(585) 448 - 0686 « www.Patriot-DC.com

P TRIOT

DESIGN & CONSULTING

STILL SERVING

ISSUED FOR BID

SCALE: 1/2" = 1'-0"

BUILDING 36 ROOM 13 SWITCH ROOM MECHANICAL PLAN

SCALE: NONE

BUILDING 36 KEYPLAN NORTH

PLAN KEYNOTES:

1. SEAL EXTERIOR WALL PENETRATIONS WATERTIGHT. PROVIDE ESCUTCHEONS ON INTERIOR AND

ZINC PLATED STEEL WALL PLATE ON EXTERIOR.

2. CONTRACTOR SHALL PROTECT ALL EXISTING SERVERS, ELECTRONICS, AND ACCESSORIES FROM CONTAMINATION. PROVIDE TEMPORARY ICRA BARRIER. USE DURING ALL WORK THAT WILL CREATE DUST, DIRT, FUMES, OR OTHER AIR-BORNE PARTICLES. COORDINATE ALL DUST CONTROL MEASURES WITH COR PRIOR TO COMMENCING WORK. CONTRACTOR IS REQUIRED TO RUN HEPA VAC WHILE ALL WORK TAKES PLACE TO CAPTURE FUMES, DUST, & DEBRIS.REFER TO SPECIFICATION 01 35 26

SECTION 1.12.

3. PROVIDE OUTDOOR PIPE WRAP ON ALL EXTERIOR INSULATION. REFER TO SPECIFICATION 230711, HVAC INSULATION.

4. EXTEND A BMS (CAT 6) CONNECTION FROM THE INDOOR UNIT TO THE EXISTING BMS GATEWAY

LOCATED IN THE SERVER RACK. REFER TO DWG M-001 FOR BMS CONTROL POINT SCHEDULE.

5. PROVIDE CONCRETE SPLASH BLOCK.

X

GENERAL NOTES:

1. PROVIDE CONTROL WIRING AND RACEWAY TO WALL-MOUNT ROOM THERMOSTAT FROM INDOOR UNIT, OR FROM MASTER INDOOR UNIT FOR MULTI-UNIT SYSTEMS. MOUNT THERMOSTAT NEAR THE BACK OF THE SERVER RACK TO ENSURE THAT THERMOSTAT EFFECTIVELY READS THE HIGH TEMPERATURES

EXPELLED FROM EQUIPMENT ON SERVER RACK.

OPERATOR SUITE

POLICE

1A

RACK SERVER #1

24,000 BTU WALL

MOUNTED UNIT

(PKA-A24KA7)

2-TON CONDENSER

(PUY-A24NHA7)

PRIOR TO DISCONNECT,

EVACUATE AND STORE R-410A

REFRIGERANT FOR REUSE.

DISCONNECT AND REMOVE

EXISTING OUTDOOR CONDENSER

UNIT. SAVE FOR REUSE IN

BUILDING 36 SWITCH ROOM.

DISCONNECT

AND REMOVE

REFRIGERANT

PIPING AND

CONDENSATE

DRAIN LINE

DISCONNECT AND REMOVED

EXISTING WALL MOUNTED UNIT.

SAVE FOR REUSE IN BUILDING

36 SWITCH ROOM. PATCH AND

PAINT AFTER UNIT REMOVAL.

PATCH AND

PAINT AFTER

UNIT REMOVAL

OPERATOR SUITE

POLICE

1A

CU-B37

RACK SERVER #1

PROVIDE 4 TON CONDENSER

UNIT AND WALL MOUNTED

SUPPORTS FOR CONDENSER.

AC-B37-A

PROVIDE 3/8" RL,

5/8" RG, AND

1-1/4" DRAIN

PROVIDE 12,000

BTU CEILING

MOUNTED UNIT

PROVIDE 24,000

BTU WALL

MOUNTED UNIT

RACK SERVER #1

PROVIDE

REFRIGERANT

Y-CONNECTOR

WHERE PIPING

BRANCHES OFF

AC-B37-C

PROVIDE 12,000

BTU CEILING UNIT

PROVIDE 3/8" RL,

5/8" RG, AND

1-1/4" DRAIN

PROVIDE 1/4" RL,

1/2" RG, AND

1-1/4" DRAIN

PROVIDE 1/4" RL,

1/2" RG, AND

1-1/4" DRAIN

CO

CO

AC-B37-B

T

PROVIDE

THERMOSTAT

1355 EAST TITUS AVENUE « ROCHESTER, NY 14622

(585) 448 - 0686 « www.Patriot-DC.com

P TRIOT

DESIGN & CONSULTING

STILL SERVING

ISSUED FOR BID

SCALE: 1/2" = 1'-0"

BUILDING 37 ROOM 1A AND 20 SWITCH ROOM MECHANICAL DEMOLITION PLAN

SCALE: 1/2" = 1'-0"

BUILDING 37 ROOM 1A AND 20 SWITCH ROOM MECHANICAL PLAN

SCALE: NONE

BUILDING 37 KEYPLAN NORTH

PLAN KEYNOTES:

1. SEAL EXTERIOR WALL PENETRATIONS WATERTIGHT. PROVIDE ESCUTCHEONS ON INTERIOR AND ZINC

PLATED STEEL WALL PLATE ON EXTERIOR.

2. CONTRACTOR SHALL PROTECT ALL EXISTING SERVERS, ELECTRONICS, AND ACCESSORIES FROM CONTAMINATION. PROVIDE TEMPORARY ICRA BARRIER. USE DURING ALL WORK THAT WILL CREATE DUST, DIRT, FUMES, OR OTHER AIR-BORNE PARTICLES. COORDINATE ALL DUST CONTROL MEASURES WITH COR PRIOR TO COMMENCING WORK. CONTRACTOR IS REQUIRED TO RUN HEPA VAC WHILE ALL WORK TAKES PLACE TO CAPTURE FUMES, DUST, & DEBRIS.REFER TO SPECIFICATION 01 35 26 SECTION 1.12.

3. PROVIDE OUTDOOR PIPE WRAP ON ALL EXTERIOR INSULATION. REFER TO SPECIFICATION 230711, HVAC

INSULATION.

4. EXTEND A BMS (CAT 6) CONNECTION FROM THE INDOOR UNIT TO THE EXISTING BMS GATEWAY LOCATED IN

THE SERVER RACK. REFER TO DWG M-001 FOR BMS CONTROL POINT SCHEDULE.

5. PROVIDE CONTROLS INTERFACE BETWEEN EACH INDOOR UNIT (CAT 6 OR MANUFACTURE'S ALTERNATIVE).

6. PROVIDE CONCRETE SPLASH BLOCK.

X

GENERAL NOTES:

1. PROVIDE CONTROL WIRING AND RACEWAY TO WALL-MOUNT ROOM THERMOSTAT FROM INDOOR UNIT, OR FROM MASTER INDOOR UNIT FOR MULTI-UNIT SYSTEMS. MOUNT THERMOSTAT NEAR THE BACK OF THE SERVER RACK TO ENSURE THAT THERMOSTAT EFFECTIVELY READS THE HIGH TEMPERATURES

EXPELLED FROM EQUIPMENT ON SERVER RACK.

COE

PRGRM ANLST.

COE

RSRCH

EMS

HAC

IS/IT

SVC RM

RACK SERVER #1

36,000 BTU DAIKIN

WALL MOUNTED UNIT

(FTXS36HVJU)

3-TON CONDENSER

(RXS36HVJU)

DISCONNECT AND

REMOVE EXISTING

OUTDOOR CONDENSER

UNIT. REMOVE

EXISTING SUPPORTS.

DISCONNECT AND REMOVE

REFRIGERANT PIPING

DISCONNECT AND REMOVE

REFRIGERANT PIPING AND

CONDENSATE DRAIN LINE

PRIOR TO DISCONNECT,

EVACUATE, AND RECYCLE

REFRIGERANT. DISCONNECT AND

REMOVE EXISTING OUTDOOR

CONDENSER UNIT. PATCH AND

PAINT AFTER UNIT REMOVAL.

PATCH AND

PAINT AFTER

UNIT REMOVAL

COE

PRGRM ANLST.

COE

RSRCH

EMS

HAC

IS/IT

SVC RM

RACK SERVER #1PROVIDE 3/8" RL

AND 5/8" RG

PROVIDE 3 TON CONDENSER

UNIT AND WALL SUPPORTS

FOR CONDENSER. CU-37-1

AC-37-1

PROVIDE 36,000 BTU WALL

MOUNTED UNIT

PROVIDE 1-1/4" DRAIN.

ROUTE ABOVE CEILING.

1-1/4" DRAIN DOWN TO

EXISTING MOP SINK

PROVIDE WALL SUPPORT

FOR PIPING ALONG WALL

T

PROVIDE

THERMOSTAT

1355 EAST TITUS AVENUE « ROCHESTER, NY 14622

(585) 448 - 0686 « www.Patriot-DC.com

P TRIOT

DESIGN & CONSULTING

STILL SERVING

ISSUED FOR BID

SCALE: 1/2" = 1'-0"

BUILDING 37 ROOM 137 SWITCH ROOM MECHANICAL DEMOLITION PLAN

SCALE: 1/2" = 1'-0"

BUILDING 37 ROOM 137 SWITCH ROOM MECHANICAL PLAN

SCALE: NONE

BUILDING 37 KEYPLAN NORTH

PLAN KEYNOTES:

1. SEAL EXTERIOR WALL PENETRATIONS WATERTIGHT. PROVIDE ESCUTCHEONS ON INTERIOR AND

ZINC PLATED STEEL WALL PLATE ON EXTERIOR.

2. CONTRACTOR SHALL PROTECT ALL EXISTING SERVERS, ELECTRONICS, AND ACCESSORIES FROM CONTAMINATION. PROVIDE TEMPORARY ICRA BARRIER. USE DURING ALL WORK THAT WILL CREATE DUST, DIRT, FUMES, OR OTHER AIR-BORNE PARTICLES. COORDINATE ALL DUST CONTROL MEASURES WITH COR PRIOR TO COMMENCING WORK. CONTRACTOR IS REQUIRED TO RUN HEPA VAC WHILE ALL WORK TAKES PLACE TO CAPTURE FUMES, DUST, & DEBRIS.REFER TO SPECIFICATION 01 35 26

SECTION 1.12.

3. PROVIDE OUTDOOR PIPE WRAP ON ALL EXTERIOR INSULATION. REFER TO SPECIFICATION 230711, HVAC INSULATION.

4. EXTEND A BMS (CAT 6) CONNECTION FROM THE INDOOR UNIT TO THE EXISTING BMS GATEWAY

LOCATED IN THE SERVER RACK. REFER TO DWG M-001 FOR BMS CONTROL POINT SCHEDULE.

X

GENERAL NOTES:

1. PROVIDE CONTROL WIRING AND RACEWAY TO WALL-MOUNT ROOM THERMOSTAT FROM INDOOR UNIT, OR FROM MASTER INDOOR UNIT FOR MULTI-UNIT SYSTEMS. MOUNT THERMOSTAT NEAR THE BACK OF THE SERVER RACK TO ENSURE THAT THERMOSTAT EFFECTIVELY READS THE HIGH TEMPERATURES

EXPELLED FROM EQUIPMENT ON SERVER RACK.

TIN SHOP

ELEC. SVC. RM

ENG

SVC. RM

10 ENG

RACK SERVER #1

PRIOR TO DISCONNECT,

EVACUATE, AND RECYCLE

REFRIGERANT. DISCONNECT

AND REMOVE EXISTING

OUTDOOR CONDENSER UNIT.

PATCH AND PAINT AFTER

UNIT REMOVAL

DISCONNECT AND REMOVE

REFRIGERANT PIPING AND

CONDENSATE DRAIN LINE

DISCONNECT AND REMOVE

EXISTING OUTDOOR

CONDENSER UNIT. REMOVE

EXISTING SUPPORTS.

TIN SHOP

ELEC. SVC. RM

ENG

SVC. RM

10 ENG

RACK SERVER #1

PROVIDE 36,000 BTU

WALL MOUNTED UNIT

PROVIDE 3/8" RL, 5/8" RG,

AND 1-1/4" DRAIN

PROVIDE 3 TON CONDENSER

UNIT AND WALL MOUNTED

SUPPORTS FOR CONDENSER.

CU-118

AC-118

T

PROVIDE

THERMOSTAT

1355 EAST TITUS AVENUE « ROCHESTER, NY 14622

(585) 448 - 0686 « www.Patriot-DC.com

P TRIOT

DESIGN & CONSULTING

STILL SERVING

ISSUED FOR BID

SCALE: 1/2" = 1'-0"

BUILDING 118 ROOM 9 SWITCH ROOM MECHANICAL DEMOLITION PLAN

SCALE: 1/2" = 1'-0"

BUILDING 118 ROOM 9 SWITCH ROOM MECHANICAL PLAN

SCALE: NONE

BUILDING 118 KEYPLAN NORTH

PLAN KEYNOTES:

1. SEAL EXTERIOR WALL PENETRATIONS WATERTIGHT. PROVIDE ESCUTCHEONS ON INTERIOR AND ZINC

PLATED STEEL WALL PLATE ON EXTERIOR.

2. CONTRACTOR SHALL PROTECT ALL EXISTING SERVERS, ELECTRONICS, AND ACCESSORIES FROM CONTAMINATION. PROVIDE TEMPORARY ICRA BARRIER. USE DURING ALL WORK THAT WILL CREATE DUST, DIRT, FUMES, OR OTHER AIR-BORNE PARTICLES. COORDINATE ALL DUST CONTROL MEASURES WITH COR PRIOR TO COMMENCING WORK. CONTRACTOR IS REQUIRED TO RUN HEPA VAC WHILE ALL WORK TAKES PLACE TO CAPTURE FUMES, DUST, & DEBRIS.REFER TO SPECIFICATION 01 35 26 SECTION 1.12.

3. PROVIDE OUTDOOR PIPE WRAP ON ALL EXTERIOR INSULATION. REFER TO SPECIFICATION 230711, HVAC

INSULATION.

4. EXTEND A BMS (CAT 6) CONNECTION FROM THE INDOOR UNIT TO THE EXISTING BMS GATEWAY LOCATED IN

THE SERVER RACK. REFER TO DWG M-001 FOR BMS CONTROL POINT SCHEDULE.

5. PROVIDE CONCRETE SPLASH BLOCK.

X

GENERAL NOTES:

1. PROVIDE CONTROL WIRING AND RACEWAY TO WALL-MOUNT ROOM THERMOSTAT FROM INDOOR UNIT, OR FROM MASTER INDOOR UNIT FOR MULTI-UNIT SYSTEMS. MOUNT THERMOSTAT NEAR THE BACK OF THE SERVER RACK TO ENSURE THAT THERMOSTAT EFFECTIVELY READS THE HIGH TEMPERATURES

EXPELLED FROM EQUIPMENT ON SERVER RACK.

1355 EAST TITUS AVENUE « ROCHESTER, NY 14622

(585) 448 - 0686 « www.Patriot-DC.com

P TRIOT

DESIGN & CONSULTING

STILL SERVING

ISSUED FOR BID

2 NTS

WALL MOUNTED SUPPORT FOR EQUIPMENT DETAIL

GENERAL NOTES:

1. WALL BRACKER MATERIALS SHALL BE AISI 1045 STEEL OR EQUIVALENT OR STRONGER. COAT WITH

NON-CORROSIVE COATING AND PAINT.

2. ALL ANCHORS USED TO MOUNT WALL BRACKET TO SURROUNDING STRUCTURE .

3. ALL HARDWARE (SCREWS/FASTENERS) SHALL BE STAINLESS STEEL CORROSION RESISTANT.

4. MOUNT AS RECOMMENDED BY CONDENSER MANUFACTURER.

CONDENSER UNITCONDENSER UNIT

WALL MOUNTED

SUPPORT BRACKET

WALL

MOUNTED

SUPPORT

BRACKET

FRONT VIEW SIDE VIEW

ADJUSTABLE CLEVIS HANGER

TYPE 1 - SEE SPECIFICATIONS

ADJUSTABLE CLEVIS HANGER

TYPE 43 - SEE SPECIFICATIONS

PROVIDE INSULATION

SHIELD & INSERT FOR

ALL PIPING MIN.)

BAND

1/2" DIA. HANGER RODS WITH 36" MAX.

SPACING ON EACH CHANNEL

WELD

SADDLE

INSULATION SHIELD

AT HANGER

PROVIDE HIGH COMPRESSIVE

STRENGTH INSULATION (9

PSF MIN. DENSITY) UNDER

INSULATION SHIELD

INSULATION (VAPOR

BARRIER TYPE IS

REQUIRED FOR LOW

TEMPERATURE PIPE)

HANGER ROD

1" M

AX

3 NTS

PIPE HANGER DETAIL

MIN.

3/4"

PENETRATION

FIRECODE COMPOUND

THERMAFIBER SAFING

INSULATION

WALL ASSEMBLY

WRAP STRIP

STEEL COLLAR

4 NTS

PIPE PENETRATION THRU RATED WALL DETAIL

T

1 NTS

AC SYSTEM REFRIGERANT PIPING DETAIL

NOTES:

1. REFRIGERANT LINES SHALL BE SIZED AND

ROUTED AS PER MANUFACTURER'S

RECOMMENDATIONS.

2. MULTIPLE REFRIGERANT CIRCUITS SHALL

BE TYPICAL TO SINGLE CIRCUIT SHOWN.

DIRECT

EXPANSION

COIL

INDOOR UNIT

THERMAL EXPANSION

VALVE

SOLENOID VALVE

ISOLATION

VALVES

CONDENSER

UNIT

RECEIVER

COMPRESSOR

CONDENSER

CONDENSER

FAN

FILTER/DRIER WITH

CHANGING PART

OIL TRAP

SIGHT GLASS AND

LIQUID INDICATOR

ISOLATION VALVES

RLRG

TO

DRAIN

D

RG

Y-CONNECTOR

TO ADDITIONAL UNIT

CEILING CASSETTE

UNIT

NON-CORROSIVE NUT & WASHER

HANGER ROD GALVANIZED OR

PAINTED (SEE SPEC.)

FAN FACE

EXPANSION BOLT

STEEL ROD

DETAIL B

NUT

DETAIL A

STEEL ROD

STEEL ANGLE

WASHER

NOTE:

ALL STEEL SUPPORTS SHALL

BE PAINTED WITH 2 COATS

OF ANTI-RUST PAINT AND 1

COAT OF FINISHED COAT OR

AS SPECIFIED.

SEE DETAIL B

SLAB

5 NTS

CEILING CASSETTE HANGER DETAIL

PRESSURE PLATE

INTERIOR WALL

BOLT

6 NTS

PIPE PENETRATION THRU EXTERIOR WALL DETAIL

NON-CORROSIVE

NUT & WASHER

ESCUTCHEON

EXTERIOR WALL

RUBBER VIBRATION WASHER

1-5/8" 12 GAUGE CHANNEL

OR 2"X2"X1/4" ANGLE

CORE DRILLED HOLE

27"

17"

MIN. 30" SPACE

STEEL CHANNEL

NUT & WASHER

(NON-CORROSIVE)

U-BOLT OR BAND STRAP

PIPE

WALL

NON-CORROSIVE

MASONRY BOLT

7 NTS

PIPE SUPPORT ON EXTERIOR WALL DETAIL

NTS

EXISTING

EXISTING CONTROL

SYSTEM TO REMAINNEW BACNET

PORTABLE

OPERATOR

TERMINAL

EXISTING ENGINEERING

CONTROL CENTER - UPGRADE

ECC WITH NEW BACNET

SOFTWARE

ECC

EXISTING

CONTROLLER

PROTOCOL

NETWORK

B-ASC

EXIST.

GLOBAL

EXIST.

CONTROLLER

B-ASC

EXIST.

B-ASC

EXIST.

B-ASC

EXIST.

B-ASC

EXIST.

B-ASC

EXIST.

NOTES:

1. REUSE EXISTING COMMUNICATION NETWORK UP TO

BACNET CONTROLLER IN EXISTING SERVER RACK IN

EACH BUILDING.

2. INSTALL NEW EQUIPMENT CONTROLLERS (B-AAC, B-ASC)

AS REQUIRED.

B-ASC

EXISTING COMMUNICATION NETWORK

B-ASC

B-ASC

B-ASC

B-ASC

B-ASC

B-AAC B-AAC

BACNET

BUILDING

CONTROLLER

(B-BC)

BACNET

BUILDING

CONTROLLER

(B-BC)

MSTP COMMUNICATION

(TYPICAL)

STAINLESS

STEEL PLATE

FILL ANNULAR GAPS ON

EACH SIDE OF SLEEVE

WITH NONCOMBUSTIBLE

SEALANT.

INTERIOR

INSULATION

INSULATION (WITH

OUTDOOR JACKET)

ELECTRICAL EQUIPMENT AND CONTROL SCHEDULE

EQUIPMENT SUPPLY CONTROL DEVICES

1 FLA

REFERENCE NOTES:

1. INDOOR UNIT RECEIVES POWER FROM THE OUTSIDE CONDENSER

UNIT. PROVIDE ALL POWER & SIGNAL WIRING AND RACEWAYS AS

REQUIRED FOR A COMPLETE WORKING SYSTEM.

2. REMOVE EXISTING 20/1 CB IN PANEL & MOVE TO OTHER PHASE TO

ACCOMMODATE INSTALLATION OF NEW 2 POLE CB.

3. PROVIDE NEMA 4X DISCONNECT SWITCH FOR OUTDOOR UNITS.

4. PROVIDE NEW CIRCUIT BREAKER IN PANEL.

5. CONTROL WIRING SHALL BE 16 AWG X 2 SHIELDED WIRE IN 3/4" C.

HP /

KW /

FLA PHASEVOLTAGE

PANEL/

CIRCUIT

NUMBER

CIRCUIT

BREAKER

OUTDOOR CONDENSER

WIRE & CONDUIT SIZE

REF

NOTES

DISC

SW

BY

E.C.

FUSED

DISC

SW

BY

E.C.

INTEGRAL

DISC

SW

BY

MFGR

MAN

MOTOR

START

BY

E.C.

MAG

START

BY

E.C.

COMB/

MAG

START

BY

E.C.EQUIPMENT NAMEID

INDOOR COOLING UNIT 1 1

TAG

1 FLA

17.3 FLAOUTDOOR CONDENSER UNIT 1 40/2 RPEM-GB

22.1 FLA 1 50/2 RPEM-GA 25,27

AU 2,3,4,5

1 40/2 RPEMG-B 25,27

AU

2 #10, 1 #10EG, 3/4" C.1 50/2 RPEM-GB

AU

SB-2 28,30

AU

AU

AU

AU

AU

ROOM

1B

1B

1A

1A

1A

1B

14B

1A

1A/20

BLDG

LOCATION

AC-05

AC-06A

AC-06B

AC-07

AC-08A

AC-08B

AC-B37-A

AC-B37-B

AC37-1

AC-118

CU-05

CU-06

CU-07

CU-08

CU-B37

CU-37-1

CU-118

INDOOR COOLING UNIT

INDOOR COOLING UNIT

INDOOR COOLING UNIT

INDOOR COOLING UNIT

INDOOR COOLING UNIT

INDOOR COOLING UNIT

INDOOR COOLING UNIT

INDOOR COOLING UNIT

INDOOR COOLING UNIT

OUTDOOR CONDENSER UNIT

OUTDOOR CONDENSER UNIT

OUTDOOR CONDENSER UNIT

OUTDOOR CONDENSER UNIT

OUTDOOR CONDENSER UNIT

OUTDOOR CONDENSER UNIT

14B7

1 FLA

2 #10, 1 #10EG, 3/4" C.

AC-36

CU-36 1 25/2 PP4 19,211336OUTDOOR CONDENSER UNIT

138 1INDOOR COOLING UNIT

2 #12, 1 #12 EG, 3/4" C.

2 #10, 1 #10EG, 3/4" C.

2 #10, 1 #10EG, 3/4" C.40/2 RPEM-1A 28,30

2 #10, 1 #10EG, 3/4" C.50/2

1 FLA

1 FLA

1 FLA

1 FLA

1 FLA

1 FLA

1 FLA

1 FLA

22.1 FLA

22.1 FLA

16.5 FLA

17.3 FLA

10 FLA

40/2 P-TS

2 #12, 1 #12 EG, 3/4" C.

2 #12, 1 #12 EG, 3/4" C.

2 #12, 1 #12 EG, 3/4" C.

2 #12, 1 #12 EG, 3/4" C.

2 #12, 1 #12 EG, 3/4" C.

2 #12, 1 #12 EG, 3/4" C.

2 #12, 1 #12 EG, 3/4" C.

2 #12, 1 #12 EG, 3/4" C.

2 #12, 1 #12 EG, 3/4" C.

2 #12, 1 #12 EG, 3/4" C.

ELECTRIC SYMBOL LIST

240/120V

EXISTING BRANCH CIRCUIT PANELBOARD, 208Y/120V OR

NEW HVAC EQUIPMENT

MOTOR CONNECTION ITEM NUMBER, REFER TO#

ELECTRIC EQUIPMENT & CONTROL SCHEDULE

DRAWING NOTE#

DENOTES NEW WORK OR EQUIPMENT

16.5 FLA

POWER FED FROM OUTDOOR UNIT

POWER FED FROM OUTDOOR UNIT

POWER FED FROM OUTDOOR UNIT

POWER FED FROM OUTDOOR UNIT

POWER FED FROM OUTDOOR UNIT

POWER FED FROM OUTDOOR UNIT

POWER FED FROM OUTDOOR UNIT

POWER FED FROM OUTDOOR UNIT

POWER FED FROM OUTDOOR UNIT

POWER FED FROM OUTDOOR UNIT

POWER FED FROM OUTDOOR UNIT

OUTDOOR

CONDENSER

INDOOR UNIT

POWER

PANEL

208V, 1Ø

INDOOR UNIT RECEIVES POWER

FROM THE OUTDOOR CONDENSERCONTROL WIRING

FROM CONDENSER

T

THERMOSTAT

1 NTS

TYPICAL SINGLE UNIT WIRING DIAGRAM

3,4,5

WIRING AS PER ELECTRICAL

EQUIPMENT AND CONTROL SCHEDULE

2 #10, 1 #10EG, 3/4" C.

2 #10, 1 #10EG, 3/4" C.

2 #10, 1 #10EG, 3/4" C.

3,4,5

3,4,5

3,4,5

3,4,5

3,4,5

3,4,5

1355 EAST TITUS AVENUE « ROCHESTER, NY 14622

(585) 448 - 0686 « www.Patriot-DC.com

P TRIOT

DESIGN & CONSULTING

STILL SERVING

ISSUED FOR BID

DISCONNECT SWITCH

INDOOR UNITS

WIRE &

CONDUIT SIZE

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

18 AWG, 3/4" C.

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

18 AWG, 3/4" C.

18 AWG, 3/4" C.

18 AWG, 3/4" C.

18 AWG, 3/4" C.

18 AWG, 3/4" C.

18 AWG, 3/4" C.

18 AWG, 3/4" C.

18 AWG, 3/4" C.

18 AWG, 3/4" C.

18 AWG, 3/4" C.

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

ASBESTOS AWARENESS NOTES

1. A PRE-RENOVATION SURVEY AND DOCUMENT REVIEW WAS PERFROMED BY WATTS

ARCHITECTURE & ENGINEERING IN NOVEMBER 2020 AND HAS BEEN INCLUDED IN THE

CONTRACT DOCUMENTS. ASBESTOS-CONTAINING MATERIALS (ACM) HAVE BEEN CONFIRMED

TO BE PRESENT IN SOME OF THE AREAS SCHEDULED FOR RENOVATION.

2. ASBESTOS-CONTAINING PIPE INSULATION, MUD FITTING INSULATION, 12” X 12” FLOOR TILES

(VARIOUS COLORS), 9” X 9” FLOOR TILES (VARIOUS COLORS), ASSOCIATED MASTIC AND

WINDOW GLAZING COMPOUND ARE LOCATED IN VARIOUS AREAS THROUGHOUT THE

BUILDINGS.

3. ALL CONTRACTORS ARE RESPONSIBLE FOR MAKING THEMSELVES AND THEIR EMPLOYEES

AWARE OF THE PRESENCE, LOCATION, AND QUANTITY OF EXISTING ASBESTOS-CONTAINING

BUILDING MATERIALS, AND TO WARN THEIR EMPLOYEES OF THE POTENTIAL DANGERS OF

EXPOSURE TO ASBESTOS. ANY DISTURBANCE OF ASBESTOS-CONTAINING MATERIALS SHALL

BE PERFORMED BY A LICENSED ASBESTOS ABATEMENT CONTRACTOR EMPLOYING CERTIFIED

WORKERS.

LEAD AWARENESS NOTES:

1. CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH OSHA 29 CFR 1926.62: LEAD

EXPOSURE IN CONSTRUCTION: INTERIM FINAL RULE FOR ALL ACTIVITIES DURING WHICH AN

EMPLOYEE MAY BE OCCUPATIONALLY EXPOSED TO LEAD. ALL CONTRACTORS SHALL ENSURE

THAT THEIR EMPLOYEES WEAR PROPER PERSONAL PROTECTIVE EQUIPMENT AND/OR UTILIZE

APPROPRIATE WORK METHODS TO PREVENT ELEVATED BLOOD LEAD LEVELS OR EXPOSURE

ABOVE THE PERMISSIBLE EXPOSURE LIMIT.

# 06

UP

SRVC.RM

AC-05

CU-05

EXISTING

EXHAUST FAN

(ETR)

EXISTING

CONDENSER

UNIT (ETR)

ELP-5

RUN POWER TO

OUTDOOR UNIT

PROVIDE

BREAKER

FOR CU-05

PROVIDE POWER CONNECTION

AND CONTROL SIGNAL FROM

OUTDOOR UNIT TO INDOOR

UNIT

PROVIDE IN

NEMA 4X

ENCLOSURE

SCALE: 1/2" = 1'-0"

BUILDING 5 ROOM 6 SWITCH ROOM ELECTRICAL PLAN

1355 EAST TITUS AVENUE « ROCHESTER, NY 14622

(585) 448 - 0686 « www.Patriot-DC.com

P TRIOT

DESIGN & CONSULTING

STILL SERVING

ISSUED FOR BID

SCALE: NONE

BUILDING 5 KEYPLAN NORTH

GENERAL NOTES:

1. REFER TO M-SERIES DRAWINGS FOR LOCATION OF DUST CONTROL MEASURES.

PERFORM ANY CUTTING, DRILLING, AND ANY WORK THAT MAY CREATE DIRT,

DUST, OR FUMES SHALL ONLY BE PERFORMED WITHIN THE TEMPORARY WORK

ENCLOSURES AND WITH CONTINUOUS HEPA VACUUM IN OPERATION FOR THE

DURATION OF WORK.

CBX2

14A

EBX1

1B

EXISTING

EXHAUST

FAN

CU-06

RPEM-GA

AC-06A AC-06B

RUN POWER TO

OUTDOOR UNIT

PROVIDE POWER

CONNECTION AND

CONTROL SIGNAL FROM

OUTDOOR UNIT TO

INDOOR UNITS

PROVIDE

BREAKER

FOR CU-06

PROVIDE IN

NEMA 4X

ENCLOSURE

BUILDING 6 ROOM 1B SWITCH ROOM ELECTRICAL PLAN

1355 EAST TITUS AVENUE « ROCHESTER, NY 14622

(585) 448 - 0686 « www.Patriot-DC.com

P TRIOT

DESIGN & CONSULTING

STILL SERVING

ISSUED FOR BID

BUILDING 6 KEYPLAN NORTH

SCALE: 1/2" = 1'-0" SCALE: NONE

GENERAL NOTES:

1. REFER TO M-SERIES DRAWINGS FOR LOCATION OF DUST CONTROL MEASURES.

PERFORM ANY CUTTING, DRILLING, AND ANY WORK THAT MAY CREATE DIRT,

DUST, OR FUMES SHALL ONLY BE PERFORMED WITHIN THE TEMPORARY WORK

14A 14

14B-EBX2

SBX2

15A

CBX2

SOILED LINENEQUIP

IT ROOM

SERVER

RACK #2

SE

R

VE

R

R

AC

K #1

AC-07

RPEMG-B

CU-07

RUN POWER TO

OUTDOOR UNIT

PROVIDE

BREAKER

FOR CU-07

PROVIDE POWER

CONNECTION AND

CONTROL SIGNAL FROM

OUTDOOR UNIT TO

INDOOR UNIT

PROVIDE IN

NEMA 4X

ENCLOSURE

SCALE: 1/2" = 1'-0"

BUILDING 7 ROOM 14B SWITCH ROOM ELECTRICAL PLAN

1355 EAST TITUS AVENUE « ROCHESTER, NY 14622

(585) 448 - 0686 « www.Patriot-DC.com

P TRIOT

DESIGN & CONSULTING

STILL SERVING

ISSUED FOR BID

SCALE: NONE

BUILDING 7 KEYPLAN NORTH

GENERAL NOTES:

1. REFER TO M-SERIES DRAWINGS FOR LOCATION OF DUST CONTROL MEASURES.

PERFORM ANY CUTTING, DRILLING, AND ANY WORK THAT MAY CREATE DIRT,

DUST, OR FUMES SHALL ONLY BE PERFORMED WITHIN THE TEMPORARY WORK

CBX1

10A

11 SBX2

13I

13J

CBX2

14B

14A

SERV. RM

CONFERENCE

SERV. RM

AUDIOLOGY

CHAPLAIN STOR

SPEECH/PATH

GROUP PROGRM. RM

BATH

CHAPLAIN SVC

COPY

AUDIOLOGIST

LAB

NURSNG

NOOK

2A

EBX1

SERVER

RACK #2SERVER

RACK #1

EXISTING

EXHAUST

FAN

AC-08A

AC-08B

CU-08

P1-A

P1

RPEM-GB

RUN POWER TO

OUTDOOR UNIT

PROVIDE

BREAKER

FOR CU-08

PROVIDE POWER

CONNECTION AND

CONTROL SIGNAL

FROM OUTDOOR UNIT

TO INDOOR UNITS PROVIDE IN

NEMA 4X

ENCLOSURE

SCALE: 1/4" = 1'-0"

BUILDING 8 ROOM 1A SWITCH ROOM ELECTRICAL PLAN

1355 EAST TITUS AVENUE « ROCHESTER, NY 14622

(585) 448 - 0686 « www.Patriot-DC.com

P TRIOT

DESIGN & CONSULTING

STILL SERVING

ISSUED FOR BID

SCALE: NONE

BUILDING 8 KEYPLAN NORTH

GENERAL NOTES:

1. REFER TO M-SERIES DRAWINGS FOR LOCATION OF DUST CONTROL MEASURES.

PERFORM ANY CUTTING, DRILLING, AND ANY WORK THAT MAY CREATE DIRT,

DUST, OR FUMES SHALL ONLY BE PERFORMED WITHIN THE TEMPORARY WORK

13EB-2

SB-1

SERVER

RACK #1

AC-36

CU-36

PP-4

PROVIDE

BREAKER

FOR CU-36

RUN POWER TO OUTDOOR UNIT

PROVIDE POWER CONNECTION

AND CONTROL SIGNAL FROM

OUTDOOR UNIT TO INDOOR UNIT

PROVIDE IN

NEMA 4X

ENCLOSURE

SCALE: 1/2" = 1'-0"

BUILDING 36 ROOM 13 SWITCH ROOM MECHANICAL PLAN

1355 EAST TITUS AVENUE « ROCHESTER, NY 14622

(585) 448 - 0686 « www.Patriot-DC.com

P TRIOT

DESIGN & CONSULTING

STILL SERVING

ISSUED FOR BID

SCALE: NONE

BUILDING 36 KEYPLAN NORTH

GENERAL NOTES:

1. REFER TO M-SERIES DRAWINGS FOR LOCATION OF DUST CONTROL MEASURES.

PERFORM ANY CUTTING, DRILLING, AND ANY WORK THAT MAY CREATE DIRT,

DUST, OR FUMES SHALL ONLY BE PERFORMED WITHIN THE TEMPORARY WORK

6A

6B

RACK

SERVER #1

AC-B37-A

CU-B37

SB-2

PROVIDE

BREAKER

FOR CU-B37

RUN POWER TO

OUTDOOR UNIT

PROVIDE IN

NEMA 4X

ENCLOSURE

1A

AC-B37-B

AC-B37-C

6A

6B

RACK

SERVER #1

SB-2

EXISTING CONDENSER UNIT

BEING REMOVED, REFER TO

MECHANICAL DRAWINGS.

DISCONNECT AND REMOVE

POWER BACK TO SOURCE PANEL.

1A

EXISTING AC UNIT TO BE

REMOVED, REFER TO

MECHANICAL DRAWINGS.

DISCONNECT AND REMOVE

POWER AND CONTROL SIGNAL

BACK TO OUTDOOR UNIT.

SCALE: 1/4 = 1'-0"

BUILDING 37 ROOM 1A AND 20 SWITCH ROOM ELECTRICAL PLAN

1355 EAST TITUS AVENUE « ROCHESTER, NY 14622

(585) 448 - 0686 « www.Patriot-DC.com

P TRIOT

DESIGN & CONSULTING

STILL SERVING

ISSUED FOR BID

SCALE: 1/4 = 1'-0"

BUILDING 37 ROOM 1A AND 20 SWITCH ROOM ELECTRICAL DEMOLITION PLAN

SCALE: NONE

BUILDING 37 KEYPLAN NORTH

GENERAL NOTES:

1. REFER TO M-SERIES DRAWINGS FOR LOCATION OF DUST CONTROL MEASURES.

PERFORM ANY CUTTING, DRILLING, AND ANY WORK THAT MAY CREATE DIRT,

DUST, OR FUMES SHALL ONLY BE PERFORMED WITHIN THE TEMPORARY WORK

RACK

SERVER #1

CU-37-1

AC-37-1

PROVIDE

BREAKER

FOR CU-37-1

RUN POWER TO

OUTDOOR UNIT

RPEM-1A

PROVIDE CONNECTION

AND CONTROL SIGNAL

FROM OUTDOOR UNIT

TO INDOOR UNIT

PROVIDE IN

NEMA 4X

ENCLOSURE

134 135

RACK

SERVER #1

EXISTING

CONDENSER

UNIT

RPEM-1A

DISCONNECT AND

REMOVE POWER

TO OUTDOOR UNIT

DISCONNECT POWER

TO POWER PANEL.

DISCONNECT AND

REMOVE POWER BACK

TO SOURCE PANEL.

134 135

EXISTING AC UNIT TO BE

REMOVED, REFER TO

MECHANICAL DRAWINGS.

DISCONNECT AND REMOVE

POWER AND CONTROL SIGNAL

BACK TO OUTDOOR UNIT.

SCALE: 1/4 = 1'-0"

BUILDING 37 ROOM 137 SWITCH ROOM ELECTRICAL PLAN

1355 EAST TITUS AVENUE « ROCHESTER, NY 14622

(585) 448 - 0686 « www.Patriot-DC.com

P TRIOT

DESIGN & CONSULTING

STILL SERVING

ISSUED FOR BID

SCALE: NONE

BUILDING 37 KEYPLAN NORTH

SCALE: 1/4 = 1'-0"

BUILDING 37 ROOM 137 SWITCH ROOM ELECTRICAL DEMOLITION PLAN

GENERAL NOTES:

1. REFER TO M-SERIES DRAWINGS FOR LOCATION OF DUST CONTROL MEASURES.

PERFORM ANY CUTTING, DRILLING, AND ANY WORK THAT MAY CREATE DIRT,

DUST, OR FUMES SHALL ONLY BE PERFORMED WITHIN THE TEMPORARY WORK

TIN SHOP

ELEC. SVC. RM

ENG

ENG

RACK SERVER #1

L/PP-4

CU-118

AC-118

P-TS

PROVIDE POWER

CONNECTION AND

CONTROL SIGNAL FROM

OUTDOOR UNIT TO

INDOOR UNIT

PROVIDE IN

NEMA 4X

ENCLOSURE

ELEC. SVC. RM

ENG

SVC. RM

RACK SERVER #1

L/PP-4

DISCONNECT AND REMOVE POWER BACK TO

SOURCE PANEL. DISCONNECT POWER AND

CONTROL SIGNAL BACK TO INDOOR UNIT.

EXISTING AC UNITS TO BE

REMOVED, REFER TO MECHANICAL

DRAWINGS. DISCONNECT AND

REMOVE POWER AND CONTROL

SIGNAL BACK TO OUTDOOR UNIT.

SCALE: 1/2" = 1'-0"

BUILDING 118 ROOM 9 SWITCH ROOM ELECTRICAL PLAN

1355 EAST TITUS AVENUE « ROCHESTER, NY 14622

(585) 448 - 0686 « www.Patriot-DC.com

P TRIOT

DESIGN & CONSULTING

STILL SERVING

ISSUED FOR BID

SCALE: NONE

BUILDING 118 KEYPLAN NORTH

SCALE: 1/2" = 1'-0"

BUILDING 118 ROOM 9 SWITCH ROOM ELECTRICAL DEMOLTION PLAN

GENERAL NOTES:

1. REFER TO M-SERIES DRAWINGS FOR LOCATION OF DUST CONTROL MEASURES.

PERFORM ANY CUTTING, DRILLING, AND ANY WORK THAT MAY CREATE DIRT,

DUST, OR FUMES SHALL ONLY BE PERFORMED WITHIN THE TEMPORARY WORK

Sheets and Views
GI-001-GI-001
M-001-M-001
B-05 M-M-101
B-06 M-M-102
B-07 M-M-103
B-08 M-M-104
B-36 M-M-105
B-37 M-M-106
B-37 M-M-107
B-118 M-M-108
M-001-M-201
E-001-E-001
B-05 E-E-101
B-06 E-E-102
B-07 E-E-103
B-08 E-E-104
B-36 E-E-105
B-37 E-E-106
B-37 E-E-107
B-118 E-E-108