UPS_Specifications.pdf
PDF 91 KB Posted
- Attached to
- Uninterruptable Power Supplies (UPS) Federal contract opportunity
- Solicitation number
- RFQ-OH-16-00012
About this file
UPS Specifications
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Page_3.pdf | ||
| UPS_Specifications_-_updated.pdf | ||
| Sol_RFQ-OH-16-00012_Amd_000005.pdf | ||
| UPS_Specifications_Rvsd.pdf | ||
| Sol_RFQ-OH-16-00012_Amd_000004.pdf | ||
| Sol_RFQ-OH-16-00012_Amd_000003.pdf | ||
| Sol_RFQ-OH-16-00012_Amd_000002.pdf | ||
| Sol_RFQ-OH-16-00012_Amd_000001.pdf | ||
| Sol_RFQ-OH-16-00012.pdf | ||
| Solicitation_Cover_Letter.doc | DOC document | |
| Synopsis.doc | DOC document |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
U.S. EPA-Cincinnati Uninterruptable Power Supply Requirements
Item # Description Qty
1 8 KVA Rack Mount UPS 3 See Page 2 “8 KVA Rack Mont UPS Specifications” for details
2 8 KVA Rack Mount UPS w/ Battery Pack 1 See Page 3 “8 KVA Rack Mount UPS w/ Battery Pack Specifications” for details
3 8 KVA Tower UPS 10 See Page 4 “8 KVA Tower UPS Specifications”
4 6 KVA Rack Mount UPS 3 See Page 5 “6 KVA Rack Mount UPS Specifications”
5 3 KVA Tower UPS 2 See Page 6 “3 KVA Tower UPS Specifications”
6 2 KVA Tower UPS 3 See Page 7 “2 KVA Tower UPS Specifications”
7 2 KVA Rack Mount UPS w/ Battery Pack 1 See Page 8 “2 KVA Rack Mount UPS w/ Battery Pack Specifications”
8 KVA Rack Mount UPS Specifications
Power requirement: 8 KVA
Physical Characteristics:
Rack mountable, single chassis (no external power distribution unit (PDU) or step-down transformer required to meet output requirements)
Input:
Nominal Input Voltage: 208V Input Frequency: 40-70 Hz (auto sensing) Input Connections: Hard Wire 3 Wire (2PH + G) Input voltage Range: 160-275V
Other Input Voltage: 240
Output:
Power Required: 7200 watts (minimum) Nominal Output Voltage: 208V Output Connections: (2) NEMA L6-20R (minimum) Output Frequency: 50/60 Hz +/- 3 Hz Bypass: Internal Bypass (Automatic and Manual) Runtime Requirement: 5 Minutes with 5000 watt load (minimum)
Communications and Management:
Interface Ports: RJ-45 Ethernet, RJ-45 Serial, USB Alarms: Audible Alarm Control Panel: Multifunction LCD or LED status and control console Network Manageable: Provides remote power management of the UPS over the network.
Surge Protection and Filtering:
Surge Protection: 480 Joules (Minimum)
8 KVA Rack Mount UPS w/ Battery Pack Specifications
Physical Characteristics:
Rack mountable, single chassis (no external power distribution unit (PDU) or step-down transformer required to meet output requirements)
Input:
Nominal Input Voltage: 208V Input Frequency: 40-70 Hz (auto sensing) Input Connections: Hard Wire 3 Wire (2PH + G) Input voltage Range: 160-275V
Other Input Voltage: 240
Output:
Power Required: 7200 watts (minimum) Nominal Output Voltage: 208V Output Connections: (2) NEMA L6-20R (minimum) Output Frequency: 50/60 Hz +/- 3 Hz Bypass: Internal Bypass (Automatic and Manual)
Communications and Management:
Interface Ports: RJ-45 Ethernet, RJ-45 Serial, USB Alarms: Audible Alarm Control Panel: Multifunction LCD or LED status and control console Network Manageable: Provides remote power management of the UPS over the network.
Surge Protection and Filtering:
Surge Protection: 480 Joules (Minimum)
Battery Pack:
Runtime Requirement: Battery pack/UPS combination must provide at least 30 minutes runtime with a 5000 watt load.
8 KVA Tower UPS Specifications
Physical Characteristics:
Tower, single chassis (no external power distribution unit (PDU) or step-down transformer required to meet output requirements)
Input:
Nominal Input Voltage: 208V Input Frequency: 40-70 Hz (auto sensing) Input Connections: Hard Wire 3 Wire (2PH + G) Input voltage Range: 160-275V
Other Input Voltage: 240
Output:
Power Required: 7200 watts (minimum) Nominal Output Voltage: 208V Output Connections: (2) NEMA L6-20R (minimum) Output Frequency: 50/60 Hz +/- 3 Hz Bypass: Internal Bypass (Automatic and Manual) Runtime Requirement: 5 Minutes with 5000 watt load (minimum)
Communications and Management:
Interface Ports: RJ-45 Ethernet, RJ-45 Serial, USB Alarms: Audible Alarm Control Panel: Multifunction LCD or LED status and control console Network Manageable: Provides remote power management of the UPS over the network.
6 KVA Rack Mount UPS Specifications
Power requirement: 6 KVA
Physical Characteristics:
Rack mountable, external power distribution unit (PDU) or step-down transformer may be used to meet output requirements.
Input:
Nominal Input Voltage: 208V Input Frequency: 40-70 Hz (auto sensing) Input Connections: Hard Wire 3 Wire (2PH + G) Input voltage Range: 160-275V
Other Input Voltage: 240
Output:
Power Required: 4200 watts (minimum) Nominal Output Voltage: 120V, 208V Output Connections: (3) NEMA L5-20R (minimum) Output Frequency: 50/60 Hz +/- 3 Hz Bypass: Internal Bypass (Automatic and Manual) Runtime Requirement: 5 Minutes with 4000 watt load (minimum)
Communications and Management:
Interface Ports: RJ-45 Ethernet, RJ-45 Serial, USB Alarms: Audible Alarm Control Panel: Multifunction LCD or LED status and control console Network Manageable: Provides remote power management of the UPS over the network.
3 KVA Tower UPS Specifications
Power requirement: 3 KVA
Physical Characteristics:
Tower, single chassis (no external power distribution unit (PDU) or step-down transformer required to meet output requirement)
Input:
Nominal Input Voltage: 120V Input Frequency: 50-60 Hz +/- 5 Hz (auto sensing) Input Connections: NEMA L5-30P Input voltage Range: 90-150V
Output:
Power Required: 2100 watts (minimum) Nominal Output Voltage: 120V Output Connections: (4) NEMA 5-15R (minimum)
(2) NEMA 5-20 (minimum) Output Frequency: 50/60 Hz +/- 3 Hz Bypass: Internal Bypass (Automatic and Manual) Runtime Requirement: 5 Minutes with 2000 watt load (minimum)
Communications and Management:
Interface Ports: RJ-45 Serial or DB-9 RS-232, USB Alarms: Audible Alarm Control Panel: Multifunction LCD or LED status and control console
2 KVA Tower UPS Specifications
Power requirement: 2 KVA (minimum)
Physical Characteristics:
Tower, single chassis (no external power distribution unit (PDU) or step-down transformer required to meet output requirement)
Input:
Nominal Input Voltage: 120V Input Frequency: 50-60 Hz +/- 5 Hz (auto sensing) Input Connections: NEMA 5-20P Input voltage Range: 90-150V
Output:
Power Required: 1600 watts (minimum) Nominal Output Voltage: 120V Output Connections: (4) NEMA 5-15R (minimum) Output Frequency: 50/60 Hz +/- 3 Hz Bypass: Built-in Bypass (Automatic and/or Manual) Runtime Requirement: 5 Minutes with 1100 watt load (minimum)
Communications and Management:
Interface Ports: RJ-45 Serial or DB-9 RS-232, USB Alarms: Audible Alarm Control Panel: LCD or LED status
2 KVA Rack Mount UPS w/ Battery Pack Specifications
Power requirement: 2 KVA (minimum)
Physical Characteristics:
Rack mount, single chassis (no external power distribution unit (PDU) or step-down transformer required to meet output requirement)
Input:
Nominal Input Voltage: 120V Input Frequency: 50-60 Hz +/- 5 Hz (auto sensing) Input Connections: NEMA 5-20P Input voltage Range: 90-150V
Output:
Power Required: 1600 watts (minimum) Nominal Output Voltage: 120V Output Connections: (4) NEMA 5-15R (minimum) Output Frequency: 50/60 Hz +/- 3 Hz Bypass: Built-in Bypass (Automatic and/or Manual) Runtime Requirement: 5 Minutes with 1100 watt load (minimum)
Communications and Management:
Interface Ports: RJ-45 Serial or DB-9 RS-232, USB Alarms: Audible Alarm Control Panel: LCD or LED status
Surge Protection and Filtering:
Surge Protection: 480 Joules (Minimum)
Battery Pack:
Runtime Requirement: Battery pack/UPS combination must provide at least 30 minutes runtime with an 1100 watt load.
File details come from the government source that posted it. Updated .