P09 04 of 13 Sealed Bid Dwgs 07092020 - 14 pages.pdf
PDF 15 MB Posted
- Attached to
- Expand and Upgrade Building 42 for Laboratory
- Solicitation number
- 36C25520R0073-0002
About this file
This is an amendment to a solicitation issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15 for the Expand and Upgrade Building 42 for Laboratory project.
The amendment provides revised structural drawings and details for the project, including notes and abbreviations, schedules, slab on grade details and legends, typical sections and details, framing elevations, model views, and special inspections. The drawings cover foundations, concrete work, masonry, structural steel, cold formed steel framing, and other structural scope. Relevant details include foundation plans, sections, connection details, and framing plans.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESIGN TABLE
Model Building Code: 2015 International Building Code Model Code Standard: ASCE 7-10 Steel Standard: AISC 360-10 Steel Seismic Standard: AISC 341-10 Concrete Standard: ACI 318-14 Masonry Standard: ACI 530-13 Wood Standard: AITC/APA/NDS Current Ed.
Dept of VA Standard: Structural Design Manual For Hospital Projects, 2014
Seismic Design Requirements, 2016 Risk Category: III Substantial Risk Exposure Category: C
ROOF DESIGN LOADS Dead Live Snow Main 20.0 psf 25.0 psf Unreducible 17.0 psf
FLOOR DESIGN LOADS Dead Live Partition Lab and Future Floor 75.0 psf 100.0 psf Reducible 0.0 psf Mechanical Floor 75.0 psf 100.0 psf Unreducible 0.0 psf
SOILS Spread Wall Allowable Bearing Pressure, qa: 2800 psf 2800 psf Soil Density, γt: 125 pcf Soils Report: Holcomb Foundation Engineering #H-17022 Dated: 2/13/2017
SLAB ON GRADE
Compacted Fill Thickness: 4 in Compaction Specification: 95% Modified Proctor D-1557
LATERAL EARTH PRESSURES
Active: 40 psf At-Rest: 65 psf Passive: 350 psf
SNOW DESIGN CRITERIA
Ground Snow Load, Pg: 15 psf Flat Roof Snow Load, Pf: 17 psf Importance Factor, Is: 1.1 Exposure Factor, Ce: 1.0 Partially Thermal Factor, Ct: 1.0 Heated Warm Slope Factor, Cs: 1.0 Drift Surchage Load, Pd: 48 psf Width of Snow Drifts, w: 12'-3"
WIND DESIGN CRITERIA
Ultimate Wind Speed, Vult: 120 mph Design Wind Speed, VASD: 94 mph Enclosure Class: Enclosed Internal Pressure Coefficient, GCpi: 0.18
SEISMIC DESIGN CRITERIA
Importance Factor, Ie: 1.25 Mapped Spectral Response, SS: 0.902 Mapped Spectral Response, S1: 0.308 Site Class: C Design Spectral Response, SDS: 0.625 Design Spectral Response, SD1: 0.306 Seismic Design Category, SDC: D Overstrength Factor, Ω: 2 Seismic Response Coefficient, CS: 0.104 Response Modification Coeff., R: 6 Unfactored Design Base Shear, V: 10.4% W Analysis Procedure: ELFA Basic Seismic-Force-Resisting System: B. Building Frame Systems
2. Steel special concentrically braced frames G8. Reactions and forces indicated are unfactored, Allowable Strength Design (ASD) loads.
G9. If Drawings and specifications are in conflict, the most stringent restrictions and requirements shall govern. Contractor shall bring all discrepancies to the attention of the engineer immediately.
G10. Verify all existing conditions prior to any construction or fabrication. If different than shown, notify engineer/architect immediately for modification of drawings.
G11. All contractors are required to coordinate their work with all disciplines to avoid conflicts. The architectural, mechanical, electrical and plumbing aspects are not in the scope of these drawings. Therefore, all required materials and work may not be indicated. It is the contractor's responsibility to coordinate these drawings with all other construction documents. Refer to architectural drawings for all dimensions not shown on these drawings. Locations, sizes and numbers of all openings may not be completely indicated in the structural drawings. The respective contractor shall verify their work with all other disciplines.
G12. The contract documents represent the structure only. They do not indicate the method of construction. The contractor shall provide all measures necessary to protect the structure during construction. Such measures shall include, but not limited to, bracing, shoring, underpinning, etc. the Engineer of Record is not responsible for the contractor's means, methods, techniques, sequences or safety procedures during construction.
G13. Notes and details shall take precedence over general structural notes. Where no details or sections are shown, construction shall conform to similar work on the project. Typical sections and details may not be cut on the plans, but apply unless noted otherwise.
G14. Provisions for future expansion:
Vertical: 1-story future roof above current roof framing Horizontal: None
GENERAL NOTES
ES1. The actual existing structure configuration, member sizes, etc. has not been field verified.
ES2. All existing structure indicated is for reference only.
ES3. Field verify existing structure. If existing structure varies from configuration, sizes, etc. from drawings, notify engineer of record immediately.
ES4. Existing structural information has been obtained from drawings prepared by FGM, Inc., dated 09/15/1995.
010002 EXISTING STRUCTURE NOTES
SSE1. A Specialty Structural Engineer (SSE), registered in the state of the project, shall be responsible for the structural design of the following products and systems complying with specific performance and design criteria indicated.
1. Steel Joists, joist girders, bridging and accessories.
2. Structural Steel Connections, except as shown on drawings.
AISC Option 2 (Detailer): Simple shear connections.
AISC Option 3 (SSE): All other connections not shown.
3. Cold-Formed Steel CFS exterior and interior wall studs, CFS floor joists and accessories.
4. Stairs, railings, and ladders.
5. Seismic restraint for non-structural components.
014000 DELEGATED DESIGN
SF1. Soil to be stripped, compacted and tested in accordance with the recommendations of the soils engineer and project specifications.
SF2. Footings shall be placed on firm, undisturbed soil or on engineered fill. Engineered Fill: Naturally or artificially graded mixture of natural or crushed gravel, crushed stone, and natural or crushed sand; ASTM D 2940; with at least 90 percent passing a 1-1/2-inch sieve and not more than 12 percent passing a No. 200 sieve.
SF3. Slabs shall be placed on compacted, free-draining, frost-free drainage course. Drainage Course: Narrowly graded mixture of washed crushed stone, or crushed or uncrushed gravel; ASTM D 448; coarse-aggregate grading Size 57; with 100 percent passing a 1-1/2-inch sieve and 0 to 5 percent passing a No. 8 sieve. All fill shall be compacted to a minimum dry density of 95% of the modified Proctor maximum dry density (ASTM- D1557), placed in 6" to 8" lifts. Pea gravel may not be used as fill. Utility trenches and excavations under the foundations or slabs shall meet the same requirements. See soils investigation report for further recommendations.
SF4. Undercutting of the soil for foundation and/or slab placement may be required. These drawings do not indicate the entire scope of undercutting, fill or bad soil removal that may be required to attain the design soil bearing pressures. It is the responsibility of the contractor to obtain a soils investigation report, before bidding, to assess the extent of excavation and compaction that may be required to meet the design criteria. The contractor shall retain the services of a soils engineer to monitor all backfilling operations and to inspect footing bearing material. A report certified by the soils engineer shall be furnished to the architect/engineer verifying that all foundations were placed on a material capable of sustaining the design bearing pressures.
SF5. If dewatering is required, sumps shall not be placed within the foundation excavation.
SF6. Maintain a maximum slope between adjacent footing bearing elevations of 2 horizontal to 1 vertical. Maintain a
2 horizontal to 1 vertical slope next to existing foundations to avoid undermining foundations.
SF7. No horizontal joints are permitted in any foundation. Vertical joints are permitted only in wall footings.
SF8. Shallow foundations may be earth-formed where the excavation permits. If earth-forming is used, add 2" to the width and length of all foundations.
SF9. The bottom of all foundations shall be a minimum of local frost depth below final grade.
020000 SHALLOW FOUNDATION AND SLAB ON GRADE NOTES
RC1. All concrete shall have the following 28 day compressive strengths:
STRENGTH LOCATION
3000 psi-0% AE All foundations and footings 4000 psi-6% AE Exterior slabs, piers, walls, columns, grade beams and concrete exposed to freezing 4000 psi-0% AE Interior slabs, fill for metal deck and all other interior concrete
RC2. All reinforcing shall conform to the following concrete cover:
COVER LOCATION
3" Foundations & Footings: All surfaces; Exterior Slabs: Bottom; Grade Beams & Trench
Footings: All surfaces; All concrete cast against soil 2" Exterior Walls, All Piers & All Pilasters: All surfaces; Exterior Slabs: Top; All exterior concrete 1 1/2" Interior beams, columns & walls: All surfaces; All concrete not exposed to weather or in contact with ground 3/4" Interior slabs & Walls
RC3. Welded Wire Fabric (WWF) for slabs and fill for metal deck shall be placed in the upper-third of the slab or fill. See details.
RC4. All reinforcing steel shall be detailed, supplied and placed in accordance with ACI 315, ACI 318 and CRSI MSP-1.
RC5. All reinforcing steel shall be shop fabricated and, where applicable, shall be wired together and conform to ASTM
A-615, Grade 60.
RC6. Chamfer edges of exposed concrete 3/4", unless noted otherwise.
RC7. Contractor shall make four, 6"x12" test cylinders for each 50 cubic yards of concrete poured for each days operation. Break 1 at 7 days, 2 at 28 days and retain spare.
RC8. All welded wire fabric shall conform to ASTM A185, Fy(min) of 65 ksi. All welded wire fabric laps shall be 8".
RC9. All finished concrete, concrete formwork and falsework shall be in accordance with ACI 301. Contractor is solely responsible for the design and construction of all formwork, falsework and shoring.
RC10. Provide sleeves for all openings in grade beams or walls to totally separate pipe from concrete.
RC11. Foundations may be earth-formed where the excavation permits. If earth-forming is used, add 2" to the width, length & thickness of all foundations.
RC12. Plastic Vapor Retarder: ASTM E 1745, Class A, not less than 10 mils (0.25 mm) thick, see specifications. Include manufacturer's recommended adhesive or pressure-sensitive joint tape.
RC13. Fiber Reinforcement, if indicated on drawings, shall be 100% virgin polypropylene in collated, fibrillated form, complying with ASTM C 1116, minimum length of 3/4". Minimum dosage = 1.5 pounds per cubic yard.
RC14. Adhesive Anchors and Adhesives Used for Reinforcing Anchorage:
1. The adhesive anchor system used for post-installed anchorage to concrete shall conform to the requirements of the most recently published ACI 355.4.
2. Adhesive anchors indicated are the Basis-of-Design. Approved equal meeting ACI 355.4 is permitted.
3. Bulk-mixed adhesives are not permitted.
4. Anchors shall be supplied as an entire system with manufacturer's recommendations adhered to.
5. Adhesive anchors shall be installed by qualified personnel trained to install adhesive anchors.
6. Installation of adhesive anchors horizontally or upwardly inclined shall be performed by personnel certified by the ACI/CRSI Adhesive Anchor Installer Certification program.
7. Adhesive anchors installed in horizontal or upwardly inclined orientations shall be continuously inspected during installation by an inspector specially approved for that purpose.
RC15. Bonding agent for bonding fresh concrete to hardened concrete: ASTM C 1059/C 1059M, Type II, nonredispersible, acrylic emulsion or styrene butadiene.
033000 CAST IN PLACE CONCRETE NOTES (Foundations, Slabs, & Walls)
M1. Minimum 28 day compressive strength of concrete masonry units shall be 2800 p.s.i. based on net area of the unit. Specified design compressive strength of masonry shall be f'm = 2000 p.s.i. All units for exterior walls, load-bearing walls and shear walls shall be normal weight block.
M2. All mortar shall be Type S. No admixtures may used unless approved by architect/engineer. Mortar shall not be used for grouting cores or filling bond beams.
M3. All block shall be laid in a running bond pattern.
M4. Course grout shall be used were grouting is required. Slump shall be 8" +/- 1". Minimum grout compressive strength shall be 3000 p.s.i.
M5. All reinforcing shall be ASTM A615 Grade 60 (Fy=60 ksi). Lap all reinforcing a minimum of 48 bar diameters.
M6. Center vertical reinforcing in block cores, unless noted otherwise.
M7. See architectural and specifications for all control joint locations. Reinforcing in bond beams shall be discontinuous at control joints.
M8. Provide ladder type horizontal joint reinforcement at 16" o.c. Side rods and cross rods shall be #9 wire, galvanized, see specifications. Cut joint reinforcement at control joints.
M9. Provide "L" bars at all bond beam corners as required.
M10. Fill cores of block solid with grout two full courses below the bearing of all beams or lintels supported on masonry.
M11. All attachments to block shall be made with Hilti HLC 1/2" diameter x 3" sleeve anchors, unless noted otherwise. Anchors shall be installed per manufacturer's recommendations.
M12. See typical schedules for masonry and steel lintels not indicated on plans.
M13. All masonry units below grade to be grouted solid.
M14. Provide ties to all structural steel.
M15. All interior, non-load bearing masonry walls over 12'-0" high, shall be supported on thickened slab as per typical detail. Wall vertical reinforcing shall be #5 @ 48" OC full height. Unless noted otherwise.
M16. All cores with reinforcing steel shall be grouted solid, full height of wall.
042000 MASONRY AND REINFORCED MASONRY NOTES
SS1. All structural steel shall conform to the following:
W Shapes ASTM A992, Grade 50.
Angles, Channels, Plates, Bars ASTM A36 (Fy=36 ksi) HSS Tubes ASTM A500, Grade B (Fy=46 ksi) HSS Pipes ASTM A500, Grade B (Fy=42 ksi) Anchor Rods ASTM F1554, Grade 36
SS2. All steel shall be detailed, fabricated and erected in accordance with:
AISC 360 "Specification for Structural Steel Buildings", Allowable Strength Design (ASD) AISC 303 "Code of Standard Practice"
SS3. If beam reaction is not indicated, design connection for minimum 15 k reaction.
SS4 All bolted connections shall be made with 3/4" diameter, A325 bolts with nuts and washers, unless otherwise noted.
All connections shall be shear bearing connections tightened to snug-tight condition, unless otherwise noted.
SS5. All shop and field welds shall be made using E70 electrodes or equivalent.
SS6. All headed concrete anchors shall be ASTM A108 (Fy=50 ksi), 3/4" diameter x 4" after welding, unless noted otherwise.
SS7. Steel fabricator shall obtain the size and location of all openings for grilles, louvers, etc. before proceeding with the fabrication and erection of any required frames.
SS8. Provide Heckman #129 and #130 channel slot and channel slot anchors at all columns that abut masonry walls, unless noted.
SS9. Provide temporary bracing of the structure until all permanent lateral support is in place.
SS10. Structure Stability: The entire roof and/or floor decking materials must be fully erected and connected to the supporting steel before temporary, erection bracing is removed.
SS11. RD = Roof Drain location. Provide steel frame for drains. See other drawings for actual drain type, number, size, etc. Coordinate with drain contractor.
051200 STRUCTURAL STEEL NOTES
Abbreviations EBF Eccentrically Braced Frame OCBF Ordinary Concentrically Braced Frame SCBF Special Concentrically Braced Frame IMF Intermediate Moment Frame OMF Ordinary Moment Frame SMF Special Moment Frame CVN Charpy V-Notch SLRS Seismic Load Resisting System WPS Welding Procedure Specification
SSC1. All design and detailing based on AISC 341-10, Seismic Provisions for Structural Steel Buildings - Allowable Strength Design (ASD), and shall comply with all requirements therein.
SSC2. If used, all IMF and SMF connections based on AISC 358-05, Prequalified Connections for Special and Intermediate Steel Moment Frames for Seismic Applications, and shall comply with all requirements therein.
SSC3. In addition to the material specifications listed, SLRS members with flanges 1 ½” thick and greater shall meet Charpy V-Notch toughness requirements per AISC.
SSC4. Portions of the SLRS members and connections are designated as PROTECTED ZONES. Within the PROTECTED ZONE, discontinuities created by fabrication and/or erection, such as tack welds, erection aids, air-arc gouging and thermal cutting shall be repaired as required by the Engineer of Record.
SSC5. PROTECED ZONE locations: connections of brace to beams/columns, the center one quarter of the brace length and 8" of the brace from each connection.
SSC6. Demand critical welds are groove welds at column splices, welds at column-to-baseplate connections, and welds at beam-to-column connections conforming to AISC 341-10 Section F2.6b.
051201 SEISMIC STRUCTURAL STEEL NOTES
SJ1. Provide all joists, bridging and accessories for the complete erection of joists in accordance with the current Steel Joist Institute "STANDARD SPECIFICATIONS AND LOAD TABLES FOR OPEN WEB STEEL JOISTS AND JOIST GIRDERS" and Underwriters Laboratories "STANDARD, FIRE TESTS OF BUILDING
CONSTRUCTION AND MATERIALS".
SJ2. Bridging shall be completely erected and joists aligned before any construction loads are placed on joists.
SJ3. Do not weld bottom chord of joists to columns unless noted on drawings.
SJ4. Install erection bolts at all joist girder to column and joist to column connections.
SJ5. Where ballasted roofing is not shown on architectural drawings, provide uplift bridging at all joists as per
"STANDARD SPECIFICATIONS AND LOAD TABLES FOR OPEN WEB STEEL JOISTS AND JOIST
GIRDERS" for a net uplift load of 12 psf, unless noted or shown otherwise.
052100 STEEL JOIST NOTES
MD1. All metal deck material, fabrication and installation shall conform to Steel Deck Institute "SDI SPECIFICATIONS AND COMMENTARY" and "CODE OF RECOMMENDED STANDARD PRACTICE", Current edition, unless noted.
MD2. FASTENING DECK
1. Roof deck shall be welded using 5/8" diameter puddle welds, 36/5 pattern with (2) #10 TEK sidelap fasteners unless otherwise shown in typical detail or indicated on drawings.
2. Floor deck shall be welded using 3/4" diameter puddle welds, 36/4 pattern with (2) welded sidelaps unless shown in typical detail or indicated on drawings
MD3. Provide TS 2 1/2x 2 1/2x 1/8 deck support, field welded to joist or beam at all deck span changes.
MD4. Provide L3x3x1/4 deck support at all columns where required, unless noted.
MD5. Provide 20 gauge cover plate at all roof deck span changes.
MD6. Provide L3x3x1/4 at all unsupported edges of deck and around roof perimeter, unless otherwise noted.
MD7. All deck shall be provided in a minimum of 3-span lengths where possible.
053100 STEEL DECK NOTES
SF1. Delegated Design: All cold formed steel framing shall be by Specialty Structural Engineer (SSE), registered in the state of the project. The SSE shall be responsible for the structural design of all cold-formed-steel design, products and systems complying with specific performance and design criteria indicated
SF2. All design and construction of cold formed steel shall comply with the contract documents, referenced codes, standards, notes, layouts and the following American Iron and Steel Institute (AISI) documents, including all AISI referenced documents therein:
S100-2007 Specification S200-2007 General Provisions S201-2007 Product Data S210-2007 Floor & Roof Systems S211-2007 Wall Stud Design S213-2007 Lateral Design with Supplement No. 1 S212-2007 Header Design S214-2007 Truss Design
SF3. Unless noted otherwise, provide the following minimum member sizes, unless larger size or lesser spacing is required:
TYPE SIZE
Exterior Wall Studs 600 S 162-54 Interior Load-Bearing Studs 600 S 162-54
SF4. All members and systems shall conform to the following maximum movements:
TYPE LIVE INDEX MAXIMUM
Exterior Wall Studs L/600 1/2" Interior Wall Studs L/240 1/2" Exterior cantilevered parapets L/300 1/2" Floor trusses and joists L/480 1" Roof trusses and joists L/360 1 1/2"
SF5. The most stringent requirements shall govern in conflicts between specified codes and standards.
SF6. All products shall have four-part identification code which identifies size, style and material thickness of each member.
SF7. All materials shall conform with ASTM A1003, structural grade 33 or structural grade 50.
SF8. Corrosion protection for all materials shall comply with ASTM A653. Minimum, hot-dipped galvanized coating weight for exterior walls and all roof materials shall be G90. All other materials shall be G60.
SF9. Provide factory punchouts in all wall studs where required.
SF10. Provide standard color coding for all products.
SF11. Provide 1/2" ASTM F1554, Grade 36 hooked anchor bolts at all steel tracks, u.n.o. Anchor bolt spacing = 48" OC, u.n.o. Provide anchor bolt at 8" from the ends of all walls, u.n.o.
SF12. For all non-load bearing studs, provide deflection clips isolating the stud from the primary structure.
SF13. All track butt joints shall be anchored to a common structural element.
SF14. Horizontal bracing of wall studs shall be provided at 6 feet on center maximum.
SF15. Place joists and trusses directly over wall studs.
SF16. Fastening of elements shall be self-drilling screws or welding of sufficient size to transfer required loads. All welding of galvanized steel shall be touched up with zinc-rich paint.
Minimum thickness of material for welding is 54 mil.
SF17. All screws shall be non-corrosive, No. 12-14 or larger.
SF18. See architectural drawings for all non-structural stud requirements.
SF19. All floor and roof trusses shall have a minimum flange width of 1 5/8".
SF20. Floor and roof truss bottom chords shall be designed for 10 psf dead load, not in addition to design loading.
SF19. Lateral Force Resisting System (LFRS) shall comply with forces indicated.
Shearwalls shall be Type II, steel sheet. Coordinate shearwalls with holdowns and ties shown.
SF20. Provide 1" gap for deflection track for live load deflections.
054000 COLD FORMED STEEL FRAMING NOTES (Delegated Design)
G1. All shoring shall be in place before demolition begins.
G2. It is the Contractor's responsibility to select the appropriate shoring system for the loads and work indicated.
G3. Reactions and forces indicated for shoring are actual, working loads.
G4. If Drawings and specifications are in conflict, the most stringent restrictions and requirements shall govern.
Contractor shall bring all discrepancies to the attention of the engineer immediately.
G5. Verify all existing conditions prior to any demolition, construction or fabrication. If different than shown, notify engineer/architect immediately for modification of drawings.
G6. All contractors are required to coordinate their work with all disciplines to avoid conflicts. The architectural, mechanical, electrical and plumbing aspects are not in the scope of these drawings. Therefore, all required materials and work may not be indicated. It is the contractor's responsibility to coordinate these drawings with all other construction documents. Refer to architectural drawings for all dimensions not shown on these drawings.
Locations, sizes and numbers of all openings may not be completely indicated in the structural drawings, the respective contractor shall verify their work with all other disciplines.
G7. The contract documents represent the structure only. They do not indicate the method of demolition, shoring or construction. The contractor shall provide all measures necessary to protect the structure during demolition and construction. The Engineer of Record is not responsible for the contractor's means, methods, techniques, sequences or safety procedures during construction.
017900 DEMOLITION NOTES
C. RODNEY
McCOMAS 081-005275
CARMEL
L
IC
E
NS
ED
ST
RUCTURAL
ENG
IN
E E R
Expires 11-30-20
STATE OF I LL
IN
O
ISINDIANA
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel
Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel
Fax
317.464.9090 317.464.9393
Office of Facilities
Management McComas/O'Donnell & Naccarato 1717 E 116th Street Carmel, IN 46032
Structural
Asaturian Eaton & Assoc.
1440 Old West Main Carbondale, IL 62901
Tel Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel Fax
618.529.5262 618.457.8991
Geotechnical
Tel Fax
317.580.0402 317.582.0766
5/22/2020 4:05:12 PM
STRUCTURAL NOTES AND
ABBREVIATIONS
Expand & Upgrade Building 42 Laboratory
S401
17057 MEI
Marion, IL
11-08-2019
Bid Documents
TMM SDS of ###
O/O OUT TO OUT
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OH OVER HEAD
OPNG OPENING
OPP OPPOSITE
OPP HD OPPOSITE HAND
OSB ORIENTED STRAND BOARD
OSL OUTSTANDING LEG
OVS OVERSIZE HOLE
PAF POWDER ACTUATED FASTENER
PC PRECAST
PL PLATE
PLF POUNDS PER LINEAR FOOT
PLYWD PLYWOOD
PNL PANEL
PROJ PROJECTION
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSL PARALLEL STRAND LUMBER
PT PRESSURE TREATED
PTN PARTITION
R RADIUS
RD ROOF DRAIN
REF REFERENCE
REINF REINFORCE(D) (ING) (MENT)
REQ'D REQUIRED
REV REVISION/REVISED
RO ROUGH OPENING
RRD ROOF RELIEF DRAIN
RTN RETURN
RTU ROOF TOP UNIT
RW RETAINING WALL
SCHED SCHEDULE
SECT SECTION
SHT SHEET
SIM SIMILAR
SJ SAWCUT JOINT
SJI STEEL JOIST INSTITUTE
SL SLOPED
SPA SPACE(S)
SPECS SPECIFICATIONS
SQ SQUARE
SS STAINLESS STEEL
SSL SHORT SLOTTED HOLES
STD STANDARD
STIFF STIFFENERS
STL STEEL
STRUCT STRUCTURAL
SYMM SYMMETRICAL
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TB TIE BEAM
TC TOP CHORD
TCX TOP CHORD EXTENSION
TEMP TEMPERATURE
TF TRENCH FOOTING
THK THICK
THKS THICKENED SLAB
THR'D THREADED
TL TOTAL LOAD
TOP'G TOPPING
TRANS TRANSVERSE
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
VIF VERIFY IN FIELD
w/ WITH
WD WOOD
WO WINDOW OPENING (MASONRY)
WP WORKING POINT
WT WEIGHT
WWF WELDED WIRE FABRIC
ELEVATION TOP AND BOTTOM OF LIST
T/ "ELEVATION, TOP OF"
B/ "ELEVATION, BOTTOM OF"
T/BB TOP OF BOND BEAM
T/BM TOP OF BEAM
T/CONC TOP OF CONCRETE
T/F TOP OF FOOTING
T/LDG TOP OF LEDGE
T/MAS TOP OF MASONRY
T/P TOP OF PIER
T/SLAB TOP OF SLAB
T/STL TOP OF STEEL
T/W TOP OF WALL
T/GB TOP OF GRADE BEAM
T/CAIS TOP OF CAISSON
B/PL BOTTOM OF PLATE
B/F BOTTOM OF FOOTING
SPECIAL CHARACTERS
° DEGREE
± PLUS OR MINUS
ELEVATION
Ø DIAMETER
AR ANCHOR RODS
ABV ABOVE
ACI AMERICAN CONCRETE INSTITUTE
ADD'L ADDITIONAL
ADH ADHESIVE
ADJ ADJACENT
AESS ARCHITECTURALLY EXPOSED
STRUCTURAL STEEL
AFF ABOVE FINISHED FLOOR
AGGR AGGREGATE
AHU AIR HANDLING UNIT
AISC AMERICAN INSTITUTE OF
STEEL CONSTRUCTION
AISI AMERICAN IRON AND
STEEL INSTITUTE
ALUM ALUMINUM
ALT ALTERNATE
APPROX APPROXIMATE
ARCH ARCHITECT
ARCH'L ARCHITECTURAL
ASTM AMERICAN SOCIETY OF
TESTING MATERIALS
AWS AMERICAN WELDING SOCIETY
L ANGLE
BAL BALANCE
BB BOND BEAM
B/B BACK TO BACK
BC BOTTOM CHORD
BD BOARD
BLDG BUILDING
BLK BLOCK
BLW BELOW
BM BEAM
BOTT BOTTOM
BP BEARING PLATE
BRDG BRIDGING
BRG BEARING
BRK BRICK
BS BOTH SIDES
BSMT BASEMENT
BTWN BETWEEN
BUC BUILT UP COLUMN
c CAMBER
C/C CENTER TO CENTER
CANT CANTILEVER
CAIS CAISSON
CFS COLD FORMED STEEL
CJ CONTROL AND/OR
CONSTRUCTION JOINT
CL CENTERLINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
COORD COORDINATE
COMP COMPACTED
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
CTR CENTER
CTR'D CENTERED
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DL DEAD LOAD
DLT DEEP LEG TRACK
DO DITTO
DN DOWN
DTL DETAIL
DWG DRAWING
DWL DOWEL
EA EACH
EE EACH END
EF EACH FACE
EJ EXPANSION JOINT
ENG ENGINEER
ELEV ELEVATION
ELECT ELECTRICAL
EOD EDGE OF DECK
EOS EDGE OF SLAB
EQ EQUAL
EQUIV EQUIVALENT
ES EACH SIDE
EW EACH WAY
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
F/ FACE OF
FD FLOOR DRAIN
FDN FOUNDATION
FIN FINISH
FLR FLOOR
FLG FLANGE
FS FARSIDE
FTG FOOTING
GA GAUGE
GALV GALVANIZED
GB GRADE BEAM
GC GENERAL CONTRACTOR
GL GLULAM
GR GRADE
HC HOLLOW CORE
HD HOLD DOWN
HGT HEIGHT
HI HIGH
HK HOOK
HORIZ HORIZONTAL
HP HIGH POINT
HS HEADED STUD
HSS HOLLOW STRUCTURAL SECTION
ID INSIDE DIAMETER
IF INSIDE FACE
INFO INFORMATION
INT INTERIOR
INV INVERT
JST JOIST
JT JOINT
K KIP
KO KNOCK OUT
LB POUND
LDG LEDGE
LG LONG
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LNTL LINTEL
LSL LONG SLOTTED HOLES
LONG LONGITUDINAL
LP LOW POINT
LVL LAMINATED VENEER LUMBER
MAS MASONRY
MAT'L MATERIAL
MAX MAXIMUM
MBM METAL BUILDING MFR
MCJ MASONRY CONTROL JT
MECH MECHANICAL
MEZZ MEZZANINE
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MOM MOMENT
MSW MASONRY SHEAR WALL
MSL MEAN SEA LEVEL
MTL METAL
NO NUMBER
NS NEAR SIDE
NTS NOT TO SCALE
ABBREVIATIONS LIST
FACE OF CONC WALL OR CONC
COLUMN
T/STL
+(SEE PLAN)3"
1/
2"
3"
3/4" DIA A325N BOLTS IN DBL L4x3xTHICKNESS
INDICATED IN SCHEDULE, TYP. PROVIDE
13/16"x1 1/2" HORIZ SLOTS IN BEAM WEB AND
INSTALL NUTS. FINGERTIGHT AND PEEN
THREADS OR PROVIDE ADDITIONAL LOCKNUT.
EMBEDDED PLATE CONNECTION EMBEDDED PLATE DETAIL
1' - 0"
2" 8" 2"
'H
1/
2" 4"
4"
1/ 2" 'T'
6" LONG HEADED STUDS
'L
1/
4"
C. RODNEY
McCOMAS 081-005275
CARMEL
L
IC
E
NS
ED
ST
RUCTURAL
ENG
IN
E E R
Expires 11-30-20
STATE OF I LL
IN
O
ISINDIANA
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel
Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel
Fax
317.464.9090 317.464.9393
Office of Facilities
Management McComas/O'Donnell & Naccarato 1717 E 116th Street Carmel, IN 46032
Structural
Asaturian Eaton & Assoc.
1440 Old West Main Carbondale, IL 62901
Tel Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel Fax
618.529.5262 618.457.8991
Geotechnical
Tel Fax
317.580.0402 317.582.0766
5/22/2020 4:05:14 PM
SCHEDULES Expand & Upgrade Building 42 Laboratory
S402
17057 MEI
Marion, IL
11-08-2019
Bid Documents
TMM SDS of ###
WALL FOOTING SCHEDULE
Mark
Dimensions Bottom Reinf
RemarksWidth Thickness
Longitudinal Reinf Transverse Reinf
No Size Size Spa
WF24 2' - 0" 1' - 0" 3 #5 NA 0"
WF36 3' - 0" 1' - 4" 4 #5 NA 0"
WF48 4' - 0" 2' - 0" 5 #6 #5 1' - 0"
WF72 6' - 0" 2' - 6" 6 #8 #6 1' - 0"
Wall Footing Schedule Notes:
1. Reinforcing clearance at bottom and sides of footings = 3"
2. Use concrete brick of CRSI Class 3, CHCP wire bar supports @ 36".
COLUMN FOOTING SCHEDULE
Mark
Ftg Dimensions Bottom Reinforcing
RemarksWidth Length Thickness
Short Direction Long Direction
No Size Length No Size Length F3x5 3' - 0" 5' - 0" 1' - 0" 6 #5 2' - 6" 3 #5 4' - 6"
F5 5' - 0" 5' - 0" 1' - 0" 5 #5 4' - 6" 5 #5 4' - 6"
F7 7' - 0" 7' - 0" 1' - 6" 7 #6 6' - 6" 7 #6 6' - 6"
F8 8' - 0" 8' - 0" 2' - 0" 10 #6 7' - 6" 10 #6 7' - 6"
F9 9' - 0" 9' - 0" 1' - 10" 10 #6 8' - 6" 10 #6 8' - 6"
F11 11' - 0" 11' - 0" 2' - 2" 11 #8 10' - 6" 11 #8 10' - 6"
F11x50 11' - 0" 50' - 0" 4' - 0" 75 #8 10' - 6" 21 #8 49' - 6"
F13 13' - 0" 13' - 0" 2' - 4" 11 #8 12' - 6" 11 #8 12' - 6"
F16x50 16' - 0" 50' - 0" 4' - 0" 75 #8 15' - 6" 21 #8 49' - 6"
F18x50 18' - 0" 50' - 0" 4' - 0" 75 #8 17' - 6" 24 #8 49' - 6"
Column Footing Schedule Notes:
1. Reinforcing clearance at bottom and sides of footings = 3"
2. Use concrete brick of CRSI Class 3, CHCP wire bar supports @ 36".
PIER SCHEDULE
Mark
Pier Size Vertical Reinforcing Ties
Width Length Qty Size Size Spa P18 1' - 6" 1' - 6" 4 #6 #3 1' - 0"
P24 2' - 0" 2' - 0" 8 #6 #3 1' - 0"
Pier Schedule Notes:
1. Provide 2 inch concrete cover over ties.
2. Space first tie 2" from top of footing, last tie 2" from top of pier.
3. Provide (3) ties in top of pier, spacing = 2 1/2" on center.
4. Provide CRSI typical bar bend T5 for all ties.
5. Provide CRSI typical bar bend T9 additional ties for all piers with more than four vertical bars.
6. Provide 90° Hook for all ties per CRSI detailing standards.
SLAB ON GRADE SCHEDULE
Mark Thickness Reinforcing Control Jt
Depth Reinf
Clearance Control Jt Spa Vapor Retarder Sub-Base Depth Remarks SOG04P 4" 6x6-W1.4xW1.4 WWF 1" 1 1/2" 13' - 0" Plastic 4"
Slab on Grade Schedule Notes:
1. Reinforcing clearance is from the top of slab.
ELEVATED SLAB SCHEDULE
Mark Total
Thickness Concrete Density Conc Reinf
Metal Deck
RemarksThickness Gauge Type Finish FD01 5" Normal 6x6-W2.9xW2.9 WWF 1 1/2" 20 C Galvanized (2) Sidelap fasteners - See General Notes
Elevated Slab Schedule Notes:
1. Provide minimum of 1 1/2" end bearing.
2. Total thickness is the thickness from top of concrete to bottom of deck.
3. If indicated, provide minimum galvanized finish equal to ASTM A653-G30.
4. Type C = Composite Deck; Type NC = Non-Composite Form Deck
ROOF DECK SCHEDULE
Mark Thickness Gauge Type Finish Sidelap Remarks RD01 1 1/2" 22 WR Painted Non-Inter (2) Sidelap fasteners - See General Notes
Roof Deck Schedule Notes:
1. Abbreviations:
WR = Wide Rib WRC = WR Cellular WRA = Wide Rib Acoustical WRAC = Wide Rib Acoustical Cellular Non-Inter = Non-interlocking sidelap Interlock = Interlocking sidelap
2. Provide minimum of 1 1/2" bearing at ends of deck.
3. Provide minimum of 4" of bearing at interior supports.
COLUMN SCHEDULE
Grid Intersection Size
Base Plate Size Anchor Rods
RemarksThickness Width Length Size (Dia) Quantity A-2 W12X72 1 1/2" 1' - 7" 1' - 7" 3/4" 4
A-3 W14X176 3 1/2" 4' - 0" 8' - 0" 2" 32 SEE FRAMING ELEVATIONS
A-4 W14X176 3 1/2" 4' - 0" 8' - 0" 2" 32 SEE FRAMING ELEVATIONS
A-5 W12X72 1 1/2" 1' - 7" 1' - 7" 3/4" 4
A.2-2 HSS5X5X3/8 3/4" 11" 11" 3/4" 4
A.2-2.5 HSS5X5X3/8 3/4" 11" 11" 3/4" 4
A.2-3 HSS5X5X3/8 3/4" 11" 11" 3/4" 4
A.2-3.5 HSS5X5X3/8 3/4" 11" 11" 3/4" 4
A.2-4 HSS5X5X3/8 3/4" 11" 11" 3/4" 4
A.2-4.5 HSS5X5X3/8 3/4" 11" 11" 3/4" 4
A.2-5 HSS5X5X3/8 3/4" 11" 11" 3/4" 4
A.6-2 HSS5X5X3/8 3/4" 11" 11" 3/4" 4
A.6-2.5 HSS5X5X3/8 3/4" 11" 11" 3/4" 4
A.6-3 HSS5X5X3/8 3/4" 11" 11" 3/4" 4
A.6-3.5 HSS5X5X3/8 3/4" 11" 11" 3/4" 4
A.6-4 HSS5X5X3/8 3/4" 11" 11" 3/4" 4
A.6-4.5 HSS5X5X3/8 3/4" 11" 11" 3/4" 4
A.6-5 HSS5X5X3/8 3/4" 11" 11" 3/4" 4
B-2 W14X176 3 1/2" 4' - 0" 8' - 0" 2" 32 SEE FRAMING ELEVATIONS
B-3 W12X72 1 1/2" 1' - 7" 1' - 7" 3/4" 4
B-4 W12X72 1 1/2" 1' - 7" 1' - 7" 3/4" 4
B-5 W14X176 3 1/2" 4' - 0" 8' - 0" 2" 32 SEE FRAMING ELEVATIONS
B.2-6 W10X33 3/4" 1' - 4" 1' - 4" 3/4" 4
C-2 W14X176 3 1/2" 4' - 0" 8' - 0" 2" 32 SEE FRAMING ELEVATIONS
C-3 W14X176 3 1/2" 4' - 0" 8' - 0" 2" 32 SEE FRAMING ELEVATIONS
C-4 W14X176 3 1/2" 4' - 0" 8' - 0" 2" 32 SEE FRAMING ELEVATIONS
C-5 W14X176 3 1/2" 4' - 0" 8' - 0" 2" 32 SEE FRAMING ELEVATIONS
C-6 W10X33 3/4" 1' - 4" 1' - 4" 3/4" 4
C.2-1 HSS5X5X1/2 3/4" 6" 1' - 0" 3/4" 4 STUB COLUMN
C.2-2.1 HSS5X5X1/2 3/4" 6" 1' - 0" 3/4" 4 STUB COLUMN
D-2.2 W12X72 1 1/2" 1' - 7" 1' - 7" 3/4" 4
D-3 W12X72 1 1/2" 1' - 7" 1' - 7" 3/4" 4
D-4 W12X72 1 1/2" 1' - 7" 1' - 7" 3/4" 4
D-5 W12X72 1 1/2" 1' - 7" 1' - 7" 3/4" 4
D-6 W10X33 1 1/2" 1' - 4" 1' - 4" 3/4" 4
Column Schedule Notes:
1. See typical details for column base construction.
STEEL BEAM TO CONCRETE COLUMN OR WALL CONNECTION SCHEDULE
Mark
EP1
Steel Beam To Concrete Column or Wall Connection Lintel Schedule Notes:
1. This schedule is for 50 ksi beams only.
2. Beam material per general notes.
3. Plate and angle material ASTM A36.
4. For beam reactions, see framing plans. Should indicated reactions exceed table capacities fabricator shall provide connection detail.
5. Beam web capacity requires verification for beams with ASTM A36 material.
6. UNO on plan or if reaction exceeds tabulated value, use this connection as typical for listed beam sizes.
Beam Rows of
Bolts
C8, W8, W10 2
Weld 'A' Size
5/16"
Angle Size
L4x3x3/8 5 1/2"
Angle 'L' Length
Embed Plate
'H'
9"
'T'
5/8"
No. Studs
Capacity (Kips) Per Concrete Strength
4 KSI
18.3 18.3
3 KSI
EP2
EP3
EP4
EP5
EP6
EP7
EP8
EP9
W12x14
W12x16 - W14
W16, W18
W21
W24
EP10
W27
W30
W33
W36, W40
5/16"
5/16"
5/16"
5/16"
5/16"
1/4"
1/4"
1/4"
1/4"
L4x3x3/8
L4x3x3/8
L4x3x3/8
L4x3x3/8
L4x3x3/8
L4x3x5/16
L4x3x5/16
L4x3x5/16
L4x3x5/16
8 1/2"
8 1/2"
11 1/2"
14 1/2"
17 1/2"
20 1/2"
23 1/2"
26 1/2"
29 1/2"
13"
13"
17"
21"
25"
29"
33"
33"
37"
5/8"
5/8"
5/8"
5/8"
5/8"
5/8"
5/8"
5/8"
5/8"
40.3
58.4
91.5
111111
40.3
58.4
CONCRETE WALL SCHEDULE
Mark Width
Horiz Reinf Vert Reinf Dowel Reinf
Reinf Location Cover RemarksSize Spa Location Size Spa Size Spa CW8 8" #4 1' - 0" #4 1' - 0" #4 1' - 0" Center 2"
CW10 10" #5 1' - 0" Each Face #5 1' - 0" #5 1' - 0" Each Face 2"
CW12 1' - 0" #5 1' - 0" Each Face #5 1' - 0" #5 1' - 0" Each Face 2"
CW14 1' - 2" #5 1' - 0" Each Face #7 8" #7 8" Each Face 2"
Concrete Wall Schedule Notes:
1. Provide concrete cover to closest bar as indicated.
2. Provide wheel spacers or CRSI Typ. Bar Bend T5 at 36" each way to assure adequate concrete cover.
3. See sections for all bars not included in schedule.
4. Horizontal Bar Location: In = Horizontal bars inside of vertical bars, Out = Horizontal bars outside of vertical bars.
MASONRY WALL SCHEDULE
Mark Thickness
Vertical Wall Reinforcing Horizontal Reinforcing Bond Beam Reinforcing
Remarks
Reinforcing Dowel Reinforcing
Size Spa Qty SizeSize Spa Location Size Spa MW8 7 5/8" #5 4' - 0" Center #5 4' - 0" Ladder 1' - 4" 2 #5 Bond Beams @ 8'-0" oc
MW12 11 5/8" #5 2' - 0" Each Face #5 2' - 0" Ladder 1' - 4" 2 #5 Bond Beams @ 8'-0" oc
Masonry Wall Schedule Notes"
1. Provide 2" cover from outside face for bars in each face.
2. Grout all cores with rebar solid, unless solid grouted wall is shown.
3. Provide ladder type horizontal reinforcement at 16" o.c., unless noted otherwise. Side and cross rods shall be #9 wire, galvanized, see specifications. Cut joint reinforcement at control joints.
4. Provide bond beam with (2) #5 continuous at top of wall, unless noted otherwise. See schedule for additional bond beams.
T/STL
+(SEE PLAN)
POCHE REPRESENTS
MASONRY WALL
P16
F4
P16
F4
T/P -0'-8"
T/F -2'-8" HSS6
M W
T
/W
0' -8
W F
T
/F
2' -8
CW8 T/W -0'-8"
WF24 T/F -2'-8"
COL MARK, SEE SCHEDULE
FOR ACTUAL SIZE,
BASEPLATE AND ANCHOR
RODS
P16 = PIER MARK, SEE SCHEDULE
T/P = TOP OF PIER ELEV
F4 = COL FTG MARK, SEE SCHEDULE
T/F = TOP FTG ELEV
CONCRETE MASONRY UNIT WALL (MW)
SEE SCHED FOR SIZE AND REINF
T/W = TOP OF WALL ELEV
CONCRETE WALL (CW), SEE SCHED
FOR WALL THICKNESS AND REINF
SPOT ELEV INDICATES
TOP OF CONC
INDICATES PLAN DETAIL
COL GRID, COLUMNS CENTERED
ON GRID INTERSECTION, UNO
T/F = TOP OF FTG ELEV
CONCRETE WALL FTG (WF), SEE
SCHED FOR SIZE AND REINF
INDICATES SECTION CUT
POCHE
REPRESENTS
CONCRETE WALL
S401
S401
INDICATES EDGE
OF WALL FTG
INDICATES EDGE OF WALL
FTG UNDER FLOOR SLAB
H
G
D
C
B
INDICATES PLAN DETAIL
INDICATES SECTION CUT
S401
S401
COL GRID, COLUMNS
CENTERED ON GRID
INTERSECTION, UNO
4" E O
D
EDGE OF DECK,
PERIMETER ANGLE
W14x22
+23'-0"
+23'-0"
OPENING THRU
DECK AND
FRAMING
W x2
(S L)
+24'-0"
W x2
'-0
TOP OF STEEL ELEV
AT GRID INTERSECTION
UNFACTORED
REACTION IN KIPS
TOP OF STEEL ELEV
INDICATES BEAM SIZE
JOIST SIZE32LH12
INDICATES KNEE BRACE
K B k k
INDICATES BRACING
W14x22 +24'-0"
MOMENT CONNECTION
"X" BRIDGING
HORIZ BRIDING
G
8N
.5 K
'-0
JOIST GIRDER SIZE
(UNFACTORED)
T/JOIST GIRDER ELEV
K
INDICATES JOIST SIZE
INDICATES BEAM SIZE
NUMBER OF
SHEAR STUDS
BEAM CAMBER
INDICATES BRACING ELEVATION
5/8"
W x1
(9
C =3
/4
IN
D
IC
A
T E
S D
E C
K
S P
A N
A N
D D
E C
K
M A
R K
S501
T/CONC
-0'-2"
T/CONC
-0'-2"
T/CONC
-0'-0"
T/CONC
-0'-10"
T/CONC
-0'-0"
S
LO
P E
EXTERIOR SLAB
SEE CIVIL
THICKENED SLAB
CONSTRUCTION OR
CONTROL JT
EXTERIOR SLAB
SEE CIVIL
GFK
J
A
J
C
ARCH
SEE
A R
C H
S E
E
CMU/CONC WALL
CMU WALL
CONC RAMP
SLAB DEPRESSION
OPENING IN
SLAB SEE
DETAIL H
LOWER SLAB
COLUMN ISOLATION
SEE DETAIL D
COLUMN ISOLATION
SEE DETAIL E
SLAB ON GRADE
B
TYPICAL SLAB ON GRADE KEY PLAN
SCALE: NTS
NOTE: KEY PLAN ILLUSTRATES CONSTRUCTION CONCEPTS ONLY. SEE PLAN FOR ACTUAL DIMENSIONS AND ARRANGEMENTS.
SOG01
SLAB MARK
SEE SCHEDULE
IN
CREASE A
S R
EQ'D
F
OR L
ARGER C
OL
2'
- 0
" M
IN
INCREASE AS REQ'D FOR LARGER COL
2' - 0" M
IN
POUR SLAB, LEAVING OUT
AREA AROUND COLUMN.
INFILL WITH CONCRETE
AFTER SLAB HAS CURED
1/2" EXP JT MAT'L
COLUMN
SLAB CONTROL JT,
TYP AT ALL
COLUMN LINES
VAPOR RETARDER
CONC SLAB
COMPACTED SUB GRADE
COMPACTED GRANULAR FILL
T/SLAB
+(SEE PLAN)
FORMED KEY
VAPOR RETARDER
CONC SLAB
COMPACTED SUB GRADE
COMPACTED GRANULAR FILL
T/SLAB
+(SEE PLAN)
1/8" SAW N CONTROL JOINT, ALL
JOINTS SHALL BE SAWN WITHIN
12 HOURS OF SLAB POUR
4" 13'-0" 1"
5" 15'-0" 1 1/4"
6" 15'-0" 1 1/2"
7" 18'-0" 1 3/4"
8" 20'-0" 2"
9" 24'-0" 2 1/4"
10" 25'-0" 2 1/2"
1'-0" 25'-0" 3"
SLAB
THICKNESS
MAX
JT
SPACING
JOINT
DEPTH
NOTE:
CONTRACTOR TO PROVIDE CONTROL JOINT LAYOUT, BASED ON MAXIMUM JOINT SPACING, UNO.
POUR SLAB, LEAVING OUT
AREA AROUND COLUMN.
INFILL WITH CONCRETE
AFTER SLAB HAS CURED
1/2" EXP JT MAT'L
COLUMN
SLAB CONTROL JT,
TYP AT ALL
COLUMN LINES
INCREASE AS REQ'D FOR LARGER COL
2' - 0" M
IN
CONC PIER (BELOW)
FOUNDATION WALL, SEE
FOUNDATION PLAN FOR
ACTUAL CONDITION
THICKEND PORTION OF
SLAB TO BE TWICE THE
SLAB THICKNESS CALLED
OUT ON THE PLANS(3) #5 CONT
REINF ALL INTERIOR
MASONRY WALLS OVER 12'-
0" HIGH w/
#5 @ 4'-0" OC, UNO
3' - 0" x#5 DOWELS, UNO 1'-0"
3' -0
8" MIN
S E
E P
LA
N
S E
E P
LA
N
S
LA
B T
H
IC
K N
E S
S
D E
P R
E S
S
IO
N U
P T
O
T/SLAB
+(SEE PLAN)
WWF TO CONT THRU
DEPRESSED SLAB AREA
SEE PLAN
FOR LIMITS
COMPACTED
DRAINAGE FILL PERIMETER
INSULATION -
SEE ARCH
CONC SLAB
1/2" EXP JT MAT'L
@ THRESHOLD
INTERIOR SLAB EXTERIOR
SLAB
SLOPE
1/4"
GRANULAR
FILL
T/SLAB
+(SEE PLAN)
T/W
+(SEE PLAN)
x#5 @ 48" OC 1'-6"
1' -6
PERIMETER
INSULATION -
SEE ARCH
CONC SLAB
1/2" EXP JT MAT'L
INTERIOR SLAB EXTERIOR
SLAB
SLOPE1/4"
GRANULAR
FILL
T/SLAB
+(SEE PLAN)
T/W
+(SEE PLAN)
x#5 @ 48" OC 1'-6"
1' -6
#5x3'-0" @ 12" OC
(3) PER DOOR MIN
T H
A N
P
LA
N T
H
IC
K N
E S
S D
E P
R E
S S
IO
N
G R
E A
T E
R
S E
E P
P
LA
N
S E
E P
LA
N
T/SLAB
+(SEE PLAN)
x#3 @ 12" OC
9"
9"CONC SLAB
#3 CONT
COMPACTED
DRAINAGE FILL
CONC SLAB
T/SLAB
+(SEE PLAN)
8" MIN
T/SLAB
+(SEE PLAN)
T/SLAB
+(SEE PLAN)
1/2" EXP JT MAT'L
CONC SLAB
CMU/CONC WALL
8" TYP 1' - 0" TYP
T H
IC
K
N E
S S
2x S
LA
B
1' - 0" TYP 8" TYP
T H
IC
K
N E
S S
2x S
LA
B
T/STL
+(SEE PLAN)
T/STL
+(SEE PLAN)
CONC SLAB
KEY
METAL CONSTUCTION JOINT
COMPACTED DRAINAGE FILL
CONC SLAB
KEY
METAL CONSTUCTION JOINT
TYP SLAB CONSTRUCTION JT
TYP SLAB CONTROL JT
SCALE:
TYPICAL CONCRETE SLAB JOINTS
NTS A
SCALE:
TYPICAL THICKENED SLAB
NTS B
SCALE:
TYP CONCRETE RAMP DETAILS
NTS C
TOP OF RAMP
BOTTOM OF RAMP
SCALE:
TYP COLUMN ISOLATION JOINT
NTS D
SCALE:
TYP COLUMN ISOLATION JOINT
NTS E
SCALE:
TYP SECTION AT ENTRY
NTS F
SCALE:
TYP SECTION AT EXTERIOR SLAB
NTS G
SCALE:
TYP DEPRESSED SLAB SECTIONS
NTS J
SECTION
SECTION
SCALE:
TYP EXPANSION JT AT WALL
NTS K
ADDITIONAL
#4x1'-6" @
EACH CORNER
ADDITIONAL
(4) #4x1'-6"
OPENING IN
SLAB
1/
2" C
LR
T Y
P
LIMITS OF SLAB
REINFORCING
SCALE:
TYP SLAB ON GRADE OPENING
NTS H
NOTE:
COORD LOCATION OF
THRESHOLD w/ ARCH
DWGS
FOUNDATION
FOUNDATION
WRAP HSS w/
1/2" EXP JT MAT'L
COLUMN
#4x1'-6" CENTERED
IN SLAB
WRAP HSS w/
1/2" EXP JT MAT'L
COLUMN
#4x1'-6" CENTERED
IN SLAB
ALTERNATE FOR HSS COL
ALTERNATE FOR HSS COL
C. RODNEY
McCOMAS 081-005275
CARMEL
L
IC
E
NS
ED
ST
RUCTURAL
ENG
IN
E E R
Expires 11-30-20
STATE OF I LL
IN
O
ISINDIANA
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel
Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel
Fax
317.464.9090 317.464.9393
Office of Facilities
Management McComas/O'Donnell & Naccarato 1717 E 116th Street Carmel, IN 46032
Structural
Asaturian Eaton & Assoc.
1440 Old West Main Carbondale, IL 62901
Tel Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel Fax
618.529.5262 618.457.8991
Geotechnical
Tel Fax
317.580.0402 317.582.0766
5/22/2020 4:05:16 PM
SLAB ON GRADE DETAILS
AND DRAWING LEGENDS
Expand & Upgrade Building 42 Laboratory
S403
17057 MEI
Marion, IL
11-08-2019
Bid Documents
TMM SDS of ###
SCALE: NTS
FOUNDATION PLAN LEGEND
SCALE: NTS
FRAMING PLAN LEGEND
CONC WALL (CW)
1/2" EXP JT MAT'L
CONC SLAB
CONC WALL FTG
(WF)
WATERPROOFING PANELS
AND DRAINAGE MAT'L
WRAP DRAINAGE MAT
AROUND DRAIN PIPE
AND COVER WITH
GRANULAR FILL
6" PERFORATED
DRAIN PIPE
1'-0"
2' -0 x#5 @ 12" OC
2" CLR
2" CLR
2" C
LR
2"
C
LR
1 1/2" CLR (TYP)
S E
E P
LA
N
PIER (P)
PIER REINF -
SEE SCHEDULE
CONC WALL (CW)
CONT WALL REINF
THROUGH PIER
WIDTH
EQ EQ
LE
N
G T
H
E Q
E Q
PIER POURED INTEGRAL
w/ WALL
COLUMN
ANCHOR RODS
WITHIN TIES
CONC PIER
PIER VERT REINF
SEE SCHEDULE
CONC FTG
T/P
+(SEE PLAN)2"
2"
3" 2' - 8 3/4"
T
IE
S
2"
O C
1' - 10"
1' - 10"
SEE PLAN
S E
E P
LA
N
PIER VERT REINF
SEE SCHEDULE
TIE
A SECTION A
T/F
-(SEE PLAN)
PLACE TIE IN FTG
FOR DOWEL
ALIGNMENT
2" C L
R
1' - 10"
1' - 10"
SEE PLAN
S E
E P
LA
N
PIER INTEGRATED w/ WALL
2" C L
R
WALL HORIZ
CONT THROUGH
PIER REINF
T/F
+(SEE PLAN)
T/F
+(SEE PLAN)
1' - 0"
MATCH FOOTING REINF
IN SIZE AND NUMBER
REQ'D
2'-0" 2'-0"
FTG REINF
FTG REINF
1' - 0" 2'
-0
M A
X
NOTE:
ALL BENT BARS SAME
SIZE AND SPACING AS
HORIZONTAL STEEL
CORNER DETAIL
NOTE:
ALL BENT BARS SAME
SIZE AND SPACING AS
HORIZONTAL STEEL
INTERSECTION DETAIL
NOTE:
ALL BENT BARS SAME
SIZE AND SPACING AS
HORIZONTAL STEEL
CORNER DETAIL
NOTE:
ALL BENT BARS SAME
SIZE AND SPACING AS
HORIZONTAL STEEL
INTERSECTION DETAIL
LAP - SEE SCHED
TOP BAR TENSION
LA
P
S
E E
S C
H E
D
T O
P B
A R
T E
N S
IO
N
LAP - SEE SCHED
TOP BAR TENSION
LA
P
S
E E
S C
H E
D
T O
P B
A R
T E
N S
IO
N
LAP - SEE SCHED
TOP BAR TENSION
LA
P
S
E E
S C
H E
D
T O
P B
A R
T E
N S
IO
N
LAP - SEE SCHED
TOP BAR TENSION
LAP - SEE SCHED
TOP BAR TENSION
LA
P
S
E E
S C
H E
D
T O
P B
A R
T E
N S
IO
N
8"
NEW CONC SLAB
EXISTING CONC SLAB
COAT WITH BONDING AGENTNEW CONC SLAB
#5x1'-8"@12" USE HILTI
HVA ADHESIVE
CARTRIDGE TO BOND
BAR TO EXISTING SLAB
T/SLAB
+(SEE PLAN)
CMU (MW) OR CONC (CW) -
SEE PLAN
T/F
-(SEE PLAN)
T/F
-(SEE PLAN)
CONC WALL FTG (WF)
PILASTER w/ (4) #6 VERTICAL
& #3 TIES @ 12" OC
1' - 0" MIN
(4) #6
DOWELS
CONC WALL FTG (WF)
T/PILASTER = BOTT/F ABOVE
-(SEE PLAN)
CONC WALL (CW) -
SEE PLAN &
SCHEDULE
PLAN
SEE
DETAIL "A"
2' - 0" M
A T
C H
F T
G W
ID
T
H A
B O
V E
PLAN
SEE
PL
A
N
SE
E
1' - 0" MIN
CENTERLINE
OF FTG
A
A x(2) #5 2'-0"
2' -0
1' - 0"
C. RODNEY
McCOMAS 081-005275
CARMEL
L
IC
E
NS
ED
ST
RUCTURAL
ENG
IN
E E R
Expires 11-30-20
STATE OF I LL
IN
O
ISINDIANA
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel
Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202
Tel
Fax
317.464.9090 317.464.9393
Office of Facilities
Management McComas/O'Donnell & Naccarato 1717 E 116th Street Carmel, IN 46032
Structural
Asaturian Eaton & Assoc.
1440 Old West Main Carbondale, IL 62901
Tel Fax
618.529.3414 618.529.3423
Civil
John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301
Tel Fax
636.757.3060 636.757.3064
Industrial Hygenist
Holcomb Foundation 393 Wood Road Carbondale, IL 62901
Tel Fax
618.529.5262 618.457.8991
Geotechnical
Tel Fax
317.580.0402 317.582.0766
5/22/2020 4:05:18 PM
TYPICAL SECTIONS AND
DETAILS
Expand & Upgrade Building 42 Laboratory
S404
17057 MEI
Marion, IL
11-08-2019
Bid Documents
TMM SDS of ###
SCALE: S404 3/4" = 1'-0"
1TYP FDN WALL FTG SECTION
SCALE: S404 3/4" = 1'-0"
2TYPICAL CORNER PIER DETAIL
SCALE: S404 3/4" = 1'-0"
3TYPICAL PIER DETAIL
SCALE: S404 3/4" = 1'-0"
4TYPICAL PIER ELEVATION
SCALE: S404 3/4" = 1'-0"
7TYP TOP OF FOOTING STEP
SCALE: S404 3/4" = 1'-0"
5TYP REINFORCED WALL DETAILS
SCALE: S404 3/4" = 1'-0"
8TYP SECTION AT EXISTING SLAB
SCALE: S404 3/4" = 1'-0"
6TYP PILASTER SECTION
6" SPLIT PVC
WATERSTOP
FOAM BACKER ROD
AND SEALANT
ALL HORIZONTAL
REINF IS CONT THRU
JOINT
1/2"
5/8"
1/
2" C
LR
LAP - SEE SCHEDULE
ROUND OR SQUARE OPNG
8" TO 3'-0" 2" CLR2" CLR
PLACE ADDITIONAL VERT (AND
HORIZ) REINFORCING BTWN STD
SPACING AT 2" INCREMENTS
WALL REINFORCING
ADDITIONAL HORIZONTAL BARS
NONE: 1" TO 7" OPENING
(1) #5: 8" TO 12" OPENING
(2) #5: 13" TO 28" OPENING
(3) #5: 29" TO 36" OPENING
ADDITIONAL VERTICAL BARS
NONE: 1" TO 7" OPENING
(2) #6: 8" TO 12" OPENING
(3) #6: 13" TO 20" OPENING
(4) #6: 21" TO 28" OPENING
(6) #6: 29" TO 36" OPENING
NOTE: PROVIDE THIS ADDITIONAL REINFORCING AROUND (4) SIDES OF OPENING.
4"
1'
4'
1' - 0"8"9"
SILL ANGLE - L6x6x1/2"
(4) #5 HORIZ
#6 @ 12" OC, EW, T&B
HYDRAULIC
SHAFT OPNG 3"
C
LR
RX WATERSTOP
GRANULAR FILL
CONC SLAB
L5x3x1/4" (LLV) w/ 1/2"Øx4" HS @ 2'-0" OC
T/SLAB
+(SEE PLAN)
T/ELEV SLAB
+(SEE PLAN)
V E
R
IF
Y w
/ E
LE
V A
T O
R S
U P
P
LI
E R
1'-0" x#5 @ 12" OC, CENTER IN WALL
2'-0"
2' -0
"x#5 @ 12" OC
1" C
LR
8"
5/16 4-12
ELEVATOR WALL
ELEVATOR SLAB
REINF TO MATCH PIT SLAB
1' - 6"
1' - 6"
1' - 0" S
LA
B
D E
P T
H
C O
O R
D
COORD
ELEVATOR SLAB
SUMP PIT, COORD SIZE,
DEPTH AND LOCATION w/
ELEVATOR SUPPLIER
T/SLAB
+(SEE PLAN)
SECTION A-A
SUMP PIT, COORD SIZE,
DEPTH AND LOCATION w/
ELEVATOR SUPPLIER
ELEVATOR WALL
ELEVATOR SLAB
ISOMETRIC OF SUMP PIT
A
A
BLOCKOUT AS REQ'D BY
ELEVATOR CONTRACTOR
SILL ANGLE & ANCHOR BY
ELEVATOR CONTRACTOR
CONC SILL
8" BOND BM w/
(2) #5 CONT
#5 WALL REINF
8" CMU BEAM
T/SLAB
+(SEE PLAN)
x#4 @ 12" OC
FIELD BEND INTO CONC SILL
1'-10"
OPEN BLOCK CMU WALL
(RUNNING BOND PATTERN)
CMU WALL
VERT REINFORCING
HORIZ REINFORCING
A TYPICAL CORNER B TYPICAL INTERSECTION
ALTERNATE LEG
DIRECTION OF
INTERSECTION BARS
CMU WALL
HORIZ REINFORCING
VERT REINFORCING
OPEN BLOCK CMU WALL
(RUNNING BOND PATTERN)
x#4 @ 8" OC24
24" x#4 @ 8" OC
" 24"
L A
P 24" M
I N
8" MIN
BOND BEAM AT TOP WALL
STEEL LINTEL
BEARING PLATE (TYP)
MASONRY OPENING
8" DEEP BOND BEAM
(OMIT AT DOOR OPENING)
8" DEEP BOND BEAM
(OMIT AT DOOR OPENING)
MASONRY OPENING
PRECAST LINTEL
VERTICAL REINF
TO MATCH
WALL REINF
BOND BEAM AT TOP WALL
REINFORCING GROUT (2)
CORES ES MASONRY OPNG
@ GABLE END WALL
8" TYP
(A) TYPICAL CORNER (B) TYPICAL INTERSECTION (C) TYPICAL JAMB
NOTES:
1.…
This is the start of the file's text. The full file is on GovTribe.