S02 2021-08-09 VAC2001 Bid Set.pdf
PDF 8 MB Posted
- Attached to
- Z1DA--528A5-19-515 PROVIDE AC IN SWITCH ROOMS
- Solicitation number
- 36C24222B0030
About this file
This document is a solicitation for project number 585A5-19-515 to provide air conditioning in switch rooms at the Canandaigua VA Medical Center in Canandaigua, New York. The scope of work includes installing ductless mini-split AC units in eight switch rooms to provide adequate cooling for VA communications infrastructure. Electrical and demolition work is required. Specifications and drawings are provided. The total project duration is 120 days from submittal approval to final punch list completion. Bidders must comply with all applicable codes and VA standards.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24222B0030 0001.docx | DOCX document | |
| VAC2001 100percent Review Spec Book.pdf | ||
| 36C24222B0030_2.docx | DOCX document | |
| P07 - WAGE DETERMINATION.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PARKING
PARKING
PARKING
WATER TOWER
CAMPUS SITE PLAN
VAMC Canandaigua
RAMP
1355 TITUS AVE « ROCHESTER, NY 14622
(585) 448- 0686
P TRIOT
DESIGN & CONSULTING
STILL SERVING
DEPARTMENT OF VETERANS AFFAIRS
PROJECT NO. 528A5-19-515
CANANDAIGUA, NY
SCALE: NONE
SITE MAP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date:
NOTE:
USERS OF THESE DRAWINGS ARE RESPONSIBLE FOR
VERIFYING EXISTING DIMENSIONS AND CONDITIONS
IN THE FIELD
o n e e ig h th in ch o n e f o o t th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t
SCALE: NONE
SITE LOCATION
AC SWITCH ROOM
G-001 1 OF 20 COVER SHEET
M-001 2 OF 20 MECHANICAL COVER SHEET
M-101 3 OF 20 BUILDING 5 MECHANICAL FLOOR PLAN
M-102 4 OF 20 BUILDING 6 MECHANICAL FLOOR PLAN
M-103 5 OF 20 BUILDING 7 MECHANICAL FLOOR PLAN
M-104 6 OF 20 BUILDING 8 MECHANICAL FLOOR PLAN
M-105 7 OF 20 BUILDING 36 MECHANICAL FLOOR PLAN
M-106 8 OF 20 BUILDING 37 MECHANICAL BASEMENT FLOOR PLAN
M-107 9 OF 20 BUILDING 37 MECHANICAL FIRST FLOOR PLAN
M-108 10 OF 20 BUILDING 118 MECHANICAL FLOOR PLAN
M-201 11 OF 20 MECHANICAL DETAILS
E-001 12 OF 20 ELECTRICAL COVER SHEET
E-101 13 OF 20 BUILDING 5 ELECTRICAL FLOOR PLAN
E-102 14 OF 20 BUILDING 6 ELECTRICAL FLOOR PLAN
E-103 15 OF 20 BUILDING 7 ELECTRICAL FLOOR PLAN
E-104 16 OF 20 BUILDING 8 ELECTRICAL FLOOR PLAN
E-105 17 OF 20 BUILDING 36 ELECTRICAL FLOOR PLAN
E-106 18 OF 20 BUILDING 37 ELECTRICAL BASEMENT FLOOR PLAN
E-107 19 OF 20 BUILDING 37 ELECTRICAL FIRST FLOOR PLAN
E-108 20 OF 20 BUILDING 118 ELECTRICAL FLOOR PLAN
DRAWING NO. SHEET NO. TITLE
LIST OF DRAWINGS:
GENERAL NOTES:
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
BTU BRITISH THERMAL UNITS
COND CONDENS-, ER, ATE, ATION
CFM CUBIC FEET PER MINUTE
D DRAIN LINE
DD DELEGATED DESIGN
DN DOWN
EA EXHAUST AIR
EDB ENTERING DRY BULB
EF EXHAUST FAN
ETR EXISTING TO REMAIN
F FARENHEIT
FPM FEET PER MINUTE
FT FEET
HP HORSEPOWER
HZ HERTZ
KW KILOWATTS
LB POUNDS
LDB LEAVING DRY BULB
MAX MAXIMUM
MBH THOUSAND BTUS PER HOUR
MCA MINIMUM CURRENT AMPACITY
MIN MINIMUM
MOP MAX ALLOWABLE CIRCUIT BREAKER
PH PHASE
RG REFRIGERANT GAS
RL REFRIGERANT LIQUID
RPM REVOLUTIONS PER MINUTE
SA SUPPLY AIR
S.P STATIC PRESSURE
TYP TYPICAL
V VOLT
1. THE SYSTEM DESIGN, INSTALLATION AND MATERIALS SHALL CONFORM TO THE 2020
INTERNATIONAL MECHANICAL CODE AND AUTHORITIES HAVING JURISDICTION. IN CASE OF
CONFLICTS WITH CODES, DRAWINGS, OR SPECIFICATIONS, THE MOST STRINGENT SHALL
PREVAIL.
2. BEFORE COMMENCEMENT OF WORK, THE CONTRACTOR SHALL VERIFY THE EXACT
LOCATIONS, ELEVATIONS AND CHARACTERISTICS OF ALL EQUIPMENT, UTILITIES AND
PIPING, AND SHALL IMMEDIATELY NOTIFY THE ARCHITECT OF ANY DISCREPANCIES.
3. THE DRAWINGS WERE PREPARED WITH THE BEST STRUCTURAL AND ARCHITECTURAL
INFORMATION AVAILABLE. IT IS UNDERSTOOD THAT EQUIPMENT LOCATIONS AND ROUTING
OF PIPING MAY VARY FROM THAT SHOWN ON THE PLANS AS CONSTRUCTION PROCEEDS. IT
IS THE CONTRACTORS RESPONSIBILITY TO:
a. NOTIFY THE ENGINEER OF CONSTRUCTION RESTRAINTS WHICH MAKE VARIATIONS
FROM THE PLANS NECESSARY.
b. COMPLETE ALL WORK INCLUDING THE VARIATIONS WITHOUT CHARGING EXTRAS TO
THE BID CONTRACT. COMPLETION OF WORK MEANS THE JOB IS WORKING AND AN
COMPLETE TO THE SATISFACTION OF THE COR.
4. THESE DRAWINGS DO NOT INCLUDE ALL NECESSARY SAFETY REQUIREMENTS.
CONTRACTOR TO COMPLY TO THE SAFETY REQUIREMENTS SET FORTH BY THE LOCAL
AUTHORITIES HAVING JURISDICTION.
5. THESE DRAWINGS ARE FOR BIDDING PURPOSES ONLY. THEY ARE ESSENTIALLY
DIAGRAMMATIC TO THE EXTENT THAT MANY OFFSETS, BONDS, UNIONS, SPECIFIC FITTINGS
AND EXACT LOCATIONS ARE NOT INDICATED.
6. PATCH AND /OR REPAIR EXISTING DUCTWORK AND PIPING INSULATION DAMAGED OR
DISTURBED DUE TO CONSTRUCTION WORK.
7. ALL EXTERIOR FLOOR AND WALL PENETRATIONS MUST BE SEALED WATERTIGHT.
8. ALL FLOOR AND WALL PENETRATIONS FIRE THROUGH RATED WALLS MUST BE SEALED
FIRESTOPPED.
9. THE CONTRACTOR SHALL VISIT THE JOB SITE PRIOR TO SUBMITTING BID. THE
CONTRACTORS SHALL FAMILIARIZE THEMSELVES WITH ALL EXISTING CONDITIONS AND
FUTURE WORK TO BE DONE. THEY SHALL INCLUDE ALL SITE INFORMATION AND CONDITIONS
WITHIN THE BASE BID. THEY SHALL BE RESPONSIBLE FOR COMPLETE AND FULLY
FUNCTIONING SYSTEMS.
10. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE EQUIPMENT
MANUFACTURER'S RECOMMENDATIONS AND APPLICABLE CODES, PROVIDE ALL FITTINGS,
VALVES, AND OTHER DEVICES REQUIRED FOR A COMPLETE WORKABLE INSTALLATION.
11. MAINTENANCE LABEL SHALL BE AFFIXED TO ALL EQUIPMENT AND A MAINTENANCE MANUAL
SHALL BE PROVIDED TO OWNER'S REPRESENTATIVE.
12. COORDINATE WITH ELECTRICAL TRADE PRIOR TO ORDERING ELECTRICALLY OPERATED
EQUIPMENT FOR AVAILABLE VOLTAGES AT EQUIPMENT LOCATIONS.
13. THESE PLANS INDICATE APPROXIMATE ROUGH-INS ONLY FOR EQUIPMENT. EXACT ROUGH-IN
DIMENSIONS MUST BE OBTAINED FROM THE EQUIPMENT MANUFACTURER.
14. ALL NEW PENETRATIONS MUST BE CUT WITH WET SAW.
ABBREVATIONS SYMBOLS
POINT OF CONNECTION
THERMOSTAT
POINT OF REMOVAL
T
AIR FLOW DESIGNATION
1355 EAST TITUS AVENUE « ROCHESTER, NY 14622
(585) 448 - 0686 « www.Patriot-DC.com
P TRIOT
DESIGN & CONSULTING
STILL SERVING
ISSUED FOR BID
ASBESTOS AWARENESS NOTES
1. A PRE-RENOVATION SURVEY AND DOCUMENT REVIEW WAS PERFROMED BY WATTS
ARCHITECTURE & ENGINEERING IN NOVEMBER 2020 AND HAS BEEN INCLUDED IN THE
CONTRACT DOCUMENTS. ASBESTOS-CONTAINING MATERIALS (ACM) HAVE BEEN CONFIRMED
TO BE PRESENT IN SOME OF THE AREAS SCHEDULED FOR RENOVATION.
2. ASBESTOS-CONTAINING PIPE INSULATION, MUD FITTING INSULATION, 12” X 12” FLOOR TILES
(VARIOUS COLORS), 9” X 9” FLOOR TILES (VARIOUS COLORS), ASSOCIATED MASTIC AND
WINDOW GLAZING COMPOUND ARE LOCATED IN VARIOUS AREAS THROUGHOUT THE
BUILDINGS.
3. ALL CONTRACTORS ARE RESPONSIBLE FOR MAKING THEMSELVES AND THEIR EMPLOYEES
AWARE OF THE PRESENCE, LOCATION, AND QUANTITY OF EXISTING ASBESTOS-CONTAINING
BUILDING MATERIALS, AND TO WARN THEIR EMPLOYEES OF THE POTENTIAL DANGERS OF
EXPOSURE TO ASBESTOS. ANY DISTURBANCE OF ASBESTOS-CONTAINING MATERIALS SHALL
BE PERFORMED BY A LICENSED ASBESTOS ABATEMENT CONTRACTOR EMPLOYING CERTIFIED
WORKERS.
LEAD AWARENESS NOTES:
1. CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH OSHA 29 CFR 1926.62: LEAD
EXPOSURE IN CONSTRUCTION: INTERIM FINAL RULE FOR ALL ACTIVITIES DURING WHICH AN
EMPLOYEE MAY BE OCCUPATIONALLY EXPOSED TO LEAD. ALL CONTRACTORS SHALL ENSURE
THAT THEIR EMPLOYEES WEAR PROPER PERSONAL PROTECTIVE EQUIPMENT AND/OR UTILIZE
APPROPRIATE WORK METHODS TO PREVENT ELEVATED BLOOD LEAD LEVELS OR EXPOSURE
ABOVE THE PERMISSIBLE EXPOSURE LIMIT.
LO
OP
BVAVSYSTEM COMPONENT:
JOB: -
VARIABLE REFRIGERANT SYSTEM
VA CANANDAIGUA
SYSTEM:
BUILDING:
AI BIAO BO AL
AR
M
TR
EN
DI
NG
SC
HE
DU
LE
REMARKS
HARDWARE
POINTS
SYSTEM SOFTWARE/CONTROL
Zone Temperature Zone Temperature Setpoint
Zone Setpoint Adjust Zone Override Zone Humidity Zone Humidity Setpoint Zone WB Temperature Zone WB Temperature Setpoint Fan Status Fan Speed Operation Mode Compressor Status Pre-Filter Status Unit Alarm Schedule
SOFTWARE
POINTS
SH
OW
O N
GR
AP
HI
CS
NOTES:
1. PROVIDE BACNET MS/TP AND IP COMPATIBLE CONTROLS INTERFACE . TIE INTO EXISTING
LOGICAL CONTROL SOLUTIONS, INC BMS SYSTEM.
2. RUN A CAT 6 CABLE IN 3/4” CONDUIT FROM THE CONTROLS CONNECTION AT THE CONDENSER
TO THE NEAREST BMS CONTROL PANEL WHICH MAY BE LOCATED IN THE SERVER ROOM OR
MECHANICAL ROOM.
BMS CONTROL POINT SCHEDULE
INDOOR COOLING UNIT
UNIT BUILDING ROOM
LIQUID PIPE
SIZE (IN)
GAS PIPE
SIZE (IN)
HOSE
CONNECTION
SIZE (IN)
DRAIN PIPE
SIZE (IN) QUANTITY AIRFLOW H/M/L
(CFM)
COOLING CAPACITY
(BTU/HR) REFRIGERANT
POWER
OUTPUT
(WATTS)
NOMINAL
CURRENT
(AMP)
TYPE INDOOR MODEL MANUFACTURER OR
APPROVED EQUAL WEIGHT (LB) DIMENSIONS (WXHXD) ACCESORIES NOTES
AC-05 5 6 3/8" 5/8" 1" 1-1/4" 1 1007/865/742 36,000 410A 97 0.56 CEILING HUNG
CASSETTE AM036RN4DCH SAMSUNG 13 33 1/16 X 11 3/8 X 33 1/16 WIRELESS THERMOSTAT, MOUNTING RACK AND
HARDWARE, REFRIGERANT Y CONNECTION 1-4, 5, 8
AC-06A/B 6 1B 3/8" 5/8" 1" 1-1/4" 2 865/706/583 24,000 410A 65 0.45 CEILING HUNG
CASSETTE AM024RN4DCH SAMSUNG 13 33 1/16 X 8 1/32 X 33 1/16 WIRELESS THERMOSTAT, MOUNTING RACK AND
HARDWARE, REFRIGERANT Y CONNECTION 1-4, 5, 8
AC-07 7 14B 3/8" 5/8" 1" 1-1/4" 1 1007/865/742 36,000 410A 97 0.56 CEILING HUNG
CASSETTE AM036RN4DCH SAMSUNG 13 33 1/16 X 8 1/32 X 33 1/16 WIRELESS THERMOSTAT, MOUNTING RACK AND
HARDWARE, REFRIGERANT Y CONNECTION 1-4, 5, 8
AC-08A/B 8 1A 3/8" 5/8" 1" 1-1/4" 2 593/530/466 24,000 410A 27 0.40 WALL MOUNTED
UNIT AM024TNVDCH SAMSUNG 28 41 1/2 X 11 3/4 X 9 WIRELESS THERMOSTAT, MOUNTING RACK AND
HARDWARE, REFRIGERANT Y CONNECTION 1-4, 6, 8
AC-B37-A 37 1A 3/8" 5/8" 1" 1-1/4" 1 593/530/466 24,000 410A 27 0.40 WALL MOUNTED UNIT AM024TNVDCH SAMSUNG 28 41 1/2 X 11 3/4 X 9 WIRELESS THERMOSTAT, MOUNTING RACK AND
HARDWARE, REFRIGERANT Y CONNECTION 1-4, 6, 8
AC-B37-B/C 37 20 1/4" 1/2" 1" 1-1/4" 2 547/494/424 12,000 410A 65 0.40 CEILING HUNG CASSETTE AM012RN4DCH SAMSUNG 13 33 1/16 X 8 1/32 X 33 1/16 WIRELESS THERMOSTAT, MOUNTING RACK AND
HARDWARE, REFRIGERANT Y CONNECTION 1-4, 5, 8
AC-37-1 37 137 3/8" 5/8" 1" 1-1/4" 1 830/752/699 36,000 410A 58 0.90 WALL MOUNTED UNIT AC036MNTDCH SAMSUNG 28 50 3/8 X 13 9/16 X 10 WIRELESS THERMOSTAT, MOUNTING RACK AND
HARDWARE, REFRIGERANT Y CONNECTION 1-4, 6, 8
AC-118 118 9 3/8" 5/8" 1" 1-1/4" 1 830/752/699 36,000 410A 58 0.90 WALL MOUNTED
UNIT AC036MNTDCH SAMSUNG 28 50 3/8 X 13 9/16 X 10 WIRELESS THERMOSTAT, MOUNTING RACK AND
HARDWARE, REFRIGERANT Y CONNECTION 1-4, 6, 8
AC-36 36 13 3/8" 5/8" 1" 1-1/4" 1 635/705/775 24,000 410A 40 0.3 WALL MOUNTED
UNIT PUYA24NHA7 MITSUBISHI 46 14 38 X 46 1/16 X 11 5/8 WIRELESS THERMOSTAT, MOUNTING RACK AND
HARDWARE, REFRIGERANT Y CONNECTION 6, 7, 8
OUTDOOR CONDENSER UNIT
UNIT BUILDING
LIQUID PIPE
SIZE (IN)
GAS PIPE
SIZE (IN) QUANTITY AIRFLOW
(CFM)
NORMINAL CAPACITY
(BTU/HR) ø / V / Hz MAX CIRCUIT
BREAKER
MCA (A) TYPE OUTDOOR MODEL MANUFACTURER OR
APPROVED EQUAL WEIGHT (LB) DIMENSION ACCESORIES NOTES
CU-05 5 3/8" 5/8" 1 3,885 36,000 1 / 208-230 / 60 40 23 TWIN BLDC ROTARYX1 AM036TXMDCH SAMSUNG 220 34 5/8 X 25 1/8 X 12 3/16 DISCONNECT SWITCH AND
NEMA 4X ENCLOSURE 1-3, 5
CU-06 6 3/8" 5/8" 1 3,885 48,000 1 / 208-230 / 60 50 29 TWIN BLDC ROTARYX1 AM048TXMDCH SAMSUNG 220 37 X 47 5/8 X 13 DISCONNECT SWITCH AND
NEMA 4X ENCLOSURE 1-3, 5
CU-07 7 3/8" 5/8" 1 3,885 36,000 1 / 208-230 / 60 40 23 TWIN BLDC ROTARYX1 AM036TXMDCH SAMSUNG 220 34 5/8 X 25 1/8 X 12 3/16 DISCONNECT SWITCH AND
NEMA 4X ENCLOSURE 1-3, 5
CU-08 8 3/8" 5/8" 1 3,885 48,000 1 / 208-230 / 60 50 29 TWIN BLDC ROTARYX1 AM048TXMDCH SAMSUNG 220 37 X 47 5/8 X 13 DISCONNECT SWITCH AND
NEMA 4X ENCLOSURE 1-3, 5
CU-B37 37 3/8" 5/8" 1 3,885 48,000 1 / 208-230 / 60 50 29 TWIN BLDC ROTARYX1 AM048TXMDCH SAMSUNG 220 37 X 47 5/8 X 13 DISCONNECT SWITCH AND
NEMA 4X ENCLOSURE 1-3, 5
CU-37-1 37 3/8" 5/8" 1 2,754 36,000 1 / 208-230 / 60 30 24 TWIN BLDC ROTARYX1 AM036MXSCCC SAMSUNG 160 37 X 39 11/16 X 13 DISCONNECT SWITCH AND
NEMA 4X ENCLOSURE 1-3, 5
CU-118 118 3/8" 5/8" 1 2,754 36,000 1 / 208-230 / 60 30 24 TWIN BLDC ROTARYX1 AM036MXSCCC SAMSUNG 160 37 X 39 11/16 X 13 DISCONNECT SWITCH AND
NEMA 4X ENCLOSURE 1-3, 5
CU-36 36 3/8" 5/8" 1 1,940 24,000 1 / 208-230 / 60 25 19 - PUYA24NHA7 MITSUBISHI 151 37 1/8 X 37 13/32 X 13 13/16 DISCONNECT SWITCH AND
NEMA 4X ENCLOSURE 2, 4, 5
NOTES:
1. PROVIDE WIND BAFFLES.
2. PROVIDE WALL MOUNT BRACKETS FOR OUTDOOR UNIT. MOUNT OUTDOOR UNIT 36” OR MORE ABOVE GRADE.
3. PROVIDE OUTDOOR UNIT WITH DISCONNECT SWITCH AND NEMA4X ENCLOSURE TO BE PROVIDED BY EC.
4. EXISTING UNIT AND ACCESSORIES TO BE RELOCATED FROM BUILDING 37 TO BUILDING 36. NEW REFRIGERANT PIPING AND VALVES SHALL BE PROVIDED BY THE CONTRACTOR.
5. CONTRACTOR RESPONSIBLE FOR ALL TESTING AND COMMISSIONING NEEDED.
NOTES:
1. UNITS TO INCLUDE CONDENSATE PUMP AND FASCIA PANELS. CONTRACTOR TO FIELD INSTALL.
2. PROVIDE 10 YEAR MANUFACTURERS WARRANTY ON COMPRESSOR AS WELL AS PARTS & DEFECTS, WITH ONE YEAR LABOR WARRANTY.
3. LOW-AMBIENT COOLING TO -40°F
4. PROVIDE EXTERNAL CONTACT CONTROL INTERFACE FOR CONNECTION TO THE BUILDING MANAGEMENT SYSTEM TO REPORT STATUS / ALARM.
5. PROVIDE CEILING HANGERS FOR INSTALLATION OF INDOOR UNIT.
6. PROVIDE WALL MOUNT BRACKET FOR INSTALLATION OF INDOOR UNIT.
7. EXISTING UNIT AND ACCESSORIES TO BE RELOCATED FROM BUILDING 37 TO BUILDING 36. NEW REFRIGERANT PIPING AND VALVES WILL BE PROVIDED BY THE CONTRACTOR.
8. CONTRACTOR RESPONSIBLE FOR ALL START UP TESTING, AND COMMISSIONING.
SRVC.RM
# 06
EXISTING
CONDENSER
UNIT (ETR)
EXISTING
EXHAUST FAN
SERVER RACK #1
PROVIDE 3 TON CONDENSER
UNIT AND WALL MOUNTED
SUPPORTS FOR CONDENSER.
PROVIDE 36,000 BTU
CEILING HUNG
CASSETTE UNIT
PROVIDE
3/8" RL,
5/8" RG, AND
1-1/4" DRAIN
AC-05
CU-05
CONNECT 1-1/4"
DRAIN INTO
STORM LINE
T
PROVIDE
THERMOSTAT
1355 EAST TITUS AVENUE « ROCHESTER, NY 14622
(585) 448 - 0686 « www.Patriot-DC.com
P TRIOT
DESIGN & CONSULTING
STILL SERVING
ISSUED FOR BID
SCALE: 1/2" = 1'-0"
BUILDING 5 ROOM 6 SWITCH ROOM MECHANICAL PLAN
NORTH
SCALE: NONE
BUILDING 5 KEYPLAN
PLAN KEYNOTES:
1. SEAL EXTERIOR WALL PENETRATIONS WATERTIGHT. PROVIDE ESCUTCHEONS ON INTERIOR AND
ZINC PLATED STEEL WALL PLATE ON EXTERIOR.
2. CONTRACTOR SHALL PROTECT ALL EXISTING SERVERS, ELECTRONICS, AND ACCESSORIES FROM CONTAMINATION. PROVIDE TEMPORARY ICRA BARRIER. USE DURING ALL WORK THAT WILL CREATE DUST, DIRT, FUMES, OR OTHER AIR-BORNE PARTICLES. COORDINATE ALL DUST CONTROL MEASURES WITH COR PRIOR TO COMMENCING WORK. CONTRACTOR IS REQUIRED TO RUN HEPA VAC WHILE ALL WORK TAKES PLACE TO CAPTURE FUMES, DUST, & DEBRIS.REFER TO SPECIFICATION 01 35 26
SECTION 1.12.
3. PROVIDE OUTDOOR PIPE WRAP ON ALL EXTERIOR INSULATION. REFER TO SPECIFICATION 230711, HVAC INSULATION.
4. EXTEND A BMS (CAT 6) CONNECTION FROM THE INDOOR UNIT TO THE EXISTING BMS GATEWAY
LOCATED IN THE SERVER RACK. REFER TO DWG M-001 FOR BMS CONTROL POINT SCHEDULE.
X
GENERAL NOTES:
1. PROVIDE CONTROL WIRING AND RACEWAY TO WALL-MOUNT ROOM THERMOSTAT FROM INDOOR UNIT, OR FROM MASTER INDOOR UNIT FOR MULTI-UNIT SYSTEMS. MOUNT THERMOSTAT NEAR THE BACK OF THE SERVER RACK TO ENSURE THAT THERMOSTAT EFFECTIVELY READS THE HIGH TEMPERATURES
EXPELLED FROM EQUIPMENT ON SERVER RACK.
2. REFER TO ELECTRICAL DRAWINGS FOR POWER WIRING TO OUTDOOR CONDENSING UNITS AND
POWER & CONTROL WIRING FROM OUTDOOR UNIT TO INDOOR EVAPORATOR UNITS.
LINEN
WOMEN
1B
14A
EBX1
SERVER RACK #1
EXISTING
EXHAUST FAN
PROVIDE 3/8" RL,
5/8" RG, AND
1-1/4" DRAIN
PROVIDE 24,000
BTU CEILING HUNG
CASSETTE UNIT
PROVIDE 3/8" RL,
5/8" RG, AND
1-1/4" DRAIN
PROVIDE 4 TON CONDENSER
UNIT AND WALL MOUNTED
SUPPORTS FOR CONDENSER.
AC-06B
CU-06
PROVIDE 3/8" RL,
5/8" RG, AND
1-1/4" DRAIN
PROVIDE REFRIGERANT
Y-CONNECTORS WHERE
PIPING BRANCHES OFF
AC-06A
CO
T
PROVIDE
THERMOSTAT
1355 EAST TITUS AVENUE « ROCHESTER, NY 14622
(585) 448 - 0686 « www.Patriot-DC.com
P TRIOT
DESIGN & CONSULTING
STILL SERVING
ISSUED FOR BID
SCALE: 1/2" = 1'-0"
BUILDING 6 ROOM 1B SWITCH ROOM MECHANICAL PLAN
SCALE: NONE
BUILDING 6 KEYPLAN
NORTH
PLAN KEYNOTES:
1. SEAL EXTERIOR WALL PENETRATIONS WATERTIGHT. PROVIDE ESCUTCHEONS ON INTERIOR AND ZINC
PLATED STEEL WALL PLATE ON EXTERIOR.
2. CONTRACTOR SHALL PROTECT ALL EXISTING SERVERS, ELECTRONICS, AND ACCESSORIES FROM CONTAMINATION. PROVIDE TEMPORARY ICRA BARRIER. USE DURING ALL WORK THAT WILL CREATE DUST, DIRT, FUMES, OR OTHER AIR-BORNE PARTICLES. COORDINATE ALL DUST CONTROL MEASURES WITH COR PRIOR TO COMMENCING WORK. CONTRACTOR IS REQUIRED TO RUN HEPA VAC WHILE ALL WORK TAKES PLACE TO CAPTURE FUMES, DUST, & DEBRIS.REFER TO SPECIFICATION 01 35 26 SECTION 1.12.
3. PROVIDE OUTDOOR PIPE WRAP ON ALL EXTERIOR INSULATION. REFER TO SPECIFICATION 230711, HVAC
INSULATION.
4. EXTEND A BMS (CAT 6) CONNECTION FROM THE INDOOR UNIT TO THE EXISTING BMS GATEWAY LOCATED IN
THE SERVER RACK. REFER TO DWG M-001 FOR BMS CONTROL POINT SCHEDULE.
5. PROVIDE CONTROLS INTERFACE BETWEEN EACH INDOOR UNIT (CAT 6 OR MANUFACTURE'S ALTERNATIVE)
6. PROVIDE CONCRETE SPLASH BLOCK.
X
GENERAL NOTES:
1. PROVIDE CONTROL WIRING AND RACEWAY TO WALL-MOUNT ROOM THERMOSTAT FROM INDOOR UNIT, OR FROM MASTER INDOOR UNIT FOR MULTI-UNIT SYSTEMS. MOUNT THERMOSTAT NEAR THE BACK OF THE SERVER RACK TO ENSURE THAT THERMOSTAT EFFECTIVELY READS THE HIGH TEMPERATURES
EXPELLED FROM EQUIPMENT ON SERVER RACK.
14A 14
14B-EBX2
SOILED LINENEQUIP
IT ROOM
SERVER
RACK #2
SE
R
VE
R
R
AC
K #1
EXISTING
EXHAUST FAN
PROVIDE 36,000
BTU CEILING
HUNG UNIT
PROVIDE 3 TON CONDENSER UNIT
AND WALL MOUNTED SUPPORTS
FOR CONDENSER.
CU-07
AC-07
PROVIDE 3/8" RL,
5/8" RG, AND
1-1/4" DRAIN
T
PROVIDE
THERMOSTAT
1355 EAST TITUS AVENUE « ROCHESTER, NY 14622
(585) 448 - 0686 « www.Patriot-DC.com
P TRIOT
DESIGN & CONSULTING
STILL SERVING
ISSUED FOR BID
SCALE: 1/2" = 1'-0"
BUILDING 7 ROOM 14B SWITCH ROOM MECHANICAL PLAN
SCALE: NONE
BUILDING 7 KEYPLAN NORTH
PLAN KEYNOTES:
1. SEAL EXTERIOR WALL PENETRATIONS WATERTIGHT. PROVIDE ESCUTCHEONS ON INTERIOR AND
ZINC PLATED STEEL WALL PLATE ON EXTERIOR.
2. CONTRACTOR SHALL PROTECT ALL EXISTING SERVERS, ELECTRONICS, AND ACCESSORIES FROM CONTAMINATION. PROVIDE TEMPORARY ICRA BARRIER. USE DURING ALL WORK THAT WILL CREATE DUST, DIRT, FUMES, OR OTHER AIR-BORNE PARTICLES. COORDINATE ALL DUST CONTROL MEASURES WITH COR PRIOR TO COMMENCING WORK. CONTRACTOR IS REQUIRED TO RUN HEPA VAC WHILE ALL WORK TAKES PLACE TO CAPTURE FUMES, DUST, & DEBRIS.REFER TO SPECIFICATION 01 35 26
SECTION 1.12.
3. PROVIDE OUTDOOR PIPE WRAP ON ALL EXTERIOR INSULATION. REFER TO SPECIFICATION 230711, HVAC INSULATION.
4. EXTEND A BMS (CAT 6) CONNECTION FROM THE INDOOR UNIT TO THE EXISTING BMS GATEWAY
LOCATED IN THE SERVER RACK. REFER TO DWG M-001 FOR BMS CONTROL POINT SCHEDULE.
5. PROVIDE CONCRETE SPLASH BLOCK.
X
GENERAL NOTES:
1. PROVIDE CONTROL WIRING AND RACEWAY TO WALL-MOUNT ROOM THERMOSTAT FROM INDOOR UNIT, OR FROM MASTER INDOOR UNIT FOR MULTI-UNIT SYSTEMS. MOUNT THERMOSTAT NEAR THE BACK OF THE SERVER RACK TO ENSURE THAT THERMOSTAT EFFECTIVELY READS THE HIGH TEMPERATURES
EXPELLED FROM EQUIPMENT ON SERVER RACK.
CBX1
SERV. RM
NURSNG
NOOK
2A
EBX1
SERVER
RACK #2
SERVER
RACK #1
EXISTING
EXHAUST FAN
PROVIDE 24,000
BTU WALL
MOUNTED UNIT
PROVIDE 4 TON CONDENSER
UNIT AND WALL MOUNTED
SUPPORTS FOR CONDENSER.
CU-08
AC-08B
AC-08A
PROVIDE REFRIGERANT
Y-CONNECTOR WHERE
PIPING BRANCHES OFF.
PROVIDE Y CONNECTION
AND CLEAN OUT ON
DRAIN LINE.
PROVIDE 3/8" RL,
5/8" RG, AND
1-1/4" DRAIN
PROVIDE 24,000
BTU WALL
MOUNTED UNIT
PROVIDE 3/8" RL,
5/8" RG, AND
1-1/4" DRAIN
PROVIDE 3/8" RL,
5/8" RG, AND
1-1/4" DRAIN
T
PROVIDE
THERMOSTAT
1355 EAST TITUS AVENUE « ROCHESTER, NY 14622
(585) 448 - 0686 « www.Patriot-DC.com
P TRIOT
DESIGN & CONSULTING
STILL SERVING
ISSUED FOR BID
SCALE: 1/2" = 1'-0"
BUILDING 8 ROOM 1A SWITCH ROOM MECHANICAL PLAN
SCALE: NONE
BUILDING 8 KEYPLAN NORTH
PLAN KEYNOTES:
1. SEAL EXTERIOR WALL PENETRATIONS WATERTIGHT. PROVIDE ESCUTCHEONS ON INTERIOR AND ZINC
PLATED STEEL WALL PLATE ON EXTERIOR.
2. CONTRACTOR SHALL PROTECT ALL EXISTING SERVERS, ELECTRONICS, AND ACCESSORIES FROM CONTAMINATION. PROVIDE TEMPORARY ICRA BARRIER. USE DURING ALL WORK THAT WILL CREATE DUST, DIRT, FUMES, OR OTHER AIR-BORNE PARTICLES. COORDINATE ALL DUST CONTROL MEASURES WITH COR PRIOR TO COMMENCING WORK. CONTRACTOR IS REQUIRED TO RUN HEPA VAC WHILE ALL WORK TAKES PLACE TO CAPTURE FUMES, DUST, & DEBRIS.REFER TO SPECIFICATION 01 35 26 SECTION 1.12.
3. PROVIDE OUTDOOR PIPE WRAP ON ALL EXTERIOR INSULATION. REFER TO SPECIFICATION 230711, HVAC
INSULATION.
4. EXTEND A BMS (CAT 6) CONNECTION FROM THE INDOOR UNIT TO THE EXISTING BMS GATEWAY LOCATED IN
THE SERVER RACK. REFER TO DWG M-001 FOR BMS CONTROL POINT SCHEDULE.
5. PROVIDE CONTROLS INTERFACE BETWEEN EACH INDOOR UNIT (CAT 6 OR MANUFACTURE'S ALTERNATIVE)
6. PROVIDE CONCRETE SPLASH BLOCK.
X
GENERAL NOTES:
1. PROVIDE CONTROL WIRING AND RACEWAY TO WALL-MOUNT ROOM THERMOSTAT FROM INDOOR UNIT, OR FROM MASTER INDOOR UNIT FOR MULTI-UNIT SYSTEMS. MOUNT THERMOSTAT NEAR THE BACK OF THE SERVER RACK TO ENSURE THAT THERMOSTAT EFFECTIVELY READS THE HIGH TEMPERATURES
EXPELLED FROM EQUIPMENT ON SERVER RACK.
D O
W N
13EB-2
IS/IT
SVC. RM VRC
SUPPT COORD
SERVER
RACK #1
PROVIDE 3/8" RL,
5/8" RG, AND
1-1/4" DRAIN
INSTALL 24,000 BTU
WALL MOUNTED UNIT.
INSTALL 2 TON CONDENSER UNIT.
PROVIDE WALL MOUNTED
SUPPORTS FOR CONDENSER.
AC-36
CU-36
INSTALL
CONDENSATE
PUMP
T
PROVIDE
THERMOSTAT
1355 EAST TITUS AVENUE « ROCHESTER, NY 14622
(585) 448 - 0686 « www.Patriot-DC.com
P TRIOT
DESIGN & CONSULTING
STILL SERVING
ISSUED FOR BID
SCALE: 1/2" = 1'-0"
BUILDING 36 ROOM 13 SWITCH ROOM MECHANICAL PLAN
SCALE: NONE
BUILDING 36 KEYPLAN NORTH
PLAN KEYNOTES:
1. SEAL EXTERIOR WALL PENETRATIONS WATERTIGHT. PROVIDE ESCUTCHEONS ON INTERIOR AND
ZINC PLATED STEEL WALL PLATE ON EXTERIOR.
2. CONTRACTOR SHALL PROTECT ALL EXISTING SERVERS, ELECTRONICS, AND ACCESSORIES FROM CONTAMINATION. PROVIDE TEMPORARY ICRA BARRIER. USE DURING ALL WORK THAT WILL CREATE DUST, DIRT, FUMES, OR OTHER AIR-BORNE PARTICLES. COORDINATE ALL DUST CONTROL MEASURES WITH COR PRIOR TO COMMENCING WORK. CONTRACTOR IS REQUIRED TO RUN HEPA VAC WHILE ALL WORK TAKES PLACE TO CAPTURE FUMES, DUST, & DEBRIS.REFER TO SPECIFICATION 01 35 26
SECTION 1.12.
3. PROVIDE OUTDOOR PIPE WRAP ON ALL EXTERIOR INSULATION. REFER TO SPECIFICATION 230711, HVAC INSULATION.
4. EXTEND A BMS (CAT 6) CONNECTION FROM THE INDOOR UNIT TO THE EXISTING BMS GATEWAY
LOCATED IN THE SERVER RACK. REFER TO DWG M-001 FOR BMS CONTROL POINT SCHEDULE.
5. PROVIDE CONCRETE SPLASH BLOCK.
X
GENERAL NOTES:
1. PROVIDE CONTROL WIRING AND RACEWAY TO WALL-MOUNT ROOM THERMOSTAT FROM INDOOR UNIT, OR FROM MASTER INDOOR UNIT FOR MULTI-UNIT SYSTEMS. MOUNT THERMOSTAT NEAR THE BACK OF THE SERVER RACK TO ENSURE THAT THERMOSTAT EFFECTIVELY READS THE HIGH TEMPERATURES
EXPELLED FROM EQUIPMENT ON SERVER RACK.
OPERATOR SUITE
POLICE
1A
RACK SERVER #1
24,000 BTU WALL
MOUNTED UNIT
(PKA-A24KA7)
2-TON CONDENSER
(PUY-A24NHA7)
PRIOR TO DISCONNECT,
EVACUATE AND STORE R-410A
REFRIGERANT FOR REUSE.
DISCONNECT AND REMOVE
EXISTING OUTDOOR CONDENSER
UNIT. SAVE FOR REUSE IN
BUILDING 36 SWITCH ROOM.
DISCONNECT
AND REMOVE
REFRIGERANT
PIPING AND
CONDENSATE
DRAIN LINE
DISCONNECT AND REMOVED
EXISTING WALL MOUNTED UNIT.
SAVE FOR REUSE IN BUILDING
36 SWITCH ROOM. PATCH AND
PAINT AFTER UNIT REMOVAL.
PATCH AND
PAINT AFTER
UNIT REMOVAL
OPERATOR SUITE
POLICE
1A
CU-B37
RACK SERVER #1
PROVIDE 4 TON CONDENSER
UNIT AND WALL MOUNTED
SUPPORTS FOR CONDENSER.
AC-B37-A
PROVIDE 3/8" RL,
5/8" RG, AND
1-1/4" DRAIN
PROVIDE 12,000
BTU CEILING
MOUNTED UNIT
PROVIDE 24,000
BTU WALL
MOUNTED UNIT
RACK SERVER #1
PROVIDE
REFRIGERANT
Y-CONNECTOR
WHERE PIPING
BRANCHES OFF
AC-B37-C
PROVIDE 12,000
BTU CEILING UNIT
PROVIDE 3/8" RL,
5/8" RG, AND
1-1/4" DRAIN
PROVIDE 1/4" RL,
1/2" RG, AND
1-1/4" DRAIN
PROVIDE 1/4" RL,
1/2" RG, AND
1-1/4" DRAIN
CO
CO
AC-B37-B
T
PROVIDE
THERMOSTAT
1355 EAST TITUS AVENUE « ROCHESTER, NY 14622
(585) 448 - 0686 « www.Patriot-DC.com
P TRIOT
DESIGN & CONSULTING
STILL SERVING
ISSUED FOR BID
SCALE: 1/2" = 1'-0"
BUILDING 37 ROOM 1A AND 20 SWITCH ROOM MECHANICAL DEMOLITION PLAN
SCALE: 1/2" = 1'-0"
BUILDING 37 ROOM 1A AND 20 SWITCH ROOM MECHANICAL PLAN
SCALE: NONE
BUILDING 37 KEYPLAN NORTH
PLAN KEYNOTES:
1. SEAL EXTERIOR WALL PENETRATIONS WATERTIGHT. PROVIDE ESCUTCHEONS ON INTERIOR AND ZINC
PLATED STEEL WALL PLATE ON EXTERIOR.
2. CONTRACTOR SHALL PROTECT ALL EXISTING SERVERS, ELECTRONICS, AND ACCESSORIES FROM CONTAMINATION. PROVIDE TEMPORARY ICRA BARRIER. USE DURING ALL WORK THAT WILL CREATE DUST, DIRT, FUMES, OR OTHER AIR-BORNE PARTICLES. COORDINATE ALL DUST CONTROL MEASURES WITH COR PRIOR TO COMMENCING WORK. CONTRACTOR IS REQUIRED TO RUN HEPA VAC WHILE ALL WORK TAKES PLACE TO CAPTURE FUMES, DUST, & DEBRIS.REFER TO SPECIFICATION 01 35 26 SECTION 1.12.
3. PROVIDE OUTDOOR PIPE WRAP ON ALL EXTERIOR INSULATION. REFER TO SPECIFICATION 230711, HVAC
INSULATION.
4. EXTEND A BMS (CAT 6) CONNECTION FROM THE INDOOR UNIT TO THE EXISTING BMS GATEWAY LOCATED IN
THE SERVER RACK. REFER TO DWG M-001 FOR BMS CONTROL POINT SCHEDULE.
5. PROVIDE CONTROLS INTERFACE BETWEEN EACH INDOOR UNIT (CAT 6 OR MANUFACTURE'S ALTERNATIVE).
6. PROVIDE CONCRETE SPLASH BLOCK.
X
GENERAL NOTES:
1. PROVIDE CONTROL WIRING AND RACEWAY TO WALL-MOUNT ROOM THERMOSTAT FROM INDOOR UNIT, OR FROM MASTER INDOOR UNIT FOR MULTI-UNIT SYSTEMS. MOUNT THERMOSTAT NEAR THE BACK OF THE SERVER RACK TO ENSURE THAT THERMOSTAT EFFECTIVELY READS THE HIGH TEMPERATURES
EXPELLED FROM EQUIPMENT ON SERVER RACK.
COE
PRGRM ANLST.
COE
RSRCH
EMS
HAC
IS/IT
SVC RM
RACK SERVER #1
36,000 BTU DAIKIN
WALL MOUNTED UNIT
(FTXS36HVJU)
3-TON CONDENSER
(RXS36HVJU)
DISCONNECT AND
REMOVE EXISTING
OUTDOOR CONDENSER
UNIT. REMOVE
EXISTING SUPPORTS.
DISCONNECT AND REMOVE
REFRIGERANT PIPING
DISCONNECT AND REMOVE
REFRIGERANT PIPING AND
CONDENSATE DRAIN LINE
PRIOR TO DISCONNECT,
EVACUATE, AND RECYCLE
REFRIGERANT. DISCONNECT AND
REMOVE EXISTING OUTDOOR
CONDENSER UNIT. PATCH AND
PAINT AFTER UNIT REMOVAL.
PATCH AND
PAINT AFTER
UNIT REMOVAL
COE
PRGRM ANLST.
COE
RSRCH
EMS
HAC
IS/IT
SVC RM
RACK SERVER #1PROVIDE 3/8" RL
AND 5/8" RG
PROVIDE 3 TON CONDENSER
UNIT AND WALL SUPPORTS
FOR CONDENSER. CU-37-1
AC-37-1
PROVIDE 36,000 BTU WALL
MOUNTED UNIT
PROVIDE 1-1/4" DRAIN.
ROUTE ABOVE CEILING.
1-1/4" DRAIN DOWN TO
EXISTING MOP SINK
PROVIDE WALL SUPPORT
FOR PIPING ALONG WALL
T
PROVIDE
THERMOSTAT
1355 EAST TITUS AVENUE « ROCHESTER, NY 14622
(585) 448 - 0686 « www.Patriot-DC.com
P TRIOT
DESIGN & CONSULTING
STILL SERVING
ISSUED FOR BID
SCALE: 1/2" = 1'-0"
BUILDING 37 ROOM 137 SWITCH ROOM MECHANICAL DEMOLITION PLAN
SCALE: 1/2" = 1'-0"
BUILDING 37 ROOM 137 SWITCH ROOM MECHANICAL PLAN
SCALE: NONE
BUILDING 37 KEYPLAN NORTH
PLAN KEYNOTES:
1. SEAL EXTERIOR WALL PENETRATIONS WATERTIGHT. PROVIDE ESCUTCHEONS ON INTERIOR AND
ZINC PLATED STEEL WALL PLATE ON EXTERIOR.
2. CONTRACTOR SHALL PROTECT ALL EXISTING SERVERS, ELECTRONICS, AND ACCESSORIES FROM CONTAMINATION. PROVIDE TEMPORARY ICRA BARRIER. USE DURING ALL WORK THAT WILL CREATE DUST, DIRT, FUMES, OR OTHER AIR-BORNE PARTICLES. COORDINATE ALL DUST CONTROL MEASURES WITH COR PRIOR TO COMMENCING WORK. CONTRACTOR IS REQUIRED TO RUN HEPA VAC WHILE ALL WORK TAKES PLACE TO CAPTURE FUMES, DUST, & DEBRIS.REFER TO SPECIFICATION 01 35 26
SECTION 1.12.
3. PROVIDE OUTDOOR PIPE WRAP ON ALL EXTERIOR INSULATION. REFER TO SPECIFICATION 230711, HVAC INSULATION.
4. EXTEND A BMS (CAT 6) CONNECTION FROM THE INDOOR UNIT TO THE EXISTING BMS GATEWAY
LOCATED IN THE SERVER RACK. REFER TO DWG M-001 FOR BMS CONTROL POINT SCHEDULE.
X
GENERAL NOTES:
1. PROVIDE CONTROL WIRING AND RACEWAY TO WALL-MOUNT ROOM THERMOSTAT FROM INDOOR UNIT, OR FROM MASTER INDOOR UNIT FOR MULTI-UNIT SYSTEMS. MOUNT THERMOSTAT NEAR THE BACK OF THE SERVER RACK TO ENSURE THAT THERMOSTAT EFFECTIVELY READS THE HIGH TEMPERATURES
EXPELLED FROM EQUIPMENT ON SERVER RACK.
TIN SHOP
ELEC. SVC. RM
ENG
SVC. RM
10 ENG
RACK SERVER #1
PRIOR TO DISCONNECT,
EVACUATE, AND RECYCLE
REFRIGERANT. DISCONNECT
AND REMOVE EXISTING
OUTDOOR CONDENSER UNIT.
PATCH AND PAINT AFTER
UNIT REMOVAL
DISCONNECT AND REMOVE
REFRIGERANT PIPING AND
CONDENSATE DRAIN LINE
DISCONNECT AND REMOVE
EXISTING OUTDOOR
CONDENSER UNIT. REMOVE
EXISTING SUPPORTS.
TIN SHOP
ELEC. SVC. RM
ENG
SVC. RM
10 ENG
RACK SERVER #1
PROVIDE 36,000 BTU
WALL MOUNTED UNIT
PROVIDE 3/8" RL, 5/8" RG,
AND 1-1/4" DRAIN
PROVIDE 3 TON CONDENSER
UNIT AND WALL MOUNTED
SUPPORTS FOR CONDENSER.
CU-118
AC-118
T
PROVIDE
THERMOSTAT
1355 EAST TITUS AVENUE « ROCHESTER, NY 14622
(585) 448 - 0686 « www.Patriot-DC.com
P TRIOT
DESIGN & CONSULTING
STILL SERVING
ISSUED FOR BID
SCALE: 1/2" = 1'-0"
BUILDING 118 ROOM 9 SWITCH ROOM MECHANICAL DEMOLITION PLAN
SCALE: 1/2" = 1'-0"
BUILDING 118 ROOM 9 SWITCH ROOM MECHANICAL PLAN
SCALE: NONE
BUILDING 118 KEYPLAN NORTH
PLAN KEYNOTES:
1. SEAL EXTERIOR WALL PENETRATIONS WATERTIGHT. PROVIDE ESCUTCHEONS ON INTERIOR AND ZINC
PLATED STEEL WALL PLATE ON EXTERIOR.
2. CONTRACTOR SHALL PROTECT ALL EXISTING SERVERS, ELECTRONICS, AND ACCESSORIES FROM CONTAMINATION. PROVIDE TEMPORARY ICRA BARRIER. USE DURING ALL WORK THAT WILL CREATE DUST, DIRT, FUMES, OR OTHER AIR-BORNE PARTICLES. COORDINATE ALL DUST CONTROL MEASURES WITH COR PRIOR TO COMMENCING WORK. CONTRACTOR IS REQUIRED TO RUN HEPA VAC WHILE ALL WORK TAKES PLACE TO CAPTURE FUMES, DUST, & DEBRIS.REFER TO SPECIFICATION 01 35 26 SECTION 1.12.
3. PROVIDE OUTDOOR PIPE WRAP ON ALL EXTERIOR INSULATION. REFER TO SPECIFICATION 230711, HVAC
INSULATION.
4. EXTEND A BMS (CAT 6) CONNECTION FROM THE INDOOR UNIT TO THE EXISTING BMS GATEWAY LOCATED IN
THE SERVER RACK. REFER TO DWG M-001 FOR BMS CONTROL POINT SCHEDULE.
5. PROVIDE CONCRETE SPLASH BLOCK.
X
GENERAL NOTES:
1. PROVIDE CONTROL WIRING AND RACEWAY TO WALL-MOUNT ROOM THERMOSTAT FROM INDOOR UNIT, OR FROM MASTER INDOOR UNIT FOR MULTI-UNIT SYSTEMS. MOUNT THERMOSTAT NEAR THE BACK OF THE SERVER RACK TO ENSURE THAT THERMOSTAT EFFECTIVELY READS THE HIGH TEMPERATURES
EXPELLED FROM EQUIPMENT ON SERVER RACK.
1355 EAST TITUS AVENUE « ROCHESTER, NY 14622
(585) 448 - 0686 « www.Patriot-DC.com
P TRIOT
DESIGN & CONSULTING
STILL SERVING
ISSUED FOR BID
2 NTS
WALL MOUNTED SUPPORT FOR EQUIPMENT DETAIL
GENERAL NOTES:
1. WALL BRACKER MATERIALS SHALL BE AISI 1045 STEEL OR EQUIVALENT OR STRONGER. COAT WITH
NON-CORROSIVE COATING AND PAINT.
2. ALL ANCHORS USED TO MOUNT WALL BRACKET TO SURROUNDING STRUCTURE .
3. ALL HARDWARE (SCREWS/FASTENERS) SHALL BE STAINLESS STEEL CORROSION RESISTANT.
4. MOUNT AS RECOMMENDED BY CONDENSER MANUFACTURER.
CONDENSER UNITCONDENSER UNIT
WALL MOUNTED
SUPPORT BRACKET
WALL
MOUNTED
SUPPORT
BRACKET
FRONT VIEW SIDE VIEW
ADJUSTABLE CLEVIS HANGER
TYPE 1 - SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER
TYPE 43 - SEE SPECIFICATIONS
PROVIDE INSULATION
SHIELD & INSERT FOR
ALL PIPING MIN.)
BAND
1/2" DIA. HANGER RODS WITH 36" MAX.
SPACING ON EACH CHANNEL
WELD
SADDLE
INSULATION SHIELD
AT HANGER
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (9
PSF MIN. DENSITY) UNDER
INSULATION SHIELD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
1" M
AX
3 NTS
PIPE HANGER DETAIL
MIN.
3/4"
PENETRATION
FIRECODE COMPOUND
THERMAFIBER SAFING
INSULATION
WALL ASSEMBLY
WRAP STRIP
STEEL COLLAR
4 NTS
PIPE PENETRATION THRU RATED WALL DETAIL
T
1 NTS
AC SYSTEM REFRIGERANT PIPING DETAIL
NOTES:
1. REFRIGERANT LINES SHALL BE SIZED AND
ROUTED AS PER MANUFACTURER'S
RECOMMENDATIONS.
2. MULTIPLE REFRIGERANT CIRCUITS SHALL
BE TYPICAL TO SINGLE CIRCUIT SHOWN.
DIRECT
EXPANSION
COIL
INDOOR UNIT
THERMAL EXPANSION
VALVE
SOLENOID VALVE
ISOLATION
VALVES
CONDENSER
UNIT
RECEIVER
COMPRESSOR
CONDENSER
CONDENSER
FAN
FILTER/DRIER WITH
CHANGING PART
OIL TRAP
SIGHT GLASS AND
LIQUID INDICATOR
ISOLATION VALVES
RLRG
TO
DRAIN
D
RG
Y-CONNECTOR
TO ADDITIONAL UNIT
CEILING CASSETTE
UNIT
NON-CORROSIVE NUT & WASHER
HANGER ROD GALVANIZED OR
PAINTED (SEE SPEC.)
FAN FACE
EXPANSION BOLT
STEEL ROD
DETAIL B
NUT
DETAIL A
STEEL ROD
STEEL ANGLE
WASHER
NOTE:
ALL STEEL SUPPORTS SHALL
BE PAINTED WITH 2 COATS
OF ANTI-RUST PAINT AND 1
COAT OF FINISHED COAT OR
AS SPECIFIED.
SEE DETAIL B
SLAB
5 NTS
CEILING CASSETTE HANGER DETAIL
PRESSURE PLATE
INTERIOR WALL
BOLT
6 NTS
PIPE PENETRATION THRU EXTERIOR WALL DETAIL
NON-CORROSIVE
NUT & WASHER
ESCUTCHEON
EXTERIOR WALL
RUBBER VIBRATION WASHER
1-5/8" 12 GAUGE CHANNEL
OR 2"X2"X1/4" ANGLE
CORE DRILLED HOLE
27"
17"
MIN. 30" SPACE
STEEL CHANNEL
NUT & WASHER
(NON-CORROSIVE)
U-BOLT OR BAND STRAP
PIPE
WALL
NON-CORROSIVE
MASONRY BOLT
7 NTS
PIPE SUPPORT ON EXTERIOR WALL DETAIL
NTS
EXISTING
EXISTING CONTROL
SYSTEM TO REMAINNEW BACNET
PORTABLE
OPERATOR
TERMINAL
EXISTING ENGINEERING
CONTROL CENTER - UPGRADE
ECC WITH NEW BACNET
SOFTWARE
ECC
EXISTING
CONTROLLER
PROTOCOL
NETWORK
B-ASC
EXIST.
GLOBAL
EXIST.
CONTROLLER
B-ASC
EXIST.
B-ASC
EXIST.
B-ASC
EXIST.
B-ASC
EXIST.
B-ASC
EXIST.
NOTES:
1. REUSE EXISTING COMMUNICATION NETWORK UP TO
BACNET CONTROLLER IN EXISTING SERVER RACK IN
EACH BUILDING.
2. INSTALL NEW EQUIPMENT CONTROLLERS (B-AAC, B-ASC)
AS REQUIRED.
B-ASC
EXISTING COMMUNICATION NETWORK
B-ASC
B-ASC
B-ASC
B-ASC
B-ASC
B-AAC B-AAC
BACNET
BUILDING
CONTROLLER
(B-BC)
BACNET
BUILDING
CONTROLLER
(B-BC)
MSTP COMMUNICATION
(TYPICAL)
STAINLESS
STEEL PLATE
FILL ANNULAR GAPS ON
EACH SIDE OF SLEEVE
WITH NONCOMBUSTIBLE
SEALANT.
INTERIOR
INSULATION
INSULATION (WITH
OUTDOOR JACKET)
ELECTRICAL EQUIPMENT AND CONTROL SCHEDULE
EQUIPMENT SUPPLY CONTROL DEVICES
1 FLA
REFERENCE NOTES:
1. INDOOR UNIT RECEIVES POWER FROM THE OUTSIDE CONDENSER
UNIT. PROVIDE ALL POWER & SIGNAL WIRING AND RACEWAYS AS
REQUIRED FOR A COMPLETE WORKING SYSTEM.
2. REMOVE EXISTING 20/1 CB IN PANEL & MOVE TO OTHER PHASE TO
ACCOMMODATE INSTALLATION OF NEW 2 POLE CB.
3. PROVIDE NEMA 4X DISCONNECT SWITCH FOR OUTDOOR UNITS.
4. PROVIDE NEW CIRCUIT BREAKER IN PANEL.
5. CONTROL WIRING SHALL BE 16 AWG X 2 SHIELDED WIRE IN 3/4" C.
HP /
KW /
FLA PHASEVOLTAGE
PANEL/
CIRCUIT
NUMBER
CIRCUIT
BREAKER
OUTDOOR CONDENSER
WIRE & CONDUIT SIZE
REF
NOTES
DISC
SW
BY
E.C.
FUSED
DISC
SW
BY
E.C.
INTEGRAL
DISC
SW
BY
MFGR
MAN
MOTOR
START
BY
E.C.
MAG
START
BY
E.C.
COMB/
MAG
START
BY
E.C.EQUIPMENT NAMEID
INDOOR COOLING UNIT 1 1
TAG
1 FLA
17.3 FLAOUTDOOR CONDENSER UNIT 1 40/2 RPEM-GB
22.1 FLA 1 50/2 RPEM-GA 25,27
AU 2,3,4,5
1 40/2 RPEMG-B 25,27
AU
2 #10, 1 #10EG, 3/4" C.1 50/2 RPEM-GB
AU
SB-2 28,30
AU
AU
AU
AU
AU
ROOM
1B
1B
1A
1A
1A
1B
14B
1A
1A/20
BLDG
LOCATION
AC-05
AC-06A
AC-06B
AC-07
AC-08A
AC-08B
AC-B37-A
AC-B37-B
AC37-1
AC-118
CU-05
CU-06
CU-07
CU-08
CU-B37
CU-37-1
CU-118
INDOOR COOLING UNIT
INDOOR COOLING UNIT
INDOOR COOLING UNIT
INDOOR COOLING UNIT
INDOOR COOLING UNIT
INDOOR COOLING UNIT
INDOOR COOLING UNIT
INDOOR COOLING UNIT
INDOOR COOLING UNIT
OUTDOOR CONDENSER UNIT
OUTDOOR CONDENSER UNIT
OUTDOOR CONDENSER UNIT
OUTDOOR CONDENSER UNIT
OUTDOOR CONDENSER UNIT
OUTDOOR CONDENSER UNIT
14B7
1 FLA
2 #10, 1 #10EG, 3/4" C.
AC-36
CU-36 1 25/2 PP4 19,211336OUTDOOR CONDENSER UNIT
138 1INDOOR COOLING UNIT
2 #12, 1 #12 EG, 3/4" C.
2 #10, 1 #10EG, 3/4" C.
2 #10, 1 #10EG, 3/4" C.40/2 RPEM-1A 28,30
2 #10, 1 #10EG, 3/4" C.50/2
1 FLA
1 FLA
1 FLA
1 FLA
1 FLA
1 FLA
1 FLA
1 FLA
22.1 FLA
22.1 FLA
16.5 FLA
17.3 FLA
10 FLA
40/2 P-TS
2 #12, 1 #12 EG, 3/4" C.
2 #12, 1 #12 EG, 3/4" C.
2 #12, 1 #12 EG, 3/4" C.
2 #12, 1 #12 EG, 3/4" C.
2 #12, 1 #12 EG, 3/4" C.
2 #12, 1 #12 EG, 3/4" C.
2 #12, 1 #12 EG, 3/4" C.
2 #12, 1 #12 EG, 3/4" C.
2 #12, 1 #12 EG, 3/4" C.
2 #12, 1 #12 EG, 3/4" C.
ELECTRIC SYMBOL LIST
240/120V
EXISTING BRANCH CIRCUIT PANELBOARD, 208Y/120V OR
NEW HVAC EQUIPMENT
MOTOR CONNECTION ITEM NUMBER, REFER TO#
ELECTRIC EQUIPMENT & CONTROL SCHEDULE
DRAWING NOTE#
DENOTES NEW WORK OR EQUIPMENT
16.5 FLA
POWER FED FROM OUTDOOR UNIT
POWER FED FROM OUTDOOR UNIT
POWER FED FROM OUTDOOR UNIT
POWER FED FROM OUTDOOR UNIT
POWER FED FROM OUTDOOR UNIT
POWER FED FROM OUTDOOR UNIT
POWER FED FROM OUTDOOR UNIT
POWER FED FROM OUTDOOR UNIT
POWER FED FROM OUTDOOR UNIT
POWER FED FROM OUTDOOR UNIT
POWER FED FROM OUTDOOR UNIT
OUTDOOR
CONDENSER
INDOOR UNIT
POWER
PANEL
208V, 1Ø
INDOOR UNIT RECEIVES POWER
FROM THE OUTDOOR CONDENSERCONTROL WIRING
FROM CONDENSER
T
THERMOSTAT
1 NTS
TYPICAL SINGLE UNIT WIRING DIAGRAM
3,4,5
WIRING AS PER ELECTRICAL
EQUIPMENT AND CONTROL SCHEDULE
2 #10, 1 #10EG, 3/4" C.
2 #10, 1 #10EG, 3/4" C.
2 #10, 1 #10EG, 3/4" C.
3,4,5
3,4,5
3,4,5
3,4,5
3,4,5
3,4,5
1355 EAST TITUS AVENUE « ROCHESTER, NY 14622
(585) 448 - 0686 « www.Patriot-DC.com
P TRIOT
DESIGN & CONSULTING
STILL SERVING
ISSUED FOR BID
DISCONNECT SWITCH
INDOOR UNITS
WIRE &
CONDUIT SIZE
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
18 AWG, 3/4" C.
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
18 AWG, 3/4" C.
18 AWG, 3/4" C.
18 AWG, 3/4" C.
18 AWG, 3/4" C.
18 AWG, 3/4" C.
18 AWG, 3/4" C.
18 AWG, 3/4" C.
18 AWG, 3/4" C.
18 AWG, 3/4" C.
18 AWG, 3/4" C.
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
ASBESTOS AWARENESS NOTES
1. A PRE-RENOVATION SURVEY AND DOCUMENT REVIEW WAS PERFROMED BY WATTS
ARCHITECTURE & ENGINEERING IN NOVEMBER 2020 AND HAS BEEN INCLUDED IN THE
CONTRACT DOCUMENTS. ASBESTOS-CONTAINING MATERIALS (ACM) HAVE BEEN CONFIRMED
TO BE PRESENT IN SOME OF THE AREAS SCHEDULED FOR RENOVATION.
2. ASBESTOS-CONTAINING PIPE INSULATION, MUD FITTING INSULATION, 12” X 12” FLOOR TILES
(VARIOUS COLORS), 9” X 9” FLOOR TILES (VARIOUS COLORS), ASSOCIATED MASTIC AND
WINDOW GLAZING COMPOUND ARE LOCATED IN VARIOUS AREAS THROUGHOUT THE
BUILDINGS.
3. ALL CONTRACTORS ARE RESPONSIBLE FOR MAKING THEMSELVES AND THEIR EMPLOYEES
AWARE OF THE PRESENCE, LOCATION, AND QUANTITY OF EXISTING ASBESTOS-CONTAINING
BUILDING MATERIALS, AND TO WARN THEIR EMPLOYEES OF THE POTENTIAL DANGERS OF
EXPOSURE TO ASBESTOS. ANY DISTURBANCE OF ASBESTOS-CONTAINING MATERIALS SHALL
BE PERFORMED BY A LICENSED ASBESTOS ABATEMENT CONTRACTOR EMPLOYING CERTIFIED
WORKERS.
LEAD AWARENESS NOTES:
1. CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH OSHA 29 CFR 1926.62: LEAD
EXPOSURE IN CONSTRUCTION: INTERIM FINAL RULE FOR ALL ACTIVITIES DURING WHICH AN
EMPLOYEE MAY BE OCCUPATIONALLY EXPOSED TO LEAD. ALL CONTRACTORS SHALL ENSURE
THAT THEIR EMPLOYEES WEAR PROPER PERSONAL PROTECTIVE EQUIPMENT AND/OR UTILIZE
APPROPRIATE WORK METHODS TO PREVENT ELEVATED BLOOD LEAD LEVELS OR EXPOSURE
ABOVE THE PERMISSIBLE EXPOSURE LIMIT.
# 06
UP
SRVC.RM
AC-05
CU-05
EXISTING
EXHAUST FAN
(ETR)
EXISTING
CONDENSER
UNIT (ETR)
ELP-5
RUN POWER TO
OUTDOOR UNIT
PROVIDE
BREAKER
FOR CU-05
PROVIDE POWER CONNECTION
AND CONTROL SIGNAL FROM
OUTDOOR UNIT TO INDOOR
UNIT
PROVIDE IN
NEMA 4X
ENCLOSURE
SCALE: 1/2" = 1'-0"
BUILDING 5 ROOM 6 SWITCH ROOM ELECTRICAL PLAN
1355 EAST TITUS AVENUE « ROCHESTER, NY 14622
(585) 448 - 0686 « www.Patriot-DC.com
P TRIOT
DESIGN & CONSULTING
STILL SERVING
ISSUED FOR BID
SCALE: NONE
BUILDING 5 KEYPLAN NORTH
GENERAL NOTES:
1. REFER TO M-SERIES DRAWINGS FOR LOCATION OF DUST CONTROL MEASURES.
PERFORM ANY CUTTING, DRILLING, AND ANY WORK THAT MAY CREATE DIRT,
DUST, OR FUMES SHALL ONLY BE PERFORMED WITHIN THE TEMPORARY WORK
ENCLOSURES AND WITH CONTINUOUS HEPA VACUUM IN OPERATION FOR THE
DURATION OF WORK.
CBX2
14A
EBX1
1B
EXISTING
EXHAUST
FAN
CU-06
RPEM-GA
AC-06A AC-06B
RUN POWER TO
OUTDOOR UNIT
PROVIDE POWER
CONNECTION AND
CONTROL SIGNAL FROM
OUTDOOR UNIT TO
INDOOR UNITS
PROVIDE
BREAKER
FOR CU-06
PROVIDE IN
NEMA 4X
ENCLOSURE
BUILDING 6 ROOM 1B SWITCH ROOM ELECTRICAL PLAN
1355 EAST TITUS AVENUE « ROCHESTER, NY 14622
(585) 448 - 0686 « www.Patriot-DC.com
P TRIOT
DESIGN & CONSULTING
STILL SERVING
ISSUED FOR BID
BUILDING 6 KEYPLAN NORTH
SCALE: 1/2" = 1'-0" SCALE: NONE
GENERAL NOTES:
1. REFER TO M-SERIES DRAWINGS FOR LOCATION OF DUST CONTROL MEASURES.
PERFORM ANY CUTTING, DRILLING, AND ANY WORK THAT MAY CREATE DIRT,
DUST, OR FUMES SHALL ONLY BE PERFORMED WITHIN THE TEMPORARY WORK
14A 14
14B-EBX2
SBX2
15A
CBX2
SOILED LINENEQUIP
IT ROOM
SERVER
RACK #2
SE
R
VE
R
R
AC
K #1
AC-07
RPEMG-B
CU-07
RUN POWER TO
OUTDOOR UNIT
PROVIDE
BREAKER
FOR CU-07
PROVIDE POWER
CONNECTION AND
CONTROL SIGNAL FROM
OUTDOOR UNIT TO
INDOOR UNIT
PROVIDE IN
NEMA 4X
ENCLOSURE
SCALE: 1/2" = 1'-0"
BUILDING 7 ROOM 14B SWITCH ROOM ELECTRICAL PLAN
1355 EAST TITUS AVENUE « ROCHESTER, NY 14622
(585) 448 - 0686 « www.Patriot-DC.com
P TRIOT
DESIGN & CONSULTING
STILL SERVING
ISSUED FOR BID
SCALE: NONE
BUILDING 7 KEYPLAN NORTH
GENERAL NOTES:
1. REFER TO M-SERIES DRAWINGS FOR LOCATION OF DUST CONTROL MEASURES.
PERFORM ANY CUTTING, DRILLING, AND ANY WORK THAT MAY CREATE DIRT,
DUST, OR FUMES SHALL ONLY BE PERFORMED WITHIN THE TEMPORARY WORK
CBX1
10A
11 SBX2
13I
13J
CBX2
14B
14A
SERV. RM
CONFERENCE
SERV. RM
AUDIOLOGY
CHAPLAIN STOR
SPEECH/PATH
GROUP PROGRM. RM
BATH
CHAPLAIN SVC
COPY
AUDIOLOGIST
LAB
NURSNG
NOOK
2A
EBX1
SERVER
RACK #2SERVER
RACK #1
EXISTING
EXHAUST
FAN
AC-08A
AC-08B
CU-08
P1-A
P1
RPEM-GB
RUN POWER TO
OUTDOOR UNIT
PROVIDE
BREAKER
FOR CU-08
PROVIDE POWER
CONNECTION AND
CONTROL SIGNAL
FROM OUTDOOR UNIT
TO INDOOR UNITS PROVIDE IN
NEMA 4X
ENCLOSURE
SCALE: 1/4" = 1'-0"
BUILDING 8 ROOM 1A SWITCH ROOM ELECTRICAL PLAN
1355 EAST TITUS AVENUE « ROCHESTER, NY 14622
(585) 448 - 0686 « www.Patriot-DC.com
P TRIOT
DESIGN & CONSULTING
STILL SERVING
ISSUED FOR BID
SCALE: NONE
BUILDING 8 KEYPLAN NORTH
GENERAL NOTES:
1. REFER TO M-SERIES DRAWINGS FOR LOCATION OF DUST CONTROL MEASURES.
PERFORM ANY CUTTING, DRILLING, AND ANY WORK THAT MAY CREATE DIRT,
DUST, OR FUMES SHALL ONLY BE PERFORMED WITHIN THE TEMPORARY WORK
13EB-2
SB-1
SERVER
RACK #1
AC-36
CU-36
PP-4
PROVIDE
BREAKER
FOR CU-36
RUN POWER TO OUTDOOR UNIT
PROVIDE POWER CONNECTION
AND CONTROL SIGNAL FROM
OUTDOOR UNIT TO INDOOR UNIT
PROVIDE IN
NEMA 4X
ENCLOSURE
SCALE: 1/2" = 1'-0"
BUILDING 36 ROOM 13 SWITCH ROOM MECHANICAL PLAN
1355 EAST TITUS AVENUE « ROCHESTER, NY 14622
(585) 448 - 0686 « www.Patriot-DC.com
P TRIOT
DESIGN & CONSULTING
STILL SERVING
ISSUED FOR BID
SCALE: NONE
BUILDING 36 KEYPLAN NORTH
GENERAL NOTES:
1. REFER TO M-SERIES DRAWINGS FOR LOCATION OF DUST CONTROL MEASURES.
PERFORM ANY CUTTING, DRILLING, AND ANY WORK THAT MAY CREATE DIRT,
DUST, OR FUMES SHALL ONLY BE PERFORMED WITHIN THE TEMPORARY WORK
6A
6B
RACK
SERVER #1
AC-B37-A
CU-B37
SB-2
PROVIDE
BREAKER
FOR CU-B37
RUN POWER TO
OUTDOOR UNIT
PROVIDE IN
NEMA 4X
ENCLOSURE
1A
AC-B37-B
AC-B37-C
6A
6B
RACK
SERVER #1
SB-2
EXISTING CONDENSER UNIT
BEING REMOVED, REFER TO
MECHANICAL DRAWINGS.
DISCONNECT AND REMOVE
POWER BACK TO SOURCE PANEL.
1A
EXISTING AC UNIT TO BE
REMOVED, REFER TO
MECHANICAL DRAWINGS.
DISCONNECT AND REMOVE
POWER AND CONTROL SIGNAL
BACK TO OUTDOOR UNIT.
SCALE: 1/4 = 1'-0"
BUILDING 37 ROOM 1A AND 20 SWITCH ROOM ELECTRICAL PLAN
1355 EAST TITUS AVENUE « ROCHESTER, NY 14622
(585) 448 - 0686 « www.Patriot-DC.com
P TRIOT
DESIGN & CONSULTING
STILL SERVING
ISSUED FOR BID
SCALE: 1/4 = 1'-0"
BUILDING 37 ROOM 1A AND 20 SWITCH ROOM ELECTRICAL DEMOLITION PLAN
SCALE: NONE
BUILDING 37 KEYPLAN NORTH
GENERAL NOTES:
1. REFER TO M-SERIES DRAWINGS FOR LOCATION OF DUST CONTROL MEASURES.
PERFORM ANY CUTTING, DRILLING, AND ANY WORK THAT MAY CREATE DIRT,
DUST, OR FUMES SHALL ONLY BE PERFORMED WITHIN THE TEMPORARY WORK
RACK
SERVER #1
CU-37-1
AC-37-1
PROVIDE
BREAKER
FOR CU-37-1
RUN POWER TO
OUTDOOR UNIT
RPEM-1A
PROVIDE CONNECTION
AND CONTROL SIGNAL
FROM OUTDOOR UNIT
TO INDOOR UNIT
PROVIDE IN
NEMA 4X
ENCLOSURE
134 135
RACK
SERVER #1
EXISTING
CONDENSER
UNIT
RPEM-1A
DISCONNECT AND
REMOVE POWER
TO OUTDOOR UNIT
DISCONNECT POWER
TO POWER PANEL.
DISCONNECT AND
REMOVE POWER BACK
TO SOURCE PANEL.
134 135
EXISTING AC UNIT TO BE
REMOVED, REFER TO
MECHANICAL DRAWINGS.
DISCONNECT AND REMOVE
POWER AND CONTROL SIGNAL
BACK TO OUTDOOR UNIT.
SCALE: 1/4 = 1'-0"
BUILDING 37 ROOM 137 SWITCH ROOM ELECTRICAL PLAN
1355 EAST TITUS AVENUE « ROCHESTER, NY 14622
(585) 448 - 0686 « www.Patriot-DC.com
P TRIOT
DESIGN & CONSULTING
STILL SERVING
ISSUED FOR BID
SCALE: NONE
BUILDING 37 KEYPLAN NORTH
SCALE: 1/4 = 1'-0"
BUILDING 37 ROOM 137 SWITCH ROOM ELECTRICAL DEMOLITION PLAN
GENERAL NOTES:
1. REFER TO M-SERIES DRAWINGS FOR LOCATION OF DUST CONTROL MEASURES.
PERFORM ANY CUTTING, DRILLING, AND ANY WORK THAT MAY CREATE DIRT,
DUST, OR FUMES SHALL ONLY BE PERFORMED WITHIN THE TEMPORARY WORK
TIN SHOP
ELEC. SVC. RM
ENG
ENG
RACK SERVER #1
L/PP-4
CU-118
AC-118
P-TS
PROVIDE POWER
CONNECTION AND
CONTROL SIGNAL FROM
OUTDOOR UNIT TO
INDOOR UNIT
PROVIDE IN
NEMA 4X
ENCLOSURE
ELEC. SVC. RM
ENG
SVC. RM
RACK SERVER #1
L/PP-4
DISCONNECT AND REMOVE POWER BACK TO
SOURCE PANEL. DISCONNECT POWER AND
CONTROL SIGNAL BACK TO INDOOR UNIT.
EXISTING AC UNITS TO BE
REMOVED, REFER TO MECHANICAL
DRAWINGS. DISCONNECT AND
REMOVE POWER AND CONTROL
SIGNAL BACK TO OUTDOOR UNIT.
SCALE: 1/2" = 1'-0"
BUILDING 118 ROOM 9 SWITCH ROOM ELECTRICAL PLAN
1355 EAST TITUS AVENUE « ROCHESTER, NY 14622
(585) 448 - 0686 « www.Patriot-DC.com
P TRIOT
DESIGN & CONSULTING
STILL SERVING
ISSUED FOR BID
SCALE: NONE
BUILDING 118 KEYPLAN NORTH
SCALE: 1/2" = 1'-0"
BUILDING 118 ROOM 9 SWITCH ROOM ELECTRICAL DEMOLTION PLAN
GENERAL NOTES:
1. REFER TO M-SERIES DRAWINGS FOR LOCATION OF DUST CONTROL MEASURES.
PERFORM ANY CUTTING, DRILLING, AND ANY WORK THAT MAY CREATE DIRT,
DUST, OR FUMES SHALL ONLY BE PERFORMED WITHIN THE TEMPORARY WORK
| Sheets and Views |
| GI-001-GI-001 |
| M-001-M-001 |
| B-05 M-M-101 |
| B-06 M-M-102 |
| B-07 M-M-103 |
| B-08 M-M-104 |
| B-36 M-M-105 |
| B-37 M-M-106 |
| B-37 M-M-107 |
| B-118 M-M-108 |
| M-001-M-201 |
| E-001-E-001 |
| B-05 E-E-101 |
| B-06 E-E-102 |
| B-07 E-E-103 |
| B-08 E-E-104 |
| B-36 E-E-105 |
| B-37 E-E-106 |
| B-37 E-E-107 |
| B-118 E-E-108 |
File details come from the government source that posted it. Updated .