Plans_and_Drawings_-_Event_4129.pdf
PDF 9 MB Posted
- Solicitation number
- 0000004129
- Issued by
- Hennepin County, Minnesota
About this file
This is a plans and drawings document for a Building Automation System (BAS) upgrade project at the Hawthorne parking ramp facility in Minneapolis, Minnesota, issued by the City of Minneapolis Division of Traffic and Parking. The project involves upgrading the existing BAS and operator graphics with replacement of terminal-level controllers using BACnet-compliant devices at a maximum baud rate of 76,800 BPS, installation of new control devices to meet specified sequences of operation, and implementation of a new front-end operator interface and graphics based on Automated Logic Corporation equipment. The scope includes no new HVAC equipment but requires replacement of field-level controllers, installation of new sensors and actuators, removal of defunct controls, and coordination with a Test and Balance contractor to balance all VAV terminal units and minimum outdoor airflow rates. The Hawthorne ramp will remain in normal operation throughout construction, requiring the general contractor to coordinate directly with the owner to establish an acceptable construction timeline and work sequencing that minimizes disruption to ramp operations and occupants.
The project documents specify detailed control sequences for multiple systems including chilled water and heating water plants, air handling units (AHU-1 through AHU-5), VAV boxes with heating water reheat, cabinet unit heaters, unit heaters, convectors, exhaust fans, and miscellaneous controls throughout the basement, first floor, third floor, fourth floor, and seventh floor levels of the facility. All work must comply with applicable local, state, and federal codes and regulations, with the contractor responsible for obtaining all necessary permits and licenses. All sub-contractors must submit Material Safety Data Sheets to the general contractor for record-keeping and submission to the owner. The contractor is responsible for maintaining the premises free from waste materials, patching and repairing existing construction to like-new condition resulting from removals or replacements, repairing any damage to existing buildings and property during construction, maintaining egress paths at all times, and controlling dust, noise, VOCs, and vibration in the occupied environment while coordinating work schedules with building users.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
G000
TITLE SHEET
DESIGNED DRAWN CHECKED
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
A pr
0,
- 3
:2 4p m
BA
R
IS
O N
E
IN
C H
O N
O R
IG
IN
AL
D
R
AW
IN
G
IF
N O
T O
N E
IN
C
H O
N T
H
IS
D R
AW
IN
G A
D
JU
ST
S
C
AL
ES
A
C C
O R
D
IN
G
LY
22308.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
BAS UPGRADES
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC AND
PARKING
SCOPED AREAS
GENERAL CONSTRUCTION PACKAGE
CITY OF MINNEAPOLIS
HAWTHORNE - BAS UPGRADES
MINNEAPOLIS, MINNESOTA
SITE LOCATION MAP
CONTACT INFORMATION PROJECT GENERAL NOTES
DANIEL COLVIN
PROJECT MANAGER
CITY OF MPLS - PARKING SERVICES
31 NORTH 9TH STREET
MINNEAPOLIS, MINNESOTA 55403
PHONE: (612) 500-3897
EMAIL: daniel,cikvub@minneapolismn.gov
OWNER REPRESENTATIVE
TKDA
BEN HUESMAN
MECHANICAL ENGINEER
3311 E OLD SHAKOPEE ROAD SUITE 300
BLOOMINGTON, MN 55425
PHONE: (651) 292-4400
EMAIL: ben.huesman@tkda.com
TIMOTHY D. HOSECK
MECHANICAL ENGINEER
3311 E OLD SHAKOPEE ROAD SUITE 300
BLOOMINGTON, MN 55425
PHONE: (651) 292-4400
EMAIL: timothy.hoseck@tkda.com
SHEET NO. SHEET NAME
G000 TITLE SHEET
M000 MECHANICAL SYMBOLS AND ABBREVIATIONS
TOTAL SHEET COUNT: 22
WORK SCOPE AREA
M100 M110 M111 M112 M130 M140 M170 M400 M401 M402 M500 M501 M502 M503 M504 M505 M506 M507
M600
HVAC CONTROLS PLAN BASEMENT LEVEL NORTHEAST
HVAC CONTROLS PLAN FIRST FLOOR RAMP
HVAC CONTROLS PLAN FIRST FLOOR NORTHEAST
HVAC CONTROLS PLAN FIRST FLOOR SOUTHWEST
HVAC CONTROLS PLAN THIRD FLOOR RAMP SKYWAY
HVAC CONTROLS PLAN FOURTH FLOOR RAMP
MECHANICAL STAIR C PLANS BASEMENT THRU THIRD LEVEL EAST AREA
MECHANICAL ROOM T112 & T137 SECOND LEVEL WEST AND SOUTH AREAS
MECHANICAL ROOMS AND SOUTH SKYWAY THIRD LEVEL
HVAC CONTROLS PLAN SEVENTH FLOOR RAMP ROOF LEVEL
MECHANICAL ROOM 050 STAIR C BASEMENT LEVEL HW & CW PLANT CONTROLS
MECHANICAL ROOM 304 FIRST FLOOR SW OFFICES AHU-1 CONTROLS
MECHANICAL ROOM 304 THIRD LEVEL SW SKYWAY AHU-2 CONTROLS
MECHANICAL ROOM 305A THIRD LEVEL NE SKYWAY AHU-4 CONTROLS
MECHANICAL ROOM 305A THIRD LEVEL NE SKYWAY AHU-5 CONTROLS
OFFICES & MECHANICAL ROOMS MULTIPLE LOCATIONS MISC. CONTROLS
ELEVATOR EQUIPMENT ROOM SEVENTH LEVEL STAIR C FCU-1 CONTROLS
PENTHOUSE MECHANICAL SEVENTH FLOOR STAIR C AHU-3 CONTROLS
EXISTING EQUIPMENT SCHEDULE
M508 HAWTHORNE OFFICES VARIOUS FLOORS VAV & FPVAV CONTROLS
A. THE WORK OF THIS CONTRACT CONSISTS OF UPGRADING THE BUILDING AUTOMATION SYSTEM (BAS) AND OPERATOR GRAPHICS FOR THE EXISTING HAWTHORNE RAMP FACILITY, OWNED BY THE CITY OF MINNEAPOLIS PARKING AUTHORITY. WORK INCLUDES REPLACEMENT OF TERMINAL-LEVEL CONTROLLERS WITH BACNET-COMPLIANT DEVICES AT A MAXIMUM BAUD RATE OF 76,800 BPS, INSTALLATION OF NEW CONTROL DEVICES AS REQUIRED TO MEET THE SPECIFIED SEQUENCES OF OPERATION, AND IMPLEMENTATION OF A NEW FRONT-END OPERATOR INTERFACE AND GRAPHICS BASED ON AUTOMATED LOGIC CORPORATION EQUIPMENT. NO NEW HVAC EQUIPMENT IS INCLUDED IN THIS CONTRACT. THE GENERAL CONTRACTOR SHALL PROVIDE A DEFICIENCY REPORT OF ALL EXISTING TO-REMAIN CONTROL SENSORS AND ACTUATORS. THE GENERAL CONTRACTOR SHALL HIRE AND COORDINATE WITH A TEST AND BALANCE CONTRACTOR TO BALANCE ALL VAV TERMINAL UNITS AND MINIMUM OUTDOOR AIRFLOW RATES; REFER TO THE DRAWINGS FOR QUANTITIES AND LOCATIONS. THE HAWTHORNE RAMP WILL REMAIN IN NORMAL OPERATION THROUGHOUT THE DURATION OF CONSTRUCTION. THE GENERAL CONTRACTOR SHALL COORDINATE DIRECTLY WITH THE OWNER TO ESTABLISH AN ACCEPTABLE CONSTRUCTION TIMELINE, WORK AREA SEQUENCING, AND SCHEDULING THAT MINIMIZES DISRUPTION TO RAMP OPERATIONS AND OCCUPANTS. ALL WORK SHALL BE
PERFORMED IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.
B. THE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE INTENDED TO INDICATE CAPACITY, SIZE, APPROXIMATE LOCATION AND GENERAL ARRANGEMENT, NOT THE SPECIFIC DETAILS OF CONSTRUCTION. ADDITIONAL OFFSETS, FITTINGS, ACCESSORIES, AND COORDINATION MAY BE NEEDED FOR PROPER INSTALLATION AND ARE THE RESPONSIBILITY OF THE
CONTRACTOR.
C. EXISTING MECHANICAL ELEMENTS, INCLUDING ALL PIPING, DUCTWORK, AND PLUMBING SHOWN ON THESE DRAWINGS ARE BASED ON ORIGINAL CONSTRUCTION DOCUMENTS AND LIMITED FIELD OBSERVATION. CONTRACTOR SHALL FIELD VERIFY
ACTUAL EXISTING CONDITIONS PRIOR TO BIDDING.
D. ALL WORK SHALL COMPLY WITH ALL APPLICABLE LOCAL, STATE & FEDERAL CODES, RULES & REGULATIONS.
E. THE CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS, LICENSES & CERTIFICATES AND PAY ALL FEES CONNECTED
THEREWITH.
F. ALL SUB-CONTRACTORS TO SUBMIT MATERIAL SAFETY DATA SHEETS MSDS IF APPLICABLE TO THEIR TRADE TO GEN. CONTR.
FOR RECORD KEEPING & SUBMITTAL TO OWNER.
G. VERIFY WITH OWNERS REPRESENTATIVE USE OF SITE, OR ADJACENT AREAS, FOR STAGING OR STOCKPILE OF NEW
MATERIALS.
H. VERIFY WITH OWNERS REPRESENTATIVE FOR POSSIBLE STOCKPILED MATERIALS AVAILABLE FOR USE ON PROJECT. I.E.
DOORS, FRAMES, ACOUSTICAL CEILING PANELS, ETC.
I. CONTRACTOR SHALL COORDINATE ALL WORK WITH OWNER TO AVOID INTERRUPTION OF BUILDING ACTIVITIES OR ACCESS.
J. ALL DIMENSIONS MUST BE FIELD VERIFIED. EXISTING BUILDING WALLS, WINDOWS AND DOORS ETC. ARE SHOWN FOR REFERENCE ONLY, & ARE SUBJECT TO FIELD VERIFICATION. NOTIFY ENGINEER REGARDING DISCREPANCIES BEFORE
PROCEEDING WITH THE WORK AFFECTED.
K. CONTRACTORS SHALL MAKE ALL NECESSARY ARRANGEMENTS WITH BLDG. OWNER & USERS FOR ACCESS TO AREA, INCLUDING, BUT NOT LIMITED TO DELIVERIES. CONTRACTOR SHALL ACKNOWLEDGE & ABIDE BY ALL BUILDING REGULATIONS.
CONTRACTOR TO SCHEDULE USE OF DOCK FOR DELIVERIES WITH OWNER.
L. THE CONTRACTOR SHALL FURNISH & INSTALL ALL ITEMS WHICH ARE NECESSARY TO ENSURE A GOOD WORKMANSHIP INSTALLATION EVEN THOUGH SUCH ITEMS ARE NOT SPECIFICALLY MENTIONED ON THE DRAWINGS. QUALITY & FINISH REQUIREMENTS SHALL BE AS A MIN. ACCEPTABLE LEVEL OF QUALITY AS RECOGNIZED BY THE INDUSTRY.
M. THE WORD - PROVIDE - AS USED IN THE DRAWINGS SHALL BE UNDERSTOOD TO MEAN - PROVIDE COMPLETE IN PLACE. THAT IS
- FURNISHED AND INSTALLED - PROVIDE ALL ACCESSORIES & TRIM AS REQUIRED FOR A COMPLETE INSTALLATION.
N. THE CONTRACTOR SHALL, AT ALL TIMES, KEEP THE PREMISES FREE FROM WASTE MATERIAL OR RUBBISH CAUSED BY THE
WORK.
O. THE CONTRACTOR SHALL PATCH & REPAIR EXISTING CONSTRUCTION TO LIKE NEW CONDITION AS A RESULT OF REMOVAL OR REPLACEMENT OF EXIST. CONSTRUCTION. ALL EXIST. & NEW HOLES OR PENETRATIONS THROUGH FIRE RATED ASSEMBLIES
MUST BE PATCHED & REPAIRED TO MAINTAIN THE INTEGRITY OF THE ASSEMBLY.
P. THE CONTRACTOR SHALL REPAIR OR REPLACE ANY DAMAGE CAUSED TO EXISTING BUILDINGS & PROPERTY DURING
CONSTRUCTION INSIDE AND OUTSIDE OF PROJECT LIMITS.
Q. CONTRACTOR TO MAINTAIN EGRESS PATHS AT ALL TIMES. SEQUENCE WORK ACCORDINGLY.
R. COVER AND PROTECT EXISTING EQUIPMENT DURING DEMOLITION AND CONSTRUCTION.
S. CONTRACTOR TO CONTROL DUST, NOISE, VOCS AND VIBRATION IN OCCUPIED ENVIRONMENT. COORDINATE WORK SCHEDULE
WITH USER - CUSTOMER.
T. ALL CONTRACTORS ARE RESPONSIBLE TO REVIEW ALL DRAWINGS, SPECS, AND COORDINATE THE WORK TO PROVIDE
COMPLETE INSTALLATION.
SHEET INDEX
M000
MECHANICAL
SYMBOLS AND
ABBREVIATIONS
SCOPED AREAS
DESIGNED DRAWN CHECKED
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
A pr
0,
- 3
:2 5p m
BA
R
IS
O N
E
IN
C H
O N
O R
IG
IN
AL
D
R
AW
IN
G
IF
N O
T O
N E
IN
C
H O
N T
H
IS
D R
AW
IN
G A
D
JU
ST
S
C
AL
ES
A
C C
O R
D
IN
G
LY
22308.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
BAS UPGRADES
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC AND
PARKING
PIPING LEGEND
FITTING AND MISCELLANEOUS LEGEND
NECK DIAMETER
( )FOR MULTIPLE
DIFFUSERS ONLY
TYPE DESIGNATION
REGISTER SIZE
REGISTER SIZE
TYPE DESIGNATION
TYPE DESIGNATION
(SEE SCHEDULE DRAWING)
(SEE SCHEDULE DRAWING)
(SEE SCHEDULE DRAWING)
CFM
CFM
CFM
6/6-100-C
6/6-100-B
(2)6-100-A
AIR REGISTER
RETURN OR EXHAUST
SUPPLY AIR DIFFUSER
SUPPLY AIR REGISTER
BD
FD
SD
FS FS
SD
FD
COMBINATION FIRE AND
FLEXIBLE DUCT
SMOKE DAMPER
SMOKE DAMPER
FIRE DAMPER
BD
MOTORIZED DAMPER
BACKDRAFT DAMPER
SPLITTER DAMPER
MANUAL VOLUME DAMPER
(UNLESS NOTED OTHERWISE)
S
M
DIAPHRAGM OPERATOR
MOTOR OPERATOR
SOLENOID OPERATOR
PRESSURE REDUCING VALVE
BALANCING VALVE
CYLINDER OPERATOR
PIPING FLOW DIRECTION
RH
C
C
H
C
HEATING RECOVERY COIL
BACKFLOW PREVENTER
DUCT FLOW DIRECTION
DAMPER
HEATING COIL
COOLING COIL
FILTER
PUMP
NON-RISING STEM GATE VALVE
THREE-WAY CONTROL VALVE
FLOAT OPERATED VALVE
CHECK VALVE
PRESSURE RELIEF VALVE
PLUG VALVE
BUTTERFLY VALVE
ANGLE VALVE
GLOBE VALVE
TWO-WAY CONTROL VALVE
BALL VALVE
O.S & Y. GATE VALVE
STRAINER
SUPPLY FAN,
PROPELLER FAN
BLOW-OFF
STRAINER W/
VALVE
QUICK CONNECT
AIR VENT
SURGE TANK
"A" SHOCK ABSORBER WITH
THERMOSTATIC TRAP
UNION
P.D.I. SIZE
BUCKET TRAP
FLEXIBLE CONNECTION
THERMOSTATIC TRAP
CONCENTRIC REDUCER
ECCENTRIC REDUCER
FLOAT AND
PIPE CAP
SECOND DIMENSION IS SIDE NOT
SHOWN-ALL SIZES ARE IN INCHES
FIRST DIMENSION IS SIDE SHOWN/
RECTANGULAR OR SQUARE DUCT-
AP
UP
AP ACCESS PANEL
TURNING VANES
FLEXIBLE CONNECTION
UPDN DN
TWO SIDED DUCT EXPANSION
OR REDUCTION
TO ROUND OR OVAL)
(RECTANGULAR OR SQUARE
DUCT TRANSITION
OR REDUCTION
ONE SIDED DUCT EXPANSION
24/12
DOUBLE LINE DRAWING
R OR D
UP UPDN DN
R OR D
24/12
OF FLOW)
UP AND DOWN
SUPPLY AIR DUCT TURNING
(SOUND INSULATION)
DUCT WITH LINER
RISE OR DROP IN DUCT
(ARROW INDICATES DIRECTION
VENTILATION LEGEND
SINGLE LINE DRAWING DESCRIPTION
FIRE PROTECTION BRANCH LINE,
CROSS MAIN, AND/OR FEED MAIN
NATURAL GAS/LOW PRESSURE
HOT/CHILLED WATER RETURNHCR
GLYR
GW
FOV
G
FOS
GRAYWATER/ABOVEGROUND
FUEL OIL VENT
FUEL OIL SUPPLY
GLYCOL RETURN
FOG
FOR
DI
F
DF2
CWS
DFO
D
CWR
CW
DEIONIZED WATER
DIESEL FUEL OIL #2
FUEL OIL GAUGE
FUEL OIL RETURN
DOMESTIC COLD WATER
CHILLED WATER SUPPLY
CHILLED WATER RETURN
DIESEL FUEL OIL
DRAIN
MU MAKE-UP WATER
PA
PC
FWP
FWP
FLAMMABLE WASTE PIPING/
UNDERGROUND
ABOVEGROUND
PUMPED CONDENSATE
PROCESS AIR
MP
METH
LPC
LPS
LO
IHW
JO
IW
ICW
IA
LOW PRESSURE CONDENSATE
LOW PRESSURE STEAM
METER PROVER
METHANOL
LUBE OIL
INSTRUMENT AIR
INDUSTRIAL HOT WATER
INDUSTRIAL COLD WATER
INDUSTRIAL WASTE
JOURNAL OIL
BA
CR
CS
CD
CA
BBD
ACID
ACID
ACID
BOOSTER AIR
CONDENSATE DRAIN
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
BOILER BLOW DOWN
COMPRESSED AIR
ACID VENT
ACID WASTE/UNDERGROUND
ACID WASTE/ABOVEGROUND
HPS
HS
HW
HRS
HRR
HR
HPG
HPC
HCS
HIGH PRESSURE STEAM
HEAT RECOVERY SUPPLY
HEAT RECOVERY RETURN
HEATING WATER RETURN
HEATING WATER SUPPLY
DOMESTIC HOT WATER
NATURAL GAS/HIGH PRESSURE
HOT/CHILLED WATER SUPPLY
HIGH PRESSURE CONDENSATE
SWITCH, SOFT WATERSW
FLG FLANGED
CLEANOUT
90° ELBOW UP
HOSE VALVE
STANDPIPE WITH FIRE DEPT.
PIPE GUIDE
WALL HYDRANT
WALL FAUCET
PIPE ANCHOR
90° ELBOW DN
TEE DN
TEE UP
HORIZONTAL SIDEWALL SPRINKLER
HEAD W/ ESCUTCHEON
DRY-TYPE SIDEWALL
DRY-TYPE PENDENT
SPRINKLER HEAD
SPRINKLER HEAD
SPRINKLER HEAD
VERTICAL SIDEWALL
SPRINKLER HEAD
WALL POST INDICATOR VALVE
YARD POST INDICATOR VALVE
EXPOSED HORIZONTAL SIDEWALL
CONNECTION
Y-TYPE FIRE DEPT.
PROCESS FLOW DIRECTION
CONNECTION
SPRINKLER HEAD W/ COVER PLATE
FULLY-RECESSED PENDENT
UPRIGHT SPRINKLER HEAD
SEMI-RECESSED PENDENT
FLUSH TYPE FIRE DEPT.
EXPOSED PENDENT
SPRINKLER HEAD
SPRINKLER HEAD
HS
DENOTES PROJECT RELATED ITEMS
DENOTES EXISTING CONDITIONS
DENOTES ROOM IDENTIFICATION
DENOTES CONNECTION
CONTINUATION
XXXX
XXXX
XXXX
XXXX
XXXX OR XXXXE
PID-101
REFERENCE
TO EXISTING
JAN
KIT
KW
ID
INSTALL
IG
INCL
INV
INSUL
HTG
HT
HW
HVAC
HTR
FLOOR DRAIN
FLOOR CLEANOUT
FLOOR DRAIN
OVERFLOW ROOF
SHOWER DRAIN
WITH FUNNEL
DENOTES REMOVAL
ORD
RD
DRAIN
ROOF DRAIN
FS
AD
SD
CO
FD
FLOOR SINK
AREA DRAIN
G
GR
HD
HP
HR
HB
GA
GAL
GEN
GPM
GALV
FWH
FW
FUT
FT
FTR
FP
FLR
FS
FPM
FLEX
UNLESS NOTED OTHERWISE
VERTICAL VERT
HOSE STATION, HTG WATER SUPPLY
KILOWATT
JANITOR
KITCHEN
INTERUPTABLE GAS
HEATING, VENT & AIR CONDITIONING
INSIDE DIAMETER
INSTALLATION
INSULATION
INVERT
INCLUDE
HOT WATER
HEATER
HEIGHT
HEATING
WALL HYDRANTWH
WATER
WEIGHT
YARD HYDRANTYDH
WTR
WT
WALL FAUCET
VIBRATION
WASTE
WITHOUT
VOLUME
WALL CLEANOUT
WET BULB
VENT THRU ROOF
W/O
WF
WCO
WC
WB
VTR
W/ W
VIB
VOL
WITH
GAS
GALLON PER MINUTE
HOUR, HTG WATER RETURN
GRILLE
HORSEPOWER
HOSE BIB
HEAD
GALVANIZED
GENERAL
GAUGE
GALLON
FEED WATER HEATER
FIN TUBE RADIATION
FIRE SMOKE DAMPER, FLOOR SINK
FEED WATER
FEET
FUTURE
FIRE PROTECTION
FEET PER MINUTE
FLEXIBLE
FLOOR
UNDERGROUNDUG
VACUUM
VELOCITY
VALVE
URINAL
VARIABLE AIR VOLUME
VOLUME DAMPER
VENTILATION
UNIT HEATER
VENT
VEL
VAC
VD
VAV
UR
VLV
V
UNO
UH
VENT
TUBE STEEL
TYPICAL
THROUGH
SYSTEM
TEMPERATURE
TRANSFER AIR
TRENCH DRAIN
THERMOSTAT
TEMPERED WATER
TEMPERATURE CONTROL
TS
TYP
THRU
TEMP
TD
T-STAT
TA
TC
SYS
T
CLG
W
VAC
V
V
UNDERGROUND WATER SERVICE
VACUUM
PLUMBING VENT
VENT
SAN
STM
TRW
T
GW
ST
SAN
SMS
SD
SC
SMR
SANITARY SEWER/UNDERGROUND
STORM SEWER/ABOVEGROUND
GRAYWATER/UNDERGROUND
TREATED RADIATOR WATER
TEMPERED WATER
STEAM
SAND CONVEYING
SANITARY SEWER/ABOVEGROUND
SNOW MELT RETURN
SNOW MELT SUPPLY
SOIL SUBDRAIN
DIM
EQUIP
FG
FIN
FIG
F&T
FD
F
EXH
ESH
EWC
EXIST
DWG
DR
EMS
EL
EA
DIV
DS
DPR
DN
DISCH
CW
DHDC
DIFF
DIA
DF
DET
CWS
CWR
DD
DEPT
DB
CUH
CONT
COOR
CTRS
CONN
CMP
COL
CO
COND
COMP
RLO
RS
S
RL
RHW
RHG
RDF
PG
RECIRCULATING HOT WATER
REFRIGERANT SUCTION
REFRIGERANT LIQUID
RECOVERED LUBE OIL
SOFT WATER
RECOVERED DIESEL FUEL OIL
REFRIGERANT HOT GAS
DISCHARGE
PROPANE GAS
AC
BD
CA
CFM
C
CI
BTUH
L
BM
BTU
BOD
BTM, B/
BLDG
ATFS
ATFR
BA
AHU
ATC
AD
AP
AG
AFF
ADJ
ON CENTEROC
CEILING
STAINLESS STEEL OR SERVICE SINK
BACKFLOW PREVENTER ASSEMBLY
REDUCED PRESSURE ZONE
RECIRCULATING HOT WATER
POWER ROOF VENTILATOR/
PRESSURE REDUCING VALVE
POUND/SQ. IN. ABSOLUTE
REFRIGERANT LIQUIDRL
DIMENSION
EQUIPMENT
FLOOR DRAIN, FIRE DEPARTMENT,
FLOAT AND THERMOSTATIC
EMERGENCY EYEWASH/SHOWER
ELECTRIC WATER COOLER
FIRM GAS
FINISHED
FIGURE
FAHRENHEIT
EXHAUST
EXISTING
ENERGY MANAGEMENT SYSTEM
ELEVATION
DRAIN
DRAWING
EACH
DOWN SPOUT
DISCHARGE
DOWN
DAMPER
DIVISION
SHOWERSHR
SQUARE
SPECIFICATIONS
STATIC PRESSURE
STORM SEWER
STANDARD
SUSPENDED
STRUCTURAL
STEAM
SUSP
STRUC
STD
ST
STM
SPEC
SQ
SS
SK
SP
SINK
ROOM
REFRIGERANT SUCTION
SUPPLY AIR
SECTION
SQUARE FOOT
SHOWER DRAIN, SMOKE DAMPER
SCHEDULE
SANITARY
SECT
SF
SCH
SD
SAN
RS
SA
RPZ
RM
COLD WATER
DISTRICT HEATING, DISTRICT COOLING
CHILLED WATER SUPPLY
CHILLED WATER RETURN
DRINKING FOUNTAIN
DIFFUSER
DIAMETER
DETAIL
DECK DRAIN
DEPARTMENT
DRY BULB TEMP
COMPRESSOR/COMPARTMENT
CABINET UNIT HEATER
CORRUGATED METAL PIPE
CONTINUATION
COORDINATE
CENTERS
CONNECTION
CONDENSATE
CLEANOUT
COLUMN
RETURN AIRRA
ROOF DRAIN
RECESSED
RADIATION
REVISION
RETURN
REFRIGERANT
REFRIGERANT HOT GAS
REQUIRED
RECIRCULATING
RHW
RHG
REV
RET
REQ
REC
REF
RECIRC
RD
RAD
OUTSIDE SCREW & YOKE
OUTSIDE DIAMETER
OPENING
POUND/SQ. IN. GAUGE
POLYVINYL CHLORIDE
OVERFLOW ROOF DRAIN
PNEUMATIC
PSIA
PVC
PSIG
PRV
ORD
OS&Y
PNEUM
OD
OPNG
AIR CONDITIONING
LENGTHL
BACKDRAFT DAMPER
CUBIC FEET PER MINUTE
BRITISH THERMAL UNIT
COMPRESSED AIR
CAST IRON
CENTERLINE
BTU PER HOUR
BOTTOM OF DUCT
BUILDING
BOTTOM
BEAM
AUTOMATIC TRANSMISSION FLUID SUPPLY
AUTOMATIC TRANSMISSION FLUID RETURN
AIR HANDLING UNIT
AUTOMATIC TEMP CONTROL
ABOVE FINISHED FLOOR
BREATHING AIR
ACCESS PANEL
ABOVEGROUND
AREA DRAIN
ADJUSTABLE
MIN MINIMUM
MOUNTED
MOTOR
NATURAL
NUMBER
OUTSIDE AIR
OPPOSED BLADE
NON-POTABLE WATER
NORMALLY OPEN
NORMALLY CLOSED
MOP SINK
NP
OA
OB
NO
NO.,#
MTD
NC
NAT
MS
MOT
MANUAL
MANHOLE
THOUSAND BTU'S/HR
MANUFACTURER
MEZZANINE
MECHANICAL
POUND
LAVATORY
LEAVING WATER TEMPERATURE
LINEAL FEET
MEZZ
MFR
MH
MBH
MECH
LF
MAN
LWT
LB
LAV
ABBREVIATIONS
GW GRAYWATER
F/ FOR
ACR
ACS
AFTERCOOLER RETURN
AFTERCOOLER SUPPLY
JWR
JWS
JACKET WATER RETURN
JACKET WATER SUPPLY
ST STORM SEWER/UNDERGROUND
SW SOFT WATER
OST OVERFLOW STORM SEWER/
UNDERGROUND
OST OVERFLOW STORM SEWER/
ABOVEGROUND
FLAMMABLE WASTE PIPING/
NP NON-POTABLE WATER
UP UPDN DN
RETURN OR OUTDOOR AIR
INTAKE DUCT TURNING UP
AND DOWN
EXHAUST AIR DUCT
TURNING UP AND DOWN
PRESSUREPRESS
ASSY ASSEMBLY
H-STAT HUMIDISTAT
PENETRATIONPEN
VD VD
M
IR IRRIGATION SUPPLY WATER
IR IRRIGATION
M
BOP BOTTOM OF PIPE
TERMINATETERM
GLYS GLYCOL SUPPLY
CCA CONTROL COMPRESSED AIR
EAT ENTERING AIR TEMPERATURE
LEAVING AIR TEMPERATURELAT
HAZARDOUS WASTEHAZ
PHAZ PUMPED HAZARDOUS WASTE
WATER CLOSET
EWT ENTERING WATER TEMPERATURE
CUBIC FEET PER MINUTE, STANDARD CONDITIONSSCFM
EFF EFFICIENCY
FPI FINS PER INCH
HZ FREQUENCY - HERTZ
GPH GALLON PER HOUR
HEAT TRANSFER COEFFICIENTU
RELATIVE HUMIDITYRH
IN INCH
KWH KILOWATT HOUR
PARTS PER MILLIONPPM
REVOLUTIONS PER MINUTERPM
ARCH ARCHITECTURAL / ARCHITECT
ELEC ELECTRICAL
MISC MISCELLANEOUS
NOT IN CONTRACTNIC
NOT TO SCALENTS
PHASEPH
EXT EXTERIOR
HORIZ HORIZONTAL
INT INTERIOR
BHP BRAKE HORSEPOWER
PLUMBINGPLMG
RO REVERSE OSMOSIS
WW WELL WATER
BD BACKWASH DRAIN
RAIN WATER LEADERRWL
FIRE DAMPER
DIST DISTRICT
REPRESENTATIVEREP
SCOPED AREAS
CV
XXX
EQUIPMENT HYDRONIC
VALVE TAG
XXX
EQUIPMENT TAG
M100
HVAC CONTROLS PLAN
BASEMENT LEVEL
NORTHEAST
SCALE: 1/8"=1'-0"
M100
BASEMENT FLOOR NORTHEAST OFFICES CONTROLS PLAN
SCOPED AREAS
T
T
T
T
T
T
T
CUH
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
39VAV
CUH
CUH
VAV
33CV
VAV
31CV
VAV
29CV
VAV
30CV
VAV
34CV
VAV
27CV
VAV
39CV
VAV
32CV
CUH
16CV
CUH
7CV
TO T-STAT ON FIRST
FLOOR SEE M111
CUH
8CV
TO T-STAT ON FIRST FLOOR
SEE M111
T
T
DESIGNED DRAWN CHECKED
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
A pr
0,
- 3
:2 5p m
BA
R
IS
O N
E
IN
C H
O N
O R
IG
IN
AL
D
R
AW
IN
G
IF
N O
T O
N E
IN
C
H O
N T
H
IS
D R
AW
IN
G A
D
JU
ST
S
C
AL
ES
A
C C
O R
D
IN
G
LY
22308.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
BAS UPGRADES
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC AND
PARKING
M
M
M
M M
M
M
M
M
M
M
M
M
T
CUH
15CV
CUH
KEYED NOTES
PROVIDE ADJUSTABLE T-STATS IN ANY CLOSED/OFFICE SPACE.
PROVIDE FLAT PLATE T-STATS IN ANY SHARED/OPEN SPACE.
EXISTING BAS HEAD END AND SERVER LOCATION.
VAV-27
T
VAV
28CV
T 1
GENERAL NOTES
1. FIELD VERIFY TSTAT LOCATIONS. REMOVE AND REPLACE EXISTING T-STATS
AND CONTROL WIRING.
2. FIELD VERIFY ALL EQUIPMENT LOCATIONS. FOR ALL CONTROLLERS REPLACE FIELD-LEVEL
CONTROLLERS AND COMMUNICATION WIRING TO GATEWAY DEVICE.
3. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM FIELD-LEVEL CONTROLLERS TO
GATEWAY DEVICE SHALL BE OPEN PROTOCOL, BACnet MS/TP (NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT NOT LIMITED TO: ARCnet, U-NET, N2, TAC, P1/2 AND COM3/4). CONTRACTOR SHALL PROVIDE ALL PROVISIONS REQURIED FOR BACnet MS/TP COMMUNICATION.
4. PROVIDE PRE-TAB ON ALL EQUIPMENT, HYDRONIC COIL VALVES, AND SUPPLY/EXHAUST/RETURN GRILLES, REGISTERS AND DIFFUSERS. AFTER BAS UPGRADES, REBALANCE SYSTEM TO PRE-TAB
AIRFLOWS.
M
VAV
35CV
VAV
DN
OPEN OFFICE
OPEN OFFICE3
RECEIVING
MECHANICAL/
ELECTRICAL
CONF/TRAINING
CONF
FOCUS FOCUS
VESTIBULE
CONF.
IT ROOM
COPY CENTER
OFFICE
136 BREAK
OUTSIDE STORAGE
TRASH/ LOADING
OPEN PATIO
MENS
WOMEN'S
CONF
LOCKER ROOM
MOTHER'S ROOM
UNISEX
RESTROOM
TRASH/STORAGE
VESTIBULE
ELEV.
CONF
OFFICE
FOCUS
FOCUS
BREAK ROOM
E1
CONF.
OFFICE
CONF.
MECHANICAL
STAIR D
D1
ELEV.
EQUIP.
M110
HVAC CONTROLS PLAN
FIRST FLOOR
RAMP
SCOPED AREAS
KEYED NOTES
1 DEMO EXISTING CO SENSOR. NEW BELIMO CO/NO2 SENSOR WITH SPLASH PROOF HOUSING.
USE EXISTING WIRING PATH AND PROVIDE NEW WIRING/RACEWAYS AS NECESSARY PER
SPECIFICATIONS.
DESIGNED DRAWN CHECKED
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
A pr
0,
- 3
:2 5p m
BA
R
IS
O N
E
IN
C H
O N
O R
IG
IN
AL
D
R
AW
IN
G
IF
N O
T O
N E
IN
C
H O
N T
H
IS
D R
AW
IN
G A
D
JU
ST
S
C
AL
ES
A
C C
O R
D
IN
G
LY
22308.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
BAS UPGRADES
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC AND
PARKING
GENERAL NOTES
1. FIELD VERIFY TSTAT LOCATIONS. REMOVE AND REPLACE EXISTING T-STATS
AND CONTROL WIRING.
2. FIELD VERIFY ALL EQUIPMENT LOCATIONS. FOR ALL CONTROLLERS REPLACE FIELD-LEVEL
CONTROLLERS AND COMMUNICATION WIRING TO GATEWAY DEVICE.
3. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM FIELD-LEVEL CONTROLLERS TO
GATEWAY DEVICE SHALL BE OPEN PROTOCOL, BACnet MS/TP (NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT NOT LIMITED TO: ARCnet, U-NET, N2, TAC, P1/2 AND COM3/4). CONTRACTOR SHALL PROVIDE ALL PROVISIONS REQURIED FOR BACnet MS/TP COMMUNICATION.
SCALE: 1/16"=1'-0"
M110
FIRST FLR (GROUND LEVEL) RAMP CONTROLS PLAN
M111
M112
NO2
CO
NO2CO
NO2CO
M111
FIRST FLOOR
NORTHEAST
SCOPED AREAS
SCALE: 1/8"=1'-0"
M111
FIRST FLOOR NORTHEAST OFFICES CONTROLS PLAN
T
T
T
T
T T
T T
T
T
TT
T
T
T T
CNV
CNV
CNV
UH
CUH
FPVAV
19 18
VAV
VAV
VAV
VAV
VAV
CNV
VAV
CV
CNV
CV
CNV
CV
CNV
CV
CNV
CV
UH
CV
VAV
CV
VAV
CV
CUH
CV 19
CV 18
CV 24
CV
VAV
CV 36
CV
VAV
CV
VAV
CV
CUH
CV 17
CV
VAV
CV
UH
T
TO CUH 8 IN BASEMENT
SEE DWG M100
T
TO CUH 7 IN
BASEMENT
SEE DWG M100
KEYED NOTES
PROVIDE ADJUSTABLE T-STATS IN ANY CLOSED/OFFICE SPACE.
PROVIDE FLAT PLATE T-STATS IN ANY SHARED/OPEN SPACE.
DESIGNED DRAWN CHECKED
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
A pr
0,
- 3
:2 5p m
BA
R
IS
O N
E
IN
C H
O N
O R
IG
IN
AL
D
R
AW
IN
G
IF
N O
T O
N E
IN
C
H O
N T
H
IS
D R
AW
IN
G A
D
JU
ST
S
C
AL
ES
A
C C
O R
D
IN
G
LY
22308.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
BAS UPGRADES
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC AND
PARKING
1 VAV-26
T 2
VAV-25
T 1
T 1
M
M
M M
M
M
M
M
M
M
M M
M
M
M
M
M M
M
M
1 2
M
CV 37
T2
FPVAV
FPVAV
FPVAV
CV
CUH
CUH
CUH
FPVAV
FPVAV
FPVAV
FPVAV
FPVAV
VAV
VAV
GENERAL NOTES
1. FIELD VERIFY TSTAT LOCATIONS. REMOVE AND REPLACE EXISTING T-STATS
AND CONTROL WIRING.
2. FIELD VERIFY ALL EQUIPMENT LOCATIONS. FOR ALL CONTROLLERS REPLACE FIELD-LEVEL
CONTROLLERS AND COMMUNICATION WIRING TO GATEWAY DEVICE.
3. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM FIELD-LEVEL CONTROLLERS TO
GATEWAY DEVICE SHALL BE OPEN PROTOCOL, BACnet MS/TP (NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT NOT LIMITED TO: ARCnet, U-NET, N2, TAC, P1/2 AND COM3/4). CONTRACTOR SHALL PROVIDE ALL PROVISIONS REQURIED FOR BACnet MS/TP COMMUNICATION.
4. PROVIDE PRE-TAB ON ALL EQUIPMENT, HYDRONIC COIL VALVES, AND SUPPLY/EXHAUST/RETURN GRILLES, REGISTERS AND DIFFUSERS. AFTER BAS UPGRADES, REBALANCE SYSTEM TO PRE-TAB
AIRFLOWS.
FPVAV-36
FPVAV
UH
T2
DN
OPEN OFFICE
OPEN OFFICE3
RECEIVING
MECHANICAL/
ELECTRICAL
CONF/TRAINING
CONF
FOCUS FOCUS
VESTIBULE
CONF.
IT ROOM
COPY CENTER
OFFICE
136 BREAK
OUTSIDE STORAGE
TRASH/ LOADING
OPEN PATIO
MENS
WOMEN'S
CONF
LOCKER ROOM
MOTHER'S ROOM
UNISEX
RESTROOM
TRASH/STORAGE
VESTIBULE
ELEV.
CONF
OFFICE
FOCUS
FOCUS
BREAK ROOM
E1
CONF.
OFFICE
CONF.
MECHANICAL
STAIR D
D1
ELEV.
EQUIP.
M112
HVAC CONTROLS PLAN
FIRST FLOOR
SOUTHWEST
SCALE: 1/8"=1'-0"
M112
FIRST FLOOR SOUTHWEST OFFICES CONTROLS PLAN
M M
M M
M
M
M
M
M
M
M
M
M T
M
T
T
T
T
T
M
T
MT
M
T
T
T
T
T
M
M
M
M
T
T
T
T
T
T
T
M
T
KEYED NOTES
CV
CUH
CUH
CV
VAV
CV
VAV
CV
VAV
CV
VAV
CV
VAV
CV
UH
CV 2
CV
VAV
CV 3
CV
CUH
CV
CNV
CV
UH
CV
VAV
CV
VAV
CV
VAV
11CV
CUH
CV
CUH
CV
UH
CV
VAV
CV
CUH
CV
CUH
CUH
EF
CNV
CUH
FPVAV
VAV
VAV
VAV
CUH
VAV
VAV
VAV
VAV
VAV
UH
UH
CUH
UH
VAV
SCOPED AREAS
DESIGNED DRAWN CHECKED
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
A pr
0,
- 3
:2 5p m
BA
R
IS
O N
E
IN
C H
O N
O R
IG
IN
AL
D
R
AW
IN
G
IF
N O
T O
N E
IN
C
H O
N T
H
IS
D R
AW
IN
G A
D
JU
ST
S
C
AL
ES
A
C C
O R
D
IN
G
LY
22308.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
BAS UPGRADES
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC AND
PARKING
VAV
CUH
PROVIDE ADJUSTABLE T-STATS IN ANY CLOSED/OFFICE SPACE.
PROVIDE FLAT PLATE T-STATS IN ANY SHARED/OPEN SPACE.
M
M
CV
VAV
CV
VAV
VAV
VAV
T
RF
T
T
T
T
VAV
T
T
FPVAV
FPVAV
M
1CV 8
FPVAV
FPVAV
CV 9
VAV-7
VAV-14
VAV-15
VAV-5
VAV
T
VAV-16
VAV-6
CV
VAV
CV 1
FPVAV
FPVAV
CV
VAV
FPVAVM
M
M
M
FPVAVFPVAV
GENERAL NOTES
1. FIELD VERIFY TSTAT LOCATIONS. REMOVE AND REPLACE EXISTING T-STATS
AND CONTROL WIRING.
2. FIELD VERIFY ALL EQUIPMENT LOCATIONS. FOR ALL CONTROLLERS REPLACE FIELD-LEVEL
CONTROLLERS AND COMMUNICATION WIRING TO GATEWAY DEVICE.
3. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM FIELD-LEVEL CONTROLLERS TO
GATEWAY DEVICE SHALL BE OPEN PROTOCOL, BACnet MS/TP (NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT NOT LIMITED TO: ARCnet, U-NET, N2, TAC, P1/2 AND COM3/4). CONTRACTOR SHALL PROVIDE ALL PROVISIONS REQURIED FOR BACnet MS/TP COMMUNICATION.
4. PROVIDE PRE-TAB ON ALL EQUIPMENT, HYDRONIC COIL VALVES, AND SUPPLY/EXHAUST/RETURN GRILLES, REGISTERS AND DIFFUSERS. AFTER BAS UPGRADES, REBALANCE SYSTEM TO PRE-TAB
AIRFLOWS.
M401
M401
M130
THIRD FLOOR RAMP
SKYWAY
SCOPED AREAS
SCALE: 1/16"=1'-0"
M130
THIRD FLOOR RAMP / SKYWAY CONTROLS PLAN
KEYED NOTES
DESIGNED DRAWN CHECKED
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
A pr
0,
- 3
:2 6p m
BA
R
IS
O N
E
IN
C H
O N
O R
IG
IN
AL
D
R
AW
IN
G
IF
N O
T O
N E
IN
C
H O
N T
H
IS
D R
AW
IN
G A
D
JU
ST
S
C
AL
ES
A
C C
O R
D
IN
G
LY
22308.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
BAS UPGRADES
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC AND
PARKING
GENERAL NOTES
1. FIELD VERIFY TSTAT LOCATIONS. REMOVE AND REPLACE EXISTING
T-STATS
AND CONTROL WIRING.
2. FIELD VERIFY ALL EQUIPMENT LOCATIONS. FOR ALL CONTROLLERS
REPLACE FIELD-LEVEL CONTROLLERS AND COMMUNICATION WIRING TO
GATEWAY DEVICE.
3. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM FIELD-LEVEL
CONTROLLERS TO GATEWAY DEVICE SHALL BE OPEN PROTOCOL, BACnet
MS/TP (NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT
NOT LIMITED TO: ARCnet, U-NET, N2, TAC, P1/2 AND COM3/4).
CONTRACTOR SHALL PROVIDE ALL PROVISIONS REQURIED FOR BACnet
MS/TP COMMUNICATION.
1 DEMO EXISTING CO SENSOR. NEW BELIMO CO/NO2 SENSOR WITH
SPLASH PROOF HOUSING. USE EXISTING WIRING PATH AND PROVIDE
NEW WIRING/RACEWAYS AS NECESSARY PER SPECIFICATIONS.
NO2CO
NO2
CO
NO2
CO
36" Ø EXHAUST DUCT TERMINNATED
12" AFF & CONT. UP (TYP. OF 4)
M402
M140
FOURTH FLOOR RAMP
SCOPED AREAS
DESIGNED DRAWN CHECKED
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
A pr
0,
- 3
:2 6p m
BA
R
IS
O N
E
IN
C H
O N
O R
IG
IN
AL
D
R
AW
IN
G
IF
N O
T O
N E
IN
C
H O
N T
H
IS
D R
AW
IN
G A
D
JU
ST
S
C
AL
ES
A
C C
O R
D
IN
G
LY
22308.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
BAS UPGRADES
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC AND
PARKING
GENERAL NOTES
1. FIELD VERIFY TSTAT LOCATIONS. REMOVE AND REPLACE EXISTING
T-STATS
AND CONTROL WIRING.
2. FIELD VERIFY ALL EQUIPMENT LOCATIONS. FOR ALL CONTROLLERS
REPLACE FIELD-LEVEL CONTROLLERS AND COMMUNICATION WIRING TO
GATEWAY DEVICE.
3. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM FIELD-LEVEL
CONTROLLERS TO GATEWAY DEVICE SHALL BE OPEN PROTOCOL, BACnet
MS/TP (NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT
NOT LIMITED TO: ARCnet, U-NET, N2, TAC, P1/2 AND COM3/4).
CONTRACTOR SHALL PROVIDE ALL PROVISIONS REQURIED FOR BACnet
MS/TP COMMUNICATION.
EF
36" Ø EXHAUST DUCT
UP/DN (TYP. OF 4)
SCALE: 1/16"=1'-0"
M140
FOURTH FLOOR RAMP / SKYWAY CONTROLS PLAN
M170
SEVENTH FLOOR RAMP
ROOF LEVEL
DESIGNED DRAWN CHECKED
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
A pr
0,
- 3
:2 6p m
BA
R
IS
O N
E
IN
C H
O N
O R
IG
IN
AL
D
R
AW
IN
G
IF
N O
T O
N E
IN
C
H O
N T
H
IS
D R
AW
IN
G A
D
JU
ST
S
C
AL
ES
A
C C
O R
D
IN
G
LY
22308.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
BAS UPGRADES
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC AND
PARKING
SCOPED
AREAS
SCALE: 1/4"=1'-0"
M170
MECHANICAL LAYOUT ROOF LEVEL PARKING
EF
EF
EF
EF
EF
EF SHALL BE SEQUENCED WITH GROUND FLOOR CO/NO2 SENSORS. SEE
SEQUENCE OF OPERATION.
EF SHALL BE SEQUENCED WITH THIRD FLOOR CO/NO2 SENSORS. SEE
SEQUENCE OF OPERATION.
GENERAL NOTES
1. FIELD VERIFY TSTAT LOCATIONS. REMOVE AND REPLACE EXISTING
T-STATS
AND CONTROL WIRING.
2. FIELD VERIFY ALL EQUIPMENT LOCATIONS. FOR ALL CONTROLLERS
REPLACE FIELD-LEVEL CONTROLLERS AND COMMUNICATION WIRING
TO GATEWAY DEVICE.
3. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM
FIELD-LEVEL CONTROLLERS TO GATEWAY DEVICE SHALL BE OPEN
PROTOCOL, BACnet MS/TP (NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT NOT LIMITED TO: ARCnet, U-NET, N2, TAC, P1/2
AND COM3/4). CONTRACTOR SHALL PROVIDE ALL PROVISIONS
REQURIED FOR BACnet MS/TP COMMUNICATION.
4. PROVIDE PRE-TAB ON ALL EQUIPMENT, HYDRONIC COIL VALVES, AND
SUPPLY/EXHAUST/RETURN GRILLES, REGISTERS AND DIFFUSERS.
AFTER BAS UPGRADES, REBALANCE SYSTEM TO PRE-TAB AIRFLOWS.
KEYED NOTES
M400
MECHANICAL STAIR C PLANS
BASEMENT THRU THIRD LEVEL
EAST AREA
SCALE: 1/8"=1'-0"
M400
STAIR C THIRD LEVEL ENLARGED CONTROLS PLAN
SCALE: 1/8"=1'-0"
M400
STAIR C PENTHOUSE ENLARGED CONTROLS PLAN
SCALE: 1/8"=1'-0"
M400
STAIR C LEVELS 4 THRU 6 ENGLARGED CONTROLS PLAN
SCALE: 1/8"=1'-0"
M400
STAIR C GROUND LEVEL ENLARGED CONTROLS PLAN
SCALE: 1/8"=1'-0"
M400
STAIR C SEVENTH LEVEL ENLARGED CONTROLS PLAN
SCALE: 1/8"=1'-0"
M400
STAIR C 050 BASEMENT ENLARGED CONTROLS PLAN
T
M
M
M M
T
M
M
M M
DESIGNED DRAWN CHECKED
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
A pr
0,
- 3
:2 6p m
BA
R
IS
O N
E
IN
C H
O N
O R
IG
IN
AL
D
R
AW
IN
G
IF
N O
T O
N E
IN
C
H O
N T
H
IS
D R
AW
IN
G A
D
JU
ST
S
C
AL
ES
A
C C
O R
D
IN
G
LY
22308.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
BAS UPGRADES
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC AND
PARKING
TYP. ALL VIEWS ON SHEET
T
TO AHU-3
CUH
CV
CUH
AHU
T T
UH
UH
CV
UH
CV
UH
AHU
CV1
AHU
CV2
FC
CV2
FC
CV1
FC
P
P
P
P
WH
HEX
P
UH
T1
M M M
GENERAL NOTES
1. FIELD VERIFY TSTAT LOCATIONS. REMOVE AND REPLACE EXISTING T-STATS
AND CONTROL WIRING.
2. FIELD VERIFY ALL EQUIPMENT LOCATIONS. FOR ALL CONTROLLERS REPLACE FIELD-LEVEL
CONTROLLERS AND COMMUNICATION WIRING TO GATEWAY DEVICE.
3. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM FIELD-LEVEL CONTROLLERS TO
GATEWAY DEVICE SHALL BE OPEN PROTOCOL, BACnet MS/TP (NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT NOT LIMITED TO: ARCnet, U-NET, N2, TAC, P1/2 AND COM3/4). CONTRACTOR SHALL PROVIDE ALL PROVISIONS REQURIED FOR BACnet MS/TP COMMUNICATION.
4. PROVIDE PRE-TAB ON ALL EQUIPMENT, HYDRONIC COIL VALVES, AND SUPPLY/EXHAUST/RETURN GRILLES, REGISTERS AND DIFFUSERS. AFTER BAS UPGRADES, REBALANCE SYSTEM TO PRE-TAB
AIRFLOWS.
KEYED NOTES
PROVIDE ADJUSTABLE T-STATS IN ANY CLOSED/OFFICE SPACE.
PROVIDE FLAT PLATE T-STATS IN ANY SHARED/OPEN SPACE.
AREA SHOWN FOR TAB REFERENCE.
SUMP PUMP LOCATION SHOWN FOR ALARM COORDINATION.
SCOPED AREA
M401
MECHANICAL ROOM T112 & T137
SECOND LEVEL
WEST AND SOUTH AREAS
SCALE: 1/8"=1'-0"
M401
SW OFFICE AREA NORTHERN MECH. ROOM ENLARGED CONTROLS PLAN
SCALE: 1/8"=1'-0"
M401
SW OFFICE AREA SOUTHERN MECH. ROOM ENLARGED CONTROLS PLAN
M
M
DESIGNED DRAWN CHECKED
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
A pr
0,
- 3
:2 6p m
BA
R
IS
O N
E
IN
C H
O N
O R
IG
IN
AL
D
R
AW
IN
G
IF
N O
T O
N E
IN
C
H O
N T
H
IS
D R
AW
IN
G A
D
JU
ST
S
C
AL
ES
A
C C
O R
D
IN
G
LY
22308.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
BAS UPGRADES
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC AND
PARKING
CV
UH
UH
WH
AHU
UH
AHU
CV1
AHU
CV2 M
UH
CV
SCOPED AREAS
SCALE: 1/16"=1'-0"
M401
EAST SKYWAY HVAC CONTROLS PLAN
T3
T
TO AHU-43
M402
M400
GENERAL NOTES
1. FIELD VERIFY TSTAT LOCATIONS. REMOVE AND REPLACE EXISTING T-STATS
AND CONTROL WIRING.
2. FIELD VERIFY ALL EQUIPMENT LOCATIONS. FOR ALL CONTROLLERS REPLACE FIELD-LEVEL
CONTROLLERS AND COMMUNICATION WIRING TO GATEWAY DEVICE.
3. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM FIELD-LEVEL CONTROLLERS TO
GATEWAY DEVICE SHALL BE OPEN PROTOCOL, BACnet MS/TP (NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT NOT LIMITED TO: ARCnet, U-NET, N2, TAC, P1/2 AND COM3/4). CONTRACTOR SHALL PROVIDE ALL PROVISIONS REQURIED FOR BACnet MS/TP COMMUNICATION.
4. PROVIDE PRE-TAB ON ALL EQUIPMENT, HYDRONIC COIL VALVES, AND SUPPLY/EXHAUST/RETURN GRILLES, REGISTERS AND DIFFUSERS. AFTER BAS UPGRADES, REBALANCE SYSTEM TO PRE-TAB
AIRFLOWS.
KEYED NOTES
EXISTING BAS CONTROL PANEL. PROVIDE NEW PANEL,
WIRING, AND INTEGRATIONS TO BAS AS REQUIRED.
DEMO EXISTING ENERGY METERING CONTROL PANEL.
PROVIDE FLAT PLATE T-STATS IN ANY SHARED/OPEN SPACE.3
M402
MECHANICAL ROOMS
AND SOUTH SKYWAY
THIRD LEVEL
SCALE: 1/4"=1'-0"
M402
THIRD LEVEL WEST MECHANICAL FLOOR LAYOUT
SCALE: 1/4"=1'-0"
M402
MECHANICAL ROOM 305 ENLARGED PLAN
SCALE: 1/4"=1'-0"
M402
MECHANICAL ROOM 304 ENLARGED PLAN
DESIGNED DRAWN CHECKED
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
A pr
0,
- 3
:2 6p m
BA
R
IS
O N
E
IN
C H
O N
O R
IG
IN
AL
D
R
AW
IN
G
IF
N O
T O
N E
IN
C
H O
N T
H
IS
D R
AW
IN
G A
D
JU
ST
S
C
AL
ES
A
C C
O R
D
IN
G
LY
22308.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
BAS UPGRADES
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC AND
PARKING
SCOPED
AREAS
T
TO AHU-41
M402
M
M
AHU
CV2
AHU
T
UH
MM
AHU
CV1
AHU
CV2
M M
AHU
CV1
AHU
CV1
AHU
AHU
EF
UH
M400
AHU
CV1
GENERAL NOTES
1. FIELD VERIFY TSTAT LOCATIONS. REMOVE AND REPLACE EXISTING T-STATS
AND CONTROL WIRING.
2. FIELD VERIFY ALL EQUIPMENT LOCATIONS. FOR ALL CONTROLLERS REPLACE
FIELD-LEVEL CONTROLLERS AND COMMUNICATION WIRING TO GATEWAY DEVICE.
3. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM FIELD-LEVEL
CONTROLLERS TO GATEWAY DEVICE SHALL BE OPEN PROTOCOL, BACnet MS/TP
(NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT NOT LIMITED
TO: ARCnet, U-NET, N2, TAC, P1/2 AND COM3/4). CONTRACTOR SHALL PROVIDE ALL PROVISIONS REQURIED FOR BACnet MS/TP COMMUNICATION.
4. PROVIDE PRE-TAB ON ALL EQUIPMENT, HYDRONIC COIL VALVES, AND
SUPPLY/EXHAUST/RETURN GRILLES, REGISTERS AND DIFFUSERS. AFTER BAS
UPGRADES, REBALANCE SYSTEM TO PRE-TAB AIRFLOWS.
KEYED NOTES
1 PROVIDE ADJUSTABLE T-STATS IN ANY CLOSED/OFFICE SPACE.
CONTROL POINTS LIST
POINT NAME POINT TYPE SYSTEM COMPONENT DESCRIPTION WORK REQUIRED
CWSupplyTemp AI CHILLED WATER SYSTEM CHILLED WATER SUPPLY TEMP PROVIDE NEW SENSOR TO REPLACE EXISTING
CWReturnTemp AI CHILLED WATER SYSTEM CHILLED WATER RETURN TEMP PROVIDE NEW SENSOR TO REPLACE EXISTING
CWPStatus1 DI CHILLED WATER SYSTEM CHILLED WATER DISTRIBUTION PUMP 1 STATUS REUSE EXISTING CONTROL
CWPEnable1 DO CHILLED WATER SYSTEM CHILLED WATER DISTRIBUTION PUMP 1 COMMAND REUSE EXISTING CONTROL
CWPStatus2 DI CHILLED WATER SYSTEM CHILLED WATER DISTRIBUTION PUMP 2 STATUS REUSE EXISTING CONTROL
CWPEnable2 DO CHILLED WATER SYSTEM CHILLED WATER DISTRIBUTION PUMP 2 COMMAND REUSE EXISTING CONTROL
HWPStatus3 DI HEATING WATER SYSTEM HEATING WATER DISTRIBUTION PUMP 3 STATUS REUSE EXISTING CONTROL
HWPEnable3 DO HEATING WATER SYSTEM HEATING WATER DISTRIBUTION PUMP 3 COMMAND REUSE EXISTING CONNECTION
HWPStatus4 DI HEATING WATER SYSTEM HEATING WATER DISTRIBUTION PUMP 4 STATUS REUSE EXISTING CONTROL
HWPEnable4 DO HEATING WATER SYSTEM HEATING WATER DISTRIBUTION PUMP 4 COMMAND REUSE EXISTING CONNECTION
StmPressure AI DISTRICT STEAM SYSTEM STEAM SYSTEM PRESSURE REUSE EXISTING SENSOR
HWReturnTemp AI HEATING WATER RETURN HEATING WATER RETURN TEMP PROVIDE NEW SENSOR TO REPLACE EXISTING
HWSupplyTemp AI HEATING WATER SUPPLY HEATING WATER SUPPLY TEMP PROVIDE NEW SENSOR TO REPLACE EXISTING
1/3-StmValvePosition AO DISTRICT STEAM SYSTEM 1/3-STEAM CONTROL VALVE FOR HX REUSE EXISTING VALVE
2/3-StmValvePosition AO DISTRICT STEAM SYSTEM 2/3-STEAM CONTROL VALVE FOR HX REUSE EXISTING VALVE
OAT AI BAS SYSTEM OUTDOOR AIR TEMPERATURE SENSOR PROVIDE NEW SENSOR TO REPLACE EXISTING
OARH AI BAS SYSTEM OUTDOOR AIR HUMIDITY SENSOR PROVIDE NEW SENSOR TO REPLACE EXISTING M500
MECHANICAL ROOM 050
STAIR C BASEMENT LEVEL
HW & CW PLANT CONTROLS
AI AI
DO DO
M
M
AI AI
DO DOAO AO
EQUIPMENT LOCATION
DESIGNED DRAWN CHECKED
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
A pr
0,
- 3
:2 6p m
BA
R
IS
O N
E
IN
C H
O N
O R
IG
IN
AL
D
R
AW
IN
G
IF
N O
T O
N E
IN
C
H O
N T
H
IS
D R
AW
IN
G A
D
JU
ST
S
C
AL
ES
A
C C
O R
D
IN
G
LY
22308.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
BAS UPGRADES
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC AND
PARKING
STEAM/HEATING WATER HX AND PUMPS - SEQUENCE OF OPERATION
SYSTEM OPERATES CONSTANTLY. PROVIDE MEANS TO MANUALLY TURN SYSTEM ON/OFF FROM USER INTERFACE.
ENABLE MODE:
· DISTRIBUTION PUMPS: START/STOP THE LEAD HW PUMP AND RUN CONTINUOUSLY. THE PUMPS ARE DESIGNED TO RUN
LEAD/STANDBY. THE PUMPS SHALL ROTATE THEIR LEAD DESIGNATION WEEKLY TO MAINTAIN EVEN RUN TIMES. WHEN ROTATING, START THE NEW LEAD PUMP PRIOR TO STOPPING THE FORMER LEAD PUMP. STANDBY PUMP SHALL
AUTOMATICALLY START UPON FAILURE OF THE LEAD PUMP DURING NOMINAL CONDITIONS.
· 1/3 & 2/3 STEAM CONTROL VALVES AND HX: UPON THE SYSTEM BEING ENABLED, THE 1/3 & 2/3 STEAM VALVES WILL BE MODULATED BY A PID CONTROL LOOP TO MAINTAIN THE REQUIRED HEATING WATER TEMPERATURE SETPOINT. THE VALVES
WILL BE CONTROLLED IN THE FOLLOWING MANNER:
·· THE 1/3 VALVE WILL BE MODULATED FIRST.
·· IF THE OUTPUT OF THE PID CONTROL LOOP EXCEEDS 25% (ADJUSTABLE) FOR MORE THAN 2 MINUTES (ADJ.), THE 2/3
VALVE WILL BECOME THE FIRST VALVE MODULATED MAKING THE 1/3 VALVE CONTROL RANGE SWITCH TO THE 66% TO
100% OUTPUT RANGE OF THE PID CONTROL LOOP.
·· IF THE OUTPUT OF THE PID CONTROL LOOP EXCEEDS 60% (ADJUSTABLE) FOR MORE THAN 2 MINUTES (ADJ.), THE 1/3 VALVE WILL BECOME THE FIRST VALVE MODULATED (THE 1/3 VALVE WILL BE 100% OPEN AT THIS TIME) MAKING THE 2/3 VALVE CONTROL RANGE SWITCH TO THE 33% TO 100% OUTPUT RANGE OF THE PID CONTROL LOOP (THE 2/3 VALVE WILL
BE MODULATING AT THIS TIME).
·· THE REVERSE SEQUENCE SHALL OCCUR AT THE 40% (ADJ.) AND THE 25% (ADJ.) POINTS AS STEAM DEMAND DECREASES.
·· THE SEQUENCE SHALL ALSO RESET ANYTIME THE OUTPUT OF THE PID CONTROL LOOP EQUALS ZERO.
· HEATING WATER SUPPLY TEMPERATURE RESET: THE HEATING WATER SUPPLY TEMP SHALL LINEARLY RESET BASED ON OA TEMPERATURE. AS THE OAT RISES FROM 20°F (ADJ.) TO 65°F (ADJ.), THE HEATING WATER SUPPLY TEMP SETPOINT SHALL
RESET FROM 175°F (ADJ.) TO 120°F (ADJ.).
DISABLE MODE:
· 1/3 & 2/3 STEAM CONTROL VALVES AND HX: UPON THE SYSTEM BEING DISABLED, THE STEAM HX CONTROL VALVES SHALL
CLOSE.
· DISTRIBUTION PUMPS: AFTER THE STEAM VALVES HAVE BEEN CLOSED FOR 5 MIN (ADJ.), THE PUMPS SHALL TURN OFF.
ALARM MODES:
· HI/LO TEMP ALARM: UPON SENSING HEATING WATER SUPPLY TEMP LOWER THAN 100°F (ADJ.) OR HIGHER THAN 190°F (ADJ.)
FOR 20 MINUTES (ADJ.), THE BAS SHALL INITIATE AN ALARM.
· MOTOR ALARM: ANY STATUS THAT DOESN'T MATCH COMMAND WITHIN 30 SEC. (ADJ.).
GENERAL NOTES
1. SOME CONTROL POINTS ARE INTENDED FOR MONITORING ONLY. EXISTING EQUIPMENT TO FOLLOW SEQUENCE OF
OPERATION AS DESCRIBED ON THIS SHEET. TEMPERATURE CONTROL CONTRACTOR TO PROVIDE DEFICIENCY REPORT TO
ENGINEER AND OWNER OF ALL EXISTING TO REMAIN CONTROL DEVICES.
2. CONTROLS CONTRACTOR IS RESPONSIBLE FOR REMOVING ANY DEFUNCT EXISTING CONTROLS INCLUDING, WIRING, TUBING, CONDUIT, PANELS, ACTUATORS, JUNCTION BOXES, ETC. NO CONTROLS EQUIPMENT SHALL BE ABANDONED IN
PLACE.
3. CONTROLS CONTRACTOR SHALL PROVIDE ALL PROVISIONS FOR ANY NEW LOGIC CONTROLLERS NEEDED INCLUDING DRIVERS, WIRING, AND COMMUNICATION CABLING TO MEET THE SEQUENCE OF OPERATION. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM FIELD-LEVEL CONTROLLERS TO GATEWAY DEVICE SHALL BE OPEN PROTOCOL, BACNET MS/TP (NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT NOT LIMITED TO: ARCNET, U-NET, N2, TAC, P1/2 AND COM3/4). CONTRACTOR SHALL PROVIDE ALL PROVISIONS REQUIRED FOR BACNET MS/TP COMMUNICATION.
4. ALL EXISTING GRAPHICS TO BE UPDATED TO WEBCTRL 10 STANDARD GRAPHICS PACKAGE. PROVIDE GRAPHICS
CONFIGURATION THAT MEETS THE CITY OF MINNEAPOLIS GRAPHICS STANDARD.
KEYED NOTES
1 PROVIDE NEW CONTROL DEVICE.
PROVIDE NEW COMBINATION OAT/OARH SENSOR WITH
RADIATION SHIELD. INSTALL SENSORS AWAY FROM
DIRECT SUNLIGHT, BUILDING EXHAUST, OR OTHER
HEATING/COOLING SOURCES.
IF SPECIFIED COMMUNICATION PROTOCOL CAN'T BE
MET WITH EXISTING BAS CONTROLLER, PROVIDE NEW
BAS CONTROLLER.
EXISTING BAS CONTROLLER HAS FAILED OUTPUTS.
PROVIDE NEW BAS CONTROLLER.
AI
AI
AI
DI DIDIDI
M
CHILLED WATER HX AND PUMPS - SEQUENCE OF OPERATION
SYSTEM OPERATES BASED ON OAT ENABLE SETPOIN. PROVIDE MEANS TO MANUALLY TURN SYSTEM ON/OFF FROM USER
INTERFACE.
ENABLE MODE:
· OAT ENABLE: WHEN THE OAT RISES ABOVE THE CHW ENABLE SETPOINT OF 55°F (ADJ. W/ 3°F DB) THE CHILLED WATER
SYSTEM SHALL BE ENABLED.
· DISTRIBUTION PUMPS: START/STOP THE LEAD CHW PUMP AND RUN CONTINUOUSLY. THE PUMPS ARE DESIGNED TO RUN
LEAD/STANDBY. THE PUMPS SHALL ROTATE THEIR LEAD DESIGNATION WEEKLY TO MAINTAIN EVEN RUN TIMES. WHEN ROTATING, START THE NEW LEAD PUMP PRIOR TO STOPPING THE FORMER LEAD PUMP. STANDBY PUMP SHALL
AUTOMATICALLY START UPON FAILURE OF THE LEAD PUMP DURING NOMINAL CONDITIONS.
DISABLE MODE:
· OAT DISABLE: WHEN THE OAT FALLS BELOW THE CHW ENABLE SETPOINT, THE CHILLED WATER SYSTEM SHALL BE DISABLED.
· DISTRIBUTION PUMPS: THE PUMPS SHALL TURN OFF.
ALARM MODES:
· HI TEMP ALARM: UPON SENSING CHILLED WATER SUPPLY TEMP HIGHER THAN 50°F (ADJ.) FOR 20 MINUTES (ADJ.), THE BAS
SHALL INITIATE AN ALARM.
· MOTOR ALARM: ANY STATUS THAT DOESN'T MATCH COMMAND WITHIN 30 SEC. (ADJ.).
M501
MECHANICAL ROOM 304
FIRST FLOOR SW OFFICES
AHU-1 CONTROLS
AI
AI
DO
AO DI
AIAIDO
M
M
AOAO
CONTROL POINTS LIST
POINT NAME POINT TYPE SYSTEM COMPONENT DESCRIPTION WORK REQUIRED
MaDmpr AO MIXED AIR MIXED AIR DAMPER CONTROL REUSE EXISTING ACTUATORS
RlfDmpr AO RELIEF AIR RELIEF AIR DAMPER CONTROL REUSE EXISTING ACTUATOR
MaTemp AI MIXED AIR MIXED AIR TEMPERATURE SENSOR REUSE EXISTING SENSOR
RFanStatus AI RETURN FAN RETURN FAN REUSE EXISTING CONTROL (HZ FEEDBACK W/ DIGITAL STS)
RFanEnable DO RETURN FAN RETURN FAN REUSE EXISTING CONNECTION
RFanSpeed AO RETURN FAN RETURN FAN REUSE EXISTING CONNECTION
FrzStat DI MIXED AIR MIXED AIR FREEZE STAT LOW LIMIT ALARM REUSE EXISTING SENSOR HtgValvePosition AO HEATING WATER COIL HEATING WATER CONTROL VALVE REUSE EXISTING VALVE/ACTUATOR
ClgValvePosition AO CHILLED WATER COIL CHILLED WATER CONTROL VALVE REUSE EXISTING VALVE/ACTUATOR
SFanStatus AI SUPPLY FAN SUPPLY FAN REUSE EXISTING CONTROL (HZ FEEDBACK W/ DIGITAL STS)
SFanEnable DO SUPPLY FAN SUPPLY FAN REUSE EXISTING CONNECTION
SFanSpeed AO SUPPLY FAN SUPPLY FAN REUSE EXISTING CONNECTION
RaTemp AI RETURN AIR RETURN AIR TEMPERATURE SENSOR REUSE EXISTING SENSOR
RaHum AI RETURN AIR RETURN AIR HUMIDITY SENSOR PROVIDE NEW SENSOR TO REPLACE EXISTING
RaSmk DI RETURN AIR RETURN AIR SMOKE DETECTOR REUSE EXISTING SENSOR
SaPressure AI SUPPLY AIR SUPPLY AIR PRESSURE SENSOR PROVIDE NEW SENSOR TO REPLACE EXISTING
SaTemp AI SUPPLY AIR SUPPLY AIR TEMPERATURE SENSOR REUSE EXISTING SENSOR
ZnPressure AI ZONE AREA ZONE PRESSURE SENSOR PROVIDE NEW SENSOR TO REPLACE EXISTING
AO
AHU-1 - SEQUENCE OF OPERATION
SYSTEM OPERATES AS OCCUPIED/UNOCCUPIED ACCORDING TO ITS OPTIMAL OPERATING SCHEDULE.
OCCUPIED MODE:
· START/STOP THE SUPPLY FAN AND RETURN FAN ACCORDING TO THE OPTIMAL START SCHEDULE AND RUN CONTINUOUSLY.
UNIT SHALL OPERATE IN FULL RECIRCULATION MODE (RETURN AIR DAMPER 100% OPEN, OA DAMPER CLOSED, AND RELIEF DAMPER CLOSED) UNTIL SPACE SET POINTS ARE MET OR SPACES ARE OCCUPIED BY MEANS OF OCCUPANCY SENSOR. THEN
UNIT SHALL RUN IN MINIMUM VENTILATION MODE.
· SUPPLY FAN SPEED CONTROL: THE VARIABLE SPEED DRIVE CONTROLLING THE SUPPLY FAN MOTOR SPEED SHALL MAINTAIN THE STATIC PRESSURE SETPOINT 1 INWC (ADJ.) AT THE STATIC PRESSURE SENSOR, LOCATED A MINIMUM 2/3S DOWN THE SUPPLY DUCT MAIN. THE SUPPLY DUCT STATIC PRESSURE SHALL AUTOMATICALLY RESET DOWNWARDS FROM DEFAULT (AS SET BY THE BALANCING CONTRACTOR) IN ORDER TO KEEP AT LEAST ONE ASSOCIATED VAV BOX CONTROL DAMPER BETWEEN
95% AND 99% OPEN POSITION.
· RETURN FAN SPEED CONTROL: THE VARIABLE SPEED DRIVE CONTROLLING THE RETURN FAN MOTORS SPEED SHALL TRACK THE SUPPLY FAN SPEED AND CALCULATE THE RETURN FAN SPEED SIGNAL AS A PERCENTAGE OF SUPPLY FAN SPEED SIGNAL VIA THE RETURN FAN SPEED TRACKING SETPOINT OF 85% (ADJ.). I.E. - SUPPLY FAN SPEED SIGNAL OF 74.6% MULTIPLIED BY THE RETURN FAN SPEED TRACKING SETPOINT OF 85%, WILL GIVE YOU A RETURN FAN SPEED OF 63.4%.
· MINIMUM VENTILATION: OPEN THE OUTDOOR AIR DAMPER AND MODULATE OUTDOOR, RETURN AND RELIEF DAMPERS TO MAINTAIN MINIMUM DAMPER POSITION SETPOINT. REFER TO SCHEDULE AND COORDINATE DAMPER SETPOINT WITH
BALANCING CONTRACTOR.
· SUPPLY AIR TEMPERATURE RESET: THE SUPPLY AIR TEMPERATURE SETPOINT SHALL RESET BETWEEN THE MINIMUM AND MAXIMUM SUPPLY AIR TEMPERATURE SETPOINTS OF 55°F (ADJ.) AND 65°F (ADJ.). THE ACTIVE SUPPLY AIR TEMPERATURE SETPOINT SHALL BE CALCULATED BASED ON THE MAXIMUM SPACE COOLING SIGNAL OF APPROPRIATE VAV BOXES AS
DETERMINED BY THE COMMISSIONING AUTHORITY AND/OR OWNER.
· ECONOMIZER COOLING: WHEN BOTH OUTDOOR AIR DEWPOINT AND DRY-BULB TEMPERATURES ARE BELOW THEIR RESPECTIVE ECONOMIZER ENABLE SETPOINTS OF 67°F DRY-BULB (ADJ.) AND 52°F DEWPOINT (ADJ.), THE UNIT SHALL ENTER ECONOMIZER MODE. MODULATE THE OUTDOOR AIR AND RETURN AIR DAMPERS TO MAINTAIN A MIXED AIR TEMPERATURE SETPOINT. THE MIXED AIR TEMPERATURE SETPOINT SHALL TRACK THE SUPPLY AIR TEMPERATURE SETPOINT WITH AN
ADJUSTABLE OFFSET INITIALLY SET AT +1°F. (SAT SP = 55°F THEN MAT SP = 56°F)
· SPACE PRESSURE CONTROL: PROVIDE MEANS TO SWITCH CONTROL STRATEGIES FOR SPACE PRESSURE BETWEEN: 1) THE RELIEF DAMPER TRACKING THE OA DAMPER. 2) THE RELIEF DAMPER MAINTAINING THE SPACE PRESSURE SETPOINT OF 0.04
INWC (ADJ.) BY MODULATING +/- 15% (ADJ.) OF THE OA DAMPER SIGNAL.
· CHW COOLING MODE: WHEN EITHER OUTDOOR AIR DRY-BULB OR DEWPOINT ARE ABOVE THEIR RESPECTIVE ECONOMIZER ENABLE SETPOINTS, THE UNIT DAMPERS SHALL BE CONTROLLED TO MINIMUM VENTILATION AND CHILLED WATER COIL
CONTROL VALVE SHALL MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT.
· DEHUMIDIFICATION MODE: WHEN THE RETURN AIR RELATIVE HUMIDITY OR SPACE RELATIVE HUMIDITY EXCEEDS THE MAXIMUM RELATIVE HUMIDITY SETPOINT OF 55%RH (ADJ.), THE UNIT SHALL RETURN TO MINIMUM VENTILATION MODE AND THE CHILLED WATER COIL CONTROL VALVE SHALL BE SET TO 100% (ADJ.) OPEN AND THE HEATING WATER COIL CONTROL
VALVE SHALL MAINTAIN THE SUPPLY AIR TEMP SETPOINT.
· HW HEATING MODE: THE HEATING COIL CONTROL VALVE SHALL MODULATE TO MAINTAIN SUPPLY AIR TEMP SETPOINT.
PROGRAMMING SHALL BE WRITTEN TO AVOID OVERLAPPING OF HEATING AND COOLING CONTROL WHEN NOT
DEHUMIDIFYING.
UNOCCUPIED MODE:
· AHU/RTU SHALL TURN ON AND RUN IN RECIRCULATION MODE (RA DAMPER OPEN, OA/RLF DAMPERS CLOSED) WITH THE
SUPPLY & RETURN FANS ON IF ANY SPACE TEMPERATURE FALLS BELOW THE AHU/RTU UNOCCUPIED HEATING SETPOINT OF 60°F (ADJ.) OR RISES ABOVE THE AHU/RTU UNOCCUPIED COOLING SETPOINT OF 83°F (ADJ.). THE HEATING AND CHILLED WATER COIL CONTROL VALVES SHALL MODULATE TO MAINTAIN SUPPLY AIR TEMPERATURE SET POINT AS DESCRIBED IN THE OCCUPIED SEQUENCE. THE VAV REHEAT COILS SHALL MAINTAIN THEIR UNOCCUPIED SPACE TEMPERATURE SETPOINTS. THE AHU/RTU SHALL TURN OFF WHEN ALL ZONES HAVE BEEN SATISFIED AND ARE ABOVE 63°F (ADJ.) AND BELOW 80°F (ADJ.).
WHEN THE UNIT IS NOT RUNNING, THE HEATING CONTROL VALVE SHALL MAINTAIN AN INTERNAL UNIT TEMPERATURE OF 50°F
(ADJ.) AT THE MAT/SAT SENSORS.
ALARM MODES:
· FREEZE ALARM: UPON SENSING LOW LIMIT SUPPLY TEMPERATURE OF 35°F (ADJ.), CLOSE THE OUTDOOR AIR DAMPER, SHUT
DOWN THE FANS, AND ALARM WITH THE HEATING VALVE OPEN 100%.
· SMOKE ALARM: SMOKE DETECTOR SENSING SMOKE SHALL SHUT DOWN THE FANS, CLOSE THE OUTDOOR AIR AND EXHAUST
AIR DAMPERS, AND SEND AN ALARM TO THE FIRE ALARM SYSTEM.
· MOTOR ALARM: ANY STATUS THAT DOESN'T MATCH COMMAND WITHIN 30 SEC. (ADJ.). SHUT DOWN THE FANS, CLOSE THE
OUTDOOR AIR AND EXHAUST AIR DAMPERS, AND SEND AN ALARM TO THE HEAD END.
· SAFETY CIRCUIT ALARM: PRESSURE SWITCHES BOTH POSITIVE AND NEGATIVE FOR EACH FAN. SHUT DOWN THE FANS, CLOSE
THE OUTDOOR AIR AND EXHAUST AIR DAMPERS, AND SEND AN ALARM TO THE HEAD END.
· ANY SPACE DROPPING BELOW A FREEZE ALARM LIMIT OF 40°F (ADJ.) SHALL INITIATE A FREEZE ALARM AND PROVIDE A
BUILDING FREEZE ALARM SIGNAL TO THE MAINTENANCE STAFF PAGING SYSTEM.
DESIGNED DRAWN CHECKED
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
A pr
0,
- 3
:2 7p m
BA
R
IS
O N
E
IN
C H
O N
O R
IG
IN
AL
D
R
AW
IN
G
IF
N O
T O
N E
IN
C
H O
N T
H
IS
D R
AW
IN
G A
D
JU
ST
S
C
AL
ES
A
C C
O R
D
IN
G
LY
22308.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
BAS UPGRADES
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC AND
PARKING
AIDI AI
AO
GENERAL NOTES
1. SOME CONTROL POINTS ARE INTENDED FOR MONITORING ONLY. EXISTING EQUIPMENT TO FOLLOW SEQUENCE OF
OPERATION AS DESCRIBED ON THIS SHEET. TEMPERATURE CONTROL CONTRACTOR TO PROVIDE DEFICIENCY REPORT TO
ENGINEER AND OWNER OF ALL EXISTING TO REMAIN CONTROL DEVICES.
2. CONTROLS CONTRACTOR IS RESPONSIBLE FOR REMOVING ANY DEFUNCT EXISTING CONTROLS INCLUDING, WIRING, TUBING, CONDUIT, PANELS, ACTUATORS, JUNCTION BOXES, ETC. NO CONTROLS EQUIPMENT SHALL BE ABANDONED IN
PLACE.
3. CONTROLS CONTRACTOR SHALL PROVIDE ALL PROVISIONS FOR ANY NEW LOGIC CONTROLLERS NEEDED INCLUDING DRIVERS, WIRING, AND COMMUNICATION CABLING TO MEET THE SEQUENCE OF OPERATION. ALL NEW WIRING AND COMMUNICATION PROTOCOLS FROM FIELD-LEVEL CONTROLLERS TO GATEWAY DEVICE SHALL BE OPEN PROTOCOL, BACNET MS/TP (NO PROPRIETARY PROTOCOLS SHALL BE USED, INCLUDING BUT NOT LIMITED TO: ARCNET, U-NET, N2, TAC, P1/2 AND COM3/4). CONTRACTOR SHALL PROVIDE ALL PROVISIONS REQUIRED FOR BACNET MS/TP COMMUNICATION.
4. ALL EXISTING GRAPHICS TO BE UPDATED TO WEBCTRL 10 STANDARD GRAPHICS PACKAGE. PROVIDE GRAPHICS
CONFIGURATION THAT MEETS THE CITY OF MINNEAPOLIS GRAPHICS STANDARD.
KEYED NOTES
1 PROVIDE NEW CONTROL DEVICE.
IF SPECIFIED COMMUNICATION PROTOCOL CAN'T BE
MET WITH EXISTING BAS CONTROLLER, PROVIDE NEW
BAS CONTROLLER.
AO
AI
AI
EQUIPMENT LOCATION
M502
MECHANICAL ROOM 304
THIRD LEVEL SW SKYWAY
AHU-2 CONTROLS
AI
AI
DO
AO DI
AIDO
M
M
AOAO
CONTROL POINTS LIST
POINT NAME POINT TYPE SYSTEM COMPONENT DESCRIPTION WORK REQUIRED
MaDmpr AO MIXED AIR MIXED AIR DAMPER CONTROL REUSE EXISTING ACTUATORS
MaTemp AI MIXED AIR MIXED AIR TEMPERATURE SENSOR REUSE EXISTING SENSOR
RFanStatus DI RETURN FAN RETURNFAN REUSE EXISTING CONNECTION
RFanEnable DO RETURN FAN RETURN FAN REUSE EXISTING CONNECTION
FrzStat DI MIXED AIR MIXED AIR FREEZE STAT LOW LIMIT ALARM REUSE EXISTING SENSOR HtgValvePosition AO HEATING WATER COIL HEATING WATER CONTROL VALVE REUSE EXISTING ACTUATED VALVE
ClgValvePosition AO CHILLED WATER COIL CHILLED WATER CONTROL VALVE REUSE EXISTING ACTUATED VALVE
SFanStatus DI SUPPLY FAN SUPPLY FAN REUSE EXISTING CONNECTION
SFanEnable DO SUPPLY FAN SUPPLY FAN REUSE EXISTING CONNECTION
RaTemp AI RETURN AIR RETURN AIR TEMPERATURE SENSOR REUSE EXISTING SENSOR
RaHum AI RETURN AIR RETURN AIR HUMIDITY SENSOR PROVIDE NEW SENSOR TO REPLACE EXISTING
RaSmk DI RETURN AIR RETURN AIR SMOKE DETECTOR REUSE EXISTING SENSOR
SaTemp AI SUPPLY AIR SUPPLY AIR TEMPERATURE SENSOR REUSE EXISTING SENSOR
RmTemp AI ZONE AREA SPACE TEMPERATURE SENSOR PROVIDE NEW SENSOR TO REPLACE EXISTING
AHU-2 - SEQUENCE OF OPERATION
SYSTEM OPERATES AS OCCUPIED/UNOCCUPIED ACCORDING TO ITS OPTIMAL OPERATING SCHEDULE.
OCCUPIED MODE:
· START/STOP THE SUPPLY FAN AND RETURN FAN ACCORDING TO THE OPTIMAL START SCHEDULE AND RUN CONTINUOUSLY.
UNIT SHALL OPERATE IN FULL RECIRCULATION MODE (RETURN AIR DAMPER 100% OPEN, OA DAMPER CLOSED, AND RELIEF DAMPER CLOSED) UNTIL SPACE SET POINTS ARE MET OR SPACES ARE OCCUPIED BY MEANS OF OCCUPANCY SENSOR. THEN
UNIT SHALL RUN IN MINIMUM VENTILATION MODE.
· MINIMUM VENTILATION: OPEN THE OUTDOOR AIR DAMPER AND MODULATE OUTDOOR, RETURN AND RELIEF DAMPERS TO MAINTAIN MINIMUM DAMPER POSITION SETPOINT. REFER TO SCHEDULE AND COORDINATE DAMPER SETPOINT WITH
BALANCING CONTRACTOR.
· SUPPLY AIR TEMPERATURE RESET: THE SUPPLY AIR TEMP SETPOINT SHALL BE RESET BASED ON SPACE TEMPERATURE VS
SETPOINT 72°F (ADJ.).
· ECONOMIZER COOLING: WHEN BOTH OUTDOOR AIR DEWPOINT AND DRY-BULB TEMPERATURES ARE BELOW THEIR RESPECTIVE ECONOMIZER ENABLE SETPOINTS OF 67°F DRY-BULB (ADJ.) AND 52°F DEWPOINT (ADJ.), THE UNIT SHALL ENTER ECONOMIZER MODE. MODULATE THE OUTDOOR AIR AND RETURN AIR DAMPERS TO MAINTAIN A MIXED AIR TEMPERATURE SETPOINT. THE MIXED AIR TEMPERATURE SETPOINT SHALL TRACK THE SUPPLY AIR TEMPERATURE SETPOINT WITH AN
ADJUSTABLE OFFSET INITIALLY SET AT +1°F. (SAT SP = 55°F THEN MAT SP = 56°F)
· CHW COOLING MODE: WHEN EITHER OUTDOOR AIR DRY-BULB OR DEWPOINT ARE ABOVE THEIR RESPECTIVE ECONOMIZER ENABLE SETPOINTS, THE UNIT DAMPERS SHALL BE CONTROLLED TO MINIMUM VENTILATION AND CHILLED WATER COIL
CONTROL VALVE SHALL MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT.
· DEHUMIDIFICATION MODE: WHEN THE RETURN AIR RELATIVE HUMIDITY OR SPACE RELATIVE HUMIDITY EXCEEDS THE MAXIMUM RELATIVE HUMIDITY SETPOINT OF 55%RH (ADJ.), THE UNIT SHALL RETURN TO MINIMUM VENTILATION MODE AND THE CHILLED WATER COIL CONTROL VALVE SHALL BE SET TO 100% (ADJ.) OPEN AND THE HEATING WATER COIL CONTROL VALVE
SHALL MAINTAIN THE SUPPLY AIR TEMP SETPOINT.
· HW HEATING MODE: THE HEATING COIL CONTROL VALVE SHALL MODULATE TO MAINTAIN SUPPLY AIR TEMP SETPOINT.
PROGRAMMING SHALL BE WRITTEN TO AVOID OVERLAPPING OF HEATING AND COOLING CONTROL WHEN NOT
DEHUMIDIFYING.
UNOCCUPIED MODE:
· AHU/RTU SHALL TURN ON AND RUN IN RECIRCULATION MODE (RA DAMPER OPEN, OA/RLF DAMPERS CLOSED) WITH THE
SUPPLY & RETURN FANS ON IF THE SPACE TEMPERATURE FALLS BELOW THE AHU/RTU UNOCCUPIED HEATING SETPOINT OF 60°F (ADJ. WITH +3°F DEADBAND) OR RISES ABOVE THE AHU/RTU UNOCCUPIED COOLING SETPOINT OF 83°F (ADJ. WITH -3°F DEADBAND). THE HEATING AND CHILLED WATER COIL CONTROL VALVES SHALL MODULATE TO MAINTAIN SUPPLY AIR TEMPERATURE SET POINT AS DESCRIBED IN THE OCCUPIED SEQUENCE. THE AHU/RTU SHALL TURN OFF WHEN ALL ZONES HAVE BEEN SATISFIED AND ARE ABOVE 63°F (ADJ.) AND BELOW 80°F (ADJ.). WHEN THE UNIT IS NOT RUNNING, THE HEATING CONTROL VALVE SHALL MAINTAIN AN INTERNAL UNIT TEMPERATURE OF 50°F (ADJ.) AT THE MAT/SAT SENSORS.
ALARM MODES:
· FREEZE ALARM: UPON SENSING LOW LIMIT SUPPLY TEMPERATURE OF 35°F (ADJ.), CLOSE THE OUTDOOR AIR DAMPER, SHUT
DOWN THE FANS, AND ALARM WITH THE HEATING VALVE OPEN 100%.
· SMOKE ALARM: SMOKE DETECTOR SENSING SMOKE SHALL SHUT DOWN THE FANS, CLOSE THE OUTDOOR AIR AND EXHAUST
AIR DAMPERS,…
This is the start of the file's text. The full file is on GovTribe.