Performance Work Statement Elevator Service (FR).docx
DOCX document 48 KB Posted
- Attached to
- J099--Syracuse VAMC Elevator Maintenance Federal contract opportunity
- Solicitation number
- 36C24220Q0724
About this file
This combined synopsis/solicitation from the Department of Veterans Affairs seeks quotes for elevator maintenance services at the Syracuse VA Medical Center. The contractor shall provide all parts, labor, equipment, and personnel identified in the attached performance work statement to maintain 21 elevators located across various buildings on the medical center campus. Quotes are due by July 13, 2020 and must include pricing for a one-year base period of performance from July 1, 2020 to June 30, 2021, as well as pricing for four one-year option periods. The contractor will also be expected to respond to emergency repair calls within two hours and provide 24/7 emergency callback services. A site visit is scheduled for potential vendors to tour the medical center facilities. The government intends to make award to the lowest priced technically acceptable offer with acceptable past performance.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| P09-QASP- Elevator Syracuse.docx | DOCX document | |
| 36C24220Q0724 0001_1.docx | DOCX document | |
| Price Schedule.docx | DOCX document | |
| P09-QASP- Elevator.docx | DOCX document | |
| P07 WD 1967-0484 Elevator Repairer.pdf | ||
| 36C24220Q0724.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
B.3 PERFORMANCE WORK STATEMENT
A. The Syracuse VA Medical Center requires a firm fixed price contract for a base July 1, 2020 thru June 30, 2021 plus a provision of four (4) option years for elevator service and maintenance on 21 elevators (4 hydraulic and 17 electric) located at the Syracuse VA Medical Center 800 Irving Avenue, Syracuse, NY 13210. The service and maintenance shall include all parts, labor, materials, supervision, tools, supplies and any other necessary items to perform:
1. All scheduled inspections, services, testing, adjustments and repairs and/or replacement parts for all elevators, and related to operations, functions and safety.
2. All required unscheduled adjustments, services and repairs for all elevator during business hours.
3. 24 hr. a day/ 7 days a week emergency call back shall be within two (2) hours of telephone request.
B. All service and repair work shall be performed in compliance with the latest approved edition of the ASME A17.1/CSA B44-2019: Safety Code For Elevators And Escalators, as of 2019 (American National Standard Institute Elevator Code – ANSI, and American National Standard Institute, Inspectors Manual – ANI, A17.2). As well as all other applicable code including NFPA 70E and OSHA Requirements - OHSA 1917.116 - Elevators and escalators; OSHA 1926.552 - Material hoists, personnel hoists, and elevators; OSHA 1910.147 The Control of Hazardous Energy (lockout/tagout).
B.3.1 GENERAL REQUIREMENTS
Table 1 Elevators to be Services
| # |
| Manufacturer / Type / Elevator ID Number |
| Location |
| 1 |
| Schindler / Electric Passenger Elev / 1680-PA01 |
| Bldg. l, C wing |
| 2 |
| Schindler / Electric Passenger Elev / 1680-PA02 |
| Bldg. l, C wing |
| 3 |
| Schindler / Electric Passenger Elev /1680-PA03 |
| Bldg. l, C wing |
| 4 |
| Schindler / Electric Passenger Elev / 1680-PA04 |
| Bldg. l, C wing |
| 5 |
| Schindler / Electric Service Elev / 1680-FR05 |
| Bldg. l, C wing |
| 6 |
| Schindler / Electric Service Elev / 1680-FR06 |
| Bldg. l, C wing |
| 7 |
| Otis / Electric Passenger Elev / 1680-PA07 |
| Bldg. 19 Garage |
| 8 |
| Otis / Electric Passenger Elev / 1680-PA08 |
| Bldg. 19 Garage |
| 9 |
| Otis / Electric Passenger Elev / 1680-PA09 |
| Bldg. 19 Garage |
| 10 |
| Otis / Electric Passenger Elev / 1680-PA10 |
| Bldg. 19 Garage |
| 11 |
| Otis / Electric Passenger Elev / 1680-PA05 |
| Bldg. 1, D wing |
| 12 |
| Dover / Hydraulic Passenger Elev / 1680-PA06 |
| Bldg. 2 |
| 13 |
| Schindler / Electric Service Elev / 1680-SR03 |
| Bldg. 1 Swing |
| 14 |
| Schindler / Electric Service Elev / 1680-SR04 |
| Bldg. 1 Swing |
| 15 |
| Global-Tardif / Hydraulic Elev / 1680-SR05 |
| Bldg. 1 Swing |
| 16 |
| Schindler / Electric Passenger Elev / 1680-PA11 |
| Bldg. 1 Swing |
| 17 |
| Schindler / Electric Passenger Elev / 1680-PA12 |
| Bldg. 1 Swing |
| 18 |
| Global-Tardif / Hydraulic Elev / 1680-PA13 |
| Bldg. 1 Swing |
| 19 |
| Global-Tardif / Hydraulic Elev / 1680-PA14 |
| Bldg. 1 Swing |
| 20 |
| Schindler / Electric Passenger Elev / 1680-PA15 |
| Bldg. 1 Swing |
| 21 |
| Schindler / Electric Passenger Elev / 1680-PA16 |
| Bldg. 1 Swing |
B.3.1.1 CONTRACTOR QUALIFICATION
A. The contractor shall have 5 years of experience providing elevator maintenance services and assigned elevator mechanics and apprentices shall be certified by the International Union of Elevator Contractors or have equivalent qualifications. Elevator Mechanics shall have 3 years of experience maintaining elevators of the same type listed. The Contracting Officer (CO) shall review for approval the qualifications and approve each elevator mechanic and apprentice before they can perform on-site repairs for this requirement.
B. A certified Journeyman mechanic shall be present at all times when apprentices are performing maintenance at the Syracuse VA Medical Center.
B.3.1.2 WORKING HOURS:
A. The Maintenance work shall normally be performed during regular working hours. Regular working hours for this purchase order shall be defines as 7:00 am to 4:30 pm Monday through Friday except Federal Holidays as follows:
New Year’s Day Martin Luther King’s Birthday President’s Day Memorial Day Independence Day Labor Day Columbus Day Veterans Day Thanksgiving Christmas
*To include any other day the President declares a Federal Holiday
B. The contractor shall report to the Contracting Officer Representative (COR), before and after performance of service, providing evidence of service performed. Time and a half labor rate shall come into effect for work performed outside of normal business hours as defined above. Double time labor comes into effect for work performed outside on Sundays and Federal Holidays. The wage premiums for both time and a half and double-time rates in excess of those stated in B.4.2 paragraph C shall be considered within the scope of this contract, but not funded. Additional Overtime (OT) premiums not covered under section B.3.2.4 paragraph C shall be funded either by a purchase card or by a modification to the contract by the Contracting Officer as required.
B.3.1.3 SCOPE OF COVERAGE
A. The Contractor shall not be required to make renewals or repairs necessitated by proven negligence or misuse of the equipment by persons other than the Contractor, Contractor representative and employees, or by reason of any other proven cause except for normal wear and tear. All needed repairs caused by negligence and abuse shall not be considered within the scope of this contract and shall be funded separately.
Examples of these:
Refinishing, repairing, or replacing car enclosures, hoistway enclosures, hoistway door panels, frames and sills, and primary distribution power supply panels and feeders. Cost of repairs, replacements or removal necessitated by any cause, other than ordinary wear, which is occasioned by negligence or abuse by personal other than the Contractor. Negligence or abuse shall be determined by a joint decision as may be arrived at by qualified representatives of the VA and the Contractor, and/or by qualified 3rd party retained by the VA.
B. The Contractor shall not be responsible for upgrading equipment to meet changes in code requirements as directed by insurance companies, federal, state, municipal, or other governmental authorities.
C. The Contractor shall be responsible for notifying the COR, in writing, of the existence or development of any defects in, or repairs required to, the elevator equipment which the Contractor does not consider to be the Contractors responsibility under the terms of the contract.
D. The Contractor shall be responsible for giving immediate notice to the Contracting Officer's Representative (COR) or their designated representative of any condition which is discovered that may present a hazard to either the equipment or passengers.
B.3.1.4 PARTS
A. The Contractor shall be responsible for furnishing and installation of replacement parts for the following elevator system components:
1. Motors
2. Generators
3. Controllers
4. Selectors
5. Worms
6. Gear
7. Thrust bearings
8. Windings
9. Commutators
10. Armatures
11. Pulleys
12. Traction sheaves
13. Hoist cables
14. Coils
15. Circuits
16. Magnet frames
17. Relays
18. Contacts
19. Printed circuit boards
20. Solid state controls
21. Logic circuits
22. Control fuses
23. Cams
24. Car doors
25. Hoist way door hangers
26. Tracks and door gibs
27. Door operating devices
28. Interlocks and contacts
29. Safety devices
30. Governors
31. Push buttons
32. Annunciators
33. Integrated circuit board batteries
34. Emergency car light and all batteries, including those for emergency lowering, smoke and fire sensors and related equipment
35. Hall lanterns and indicators
36. Lamp replacement in signal systems and all other elevator signal and accessory equipment
37. Circuit breakers and/or main line switches together with fuses or same are excluded
All parts shall be of the original manufacturer's design and specification or equal.
B. Existing elevator intercom system shall be maintained according to manufacturer’s specifications. The manufacturer's name and remote annunciator console locations are as follows:
1. Manufacturer-Executone
2. Annunciator Locations- Police dispatch and telephone operators' room
C. In addition to the minor spare parts herein before specified, the Contractor shall have available at all times, for immediate delivery and installation, sufficient supply of the following spare parts for the repair of each elevator system concerned, the inventory shall include, but not necessarily be limited to the following:
1. Lamps, minimum two (2) each type
2. Door operator motor s and gear reduction units, for both side slide and vertical bi-parting doors
3. Transformers and rectifiers for each type and size used
4. Relays and switches, minimum one of each type
5. Controller and selector switch contacts and coils for each size and type used
6. Selector tapes and selector motor (when used), leveling switches, magnets and induction
7. Door interlocks
8. Car door safety device
9. Car door electric door detectors complete to include preamplifiers and power pack
10. Hanger rollers for both car and hall doors
11. Limit switches and terminal stopping switches
12. Roller guides for car
13. Electronic tubes for each type and size used
14. Flexible guide shoe gibs
15. Torque wrenches and other small tools
16. Pressure, relief and control valves for each type and size used (hydraulic elevator)
17. Any/all network system - computer components that cannot be substituted shall be "next day delivered" to site
D. If spare parts are to be stored at VA Facility the Contractor shall provide lockable metal storage cabinets for their spare parts.
E. Cleaning and refinishing painting of the interior of cars and exterior surfaces of hoistway frames and doors are excluded from the requirements of this contract, however all other "in car items" e.g.: Hoist motor and generator brushes shall be checked for wear at least every two weeks. Accumulated carbon dust shall be removed from commutators, brush rigs and windings at the same time. buttons, ventilation fan(s), lighting and the like shall be included in the scope of work for this contract.
F. The contractor shall furnish all lubricants, cleaning supplies and tools necessary to perform the work described herein. All lubricants shall be recommended by the manufacturer of the equipment or an approved equal.
G. The Contractor shall NOT supply and replace fluorescent ballast or lamps for car lighting fixtures or floor covering on elevator platform.
H. Items not covered under this contract:
1. The cleaning, refinishing, repair or replacement of any component of the car enclosure
2. Hoist way enclosure
3. Gates
4. Cover plates
5. Main line power switches
6. Emergency power plant and associated contactors
7. Each unit cylinder
8. Buried piping and buried conduit
B.3.2 SERVICES TO BE PROVIDED
B.3.2.1 MAINTENANCE PROGRAM
A. Scheduled service shall include the following tasks listed in this section and shall be performed in accordance with the schedules listed in section B.3.3.
B. A record shall be maintained by the Contractor of non-emergency maintenance items in need of correction which comes to his attention, and he shall provide this list to the COR. The Contractor shall complete all repairs possible during the scheduled maintenance visits and coordinate with the COR to schedule the completion of all remaining repairs during regular business hours. Reports shall be submitted weekly.
B.3.2.2 SERVICES TO BE PROVIDED:
1. Cleaning, lubrication, examine and adjustments of the non-exclusive list of parts below shall be performed at a minimum as required by maintenance schedules found in section B.4.6 of this contract.
1. Motors
2. Generators
3. Controllers
4. Printed circuit boards
5. Timing devices
6. Relay panels
7. Selector
8. Leveling devices
9. Switches on car and in hoistway
10. Operating devices
11. Hoistway door and car door or gate operating device
12. Interlocks and contacts
13. Guide shoes
14. Guide grooves in hoistway and car door sills
15. Hangers for all doors and car doors or gates
16. Signal system
17. Car safety device
18. Governors
19. Tension frames and sheaves
20. Elevator pits
21. Clean all door opening and tracks for all elevators bi-weekly.
22. Test and repair phones and work with VA to resolve phone issues within the elevators and at emergency panels. (service and passenger side lobbies)
1. Hoist motor and generator brushes shall be checked for wear a minimum every two weeks. Accumulated carbon dust shall be removed from commutators, brush rigs and winding at the same time. Cleaning and refinishing painting of the interior of cars and exterior surfaces of hoistway frames and doors are excluded from the requirements of this contract, however all other "in car items" e.g.: push buttons, ventilation fan(s), lighting and the like shall be include in the scope of work for this contract.
1. The Contractor shall examine, adjust lubricate, clean, and when conditions warrant, repair or replace the following items listed below and related components at a minimum as required by maintenance schedules found in section of this contract. Replacement of hoisting, compensating, traction sheaves motor and governor cables shall be considered within the scope of this contract.
1. Entire machine, including housing, drive sheave, drive sheave shaft bearings, brake and brake assembly and component parts
1. Motors including auxiliary rotating systems, motor windings, rotating elements, couplings and bearings
1. All sheaves, beams, pulleys, sprockets, and other drive components
1. Controller: All components including all relays, contacts, solid state components, resistors, condensers, transformers, contacts, leads, mechanical or electrical timing devices, computer devices, circuit boards, integrated circuit board batteries, integrated circuit chips, and etc. Adjust and modify operations program after acceptance of proposed changes by the COR
1. Selector: All components including selector drive tape, wire or cable, hoistway vanes, magnets, indicators and all other mechanical and electrical drive components
1. Motor and motor generator worms, gear, thrust bearings, windings, circuits, commutators, coils, armatures, magnet frames, logic circuits, control fuses, annunciators, emergency lighting, brushes and brush holders
1. Hoistway door interlocks or locks and contacts, hoistway door hangers and tracks, bottom door guides, cams, rollers, and auxiliary door closing devices for power operated doors. Chains, tracks, cams, interlocks, sheaves for vertical bi-parting doors
1. Hoistway limit switches, slowdown switches, leveling switches and associated cams and vanes
1. Guide shoes including rollers or replaceable guides
1. Automatic power operated door operators, door protective devices, car hangers, tracks and car door contacts for both slide and vertical bi-parting doors
1. Traveling cables
1. Elevator control wiring systems in hoistway and machine room
1. Govemor including governor sheave and shaft assembly bearings, contact jaw and governor tension assemblies
1. Car and counterweight safety mechanism and load weighing equipment, shall be brushed clean at least every three months
1. Hoist cables, govemor cables, compensating cables, and compensating chains, including adjustment of tension on all hoist ropes
1. Buffers
1. Fixture contacts, push buttons, key switches, locks, lamps, and sockets of button stations (car and hall), hall lanterns, position indicators (car and hall), direction indicators, and voice synthesizers, phones and call boxes located in elevators and in lobbies (as applicable)
1. Power unit to include pump, motor, valves and all related parts and assemblies
1. Hydraulic system accessories to include exposed piping, fitting accessories between pumping unit and the jack, jack packing, hydraulic fluid, filters, filter accessories, and any heating or cooling elements installed by the OEM for controlling temperature
C. The Contractor shall, keep the guide rails free of rust where roller guides are used and properly lubricated when sliding guides are used, renew guide shoe rollers, gibs and guide as required to insure smooth and satisfactory operations.
D. The Contractor shall also examine, and make necessary adjustments or repairs to the following accessory equipment: hall lanterns, car and corridor position indicators, car stations, traffic director station, electric door operators, interlocks, door hangers, and safety edges, including relamping of signal equipment, and video display system components.
E. The Contractor shall be responsible for keeping the exterior of the elevator machinery, and any other parts of the equipment subject to rust, painted with heat resistant enamel, and presentable at all times. The motor windings shall be treated as needed, with proper insulating compound as recommended by the motor manufacturer.
F. The Contractor shall maintain all elevator equipment in hoistways, pits, machine rooms, and pits and assigned elevator Contractor workspace in a clean orderly condition, free of dirt, dust, and debris, pits and machine spaces shall be kept dry and clean. A complete cleaning of the entire installation including all machine room equipment, hoist way, equipment, machine room floors, hoist way, supporting structures, etc., shall be accomplished twice a year in October and March of the contract year for all necessary cleaning.
G. The Contractor shall not be responsible for upgrading equipment to meet changes in code requirements as directed by insurance companies, federal, state, municipal, or other governmental authorities.
H. The Contractor shall be responsible for notifying the COR, in writing, of the existence or development of any defects in, or repairs required to, the elevator equipment which he does not consider to be his responsibility under the terms of the contract.
I. The Contractor shall be responsible for giving immediate notice to the Contracting Officer's Representative (COR) or their designated representative of any condition which is discovered that may present a hazard to either the equipment or passengers.
J. All electrical wiring and conductors extending to elevators from circuit breakers and/or main line switches in machine rooms and from outlets in the hoist ways shall be repaired and/or replaced when required.
K. Elevators have auto dialer as the communication method. These auto dialers are to be tested monthly to ensure that they are in working order.
L. Items not covered under this contract:
1. The cleaning, refinishing, repair or replacement of any component of the car Enclosure
2. Hoist way enclosure
3. Gates
4. Cover plates
5. Main line power switches
6. Emergency power plant and associated contractors All parts shall be of the original manufacturers design and specification or equal
B.3.2.3 TESTING AND INSPECTIONS
A. Periodic safety tests and inspections of all elevators shall be performed by the Contractor as required by the latest approved edition of the ANSI/ASME Safety Codes for Elevators and Escalators, “Routine, Periodic and Acceptance Inspections and Tests". The Contractor shall provide elevator mechanic(s) and apprentice(s) who are familiar with the equipment to perform tests. The Contractor shall periodically examine and test all safety devices. Contractor personnel shall make formal safety tests and inspections as required and outlined in the ANSI Code twice a year, tests to be witnessed by an independent inspector - Qualified Elevator Inspector (QEI) (3rd party contractor provided by the VA) and VA representative. Upon award the vendor shall do an immediate site visit and establish maintenance scheduling, testing intervals, and equipment assessment to maintain testing intervals and equipment reliability. These tests shall be coordinated with the COR and not reduce the maintenance hours below those stipulated.
B. All passenger elevators shall be inspected weekly for proper operation, all service elevators shall be inspected weekly for proper operation. Inspections due to occur on legal holidays will be rescheduled for the following workday.
C. All Safety tests, full load, no load, rupture valve and any other required testing shall be performed by the Elevator Maintenance Contractor, including providing and utilizing required weights. The required elevator testing(s) with the federal elevator inspector shall be supported by one (1) dedicated elevator service technician by the Elevator Maintenance Contractor for the Medical Center, two (2) Elevator Maintenance Contractor technicians shall be required for full load testing. Elevator Inspection Contractor shall provide, upon completion of all testing and/or inspections, a verbal notice to the COR on the day of the inspection of all deficiencies and recommended actions before checking out for the day, with a final electronic report is to be sent to the COR within two weeks after the test. The final report will clearly indicate what was tested, all findings and corrective actions with a final disclosure of all elements tested and whether they passed or failed the test. Any failed inspection will be re-tested after deficiencies are corrected by Elevator Maintenance Contractor and written passing results noted on submitted follow up report as having passed the inspection to COR for review. Contractor shall provide two (2) certified mechanics, weights and any special equipment or provisions to complete all testing. Work shall be performed in accordance with the elevator inspector contractor’s schedule. The VAMC will provide notification no less than 2 weeks prior to the scheduled inspection.
D. Elevator Inspection Contractor shall provide, upon completion of all testing and/or inspections, a verbal notice to the COR on the day of the inspection of all deficiencies and recommended actions before checking out for the day, with a final written report sent to the COR within two weeks after the test. The final report will clearly indicate what was tested, all findings and corrective actions with final disclosure of all elements tested and whether they passed or failed the test.
E. Schedule of Tests for Elevators: To be verified as current by vendor at time of award following the ANSI/ASME Safety Codes for Elevators and Escalators and using reports provided by Syracuse VA Hospital and current elevator contractor. All 5-year full load testing on applicable elevator cars shall be done during calendar year 2021 within a two (2) month time frame, in order to bring all elevator 5 year testing concurrent and completed within the same calendar year
TYPE TEST CY20 CY21 CY22 CY23 CY24
ANNUAL X X X X X
5 YR X
B.3.2.4 EMERGENCY REPAIR SERVICE
A. The Contractor shall provide 24 hr. a day/ 7 days a week emergency repair services to the Syracuse VA Medical Center in the case of an emergency breakdown. The Contractor shall provide prompt emergency call back service at no extra charge to the Government. Upon arriving at the facility to perform services, the contractor shall report to the Contracting Officer's Representative, before and after performance of service, providing evidence of service performed. For emergency repairs, the contractor shall have personnel on site within two (2) hours of receiving the initial request. All travel, labor and parts associated with work performed during regular work hours shall be considered within the scope of this procurement. Only the COR and individuals identified by the COR shall be able to place emergency service calls at no additional expense to the government. If repairs require more than 4 hours of overtime to complete, the Contractor shall notify the COR or their onsite designated representative and a decision will be made by the COR or designee if the elevator can be taken out of service until normal business hours; and terminate the emergency service call.
Emergency call shall be defined as:
1. Any TWO passenger elevators in the same bank of elevators are out of service.
2. One Service elevator is out of service.
3. Or if passengers are trapped
B. The contract shall also include in its services provided to the Syracuse VA Medical Center the travel costs associated with twenty-five (25) emergency calls and up to 100 hours’ worth of overtime/weekend emergency service premiums per contract period at no additional cost to the VA. If and after the initial covered 100 hours of overtime/weekend calls are exhausted the Medical Center will only pay the premium portion of the overtime/weekend calls for any additional service after regular business hours.
C. The Contractor shall provide prompt emergency call back service at no extra charge to the Government. Response time/arrival time for Emergency call back service shall be within two (2) hours of telephone request from the Contracting Officer or his/her representative. Upon arriving at the facility to perform services, the contractor shall report to the Contracting Officer's Representative, before and after performance of service, providing evidence of service performed.
B.3.2.5 SCHEDULED DOWNTIME
A. Not more than one elevator per bank shall be put out of service at one time for regular maintenance, testing, lubrication, and servicing, The time of day that each elevator can be shut down for routine maintenance shall be scheduled with the COR to minimize the disruption caused by the elevators being out of service. Generally, all shutdowns will be accomplished during business hours, or otherwise determined by the COR. If for any reason an elevator should be out of service for more than the usual trouble shooting time of 30 to 60 minutes, the Contractor shall notify the COR when the elevator was taken out of service, the reason why and what time the elevator is expected to be put back in service for proper and safe operation. The following schedule will be considered maximum shutdown times allowed:
1. Major Repairs
a. Cables-hoist, governor, compensating and tail ropes. Completion within 4 calendar days after replacement cables are received
b. Brake coils and motor field coils - 7 calendar days
c. Rewind motor or MG set armature -14 calendar days
d. Turn down and undercut machine commutator 4 calendar days
e. Governor repairs -4 calendar days
f. Replace motor bearing- 5 calendar days
2. Minor Repairs: Completion within 1 calendar-day
a. Replace relay coils
b. Replace relays
c. Replace door interlocks
d. Replace door guides
e. Door operator repairs
f. Repair selector drive tape
g. Replace door operation motor
h. Replace selector drive motor
i. Replace brake linings
j. Replace valves (hydraulic elevator)
k. Replace pump unit (hydraulic elevator)
B. The Syracuse VAMC reserves the right to make inspections and tests as and when deemed advisable. If it is found that the elevators and associated equipment are deficient either electrically or mechanically, the Contractor will be notified of deficiencies in writing.
B.3.2.6 PERFORMANCE
A. The Contractor shall keep the elevator maintained to operate at the original contract speed, keeping the original performance measures, including acceleration and retardation times, average wailing time, door opening and closing times, accuracy of leveling and variance from rated speed under all load conditions and as designed and installed by the manufacturer. Any changes shall be discussed with the COR and approved before implementation. Each elevator must be operable and available for use 90% of the Medical Center’s normal work hours. Failure to meet this requirement for three consecutive months may be grounds for default action. Contractor shall keep a running total of hours out of service and provide it to the COR weekly. Scheduled maintenance time shall be excluded from normal work hours when calculating operational uptime.
A. All work will commence within twenty-four (24) hours after receipt of telephone, written or verbal notification from the Contracting Officer or his/her representative and will proceed progressively to accomplishment without undue delay. The Contractor is expected to spend a minimum of (53) hours per month on required maintenance.
B. The Syracuse VAMC reserves the right to make inspections and tests as and when deemed advisable. If it is found that the elevators and associated equipment are deficient either electrically or mechanically, the Contractor will be notified of deficiencies in writing.
B.3.2.6 EQUIPMENT, WIRING, AND CIRCUIT CHANGES
A. The Contractor shall not make any changes or alterations to the existing mechanical equipment, circuits, circuit wiring, programming, or sequencing, nor alter the original circuit or wiring design of the elevators unless changes are authorized in writing by the COR, as hereinafter provided. The Contractor shall submit any proposed changes to the COR, for approval. The submission shall be complete, neatly prepared, drawings, and wiring diagrams as well as a complete description of the proposed changes. Prior to submitting the proposed change to the facility, the Contractor shall at his own cost and expense have obtained comments from the original equipment manufacturer concerning the overall effect of such changes on the system. If changes are made, Contractor shall provide as-built drawings of modifications.
B.3.2.7 RECORDS
A. The Contractor shall maintain a complete, orderly and chronological file, including drawings, complete parts lists and copies of all reports as required by these specifications. A record of all call backs and repairs shall be kept by the Contractor indicating any difficulty experienced and the corrective measures taken to eliminate these difficulties. The file shall be available for inspection upon request and a copy of this complete file shall be furnished to the VA facility during the last month of each contract period. This monthly report shall indicate the elevator number, date work was performed, type of work (emergency replacement or repair), brief description of the work performed, man-hours expended, and materials used.
B. The contractor will provide written reports to the VA weekly of the work accomplished and document all preventative maintenance and other maintenance preformed. The contractor shall provide all Joint Commission documentation monthly to the VA.
C. The Contractor shall provide and keep current suitable check charts for each elevator. One shall be kept in the appropriate machine room of the building in which the elevator is located; a copy shall be turned over to the COR. Upon completion of maintenance, the contract shall properly initial the chart to indicate the work has been completed. In addition to the check charts in each machine room the Contractor shall maintain, on the premises a log of arrival and departure times of all Contractor employees. The log shall contain columnar line entries for date, employee position classification, employee name, time of arrival, time of departure, hours worked, and type and extent of work performed on each unit. The log shall be kept in the VA, Engineering Service and shall be completed when the Contractor's employee checks in and out for each service visit.
D. Drawings and wiring diagrams which are furnished by the VA to facilitate the Contractor's work shall be maintained and revised by him periodically as changes occur. At the expiration of the contract, the Contractor shall turn over to the VA three (3) copies of the drawings and wiring diagrams, completely revised to date, covering each elevator. Those drawings and wiring diagrams shall faithfully represent the "as modified" condition existing at the expiration date.
E. Any and all drawings and wiring diagrams furnished the Contractor by the VA or drawings and wiring diagrams prepared by the Contractor for work under the contract shall be considered the property of the VA and shall be accessible to the COR and VA personnel identified by the COR at all times, and be turned over to him upon demand and upon termination of this contract.
F. A record of all call backs and repairs shall be kept by the Contractor indicating any difficulty experienced and the corrective measures taken to eliminate these difficulties. The file shall be available for inspection upon request and a copy of this complete file will be furnished to the VA Medical Center during the last month of the contract period.
G. The Contractor shall complete any/all forms required by the latest ANSI/ASME with respect to tests/inspections. The contractor will support required testing of elevators by 3rd party inspectors, operating and assisting with the test/inspections. All deficiencies will be address by the contractor that were identified by the 3rd party inspector.
H. A written report on the condition of all hoisting, compensating and governor cables shall be submitted to the COR each May and November during the life of this contract.
I. A record shall be maintained by the Contractor of non-emergency maintenance items in need of correction which comes to his attention, and he shall provide this list to the COR. The Contractor shall complete all repairs possible during the scheduled maintenance visits and coordinate with the COR to schedule the completion of all remaining repairs during regular business hours. Reports shall be submitted weekly.
B.3.2.8 IDENTIFICATION, PARKING, SMOKING AND VAMC REGULATIONS
A. Contractor employees shall always wear visible identification while on the premises of the VAMC. It is the responsibility of the vendor to park in the appropriate designated parking areas. Information on parking is available from the VA Police Section. The VAMC will not invalidate or make reimbursement of parking violations of the vendor under any conditions. Smoking and Vaping is prohibited inside any buildings at the VAMC. Possession of weapons is prohibited. Enclosed containers, including tool kits, shall be subject to search. Violations of VA regulations may result in citation answerable in the United States (Federal) District Court, not a local district, state, or municipal court.
B. Contractor shall report to Police office and have a designated person (to be determined after award and conveyed in the COR designation letter) contacted when contractor personnel are in the Medical Center or premises for routine maintenance or emergency service. Not following this procedure can be grounds for default.
C. All equipment shall be catalogued by the contractor with the dates and types of service rendered shall be noted thereon. A legible, written report of each inspection/service shall be furnished to the COR (Contracting Officer's Representative). Each report shall advice of any repairs or repair parts (including adequate description and part number) not required to be furnished under the contract that are necessary to maintain the equipment in perfect operating condition. An explanation of special codes and abbreviations used on the furnished report shall be submitted to the COR.
B.3.2.9 SAFETY REQUIREMENTS
A. In the performance of this contract, the Contractor shall take such safety precautions as the Contracting Officer or his/her designee may determine to be reasonably necessary to protect the lives and health of occupants of the building. The Contracting Officer or his/her designee will notify the contractor of any noncompliance with the foregoing provisions and the action to be taken. The Contractor shall, after receipt of such notice, immediately correct the conditions to which attention has been directed. Such notice, when served on the Contractor or his/her representative at the site of the work, shall be deemed sufficient for the purpose aforesaid. If the Contractor fails or refuses to comply promptly, the Contracting Officer may issue an order stopping all and any part of the work and hold the Contractor in default.
B.3.3 SCHEDULE
ITEMS OF PREVENTIVE MAINTENANCE WORK
B. The preventive maintenance specified herein is considered the minimum for all equipment. If specific equipment covered by this contract requires additional preventive maintenance for safe reliable operation as specified by the manufacturer, the Contractor shall perform the required additional preventive maintenance without added cost to the VA.
1. WEEKLY:
a. Perform general inspection of machinery, sheaves, worm, and gear motor, brake, selector or floor controllers (when used). Lubricate as required.
b. Empty oil pans, discard oil, in an approved manner, check reservoir oil level.
c. Observe brake operation and adjust or repair if required.
d. Inspect and lubricate machinery, contacts, linkage, and gearing, if required.
e. Clean and inspect brushes and commutator, perform needed repairs.
f. Clean and inspect controllers, selectors, relays, connectors, contacts, etc.
g. Ride Car and observe operation of doors, leveling, reopening devices, push buttons, lights, etc.
h. If rails are lubricated, check condition and lubricate. Service lubricators.
i. Replace all burned out lamps in elevator car, machine room, pit, hall lanterns, etc.
j. Clean trash from pit and empty drip pans.
k. Check governor and tape tension sheave lubrication.
l. Bi-weekly clean all door tracks on all elevators.
m. Burned out lamps in hall lanterns, push buttons, car and corridor position indicators, director stations, "This Car Up" signs and other signal fixtures shall be supplied and installed by the Contractor. Burned out lamps in elevator cars, machine rooms and pits shall be supplied by VA and installed by the Contractor.
2. BIWEEKLY:
a. Hoist motor and generator brushes shall be checked for wear at least every two weeks.
b. Accumulated carbon dust shall be removed from commutators, brush rigs and
c. windings at the same time.
3. MONTHLY:
a. Observe operations of elevator throughout its full range and at all floors it serves to test controls, safety devices, leveling, re-leveling, and other devices.
b. Check door operation, clean, lubricate and adjust brakes, check linkages~ gears, wiring motors, check keys, set screws, contacts, chains, cams, and door closer.
c. Check selector. Clean, adjust and lubricate brushes, dashpots, traveling cables, chain, pawl magnets, wiring, contacts, relays, tape drive and broken tape switch.
d. Check car. Clean, adjust, and lubricate car door and gate tracks, pivots, hangers, car grill, side and top exits.
e. Inspect interior of cab. Test telephone or intercommunication system, normal and emergency lights, fan, emergency call system or alarm, car station. Make needed repairs.
f. Visually inspect controller, contacts, and relays. Check adjustment and replace contacts as required.
g. Observe operation of signal and dispatching system. Inspect compensating hitches, buffers, rope clamps slack cable switch, couplings, keyways, and pulleys. Check load weighing device and dispatching time settings. Clean, adjust, and lubricate as necessary.
h. Check oil level in car and counterweight oil buffers and add oil as required.
i. Check brushes and commutators. Inspect commutator to provide proper commutation. Inspect brushes for tension seating and wear, replace or adjust as required.
j. Check and adjust:
i. Car ventilation system.
ii. Car position indicators.
iii. Director Stations.
iv. Hall and car call buttons.
v. Hall lanterns.
This car up signs.
4. QUARTERLY:
a. Check leveling operation. Clean and adjust leveling switches, hoistway vanes, magnets, and inductors. Repair and/or adjust for proper leveling.
b. Check hoistway doors. Clean, lubricate, and adjust tracks, hangers, and up thrust eccentrics, linkage guides, and interlocks.
c. Clean, adjust, and lubricate car door or gate tracks pivots, and hangers.
d. On hoistway doors, clean lubricate, and adjust tracks, hangers, and eccentrics, linkage guides, and interlocks.
e. Inspect all fastenings and ropes for wear and lubrication. Clean both governor, hoist ropes, and lubricate hoist ropes if needed. Inspect all rope hitches and shackles and equalize rope tension.
f. In the car, test alarm bell system. Clean light fixtures. Inspect, clean, and adjust retiring CA device, chain dashpots, commutators, brushes, cam pivots, and fastenings. Test emergency switch (ground case if necessary). Inspect safety parts, pivots, set screws, switches, etc. Check adjustment of car and counterweight guides, shoe or roller guides, lubricate, and adjust, if necessary.
g. In the pit, lubricate compensating sheave and inspect hitches. Inspect governor and tape tension sheaves fastenings. Empty and clean oil drip pans.
h. Clean all parts of safeties and lubricate moving parts to assure their proper operation. Check and adjust clearance between safety jaws and guide rails. Visually inspect all safety parts.
i. Clean and examine governor rope, replacing if needed. (Do not lubricate governor rope).
5. SEMI-ANNUAL:
a. Check controllers. Clean with blower, check alignment of switches, relays, timers, contacts, hang pins, etc. adjust and lubricate. Check all resistance tubes and grids. Check oil in overload relays settings and operation of overloads. Clean and inspect fuses, holders, and all Controller connections.
b. In hoistway examine guide rails, cams, and fastenings. Inspect and test limit and terminal switches. Check and adjust car shoes, guides or roller guides. Adjust or replace as required.
c. Clean all overhead cams sheaves, sills, bottom of plat form, car tops counterweights and hoistway walls.
d. Inspect sheaves to ensure they are tight on shafts. Sound spokes and rim with hammer.
e. Examine all hoist ropes for wear, lubrication, length and tension.
f. Replace, lubricate and adjust as required to meet code requirements.
g. On tape drives, check hitches and broken tape switch.
h. Lubricate moving parts of vertical rising or collapsible car gates. Check pivot points sheaves, guides, and track for wear.
i. Lubricate guide shoe stems.
j. Check governor and tape tension sheave fastenings.
k. For bi-parting doors, clean chains, tracks and sheaves, lubricate as required. Check door contacts.
l. Check fastenings and operation of door checks, interlocks, clean, and lubricate pivot points as required.
6. ANNUAL
a. Thoroughly clean car and counterweight guide rails using a nonflammable or high flash point solvent to remove lint dust and excess lubricant. Remove, clean, and lubricate brake cores on brakes, clean linings, if necessary, and inspect for wear and adjust.
b. Inspect motor-generator and hoist motor armatures and rotor clearances. Check motor and MG set connection and lubricate in accordance with manufacturer's instructions.
c. Oil, drain, flush and refill oil reservoirs of each hoisting motor and motor generator.
d. Check and reset, if necessary, all brushes for neutral settings, proper quartering and spacing on commutations.
e. Group supervisory control systems where installed shall be check out.
The system's dispatching, scheduling, and emergency service features shall be tested and adjusted in accordance with manufacturer's literature. The Contractor shall prove to the satisfaction of the COR that the system functions properly. All work shall be performed during other than normal working hours with no inconvenience to building occupants. A full report covering adjustment time intervals, dispatch times on various programs, door standing time and door opening and closing speeds shall be furnished to the Manager, Engineering Service.
ANY WORK NOT COVERED BY THIS CONTRACT MUST BE AUTHORIZED IN ADVANCE BY A CONTRACTING OFFICER AND MUST HAVE A SEPARATE PURCHASE ORDER ISSUED PRIOR TO ACCOMPLISHMENT OF WORK.