Plans_and_Drawings_-_Event_4129.pdf

PDF 9 MB Posted

Attached to
Bid-PW Building Automation System Upgrade - Hawth.
Solicitation number
0000004129
Issued by
Hennepin County, Minnesota

About this file

This is a plans and drawings document for a Building Automation System (BAS) upgrade project at the Hawthorne parking ramp facility in Minneapolis, Minnesota, issued by the City of Minneapolis Division of Traffic and Parking. The project involves upgrading the existing BAS and operator graphics with replacement of terminal-level controllers using BACnet-compliant devices at a maximum baud rate of 76,800 BPS, installation of new control devices to meet specified sequences of operation, and implementation of a new front-end operator interface and graphics based on Automated Logic Corporation equipment. The scope includes no new HVAC equipment but requires replacement of field-level controllers, installation of new sensors and actuators, removal of defunct controls, and coordination with a Test and Balance contractor to balance all VAV terminal units and minimum outdoor airflow rates. The Hawthorne ramp will remain in normal operation throughout construction, requiring the general contractor to coordinate directly with the owner to establish an acceptable construction timeline and work sequencing that minimizes disruption to ramp operations and occupants.

The project documents specify detailed control sequences for multiple systems including chilled water and heating water plants, air handling units (AHU-1 through AHU-5), VAV boxes with heating water reheat, cabinet unit heaters, unit heaters, convectors, exhaust fans, and miscellaneous controls throughout the basement, first floor, third floor, fourth floor, and seventh floor levels of the facility. All work must comply with applicable local, state, and federal codes and regulations, with the contractor responsible for obtaining all necessary permits and licenses. All sub-contractors must submit Material Safety Data Sheets to the general contractor for record-keeping and submission to the owner. The contractor is responsible for maintaining the premises free from waste materials, patching and repairing existing construction to like-new condition resulting from removals or replacements, repairing any damage to existing buildings and property during construction, maintaining egress paths at all times, and controlling dust, noise, VOCs, and vibration in the occupied environment while coordinating work schedules with building users.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

G000

TITLE SHEET

DESIGNED DRAWN CHECKED

SIGNATURE:

PRINTED NAME:

LIC. NO.: DATE:

DATENO. ISSUE RECORD

A pr

0,

- 3

:2 4p m

BA

R

IS

O N

E

IN

C H

O N

O R

IG

IN

AL

D

R

AW

IN

G

IF

N O

T O

N E

IN

C

H O

N T

H

IS

D R

AW

IN

G A

D

JU

ST

S

C

AL

ES

A

C C

O R

D

IN

G

LY

22308.000

RAMP C

RAMP B

RAMP A

HAWTHORNE

KEY PLAN

HAWTHORNE

BAS UPGRADES

CITY OF MINNEAPOLIS

DIVISION OF TRAFFIC AND

PARKING

SCOPED AREAS

GENERAL CONSTRUCTION PACKAGE

CITY OF MINNEAPOLIS

HAWTHORNE - BAS UPGRADES

MINNEAPOLIS, MINNESOTA

SITE LOCATION MAP

CONTACT INFORMATION PROJECT GENERAL NOTES

DANIEL COLVIN

PROJECT MANAGER

CITY OF MPLS - PARKING SERVICES

31 NORTH 9TH STREET

MINNEAPOLIS, MINNESOTA 55403

PHONE: (612) 500-3897

EMAIL: daniel,cikvub@minneapolismn.gov

OWNER REPRESENTATIVE

TKDA

BEN HUESMAN

MECHANICAL ENGINEER

3311 E OLD SHAKOPEE ROAD SUITE 300

BLOOMINGTON, MN 55425

PHONE: (651) 292-4400

EMAIL: ben.huesman@tkda.com

TIMOTHY D. HOSECK

MECHANICAL ENGINEER

3311 E OLD SHAKOPEE ROAD SUITE 300

BLOOMINGTON, MN 55425

PHONE: (651) 292-4400

EMAIL: timothy.hoseck@tkda.com

SHEET NO. SHEET NAME

G000 TITLE SHEET

M000 MECHANICAL SYMBOLS AND ABBREVIATIONS

TOTAL SHEET COUNT: 22

WORK SCOPE AREA

M100 M110 M111 M112 M130 M140 M170 M400 M401 M402 M500 M501 M502 M503 M504 M505 M506 M507

M600

HVAC CONTROLS PLAN BASEMENT LEVEL NORTHEAST

HVAC CONTROLS PLAN FIRST FLOOR RAMP

HVAC CONTROLS PLAN FIRST FLOOR NORTHEAST

HVAC CONTROLS PLAN FIRST FLOOR SOUTHWEST

HVAC CONTROLS PLAN THIRD FLOOR RAMP SKYWAY

HVAC CONTROLS PLAN FOURTH FLOOR RAMP

MECHANICAL STAIR C PLANS BASEMENT THRU THIRD LEVEL EAST AREA

MECHANICAL ROOM T112 & T137 SECOND LEVEL WEST AND SOUTH AREAS

MECHANICAL ROOMS AND SOUTH SKYWAY THIRD LEVEL

HVAC CONTROLS PLAN SEVENTH FLOOR RAMP ROOF LEVEL

MECHANICAL ROOM 050 STAIR C BASEMENT LEVEL HW & CW PLANT CONTROLS

MECHANICAL ROOM 304 FIRST FLOOR SW OFFICES AHU-1 CONTROLS

MECHANICAL ROOM 304 THIRD LEVEL SW SKYWAY AHU-2 CONTROLS

MECHANICAL ROOM 305A THIRD LEVEL NE SKYWAY AHU-4 CONTROLS

MECHANICAL ROOM 305A THIRD LEVEL NE SKYWAY AHU-5 CONTROLS

OFFICES & MECHANICAL ROOMS MULTIPLE LOCATIONS MISC. CONTROLS

ELEVATOR EQUIPMENT ROOM SEVENTH LEVEL STAIR C FCU-1 CONTROLS

PENTHOUSE MECHANICAL SEVENTH FLOOR STAIR C AHU-3 CONTROLS

EXISTING EQUIPMENT SCHEDULE

M508 HAWTHORNE OFFICES VARIOUS FLOORS VAV & FPVAV CONTROLS

A. THE WORK OF THIS CONTRACT CONSISTS OF UPGRADING THE BUILDING AUTOMATION SYSTEM (BAS) AND OPERATOR GRAPHICS FOR THE EXISTING HAWTHORNE RAMP FACILITY, OWNED BY THE CITY OF MINNEAPOLIS PARKING AUTHORITY. WORK INCLUDES REPLACEMENT OF TERMINAL-LEVEL CONTROLLERS WITH BACNET-COMPLIANT DEVICES AT A MAXIMUM BAUD RATE OF 76,800 BPS, INSTALLATION OF NEW CONTROL DEVICES AS REQUIRED TO MEET THE SPECIFIED SEQUENCES OF OPERATION, AND IMPLEMENTATION OF A NEW FRONT-END OPERATOR INTERFACE AND GRAPHICS BASED ON AUTOMATED LOGIC CORPORATION EQUIPMENT. NO NEW HVAC EQUIPMENT IS INCLUDED IN THIS CONTRACT. THE GENERAL CONTRACTOR SHALL PROVIDE A DEFICIENCY REPORT OF ALL EXISTING TO-REMAIN CONTROL SENSORS AND ACTUATORS. THE GENERAL CONTRACTOR SHALL HIRE AND COORDINATE WITH A TEST AND BALANCE CONTRACTOR TO BALANCE ALL VAV TERMINAL UNITS AND MINIMUM OUTDOOR AIRFLOW RATES; REFER TO THE DRAWINGS FOR QUANTITIES AND LOCATIONS. THE HAWTHORNE RAMP WILL REMAIN IN NORMAL OPERATION THROUGHOUT THE DURATION OF CONSTRUCTION. THE GENERAL CONTRACTOR SHALL COORDINATE DIRECTLY WITH THE OWNER TO ESTABLISH AN ACCEPTABLE CONSTRUCTION TIMELINE, WORK AREA SEQUENCING, AND SCHEDULING THAT MINIMIZES DISRUPTION TO RAMP OPERATIONS AND OCCUPANTS. ALL WORK SHALL BE

PERFORMED IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.

B. THE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE INTENDED TO INDICATE CAPACITY, SIZE, APPROXIMATE LOCATION AND GENERAL ARRANGEMENT, NOT THE SPECIFIC DETAILS OF CONSTRUCTION. ADDITIONAL OFFSETS, FITTINGS, ACCESSORIES, AND COORDINATION MAY BE NEEDED FOR PROPER INSTALLATION AND ARE THE RESPONSIBILITY OF THE

CONTRACTOR.

C. EXISTING MECHANICAL ELEMENTS, INCLUDING ALL PIPING, DUCTWORK, AND PLUMBING SHOWN ON THESE DRAWINGS ARE BASED ON ORIGINAL CONSTRUCTION DOCUMENTS AND LIMITED FIELD OBSERVATION. CONTRACTOR SHALL FIELD VERIFY

ACTUAL EXISTING CONDITIONS PRIOR TO BIDDING.

D. ALL WORK SHALL COMPLY WITH ALL APPLICABLE LOCAL, STATE & FEDERAL CODES, RULES & REGULATIONS.

E. THE CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS, LICENSES & CERTIFICATES AND PAY ALL FEES CONNECTED

THEREWITH.

F. ALL SUB-CONTRACTORS TO SUBMIT MATERIAL SAFETY DATA SHEETS MSDS IF APPLICABLE TO THEIR TRADE TO GEN. CONTR.

FOR RECORD KEEPING & SUBMITTAL TO OWNER.

G. VERIFY WITH OWNERS REPRESENTATIVE USE OF SITE, OR ADJACENT AREAS, FOR STAGING OR STOCKPILE OF NEW

MATERIALS.

H. VERIFY WITH OWNERS REPRESENTATIVE FOR POSSIBLE STOCKPILED MATERIALS AVAILABLE FOR USE ON PROJECT. I.E.

DOORS, FRAMES, ACOUSTICAL CEILING PANELS, ETC.

I. CONTRACTOR SHALL COORDINATE ALL WORK WITH OWNER TO AVOID INTERRUPTION OF BUILDING ACTIVITIES OR ACCESS.

J. ALL DIMENSIONS MUST BE FIELD VERIFIED. EXISTING BUILDING WALLS, WINDOWS AND DOORS ETC. ARE SHOWN FOR REFERENCE ONLY, & ARE SUBJECT TO FIELD VERIFICATION. NOTIFY ENGINEER REGARDING DISCREPANCIES BEFORE

PROCEEDING WITH THE WORK AFFECTED.

K. CONTRACTORS SHALL MAKE ALL NECESSARY ARRANGEMENTS WITH BLDG. OWNER & USERS FOR ACCESS TO AREA, INCLUDING, BUT NOT LIMITED TO DELIVERIES. CONTRACTOR SHALL ACKNOWLEDGE & ABIDE BY ALL BUILDING REGULATIONS.

CONTRACTOR TO SCHEDULE USE OF DOCK FOR DELIVERIES WITH OWNER.

L. THE CONTRACTOR SHALL FURNISH & INSTALL ALL ITEMS WHICH ARE NECESSARY TO ENSURE A GOOD WORKMANSHIP INSTALLATION EVEN THOUGH SUCH ITEMS ARE NOT SPECIFICALLY MENTIONED ON THE DRAWINGS. QUALITY & FINISH REQUIREMENTS SHALL BE AS A MIN. ACCEPTABLE LEVEL OF QUALITY AS RECOGNIZED BY THE INDUSTRY.

M. THE WORD - PROVIDE - AS USED IN THE DRAWINGS SHALL BE UNDERSTOOD TO MEAN - PROVIDE COMPLETE IN PLACE. THAT IS

- FURNISHED AND INSTALLED - PROVIDE ALL ACCESSORIES & TRIM AS REQUIRED FOR A COMPLETE INSTALLATION.

N. THE CONTRACTOR SHALL, AT ALL TIMES, KEEP THE PREMISES FREE FROM WASTE MATERIAL OR RUBBISH CAUSED BY THE

WORK.

O. THE CONTRACTOR SHALL PATCH & REPAIR EXISTING CONSTRUCTION TO LIKE NEW CONDITION AS A RESULT OF REMOVAL OR REPLACEMENT OF EXIST. CONSTRUCTION. ALL EXIST. & NEW HOLES OR PENETRATIONS THROUGH FIRE RATED ASSEMBLIES

MUST BE PATCHED & REPAIRED TO MAINTAIN THE INTEGRITY OF THE ASSEMBLY.

P. THE CONTRACTOR SHALL REPAIR OR REPLACE ANY DAMAGE CAUSED TO EXISTING BUILDINGS & PROPERTY DURING

CONSTRUCTION INSIDE AND OUTSIDE OF PROJECT LIMITS.

Q. CONTRACTOR TO MAINTAIN EGRESS PATHS AT ALL TIMES. SEQUENCE WORK ACCORDINGLY.

R. COVER AND PROTECT EXISTING EQUIPMENT DURING DEMOLITION AND CONSTRUCTION.

S. CONTRACTOR TO CONTROL DUST, NOISE, VOCS AND VIBRATION IN OCCUPIED ENVIRONMENT. COORDINATE WORK SCHEDULE

WITH USER - CUSTOMER.

T. ALL CONTRACTORS ARE RESPONSIBLE TO REVIEW ALL DRAWINGS, SPECS, AND COORDINATE THE WORK TO PROVIDE

COMPLETE INSTALLATION.

SHEET INDEX

M000

MECHANICAL

SYMBOLS AND

ABBREVIATIONS

SCOPED AREAS

DESIGNED DRAWN CHECKED

SIGNATURE:

PRINTED NAME:

LIC. NO.: DATE:

DATENO. ISSUE RECORD

A pr

0,

- 3

:2 5p m

BA

R

IS

O N

E

IN

C H

O N

O R

IG

IN

AL

D

R

AW

IN

G

IF

N O

T O

N E

IN

C

H O

N T

H

IS

D R

AW

IN

G A

D

JU

ST

S

C

AL

ES

A

C C

O R

D

IN

G

LY

22308.000

RAMP C

RAMP B

RAMP A

HAWTHORNE

KEY PLAN

HAWTHORNE

BAS UPGRADES

CITY OF MINNEAPOLIS

DIVISION OF TRAFFIC AND

PARKING

PIPING LEGEND

FITTING AND MISCELLANEOUS LEGEND

NECK DIAMETER

( )FOR MULTIPLE

DIFFUSERS ONLY

TYPE DESIGNATION

REGISTER SIZE

REGISTER SIZE

TYPE DESIGNATION

TYPE DESIGNATION

(SEE SCHEDULE DRAWING)

(SEE SCHEDULE DRAWING)

(SEE SCHEDULE DRAWING)

CFM

CFM

CFM

6/6-100-C

6/6-100-B

(2)6-100-A

AIR REGISTER

RETURN OR EXHAUST

SUPPLY AIR DIFFUSER

SUPPLY AIR REGISTER

BD

FD

SD

FS FS

SD

FD

COMBINATION FIRE AND

FLEXIBLE DUCT

SMOKE DAMPER

SMOKE DAMPER

FIRE DAMPER

BD

MOTORIZED DAMPER

BACKDRAFT DAMPER

SPLITTER DAMPER

MANUAL VOLUME DAMPER

(UNLESS NOTED OTHERWISE)

S

M

DIAPHRAGM OPERATOR

MOTOR OPERATOR

SOLENOID OPERATOR

PRESSURE REDUCING VALVE

BALANCING VALVE

CYLINDER OPERATOR

PIPING FLOW DIRECTION

RH

C

C

H

C

HEATING RECOVERY COIL

BACKFLOW PREVENTER

DUCT FLOW DIRECTION

DAMPER

HEATING COIL

COOLING COIL

FILTER

PUMP

NON-RISING STEM GATE VALVE

THREE-WAY CONTROL VALVE

FLOAT OPERATED VALVE

CHECK VALVE

PRESSURE RELIEF VALVE

PLUG VALVE

BUTTERFLY VALVE

ANGLE VALVE

GLOBE VALVE

TWO-WAY CONTROL VALVE

BALL VALVE

O.S & Y. GATE VALVE

STRAINER

SUPPLY FAN,

PROPELLER FAN

BLOW-OFF

STRAINER W/

VALVE

QUICK CONNECT

AIR VENT

SURGE TANK

"A" SHOCK ABSORBER WITH

THERMOSTATIC TRAP

UNION

P.D.I. SIZE

BUCKET TRAP

FLEXIBLE CONNECTION

THERMOSTATIC TRAP

CONCENTRIC REDUCER

ECCENTRIC REDUCER

FLOAT AND

PIPE CAP

SECOND DIMENSION IS SIDE NOT

SHOWN-ALL SIZES ARE IN INCHES

FIRST DIMENSION IS SIDE SHOWN/

RECTANGULAR OR SQUARE DUCT-

AP

UP

AP ACCESS PANEL

TURNING VANES

FLEXIBLE CONNECTION

UPDN DN

TWO SIDED DUCT EXPANSION

OR REDUCTION

TO ROUND OR OVAL)

(RECTANGULAR OR SQUARE

DUCT TRANSITION

OR REDUCTION

ONE SIDED DUCT EXPANSION

24/12

DOUBLE LINE DRAWING

R OR D

UP UPDN DN

R OR D

24/12

OF FLOW)

UP AND DOWN

SUPPLY AIR DUCT TURNING

(SOUND INSULATION)

DUCT WITH LINER

RISE OR DROP IN DUCT

(ARROW INDICATES DIRECTION

VENTILATION LEGEND

SINGLE LINE DRAWING DESCRIPTION

FIRE PROTECTION BRANCH LINE,

CROSS MAIN, AND/OR FEED MAIN

NATURAL GAS/LOW PRESSURE

HOT/CHILLED WATER RETURNHCR

GLYR

GW

FOV

G

FOS

GRAYWATER/ABOVEGROUND

FUEL OIL VENT

FUEL OIL SUPPLY

GLYCOL RETURN

FOG

FOR

DI

F

DF2

CWS

DFO

D

CWR

CW

DEIONIZED WATER

DIESEL FUEL OIL #2

FUEL OIL GAUGE

FUEL OIL RETURN

DOMESTIC COLD WATER

CHILLED WATER SUPPLY

CHILLED WATER RETURN

DIESEL FUEL OIL

DRAIN

MU MAKE-UP WATER

PA

PC

FWP

FWP

FLAMMABLE WASTE PIPING/

UNDERGROUND

ABOVEGROUND

PUMPED CONDENSATE

PROCESS AIR

MP

METH

LPC

LPS

LO

IHW

JO

IW

ICW

IA

LOW PRESSURE CONDENSATE

LOW PRESSURE STEAM

METER PROVER

METHANOL

LUBE OIL

INSTRUMENT AIR

INDUSTRIAL HOT WATER

INDUSTRIAL COLD WATER

INDUSTRIAL WASTE

JOURNAL OIL

BA

CR

CS

CD

CA

BBD

ACID

ACID

ACID

BOOSTER AIR

CONDENSATE DRAIN

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

BOILER BLOW DOWN

COMPRESSED AIR

ACID VENT

ACID WASTE/UNDERGROUND

ACID WASTE/ABOVEGROUND

HPS

HS

HW

HRS

HRR

HR

HPG

HPC

HCS

HIGH PRESSURE STEAM

HEAT RECOVERY SUPPLY

HEAT RECOVERY RETURN

HEATING WATER RETURN

HEATING WATER SUPPLY

DOMESTIC HOT WATER

NATURAL GAS/HIGH PRESSURE

HOT/CHILLED WATER SUPPLY

HIGH PRESSURE CONDENSATE

SWITCH, SOFT WATERSW

FLG FLANGED

CLEANOUT

90° ELBOW UP

HOSE VALVE

STANDPIPE WITH FIRE DEPT.

PIPE GUIDE

WALL HYDRANT

WALL FAUCET

PIPE ANCHOR

90° ELBOW DN

TEE DN

TEE UP

HORIZONTAL SIDEWALL SPRINKLER

HEAD W/ ESCUTCHEON

DRY-TYPE SIDEWALL

DRY-TYPE PENDENT

SPRINKLER HEAD

SPRINKLER HEAD

SPRINKLER HEAD

VERTICAL SIDEWALL

SPRINKLER HEAD

WALL POST INDICATOR VALVE

YARD POST INDICATOR VALVE

EXPOSED HORIZONTAL SIDEWALL

CONNECTION

Y-TYPE FIRE DEPT.

PROCESS FLOW DIRECTION

CONNECTION

SPRINKLER HEAD W/ COVER PLATE

FULLY-RECESSED PENDENT

UPRIGHT SPRINKLER HEAD

SEMI-RECESSED PENDENT

FLUSH TYPE FIRE DEPT.

EXPOSED PENDENT

SPRINKLER HEAD

SPRINKLER HEAD

HS

DENOTES PROJECT RELATED ITEMS

DENOTES EXISTING CONDITIONS

DENOTES ROOM IDENTIFICATION

DENOTES CONNECTION

CONTINUATION

XXXX

XXXX

XXXX

XXXX

XXXX OR XXXXE

PID-101

REFERENCE

TO EXISTING

JAN

KIT

KW

ID

INSTALL

IG

INCL

INV

INSUL

HTG

HT

HW

HVAC

HTR

FLOOR DRAIN

FLOOR CLEANOUT

FLOOR DRAIN

OVERFLOW ROOF

SHOWER DRAIN

WITH FUNNEL

DENOTES REMOVAL

ORD

RD

DRAIN

ROOF DRAIN

FS

AD

SD

CO

FD

FLOOR SINK

AREA DRAIN

G

GR

HD

HP

HR

HB

GA

GAL

GEN

GPM

GALV

FWH

FW

FUT

FT

FTR

FP

FLR

FS

FPM

FLEX

UNLESS NOTED OTHERWISE

VERTICAL VERT

HOSE STATION, HTG WATER SUPPLY

KILOWATT

JANITOR

KITCHEN

INTERUPTABLE GAS

HEATING, VENT & AIR CONDITIONING

INSIDE DIAMETER

INSTALLATION

INSULATION

INVERT

INCLUDE

HOT WATER

HEATER

HEIGHT

HEATING

WALL HYDRANTWH

WATER

WEIGHT

YARD HYDRANTYDH

WTR

WT

WALL FAUCET

VIBRATION

WASTE

WITHOUT

VOLUME

WALL CLEANOUT

WET BULB

VENT THRU ROOF

W/O

WF

WCO

WC

WB

VTR

W/ W

VIB

VOL

WITH

GAS

GALLON PER MINUTE

HOUR, HTG WATER RETURN

GRILLE

HORSEPOWER

HOSE BIB

HEAD

GALVANIZED

GENERAL

GAUGE

GALLON

FEED WATER HEATER

FIN TUBE RADIATION

FIRE SMOKE DAMPER, FLOOR SINK

FEED WATER

FEET

FUTURE

FIRE PROTECTION

FEET PER MINUTE

FLEXIBLE

FLOOR

UNDERGROUNDUG

VACUUM

VELOCITY

VALVE

URINAL

VARIABLE AIR VOLUME

VOLUME DAMPER

VENTILATION

UNIT HEATER

VENT

VEL

VAC

VD

VAV

UR

VLV

V

UNO

UH

VENT

TUBE STEEL

TYPICAL

THROUGH

SYSTEM

TEMPERATURE

TRANSFER AIR

TRENCH DRAIN

THERMOSTAT

TEMPERED WATER

TEMPERATURE CONTROL

TS

TYP

THRU

TEMP

TD

T-STAT

TA

TC

SYS

T

CLG

W

VAC

V

V

UNDERGROUND WATER SERVICE

VACUUM

PLUMBING VENT

VENT

SAN

STM

TRW

T

GW

ST

SAN

SMS

SD

SC

SMR

SANITARY SEWER/UNDERGROUND

STORM SEWER/ABOVEGROUND

GRAYWATER/UNDERGROUND

TREATED RADIATOR WATER

TEMPERED WATER

STEAM

SAND CONVEYING

SANITARY SEWER/ABOVEGROUND

SNOW MELT RETURN

SNOW MELT SUPPLY

SOIL SUBDRAIN

DIM

EQUIP

FG

FIN

FIG

F&T

FD

F

EXH

ESH

EWC

EXIST

DWG

DR

EMS

EL

EA

DIV

DS

DPR

DN

DISCH

CW

DHDC

DIFF

DIA

DF

DET

CWS

CWR

DD

DEPT

DB

CUH

CONT

COOR

CTRS

CONN

CMP

COL

CO

COND

COMP

RLO

RS

S

RL

RHW

RHG

RDF

PG

RECIRCULATING HOT WATER

REFRIGERANT SUCTION

REFRIGERANT LIQUID

RECOVERED LUBE OIL

SOFT WATER

RECOVERED DIESEL FUEL OIL

REFRIGERANT HOT GAS

DISCHARGE

PROPANE GAS

AC

BD

CA

CFM

C

CI

BTUH

L

BM

BTU

BOD

BTM, B/

BLDG

ATFS

ATFR

BA

AHU

ATC

AD

AP

AG

AFF

ADJ

ON CENTEROC

CEILING

STAINLESS STEEL OR SERVICE SINK

BACKFLOW PREVENTER ASSEMBLY

REDUCED PRESSURE ZONE

RECIRCULATING HOT WATER

POWER ROOF VENTILATOR/

PRESSURE REDUCING VALVE

POUND/SQ. IN. ABSOLUTE

REFRIGERANT LIQUIDRL

DIMENSION

EQUIPMENT

FLOOR DRAIN, FIRE DEPARTMENT,

FLOAT AND THERMOSTATIC

EMERGENCY EYEWASH/SHOWER

ELECTRIC WATER COOLER

FIRM GAS

FINISHED

FIGURE

FAHRENHEIT

EXHAUST

EXISTING

ENERGY MANAGEMENT SYSTEM

ELEVATION

DRAIN

DRAWING

EACH

DOWN SPOUT

DISCHARGE

DOWN

DAMPER

DIVISION

SHOWERSHR

SQUARE

SPECIFICATIONS

STATIC PRESSURE

STORM SEWER

STANDARD

SUSPENDED

STRUCTURAL

STEAM

SUSP

STRUC

STD

ST

STM

SPEC

SQ

SS

SK

SP

SINK

ROOM

REFRIGERANT SUCTION

SUPPLY AIR

SECTION

SQUARE FOOT

SHOWER DRAIN, SMOKE DAMPER

SCHEDULE

SANITARY

SECT

SF

SCH

SD

SAN

RS

SA

RPZ

RM

COLD WATER

DISTRICT HEATING, DISTRICT COOLING

CHILLED WATER SUPPLY

CHILLED WATER RETURN

DRINKING FOUNTAIN

DIFFUSER

DIAMETER

DETAIL

DECK DRAIN

DEPARTMENT

DRY BULB TEMP

COMPRESSOR/COMPARTMENT

CABINET UNIT HEATER

CORRUGATED METAL PIPE

CONTINUATION

COORDINATE

CENTERS

CONNECTION

CONDENSATE

CLEANOUT

COLUMN

RETURN AIRRA

ROOF DRAIN

RECESSED

RADIATION

REVISION

RETURN

REFRIGERANT

REFRIGERANT HOT GAS

REQUIRED

RECIRCULATING

RHW

RHG

REV

RET

REQ

REC

REF

RECIRC

RD

RAD

OUTSIDE SCREW & YOKE

OUTSIDE DIAMETER

OPENING

POUND/SQ. IN. GAUGE

POLYVINYL CHLORIDE

OVERFLOW ROOF DRAIN

PNEUMATIC

PSIA

PVC

PSIG

PRV

ORD

OS&Y

PNEUM

OD

OPNG

AIR CONDITIONING

LENGTHL

BACKDRAFT DAMPER

CUBIC FEET PER MINUTE

BRITISH THERMAL UNIT

COMPRESSED AIR

CAST IRON

CENTERLINE

BTU PER HOUR

BOTTOM OF DUCT

BUILDING

BOTTOM

BEAM

AUTOMATIC TRANSMISSION FLUID SUPPLY

AUTOMATIC TRANSMISSION FLUID RETURN

AIR HANDLING UNIT

AUTOMATIC TEMP CONTROL

ABOVE FINISHED FLOOR

BREATHING AIR

ACCESS PANEL

ABOVEGROUND

AREA DRAIN

ADJUSTABLE

MIN MINIMUM

MOUNTED

MOTOR

NATURAL

NUMBER

OUTSIDE AIR

OPPOSED BLADE

NON-POTABLE WATER

NORMALLY OPEN

NORMALLY CLOSED

MOP SINK

NP

OA

OB

NO

NO.,#

MTD

NC

NAT

MS

MOT

MANUAL

MANHOLE

THOUSAND BTU'S/HR

MANUFACTURER

MEZZANINE

MECHANICAL

POUND

LAVATORY

LEAVING WATER TEMPERATURE

LINEAL FEET

MEZZ

MFR

MH

MBH

MECH

LF

MAN

LWT

LB

LAV

ABBREVIATIONS

GW GRAYWATER

F/ FOR

ACR

ACS

AFTERCOOLER RETURN

AFTERCOOLER SUPPLY

JWR

JWS

JACKET WATER RETURN

JACKET WATER SUPPLY

ST STORM SEWER/UNDERGROUND

SW SOFT WATER

OST OVERFLOW STORM SEWER/

UNDERGROUND

OST OVERFLOW STORM SEWER/

ABOVEGROUND

FLAMMABLE WASTE PIPING/

NP NON-POTABLE WATER

UP UPDN DN

RETURN OR OUTDOOR AIR

INTAKE DUCT TURNING UP

AND DOWN

EXHAUST AIR DUCT

TURNING UP AND DOWN

PRESSUREPRESS

ASSY ASSEMBLY

H-STAT HUMIDISTAT

PENETRATIONPEN

VD VD

M

IR IRRIGATION SUPPLY WATER

IR IRRIGATION

M

BOP BOTTOM OF PIPE

TERMINATETERM

GLYS GLYCOL SUPPLY

CCA CONTROL COMPRESSED AIR

EAT ENTERING AIR TEMPERATURE

LEAVING AIR TEMPERATURELAT

HAZARDOUS WASTEHAZ

PHAZ PUMPED HAZARDOUS WASTE

WATER CLOSET

EWT ENTERING WATER TEMPERATURE

CUBIC FEET PER MINUTE, STANDARD CONDITIONSSCFM

EFF EFFICIENCY

FPI FINS PER INCH

HZ FREQUENCY - HERTZ

GPH GALLON PER HOUR

HEAT TRANSFER COEFFICIENTU

RELATIVE HUMIDITYRH

IN INCH

KWH KILOWATT HOUR

PARTS PER MILLIONPPM

REVOLUTIONS PER MINUTERPM

ARCH ARCHITECTURAL / ARCHITECT

ELEC ELECTRICAL

MISC MISCELLANEOUS

NOT IN CONTRACTNIC

NOT TO SCALENTS

PHASEPH

EXT EXTERIOR

HORIZ HORIZONTAL

INT INTERIOR

BHP BRAKE HORSEPOWER

PLUMBINGPLMG

RO REVERSE OSMOSIS

WW WELL WATER

BD BACKWASH DRAIN

RAIN WATER LEADERRWL

FIRE DAMPER

DIST DISTRICT

REPRESENTATIVEREP

SCOPED AREAS

CV

XXX

EQUIPMENT HYDRONIC

VALVE TAG

XXX

EQUIPMENT TAG

M100

HVAC CONTROLS PLAN

BASEMENT LEVEL

NORTHEAST

SCALE: 1/8"=1'-0"

M100

BASEMENT FLOOR NORTHEAST OFFICES CONTROLS PLAN

SCOPED AREAS

T

T

T

T

T

T

T

CUH

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

39VAV

CUH

CUH

VAV

33CV

VAV

31CV

VAV

29CV

VAV

30CV

VAV

34CV

VAV

27CV

VAV

39CV

VAV

32CV

CUH

16CV

CUH

7CV

TO T-STAT ON FIRST

FLOOR SEE M111

CUH

8CV

TO T-STAT ON FIRST FLOOR

SEE M111

T

T

DESIGNED DRAWN CHECKED

SIGNATURE:

PRINTED NAME:

LIC. NO.: DATE:

DATENO. ISSUE RECORD

A pr

0,

- 3

:2 5p m

BA

R

IS

O N

E

IN

C H

O N

O R

IG

IN

AL

D

R

AW

IN

G

IF

N O

T O

N E

IN

C

H O

N T

H

IS

D R

AW

IN

G A

D

JU

ST

S

C

AL

ES

A

C C

O R

D

IN

G

LY

22308.000

RAMP C

RAMP B

RAMP A

HAWTHORNE

KEY PLAN

HAWTHORNE

BAS UPGRADES

CITY OF MINNEAPOLIS

DIVISION OF TRAFFIC AND

PARKING

M

M

M

M M

M

M

M

M

M

M

M

M

T

CUH

15CV

CUH

KEYED NOTES

PROVIDE ADJUSTABLE T-STATS IN ANY CLOSED/OFFICE SPACE.

PROVIDE FLAT PLATE T-STATS IN ANY SHARED/OPEN SPACE.

EXISTING BAS HEAD END AND SERVER LOCATION.

VAV-27

T

VAV

28CV

T 1

GENERAL NOTES

1. FIELD VERIFY TSTAT LOCATIONS. REMOVE AND REPLACE EXISTING T-STATS

AND CONTROL WIRING.

2. FIELD VERIFY ALL EQUIPMENT LOCATIONS. FOR ALL CONTROLLERS REPLACE FIELD-LEVEL

CONTROLLERS AND COMMUNICATION WIRING TO GATEWAY DEVICE.

3. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM FIELD-LEVEL CONTROLLERS TO

GATEWAY DEVICE SHALL BE OPEN PROTOCOL, BACnet MS/TP (NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT NOT LIMITED TO: ARCnet, U-NET, N2, TAC, P1/2 AND COM3/4). CONTRACTOR SHALL PROVIDE ALL PROVISIONS REQURIED FOR BACnet MS/TP COMMUNICATION.

4. PROVIDE PRE-TAB ON ALL EQUIPMENT, HYDRONIC COIL VALVES, AND SUPPLY/EXHAUST/RETURN GRILLES, REGISTERS AND DIFFUSERS. AFTER BAS UPGRADES, REBALANCE SYSTEM TO PRE-TAB

AIRFLOWS.

M

VAV

35CV

VAV

DN

OPEN OFFICE

OPEN OFFICE3

RECEIVING

MECHANICAL/

ELECTRICAL

CONF/TRAINING

CONF

FOCUS FOCUS

VESTIBULE

CONF.

IT ROOM

COPY CENTER

OFFICE

136 BREAK

OUTSIDE STORAGE

TRASH/ LOADING

OPEN PATIO

MENS

WOMEN'S

CONF

LOCKER ROOM

MOTHER'S ROOM

UNISEX

RESTROOM

TRASH/STORAGE

VESTIBULE

ELEV.

CONF

OFFICE

FOCUS

FOCUS

BREAK ROOM

E1

CONF.

OFFICE

CONF.

MECHANICAL

STAIR D

D1

ELEV.

EQUIP.

M110

HVAC CONTROLS PLAN

FIRST FLOOR

RAMP

SCOPED AREAS

KEYED NOTES

1 DEMO EXISTING CO SENSOR. NEW BELIMO CO/NO2 SENSOR WITH SPLASH PROOF HOUSING.

USE EXISTING WIRING PATH AND PROVIDE NEW WIRING/RACEWAYS AS NECESSARY PER

SPECIFICATIONS.

DESIGNED DRAWN CHECKED

SIGNATURE:

PRINTED NAME:

LIC. NO.: DATE:

DATENO. ISSUE RECORD

A pr

0,

- 3

:2 5p m

BA

R

IS

O N

E

IN

C H

O N

O R

IG

IN

AL

D

R

AW

IN

G

IF

N O

T O

N E

IN

C

H O

N T

H

IS

D R

AW

IN

G A

D

JU

ST

S

C

AL

ES

A

C C

O R

D

IN

G

LY

22308.000

RAMP C

RAMP B

RAMP A

HAWTHORNE

KEY PLAN

HAWTHORNE

BAS UPGRADES

CITY OF MINNEAPOLIS

DIVISION OF TRAFFIC AND

PARKING

GENERAL NOTES

1. FIELD VERIFY TSTAT LOCATIONS. REMOVE AND REPLACE EXISTING T-STATS

AND CONTROL WIRING.

2. FIELD VERIFY ALL EQUIPMENT LOCATIONS. FOR ALL CONTROLLERS REPLACE FIELD-LEVEL

CONTROLLERS AND COMMUNICATION WIRING TO GATEWAY DEVICE.

3. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM FIELD-LEVEL CONTROLLERS TO

GATEWAY DEVICE SHALL BE OPEN PROTOCOL, BACnet MS/TP (NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT NOT LIMITED TO: ARCnet, U-NET, N2, TAC, P1/2 AND COM3/4). CONTRACTOR SHALL PROVIDE ALL PROVISIONS REQURIED FOR BACnet MS/TP COMMUNICATION.

SCALE: 1/16"=1'-0"

M110

FIRST FLR (GROUND LEVEL) RAMP CONTROLS PLAN

M111

M112

NO2

CO

NO2CO

NO2CO

M111

FIRST FLOOR

NORTHEAST

SCOPED AREAS

SCALE: 1/8"=1'-0"

M111

FIRST FLOOR NORTHEAST OFFICES CONTROLS PLAN

T

T

T

T

T T

T T

T

T

TT

T

T

T T

CNV

CNV

CNV

UH

CUH

FPVAV

19 18

VAV

VAV

VAV

VAV

VAV

CNV

VAV

CV

CNV

CV

CNV

CV

CNV

CV

CNV

CV

UH

CV

VAV

CV

VAV

CV

CUH

CV 19

CV 18

CV 24

CV

VAV

CV 36

CV

VAV

CV

VAV

CV

CUH

CV 17

CV

VAV

CV

UH

T

TO CUH 8 IN BASEMENT

SEE DWG M100

T

TO CUH 7 IN

BASEMENT

SEE DWG M100

KEYED NOTES

PROVIDE ADJUSTABLE T-STATS IN ANY CLOSED/OFFICE SPACE.

PROVIDE FLAT PLATE T-STATS IN ANY SHARED/OPEN SPACE.

DESIGNED DRAWN CHECKED

SIGNATURE:

PRINTED NAME:

LIC. NO.: DATE:

DATENO. ISSUE RECORD

A pr

0,

- 3

:2 5p m

BA

R

IS

O N

E

IN

C H

O N

O R

IG

IN

AL

D

R

AW

IN

G

IF

N O

T O

N E

IN

C

H O

N T

H

IS

D R

AW

IN

G A

D

JU

ST

S

C

AL

ES

A

C C

O R

D

IN

G

LY

22308.000

RAMP C

RAMP B

RAMP A

HAWTHORNE

KEY PLAN

HAWTHORNE

BAS UPGRADES

CITY OF MINNEAPOLIS

DIVISION OF TRAFFIC AND

PARKING

1 VAV-26

T 2

VAV-25

T 1

T 1

M

M

M M

M

M

M

M

M

M

M M

M

M

M

M

M M

M

M

1 2

M

CV 37

T2

FPVAV

FPVAV

FPVAV

CV

CUH

CUH

CUH

FPVAV

FPVAV

FPVAV

FPVAV

FPVAV

VAV

VAV

GENERAL NOTES

1. FIELD VERIFY TSTAT LOCATIONS. REMOVE AND REPLACE EXISTING T-STATS

AND CONTROL WIRING.

2. FIELD VERIFY ALL EQUIPMENT LOCATIONS. FOR ALL CONTROLLERS REPLACE FIELD-LEVEL

CONTROLLERS AND COMMUNICATION WIRING TO GATEWAY DEVICE.

3. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM FIELD-LEVEL CONTROLLERS TO

GATEWAY DEVICE SHALL BE OPEN PROTOCOL, BACnet MS/TP (NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT NOT LIMITED TO: ARCnet, U-NET, N2, TAC, P1/2 AND COM3/4). CONTRACTOR SHALL PROVIDE ALL PROVISIONS REQURIED FOR BACnet MS/TP COMMUNICATION.

4. PROVIDE PRE-TAB ON ALL EQUIPMENT, HYDRONIC COIL VALVES, AND SUPPLY/EXHAUST/RETURN GRILLES, REGISTERS AND DIFFUSERS. AFTER BAS UPGRADES, REBALANCE SYSTEM TO PRE-TAB

AIRFLOWS.

FPVAV-36

FPVAV

UH

T2

DN

OPEN OFFICE

OPEN OFFICE3

RECEIVING

MECHANICAL/

ELECTRICAL

CONF/TRAINING

CONF

FOCUS FOCUS

VESTIBULE

CONF.

IT ROOM

COPY CENTER

OFFICE

136 BREAK

OUTSIDE STORAGE

TRASH/ LOADING

OPEN PATIO

MENS

WOMEN'S

CONF

LOCKER ROOM

MOTHER'S ROOM

UNISEX

RESTROOM

TRASH/STORAGE

VESTIBULE

ELEV.

CONF

OFFICE

FOCUS

FOCUS

BREAK ROOM

E1

CONF.

OFFICE

CONF.

MECHANICAL

STAIR D

D1

ELEV.

EQUIP.

M112

HVAC CONTROLS PLAN

FIRST FLOOR

SOUTHWEST

SCALE: 1/8"=1'-0"

M112

FIRST FLOOR SOUTHWEST OFFICES CONTROLS PLAN

M M

M M

M

M

M

M

M

M

M

M

M T

M

T

T

T

T

T

M

T

MT

M

T

T

T

T

T

M

M

M

M

T

T

T

T

T

T

T

M

T

KEYED NOTES

CV

CUH

CUH

CV

VAV

CV

VAV

CV

VAV

CV

VAV

CV

VAV

CV

UH

CV 2

CV

VAV

CV 3

CV

CUH

CV

CNV

CV

UH

CV

VAV

CV

VAV

CV

VAV

11CV

CUH

CV

CUH

CV

UH

CV

VAV

CV

CUH

CV

CUH

CUH

EF

CNV

CUH

FPVAV

VAV

VAV

VAV

CUH

VAV

VAV

VAV

VAV

VAV

UH

UH

CUH

UH

VAV

SCOPED AREAS

DESIGNED DRAWN CHECKED

SIGNATURE:

PRINTED NAME:

LIC. NO.: DATE:

DATENO. ISSUE RECORD

A pr

0,

- 3

:2 5p m

BA

R

IS

O N

E

IN

C H

O N

O R

IG

IN

AL

D

R

AW

IN

G

IF

N O

T O

N E

IN

C

H O

N T

H

IS

D R

AW

IN

G A

D

JU

ST

S

C

AL

ES

A

C C

O R

D

IN

G

LY

22308.000

RAMP C

RAMP B

RAMP A

HAWTHORNE

KEY PLAN

HAWTHORNE

BAS UPGRADES

CITY OF MINNEAPOLIS

DIVISION OF TRAFFIC AND

PARKING

VAV

CUH

PROVIDE ADJUSTABLE T-STATS IN ANY CLOSED/OFFICE SPACE.

PROVIDE FLAT PLATE T-STATS IN ANY SHARED/OPEN SPACE.

M

M

CV

VAV

CV

VAV

VAV

VAV

T

RF

T

T

T

T

VAV

T

T

FPVAV

FPVAV

M

1CV 8

FPVAV

FPVAV

CV 9

VAV-7

VAV-14

VAV-15

VAV-5

VAV

T

VAV-16

VAV-6

CV

VAV

CV 1

FPVAV

FPVAV

CV

VAV

FPVAVM

M

M

M

FPVAVFPVAV

GENERAL NOTES

1. FIELD VERIFY TSTAT LOCATIONS. REMOVE AND REPLACE EXISTING T-STATS

AND CONTROL WIRING.

2. FIELD VERIFY ALL EQUIPMENT LOCATIONS. FOR ALL CONTROLLERS REPLACE FIELD-LEVEL

CONTROLLERS AND COMMUNICATION WIRING TO GATEWAY DEVICE.

3. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM FIELD-LEVEL CONTROLLERS TO

GATEWAY DEVICE SHALL BE OPEN PROTOCOL, BACnet MS/TP (NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT NOT LIMITED TO: ARCnet, U-NET, N2, TAC, P1/2 AND COM3/4). CONTRACTOR SHALL PROVIDE ALL PROVISIONS REQURIED FOR BACnet MS/TP COMMUNICATION.

4. PROVIDE PRE-TAB ON ALL EQUIPMENT, HYDRONIC COIL VALVES, AND SUPPLY/EXHAUST/RETURN GRILLES, REGISTERS AND DIFFUSERS. AFTER BAS UPGRADES, REBALANCE SYSTEM TO PRE-TAB

AIRFLOWS.

M401

M401

M130

THIRD FLOOR RAMP

SKYWAY

SCOPED AREAS

SCALE: 1/16"=1'-0"

M130

THIRD FLOOR RAMP / SKYWAY CONTROLS PLAN

KEYED NOTES

DESIGNED DRAWN CHECKED

SIGNATURE:

PRINTED NAME:

LIC. NO.: DATE:

DATENO. ISSUE RECORD

A pr

0,

- 3

:2 6p m

BA

R

IS

O N

E

IN

C H

O N

O R

IG

IN

AL

D

R

AW

IN

G

IF

N O

T O

N E

IN

C

H O

N T

H

IS

D R

AW

IN

G A

D

JU

ST

S

C

AL

ES

A

C C

O R

D

IN

G

LY

22308.000

RAMP C

RAMP B

RAMP A

HAWTHORNE

KEY PLAN

HAWTHORNE

BAS UPGRADES

CITY OF MINNEAPOLIS

DIVISION OF TRAFFIC AND

PARKING

GENERAL NOTES

1. FIELD VERIFY TSTAT LOCATIONS. REMOVE AND REPLACE EXISTING

T-STATS

AND CONTROL WIRING.

2. FIELD VERIFY ALL EQUIPMENT LOCATIONS. FOR ALL CONTROLLERS

REPLACE FIELD-LEVEL CONTROLLERS AND COMMUNICATION WIRING TO

GATEWAY DEVICE.

3. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM FIELD-LEVEL

CONTROLLERS TO GATEWAY DEVICE SHALL BE OPEN PROTOCOL, BACnet

MS/TP (NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT

NOT LIMITED TO: ARCnet, U-NET, N2, TAC, P1/2 AND COM3/4).

CONTRACTOR SHALL PROVIDE ALL PROVISIONS REQURIED FOR BACnet

MS/TP COMMUNICATION.

1 DEMO EXISTING CO SENSOR. NEW BELIMO CO/NO2 SENSOR WITH

SPLASH PROOF HOUSING. USE EXISTING WIRING PATH AND PROVIDE

NEW WIRING/RACEWAYS AS NECESSARY PER SPECIFICATIONS.

NO2CO

NO2

CO

NO2

CO

36" Ø EXHAUST DUCT TERMINNATED

12" AFF & CONT. UP (TYP. OF 4)

M402

M140

FOURTH FLOOR RAMP

SCOPED AREAS

DESIGNED DRAWN CHECKED

SIGNATURE:

PRINTED NAME:

LIC. NO.: DATE:

DATENO. ISSUE RECORD

A pr

0,

- 3

:2 6p m

BA

R

IS

O N

E

IN

C H

O N

O R

IG

IN

AL

D

R

AW

IN

G

IF

N O

T O

N E

IN

C

H O

N T

H

IS

D R

AW

IN

G A

D

JU

ST

S

C

AL

ES

A

C C

O R

D

IN

G

LY

22308.000

RAMP C

RAMP B

RAMP A

HAWTHORNE

KEY PLAN

HAWTHORNE

BAS UPGRADES

CITY OF MINNEAPOLIS

DIVISION OF TRAFFIC AND

PARKING

GENERAL NOTES

1. FIELD VERIFY TSTAT LOCATIONS. REMOVE AND REPLACE EXISTING

T-STATS

AND CONTROL WIRING.

2. FIELD VERIFY ALL EQUIPMENT LOCATIONS. FOR ALL CONTROLLERS

REPLACE FIELD-LEVEL CONTROLLERS AND COMMUNICATION WIRING TO

GATEWAY DEVICE.

3. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM FIELD-LEVEL

CONTROLLERS TO GATEWAY DEVICE SHALL BE OPEN PROTOCOL, BACnet

MS/TP (NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT

NOT LIMITED TO: ARCnet, U-NET, N2, TAC, P1/2 AND COM3/4).

CONTRACTOR SHALL PROVIDE ALL PROVISIONS REQURIED FOR BACnet

MS/TP COMMUNICATION.

EF

36" Ø EXHAUST DUCT

UP/DN (TYP. OF 4)

SCALE: 1/16"=1'-0"

M140

FOURTH FLOOR RAMP / SKYWAY CONTROLS PLAN

M170

SEVENTH FLOOR RAMP

ROOF LEVEL

DESIGNED DRAWN CHECKED

SIGNATURE:

PRINTED NAME:

LIC. NO.: DATE:

DATENO. ISSUE RECORD

A pr

0,

- 3

:2 6p m

BA

R

IS

O N

E

IN

C H

O N

O R

IG

IN

AL

D

R

AW

IN

G

IF

N O

T O

N E

IN

C

H O

N T

H

IS

D R

AW

IN

G A

D

JU

ST

S

C

AL

ES

A

C C

O R

D

IN

G

LY

22308.000

RAMP C

RAMP B

RAMP A

HAWTHORNE

KEY PLAN

HAWTHORNE

BAS UPGRADES

CITY OF MINNEAPOLIS

DIVISION OF TRAFFIC AND

PARKING

SCOPED

AREAS

SCALE: 1/4"=1'-0"

M170

MECHANICAL LAYOUT ROOF LEVEL PARKING

EF

EF

EF

EF

EF

EF SHALL BE SEQUENCED WITH GROUND FLOOR CO/NO2 SENSORS. SEE

SEQUENCE OF OPERATION.

EF SHALL BE SEQUENCED WITH THIRD FLOOR CO/NO2 SENSORS. SEE

SEQUENCE OF OPERATION.

GENERAL NOTES

1. FIELD VERIFY TSTAT LOCATIONS. REMOVE AND REPLACE EXISTING

T-STATS

AND CONTROL WIRING.

2. FIELD VERIFY ALL EQUIPMENT LOCATIONS. FOR ALL CONTROLLERS

REPLACE FIELD-LEVEL CONTROLLERS AND COMMUNICATION WIRING

TO GATEWAY DEVICE.

3. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM

FIELD-LEVEL CONTROLLERS TO GATEWAY DEVICE SHALL BE OPEN

PROTOCOL, BACnet MS/TP (NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT NOT LIMITED TO: ARCnet, U-NET, N2, TAC, P1/2

AND COM3/4). CONTRACTOR SHALL PROVIDE ALL PROVISIONS

REQURIED FOR BACnet MS/TP COMMUNICATION.

4. PROVIDE PRE-TAB ON ALL EQUIPMENT, HYDRONIC COIL VALVES, AND

SUPPLY/EXHAUST/RETURN GRILLES, REGISTERS AND DIFFUSERS.

AFTER BAS UPGRADES, REBALANCE SYSTEM TO PRE-TAB AIRFLOWS.

KEYED NOTES

M400

MECHANICAL STAIR C PLANS

BASEMENT THRU THIRD LEVEL

EAST AREA

SCALE: 1/8"=1'-0"

M400

STAIR C THIRD LEVEL ENLARGED CONTROLS PLAN

SCALE: 1/8"=1'-0"

M400

STAIR C PENTHOUSE ENLARGED CONTROLS PLAN

SCALE: 1/8"=1'-0"

M400

STAIR C LEVELS 4 THRU 6 ENGLARGED CONTROLS PLAN

SCALE: 1/8"=1'-0"

M400

STAIR C GROUND LEVEL ENLARGED CONTROLS PLAN

SCALE: 1/8"=1'-0"

M400

STAIR C SEVENTH LEVEL ENLARGED CONTROLS PLAN

SCALE: 1/8"=1'-0"

M400

STAIR C 050 BASEMENT ENLARGED CONTROLS PLAN

T

M

M

M M

T

M

M

M M

DESIGNED DRAWN CHECKED

SIGNATURE:

PRINTED NAME:

LIC. NO.: DATE:

DATENO. ISSUE RECORD

A pr

0,

- 3

:2 6p m

BA

R

IS

O N

E

IN

C H

O N

O R

IG

IN

AL

D

R

AW

IN

G

IF

N O

T O

N E

IN

C

H O

N T

H

IS

D R

AW

IN

G A

D

JU

ST

S

C

AL

ES

A

C C

O R

D

IN

G

LY

22308.000

RAMP C

RAMP B

RAMP A

HAWTHORNE

KEY PLAN

HAWTHORNE

BAS UPGRADES

CITY OF MINNEAPOLIS

DIVISION OF TRAFFIC AND

PARKING

TYP. ALL VIEWS ON SHEET

T

TO AHU-3

CUH

CV

CUH

AHU

T T

UH

UH

CV

UH

CV

UH

AHU

CV1

AHU

CV2

FC

CV2

FC

CV1

FC

P

P

P

P

WH

HEX

P

UH

T1

M M M

GENERAL NOTES

1. FIELD VERIFY TSTAT LOCATIONS. REMOVE AND REPLACE EXISTING T-STATS

AND CONTROL WIRING.

2. FIELD VERIFY ALL EQUIPMENT LOCATIONS. FOR ALL CONTROLLERS REPLACE FIELD-LEVEL

CONTROLLERS AND COMMUNICATION WIRING TO GATEWAY DEVICE.

3. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM FIELD-LEVEL CONTROLLERS TO

GATEWAY DEVICE SHALL BE OPEN PROTOCOL, BACnet MS/TP (NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT NOT LIMITED TO: ARCnet, U-NET, N2, TAC, P1/2 AND COM3/4). CONTRACTOR SHALL PROVIDE ALL PROVISIONS REQURIED FOR BACnet MS/TP COMMUNICATION.

4. PROVIDE PRE-TAB ON ALL EQUIPMENT, HYDRONIC COIL VALVES, AND SUPPLY/EXHAUST/RETURN GRILLES, REGISTERS AND DIFFUSERS. AFTER BAS UPGRADES, REBALANCE SYSTEM TO PRE-TAB

AIRFLOWS.

KEYED NOTES

PROVIDE ADJUSTABLE T-STATS IN ANY CLOSED/OFFICE SPACE.

PROVIDE FLAT PLATE T-STATS IN ANY SHARED/OPEN SPACE.

AREA SHOWN FOR TAB REFERENCE.

SUMP PUMP LOCATION SHOWN FOR ALARM COORDINATION.

SCOPED AREA

M401

MECHANICAL ROOM T112 & T137

SECOND LEVEL

WEST AND SOUTH AREAS

SCALE: 1/8"=1'-0"

M401

SW OFFICE AREA NORTHERN MECH. ROOM ENLARGED CONTROLS PLAN

SCALE: 1/8"=1'-0"

M401

SW OFFICE AREA SOUTHERN MECH. ROOM ENLARGED CONTROLS PLAN

M

M

DESIGNED DRAWN CHECKED

SIGNATURE:

PRINTED NAME:

LIC. NO.: DATE:

DATENO. ISSUE RECORD

A pr

0,

- 3

:2 6p m

BA

R

IS

O N

E

IN

C H

O N

O R

IG

IN

AL

D

R

AW

IN

G

IF

N O

T O

N E

IN

C

H O

N T

H

IS

D R

AW

IN

G A

D

JU

ST

S

C

AL

ES

A

C C

O R

D

IN

G

LY

22308.000

RAMP C

RAMP B

RAMP A

HAWTHORNE

KEY PLAN

HAWTHORNE

BAS UPGRADES

CITY OF MINNEAPOLIS

DIVISION OF TRAFFIC AND

PARKING

CV

UH

UH

WH

AHU

UH

AHU

CV1

AHU

CV2 M

UH

CV

SCOPED AREAS

SCALE: 1/16"=1'-0"

M401

EAST SKYWAY HVAC CONTROLS PLAN

T3

T

TO AHU-43

M402

M400

GENERAL NOTES

1. FIELD VERIFY TSTAT LOCATIONS. REMOVE AND REPLACE EXISTING T-STATS

AND CONTROL WIRING.

2. FIELD VERIFY ALL EQUIPMENT LOCATIONS. FOR ALL CONTROLLERS REPLACE FIELD-LEVEL

CONTROLLERS AND COMMUNICATION WIRING TO GATEWAY DEVICE.

3. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM FIELD-LEVEL CONTROLLERS TO

GATEWAY DEVICE SHALL BE OPEN PROTOCOL, BACnet MS/TP (NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT NOT LIMITED TO: ARCnet, U-NET, N2, TAC, P1/2 AND COM3/4). CONTRACTOR SHALL PROVIDE ALL PROVISIONS REQURIED FOR BACnet MS/TP COMMUNICATION.

4. PROVIDE PRE-TAB ON ALL EQUIPMENT, HYDRONIC COIL VALVES, AND SUPPLY/EXHAUST/RETURN GRILLES, REGISTERS AND DIFFUSERS. AFTER BAS UPGRADES, REBALANCE SYSTEM TO PRE-TAB

AIRFLOWS.

KEYED NOTES

EXISTING BAS CONTROL PANEL. PROVIDE NEW PANEL,

WIRING, AND INTEGRATIONS TO BAS AS REQUIRED.

DEMO EXISTING ENERGY METERING CONTROL PANEL.

PROVIDE FLAT PLATE T-STATS IN ANY SHARED/OPEN SPACE.3

M402

MECHANICAL ROOMS

AND SOUTH SKYWAY

THIRD LEVEL

SCALE: 1/4"=1'-0"

M402

THIRD LEVEL WEST MECHANICAL FLOOR LAYOUT

SCALE: 1/4"=1'-0"

M402

MECHANICAL ROOM 305 ENLARGED PLAN

SCALE: 1/4"=1'-0"

M402

MECHANICAL ROOM 304 ENLARGED PLAN

DESIGNED DRAWN CHECKED

SIGNATURE:

PRINTED NAME:

LIC. NO.: DATE:

DATENO. ISSUE RECORD

A pr

0,

- 3

:2 6p m

BA

R

IS

O N

E

IN

C H

O N

O R

IG

IN

AL

D

R

AW

IN

G

IF

N O

T O

N E

IN

C

H O

N T

H

IS

D R

AW

IN

G A

D

JU

ST

S

C

AL

ES

A

C C

O R

D

IN

G

LY

22308.000

RAMP C

RAMP B

RAMP A

HAWTHORNE

KEY PLAN

HAWTHORNE

BAS UPGRADES

CITY OF MINNEAPOLIS

DIVISION OF TRAFFIC AND

PARKING

SCOPED

AREAS

T

TO AHU-41

M402

M

M

AHU

CV2

AHU

T

UH

MM

AHU

CV1

AHU

CV2

M M

AHU

CV1

AHU

CV1

AHU

AHU

EF

UH

M400

AHU

CV1

GENERAL NOTES

1. FIELD VERIFY TSTAT LOCATIONS. REMOVE AND REPLACE EXISTING T-STATS

AND CONTROL WIRING.

2. FIELD VERIFY ALL EQUIPMENT LOCATIONS. FOR ALL CONTROLLERS REPLACE

FIELD-LEVEL CONTROLLERS AND COMMUNICATION WIRING TO GATEWAY DEVICE.

3. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM FIELD-LEVEL

CONTROLLERS TO GATEWAY DEVICE SHALL BE OPEN PROTOCOL, BACnet MS/TP

(NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT NOT LIMITED

TO: ARCnet, U-NET, N2, TAC, P1/2 AND COM3/4). CONTRACTOR SHALL PROVIDE ALL PROVISIONS REQURIED FOR BACnet MS/TP COMMUNICATION.

4. PROVIDE PRE-TAB ON ALL EQUIPMENT, HYDRONIC COIL VALVES, AND

SUPPLY/EXHAUST/RETURN GRILLES, REGISTERS AND DIFFUSERS. AFTER BAS

UPGRADES, REBALANCE SYSTEM TO PRE-TAB AIRFLOWS.

KEYED NOTES

1 PROVIDE ADJUSTABLE T-STATS IN ANY CLOSED/OFFICE SPACE.

CONTROL POINTS LIST

POINT NAME POINT TYPE SYSTEM COMPONENT DESCRIPTION WORK REQUIRED

CWSupplyTemp AI CHILLED WATER SYSTEM CHILLED WATER SUPPLY TEMP PROVIDE NEW SENSOR TO REPLACE EXISTING

CWReturnTemp AI CHILLED WATER SYSTEM CHILLED WATER RETURN TEMP PROVIDE NEW SENSOR TO REPLACE EXISTING

CWPStatus1 DI CHILLED WATER SYSTEM CHILLED WATER DISTRIBUTION PUMP 1 STATUS REUSE EXISTING CONTROL

CWPEnable1 DO CHILLED WATER SYSTEM CHILLED WATER DISTRIBUTION PUMP 1 COMMAND REUSE EXISTING CONTROL

CWPStatus2 DI CHILLED WATER SYSTEM CHILLED WATER DISTRIBUTION PUMP 2 STATUS REUSE EXISTING CONTROL

CWPEnable2 DO CHILLED WATER SYSTEM CHILLED WATER DISTRIBUTION PUMP 2 COMMAND REUSE EXISTING CONTROL

HWPStatus3 DI HEATING WATER SYSTEM HEATING WATER DISTRIBUTION PUMP 3 STATUS REUSE EXISTING CONTROL

HWPEnable3 DO HEATING WATER SYSTEM HEATING WATER DISTRIBUTION PUMP 3 COMMAND REUSE EXISTING CONNECTION

HWPStatus4 DI HEATING WATER SYSTEM HEATING WATER DISTRIBUTION PUMP 4 STATUS REUSE EXISTING CONTROL

HWPEnable4 DO HEATING WATER SYSTEM HEATING WATER DISTRIBUTION PUMP 4 COMMAND REUSE EXISTING CONNECTION

StmPressure AI DISTRICT STEAM SYSTEM STEAM SYSTEM PRESSURE REUSE EXISTING SENSOR

HWReturnTemp AI HEATING WATER RETURN HEATING WATER RETURN TEMP PROVIDE NEW SENSOR TO REPLACE EXISTING

HWSupplyTemp AI HEATING WATER SUPPLY HEATING WATER SUPPLY TEMP PROVIDE NEW SENSOR TO REPLACE EXISTING

1/3-StmValvePosition AO DISTRICT STEAM SYSTEM 1/3-STEAM CONTROL VALVE FOR HX REUSE EXISTING VALVE

2/3-StmValvePosition AO DISTRICT STEAM SYSTEM 2/3-STEAM CONTROL VALVE FOR HX REUSE EXISTING VALVE

OAT AI BAS SYSTEM OUTDOOR AIR TEMPERATURE SENSOR PROVIDE NEW SENSOR TO REPLACE EXISTING

OARH AI BAS SYSTEM OUTDOOR AIR HUMIDITY SENSOR PROVIDE NEW SENSOR TO REPLACE EXISTING M500

MECHANICAL ROOM 050

STAIR C BASEMENT LEVEL

HW & CW PLANT CONTROLS

AI AI

DO DO

M

M

AI AI

DO DOAO AO

EQUIPMENT LOCATION

DESIGNED DRAWN CHECKED

SIGNATURE:

PRINTED NAME:

LIC. NO.: DATE:

DATENO. ISSUE RECORD

A pr

0,

- 3

:2 6p m

BA

R

IS

O N

E

IN

C H

O N

O R

IG

IN

AL

D

R

AW

IN

G

IF

N O

T O

N E

IN

C

H O

N T

H

IS

D R

AW

IN

G A

D

JU

ST

S

C

AL

ES

A

C C

O R

D

IN

G

LY

22308.000

RAMP C

RAMP B

RAMP A

HAWTHORNE

KEY PLAN

HAWTHORNE

BAS UPGRADES

CITY OF MINNEAPOLIS

DIVISION OF TRAFFIC AND

PARKING

STEAM/HEATING WATER HX AND PUMPS - SEQUENCE OF OPERATION

SYSTEM OPERATES CONSTANTLY. PROVIDE MEANS TO MANUALLY TURN SYSTEM ON/OFF FROM USER INTERFACE.

ENABLE MODE:

· DISTRIBUTION PUMPS: START/STOP THE LEAD HW PUMP AND RUN CONTINUOUSLY. THE PUMPS ARE DESIGNED TO RUN

LEAD/STANDBY. THE PUMPS SHALL ROTATE THEIR LEAD DESIGNATION WEEKLY TO MAINTAIN EVEN RUN TIMES. WHEN ROTATING, START THE NEW LEAD PUMP PRIOR TO STOPPING THE FORMER LEAD PUMP. STANDBY PUMP SHALL

AUTOMATICALLY START UPON FAILURE OF THE LEAD PUMP DURING NOMINAL CONDITIONS.

· 1/3 & 2/3 STEAM CONTROL VALVES AND HX: UPON THE SYSTEM BEING ENABLED, THE 1/3 & 2/3 STEAM VALVES WILL BE MODULATED BY A PID CONTROL LOOP TO MAINTAIN THE REQUIRED HEATING WATER TEMPERATURE SETPOINT. THE VALVES

WILL BE CONTROLLED IN THE FOLLOWING MANNER:

·· THE 1/3 VALVE WILL BE MODULATED FIRST.

·· IF THE OUTPUT OF THE PID CONTROL LOOP EXCEEDS 25% (ADJUSTABLE) FOR MORE THAN 2 MINUTES (ADJ.), THE 2/3

VALVE WILL BECOME THE FIRST VALVE MODULATED MAKING THE 1/3 VALVE CONTROL RANGE SWITCH TO THE 66% TO

100% OUTPUT RANGE OF THE PID CONTROL LOOP.

·· IF THE OUTPUT OF THE PID CONTROL LOOP EXCEEDS 60% (ADJUSTABLE) FOR MORE THAN 2 MINUTES (ADJ.), THE 1/3 VALVE WILL BECOME THE FIRST VALVE MODULATED (THE 1/3 VALVE WILL BE 100% OPEN AT THIS TIME) MAKING THE 2/3 VALVE CONTROL RANGE SWITCH TO THE 33% TO 100% OUTPUT RANGE OF THE PID CONTROL LOOP (THE 2/3 VALVE WILL

BE MODULATING AT THIS TIME).

·· THE REVERSE SEQUENCE SHALL OCCUR AT THE 40% (ADJ.) AND THE 25% (ADJ.) POINTS AS STEAM DEMAND DECREASES.

·· THE SEQUENCE SHALL ALSO RESET ANYTIME THE OUTPUT OF THE PID CONTROL LOOP EQUALS ZERO.

· HEATING WATER SUPPLY TEMPERATURE RESET: THE HEATING WATER SUPPLY TEMP SHALL LINEARLY RESET BASED ON OA TEMPERATURE. AS THE OAT RISES FROM 20°F (ADJ.) TO 65°F (ADJ.), THE HEATING WATER SUPPLY TEMP SETPOINT SHALL

RESET FROM 175°F (ADJ.) TO 120°F (ADJ.).

DISABLE MODE:

· 1/3 & 2/3 STEAM CONTROL VALVES AND HX: UPON THE SYSTEM BEING DISABLED, THE STEAM HX CONTROL VALVES SHALL

CLOSE.

· DISTRIBUTION PUMPS: AFTER THE STEAM VALVES HAVE BEEN CLOSED FOR 5 MIN (ADJ.), THE PUMPS SHALL TURN OFF.

ALARM MODES:

· HI/LO TEMP ALARM: UPON SENSING HEATING WATER SUPPLY TEMP LOWER THAN 100°F (ADJ.) OR HIGHER THAN 190°F (ADJ.)

FOR 20 MINUTES (ADJ.), THE BAS SHALL INITIATE AN ALARM.

· MOTOR ALARM: ANY STATUS THAT DOESN'T MATCH COMMAND WITHIN 30 SEC. (ADJ.).

GENERAL NOTES

1. SOME CONTROL POINTS ARE INTENDED FOR MONITORING ONLY. EXISTING EQUIPMENT TO FOLLOW SEQUENCE OF

OPERATION AS DESCRIBED ON THIS SHEET. TEMPERATURE CONTROL CONTRACTOR TO PROVIDE DEFICIENCY REPORT TO

ENGINEER AND OWNER OF ALL EXISTING TO REMAIN CONTROL DEVICES.

2. CONTROLS CONTRACTOR IS RESPONSIBLE FOR REMOVING ANY DEFUNCT EXISTING CONTROLS INCLUDING, WIRING, TUBING, CONDUIT, PANELS, ACTUATORS, JUNCTION BOXES, ETC. NO CONTROLS EQUIPMENT SHALL BE ABANDONED IN

PLACE.

3. CONTROLS CONTRACTOR SHALL PROVIDE ALL PROVISIONS FOR ANY NEW LOGIC CONTROLLERS NEEDED INCLUDING DRIVERS, WIRING, AND COMMUNICATION CABLING TO MEET THE SEQUENCE OF OPERATION. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM FIELD-LEVEL CONTROLLERS TO GATEWAY DEVICE SHALL BE OPEN PROTOCOL, BACNET MS/TP (NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT NOT LIMITED TO: ARCNET, U-NET, N2, TAC, P1/2 AND COM3/4). CONTRACTOR SHALL PROVIDE ALL PROVISIONS REQUIRED FOR BACNET MS/TP COMMUNICATION.

4. ALL EXISTING GRAPHICS TO BE UPDATED TO WEBCTRL 10 STANDARD GRAPHICS PACKAGE. PROVIDE GRAPHICS

CONFIGURATION THAT MEETS THE CITY OF MINNEAPOLIS GRAPHICS STANDARD.

KEYED NOTES

1 PROVIDE NEW CONTROL DEVICE.

PROVIDE NEW COMBINATION OAT/OARH SENSOR WITH

RADIATION SHIELD. INSTALL SENSORS AWAY FROM

DIRECT SUNLIGHT, BUILDING EXHAUST, OR OTHER

HEATING/COOLING SOURCES.

IF SPECIFIED COMMUNICATION PROTOCOL CAN'T BE

MET WITH EXISTING BAS CONTROLLER, PROVIDE NEW

BAS CONTROLLER.

EXISTING BAS CONTROLLER HAS FAILED OUTPUTS.

PROVIDE NEW BAS CONTROLLER.

AI

AI

AI

DI DIDIDI

M

CHILLED WATER HX AND PUMPS - SEQUENCE OF OPERATION

SYSTEM OPERATES BASED ON OAT ENABLE SETPOIN. PROVIDE MEANS TO MANUALLY TURN SYSTEM ON/OFF FROM USER

INTERFACE.

ENABLE MODE:

· OAT ENABLE: WHEN THE OAT RISES ABOVE THE CHW ENABLE SETPOINT OF 55°F (ADJ. W/ 3°F DB) THE CHILLED WATER

SYSTEM SHALL BE ENABLED.

· DISTRIBUTION PUMPS: START/STOP THE LEAD CHW PUMP AND RUN CONTINUOUSLY. THE PUMPS ARE DESIGNED TO RUN

LEAD/STANDBY. THE PUMPS SHALL ROTATE THEIR LEAD DESIGNATION WEEKLY TO MAINTAIN EVEN RUN TIMES. WHEN ROTATING, START THE NEW LEAD PUMP PRIOR TO STOPPING THE FORMER LEAD PUMP. STANDBY PUMP SHALL

AUTOMATICALLY START UPON FAILURE OF THE LEAD PUMP DURING NOMINAL CONDITIONS.

DISABLE MODE:

· OAT DISABLE: WHEN THE OAT FALLS BELOW THE CHW ENABLE SETPOINT, THE CHILLED WATER SYSTEM SHALL BE DISABLED.

· DISTRIBUTION PUMPS: THE PUMPS SHALL TURN OFF.

ALARM MODES:

· HI TEMP ALARM: UPON SENSING CHILLED WATER SUPPLY TEMP HIGHER THAN 50°F (ADJ.) FOR 20 MINUTES (ADJ.), THE BAS

SHALL INITIATE AN ALARM.

· MOTOR ALARM: ANY STATUS THAT DOESN'T MATCH COMMAND WITHIN 30 SEC. (ADJ.).

M501

MECHANICAL ROOM 304

FIRST FLOOR SW OFFICES

AHU-1 CONTROLS

AI

AI

DO

AO DI

AIAIDO

M

M

AOAO

CONTROL POINTS LIST

POINT NAME POINT TYPE SYSTEM COMPONENT DESCRIPTION WORK REQUIRED

MaDmpr AO MIXED AIR MIXED AIR DAMPER CONTROL REUSE EXISTING ACTUATORS

RlfDmpr AO RELIEF AIR RELIEF AIR DAMPER CONTROL REUSE EXISTING ACTUATOR

MaTemp AI MIXED AIR MIXED AIR TEMPERATURE SENSOR REUSE EXISTING SENSOR

RFanStatus AI RETURN FAN RETURN FAN REUSE EXISTING CONTROL (HZ FEEDBACK W/ DIGITAL STS)

RFanEnable DO RETURN FAN RETURN FAN REUSE EXISTING CONNECTION

RFanSpeed AO RETURN FAN RETURN FAN REUSE EXISTING CONNECTION

FrzStat DI MIXED AIR MIXED AIR FREEZE STAT LOW LIMIT ALARM REUSE EXISTING SENSOR HtgValvePosition AO HEATING WATER COIL HEATING WATER CONTROL VALVE REUSE EXISTING VALVE/ACTUATOR

ClgValvePosition AO CHILLED WATER COIL CHILLED WATER CONTROL VALVE REUSE EXISTING VALVE/ACTUATOR

SFanStatus AI SUPPLY FAN SUPPLY FAN REUSE EXISTING CONTROL (HZ FEEDBACK W/ DIGITAL STS)

SFanEnable DO SUPPLY FAN SUPPLY FAN REUSE EXISTING CONNECTION

SFanSpeed AO SUPPLY FAN SUPPLY FAN REUSE EXISTING CONNECTION

RaTemp AI RETURN AIR RETURN AIR TEMPERATURE SENSOR REUSE EXISTING SENSOR

RaHum AI RETURN AIR RETURN AIR HUMIDITY SENSOR PROVIDE NEW SENSOR TO REPLACE EXISTING

RaSmk DI RETURN AIR RETURN AIR SMOKE DETECTOR REUSE EXISTING SENSOR

SaPressure AI SUPPLY AIR SUPPLY AIR PRESSURE SENSOR PROVIDE NEW SENSOR TO REPLACE EXISTING

SaTemp AI SUPPLY AIR SUPPLY AIR TEMPERATURE SENSOR REUSE EXISTING SENSOR

ZnPressure AI ZONE AREA ZONE PRESSURE SENSOR PROVIDE NEW SENSOR TO REPLACE EXISTING

AO

AHU-1 - SEQUENCE OF OPERATION

SYSTEM OPERATES AS OCCUPIED/UNOCCUPIED ACCORDING TO ITS OPTIMAL OPERATING SCHEDULE.

OCCUPIED MODE:

· START/STOP THE SUPPLY FAN AND RETURN FAN ACCORDING TO THE OPTIMAL START SCHEDULE AND RUN CONTINUOUSLY.

UNIT SHALL OPERATE IN FULL RECIRCULATION MODE (RETURN AIR DAMPER 100% OPEN, OA DAMPER CLOSED, AND RELIEF DAMPER CLOSED) UNTIL SPACE SET POINTS ARE MET OR SPACES ARE OCCUPIED BY MEANS OF OCCUPANCY SENSOR. THEN

UNIT SHALL RUN IN MINIMUM VENTILATION MODE.

· SUPPLY FAN SPEED CONTROL: THE VARIABLE SPEED DRIVE CONTROLLING THE SUPPLY FAN MOTOR SPEED SHALL MAINTAIN THE STATIC PRESSURE SETPOINT 1 INWC (ADJ.) AT THE STATIC PRESSURE SENSOR, LOCATED A MINIMUM 2/3S DOWN THE SUPPLY DUCT MAIN. THE SUPPLY DUCT STATIC PRESSURE SHALL AUTOMATICALLY RESET DOWNWARDS FROM DEFAULT (AS SET BY THE BALANCING CONTRACTOR) IN ORDER TO KEEP AT LEAST ONE ASSOCIATED VAV BOX CONTROL DAMPER BETWEEN

95% AND 99% OPEN POSITION.

· RETURN FAN SPEED CONTROL: THE VARIABLE SPEED DRIVE CONTROLLING THE RETURN FAN MOTORS SPEED SHALL TRACK THE SUPPLY FAN SPEED AND CALCULATE THE RETURN FAN SPEED SIGNAL AS A PERCENTAGE OF SUPPLY FAN SPEED SIGNAL VIA THE RETURN FAN SPEED TRACKING SETPOINT OF 85% (ADJ.). I.E. - SUPPLY FAN SPEED SIGNAL OF 74.6% MULTIPLIED BY THE RETURN FAN SPEED TRACKING SETPOINT OF 85%, WILL GIVE YOU A RETURN FAN SPEED OF 63.4%.

· MINIMUM VENTILATION: OPEN THE OUTDOOR AIR DAMPER AND MODULATE OUTDOOR, RETURN AND RELIEF DAMPERS TO MAINTAIN MINIMUM DAMPER POSITION SETPOINT. REFER TO SCHEDULE AND COORDINATE DAMPER SETPOINT WITH

BALANCING CONTRACTOR.

· SUPPLY AIR TEMPERATURE RESET: THE SUPPLY AIR TEMPERATURE SETPOINT SHALL RESET BETWEEN THE MINIMUM AND MAXIMUM SUPPLY AIR TEMPERATURE SETPOINTS OF 55°F (ADJ.) AND 65°F (ADJ.). THE ACTIVE SUPPLY AIR TEMPERATURE SETPOINT SHALL BE CALCULATED BASED ON THE MAXIMUM SPACE COOLING SIGNAL OF APPROPRIATE VAV BOXES AS

DETERMINED BY THE COMMISSIONING AUTHORITY AND/OR OWNER.

· ECONOMIZER COOLING: WHEN BOTH OUTDOOR AIR DEWPOINT AND DRY-BULB TEMPERATURES ARE BELOW THEIR RESPECTIVE ECONOMIZER ENABLE SETPOINTS OF 67°F DRY-BULB (ADJ.) AND 52°F DEWPOINT (ADJ.), THE UNIT SHALL ENTER ECONOMIZER MODE. MODULATE THE OUTDOOR AIR AND RETURN AIR DAMPERS TO MAINTAIN A MIXED AIR TEMPERATURE SETPOINT. THE MIXED AIR TEMPERATURE SETPOINT SHALL TRACK THE SUPPLY AIR TEMPERATURE SETPOINT WITH AN

ADJUSTABLE OFFSET INITIALLY SET AT +1°F. (SAT SP = 55°F THEN MAT SP = 56°F)

· SPACE PRESSURE CONTROL: PROVIDE MEANS TO SWITCH CONTROL STRATEGIES FOR SPACE PRESSURE BETWEEN: 1) THE RELIEF DAMPER TRACKING THE OA DAMPER. 2) THE RELIEF DAMPER MAINTAINING THE SPACE PRESSURE SETPOINT OF 0.04

INWC (ADJ.) BY MODULATING +/- 15% (ADJ.) OF THE OA DAMPER SIGNAL.

· CHW COOLING MODE: WHEN EITHER OUTDOOR AIR DRY-BULB OR DEWPOINT ARE ABOVE THEIR RESPECTIVE ECONOMIZER ENABLE SETPOINTS, THE UNIT DAMPERS SHALL BE CONTROLLED TO MINIMUM VENTILATION AND CHILLED WATER COIL

CONTROL VALVE SHALL MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT.

· DEHUMIDIFICATION MODE: WHEN THE RETURN AIR RELATIVE HUMIDITY OR SPACE RELATIVE HUMIDITY EXCEEDS THE MAXIMUM RELATIVE HUMIDITY SETPOINT OF 55%RH (ADJ.), THE UNIT SHALL RETURN TO MINIMUM VENTILATION MODE AND THE CHILLED WATER COIL CONTROL VALVE SHALL BE SET TO 100% (ADJ.) OPEN AND THE HEATING WATER COIL CONTROL

VALVE SHALL MAINTAIN THE SUPPLY AIR TEMP SETPOINT.

· HW HEATING MODE: THE HEATING COIL CONTROL VALVE SHALL MODULATE TO MAINTAIN SUPPLY AIR TEMP SETPOINT.

PROGRAMMING SHALL BE WRITTEN TO AVOID OVERLAPPING OF HEATING AND COOLING CONTROL WHEN NOT

DEHUMIDIFYING.

UNOCCUPIED MODE:

· AHU/RTU SHALL TURN ON AND RUN IN RECIRCULATION MODE (RA DAMPER OPEN, OA/RLF DAMPERS CLOSED) WITH THE

SUPPLY & RETURN FANS ON IF ANY SPACE TEMPERATURE FALLS BELOW THE AHU/RTU UNOCCUPIED HEATING SETPOINT OF 60°F (ADJ.) OR RISES ABOVE THE AHU/RTU UNOCCUPIED COOLING SETPOINT OF 83°F (ADJ.). THE HEATING AND CHILLED WATER COIL CONTROL VALVES SHALL MODULATE TO MAINTAIN SUPPLY AIR TEMPERATURE SET POINT AS DESCRIBED IN THE OCCUPIED SEQUENCE. THE VAV REHEAT COILS SHALL MAINTAIN THEIR UNOCCUPIED SPACE TEMPERATURE SETPOINTS. THE AHU/RTU SHALL TURN OFF WHEN ALL ZONES HAVE BEEN SATISFIED AND ARE ABOVE 63°F (ADJ.) AND BELOW 80°F (ADJ.).

WHEN THE UNIT IS NOT RUNNING, THE HEATING CONTROL VALVE SHALL MAINTAIN AN INTERNAL UNIT TEMPERATURE OF 50°F

(ADJ.) AT THE MAT/SAT SENSORS.

ALARM MODES:

· FREEZE ALARM: UPON SENSING LOW LIMIT SUPPLY TEMPERATURE OF 35°F (ADJ.), CLOSE THE OUTDOOR AIR DAMPER, SHUT

DOWN THE FANS, AND ALARM WITH THE HEATING VALVE OPEN 100%.

· SMOKE ALARM: SMOKE DETECTOR SENSING SMOKE SHALL SHUT DOWN THE FANS, CLOSE THE OUTDOOR AIR AND EXHAUST

AIR DAMPERS, AND SEND AN ALARM TO THE FIRE ALARM SYSTEM.

· MOTOR ALARM: ANY STATUS THAT DOESN'T MATCH COMMAND WITHIN 30 SEC. (ADJ.). SHUT DOWN THE FANS, CLOSE THE

OUTDOOR AIR AND EXHAUST AIR DAMPERS, AND SEND AN ALARM TO THE HEAD END.

· SAFETY CIRCUIT ALARM: PRESSURE SWITCHES BOTH POSITIVE AND NEGATIVE FOR EACH FAN. SHUT DOWN THE FANS, CLOSE

THE OUTDOOR AIR AND EXHAUST AIR DAMPERS, AND SEND AN ALARM TO THE HEAD END.

· ANY SPACE DROPPING BELOW A FREEZE ALARM LIMIT OF 40°F (ADJ.) SHALL INITIATE A FREEZE ALARM AND PROVIDE A

BUILDING FREEZE ALARM SIGNAL TO THE MAINTENANCE STAFF PAGING SYSTEM.

DESIGNED DRAWN CHECKED

SIGNATURE:

PRINTED NAME:

LIC. NO.: DATE:

DATENO. ISSUE RECORD

A pr

0,

- 3

:2 7p m

BA

R

IS

O N

E

IN

C H

O N

O R

IG

IN

AL

D

R

AW

IN

G

IF

N O

T O

N E

IN

C

H O

N T

H

IS

D R

AW

IN

G A

D

JU

ST

S

C

AL

ES

A

C C

O R

D

IN

G

LY

22308.000

RAMP C

RAMP B

RAMP A

HAWTHORNE

KEY PLAN

HAWTHORNE

BAS UPGRADES

CITY OF MINNEAPOLIS

DIVISION OF TRAFFIC AND

PARKING

AIDI AI

AO

GENERAL NOTES

1. SOME CONTROL POINTS ARE INTENDED FOR MONITORING ONLY. EXISTING EQUIPMENT TO FOLLOW SEQUENCE OF

OPERATION AS DESCRIBED ON THIS SHEET. TEMPERATURE CONTROL CONTRACTOR TO PROVIDE DEFICIENCY REPORT TO

ENGINEER AND OWNER OF ALL EXISTING TO REMAIN CONTROL DEVICES.

2. CONTROLS CONTRACTOR IS RESPONSIBLE FOR REMOVING ANY DEFUNCT EXISTING CONTROLS INCLUDING, WIRING, TUBING, CONDUIT, PANELS, ACTUATORS, JUNCTION BOXES, ETC. NO CONTROLS EQUIPMENT SHALL BE ABANDONED IN

PLACE.

3. CONTROLS CONTRACTOR SHALL PROVIDE ALL PROVISIONS FOR ANY NEW LOGIC CONTROLLERS NEEDED INCLUDING DRIVERS, WIRING, AND COMMUNICATION CABLING TO MEET THE SEQUENCE OF OPERATION. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM FIELD-LEVEL CONTROLLERS TO GATEWAY DEVICE SHALL BE OPEN PROTOCOL, BACNET MS/TP (NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT NOT LIMITED TO: ARCNET, U-NET, N2, TAC, P1/2 AND COM3/4). CONTRACTOR SHALL PROVIDE ALL PROVISIONS REQUIRED FOR BACNET MS/TP COMMUNICATION.

4. ALL EXISTING GRAPHICS TO BE UPDATED TO WEBCTRL 10 STANDARD GRAPHICS PACKAGE. PROVIDE GRAPHICS

CONFIGURATION THAT MEETS THE CITY OF MINNEAPOLIS GRAPHICS STANDARD.

KEYED NOTES

1 PROVIDE NEW CONTROL DEVICE.

IF SPECIFIED COMMUNICATION PROTOCOL CAN'T BE

MET WITH EXISTING BAS CONTROLLER, PROVIDE NEW

BAS CONTROLLER.

AO

AI

AI

EQUIPMENT LOCATION

M502

MECHANICAL ROOM 304

THIRD LEVEL SW SKYWAY

AHU-2 CONTROLS

AI

AI

DO

AO DI

AIDO

M

M

AOAO

CONTROL POINTS LIST

POINT NAME POINT TYPE SYSTEM COMPONENT DESCRIPTION WORK REQUIRED

MaDmpr AO MIXED AIR MIXED AIR DAMPER CONTROL REUSE EXISTING ACTUATORS

MaTemp AI MIXED AIR MIXED AIR TEMPERATURE SENSOR REUSE EXISTING SENSOR

RFanStatus DI RETURN FAN RETURNFAN REUSE EXISTING CONNECTION

RFanEnable DO RETURN FAN RETURN FAN REUSE EXISTING CONNECTION

FrzStat DI MIXED AIR MIXED AIR FREEZE STAT LOW LIMIT ALARM REUSE EXISTING SENSOR HtgValvePosition AO HEATING WATER COIL HEATING WATER CONTROL VALVE REUSE EXISTING ACTUATED VALVE

ClgValvePosition AO CHILLED WATER COIL CHILLED WATER CONTROL VALVE REUSE EXISTING ACTUATED VALVE

SFanStatus DI SUPPLY FAN SUPPLY FAN REUSE EXISTING CONNECTION

SFanEnable DO SUPPLY FAN SUPPLY FAN REUSE EXISTING CONNECTION

RaTemp AI RETURN AIR RETURN AIR TEMPERATURE SENSOR REUSE EXISTING SENSOR

RaHum AI RETURN AIR RETURN AIR HUMIDITY SENSOR PROVIDE NEW SENSOR TO REPLACE EXISTING

RaSmk DI RETURN AIR RETURN AIR SMOKE DETECTOR REUSE EXISTING SENSOR

SaTemp AI SUPPLY AIR SUPPLY AIR TEMPERATURE SENSOR REUSE EXISTING SENSOR

RmTemp AI ZONE AREA SPACE TEMPERATURE SENSOR PROVIDE NEW SENSOR TO REPLACE EXISTING

AHU-2 - SEQUENCE OF OPERATION

SYSTEM OPERATES AS OCCUPIED/UNOCCUPIED ACCORDING TO ITS OPTIMAL OPERATING SCHEDULE.

OCCUPIED MODE:

· START/STOP THE SUPPLY FAN AND RETURN FAN ACCORDING TO THE OPTIMAL START SCHEDULE AND RUN CONTINUOUSLY.

UNIT SHALL OPERATE IN FULL RECIRCULATION MODE (RETURN AIR DAMPER 100% OPEN, OA DAMPER CLOSED, AND RELIEF DAMPER CLOSED) UNTIL SPACE SET POINTS ARE MET OR SPACES ARE OCCUPIED BY MEANS OF OCCUPANCY SENSOR. THEN

UNIT SHALL RUN IN MINIMUM VENTILATION MODE.

· MINIMUM VENTILATION: OPEN THE OUTDOOR AIR DAMPER AND MODULATE OUTDOOR, RETURN AND RELIEF DAMPERS TO MAINTAIN MINIMUM DAMPER POSITION SETPOINT. REFER TO SCHEDULE AND COORDINATE DAMPER SETPOINT WITH

BALANCING CONTRACTOR.

· SUPPLY AIR TEMPERATURE RESET: THE SUPPLY AIR TEMP SETPOINT SHALL BE RESET BASED ON SPACE TEMPERATURE VS

SETPOINT 72°F (ADJ.).

· ECONOMIZER COOLING: WHEN BOTH OUTDOOR AIR DEWPOINT AND DRY-BULB TEMPERATURES ARE BELOW THEIR RESPECTIVE ECONOMIZER ENABLE SETPOINTS OF 67°F DRY-BULB (ADJ.) AND 52°F DEWPOINT (ADJ.), THE UNIT SHALL ENTER ECONOMIZER MODE. MODULATE THE OUTDOOR AIR AND RETURN AIR DAMPERS TO MAINTAIN A MIXED AIR TEMPERATURE SETPOINT. THE MIXED AIR TEMPERATURE SETPOINT SHALL TRACK THE SUPPLY AIR TEMPERATURE SETPOINT WITH AN

ADJUSTABLE OFFSET INITIALLY SET AT +1°F. (SAT SP = 55°F THEN MAT SP = 56°F)

· CHW COOLING MODE: WHEN EITHER OUTDOOR AIR DRY-BULB OR DEWPOINT ARE ABOVE THEIR RESPECTIVE ECONOMIZER ENABLE SETPOINTS, THE UNIT DAMPERS SHALL BE CONTROLLED TO MINIMUM VENTILATION AND CHILLED WATER COIL

CONTROL VALVE SHALL MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT.

· DEHUMIDIFICATION MODE: WHEN THE RETURN AIR RELATIVE HUMIDITY OR SPACE RELATIVE HUMIDITY EXCEEDS THE MAXIMUM RELATIVE HUMIDITY SETPOINT OF 55%RH (ADJ.), THE UNIT SHALL RETURN TO MINIMUM VENTILATION MODE AND THE CHILLED WATER COIL CONTROL VALVE SHALL BE SET TO 100% (ADJ.) OPEN AND THE HEATING WATER COIL CONTROL VALVE

SHALL MAINTAIN THE SUPPLY AIR TEMP SETPOINT.

· HW HEATING MODE: THE HEATING COIL CONTROL VALVE SHALL MODULATE TO MAINTAIN SUPPLY AIR TEMP SETPOINT.

PROGRAMMING SHALL BE WRITTEN TO AVOID OVERLAPPING OF HEATING AND COOLING CONTROL WHEN NOT

DEHUMIDIFYING.

UNOCCUPIED MODE:

· AHU/RTU SHALL TURN ON AND RUN IN RECIRCULATION MODE (RA DAMPER OPEN, OA/RLF DAMPERS CLOSED) WITH THE

SUPPLY & RETURN FANS ON IF THE SPACE TEMPERATURE FALLS BELOW THE AHU/RTU UNOCCUPIED HEATING SETPOINT OF 60°F (ADJ. WITH +3°F DEADBAND) OR RISES ABOVE THE AHU/RTU UNOCCUPIED COOLING SETPOINT OF 83°F (ADJ. WITH -3°F DEADBAND). THE HEATING AND CHILLED WATER COIL CONTROL VALVES SHALL MODULATE TO MAINTAIN SUPPLY AIR TEMPERATURE SET POINT AS DESCRIBED IN THE OCCUPIED SEQUENCE. THE AHU/RTU SHALL TURN OFF WHEN ALL ZONES HAVE BEEN SATISFIED AND ARE ABOVE 63°F (ADJ.) AND BELOW 80°F (ADJ.). WHEN THE UNIT IS NOT RUNNING, THE HEATING CONTROL VALVE SHALL MAINTAIN AN INTERNAL UNIT TEMPERATURE OF 50°F (ADJ.) AT THE MAT/SAT SENSORS.

ALARM MODES:

· FREEZE ALARM: UPON SENSING LOW LIMIT SUPPLY TEMPERATURE OF 35°F (ADJ.), CLOSE THE OUTDOOR AIR DAMPER, SHUT

DOWN THE FANS, AND ALARM WITH THE HEATING VALVE OPEN 100%.

· SMOKE ALARM: SMOKE DETECTOR SENSING SMOKE SHALL SHUT DOWN THE FANS, CLOSE THE OUTDOOR AIR AND EXHAUST

AIR DAMPERS,…