Plans.pdf
PDF 11 MB Posted
- Solicitation number
- 0000040216
About this file
This is a set of construction plans and specifications for a state project involving the California Department of Veterans Affairs and the California Department of General Services' Real Estate Services Division. The project involves the replacement of two 245-ton chillers and four associated pumps at the Veterans Home of California in Chula Vista, located at 700 E. Naples Court, Chula Vista, California 91911. The scope of work includes removing and replacing existing chillers CH-1 and CH-2, removing and replacing pumps P-1 through P-4, removing and replacing two variable frequency drives serving P-3 and P-4, and providing a temporary air-cooled chiller system to maintain building operations during construction. The contractor is responsible for providing chilled water service without interruption throughout the project duration, coordinating with facility management for temporary equipment placement and connection, and developing a phasing plan for utility shutdowns that minimizes downtime. The project is exempt from Department of State Architect accessibility compliance review under DSA IR 11B-6 but must comply with all applicable building codes. The Office of the State Fire Marshal approved the plans on August 4, 2026 (OSFM Permit 25-S-0426-C-NW), with plans dated June 25, 2026.
The project requires compliance with 2022 California Building Standards, including seismic protection requirements per CBC sections 1613A and ASCE 7-16. All new piping, conduit, ductwork, and equipment must be seismically braced using OSHPD pre-approved bracing systems from manufacturers including ISAT, Mason Industries, or B-Line/Tolco. The contractor must submit shop drawings for approval at least four weeks prior to installation and obtain HCAI peer review for the temporary air-cooled chiller trailer and anchorage prior to installation. The temporary chiller is specified as a Carrier 30XA352 or equivalent with 300-ton capacity, 720 GPM, 44°F leaving water temperature, and 460V/3PH/60HZ power requirements. All new chillers and pumps will use refrigerant R-513a, requiring replacement of refrigeration monitoring devices and sensors compatible with this refrigerant. The project includes commissioning by an independent contractor with no less than five years of experience, covering chiller system validation, pump balancing, VFD operation, sensor calibration, and water balance verification. Cooling and heating equipment must be restored to power within sufficient time to maintain building temperatures between 71°F and 81°F throughout construction phases.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Bid_Package_Documents.pdf | ||
| Project_Manual.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T0.1
TITLE SHEET
RF RF RN
E0.1
E0.2
E1.1
E2.0
E2.1
GENERAL NOTES, SYMBOL LIST, ABBREVIATIONS,
DRAWING LIST AND DEFINITION
SITE PLAN - ELECTRICAL TEMPORARY AIR COOLED
CHILLER PLAN
DEMOLITION SINGLE LINE DIAGRAM
NEW WORK SINGLE LINE DIAGRAM
ELECTRICAL DEMOLITION PLAN - BUILDING A
ELECTRICAL NEW WORK PLAN - BUILDING A
TITLE SHEET
SEISMIC PROTECTION NOTES AND ADDITIONAL APPLICABLE
CODES AND STANDARDS
CALIFORNIA DEPARTMENT OF
VETERANS AFFAIRS
VETERANS HOME OF CALIFORNIA, CHULA VISTA
700 E. NAPLES CT. CHULA VISTA, CALIFORNIA 91911
TWO 245 TON CHILLER AND PUMP REPLACEMENT
LOCATION MAP DRAWING INDEX
PROJECT DIRECTORY & CONTACT NAME
SCOPE OF WORKVICINITY MAP
APPLICABLE CODES AND STANDARDS
MECHANICAL COVER SHEET
MECHANICAL SCHEDULE
SITE PLAN
MECHANICAL DEMOLITION PLAN - BUILDING A
SITE PLAN - TEMPORARY AIR COOLED CHILLER PLAN
MECHANICAL NEW WORK PLAN - BUILDING A
ENLARGED TEMPORARY AIR COOLED CHILLER PLAN
TEMPORARY AIR COOLED CHILLER PLAN - PHOTOS
MECHANICAL DETAILS - PIPING DIAGRAM
MECHANICAL DETAILS - CHILLER
MECHANICAL DETAILS - CHILLER
CONTROL COVER SHEET
CONTROLS DIAGRAM - CHILLER PLANT
CONTROLS DIAGRAM - EXISTING
M0.1
M0.2
M1.0
M1.1
M2.0
M2.1
M2.2
M2.3
M3.1
M3.2
M3.3
M4.1
M4.2
M4.3
1. REMOVE AND REPLACE EXISTING TWO 245-TON CHILLERS (CH-1 AND CH-2)
LOCATED INSIDE CHILLER ROOM A237 INCLUDING POWER SOURCES.
NOTE: THE (2) 245 TON CHILLER DOES NOT CURRENTLY MEET HCAI PIN 74
AND WILL NOT BE PART OF THIS PROJECT. LETTER IS PROVIDED BY
CAPITAL THAT THEY ARE AWARE OF THE NON-COMPLIANT AND WILL
APPROACH THE ISSUE TO ADDRESS HCAI PIN 74 COMPLIANCE.
2. REMOVE AND REPLACE FOUR EXISTING PUMPS (P-1, P-2, P-3, P-4) LOCATED
INSIDE CHILLER ROOM A237 INCLUDING POWER SOURCES.
3. REMOVE AND REPLACE TWO VARIABLE FREQUENCY DRIVE. SERVING P-3
AND P-4 LOCATED INSIDE CHILLER ROOM A237.
4. CONTRACTOR TO PROVIDE TEMPORARY CHILLED WATER DURING
CONSTRUCTION IN REPLACING THE CHILLERS AND PUMPS FOR
NON-INTERRUPTION OF BUILDING OPERATION. CONTRACTOR SHALL
COORDINATE WITH THE OWNER FOR THE LOCATION AND SET UP OF THE
TEMPORARY AIR COOLED CHILLER, PUMPS, VALVES, PIPING, AND POWER
FOR THE DURATION OF CONSTRUCTION. REFER TO DGS DEFERRED
APPROVAL ON T0.1 FOR SUBMITTAL OF TEMPORARY CHILLED WATER.
5. PROVIDE PHASING PLAN FOR UTILITY SHUTDOWN. MINIMIZE DOWNTIME.
PHASING PLAN SHALL BE APPROVED BY DGS.
DSA EXEMPTION NOTES
1. THIS PROJECT IS UNDERTAKEN SOLELY FOR THE PURPOSE OF UPGRADING THE CHILLERS
AT THE PROJECT SITE. THIS PROJECT IS EXEMPT BY ACCESSIBILITY CODE PROVISION
AND DOES NOT REQUIRE DSA ACCESS COMPLIANCE REVIEW OR APPROVAL UNDER DSA
IR 11B-6. THIS INCLUDES MECHANICAL ONLY PROJECTS THAT CONTAIN INCIDENTAL
STRUCTURAL COMPONENTS REQUIRED SOLELY FOR THE PURPOSE OF PERFORMING
MECHANICAL ONLY WORK. HOWEVER, THE COMPLIANCE WITH BUILDING CODE IS STILL
REQUIRED AND PROVIDED.
GENERAL
MECHANICAL
ELECTRICAL
1. TEMPORARY AIR COOLED CHILLER TRAILER, ANCHORAGE AND
SUPPORTS SHALL BE SUBMITTED BY CONTRACTOR FOR HCAI PEER
REVIEW PRIOR TO INSTALLATION, ALL ITEMS SHALL BE SEISMICALLY
RESTRAINED AND INSTALLED PER 2022 CBC REQUIREMENTS. REFER
TO TEMPORARY AIR COOLED CHILLER NOTES ON SHEET T0.2 FOR
ADDITIONAL INFORMATION.
2. CONTRACTOR SHALL HIRE HCAI PREAPPROVED OPM
MANUFACTURER TO PROVIDE PIPE AND CONDUIT SUPPORT FOR
SEISMIC BRACING DESIGN AND DETAILS FOR ALL NEW WORK.
HCAI DEFERRED APPROVALS
N M L K J I H G
Checked
Vault File Number
DSA Building Number
Reference North Sheet Scale
Sheet Number
Work Order
Designed
Sheet Title
Supervisor
File Date
Drawn
DescriptionNo. Date
Issue:
F E D C B
A
-06/25/2026
C op yr ig ht
5, C al ifo rn ia
D ep ar tm en t o f G en er al
S er vi ce s
- R ea l E st at e Se rv ic es D iv is io n
DGS PROJECT # DGS00000011694
SFM FAC #01-37-41-0048-00001
JCCA#: 24590-1
FI
LE
: L :\2
4\
0-
Tw o
5-
To n
C hi lle rs
, V et er an s H om e, C hu la V is ta
\C
AD
\2
1_
T0 1.
dw g
D
AT
E/
TI
M E:
Ju n
, 0 8:
AM
JCCA
TWO 245-TON
CHILLER AND PUMP
REPLACEMENT
VETERANS HOME OF CALIFORNIA
700 E. NAPLES CT.
CHULA VISTA, CA 91911
Project
XX-X-XXXX-X-XX
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
RN
Department of General Services State of California
Real Estate Services Division
Project Management And Development Branch
DATE SIGNED: 11/24/2025
4TH
AVE
BR
O
AD
W
AY
BR
O
AD
W
AY
3R D
AVE
2N
D
AVE
HILLTOP DR
G ST
H ST
J ST
NAPLES ST
PALOMAR ST
MOSS ST
C ST
D ST
E ST
MELROSE AVE
ORANGE AVE
MAIN ST
L ST
OXFORD ST
BR
AN
D
YW
IN
E
AV
E
J ST
H ST
TELEGRAPHCANTON RD
PALOMAR
ST
NAPLES
ST
SAN
DIEGO
BAY
CHULA
VISTA
PROJECT
LOCATION
40' 40'
40' 40'40'40'40'40'40'40'
40' 40'
60'60'60'60'60'60'60'60'60' 40'
PROJECT AREA
MEDICAL CENTER COURT
EAST NAPLES ST.
M
ED
IC
AL
C
EN
TE
R
D R
E
C
D B
A-1
A-3
A-2
F
A-4 A-5
NOT TO SCALE
STATE FIRE MARSHALL SPECIAL INSPECTIONS
A MINIMUM OF 72 HOURS NOTICE WILL BE PROVIDED TO THE STATE FIRE MARSHALL WHEN
SCHEDULING ANY TEST OR INSPECTIONS.
FIRE SAFETY DURING CONSTRUCTION
1. CONTRACTOR SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTER 33 - FIRE SAFETY
DURING CONSTRUCTION OF THE 2022 CALIFORNIA FIRE CODE.
1. SEE MECHANICAL SHEETS AND T0.2 FOR SEISMIC NOTES.
2. SEE DEFERRED APPROVAL NOTES THIS SHEET.
SEISMIC NOTES
1. 2022 BUILDING STANDARDS ADMINISTRATIVE CODE, PART 1, TITLE 24 C.C.R.
2. 2022 CALIFORNIA BUILDING CODE (CBC), PART 2, TITLE 24 C.C.R.
(2021 INTERNATIONAL BUILDING CODE & 2022 CALIFORNIA AMENDMENTS)
3. 2022 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 C.C.R.
(2020 NATIONAL ELECTRICAL CODE AND 2022 CALIFORNIA AMENDMENTS)
4. 2022 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 C.C.R.
(2021 UNIFORM MECHANICAL CODE AND 2022 CALIFORNIA AMENDMENTS)
5. 2022 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 C.C.R.
(2021 UNIFORM PLUMBING CODE AND 2022 CALIFORNIA AMENDMENTS)
6. 2022 CALIFORNIA ENERGY CODE (CEC), PART 6, TITLE 24 C.C.R.
7. 2022 CALIFORNIA FIRE CODE, PART 9, TITLE 24 C.C.R.
(2021 INTERNATIONAL FIRE CODE AND 2019 CALIFORNIA AMENDMENTS)
8. 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN), PART 11,
TITLE 24 C.C.R.
9. 2022 CALIFORNIA REFERENCED STANDARDS, PART 12, TITLE 24 C.C.R.
10. TITLE 19 C.C.R., PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS.
11. OSHPD 2 PROJECT.
STRUCTURAL NOTES AND STRUCTURAL DETAILS
MECHANICAL ROOM PLAN
S0.1
S2.1
STRUCTURAL
CONSTRUCTION LOGISTICS
1. CONTRACTOR TO PROVIDE CONSTRUCTION LOGISTICS AND PRESENT TO FACILITY
FOR APPROVAL PRIOR TO START OF WORK. COORDINATE WITH FACILITY.
PREPARED FOR:
DEPARTMENT OF GENERAL SERVICES (DGS)
REAL ESTATE SERVICES DIVISION (RESD)
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
(PMDB)
707 3RD STREET, 4TH FLOOR, MS 504
WEST SACRAMENTO, CA 95605
JETHRO TARN
PROJECT DIRECTOR III
CELL: (279) 799-4113
EMAIL: JETHRO.TARN@DGS.CA.GOV
CALIFORNIA DEPARTMENT OF VETERANS AFFAIRS
1227 O ST
SACRAMENTO, CALIFORNIA 95814
DANIELLE De SILVA, DCMS
FACILITIES AND BUSINESS SERVICES DIVISION
OFFICE: (916) 651-7495
EMAIL: DANIELLE.DESILVA@CALVET.CA.GOV
BETSY VIERRA, ACA
FACILITIES AND BUSINESS SERVICES DIVISION
OFFICE: (916) 503-8040
EMAIL: BETSY.VIERRA@CALVET.CA.GOV
PREPARED BY:
J.C. CHANG & ASSOCIATES, INC.
ENGINEERS, ARCHITECTS AND PLANNERS
385 VAN NESS AVENUE, SUITE 208
TORRANCE, CALIFORNIA 90501
PHONE : (310) 212-7644
MECHANICAL ENGINEER OF RECORD
ROBERT NOLAN
LIC. NO. 31684
385 VAN NESS AVE. #208
TORRANCE, CALIFORNIA 90501
ELECTRICAL ENGINEER OF RECORD
HECTOR LACSA
LIC. NO. E18399
385 VAN NESS AVE. #208
TORRANCE, CALIFORNIA 90501
STRUCTURAL ENGINEER OF RECORD
ROBERT ONISHI
LIC. NO. 3705
385 VAN NESS AVE. #208
TORRANCE, CALIFORNIA 90501
CONTROLS INTEGRATION
1. SEE CONTROLS INTEGRATION NOTE ON SHEET M0.2
E1.0
OSFM PERMIT NUMBER: 25-S-0426-C-NW
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
7/15/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-0426
ISSUE DATE: AUGUST 4, 2026
T0.2
RF RF RN
ADDITIONAL APPLICABLE CODES & STANDARDS FOR CDVA PROJECTSSEISMIC PROTECTION NOTES
OTHER AGENCY REQUIREMENTS
1. DEPARTMENT OF GENERAL SERVICES, DIVISION OF STATE ARCHITECT,
ACCESSIBILITY REQUIREMENTS.
2. DEPARTMENT OF GENERAL SERVICES- BUILDING STANDARDS COMMISSION,
DIVISION OF STATE ARCHITECT, OSHPD CERTIFICATION, CALIFORNIA
ENVIRONMENTAL QUALITY ACT DOCUMENT.
3. STATE FIRE MARSHALL- AUTHORITY HAVING JURISDICTION ON STATE
CONSTRUCTION PROJECTS, ANNUAL INSPECTIONS, ENFORCEMENT OF THE
CALIFORNIA FIRE CODE AND THE CALIFORNIA BUILDING STANDARDS CODE.
4. CALIFORNIA DIVISION OF OCCUPATIONAL SAFETY AND HEALTH (CAL/OSHA)-
REGULATES JOB SAFETY.
CODES
1. 2022 CALIFORNIA HISTORICAL BUILDING CODE, PART 8, TITLE 24 CCR (INCLUDED IN PART 10).
2. 2022 CALIFORNIA EXISTING BUILDING CODE, PART 10, TITLE 24 CCR (INCLUDED IN PART 10).
3. HEALTH AND SAFETY CODE SECTIONS 1250 ET SEQ.- LICENSING PROVISIONS FOR
HEALTH FACILITIES.
4. HEALTH AND SAFETY CODE SECTION 1418- DEFINES LONG-TERM FACILITIES.
5. HEALTH AND SAFETY CODE SECTIONS 16000-16023- ESSENTIAL SERVICES BUILDINGS.
6. HEALTH AND SAFETY CODE SECTION 17922- RULES AND REGULATIONS.
7. HEALTH AND SAFETY CODE SECTION 17960- REGULATION OF BUILDINGS USED FOR
HUMAN HABITAT.
8. HEALTH AND SAFETY CODE SECTION 18909- DEFINES "BUILDING STANDARD".
9. HEALTH AND SAFETY CODE SECTIONS 18950-18961- STATE HISTORICAL.
10. CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 8.
11. CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 9.
12. CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 17.
13. CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 19.
14. CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 22.
15. CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 23.
16. CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24.
17. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 101 LIFE SAFETY CODE, CURRENT
VERSION.
18. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 99 HEALTH CARE FACILITIES CODE.
19. HEALTH AND SAFETY CODE 17960.
20. GOVERNMENT CODE SECTION 4450- ACCESS TO PUBLIC BUILDINGS BY PHYSICALLY
HANDICAPPED PERSONS.
21. GOVERNMENT CODE SECTION 4465- DISABILITY ACCESS AND EDUCATION.
22. GOVERNMENT CODE SECTION 8875.2- LOCAL BUILDING DEPARTMENTS.
23. GOVERNMENT CODE SECTION 14680- RELOCATION OR REMOVAL OF PUBLIC UTILITY
FACILITIES WHEN A STATE STRUCTURE IS TO BE CONSTRUCTED.
24. GOVERNMENT CODE SECTION 14963- FIRE AND LIFE SAFETY.
25. GOVERNMENT CODE SECTION 14685- CALIFORNIA HIGHWAY PATROL REGULATIONS FOR
PROTECTION OF STATE EMPLOYEES, PROPERTIES, BUILDINGS AND GROUNDS, AND
OCCUPANTS OF STATE PROPERTIES.
26. PUBLIC RESOURCES CODE SECTIONS 5024, 5024.1, 5024.5- PROJECT COMPLIANCE WITH
FEDERAL AND STATE HISTORIC PRESERVATION LAWS.
27. PATIENT AND STAFF SAFETY (SB1299) OSHA.
28. AMERICANS WITH DISABILITY ACT (ADA).
29. OFFICE OF STATEWIDE HEALTH PLANNING AND DEVELOPMENT (OSHPD), OSHPD 2.
SEISMIC PROTECTION
NOTES & ADDITIONAL
APPLICABLE CODES &
STANDARDS
1. CONTRACTOR SHALL SUBMIT TEMPORARY AIR COOLED CHILLER SHOP
DRAWING SUBMITTAL FOR APPROVAL.
2. TEMPORARY AIR COOLED CHILLER SHALL BE INSTALLED ADJACENT TO THE
EXISTING COOLING TOWER OUTSIDE-BUILDING IN LOCATION THAT DOES NOT
IMPEDE FIRE TRUCK ACCESS TO BUILDING AND AREA. VERIFY AND
COORDINATE IN FIELD PRIOR TO START OF WORK.
3. TEMPORARY AIR COOLED CHILLER SHALL BE SEISMICALLY ANCHORED TO
FLATBED TRAILER.
4. PROVIDE K-RAILS AND STEEL CABLES FOR TRAILER TIE DOWN.
5. PROVIDE S/O CHORDS AND CONNECT TO PENTHOUSE ELECTRICAL PANEL TO
EXISTING SPARE CIRCUIT DESIGNATED FOR TEMPORARY AIR COOLED
CHILLER.
6. PROVIDE CHILLER WATER FLEX PIPING SIZED FOR TEMPORARY AIR COOLED
CHILLER TONNAGE AND FLOW AND CONNECT TO EXISTING BUTTERFLY
VALVES LOCATED IN COOLING CONDENSER-BUILDING FOR TEMPORARY AIR
COOLED CHILLER CONNECT. VERIFY AND COORDINATE IN FIELD PRIOR TO
START OF WORK.
7. ENSURE TO ROUTE FLEX PIPING AS NOT TO BLOCK ANY ENTRANCE WAY.
COORDINATE WITH FACILITY FOR THE PREFERRED ROUTING OF THE CHILLER
WATER FLEX PIPING.
8. CONTRACTOR SHALL PROVIDE NECESSARY PROTECTION TO THE
TEMPORARY CHILLER FLEX PIPING TO AVOID SWEATING.
9. SEE SHEET M2.2 FOR TEMPORARY CHILLER PLAN.
10. COOLING AND HEATING EQUIPMENT WILL BE RESTORED TO POWER WITHIN
SUFFICIENT TIME TO MAINTAIN TEMPERATURE BETWEEN 71° - 81°F.
TEMPORARY AIR COOLED CHILLER
N M L K J I H G
Checked
Vault File Number
DSA Building Number
Reference North Sheet Scale
Sheet Number
Work Order
Designed
Sheet Title
Supervisor
File Date
Drawn
DescriptionNo. Date
Issue:
F E D C B
A
-06/25/2026
C op yr ig ht
5, C al ifo rn ia
D ep ar tm en t o f G en er al
S er vi ce s
- R ea l E st at e Se rv ic es D iv is io n
DGS PROJECT # DGS00000011694
SFM FAC #01-37-41-0048-00001
JCCA#: 24590-1
FI
LE
: L :\2
4\
0-
Tw o
5-
To n
C hi lle rs
, V et er an s H om e, C hu la V is ta
\C
AD
\2
1_
T0 2.
dw g
D
AT
E/
TI
M E:
Ju n
, 0 9:
AM
JCCA
TWO 245-TON
CHILLER AND PUMP
REPLACEMENT
VETERANS HOME OF CALIFORNIA
700 E. NAPLES CT.
CHULA VISTA, CA 91911
Project
XX-X-XXXX-X-XX
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
RN
Department of General Services State of California
Real Estate Services Division
Project Management And Development Branch
DATE SIGNED: 11/24/2025
1. ONLY ONE OSHPD PRE-APPROVED BRACING SYSTEM (OPM) SHALL BE USED FOR A
RUN OF PIPE, DUCT, OR CONDUIT. ANY SUBSTITUTION OF ANY COMPONENT OF A
PRE-APPROVED BRACING SYSTEM SHALL REQUIRE CDVA PROJECT MANAGER
REVIEW AND APPROVAL. COMPONENTS OF TWO OR MORE BRACING SYSTEMS
SHALL NOT BE MIXED. A COPY OF THE CHOSEN BRACING SYSTEM(S) INSTALLATION
GUIDE/MANUAL SHALL BE ON THE JOBSITE PRIOR TO STARTING THE INSTALLATION
OF HANGERS AND/OR BRACES. IT IS THE CONTRACTOR'S RESPONSIBILITY TO
OBTAIN COPIES OF OSHPD PRE-APPROVALS AND FURNISH THE OWNER WITH A
COPY OF EACH.
2. IN NEW WORK AREAS AND LIMITED NEW WORK AREAS ALL NEW PIPING, CONDUIT,
DUCTWORK, EQUIPMENT, PANELS, ETC. SHALL BE SEISMICALLY BRACED (SEE NOTE
4 BELOW).
3. SEISMIC ANCHORAGE OF ALL NEW PIPING, CONDUIT, DUCTWORK, EQUIPMENT,
PANELS, ETC. SHALL BE BY ONE OF THE FOLLOWING MANUFACTURERS IN
ACCORDANCE WITH THE 2022 CBC AND THE LATEST ISSUE OF "ENGINEERED
SEISMIC BRACING OF SUSPENDED UTILITIES" AS PUBLISHED BY THE
INTERNATIONAL SEISMIC APPLICATION TECHNOLOGY (ISAT). APPROVED
MANUFACTURERS INCLUDE: ISAT OPM-0403-13, MASON INDUSTRIES OPM-0043-13,
B-LINE/TOLCO OPM-0052-13, OR EQUAL.
4. DEFERRED APPROVAL - LAYOUT DRAWINGS, SHOWING THE BRACING/SUPPORT
LOCATIONS AND REFERENCES TO DETAILS FROM THE RELEVANT OSHPD
PRE-APPROVALS FOR PIPING/DUCTS/CONDUITS EXCEPT FIRE SPRINKLERS, NEED
TO BE SUBMITTED FOR USE BY THE INSPECTOR OF RECORD (IOR) (IF APPLICABLE
FOR THIS PROJECT) AND CDVA PROJECT MANAGER. THE LAYOUT DRAWINGS,
PREPARED PER ASCE 7 CHAPTER 13 AS MODIFIED BY CBC SECTIONS 1613A, NEED
TO BE REVIEWED AND ACCEPTED BY THE EOR (SE AND/OR ME/EE) AND CEG PRIOR
TO STARTING INSTALLATION OF THE BRACING/SUPPORT. IOR (IF APPLICABLE FOR
THIS PROJECT) SHALL ENSURE THE ABOVE REQUIREMENTS ARE SATISFIED.
5. AT LEAST FOUR WEEKS PRIOR TO BEGINNING INSTALLATION, FOUR COPIES OF THE
PLANS SHALL BE SUBMITTED TO THE ARCHITECT OF RECORD WHO WILL SUBMIT
THEM TO THE STRUCTURAL ENGINEER OF RECORD FOR REVIEW AND APPROVAL.
THE PLANS SHALL BE COORDINATED WITH THE PLANS OF THE OTHER TRADES. A
COPY OF THE CHOSEN BRACING SYSTEM INSTALLATION GUIDE/MANUAL SHALL BE
ON THE JOBSITE PRIOR TO STARTING THE INSTALLATION. SEE DEFERRED
APPROVAL NOTES ON ARCHITECTURAL SHEET T0.1.
6. CONTRACTOR SHALL PROVIDE CALCULATIONS AND DETAILS FOR THE SUPPORT
AND BRACING OF ALL PIPES, DUCTS, EQUIPMENT AND CONDUITS. SHOP DRAWINGS
SHALL INCLUDE ALL BRACING AND SUPPORT LOCATIONS AND REFERENCES TO
DETAILS FROM RELEVANT OSHPD PRE-APPROVALS AND SHALL BE SUBMITTED TO
THE IOR (IF APPLICABLE FOR THIS PROJECT) AND CDVA PROJECT MANAGER.
7. EQUIPMENT SUPPORTS AND ANCHORAGE SHALL BE APPROVED BY THE
APPROPRIATE DESIGN PROFESSIONAL OF RECORD AND PRIOR TO INSTALLATION.
THE IOR (IF APPLICABLE FOR THIS PROJECT) SHALL ASSURE THAT THE FIELD
INSTALLATION CONFORMS TO APPROVED SUBMITTED DETAILS.
8. SEISMIC LATERAL FORCE Fp, INCLUDING ap & Rp MUST BE DETERMINED AT EACH
LEVEL OF THE BUILDING BY THE CONTRACTOR'S STRUCTURAL ENGINEER SO THAT
THE BRACING SPACING CAN BE CALCULATED AND SUBMITTED TO THE SEOR FOR
REVIEW.
9. ONCE EXACT LOCATIONS OF ALL CONDUIT HAVE BEEN ESTABLISHED, THE
STRUCTURAL ENGINEER MUST CHECK THE ADEQUACY OF THE SUPPORTING
STRUCTURE TO ENSURE THAT THE ORIGINAL DESIGN IS STILL ADEQUATE. THE
INSPECTOR OF RECORD SHALL ENSURE THAT ALL WORK IS PROPERLY INSTALLED
PER THE APPLICABLE HCAI PRE-APPROVAL.
10. SPECIAL INSPECTION SHALL BE PERFORMED BY SPECIAL INSPECTOR IN
ACCORDANCE WITH CBC 1705A.12.4 FOR SPECIAL SEISMIC CERTIFICATION.
PRE-APPROVED COMPONENT AND SYSTEM LIMITATIONS:
A. SOME PRE-APPROVALS HAVE LIMITATIONS THAT REQUIRE EITHER A DEFERRED
SUBMITTAL COMMENT ON LAYOUT DRAWINGS AND COMPONENT DESIGN OR A
PRE-ENGINEERED DESIGN THAT IS A PART OF THE CONTRACT DOCUMENTS. ALL
OF THE PRE-APPROVED SYSTEMS REQUIRE THAT THE SEISMIC LATERAL FORCE,
Fp, INCLUDING CONSIDERATION OF Ap AND Rp BE DETERMINED AT EACH LEVEL
OF THE BUILDING SO THAT BRACE SPACING AND ANCHORAGE REQUIREMENTS
CAN BE DETERMINED. PROVIDE ALL PARAMETERS REQUIRED TO COMPUTE Fp (e.g. Ap,Rp,Sps,Ip,h AND z AT EACH LEVEL) ON THE SHOP DRAWINGS. THE SEOR
MAY APPROVE SEISMIC LATERAL FORCE COMPUTATIONS SUBMITTED BY THE
CONTRACTOR.
PRE-APPROVED PIPE, DUCT, AND CONDUIT BRACING:
A. SHOP DRAWINGS OF THE SUPPORT AND BRACING SYSTEMS PER THE
PRE-APPROVAL SHALL BE SUBMITTED TO THE DISCIPLINE IN RESPONSIBLE
CHARGE OF THE PROJECT FOR REVIEW TO VERIFY THAT THE DETAILS ARE IN
CONFORMANCE WITH ALL CODE REQUIREMENTS. THE SHOP DRAWINGS SHALL
BE IN ACCORDANCE WITH ASCE 7-16 SECTION 13.6 AS MODIFIED BY THE CBC
2022 SECTION 1613A.
a) THE CONTRACTOR'S STRUCTURAL ENGINEER SHALL FORWARD THE
ANCHORAGE AND BRACING PLANS (INCLUDING APPROVED CHANGE ORDERS
FOR SUPPLEMENTARY FRAMING WHERE REQUIRED) TO THE STRUCTURAL
ENGINEER OF RECORD (SEOR) WITH A NOTATION INDICATING THAT THE
PLANS HAVE BEEN REVIEWED AND ARE IN GENERAL CONFORMANCE WITH
THE PRE-APPROVAL AND THE DESIGN OF THE PROJECT.
b) A "SHOP DRAWING STAMP" MAY BE USED TO INDICATE COMPLIANCE WITH
THIS REQUIREMENT.
c) THE REGISTERED DESIGN PROFESSIONAL (OTHER THAN SEOR) MAY PROVIDE
THE SHOP DRAWING STAMP FOR SMALL INSTALLATIONS AT THE DISCRETION
OF THE SEOR.
B. THE CONTRACTOR'S STRUCTURAL ENGINEER SHALL DESIGN ANY
SUPPLEMENTARY FRAMING THAT IS NEEDED TO RESIST THE LOADS, MAINTAIN
STABILITY AND/OR IS REQUIRED FOR INSTALLATION OF PRE-APPROVED SYSTEM.
THE SUPPLEMENTARY FRAMING SHALL BE SUBMITTED TO THE SEOR PRIOR TO
CONSTRUCTION FOR REVIEW.
C. THE SHOP DRAWINGS (WITH THE SHOP DRAWING STAMP) SHALL BE SUBMITTED
TO THE SEOR TO REVIEW THE Fp FOR PRE-APPROVED SYSTEM.
D. THE SHOP DRAWINGS (WITH THE SHOP DRAWING STAMP) SHALL BE KEPT ON
THE JOBSITE AND CAN THEN BE USED FOR INSTALLATION OF THE SUPPORT AND
BRACING.
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
7/15/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
N M L K J I H G
F E D C B
A
F
IL
E : O
:\J O
B F
O
LD
E R
\C al
V et a ka
V et er an s H om e\
V et er an s H o m e C hu la
V is ta \V et er an s
H om e of
C A
C hu la V is ta
S 0.
1.
dw g D
A T
E /T
IM
E
: 2
S e p
, 0
3:
P M
DSA STAMP
AS SHOWN
S0.1
STRUCTURAL NOTES &
STRUCTURAL DETAILS
Checked
Vault File Number
DSA Building Number
Reference North Sheet Scale
Sheet Number
Work Order
Designed
Sheet Title
Supervisor
File Date
Drawn
DescriptionNo. Date
Issue:
C op yr ig ht
5, C al ifo rn ia
D ep ar tm en t o f G en er al
S er vi ce s
R ea l E st at e
S er vi ce s D iv is io n
SFM FAC #01-37-41-0048-00001
JCCA#: 24590-1
TWO 245-TON
CHILLER AND PUMP
REPLACEMENT
VETERANS HOME OF CALIFORNIA
700 E. NAPLES CT.
CHULA VISTA, CA 91911
Project
XX-X-XXXX-X-XX
RN
Department of General Services State of California
Real Estate Services Division
DATE SIGNED: 11/24/2025
06/25/2026
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
7/15/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
N M L K J I H G
F E D C B
A
F
IL
E : O
:\J O
B F
O
LD
E R
\C al
V et a ka
V et er an s H om e\
V et er an s H o m e C hu la
V is ta \V et er an s
H om e of
C A
C hu la V is ta
S 2.
1.
dw g D
A T
E /T
IM
E
: 2
S e p
, 0
3:
P M
MECHANICAL ROOM
PLAN
DSA STAMP
AS SHOWN
S2.1
Checked
Vault File Number
DSA Building Number
Reference North Sheet Scale
Sheet Number
Work Order
Designed
Sheet Title
Supervisor
File Date
Drawn
DescriptionNo. Date
Issue:
C op yr ig ht
5, C al ifo rn ia
D ep ar tm en t o f G en er al
S er vi ce s
R ea l E st at e
S er vi ce s D iv is io n
JCCA#: 24590-1
TWO 245-TON
CHILLER AND PUMP
REPLACEMENT
VETERANS HOME OF CALIFORNIA
700 E. NAPLES CT.
CHULA VISTA, CA 91911
Project
XX-X-XXXX-X-XX
RN
SFM FAC #01-37-41-0048-00001
Department of General Services State of California
Real Estate Services Division
DATE SIGNED: 11/24/2025
06/25/2026
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
7/15/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
M0.1
MECHANICAL COVER
SHEET
N M L K J I H G
Checked
Vault File Number
DSA Building Number
Reference North Sheet Scale
Sheet Number
Work Order
Designed
Sheet Title
Supervisor
File Date
Drawn
DescriptionNo. Date
Issue:
F E D C B
A
-06/25/2026
C op yr ig ht
5, C al ifo rn ia
D ep ar tm en t o f G en er al
S er vi ce s
- R ea l E st at e Se rv ic es D iv is io n
DGS PROJECT # DGS00000011694
SFM FAC #01-37-41-0048-00001
JCCA#: 24590-1
FI
LE
: L :\2
4\
0-
Tw o
5-
To n
C hi lle rs
, V et er an s H om e, C hu la V is ta
\C
AD
\2
1_
M
.d w g D
AT
E/
TI
M
E:
Ju n
, 0
8:
AM
JCCA
TWO 245-TON
CHILLER AND PUMP
REPLACEMENT
VETERANS HOME OF CALIFORNIA
700 E. NAPLES CT.
CHULA VISTA, CA 91911
Project
XX-X-XXXX-X-XX
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
RN
Department of General Services State of California
Real Estate Services Division
Project Management And Development Branch
DATE SIGNED: 11/24/2025
MECHANICAL SYMBOLSPROJECT NOTES
1. REFER TO CONSTRUCTION PHASING NOTE ON SHEET M0.2 FOR MAINTAINING
SYSTEM OPERATIONAL DURING ALL PHASES OF WORK.
2. THE CONTRACTOR SHALL PERFORM THE DEMOLITION AND INSTALLATION OF, AND
PROVIDE, THE CHILLER, CHILLER PUMPS, ASSOCIATED PIPING, AND VARIABLE
FREQUENCY DRIVES.
3. REFER TO SHEET T0.2 NOTE 4 AND HCAI DEFFERED APPROVAL NOTE 2 ON SHEET
T0.1 FOR ALL NEW PIPE AND EQUIPMENT SUPPORTS AND SEISMIC REQUIREMENTS.
4. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE A FULLY FUNCTIONAL
INSTALLATION AND TO INTEGRATE THE NEW WORK TO EXISTING SITE CONDITIONS.
5. CONTRACTOR SHALL PROVIDE SHOP DRAWINGS OF PIPING, CONTROLS AND PIPING
SYSTEMS TO VETERANS HOME OF CALIFORNIA CHULA VISTA FOR APPROVAL PRIOR
TO FABRICATION. CONTRACTOR SHALL PROVIDE EQUIPMENT SUBMITTALS OF ALL
HARDWARE TO BE INSTALLED ON THIS JOB PRIOR TO PURCHASE.
6. CONTRACTOR SHALL LABEL FINAL PIPING INSTALLATION SHOWING DIRECTION OF
FLOW ARROWS AND TYPE OF WATER (E.G. CONDENSER WATER SUPPLY, AND
RETURN, VENT, DRAIN, CHILLER WATER SUPPLY AND RETURN, ETC).
7. CONTRACTOR SHALL PROVIDE ONE (1) HARD COPY AND ONE (1) SOFT COPY OF
EQUIPMENT SUBMITTALS OR SHOP DRAWINGS OF ALL EQUIPMENT SPECIFIED IN
THE MATERIAL LIST AND SCHEDULES ON DRAWINGS M0.2, TO THE STATE FOR
APPROVAL PRIOR TO PURCHASE.
8. CONTRACTOR SHALL PROVIDE ONE (1) HARD COPY AND ONE (1) SOFT COPY OF
OPERATION & MAINTENANCE MANUALS OF ALL EQUIPMENT SPECIFIED.
9. CONTRACTOR SHALL INSTALL NEW PIPING WITH SPOOL SECTIONS TO ALLOW
MAINTENANCE ACCESS TO NEW EQUIPMENT PER EQUIPMENT MANUFACTURER'S
REQUIREMENT AND ALL CODE CLEARANCES.
10. DGS SHALL ENGAGE THE SERVICES OF AN INDEPENDENT COMMISSIONING
CONTRACTOR (NO LESS THAN 5 YEARS OF EXPERIENCE) TO GENERATE AND SUBMIT
A COMMISSIONING PLAN.
11. COMMISSIONING CONTRACTOR WILL PROVIDE COMPREHENSIVE SYSTEM
COMMISSIONING TESTING AND VERIFICATION AND CORRESPONDING COMPLIANCE
REPORT TO INCLUDE THE FOLLOWING:
a) CHILLER UNITS. PERFORM CHILLER SYSTEMS COMMISSIONING PER
MANUFACTURER RECOMMENDATIONS.
b) PUMPS. PERFORM PUMP SYSTEM COMMISSIONING PER MANUFACTURER
RECOMMENDATIONS. THIS SHALL INCLUDE CIRCUIT SETTER ADJUSTMENT AND
FLOW VERIFICATION.
c) CHILLER SYSTEM. VALIDATE EQUIPMENT INSTALLATION AND OPERATION OF
COMPONENTS AT THE SYSTEM LEVEL.
d) VALIDATE CALIBRATION OF SYSTEM SENSORS, THERMOSTATS, METERS, ETC.
e) WATER BALANCE OF THE CHILLED WATER AND CONDENSER WATER LOOPS.
f) COOLING TOWER PUMPS PROVIDING CWS&R SHALL BE BALANCED.
g) VARIABLE FREQUENCY DRIVES. VALIDATE EQUIPMENT INSTALLATION AND
OPERATION OF COMPONENTS AT THE SYSTEM LEVEL.
SMOKE DETECTOR
TYPE OF DIFFUSER OR GRILLE
A
POINT OF DISCONNECTION
SHEET WHERE DETAIL IS DRAWN
ROOM THERMOSTAT
8x8 OR 10ø
DUCT SIZE IN INCHES
T
DETAIL NO.
NEW WORK KEY NOTE
DEMOLITION KEY NOTE
POINT OF CONNECTION
DESCRIPTION
MANUAL DAMPER
MOTORIZED DAMPERM
AIR VOLUME FROM SUPPLY
DIFFUSER OR TO RETURN GRILLE IN
CFM
EXHAUST
CUBIC FEET PER
ABOVE FLOOR
ACCESS DOOR
GALLONS PER MINUTE
GAUGEGA.
GPM
EXH.
A.D.
A.F.
CFM
HHWS
DI
HHWR
HEATING HOT WATER SUPPLY
DEIONIZED WATER SUPPLY
HETING HOT WATER RETURN
DOMESTIC HOT WATER
DOMESTIC COLD WATER
WASTE
DEIONIZED WATER
INDUSTRIAL COLD WATER
CHILLED WATER SUPPLY
CHILLED WATER RETURN
REVERSE OSMOSIS WATER
CONDENSATE DRAIN
FIRE SPRINKLER LINE
COMPRESSED AIR
VENT
DCW
HW
ICW
DI
CHWS
CHWR
W
RO
CD
F
CA
V
MECHANICAL PIPING LEGEND
SYMBOL DESCRIPTION
CONTROL VALVE
M MOTOR ACUATED MODULATING
SYMBOL
S
A
PUMP
P
PRESSURE RELIEF
AUTOMATIC AIR VENT
PETE'S PLUG
PRESSURE GAUGE
THERMOMETER
PNEUMATIC ACTUATED
SOLENOID ACTUATED
PRESSURE REGULATOR
ANGLE VALVE
CHECK VALVE
VENTURI FLOW METER
PLUG VALVE
GAS VALVE
STRAINER
GLOBE VALVE
BUTTERFLY VALVE
DESCRIPTION
GATE VALVE
BALL VALVE
MECHANICAL PIPING SYMBOLS
GENERAL NOTES
MINUTE
SYMBOL
EXISTING(E)
OPENING
PLATFORM
OPNG.
PLAT.
POINT OF DISCONNECTPOD
NEW(N)
MECHANICAL ABBREVIATIONS
SYNTHETIC NATURAL GASSNG
PROPANEP
POINT OF CONNECTIONPOC
CONDENSER WATER SUPPLYCWS
CONDENSER WATER RETURNCWR
CONDENSER WATERCW
SEISMIC NOTES
REFER TO T0.2 FOR ALL RELEVANT SEISMIC REQUIREMENTS.
BUILDING MANAGEMENT SYSTEMB.M.S.
DEMO(D)
1. THE CONTRACTOR SHALL FURNISH ALL LABOR, SUPERVISION, MATERIALS,
EQUIPMENT, TOOLS, TRANSPORTATION, WAREHOUSING, AND ANY OTHER
SERVICES REQUIRED TO COMPLETE THE WORK IN A TIMELY AND EFFICIENT
MANNER.
2. INDIVIDUAL ITEMS OF WORK ARE DETAILED IN THE VARIOUS SECTIONS OF THIS
SCOPE OF WORK, THE ATTACHED DRAWINGS, AND THE NOTES AND LEGENDS
ON THE DRAWINGS. THE CONTRACTOR IS RESPONSIBLE TO COMPLETE THE
REQUIREMENTS FOUND IN ANY OF THE ABOVE.
3. CONTRACTOR BIDS ARE TO BE BASED UPON COMPLETING THE WORK WITHIN
THE AMOUNT BID. ANY QUESTIONS PERTAINING TO UNKNOWN CONDITIONS,
CHANGES IN DESIGN, OMISSIONS IN THE DESIGN OR SCOPE OF WORK,
MATERIALS, AND INSTALLATION TECHNIQUE SHOULD BE THROUGH RFBI'S/RFI'S
GIVEN TO THE STATE PROJECT DIRECTOR. THE STATE PROJECT DIRECTOR WILL
GET THE ANSWERS TO QUESTIONS, AS SOON AS POSSIBLE, IF "ON-THE-SPOT"
ANSWERS CAN NOT BE PROVIDED. UNKNOWN CONDITIONS ENCOUNTERED
DURING THE COURSE OF WORK, WHICH MAY DELAY WORK OR ADD COST, WILL
BE REPORTED TO THE STATE PROJECT DIRECTOR IMMEDIATELY-SO THAT
PROPER ARRANGEMENTS CAN BE MADE WITHOUT WORK STOPPAGE.
4. ALL WORK SHALL BE IN COMPLIANCE WITH CONTRACT DOCUMENT INCLUDING
PROJECT MANUAL AND SPECIFICATIONS.
5. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL ALL
TEMPORARY BRACING OF EQUIPMENTS TO INSURE THE SAFETY OF THE WORK
UNTIL IT IS IN ITS COMPLETED FORM.
6. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO ENSURE THAT ALL
APPLICABLE SAFETY LAWS ARE STRICTLY ENFORCED AND TO MAINTAIN A SAFE
CONSTRUCTION PROJECT.
7. THE CONTRACTOR SHALL REPAIR AND/OR REPAINT ALL AREAS DAMAGED BY
DEMOLITION OR CONSTRUCTION, AND FINISH TO MATCH EXISTING ADJACENT
SURFACES.
8. THE CONTRACTOR SHALL MAINTAIN DURING THE PROJECT, LEGIBLE AS BUILT
REVISIONS AND SUBMIT IN AUTOCAD FORMAT FINAL "AS-BUILT" DRAWINGS TO
THE STATE UPON COMPLETION OF CONSTRUCTION.
9. DAILY, AND UPON COMPLETION OF WORK, CONTRACTOR SHALL REMOVE
DEBRIS, RUBBISH, WASTE, AND SURPLUS MATERIAL FROM VETERANS HOME OF
CALIFORNIA CHULA VISTA PREMISES.
10. THE CONTRACTOR SHALL PROTECT AND COVER ALL FIXTURES AND EQUIPMENT
IN AREAS AFFECTED BY WORK, AND UPON COMPLETION OF WORK, SHALL
THOROUGHLY CLEAN ALL FIXTURES, EQUIPMENT, WALLS, CEILING, FLOOR, AND
HARDWARE.
11. CONTRACTOR SHALL VERIFY ALL INDOOR/OUTDOOR DIMENSIONS AND
OUTDOOR JOB CONDITIONS AT THE JOB SITE PRIOR TO BID, DO NOT SCALE
DRAWINGS.
12. FOR PURPOSES OF CLEARNESS AND LEGIBILITY, THE CONTRACT DRAWINGS
ARE ESSENTIALLY DIAGRAMMATIC AND, ALTHOUGH LOCATION OF THE
EQUIPMENT IS DRAWN TO SCALE, THE CONTRACTOR SHALL MAKE USE OF ALL
DATA IN ALL THE CONTRACT DOCUMENTS, TO ACCOMPLISH A COMPLETE,
OPERABLE AND MAINTAINABLE INSTALLATION.
13. ALL INSULATION AND COVERINGS INSTALL ON PIPING AND TUBING SHALL HAVE
A FLAME-SPREAD RATING NOT TO EXCEED 25 AND A SMOKE DENSITY NOT TO
EXCEED 50 WHEN TESTED IN ACCORDANCE WITH NFPA 255. (PER PARAGRAPH
1201.2.1.8 CMC 2022.
14. PROVIDE IN WRITING UPON COMPLETION OF WORK, ONE (1) YEAR WARRANTY
GUARANTY OF THE INSTALLATION.
RF RF RN
(E) MACHINERY ROOM VENTILATION
REFRIGERATION MACHINERY ROOM VENTILATION
CALCULATION BASED ON 2022 CMC SECTION 1106.2.5.1 FOR
REFRIGERANT R513a.
ROOM GROSS AREA: 1042 SQFT
1. EMERGENCY VENTILATION FOR REFRIGERANT GROUP A1
BASED ON 2022 CMC TABLE 1102.3 FOR REFRIGERANT R513a.
Q = 100 G
G = REFRIGERANT MASS = 385 LBS EACH CHILLER
Q = 100 385 + 385
Q = 2775 CFM
EXISTING VENTILATION EXHAUST FAN IN CHILLER ROOM
(EF-A76) HAS AN EXHAUST RATE OF 4000 CFM WHICH HAS
ADEQUATE VENTILATION TO SERVE THE NEW CHILLER.
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
7/15/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
M0.2
MECHANICAL
SCHEDULES
N M L K J I H G
Checked
Vault File Number
DSA Building Number
Reference North Sheet Scale
Sheet Number
Work Order
Designed
Sheet Title
Supervisor
File Date
Drawn
DescriptionNo. Date
Issue:
F E D C B
A
-06/25/2026
C op yr ig ht
5, C al ifo rn ia
D ep ar tm en t o f G en er al
S er vi ce s
- R ea l E st at e Se rv ic es D iv is io n
DGS PROJECT # DGS00000011694
SFM FAC #01-37-41-0048-00001
JCCA#: 24590-1
FI
LE
: L :\2
4\
0-
Tw o
5-
To n
C hi lle rs
, V et er an s H om e, C hu la V is ta
\C
AD
\2
1_
M
.d w g D
AT
E/
TI
M
E:
Ju n
, 0
8:
AM
JCCA
TWO 245-TON
CHILLER AND PUMP
REPLACEMENT
VETERANS HOME OF CALIFORNIA
700 E. NAPLES CT.
CHULA VISTA, CA 91911
Project
XX-X-XXXX-X-XX
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
RN
Department of General Services State of California
Real Estate Services Division
Project Management And Development Branch
DATE SIGNED: 11/24/2025
UTILITY SHUTDOWNS AFFECTING THE FACILITY OPERATION MUST BE REPORTED
TO DGS AND APPROVED BY DGS PRIOR TO SHUTDOWN AND MUST BE DONE IN
ACCORDANCE WITH HCAI PIN 74
CONSTRUCTION PHASING & TEMPORARY
HVAC EQUIPMENT REQUIREMENTS
CONTRACTOR SHALL BE RESPONSIBLE TO PERFORM DEMOLITION AND NEW
CONSTRUCTION IN SUCH A WAY AND IN INCREMENTS THAT IT WOULD NOT DISTURB
OPERATION.
1.
2. IT IS IMPERATIVE THAT THE COOLING SYSTEM TO BE OPERATIONAL DURING ALL
PHASES OF WORK. CONTRACTOR SHALL PROVIDE WHATEVER MEANS NECESSARY
TO MAINTAIN BUILDING MECHANICAL SYSTEM OPERATIONAL AT ALL TIMES.
3. CONTRACTOR TO PROVIDE TEMPORARY AIR COOLED CHILLER DURING
CONSTRUCTION IN REPLACING THE CHILLERS WITH NON-INTERRUPTION OF
BUILDING OPERATION. CONTRACTOR SHALL COORDINATE WITH THE OWNER FOR
THE LOCATION AND SET UP OF THE TEMPORARY AIR COOLED CHILLER, PUMPS,
VALVES, PIPING, AND POWER FOR THE DURATION OF CONSTRUCTION.
CONTRACTOR SHALL HIRE AND PAY FOR THE MANUFACTURER REPRESENTATIVE
RESPONSIBLE FOR ITS EQUIPMENT TO DO A COMPLETE UNIT START UP, TROUBLE
SHOOTING AND PROVIDE A WRITTEN CERTIFICATE OF PERFORMANCE TO THE OWNER
PRIOR TO CLOSE OF PROJECT FOR THE NEW CHILLERS, PUMPS, AND VFD'S.
CONTRACTOR SHALL FLUSH ABOUT 20 FEET OF PIPING PRIOR TO EQUIPMENT START
UP AND FINAL INTEGRATION TO EXISTING HYDRONIC PIPING.
START UP AND CERTIFICATE
303.2
CHILLER SCHEDULE
OPER.
LBS.
WT.
MCA TYPEV/PH/HZ
ELECTRICAL
R-513A460/3/60
EVAPORATOR CONDENSER REFRIGERANT
MANUFACTURERTAG MODEL NO.
10,914
QTY KW EA.
30HXC246
COMPRESSOR REMARKS
FURNISH KW TRANSDUCER , CHW TEMP. CONTROL POINT ADJUSTMENT MODBUS CONNECTIVITY, BACnet CARD & CARRIER CONTROLLER WITH TOUCH PANEL AND INTERNET CAPABILITY, MINIMUM LOAD CONTROL (TO 10% CAPACITY), SUCTION SERVICE VALVES, R513A CHARGE, STANDARD COOLER PASS, Y-DELTA STARTER, CONTROL TRANSFORMER, &
NON FUSED DISCONNECT.
LOCATION
LOCATION
EXISTING EXPANSION TANK SCHEDULE (FOR REFERENCE ONLY)
TYPE
GPM
LOCATION
LOCATIONTAG
TAG
SERVICE
SERVICE
MODEL
SYSTEM DESIGN ON
EFF.%(FT. W.C.) MAKE
EXISTING PUMP SCHEDULE (FOR REFERENCE ONLY)
MIN.HEAD
RPM HP
GAL.
VOLUME
TANK
(INCHES)
SIZE (D X H)
V PH.
SYSTEM DESIGNED ON
MAKE
MODEL (LBS.)
TAG
REMARKS
REMARKS
WT.
OPER.
(LBS.)
WT.
OPER.
EXISTING COOLING TOWER SCHEDULE (FOR REFRENCE ONLY)
OUT
(^F)
TAG
(GPM)
QUAN.
LOCATION
(^F)
WATER
IN
SYSTEM DESIGNED ON
WB)
(^F
TEMP.
AMB.
MAKE MODEL (LBS.)
WEIGHT
OPER.
REMARKS
TAG
EXISTING HEAT EXCHANGER SCHEDULE (FOR REFERENCE ONLY)
CONDENSER WATER
( F)
IN
(GPM)
QUAN.
IN
( F)
(FT. W.G.)
PRESS.
OUT
( F)°
DROP
QUAN.
(GPM) °
CHILLED WATER
MAKE
(FT. W.G.)
( F)
OUT
PRESS.
DROP MODEL
SYSTEM DESIGNED ON
WATER TEMP (^F)
EXISTING HEATING WATER GENERATOR SCHEDULE (FOR REFERENCE ONLY)
(CFH)
INPUT
GAS
SERVICE
OUTPUT
CAPACITY (MBH)
INPUT ENT.
SYSTEM DESIGNED ON
EFF.
MIN.
LEAV. MAKE MODEL
OPER.
REMARKS
(LBS.)
WEIGHT
(LBS.)
OPER.
REMARKS WT.
HX-1
A237
CHILLER RM.
1208 58 48 1414 45 53.5 BELL & GOSSETT
HWG-1
BOILER RM.
A239 4250 4,250 3,400
HOT WATER
HEATING
140 160 80% AJAX WG4250 8000
BOILER RM.
HWG-2 4250
HOT WATER
HEATINGA239
4,250 3,400 140 AJAX80%160 WG4250 8000
P-1
CHILLER RM.
A237
CHILLED WATER
PRIMARY 604 1750 7 460 3 B&G 1510-5A
CHILLER RM.
P-2
CHILLED WATER
A237 PRIMARY 4601750 7 3
604SECONDARYA237
CHILLER RM.
P-3
CHILLED WATER
4601750 40 B&G3 1510-4GB
CHILLER RM.
P-4 SECONDARY
CHILLED WATER
A237 4601750 40 3
ENCLOSURE
P-5
WATER
CONDENSERCOOLING TOWER 4601750 PEERLESS3 F1040A
ENCLOSURE
COOLING TOWERP-6 CONDENSER
WATER
4601750 PEERLESS3 F1040A
A239
BOILER RM.
P-7 HEATING
HOT WATER
4601750 PEERLESS3 F1220A
BOILER RM.
P-8 A239
HOT WATER
HEATING 4601750 PEERLESS3 F1220A
CHILLER RM.
ET-1 A237
WATER
CHILLED DIAPHRAM 211 30''~x83'' BELL & GOSSETT B-800 2400
B-600BELL & GOSSETT30''~x65''158DIAPHRAMHEATINGET-2 A239
BOILER RM. HOT WATER
DIAPHRAM
BOILER RM.
ET-3
HOT WATER
HEATINGA239 B-600158 30''~x65'' BELL & GOSSETT 1700
CT-1
ENCLOSURE
COOLING TOWER
1414 87 77 69 BAC 3269-2 28,2401 2 3 4
(2)-15 H.P., 2 SPEED, 460/3/60 FAN MOTORS.
AIR INLET SCREENS.
EXTENDED LUBRICATION LINES.
PROCESS EFFICIENCY PRODUCTS INC. MODEL SMF/PG FILTRATION SYSTEM WITH 24 GALLON FIBERGLASS TANK, 2 H.P. PUMP RATED AT 63 GPM, W/ 460/3/60 MOTOR & AUTOMATIC BACKWASH CONTROL.
CT-2 BAC7766 73.1 68 FXT-20 5 1350ROOF BLDG''A''
1 HP, 460/3/60 FAN MOTOR.5
REDUNDANT LOW WATER CUT OFFS.
BOILER SHALL MEET ALL STATE OF CALIFORNIA CODE REQUIREMENTS.1
1 2
TEFC MOTOR.
PEDESTAL BASE.
VARIABLE SPEED DRIVES.
2 3P-9 1750 460 PEERLESS3 PV2x2x8AROOF BLDG''A''
WATER
MU-1 PRECOOLER 155%4066 140
GPX 600018 18
MAX. MAX.
35 80 600
90020
35 80
130 75
130 75
50 78
50 78
130 71
130 71
(IN.)
SUCTION
HP REMARKS
TOTAL
RPMPOWER(FT)
DESIGN
(GPM)
SERVICE
HEAD
DESIGN
TYPEMODEL NO.TAG MANUFACTURER LOCATION
MOTOR DATA
PUMP SCHEDULE
OPER.
(LBS)
WT.
BELL & GOSSETT CHILLER
ROOM
CHILLED
WATER 35 460/3/60 1800 7.5 500
(IN.)
DISCHARGE
5BASE MOUNTED
END SUCTION
e-1510-5A-
SS-213T-S
CHILLED
WATER
CHILLED
WATER
** P-1 TO BE DEMO, REMOVED AND REPLACED WITH NEW. SEE PUMP SCHEDULE THIS SHEET FOR INFORMATION.
CARRIER 259.3 604
FLOW
GPM
LWT
°F
EWT
°F
54.29 16.6
PD FT
CAPACITY
(TONS)
FLOW
GPM
LWT
°F
87.25
EWT
°F
77 22.3
PD FT
0.5794
KW/TON
FULL LOAD
1 150.3 400
MOCP
30HXC246CARRIER
RF RF RN
6604BELL & GOSSETT 35 460/3/60 1800 7.5 500 5e-1510-5A-
SS-213T-S
4604BELL & GOSSETT 130 460/3/60 3600 30 560 3e-1510-3AD-
SS-284TS-L
604BELL & GOSSETT 130 460/3/60 560
BASE MOUNTED
END SUCTION
BASE MOUNTED
END SUCTION
BASE MOUNTED
END SUCTION
PROVIDE WITH STAINLESS STEEL VOLUTE WEAR RING.1
PROVIDE WITH STAINLESS STEEL SHAFT.2
PROVIDE WITH FALK T31 SPACER COUPLING.3
PROVIDE WITH EPOXY COATED INTERNAL CAST IRON COMPONENTS.4
PROVIDE WITH SPECIAL IMPELLER BALANCING (ISO 1940 G2.5 0R G1.0).5
PROVIDE WITH CERTIFIED PERFORMANCE TESTS (PER HI STANDARD 14.6).6
REMARKS: PUMP OPTIONS
1 THROUGH 6
1 THROUGH 6
1 THROUGH 7
1 THROUGH 7
PROVIDE WITH VFD, B-551G 7
INTELLIGENT PUMP CONTROLLER (IPC).
FURNISH KW TRANSDUCER , CHW TEMP. CONTROL POINT ADJUSTMENT MODBUS CONNECTIVITY, BACnet CARD & CARRIER CONTROLLER WITH TOUCH PANEL AND INTERNET CAPABILITY, MINIMUM LOAD CONTROL (TO 10% CAPACITY), SUCTION SERVICE VALVES, R513A CHARGE, STANDARD COOLER PASS, Y-DELTA STARTER, CONTROL TRANSFORMER, &
NON FUSED DISCONNECT.
** P-2 TO BE DEMO, REMOVED AND REPLACED WITH NEW. SEE PUMP SCHEDULE THIS SHEET FOR INFORMATION.
** P-3 TO BE DEMO, REMOVED AND REPLACED WITH NEW. SEE PUMP SCHEDULE THIS SHEET FOR INFORMATION.
** P-4 TO BE DEMO, REMOVED AND REPLACED WITH NEW. SEE PUMP SCHEDULE THIS SHEET FOR INFORMATION.
B&G 1510-5A
B&G 1510-4GB
OSP
NUMBER
OSP-0161
CHILLED
WATER
OSP-0316-10, 30HP, 460V/3PH/60HZ,
430 3e-1510-3AD-
SS-284TS-L 3600
WITH SERVICE DISCONNECT SWITCH
303.2 R-513A460/3/60 10,914259.3 604 44 54.29 16.6 707 87.25 77 22.3 0.5794 1 150.3 400
CONTRACTOR SHALL HIRE CONTROLS CONTRACTOR FOR DISCONNECTING,
RECONNECTING AND INTEGRATING THE BMS CONTROLS FOR THE CHILLERS, PUMPS,
VFD'S. CONTROLS CONTRACTOR TO PROVIDE THE NECESSARY COMPONENTS TO
ENSURE THE NEW CHILLERS, PUMPS, AND VFD'S ARE FUNCTIONING PROPERLY FOR
PLANT OPERATIONS TO VIEW AT A CENTRAL BMS LOCATION. CONTROLS CONTRACTOR
SHALL SUBMIT A SHOP DRAWING SHOWING SCHEMATIC DIAGRAM AND COMPONENTS
FOR A FULLY FUNCTIONAL SYSTEM FOR APPROVAL.
FOR REFERENCE ONLY, THE CURRENT MAINTENANCE CONTROL CONTRACTOR FOR
THE FACILITY IS BY CLIMATEC. CONTACT PERSON IS STEPHANIE PATERNO (858)
391-7001.
CONTROLS INTEGRATION
OSP-0161
CHILLER
ROOM
CHILLER
ROOM
CHILLER
ROOM
LBS
BHP
6.66
6.66
23.51
23.51
4. COOLING AND HEATING EQUIPMENT WILL BE RESTORED TO POWER WITHIN
SUFFICIENT TIME TO MAINTAIN TEMPERATURE BETWEEN 71°-81°F.
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
7/15/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
M1.0
SITE PLAN
SITE PLAN
SCALE:
N M L K J I H G
Checked
Vault File Number
DSA Building Number
Reference North Sheet Scale
Sheet Number
Work Order
Designed
Sheet Title
Supervisor
File Date
Drawn
DescriptionNo. Date
Issue:
F E D C B
A
-06/25/2026
C op yr ig ht
5, C al ifo rn ia
D ep ar tm en t o f G en er al
S er vi ce s
- R ea l E st at e Se rv ic es D iv is io n
DGS PROJECT # DGS00000011694
SFM FAC #01-37-41-0048-00001
JCCA#: 24590-1
FI
LE
: L :\2
4\
0-
Tw o
5-
To n
C hi lle rs
, V et er an s H om e, C hu la V is ta
\C
AD
\2
1_
M
.d w g D
AT
E/
TI
M
E:
Ju n
, 0
8:
AM
JCCA
TWO 245-TON
CHILLER AND PUMP
REPLACEMENT
VETERANS HOME OF CALIFORNIA
700 E. NAPLES CT.
CHULA VISTA, CA 91911
Project
XX-X-XXXX-X-XX
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
RN
Department of General Services State of California
Real Estate Services Division
Project Management And Development Branch
DATE SIGNED: 11/24/2025
0 24020 FEET120
1" = 120'
SEE ENLARGED PLANS
M1.1 FOR DEMOLITION
AND M2.1 FOR NEW WORK.
RF RF RN
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
7/15/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
CWR
CWS
UNDERGROUND
PIPING
2''
10'' 10''
4'' 6''
4''4''
1''
6''
4''
6''
4''
4''
10"
6"
CHWS
CHWR
HHWS
HHWR
6" 1"
6"
10"
R
IS
E
6" 6"
10"
10"
10"10"
10"
6" 6"
10" 6"
6"6"
6" 10"10"
10" 6" 6"
6"
M
P1
P2 P3
P4
10" 10"
P8P7
6"
P6
P5
M1.1
MECHANICAL
DEMOLITION PLAN -
BUILDING A
MECHANICAL DEMOLITION PLAN - BUILDING "A"
N M L K J I H G
Checked
Vault File Number
DSA Building Number
Reference North Sheet Scale
Sheet Number
Work Order
Designed
Sheet Title
Supervisor
File Date
Drawn
DescriptionNo. Date
Issue:
F E D C B
A
-06/25/2026
C op yr ig ht
5, C al ifo rn ia
D ep ar tm en t o f G en er al
S er vi ce s
- R ea l E st at e Se rv ic es D iv is io n
DGS PROJECT # DGS00000011694
SFM FAC #01-37-41-0048-00001
JCCA#: 24590-1
FI
LE
: L :\2
4\
0-
Tw o
5-
To n
C hi lle rs
, V et er an s H om e, C hu la V is ta
\C
AD
\2
1_
M
.d w g D
AT
E/
TI
M
E:
Ju n
, 0
8:
AM
JCCA
TWO 245-TON
CHILLER AND PUMP
REPLACEMENT
VETERANS HOME OF CALIFORNIA
700 E. NAPLES CT.
CHULA VISTA, CA 91911
Project
XX-X-XXXX-X-XX
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
RN
Department of General Services State of California
Real Estate Services Division
Project Management And Development Branch
DATE SIGNED: 11/24/2025
DEMOLITION KEYNOTES:
EXISTING EXPANSION TANK TO REMAIN. FOR REFERENCE ONLY.
EXISTING FLOW METER TO REMAIN. FOR REFERENCE ONLY.
EXISTING GRAVITY MAKE UP AIR DUCT FROM ROOF TO REMAIN. FOR
REFERENCE ONLY.
EXISTING EXHAUST DUCT FROM EXHAUST FAN (EF-A76) ON ROOF TO
REMAIN. FOR REFERENCE ONLY. 4000 CFM EXHAUST RATE.
12"X6" EXHAUST GRILLE TO REMAIN. FOR REFERENCE ONLY.
EXISTING DDC CONTROL AND REFRIGERATION MONITOR PANELS TO
REMAIN. REPLACE DEVICES IN REFRIGERATION MONITOR PANEL AND
INSTALL NEW MODULES FOR REFRIGERANT 513a. INTERLOCKING
SEQUENCE WITH EXHAUST (EF-A76) SHALL REMAIN.
EXISTING REFRIGERATION SENSOR TO REMOVED AND REPLACED WITH
NEW SENSOR COMPATIBLE WITH REFRIGERANT 513a.
EMERGENCY SHUT OFF BUTTON LOCATED OUTSIDE THE CHILLER
ROOM TO REMAIN. FOR REFERENCE ONLY.
EXISTING HEAT EXCHANGER TO REMAIN.
EXISTING BOILER IN BOILER ROOM TO REMAIN. FOR REFERENCE ONLY.
EXISTING PUMPS FOR BOILER IN BOILER ROOM TO REMAIN. FOR
REFERENCE ONLY.
EXISTING COOLING TOWER IN MECHANICAL YARD TO REMAIN. FOR
REFERENCE ONLY.
EXISTING PUMPS FOR COOLING TOWER IN MECHANICAL YARD TO
REMAIN. FOR REFERENCE ONLY.
EXISTING WATER FILTRATION FOR COOLING TOWER IN MECHANICAL
YARD TO REMAIN. FOR REFERENCE ONLY.
5 5
CT
CT
11 11
DEMOLITION KEYNOTES (CONT.):
REMOVE AND DEMO EXISTING CHILLERS CH-1 AND CH-2.
POINT OF DISCONNECT. DISCONNECT CHWS FROM EXISTING CHILLER.
TEMPORARY CAP OPENING TO KEEP DIRT AND DEBRIS FROM GETTING
INSIDE THE PIPE. REFER TO SHEET M3.1, CHILLER PIPING DIAGRAM,
FOR MORE DEMOLITION INFORMATION.
POINT OF DISCONNECT. DISCONNECT CHWR FROM EXISTING CHILLER.
TEMPORARY CAP OPENING TO KEEP DIRT AND DEBRIS FROM GETTING
INSIDE THE PIPE. REFER TO SHEET M3.1, CHILLER PIPING DIAGRAM,
FOR MORE DEMOLITION INFORMATION.
POINT OF DISCONNECT. DISCONNECT CWS FROM EXISTING CHILLER.
TEMPORARY CAP OPENING TO KEEP DIRT AND DEBRIS FROM GETTING
INSIDE THE PIPE. REFER TO SHEET M3.1, CHILLER PIPING DIAGRAM,
FOR MORE DEMOLITION INFORMATION.
POINT OF DISCONNECT. DISCONNECT CWR FROM EXISTING CHILLER.
TEMPORARY CAP OPENING TO KEEP DIRT AND DEBRIS FROM GETTING
INSIDE THE PIPE. REFER TO SHEET M3.1, CHILLER PIPING DIAGRAM,
FOR MORE DEMOLITION INFORMATION.
REMOVE AND DEMO PRIMARY CHILLED WATER PUMP.
REMOVE AND DEMO SECONDARY CHILLED WATER PUMP.
POINT OF DISCONNECT. DISCONNECT CHWS FROM EXISTING PUMP.
TEMPORARY CAP OPENING TO KEEP DIRT AND DEBRIS FROM GETTING
INSIDE THE PIPE. REFER TO SHEET M3.1, PUMP PIPING DIAGRAM, FOR
MORE DEMOLITION INFORMATION.
POINT OF DISCONNECT. DISCONNECT CHWR FROM EXISTING PUMP.
TEMPORARY CAP OPENING TO KEEP DIRT AND DEBRIS FROM GETTING
INSIDE THE PIPE. REFER TO SHEET M3.1, PUMP PIPING DIAGRAM, FOR
MORE DEMOLITION INFORMATION.
REMOVE AND DEMO EXISTING VFD DRIVE FOR P3 AND P4 LOCATED ON
THE WALL.
20 20 21 21
22 22 22 22
(E)MAKE UP WATER
TO REMAIN.
RF RF TPK
GENERAL NOTES:
1. ALL WORK ARE WITHIN CHILLER ROOM A237. NO NEW
PIPES ARE PENETRATING ANY EXISTING WALLS.
REFER TO DEMOLITION KEYNOTES FOR MORE
INFORMATION.
2. COOLING TOWER AND ASSOCIATED EQUIPMENTS
AND PIPING IN COOLING TOWER YARD ARE SHOWN
FOR REFERENCE ONLY. NO WORK IN COOLING
TOWER YARD.
3. SEE M2.4 FOR EXISTING SEQUENCE OF OPERATION
(SOP) AND SHALL CARRY OVER TO NEW CHILLERS.
DEMOLITION PHASING NOTE:
1. CONTRACTOR TO TAKE A CLOSE LOOK IN THE FIELD
AS TO WHICH CHILLER IS BEST TO REMOVE FIRST
PRIOR TO START OF WORK. NOTIFY CHULA VISTA
ENGINEER OF WHICH CHILLER WILL BE REMOVED
FIRST PRIOR TO DEMO.
2. THE PREFERENCE IS FIRST TO DEMO AND REMOVE
CHILLER CH-2, PUMPS, AND PIPING.
DEMOLITION KEYNOTES (CONT.):
(E) 10" CHWS AND CHWR ISOLATION VALVE USED TO TAP FOR
TEMPORARY CHILLERS.
A76
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
7/15/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
M2.0
SITE PLAN -
TEMPORARY AIR
COOLED CHILLER
PLANSITE PLAN - TEMPORARY AIR COOLED CHILLER PLAN
SCALE:
N M L K J I H G
Checked
Vault File Number
DSA Building Number
Reference North Sheet Scale
Sheet Number
Work Order
Designed
Sheet Title
Supervisor
File Date
Drawn
DescriptionNo. Date
Issue:
F E D C B
A
-06/25/2026
C op yr ig ht
5, C al ifo rn ia
D ep ar tm en t o f G en er al
S er vi ce s
- R ea l E st at e Se rv ic es D iv is io n
DGS PROJECT # DGS00000011694
SFM FAC #01-37-41-0048-00001
JCCA#: 24590-1
FI
LE
: L :\2
4\
0-
Tw o
5-
To n
C hi lle rs
, V et er an s H om e, C hu la V is ta
\C
AD
\2
1_
M
.d w g D
AT
E/
TI
M
E:
Ju n
, 0
8:
AM
JCCA
TWO 245-TON
CHILLER AND PUMP
REPLACEMENT
VETERANS HOME OF CALIFORNIA
700 E. NAPLES CT.
CHULA VISTA, CA 91911
Project
XX-X-XXXX-X-XX
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
RN
Department of General Services State of California
Real Estate Services Division
Project Management And Development Branch
DATE SIGNED: 11/24/2025
SEE ENLARGE PLAN M2.2
RF RF RN
0 100050 FEET500
1" = 500'
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
7/15/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
CWR
CWS
UNDERGROUND
PIPING
2''
10'' 10''
4'' 6''
4''4''
1''
6''
4''
6''
4''
4''
10"
6"
CHWS
CHWR
HHWS
HHWR
6" 1"
6"
10"
R
IS
E
6" 6"
10"
10"
10"10"
10"
6" 6"
10" 6"
6"6"
6" 10"10"
10" 6" 6"
6"
M
P1
P2 P3
P4
10" 10"
P8P7
6"
P6
P5
M2.1
MECHANICAL NEW
WORK PLAN PLAN -
BUILDING A
MECHANICAL NEW WORK PLAN - BUILDING "A"
N M L K J I H G
Checked
Vault File Number
DSA Building Number
Reference North Sheet Scale
Sheet Number
Work Order
Designed
Sheet Title
Supervisor
File Date
Drawn
DescriptionNo. Date
Issue:
F E D C B
A
-06/25/2026
C op yr ig ht
5, C al ifo rn ia
D ep ar tm en t o f G en er al
S er vi ce s
- R ea l E st at e Se rv ic es D iv is io n
DGS PROJECT # DGS00000011694
SFM FAC #01-37-41-0048-00001
JCCA#: 24590-1
FI
LE
: L :\2
4\
0-
Tw o
5-
To n
C hi lle rs
, V et er an s H om e, C hu la V is ta
\C
AD
\2
1_
M
.d w g D
AT
E/
TI
M
E:
Ju n
, 0
8:
AM
JCCA
TWO 245-TON
CHILLER AND PUMP
REPLACEMENT
VETERANS HOME OF CALIFORNIA
700 E. NAPLES CT.
CHULA VISTA, CA 91911
Project
XX-X-XXXX-X-XX
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
RN
Department of General Services State of California
Real Estate Services Division
Project Management And Development Branch
DATE SIGNED: 11/24/2025
RF RF RN
ET
HX
ET
ET
B
B
CT
CT
CH
CH
(E) MAKE UP WATER
NEW WORK KEYNOTES:
FURNISH AND INSTALL (N) CHILLERS (CH-1 AND CH-2). SEE M0.2 FOR
SCHEDULE. SEE STRUCTURAL S2.1 FOR ANCHORAGE.
POINT OF CONNECTION. INSTALL AND CONNECT CHWS PIPING TO (N)
CHILLER EVAPORATOR OUTLET. REFER TO SHEET M3.1, CHILLER
PIPING DIAGRAM, FOR MORE INFORMATION.
POINT OF CONNECTION. INSTALL AND CONNECT CHWR PIPING TO (N)
CHILLER EVAPORATOR INLET. REFER TO SHEET M3.1, CHILLER PIPING
DIAGRAM, FOR MORE INFORMATION.
POINT OF CONNECTION. INSTALL AND CONNECT CWS PIPING TO (N)
CHILLER CONDENSER INLET. REFER TO SHEET M3.1, CHILLER PIPING
DIAGRAM, FOR MORE INFORMATION.
POINT OF CONNECTION. INSTALL AND CONNECT CWR PIPING TO (N)
CHILLER CONDENSER OUTLET. REFER TO SHEET M3.1, CHILLER PIPING
DIAGRAM, FOR MORE INFORMATION.
FURNISH AND INSTALL (N) PUMPS (P1 THROUGH P4). SEE M0.2 FOR
SCHEDULE. SEE STRUCTURAL S2.1 FOR ANCHORAGE.
POINT OF CONNECTION. INSTALL AND CONNECT CHWS PIPING TO (N)
PUMP. REFER TO SHEET M3.1, CHILLER PIPING DIAGRAM, FOR MORE
INFORMATION. PROVIDE REQUIRED TRANSITION TO PUMP DISCHARGE.
POINT OF CONNECTION. INSTALL AND CONNECT CHWR PIPING TO (N)
PUMP. REFER TO SHEET M3.1, CHILLER PIPING DIAGRAM, FOR MORE
INFORMATION. PROVIDE REQUIRED TRANSITION TO PUMP SUCTION.
FURNISH AND INSTALL (N) VFD (P3 AND P4). SEE M0.2 FOR SCHEDULE.
REFER TO STRUCTURAL PLAN S2.1 FOR ANCHORAGE DETAIL.
10-INCH CHWS AND CHWR ISOLATION VALVE FOR TEMPORARY TAP OF
TEMPORARY CHILLERS.
1 1
(E)
(E) FLOW METER
6 6 6 6
8 8 8 8 (E)
(E) (E)
(E)
(E)
(E)
(E)
REFRIGERATION SENSOR
(E) DDC AND REFRIGERATION
CONTROL PANEL
(E) EMERGENCY SHUT-OFF BUTTON
(E)
(E)
(E)
(E)
(E) COOLING TOWER WATER
FILTRATION
FURNISH AND INSTALL NEW REFRIGERANT SENSOR. REFER TO M1.1
KEYNOTE 7 FOR MORE INFORMATION REGARDING SENSOR AND
DEVICES INSIDE REFRIGERANT MONITORING PANEL. CONTRACTOR
SHALL TEST VAPOR DETECTION SYSTEM TO ENSURE ALL
FUNCTIONALITY PRIOR TO FINAL COMMISSIONING.
ALARM LEVELS FOR R-513a REFRIGERANT DETECTION SYSTEM:
- PRE-ALARM: 75 PPM
- HIGH ALARM: 650 PPM
HIGH ALARM SHALL ACTIVATE EXHAUST FAN (EF-A76).
NEW WORK KEYNOTES (CONT.):
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
7/15/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
M2.2
ENLARGED
TEMPORARY AIR
COOLED CHILLER
PLANENLARGED TEMPORARY AIR COOLED CHILLER PLAN
SCALE:
N M L K J I H G
Checked
Vault File Number
DSA Building Number
Reference North Sheet Scale
Sheet Number
Work Order
Designed
Sheet Title
Supervisor
File Date
Drawn
DescriptionNo. Date
Issue:
F E D C B
A
-06/25/2026
C op yr ig ht
5, C al ifo rn ia
D ep ar tm en t o f G en er al
S er vi ce s
- R ea l E st at e Se rv ic es D iv is io n
DGS PROJECT # DGS00000011694
SFM FAC #01-37-41-0048-00001
JCCA#: 24590-1
FI
LE
: L :\2
4\
0-
Tw o
5-
To n
C hi lle rs
, V et er an s H om e, C hu la V is ta
\C
AD
\2
1_
M
.d w g D
AT
E/
TI
M
E:
Ju n
, 0
8:
AM
JCCA
TWO 245-TON
CHILLER AND PUMP
REPLACEMENT
VETERANS HOME OF CALIFORNIA
700 E. NAPLES CT.
CHULA VISTA, CA 91911
Project
XX-X-XXXX-X-XX
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
RN
Department of General Services State of California
Real Estate Services Division
Project Management And Development Branch
DATE SIGNED: 11/24/2025
RF RF RN
NEW WORK KEYNOTES:
PROPOSED LOCATION OF TEMPORARY AIR COOLED CHILLER. 300 TON
CAPACITY TEMPORARY CHILLER MOUNTED ON A TRUCK BED. TRUCK
BED SIZE IS 8'-6" WIDE x 48'-0" LONG. TRUCK TRAILER AND TEMPORARY
CHILLER TO BE ANCHORED PER HCAI REGULATIONS AND TO BE
SUBMITTED FOR HCAI REVIEW AND APPROVAL.
TEMPORARY AIR COOLED CHILLER BASED ON CARRIER 300 TON
CAPACITY MODEL 30XA352 OR EQUAL. CHILLER SPECIFICATIONS AS
FOLLOW: 720 GPM, 44°F LEAVING WATER TEMPERATURE, 54°F
ENTERING WATER TEMPERATURE. SINGLE POINT OF POWER
460V/3PH/60HZ, 650 FLA, 695 MCA, 800 MOCP, MOUNTED DISCONNECT
WITH (2) INTERNAL CIRCUIT BREAKER. SHIPPING WEIGHT (21,000 LBS
CHILLER ONLY), TRAILER 17,000 LBS, CLEARANCE IS 8'-0" ON THE SIDES
AND 4'-0" ON THE ELECTRICAL SIDE.
8" CHWS/R UP ALONG WALL TO ABOVE ROOF.
8" CHWS/R DOWN ALONG WALL…