RFQ 19J01026Q0020 - Water Treatment Systems.pdf
PDF 912 KB Posted
- Solicitation number
- RFQ-19J01026Q0020
- Issued by
-
Department of State
About this file
RFQ Summary: Water Treatment Services for U.S. Embassy Amman
This is a Request for Quotation (RFQ) for firm-fixed-price water treatment services at the U.S. Embassy Amman compound in Jordan. The solicitation number is 19J01026Q0020, with an offer due date of September 6, 2026, at 16:30 Jordan Time. The contracting activity is the General Services Office (GSO) at the American Embassy in Amman, with inquiries directed to Hebah Fadli at (962) 6 590-7312 or AmmanRFQQuestions@state.gov. Award will be made to the lowest-priced, acceptable, responsible offeror based on compliance with technical requirements.
The contract covers a one-year base period plus four one-year options for water treatment services across three systems: HVAC water treatment (closed and open loops with 90,000 liters chilled water, 50,000 liters heating water, and 20,000 liters condenser water); potable water treatment (260,000 liters capacity with multi-barrier filtration, softening, and disinfection); and swimming pool water treatment. Services include preventive maintenance, chemical treatment, laboratory analysis, monitoring, reporting, and compliance with U.S. EPA regulations and ASHRAE 188 Legionella control standards. Pricing must be submitted in Jordanian Dinars (JOD) with no escalation provisions. Offerors must provide evidence of established business operations in Amman, SAM registration, three years of relevant project experience with references, quality assurance plans, proof of required licenses and permits, personnel CVs and qualifications, and certificates of insurance. A mandatory site visit is scheduled for August 27, 2026, at 10:00 AM. Payment will be made within 30 days of invoice receipt, and minimum public liability insurance of 30,000 JOD per occurrence and 140,000 JOD cumulative for bodily injury is required.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFQ 19J01026Q0020 - ATTACHMENT A - PERFORMANCE WORK STATEMENT.pdf | ||
| NDAA-Document.pdf | ||
| RFQ 19J01026Q0020 - Cover page.pdf | ||
| SAM-Registration.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFQ - 19J01026Q0020
Water Treatment Services for All Water Systems on the U.S Embassy Amman Compound
SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL ITEMS
OFFEROR TO COMPLETE BLOCKS 12, 17, 23, 24, & 30
1. REQUISITION NUMBER
PR16198811
2. CONTRACT NO.
3. AWARD/EFFECTIVE DATE 4. ORDER NUMBER
5. SOLICITATION NUMBER
19J01026Q0020
6. SOLICITATION ISSUE DATE
Aug 23rd, 2026
7. FOR SOLICITATION
INFORMATION CALL
a. NAME
Hebah Fadli - Fadlihf@state.gov AmmanRFQQuestions@state.gov
b. TELEPHONE NUMBER(No collect calls)
(962) 6 590-7312
8. OFFER DUE DATE/ LOCAL
TIME
Sep 6th, 2026, at 16:30 (Jordan Time)
9. ISSUED BY CODE
19J010 10. THIS ACQUISITION IS 11. DELIVERY FOR FOB 12. DISCOUNT TERMS
General Services Office (GSO) American Embassy – Amman, Jordan Email: AmmanRFQ@state.gov Tel: + 962 6 5906025 - Fax: + 962 6 5907957
UNRESTRICTED
SET ASIDE: % FOR
SMALL BUSINESS
DESTINATION UNLESS
BLOCK IS MARKED
SEE SCHEDULE
HUBZONE SMALL
BUSINESS
13a. THIS CONTRACT IS A RATED ORDER
UNDER DPAS (15 CFR 700)
8(A) 13b. RATING
NAICS: 14. METHOD OF SOLICITATION
RFQ IFB RFP
15. DELIVER TO CODE
19J010 16. ADMINISTERED BY CODE
American Embassy Amman - Jordan
See Item 9
17a. CONTRACTOR/ CODE
OFFEROR FACILITY
CODE 18a. PAYMENT WILL BE MADE BY CODE
TELEPHONE NO.
Financial Management Office (FMO) American Embassy - Amman – Jordan E-mail: AmmanBilling@state.gov Payment will be made within 30 days after receiving the services with a proper invoice. Invoices to be sent to FMO via Email.
17b. CHECK IF REMITTANCE IS DIFFERENT AND PUT
SUCH ADDRESS IN OFFER
18b. SUBMIT INVOICES TO ADDRESS SHOWN IN BLOCK 18a UNLESS
BLOCK BELOW IS CHECKED SEE ADDENDUM
19.
ITEM NO.
20.
SCHEDULE OF SUPPLIES/SERVICES
21.
QUANTIT
Y
22.
UNIT
23.
UNIT PRICE
JOD
24.
AMOUNT
JOD
1 Water Treatment Services for All Water System – Base Year 12 Month
2 Water Treatment Services for All Water System – Option Year 1
12 Month
3 Water Treatment Services for All Water System – Option Year 2
4 Water Treatment Services for All Water System – Option Year 3
5 Water Treatment Services for All Water System – Option Year 4
6 Water Treatment Services for All Water System – Option 6 Months
25. ACCOUNTING AND APPROPRIATION DATA
26. TOTAL AWARD AMOUNT (For Govt. Use Only)
27a. SOLICITATION INCORPORATES BY REFERENCE FAR 52.212-1, 52.212-4. FAR 52.212-3 AND 52.212-5 ARE ATTACHED. ADDENDA ARE ARE NOT ATTACHED.
27b. CONTRACT/PURCHASE ORDER INCORPORATES BY REFERENCE FAR 52.212-4. FAR 52.212-5 IS ATTACHED. ADDENDA ARE ARE NOT ATTACHED.
28. CONTRACTOR IS REQUIRED TO SIGN THIS DOCUMENT AND RETURN _1_ COPIES TO ISSUING
OFFICE. CONTRACTOR AGREES TO FURNISH AND DELIVER ALL ITEMS SET FORTH OR
OTHERWISE IDENTIFIED ABOVE AND ON ANY ADDITIONAL SHEETS SUBJECT TO THE TERMS AND
CONDITIONS SPECIFIED HEREIN.
29.AWARD OF CONTRACT: REF. _________________ OFFER DATED
_______________. YOUR OFFER ON SOLICITATION (BLOCK 5), INCLUDING
ANY ADDITIONS OR CHANGES WHICH ARE SET FORTH HEREIN, IS
ACCEPTED AS TO ITEMS:
30a. SIGNATURE OF OFFEROR/CONTRACTOR 31a. UNITED STATES OF AMERICA (SIGNATURE OF CONTRACTING OFFICER)
30b. NAME AND TITLE OF SIGNER (TYPE OR PRINT)
30c. DATE SIGNED
31b. NAME OF CONTRACTING OFFICER (Type or Print)
Emily Tietze 31c. DATE SIGNED mailto:Fadlihf@state.gov mailto:AmmanRFQQuestions@state.gov mailto:AmmanRFQ@state.gov mailto:AmmanBilling@state.gov
TABLE OF CONTENTS
SECTION 1 - THE SCHEDULE
• SF 1449 cover sheet
• Continuation To SF-1449, RFQ Number 19J01026Q0020, Prices, Block 23
• Continuation To SF-1449, RFQ Number 19J01026Q0020, Schedule Of
Supplies/Services, Block 20 Description/Specifications/Work Statement
• Attachment 1 to Description/Specifications/Performance Work Statement, Government Furnished Property
SECTION 2 - CONTRACT CLAUSES
• Contract Clauses
• Addendum to Contract Clauses - FAR and DOSAR Clauses not Prescribed in Part 12
SECTION 3 - SOLICITATION PROVISIONS
• Solicitation Provisions
• Addendum to Solicitation Provisions - FAR and DOSAR Provisions not Prescribed in
Part 12
SECTION 4 - EVALUATION FACTORS
• Evaluation Factors
• Addendum to Evaluation Factors - FAR and DOSAR Provisions not Prescribed in
Part 12
SECTION 5 - REPRESENTATIONS AND CERTIFICATIONS
• Offeror Representations and Certifications
• Addendum to Offeror Representations and Certifications - FAR and DOSAR
Provisions not Prescribed in Part 12
SECTION 1 - THE SCHEDULE
CONTINUATION TO SF-1449
RFQ NUMBER S - 19J01026Q0020
PRICES, BLOCK 23
I. PERFORMANCE WORK STATEMENT
A. The purpose of this firm fixed price purchase order is to Water Treatment Services for All
Water Systems on the U.S Embassy Amman Compound in accordance with Attachment A.
B. The contract will be for a one-year period from the date of the contract award, with (4) Four one-year options.
II. PRICING
The rates below include all costs associated with providing Water Treatment Services for All Water Systems on the U.S Embassy Amman Compound in accordance with the attached scope of work, including materials, labor, insurance (see FAR 52.228-4 and 52.228-5), overhead, profit.
1. Base Year: The Contractor shall provide the services shown below for the base period of the contract and continuing for a period of 12 months
Description Quantity Unit Price
(JOD)
Total for Base Year
(JOD)
HVAC Water Treatment (chilled + heating closed loops;
condenser / cooling towers open loop) 12
Potable (Domestic) Water Treatment (multi-barrier plant, softeners, disinfection, pumps, wells, tanks) 12
Swimming Pool Water Treatment (recirculation/filtration, chlorine/pH dosing, salt cell, heater) 12
Legionella WMP & Lab Compliance (ASHRAE 188) (WMP upkeep, quarterly Legionella culture testing, enhanced monitoring)
Grand Total of Base Year JOD
2. Option Year 1: The Contractor shall provide the services shown below for Option Year 1 of the contract and continuing for a period of 12 months
Total for Base Year
(JOD)
HVAC Water Treatment (chilled + heating closed loops;
condenser / cooling towers open loop) 12
Potable (Domestic) Water Treatment (multi-barrier plant, softeners, disinfection, pumps, wells, tanks) 12
Swimming Pool Water Treatment (recirculation/filtration, chlorine/pH dosing, salt cell, heater) 12
Legionella WMP & Lab Compliance (ASHRAE 188) (WMP upkeep, quarterly Legionella culture testing, enhanced monitoring)
Grand Total of Option Year 1 JOD
3. Option Year 2: The Contractor shall provide the services shown below for Option Year 2 of
Total for Base Year
(JOD)
HVAC Water Treatment (chilled + heating closed loops;
condenser / cooling towers open loop) 12
Potable (Domestic) Water Treatment (multi-barrier plant, softeners, disinfection, pumps, wells, tanks) 12
Swimming Pool Water Treatment (recirculation/filtration, chlorine/pH dosing, salt cell, heater) 12
Legionella WMP & Lab Compliance (ASHRAE 188) (WMP upkeep, quarterly Legionella culture testing, enhanced monitoring)
Grand Total of Option Year 2 JOD
4. Option Year 3: The Contractor shall provide the services shown below for Option Year 3 of
Total for Base Year
(JOD)
HVAC Water Treatment (chilled + heating closed loops;
condenser / cooling towers open loop) 12
Potable (Domestic) Water Treatment (multi-barrier plant, softeners, disinfection, pumps, wells, tanks) 12
Swimming Pool Water Treatment (recirculation/filtration, chlorine/pH dosing, salt cell, heater) 12
Legionella WMP & Lab Compliance (ASHRAE 188) (WMP upkeep, quarterly Legionella culture testing, enhanced monitoring)
Grand Total of Option Year 3 JOD
5. Option Year 4: The Contractor shall provide the services shown below for Option Year 4 of
Total for Base Year
(JOD)
HVAC Water Treatment (chilled + heating closed loops;
condenser / cooling towers open loop) 12
Potable (Domestic) Water Treatment (multi-barrier plant, softeners, disinfection, pumps, wells, tanks) 12
Swimming Pool Water Treatment (recirculation/filtration, chlorine/pH dosing, salt cell, heater) 12
Legionella WMP & Lab Compliance (ASHRAE 188) (WMP upkeep, quarterly Legionella culture testing, enhanced monitoring)
Grand Total of Option Year 4 JOD
6. FAR Clause 52.217-8 OPTION TO EXTEND SERVICES (6-MONTHS)
Price information on the table below is for price evaluation for award purposes only. The proposed price on the table below will not be incorporated in the overall cost of the contract at the time of award.
The Contracting Officer may exercise FAR clause 52.217-8 for extension of services for no more than six months, if determined to be in the best interest to the Government.
Total for Base Year
(JOD)
HVAC Water Treatment (chilled + heating closed loops;
condenser / cooling towers open loop) 6
Potable (Domestic) Water Treatment (multi-barrier plant, softeners, disinfection, pumps, wells, tanks) 6
Swimming Pool Water Treatment (recirculation/filtration, chlorine/pH dosing, salt cell, heater) 6
Legionella WMP & Lab Compliance (ASHRAE 188) (WMP upkeep, quarterly Legionella culture testing, enhanced monitoring)
Grand Total of Option to Extend (6-Months) JOD
7. Grand Total of Base Year plus All Options Years in Jordanian Dinar
Year Price in (JOD) Base Year Total in Jordanian Dinar Option Year 1 Total in Jordanian Dinar Option Year 2 Total in Jordanian Dinar Option Year 3 Total in Jordanian Dinar Option Year 4 Total in Jordanian Dinar Option to Extend Services 52-217-8 Total (6-MONTHS) Grand Total of Base plus All Option Years in Jordanian Dinar
III. VALUE ADDED TAX
VALUE ADDED TAX. Value Added Tax (VAT) is not applicable to this contract and shall not be included in the CLIN rates or Invoices because the U.S. Embassy has a tax exemption certificate from the host government.
CONTINUATION TO SF-1449,
RFQ NUMBER 19J01026Q0020
SCHEDULE OF SUPPLIES/SERVICES, BLOCK 20
DESCRIPTION/SPECIFICATIONS/WORK STATEMENT
1. General Information
1.1 Purpose
The purpose of this Statement of Work (SOW) is to define the requirements for the planning, procurement, preventive maintenance, testing, monitoring and reporting of the water treatment programs serving all water systems on the U.S. Embassy Amman compound. This is a support-service water treatment contract under which the Contractor furnishes the treatment chemicals, equipment, laboratory analysis, professional water-treatment services and reporting required to preserve the interior waterside condition of the compound's piping and equipment; to control corrosion, scaling, deposition, and microbiological fouling (including Legionella); and to maintain water quality within the parameters established in this SOW. The intent is to establish a cost-effective, reliability-centered program that protects asset value, reduces operating cost, conserves water and chemicals, and safeguards the health of building occupants and operating personnel.
1.2 Scope Summary
The Contractor shall provide all labor, supervision, project management, transportation, chemicals, consumables, test kits, laboratory services, tools, and reporting necessary to deliver a complete water-treatment maintenance program for the following systems:
System Sub-systems / Loops Covered Primary Control Objectives
HVAC Water Treatment
Primary & secondary chilled water (closed); heating hot water (closed); condenser water / cooling towers (open)
Corrosion & scale control, glycol integrity, microbiological & Legionella control, deposition control
Potable (Domestic) Water Treatment
Pre-treatment & storage, filtration (media / cartridge / GAC), softening, disinfection, booster & transfer pumping, wells, storage tanks
Compliance with U.S. EPA Primary & Secondary Drinking Water Regulations; disinfection residual; hardness; corrosion control
Swimming Pool Water Treatment
Recirculation & filtration, chemical dosing (chlorine / pH), Sanitizer & pH control, water clarity, bather safety, equipment protection
System Sub-systems / Loops Covered Primary Control Objectives salt chlorination where installed, heater and circulation equipment
Note on scope boundaries: This contract addresses water chemistry treatment, monitoring, and the maintenance of treatment/dosing equipment and directly associated pumps as listed in the equipment inventory (Exhibit E). Major mechanical overhaul or replacement of chillers, boilers, or cooling-tower structures is outside this contract, except where the Contractor identifies and reports conditions that jeopardize the treatment program.
1.3 Contract Type and Period of Performance
• Contract type. Firm-fixed-price (FFP) commercial service contract, payable entirely in
Jordanian Dinars (JOD). No additional sums are payable for escalation in materials, equipment, or labor, or for currency-exchange fluctuation.
• Period of performance. One (1) base year from the date of award, with four (4) one-year options to renew, exercised at the Government's discretion in accordance with FAR 52.217- 9.
• Award basis. Award is anticipated to the responsive, responsible offeror proposing the lowest evaluated price that meets all requirements of this SOW. This document is the technical reference against which offerors price the work.
1.4 Definitions and Acronyms
Term Definition
CO Contracting Officer — the sole authority to enter into, administer, or modify the contract.
COR
Contracting Officer's Representative — the FAC Mechanical Engineer / Facilities Manager designated in writing to act for the CO on technical matters within delegated limits.
FAC / FM Facilities Management Office / Facilities Manager, U.S. Embassy Amman.
OBO Bureau of Overseas Buildings Operations, U.S. Department of State.
PM Preventive Maintenance.
RCM Reliability-Centered Maintenance.
SDS / MSDS Safety Data Sheet / Material Safety Data Sheet.
WMP Water Management Program (Legionella risk management per ASHRAE 188).
mpy Mils per year (corrosion rate).
Term Definition TDS Total Dissolved Solids.
HPC Heterotrophic Plate Count.
CoC Cycles of Concentration (open recirculating systems).
LSI / RSI Langelier Saturation Index / Ryznar Stability Index.
POSHO Post Occupational Safety and Health Officer.
NTU Nephelometric Turbidity Units.
2. Systems to Be Maintained (As-Built Basis) The volumes and equipment below establish the design basis for treatment. The Contractor shall verify actual system volumes, equipment counts, and connection points during the initial site survey (Section 4) and reconcile any discrepancies with the COR in writing. Approximate loop volumes are provided for chemical-dosing calculations and do not relieve the Contractor of the responsibility to confirm field conditions.
2.1 HVAC Water Systems
Loop / System Type Approx. Volume Primary & Secondary Chilled Water Closed loop 90,000 liters Condenser Water (cooling towers) Open loop 20,000 liters Heating Hot Water Closed loop 50,000 liters
Cooling towers. Open-circuit, induced-draft, counter-flow cooling towers (design basis Evapco Series AT or approved equal, e.g., Baltimore Aircoil or Marley). Towers include FRP/galvanized basins, drift eliminators, PVC fill, makeup water level control, and basin strainers. Because these are open evaporative devices, they are the compound's principal Legionella risk and are subject to the Water Management Program in Section 8.
Closed loops. Chilled-water and heating-hot-water loops are treated with a molybdate-based corrosion/scale inhibitor package. The chilled-water system is maintained at a nominal 30% propylene-glycol concentration for freeze protection; glycol integrity (freeze point, inhibitor reserve, and degradation by-products) is part of the treatment program.
Side-stream filtration. Condenser water is served by a sand side-stream filter; chilled- and hot-water loops are served by cartridge/bag filtration rated 98% efficient at 20 microns, fitted to the Embassy's existing filter housings.
2.2 Potable (Domestic) Water Treatment System
Approximate treated/stored domestic water volume: 260,000 liters. The system is a multi-barrier potable treatment train designed to comply with the U.S. EPA National Primary and Secondary Drinking Water Regulations (40 CFR Parts 141–143) and the Safe Drinking Water Act, and to be capable of producing potable water with one unit of each process out of service. Principal components include:
• Pre-treatment: pre-storage filtration removing particles ≥ 5 microns, with redundancy (one unit out of service).
• Filtration: carbon (GAC) filters, cartridge filters, and media filtration.
• Softening: duplex water softeners (ion exchange) with brine tank(s).
• Disinfection: chlorination (liquid/tablet/on-site generation) and/or UV, maintaining a free-chlorine residual of 0.2–0.5 mg/L throughout the distribution system.
• Process pressure FRP tanks (ASME Section X), controls, and testing/monitoring equipment
(turbidity, chlorine residual, hardness, incubator/membrane-filtration bacteriological kit).
• Pumping: cistern, booster, transfer, and chemical-dosing pumps; submersible well pump(s) and water well(s) where present.
• Storage: below-ground raw and finished/treated water storage (Plant Room) and above-ground UTL Building storage.
2.3 Swimming Pool Water Treatment System
The compound swimming pool(s) are served by a recirculation, filtration, and automated chemical-treatment system. The design basis includes cartridge filtration, automated chlorine and pH (acid) dosing with a controller, salt chlorine generation where installed, a pool heater, circulation pumps, and associated safety equipment. The treatment objective is to maintain sanitizer and pH within safe bather-health ranges, water clarity, and equipment protection. Target operating set-points: pH ≈ 7.2 and free chlorine residual ≈ 0.6 mg/L (or per governing pool code and COR direction).
3. General Requirements
Requirement Description
Statement of intent
This SOW describes the preventive maintenance, testing, monitoring, and deliverables to be performed by the Contractor. The Contractor's accepted cost proposal and maintenance schedule, together with this SOW and the deliverables developed by the Contractor and accepted by the U.S. Government (USG), delineate the full scope and work limits of the service.
Sole points of contact
The Contracting Officer (CO) and the Contracting Officer's Representative (COR) are the sole points of contact for all technical and contractual matters. The Contractor shall take no direction, verbal or otherwise, from any USG personnel other than the CO or
COR.
Requirement Description
Services included
The Contractor shall provide site assessment and survey; project management; professional water-treatment services; chemical and material procurement and logistics; preventive maintenance and testing; laboratory analysis; cost estimating and scheduling; and general support for the duration of the contract.
Reliability-centered maintenance (RCM)
The Contractor shall apply RCM principles to all activities, using high-quality, cost-effective materials and chemicals that are maintainable with locally available supplies and services to the extent practical, and shall maximize interchangeability of parts with existing Post systems.
New parts and materials
Except as otherwise directed by the CO, all parts, materials, components, and equipment furnished by the Contractor shall be new (not used or third-party remanufactured) and equal to or better than the manufacturer's recommended replacements.
Discrepancy reporting Within three (3) calendar days of receipt of the USG SOW/technical data, the Contractor shall notify the CO in writing of any discrepancies, errors, or conflicts discovered.
References The Contractor shall provide at least three (3) customer references for water-treatment work of similar scope and value.
Technician documentation
The Contractor shall provide technicians' resumes and training/certification documentation within twenty (20) days of the notice to proceed.
Quality control
The Contractor shall maintain a documented quality-control process agreed with the COR, and shall allow the USG (and its subcontractors' relevant quality systems) access for monitoring and quality auditing throughout the contract.
Care of Government property
The Contractor shall not use any method or substance that may damage equipment or systems. Any damage or loss caused by the Contractor's negligence or practices shall be corrected at the Contractor's expense, or the Contractor shall reimburse the USG for the cost of rectification.
Document ownership
All deliverables, documents, data, and media (including USG-provided documents) remain USG property. Duplication or distribution outside the Contractor's execution team is prohibited without the CO's written authorization. Upon completion of each visit, all documents, electronic media, and photographs shall be submitted to the Government with the service report.
Least interference The Contractor shall schedule and coordinate all work to cause the least interference with Post operations. Where interference is unavoidable, the Contractor shall minimize its impact and modify
Requirement Description schedules if the COR determines a conflict with critical Post operations exists.
4. Initial Site Survey, Baseline and Mobilization
Within thirty (30) calendar days of the notice to proceed, the Contractor shall complete a comprehensive baseline survey and submit a Baseline Report to the COR. The survey establishes the starting condition of each system and the specific chemical program to be applied. At a minimum the Contractor shall:
1. Verify and document actual loop volumes, equipment inventory, connection/injection points, and existing dosing/control equipment for all three systems.
2. Perform a full baseline water analysis of each loop and of the make-up/source water, including an AWWA RTW analysis of source water to determine the CCPP, Langelier Saturation Index (LSI), Ryznar Stability Index (RSI), and Aggressiveness Index, and use these to establish the chemical balance required to prevent corrosion and scale.
3. Establish, for each chemical, the minimum and maximum control ranges to be maintained, avoiding unnecessarily high chemical levels in order to control cost and adverse chemical reactions.
4. Submit the proposed chemical program with manufacturer specifications, chemical composition, SDS/MSDS, and equipment cut sheets (English and Arabic) for COR approval before use (Section 6).
5. Submit a proposed 12-month maintenance schedule (monthly visit calendar) and the routine (daily/weekly) operator test plan to be executed by Post staff.
6. Draft or update the compound Water Management Program (WMP) for Legionella control per Section 8.
5. Contracting Officer's Representative (COR) The CO may designate one or more Government employees, by name or position, as COR, with the scope and limits of authority stated in the designation. The COR may not change the terms, conditions, or price of the contract unless the COR is a warranted Contracting Officer with delegated authority. All technical questions concerning the scope and requirements of this contract shall be directed to the COR (the Facilities Manager / Mechanical Engineer, U.S. Embassy Amman).
6. Technical Specifications — Chemicals, Equipment and Testing
6.1 General
• All equipment, chemicals, and testing procedures/kits shall be approved by the COR prior to use.
• The Contractor shall submit manufacturer specifications, SDS/MSDS (including chemical composition), and equipment cut sheets for all equipment, chemicals, and testing procedures in both English and Arabic.
• Chemicals shall have a storage-life expectancy of at least one (1) year; the Contractor shall ensure proper storage and that no chemical past its expiration date is used.
• The Contractor shall establish and maintain minimum/maximum control ranges for each chemical (Section 4.3).
• Sustainable chemistry preference. Where technically suitable, the Contractor shall favor NSF-certified, environmentally responsible chemistries (e.g., non-chromate corrosion inhibitors, and non-nitrite formulations where compatible), and shall optimize cooling-tower cycles of concentration to minimize make-up water, blowdown, and chemical consumption without compromising corrosion, scale, or microbiological control.
6.2 HVAC Water Treatment Chemistry
• 6.2.1 Closed Loops (Chilled Water and Heating Hot Water)
• Corrosion/scale inhibitor: molybdate-based inhibitor designed for closed hot and chilled recirculating systems, in liquid form, pH 10.8–12.5, density 1.03–1.07 kg/L, containing no sodium nitrite, compatible with propylene glycol. Minimum composition to include sodium molybdate, sodium hydroxide, sodium tetraborate, and pentahydrate.
• Glycol: propylene glycol with inhibitors, maintained at 30% concentration in the chilled-water system, meeting the requirements of DOWFROST by Dow Chemical Company or approved equal.
• Closed-loop filter media: rated 98% efficient at 20-micron particulate and dimensioned to fit the Embassy's existing filtration units; cartridge/bag pressure drop not to exceed ~18 kPa clean and ~35 kPa dirty at design flow.
• Passivation: newly cleaned or refilled closed loops shall be chemically cleaned/flushed and passivated in accordance with the inhibitor manufacturer's procedure before being returned to normal treatment.
• 6.2.2 Open Loop (Condenser Water / Cooling Towers)
• Program to include a scale/deposit sequestering agent, corrosion inhibitor, acid for alkalinity/pH adjustment (as required), and dual (alternating) biocides to prevent microbial immunity.
• Chemical feed to be automatic and controller-based: inhibitor fed on make-up volume;
bleed-off/blowdown controlled on conductivity; biocides fed on a programmable timer with alternation between two formulations.
• Low-chemical liquid-level switches shall deactivate solution pumps and signal an alarm.
• 6.2.3 HVAC Control Parameters
Parameter Closed Systems Condenser / Open pH 7.0 – 10.0 6.5 – 8.5 Chilled water corrosion inhibitor (as molybdate) 50 – 100 ppm —
Heating hot water corrosion inhibitor (as molybdate) 100 – 150 ppm —
Scale / corrosion inhibitor (as molybdate) — 4 – 10 ppm
Corrosion — mild steel < 1.0 mpy < 2.0 mpy Pitting — mild steel None None Corrosion — copper alloys < 0.1 mpy < 0.2 mpy Scaling & deposition None None
Organic / microbiological growth Total aerobic count < 10,000/mL; no visible deposits; no health hazard
None; controlled by biocide program
6.3 Potable (Domestic) Water Treatment Chemistry
• All chemicals in contact with potable water shall comply with U.S. EPA regulations and be certified to NSF/ANSI Standard 60 (Drinking Water Treatment Chemicals);
materials/piping to NSF 61 and NSF 14 as applicable.
• Maintain a free-chlorine residual of 0.2–0.5 mg/L in all parts of the distribution system.
• Treated water shall meet U.S. EPA Primary and Secondary Drinking Water Regulations (40
CFR Parts 141–143).
Potable Parameter Maintenance Target Chlorine residual 0.2 – 0.5 mg/L throughout distribution
Microbiological & chemical constituents Meet U.S. EPA Primary & Secondary Drinking Water Regulations (40 CFR 141–143)
Corrosion — mild steel < 2.0 mpy Pitting — mild steel None Corrosion — copper alloys < 0.2 mpy
Potable Parameter Maintenance Target Scaling & deposition None
Microbiological fouling No visible deposits; no health hazard; total HPC < 500 CFU/mL
6.4 Swimming Pool Water Chemistry
• Sanitizer and pH chemicals shall be handled per manufacturer and occupational-safety requirements; SDS provided in English and Arabic.
• Maintain sanitizer and pH within the governing pool code and COR-approved ranges
(nominal free chlorine ≈ 0.6 mg/L, pH ≈ 7.2), with balanced total alkalinity, calcium hardness, and cyanuric acid where applicable.
• Where salt chlorine generation is installed, verify cell operation, salinity, and output; where acid/chlorine dosing is automated, verify controller calibration, feed rates, and tank levels.
6.5 Test Equipment and Laboratory Standards
• HVAC test kit: capable of pH, TDS, dissolved oxygen, biological/microbial count (dip slides), chloride, total alkalinity, and calcium hardness field tests, plus conductivity meter.
• Corrosion coupon racks: two-station rack for each closed loop and four-station rack for the open condenser system, with mild-steel and copper coupons (copper installed downstream of mild steel).
• Potable test set: turbidity, free/total chlorine, hardness, and a membrane-filtration/incubator bacteriological kit (e.g., Colilert or MILLIPORE) for coliform/HPC.
• Applicable laboratory standards include ASTM D 3370 (sampling) and, as relevant, ASTM D 859 (silica), D 1066 (steam), D 1067 (acidity/alkalinity), D 1068 (iron), and D 1126 (hardness); potable bacteriological analyses by a certified laboratory.
7. Safety, Health and Environmental Management (SHEM) The Contractor shall take all reasonable and proper safety precautions to prevent death, injury, or property damage on the compound and at any offsite locations, and shall maintain and use all equipment so as to minimize the risk of accident, injury, loss, or damage. In addition to host-country statutory requirements, the Contractor shall:
• Ensure proper disposal of toxic substances where applicable, and that personnel are knowledgeable of and adhere to all relevant occupational health-and-safety legislation and
SDS.
• Ensure all electrical equipment and associated materials comply with UL requirements, and follow all NFPA guidelines regarding fire, smoke, or venting of noxious substances.
• Ensure personnel are adequately trained and instructed in the safe use, handling, and operation of materials and equipment, and provide reasonable proof of such training to the U.S. Embassy on request.
• Ensure personnel are certified as having completed occupational health-and-safety training and have been issued all necessary Personal Protective Equipment (PPE) for safe execution of this contract.
• Present training program(s) that satisfy the U.S. Embassy during submittal, and bring any questions or injuries to the attention of the Post Occupational Safety and Health Officer
(POSHO).
• Provide and maintain SDS at all chemical storage and use points, ensure secondary containment and correct storage of chemicals, and protect personnel against corrosive or hazardous treatment chemicals.
8. Water Management Program for Legionella Control (ASHRAE 188) Because the compound operates open evaporative cooling towers and stored potable water, the Contractor shall support a written Water Management Program (WMP) consistent with ANSI/ASHRAE Standard 188 and applicable CDC/industry guidance. The WMP is a living document maintained jointly by the FAC/COR and the Contractor.
1. Establish and maintain a program team, process-flow description, and building water-system schematics identifying areas where Legionella and other waterborne pathogens could grow and spread.
2. Identify control locations and control limits (e.g., disinfectant residual, temperature, biocide levels, conductivity) and the monitoring frequency at each.
3. Define corrective actions when control limits are exceeded, and confirmation/verification procedures that the WMP is being followed and is effective.
4. Implement a routine microbiological monitoring regime for cooling-tower water, including dip-slide/aerobic counts at each service visit and periodic Legionella culture testing (recommended at least quarterly for cooling towers, and additionally after any disinfection or system disturbance) by a certified laboratory.
5. Maintain cooling-tower cleanliness and biocide control to prevent biofilm, and perform disinfection/remediation cleaning of towers on a scheduled basis and following elevated results, extended shutdown, or COR request.
6. Document all monitoring, exceedances, and corrective actions in the service reports and in the WMP log.
9. Maintenance Program, Visits and Frequencies
9.1 Support-Service Delivery Model
This is a support-service water-treatment contract with joint responsibilities between the Embassy facility-management staff and the Contractor:
• Routine operator testing (by Post staff). Embassy FAC staff conduct routine (daily/weekly) water-treatment tests of the HVAC and potable systems and e-mail the results to the Contractor on a weekly basis (potable results at least monthly).
• Technical analysis (by Contractor). The Contractor performs a technical analysis of each set of results and responds within twenty-four (24) hours, directing FAC staff to adjust chemical dosages and/or equipment operation as necessary to keep each system in range.
• Monthly on-site visits (by Contractor). The Contractor visits the compound monthly (twelve (12) times per year) to service all covered systems, and is responsible for all logistics, including transportation and any lodging for its staff.
• Log review. At each visit the Contractor reviews the facility's water-treatment and operating logs to verify chemicals are within design parameters and to identify trends.
• Monthly conference & report. The Contractor discusses conditions with the COR and operating engineers monthly and follows up with a written service report within three (3) business days of each visit (Section 10).
9.2 Preventive-Maintenance Frequency Matrix
The table consolidates the minimum tasks and frequencies across all systems. Detailed task content follows in Sections 9.3–9.6. Manufacturer O&M requirements take precedence where more stringent.
• 9.2.1 HVAC Water Treatment
Task Frequency Notes Routine chemistry tests (pH, conductivity, inhibitor, biocide) by Post staff
Daily / Weekly
Results emailed weekly to Contractor
Contractor technical analysis & dosing direction Weekly (≤24 h response) Adjust feeds as required
On-site inspection & full water analysis (all loops) Monthly Controller, sensors, pumps, tubing, accessories Controller/sensor calibration against known standard Monthly Conductivity, pH; verify solenoid, meter, pumps Cooling-tower dip-slide / aerobic count Monthly Feeds the WMP (Section 8)
Corrosion coupon change-out & lab analysis (mild steel & copper)
Every 90 days
Written coupon report to COR within 14 days of analysis
Glycol test — freeze point, inhibitor reserve, pH/degradation
Semi-annually
Top-up/replace glycol as required
Legionella culture test (cooling towers) Quarterly (min.)
Certified lab; plus after disinfection/disturbance
Task Frequency Notes Side-stream / cartridge filter media inspection & change
Quarterly / As required Per pressure-drop limits
Cooling-tower cleaning & disinfection Semi-annually / As required
And after elevated results or shutdown
Comprehensive annual water-treatment review & report Annually Trends, asset condition, recommendations
• 9.2.2 Potable (Domestic) Water Treatment
Task Frequency Notes Routine operator testing (chlorine, pH) by Post staff
Daily / Weekly
Results emailed monthly to Contractor
Contractor technical analysis & operations direction
Monthly (≤24 h response)
Re-establish effective treatment
Record pressures & chemical levels; replace dosing detection probes Quarterly Inspect metering pumps & tubing Free/total chlorine & pH in all domestic tanks Quarterly Distribution verification Booster pump service (clean, inspect, lubricate, megger, current/voltage)
Semi-annually Record readings
Full potable system service (softeners, media, backwash, brine, dosing, pumps, wells, tanks, controllers)
Annually See Section 9.4
Certified-lab potable analysis (full panel incl.
metals, coliform, HPC, turbidity) Annually Plus well chemical & bacteriological analysis Backflow preventer / anti-siphon certification (wells) Annually Where wells present
Tank inspection, cleaning & disinfection Annually / As required
Per AWWA C652 (tanks) &
ALDAC 137958
• 9.2.3 Swimming Pool Water Treatment
Task Frequency Notes
Sanitizer & pH verification / controller check Each visit (monthly)
Calibrate controller; verify feed rates
Water balance (alkalinity, hardness, CYA), clarity check Monthly Adjust to code / COR ranges
Filter inspection / backwash verification; salt cell inspection
Monthly / Quarterly Where salt system installed
Task Frequency Notes Circulation pump, strainer, heater check Quarterly Report deficiencies Full seasonal service & water-quality certification
Annually / Season start
Test kit & consumables verified
9.3 Detailed Tasks — HVAC Water Treatment
• 9.3.1 Safety and Standing Requirements
• Chemicals shall comply with EPA regulations and be handled per occupational-safety requirements; employ PPE against corrosive/hazardous chemicals; be familiar with all SDS.
• Water-treatment specialists shall be properly trained and certified; treatment shall be based on proven standard engineering practice and the manufacturer's directions.
• Maintenance includes chemicals, chemical feeding, maintaining proper water conditions, controlling bleed-off, protecting idle equipment, and record-keeping; ensure chemicals are properly stored, test equipment clean, and no chemical past expiration.
• 9.3.2 Monthly Inspection and Analysis
1. Sample water from each closed loop and the open system per manufacturer recommendations; test for proper chemical levels and adjust feeds to maintain optimal conditions.
2. Use the conductivity meter to test total solids/conductivity; record and analyze abnormal changes in the log.
3. Check pH with strips and/or meter; clean sample bottles and wipe down all chemical-treatment equipment.
4. Visually inspect the controller, sensors, pumps, tubing, and accessories; test chemical parameters (pH, TDS, conductivity, aerobic plate count, corrosion-inhibitor level, biocide dosage for both biocides); test supply water for base conditions (iron, manganese, alkalinity, total hardness, silica, chloride).
5. Calibrate sensors against a known standard; verify the controller, solenoid valves, contact water meter, inhibitor pump, and biocide pumps are functioning per controller settings;
verify chemical is dosed only per specification.
6. Submit a service report describing any errors/causes and corrective action taken.
• 9.3.3 Corrosion Coupon Program (every 90 days)
• Monitor and change mild-steel and copper corrosion coupons every 90 days; send used coupons to the laboratory for analysis.
• Provide a written coupon corrosion-test report to the COR within fourteen (14) calendar days after analysis, comparing results against the control limits in Section 6.2.3.
9.4 Detailed Tasks — Potable (Domestic) Water Treatment
• 9.4.1 Quarterly
1. Check and record pressures and chemical levels; replace chemical dosing detection probes.
2. Review daily logs for trends; check chemical levels in addition tanks; adjust and clean tanks as necessary; check the system for leakage and all tubing for tightness.
3. Inspect and clean metering pumps (diaphragm, seepage at vent hole, discharge tubing, watertightness, correct feed, electrical connections); replace pH/chlorine sensors as applicable, clean filters/flow cell/fittings, and calibrate new sensors.
4. Test unit safety functions (alarm relay, flow sensor/controller stop); wipe down the unit;
verify maintenance records; check total & free chlorine and pH in all domestic tanks.
• 9.4.2 Semi-Annually — Booster Pumps
1. Perform lockout/tagout; schedule the outage with operating personnel; follow site and manufacturer safety procedures.
2. Clean and inspect the pump (casing, coupling, motor); inspect wiring/motor/controls for overheating, broken insulation, loose/corroded connections, damaged conduit; check for leaks and coupling alignment/base-plate bolts.
3. Lubricate pump/motor as applicable (use motor-rated grease; do not over-grease; do not use pump grease in the motor); conduct an operational test; megger the motor and record; check running current and voltage per phase and record.
• 9.4.3 Annually — Potable System (in addition to quarterly)
1. Cycle the backwash flow controller and verify proper operation; evaluate media for replacement; check/flush softening; check and adjust dosage/metering.
2. Measure and adjust water hardness to target; measure conductivity, pH, and pressures;
check brine density, float control, and automatic fill valve; inspect softener/brine tank for corrosion and repair; lubricate valves/motors; check wiring and phasing.
3. Have treated water tested by a certified laboratory for: pH, alkalinity, aluminum, calcium, copper, bromide, fluoride, nitrite, nitrate, orthophosphate, silica, strontium, iron, manganese, lead, magnesium, sodium, chloride, total hardness, TDS, turbidity, free chlorine, coliform bacteria, HPC, and temperature.
4. Controllers (chlorination, R/O, pH, corrosion inhibitor) and pumps (circulation, well):
clean/inspect, check line/load connections and control wiring for tightness, verify timers/clocks, energize and confirm each controlled circuit, replace burned-out pilot lights, evaluate UPS/battery backup.
5. Submersible/well pumps: inspect wiring, verify capacity/pressure, measure current and voltage vs. nameplate, megger the motor.
• 9.4.4 Water Wells (where present)
1. Inspect well-head casing, cover/cap, and sanitary seal for cracks, cleanliness, and watertightness; verify no contamination sources are stored nearby and ground slopes away
≥ 15 ft; check backflow preventers/anti-siphon devices and provide annual backflow certification.
2. Sample and send to a certified laboratory for chemical/physical analysis (pH, alkalinity, TDS, turbidity, iron, manganese, nitrate, nitrite, total hardness, ammonia) and bacteriological analysis (total coliform, fecal coliform, E. coli, HPC).
• 9.4.5 Water Tanks with Controls (above and underground)
1. Perform lockout/tagout and schedule the outage; examine visible interior (fittings, hatches, ladders, manholes) for corrosion and correct; clean/test/inspect sight glasses, valves, fittings, drains, and controls; clean and inspect the tank level control panel and verify all alarm/control/communication circuits and mechanical level devices.
2. Check for contamination (insects, debris) and notify Post if found; drain, clean, and disinfect tanks per current U.S. Department of State guidelines (ALDAC 137958) and AWWA C652; return the system to service.
9.5 Detailed Tasks — Swimming Pool Water Treatment
1. At each visit: test and balance sanitizer, pH, total alkalinity, calcium hardness, and cyanuric acid (where used); verify the automated chlorine/acid controller calibration, feed rates, and chemical tank levels; verify salt-cell operation and salinity where a salt system is installed.
2. Inspect and verify filtration and backwash operation; inspect circulation pump, strainer basket, and heater; confirm flow and pressure readings and report deficiencies.
3. Verify water clarity and safety; confirm test-kit reagents and required consumables are on hand; document readings and corrective actions in the service report.
4. Perform a full seasonal service and water-quality certification at least annually (or at season start), coordinated with the COR.
9.6 Hours of Work
The Contractor shall schedule all preventive maintenance during normal working hours (Sunday– Thursday), including periodic maintenance that may be required on Saturdays, except on regular or special public holidays when the compound is closed, or as otherwise agreed with the U.S.
Embassy before commencement. Where a manufacturer's maintenance specification conflicts with this SOW, the more stringent manufacturer specification prevails.
10. Deliverables and Reporting
All reports shall be in English (with SDS and cut sheets additionally in Arabic), submitted electronically to the COR, and shall become USG property. At a minimum, the Contractor shall deliver:
Deliverable Due Content
Baseline / Survey Report Within 30 days of NTP
Verified volumes, equipment inventory, source-water RTW analysis
Deliverable Due Content (LSI/RSI/CCPP), proposed chemical program & control ranges
Technician resumes & training records
Within 20 days of NTP
Qualifications, certifications, safety training
Chemical submittals Before use Manufacturer specs, composition, SDS/MSDS, cut sheets (English & Arabic)
Weekly analysis response ≤ 24 h of receiving Post results
Technical analysis and dosing/operations direction
Monthly service report ≤ 3 business days after each visit
On-site & lab test results, system status, corrective actions, recommendations, photos, media
Corrosion coupon report ≤ 14 days after analysis
Mild-steel & copper corrosion rates vs.
limits
Legionella / WMP monitoring Per WMP schedule
Dip-slide & culture results, exceedances, corrective actions, WMP updates
Certified potable & well analysis Annually Full chemical/physical & bacteriological panel
Annual program review Annually Trend analysis, asset condition, water/chemical efficiency, next-year recommendations
Training / familiarization records
After each session
Attendance, topics, materials (16 h/yr, English & Arabic)
11. Performance Criteria and Monitoring The objective of this contract is to provide, throughout its term, a professional level of service delivering: U.S. Embassy satisfaction with water-treatment maintenance and prompt reaction to changing operational requirements; compliance with applicable statutory and regulatory provisions; best-in-class industry practice; risk reduction; preservation of asset value; and reduced operating cost. The Contractor shall monitor its own performance against the criteria below and provide reports when required by the U.S. Embassy; the U.S. Embassy may reject any aspect of the services that fails to comply with the contract or the Contractor's quality system at any time.
Performance Objective Standard Acceptable Level
Water chemistry in range All loops maintained within Section 6 parameters
≥ 95% of tests in range
Performance Objective Standard Acceptable Level
Responsiveness Analysis & dosing direction after Post results Within 24 hours
Visit schedule Monthly on-site visits performed 12 visits/year; no missed visit
Reporting timeliness Service reports after each visit Within 3 business days
Legionella control Cooling-tower monitoring & corrective action per WMP
Within control limits;
timely remediation
Potable compliance Meets 40 CFR 141–143 No unresolved exceedance
Corrosion/scale Coupon & deposition results Within Section 6 limits
Safety Zero preventable incidents; PPE & SDS compliance Full compliance
12. Training and Familiarization The Contractor shall provide sixteen (16) hours of familiarization training annually, in both English and Arabic, to acquaint Post operators with the necessary water-treatment tests, the control ranges for each chemical, safe handling of equipment and chemicals, and new water-treatment procedures and technologies. Training content and schedule shall be submitted for COR approval, and training records delivered after each session. The Contractor shall also assure that Post water-treatment personnel understand the proper operation and maintenance of the treatment equipment and shall correct deficiencies found during on-site familiarization.
13. Access to Government Buildings and Security Requirements
• Designated representative. The Contractor shall designate a representative to supervise its technicians and serve as liaison with the U.S. Embassy. Contractor employees shall be on-site only for contractual duties and shall access system-dedicated rooms only with the specific permission of the Facility Manager, CO, or COR, with or without security escort as directed.
• Personnel security. The U.S. Embassy reserves the right to deny access to any individual.
The Contractor shall provide names, biographic data, and police clearances for all personnel prior to their use on this contract.
• Contractor identification. Personnel shall identify themselves as non-federal (contractor) employees in meetings, e-mail signature blocks, and directories, and shall not use Department of State logos on business cards.
14. Standards of Conduct
• Contractor employees shall maintain satisfactory standards of competency, conduct, cleanliness, appearance, and integrity, and shall reflect credit on themselves, their employer, and the U.S. Government; the Embassy may direct removal of any employee for failure to comply, and the Contractor shall immediately replace such employee at no additional cost.
• Employees shall wear clean, neat, complete uniforms on duty; the Contractor bears the cost of purchasing, cleaning, and repairing uniforms and personal equipment.
• Neglect of duties (including sleeping on duty, unreasonable delays, conducting personal affairs on duty, or refusing to cooperate in worksite security) shall not be condoned.
• Employees shall not possess, sell, consume, or be under the influence of intoxicants, drugs, or similar substances while on duty.
15. Observance of Legal Holidays The Contractor shall not perform routine work on days observed as holidays by the Department of State at Post, except as agreed with the COR. When the Department grants administrative leave to Government employees, assigned contractor personnel in Government facilities are dismissed accordingly, provided the Contractor continues to furnish sufficient personnel for round-the-clock or scheduled critical tasks. Holiday work carries no premium compensation unless authorized elsewhere in the contract.
16. Contract Administration, Invoicing and Clauses
16.1 Invoicing and Payment
This is a firm-fixed-price contract. The Contractor should expect payment thirty (30) days after completion of service/delivery or thirty (30) days after receipt of a proper invoice at the Embassy's payment office, whichever is later. Invoices shall be submitted in PDF to the Financial Management Office (FMO) and shall include: the business name and invoice date; a description (in English) of services provided and dates of service; the Purchase Order number; payment terms including discounts; the name, title, telephone, and address of the responsible employee who can answer invoice questions; and bank information.
16.2 Incorporated Clauses
The FAR and DOSAR terms and conditions are incorporated by reference and apply to this contract, including but not limited to FAR 52.212-4 (Contract Terms and Conditions — Commercial Items), 52.212-5, 52.217-8 (Option to Extend Services), 52.217-9 (Option to Extend the Term of the Contract), 52.228-3/5 (insurance), 52.229-6 (Foreign Fixed-Price Contracts), and the DOSAR clauses for Contractor Identification, Payment Schedule and Invoice Submission (652.232-70), Observance of Legal Holidays and Administrative Leave (652.237-72), Contracting Officer's Representative (652.242-70), and Authorization and Performance (652.242-73).