UPS_Specifications.pdf

PDF 91 KB Posted

Attached to
Uninterruptable Power Supplies (UPS) Federal contract opportunity
Solicitation number
RFQ-OH-16-00012
Issued by
Environmental Protection Agency Cincinatti Procurement Operations Division

About this file

UPS Specifications

View the file

Other files for this federal contract opportunity

Other files attached to Uninterruptable Power Supplies (UPS), newest first.
File Type Posted
Page_3.pdf PDF
UPS_Specifications_-_updated.pdf PDF
Sol_RFQ-OH-16-00012_Amd_000005.pdf PDF
UPS_Specifications_Rvsd.pdf PDF
Sol_RFQ-OH-16-00012_Amd_000004.pdf PDF
Sol_RFQ-OH-16-00012_Amd_000003.pdf PDF
Sol_RFQ-OH-16-00012_Amd_000002.pdf PDF
Sol_RFQ-OH-16-00012_Amd_000001.pdf PDF
Sol_RFQ-OH-16-00012.pdf PDF
Solicitation_Cover_Letter.doc DOC document
Synopsis.doc DOC document
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

U.S. EPA-Cincinnati Uninterruptable Power Supply Requirements

Item # Description Qty

1 8 KVA Rack Mount UPS 3 See Page 2 “8 KVA Rack Mont UPS Specifications” for details

2 8 KVA Rack Mount UPS w/ Battery Pack 1 See Page 3 “8 KVA Rack Mount UPS w/ Battery Pack Specifications” for details

3 8 KVA Tower UPS 10 See Page 4 “8 KVA Tower UPS Specifications”

4 6 KVA Rack Mount UPS 3 See Page 5 “6 KVA Rack Mount UPS Specifications”

5 3 KVA Tower UPS 2 See Page 6 “3 KVA Tower UPS Specifications”

6 2 KVA Tower UPS 3 See Page 7 “2 KVA Tower UPS Specifications”

7 2 KVA Rack Mount UPS w/ Battery Pack 1 See Page 8 “2 KVA Rack Mount UPS w/ Battery Pack Specifications”

8 KVA Rack Mount UPS Specifications

Power requirement: 8 KVA

Physical Characteristics:

Rack mountable, single chassis (no external power distribution unit (PDU) or step-down transformer required to meet output requirements)

Input:

Nominal Input Voltage: 208V Input Frequency: 40-70 Hz (auto sensing) Input Connections: Hard Wire 3 Wire (2PH + G) Input voltage Range: 160-275V

Other Input Voltage: 240

Output:

Power Required: 7200 watts (minimum) Nominal Output Voltage: 208V Output Connections: (2) NEMA L6-20R (minimum) Output Frequency: 50/60 Hz +/- 3 Hz Bypass: Internal Bypass (Automatic and Manual) Runtime Requirement: 5 Minutes with 5000 watt load (minimum)

Communications and Management:

Interface Ports: RJ-45 Ethernet, RJ-45 Serial, USB Alarms: Audible Alarm Control Panel: Multifunction LCD or LED status and control console Network Manageable: Provides remote power management of the UPS over the network.

Surge Protection and Filtering:

Surge Protection: 480 Joules (Minimum)

8 KVA Rack Mount UPS w/ Battery Pack Specifications

Physical Characteristics:

Rack mountable, single chassis (no external power distribution unit (PDU) or step-down transformer required to meet output requirements)

Input:

Nominal Input Voltage: 208V Input Frequency: 40-70 Hz (auto sensing) Input Connections: Hard Wire 3 Wire (2PH + G) Input voltage Range: 160-275V

Other Input Voltage: 240

Output:

Power Required: 7200 watts (minimum) Nominal Output Voltage: 208V Output Connections: (2) NEMA L6-20R (minimum) Output Frequency: 50/60 Hz +/- 3 Hz Bypass: Internal Bypass (Automatic and Manual)

Communications and Management:

Interface Ports: RJ-45 Ethernet, RJ-45 Serial, USB Alarms: Audible Alarm Control Panel: Multifunction LCD or LED status and control console Network Manageable: Provides remote power management of the UPS over the network.

Surge Protection and Filtering:

Surge Protection: 480 Joules (Minimum)

Battery Pack:

Runtime Requirement: Battery pack/UPS combination must provide at least 30 minutes runtime with a 5000 watt load.

8 KVA Tower UPS Specifications

Physical Characteristics:

Tower, single chassis (no external power distribution unit (PDU) or step-down transformer required to meet output requirements)

Input:

Nominal Input Voltage: 208V Input Frequency: 40-70 Hz (auto sensing) Input Connections: Hard Wire 3 Wire (2PH + G) Input voltage Range: 160-275V

Other Input Voltage: 240

Output:

Power Required: 7200 watts (minimum) Nominal Output Voltage: 208V Output Connections: (2) NEMA L6-20R (minimum) Output Frequency: 50/60 Hz +/- 3 Hz Bypass: Internal Bypass (Automatic and Manual) Runtime Requirement: 5 Minutes with 5000 watt load (minimum)

Communications and Management:

Interface Ports: RJ-45 Ethernet, RJ-45 Serial, USB Alarms: Audible Alarm Control Panel: Multifunction LCD or LED status and control console Network Manageable: Provides remote power management of the UPS over the network.

6 KVA Rack Mount UPS Specifications

Power requirement: 6 KVA

Physical Characteristics:

Rack mountable, external power distribution unit (PDU) or step-down transformer may be used to meet output requirements.

Input:

Nominal Input Voltage: 208V Input Frequency: 40-70 Hz (auto sensing) Input Connections: Hard Wire 3 Wire (2PH + G) Input voltage Range: 160-275V

Other Input Voltage: 240

Output:

Power Required: 4200 watts (minimum) Nominal Output Voltage: 120V, 208V Output Connections: (3) NEMA L5-20R (minimum) Output Frequency: 50/60 Hz +/- 3 Hz Bypass: Internal Bypass (Automatic and Manual) Runtime Requirement: 5 Minutes with 4000 watt load (minimum)

Communications and Management:

Interface Ports: RJ-45 Ethernet, RJ-45 Serial, USB Alarms: Audible Alarm Control Panel: Multifunction LCD or LED status and control console Network Manageable: Provides remote power management of the UPS over the network.

3 KVA Tower UPS Specifications

Power requirement: 3 KVA

Physical Characteristics:

Tower, single chassis (no external power distribution unit (PDU) or step-down transformer required to meet output requirement)

Input:

Nominal Input Voltage: 120V Input Frequency: 50-60 Hz +/- 5 Hz (auto sensing) Input Connections: NEMA L5-30P Input voltage Range: 90-150V

Output:

Power Required: 2100 watts (minimum) Nominal Output Voltage: 120V Output Connections: (4) NEMA 5-15R (minimum)

(2) NEMA 5-20 (minimum) Output Frequency: 50/60 Hz +/- 3 Hz Bypass: Internal Bypass (Automatic and Manual) Runtime Requirement: 5 Minutes with 2000 watt load (minimum)

Communications and Management:

Interface Ports: RJ-45 Serial or DB-9 RS-232, USB Alarms: Audible Alarm Control Panel: Multifunction LCD or LED status and control console

2 KVA Tower UPS Specifications

Power requirement: 2 KVA (minimum)

Physical Characteristics:

Tower, single chassis (no external power distribution unit (PDU) or step-down transformer required to meet output requirement)

Input:

Nominal Input Voltage: 120V Input Frequency: 50-60 Hz +/- 5 Hz (auto sensing) Input Connections: NEMA 5-20P Input voltage Range: 90-150V

Output:

Power Required: 1600 watts (minimum) Nominal Output Voltage: 120V Output Connections: (4) NEMA 5-15R (minimum) Output Frequency: 50/60 Hz +/- 3 Hz Bypass: Built-in Bypass (Automatic and/or Manual) Runtime Requirement: 5 Minutes with 1100 watt load (minimum)

Communications and Management:

Interface Ports: RJ-45 Serial or DB-9 RS-232, USB Alarms: Audible Alarm Control Panel: LCD or LED status

2 KVA Rack Mount UPS w/ Battery Pack Specifications

Power requirement: 2 KVA (minimum)

Physical Characteristics:

Rack mount, single chassis (no external power distribution unit (PDU) or step-down transformer required to meet output requirement)

Input:

Nominal Input Voltage: 120V Input Frequency: 50-60 Hz +/- 5 Hz (auto sensing) Input Connections: NEMA 5-20P Input voltage Range: 90-150V

Output:

Power Required: 1600 watts (minimum) Nominal Output Voltage: 120V Output Connections: (4) NEMA 5-15R (minimum) Output Frequency: 50/60 Hz +/- 3 Hz Bypass: Built-in Bypass (Automatic and/or Manual) Runtime Requirement: 5 Minutes with 1100 watt load (minimum)

Communications and Management:

Interface Ports: RJ-45 Serial or DB-9 RS-232, USB Alarms: Audible Alarm Control Panel: LCD or LED status

Surge Protection and Filtering:

Surge Protection: 480 Joules (Minimum)

Battery Pack:

Runtime Requirement: Battery pack/UPS combination must provide at least 30 minutes runtime with an 1100 watt load.