UPS_Specifications_Rvsd.pdf

PDF 92 KB Posted

Attached to
Uninterruptable Power Supplies (UPS) Federal contract opportunity
Solicitation number
RFQ-OH-16-00012
Issued by
Environmental Protection Agency Cincinatti Procurement Operations Division

About this file

Amendment 04 - Revised Specifications

View the file

Other files for this federal contract opportunity

Other files attached to Uninterruptable Power Supplies (UPS), newest first.
File Type Posted
Sol_RFQ-OH-16-00012_Amd_000005.pdf PDF
UPS_Specifications_-_updated.pdf PDF
Page_3.pdf PDF
Sol_RFQ-OH-16-00012_Amd_000004.pdf PDF
Sol_RFQ-OH-16-00012_Amd_000003.pdf PDF
Sol_RFQ-OH-16-00012_Amd_000002.pdf PDF
Sol_RFQ-OH-16-00012_Amd_000001.pdf PDF
UPS_Specifications.pdf PDF
Sol_RFQ-OH-16-00012.pdf PDF
Solicitation_Cover_Letter.doc DOC document
Synopsis.doc DOC document
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RFQ-OH-16-00012

U.S. EPA-Cincinnati Uninterruptable Power Supply Requirements

Item # Description Qty

1 8 KVA Rack Mount UPS 3 See Page 2 “8 KVA Rack Mont UPS Specifications” for details

2 8 KVA Rack Mount UPS w/ Battery Pack 1 See Page 3 “8 KVA Rack Mount UPS w/ Battery Pack Specifications” for details

3 8 KVA Tower UPS 10 See Page 4 “8 KVA Tower UPS Specifications”

4 6 KVA Rack Mount UPS 3 See Page 5 “6 KVA Rack Mount UPS Specifications”

5 3 KVA Tower UPS 2 See Page 6 “3 KVA Tower UPS Specifications”

6 2 KVA Tower UPS 3 See Page 7 “2 KVA Tower UPS Specifications”

7 2 KVA Rack Mount UPS w/ Battery Pack 1 See Page 8 “2 KVA Rack Mount UPS w/ Battery Pack Specifications”

8 KVA Rack Mount UPS Specifications

Power requirement: 8 KVA

Minimum of 4 L6-20 Receptacles.

Physical Characteristics:

Rack mountable, single chassis (no external power distribution unit (PDU) or step-down transformer required to meet output requirements)

Input:

Nominal Input Voltage: 208V Input Frequency: 40-70 Hz (auto sensing) Input Connections: Hard Wire 3 Wire (2PH + G) Input voltage Range: 160-275V

Other Input Voltage: 240

Output:

Power Required: 7200 watts (minimum) Nominal Output Voltage: 208V Output Connections: (2) NEMA L6-20R (minimum) Output Frequency: 50/60 Hz +/- 3 Hz Bypass: Internal Bypass (Automatic and Manual) Runtime Requirement: 5 Minutes with 5000 watt load (minimum)

Communications and Management:

Interface Ports: RJ-45 Ethernet, RJ-45 Serial, USB Alarms: Audible Alarm Control Panel: Multifunction LCD or LED status and control console Network Manageable: Provides remote power management of the UPS over the network.

Surge Protection and Filtering:

Surge Protection: 480 Joules (Minimum)

8 KVA Rack Mount UPS w/ Battery Pack Specifications

Minimum of 4 L6-20 Receptacles.

Physical Characteristics:

Rack mountable, single chassis (no external power distribution unit (PDU) or step-down transformer required to meet output requirements)

Input:

Nominal Input Voltage: 208V Input Frequency: 40-70 Hz (auto sensing) Input Connections: Hard Wire 3 Wire (2PH + G) Input voltage Range: 160-275V

Other Input Voltage: 240

Output:

Power Required: 7200 watts (minimum) Nominal Output Voltage: 208V Output Connections: (2) NEMA L6-20R (minimum) Output Frequency: 50/60 Hz +/- 3 Hz Bypass: Internal Bypass (Automatic and Manual)

Communications and Management:

Interface Ports: RJ-45 Ethernet, RJ-45 Serial, USB Alarms: Audible Alarm Control Panel: Multifunction LCD or LED status and control console Network Manageable: Provides remote power management of the UPS over the network.

Surge Protection and Filtering:

Surge Protection: 480 Joules (Minimum)

Battery Pack:

Runtime Requirement: Battery pack/UPS combination must provide at least 30 minutes runtime with a 5000 watt load.

8 KVA Tower UPS Specifications

Minimum of 4 L6-20 Receptacles.

Physical Characteristics:

Tower, single chassis (no external power distribution unit (PDU) or step-down transformer required to meet output requirements)

Input:

Nominal Input Voltage: 208V Input Frequency: 40-70 Hz (auto sensing) Input Connections: Hard Wire 3 Wire (2PH + G) Input voltage Range: 160-275V

Other Input Voltage: 240

Output:

Power Required: 7200 watts (minimum) Nominal Output Voltage: 208V Output Connections: (2) NEMA L6-20R (minimum) Output Frequency: 50/60 Hz +/- 3 Hz Bypass: Internal Bypass (Automatic and Manual) Runtime Requirement: 5 Minutes with 5000 watt load (minimum)

Communications and Management:

Interface Ports: RJ-45 Ethernet, RJ-45 Serial, USB Alarms: Audible Alarm Control Panel: Multifunction LCD or LED status and control console Network Manageable: Provides remote power management of the UPS over the network.

6 KVA Rack Mount UPS Specifications

Power requirement: 6 KVA

Physical Characteristics:

Rack mountable, external power distribution unit (PDU) or step-down transformer may be used to meet output requirements.

Input:

Nominal Input Voltage: 208V Input Frequency: 40-70 Hz (auto sensing) Input Connections: Hard Wire 3 Wire (2PH + G) Input voltage Range: 160-275V

Other Input Voltage: 240

Output:

Power Required: 4200 watts (minimum) Nominal Output Voltage: 120V, 208V Output Connections: (3) NEMA L5-20R (minimum) Output Frequency: 50/60 Hz +/- 3 Hz Bypass: Internal Bypass (Automatic and Manual) Runtime Requirement: 5 Minutes with 4000 watt load (minimum)

Communications and Management:

Interface Ports: RJ-45 Ethernet, RJ-45 Serial, USB Alarms: Audible Alarm Control Panel: Multifunction LCD or LED status and control console Network Manageable: Provides remote power management of the UPS over the network.

3 KVA Tower UPS Specifications

Power requirement: 3 KVA

Physical Characteristics:

Tower, single chassis (no external power distribution unit (PDU) or step-down transformer required to meet output requirement)

Input:

Nominal Input Voltage: 120V Input Frequency: 50-60 Hz +/- 5 Hz (auto sensing) Input Connections: NEMA L5-30P Input voltage Range: 90-150V

Output:

Power Required: 2100 watts (minimum) Nominal Output Voltage: 120V Output Connections: (4) NEMA 5-15R (minimum)

(2) NEMA 5-20 (minimum) Output Frequency: 50/60 Hz +/- 3 Hz Bypass: Internal Bypass (Automatic and Manual) Runtime Requirement: 5 Minutes with 2000 watt load (minimum)

Communications and Management:

Interface Ports: RJ-45 Serial or DB-9 RS-232, USB Alarms: Audible Alarm Control Panel: Multifunction LCD or LED status and control console

2 KVA Tower UPS Specifications

Power requirement: 2 KVA (minimum)

Physical Characteristics:

Tower, single chassis (no external power distribution unit (PDU) or step-down transformer required to meet output requirement)

Input:

Nominal Input Voltage: 120V Input Frequency: 50-60 Hz +/- 5 Hz (auto sensing) Input Connections: NEMA 5-20P Input voltage Range: 90-150V

Output:

Power Required: 1600 watts (minimum) Nominal Output Voltage: 120V Output Connections: (4) NEMA 5-15R (minimum) Output Frequency: 50/60 Hz +/- 3 Hz Bypass: Built-in Bypass (Automatic and/or Manual) Runtime Requirement: 5 Minutes with 1100 watt load (minimum)

Communications and Management:

Interface Ports: RJ-45 Serial or DB-9 RS-232, USB Alarms: Audible Alarm Control Panel: LCD or LED status

2 KVA Rack Mount UPS w/ Battery Pack Specifications

Power requirement: 2 KVA (minimum)

Physical Characteristics:

Rack mount, single chassis (no external power distribution unit (PDU) or step-down transformer required to meet output requirement)

Input:

Nominal Input Voltage: 120V Input Frequency: 50-60 Hz +/- 5 Hz (auto sensing) Input Connections: NEMA 5-20P Input voltage Range: 90-150V

Output:

Power Required: 1600 watts (minimum) Nominal Output Voltage: 120V Output Connections: (4) NEMA 5-15R (minimum) Output Frequency: 50/60 Hz +/- 3 Hz Bypass: Built-in Bypass (Automatic and/or Manual) Runtime Requirement: 5 Minutes with 1100 watt load (minimum)

Communications and Management:

Interface Ports: RJ-45 Serial or DB-9 RS-232, USB Alarms: Audible Alarm Control Panel: LCD or LED status

Surge Protection and Filtering:

Surge Protection: 480 Joules (Minimum)

Battery Pack:

Runtime Requirement: Battery pack/UPS combination must provide at least 30 minutes runtime with an 1100 watt load.