NFC Fitness Court Studio Concrete Slab Drawing.pdf
PDF 1 MB Posted
- Attached to
- On-Call Excavation Service
- Solicitation number
- 38226
- Issued by
- Connecticut
About this file
This document is a technical specification drawing prepared by the National Fitness Campaign for the construction of a concrete slab foundation suitable for outdoor fitness court installations. The drawing package, dated February 13, 2025, and prepared under engineer of record Wells L. Holmes, S.E., provides comprehensive standards and detailed construction requirements for a fitness court studio concrete slab measuring a minimum of 38 feet wide by 73 feet long with a 4-inch minimum thickness. The scope of work includes site preparation with compacted soil and gravel base, installation of vapor barriers, welded wire mesh reinforcement, concrete placement meeting 4,000 PSI strength requirements at 28 days, finishing operations including light broom finish application, contraction joint sawcutting within 24 hours of pour, and application of Spray-Lock P3 Industrial concrete sealer within 24 hours. The construction sequence specifies that reinforcement steel, anchor bolts, and mesh must be installed at mid-depth, concrete must be finished to a specific slope for drainage with a 1/8-inch per 12-inch slope perpendicular to the wall face, and all work must comply with ACI 318 standards and local code requirements. Installation of the fitness wall, anchors, fitness flooring, and equipment are performed by others following completion of the concrete work.
The specifications mandate concrete compressive strength of 4,000 PSI at 28 days using ASTM C-150 Type II Portland cement with a maximum water-cement ratio of 0.5, strict limitations on admixtures excluding calcium chloride and thiocyanate compounds, and maximum slump of 5 inches unless superplasticizers are approved by the engineer. Concrete placement is prohibited when atmospheric temperatures fall below 40 degrees Fahrenheit without engineer permission, and hot weather concrete placement plans are required for temperatures exceeding 90 degrees. The reinforcement layout specifies 6x6 W2.9/W2.9 welded wire mesh with 2-inch minimum spacing from concrete edges, and a 10-mil minimum vapor barrier with 12-inch overlaps at joints. Contraction joints must be sawcut to a maximum depth of 25 percent of slab depth at 15-foot maximum spacing with specific anchor placement coordination to maintain 3-inch clearance between anchor centers and joints. The Spray-Lock P3 Industrial sealer application is mandatory with no acceptable equals, and flooring installation is permitted after 14 days post-treatment, though full 28-day cure time is preferred. The drawing package includes detailed anchor specifications for wall, coupling, and equipment installations, specific anchor location coordinates measured from a point of beginning, and comprehensive do's and don'ts addressing contraction joint placement, expansion joint restrictions, prevention of plastic shrinkage cracking, and prohibition against reusing old tennis courts as foundations without NFC project manager approval.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 38226_Aug_3_26_solicitation_doc.pdf | ||
| Bid No.2027-01 PLAN SET IFB.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROVIDE A MINIMUM OF 4" THICK CONCRETE SLAB PER PLANS. MINIMUM DIMENSIONS ARE 38'-0" WIDE X 73'-0" LONG. SEE SITE SPECIFIC PLANS AND / OR ENGINEERING PROVIDED BY OTHERS IF DIFFERENT.
NFC FITNESS COURT STUDIO CONCRETE SLAB
MINIMUM STANDARDS
SHEET INDEX
SHT. NO.
DESCRIPTION
COVER
SPECIFICATIONS
STANDARD DETAILS
CONCRETE SLAB LAYOUT
SITE PREP / LAYOUT
ANCHOR DETAILS
JOINT / AB LAYOUT PLAN
DO'S & DON'TS
PROPERTY OF NATIONAL FITNESS CAMPAIGN ©
THIS DOCUMENT IS PROPERTY OF NFC (THE NATIONAL FITNESS CAMPAIGN). THIS
DOCUMENT CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION AND MAY
ONLY BE USED BY PERMISSION FROM NFC AND FOR THE PURPOSES AUTHORIZED BY
NFC. DISCLOSURE, DUPLICATION, MODIFICATION, OR OTHER USE OF THIS
DOCUMENT IS NOT PERMITTED WITHOUT THE PRIOR WRITTEN PERMISSION OF NFC.
REVIEW
PLANS/
ORDER
SPRAYLOCK
GRADE /
PREPARE
SITE PER
PLANS
INSTALL
VAPOR
BARRIER
SET FORMS
AND
INSTALL
WW MESH
POUR
CONCRETE
PER
PLANS
SAWCUT
CONTRACTION
JOINTS
WITHIN
24 HRS OF
POUR
APPLY
SPRAYLOCK
WITHIN
24 HRS OF
POUR
INSTALL
COMPACTED
GRAVEL BASE
PER
PLANS
38'-0" WIDE
CONCRETE SLAB
PER PLANS
73'-0" LONG
CONCRETE SLAB
PER PLANS
SCOPE:
PROVIDE CONCRETE SLAB FOR USE WITH OUTDOOR FITNESS FLOORING AND EQUIPMENT. THIS
CONCRETE SLAB WILL HAVE SPECIALTY FLOORING INSTALLED ON IT SO COMPLIANCE TO THE PROJECT PLANS AND SPECIFICATIONS ARE CRITICAL TO AVOID REWORK OR REPAIR PRIOR TO INSTALLATION OF THE FITNESS COURT (BY OTHERS). INSTALL CONCRETE PER THESE SPECIFICATIONS TO ENSURE
COMPLIANCE WITH SPECIALTY FLOORING & ADHESIVE MANUFACTURER'S REQUIREMENTS.
SEQUENCE OF CONSTRUCTION:
1. REVIEW ALL DRAWINGS INCLUDING ALL NOTES TO BECOME FAMILIAR WITH SEQUENCE AND DETAILS.
2. DURING INSTALLATION SEQUENCE, REFER TO AND COMPLY WITH APPLICABLE NOTES.
3. PREPARE AREA BELOW SLAB WITH WITH COMPACTED SOIL AND GRAVEL PER PLANS.
4. BUILD FORMS FOR OUTER PERIMETER OF THE SLAB WITH DIMENSIONS PER SLAB PLAN AND SELECTED
WIDTH OF OUTER BAND AROUND FITNESS COURT AREA.
5. INSTALL REINFORCEMENT STEEL, ANCHOR BOLTS & WW MESH PER PLANS.
6. PLACE SPECIFIED CONCRETE PER PLANS (4" MINIMUM).
7. FINISH CONCRETE TO THE SLOPE SPECIFIED FOR DRAINAGE.
8. APPLY SPRAYLOCK PER MANUFACTURER'S SPECIFICATIONS WITHIN 24 HOURS OF CONCRETE POUR.
9. PROVIDE CONTRACTION JOINTS WITHIN 24 HOURS OF CONCRETE POUR.
10. INSTALLATION OF FITNESS WALL, ANCHORS, FITNESS FLOORING, AND ALL EQUIPMENT BY OTHERS.
SHEET #:
N
AT
IO
N
AL
F
IT
N
ES
S
C
AM
PA
IG
N
SA
N F
R
AN
C
IS
C O
. C A
DRAWING NAME:
Date: 2/13/25 Drawn By: DH Checked By: DH Engineer of Record:
Wells L. Holmes S.E.
OF
REV.: 9.0
FITNESS COURT
STUDIO
AutoCAD SHX Text
AutoCAD SHX Text
CONCRETE SLAB MINIMUM
SPECIFICATIONS
SPRAYLOCK
SPECIFICATIONS
SPRAY-LOCK IS DESIGNED TO IMPROVE AND PROTECT THE CONCRETE SLAB THROUGHOUT THE
CONCRETE'S LIFE DECREASING THE PERMEABILITY OF THE CONCRETE.
WATER VAPOR MOVING THROUGH A SLAB IS A PROBLEM FOR MANY ADHESIVES AND FLOORING MATERIALS.
THE USE OF THE SPRAY-LOCK PRODUCT HELPS CONDITION THE CONCRETE IN PREPARATION FOR THE INSTALLATION OF OUTDOOR FLOORING TILES. SPRAY-LOCK IS USED TO HELP MANAGE WATER IN CONCRETE
SLABS WHICH CAN HELP MINIMIZE THE RISK OF FLOOR SYSTEM FAILURES.
SPRAYLOCK IS APPLIED TO THE SURFACE OF THE CONCRETE SHORTLY AFTER FINISHING OPERATIONS ARE COMPLETED. WHEN USED AT TIME OF PLACEMENT, SPRAY-LOCK CONCRETE PROTECTION (SCP) PRODUCTS REDUCE WATER VAPOR TRANSMISSION TO THE POINT WHERE THE PERFORMANCE OF MOISTURE-SENSITIVE FLOORING, ADHESIVES, AND COATINGS ARE NOT AFFECTED AFTER FOURTEEN (14) DAYS POST-TREATMENT.
FOR ADDITIONAL INFORMATION CONTACT YOUR NFC PROJECT MANAGER.
SPRAYLOCK CAN BE PURCHASED BY CONTACTING THE NFC PRODUCT REPRESENTATIVE AT:
NATIONAL FITNESS CAMPAIGN
SPRAYLOCK@NFCHQ.COM
NOTE: ONLY SPRAY-LOCK P3 INDUSTRIAL IS APPROVED FOR THIS APPLICATION. NO EQUAL.
SPRAY-LOCK CONCRETE PROTECTION (SPC) PRODUCTS SHOULD BE KEPT FROM FREEZING DURING STORAGE AND SHOULD NOT BE APPLIED TO CONCRETE WITH TEMPERATURES LESS THAN 40° F (4.4° C).
NOTES:
CONCRETE:
1. PROVIDE 4" TO 6" OF CRUSHER RUN GRAVEL AS SHOWN IN SECTION DETAIL.
2. SOIL TO BE COMPACTED TO MEET THE REQUIREMENTS OF 95% MODIFIED PROCTOR.
3. SLAB DESIGN BASED ON SOIL CLASS D - 1500 PSF CAPACITY.
4. ALL SLAB CONCRETE TO BE 4,000 PSI AT 28 DAYS (CONCRETE STRENGTH REQUIREMENT). A HIGH
EARLY MIX MAY BE UTILIZED ONLY IF THE MIX DESIGN IS APPROVED BY THE ENGINEER.
5. CEMENT SHALL CONFORM TO ASTM C 150, TYPE II.
6. FINE AGGREGATE SHALL CONFORM TO ASTM C 33.
7. COARSE AGGREGATE SHALL BE GRAVEL OR CRUSHED STONE CONFORMING TO ASTM C 33. COARSE
AGGREGATE FOR FLOOR SLAB SHALL NOT EXCEED 3/4" AT ITS MAXIMUM WIDTH.
8. WATER SHALL BE CLEAN AND FREE FROM INJURIOUS AMOUNTS OF OILS, ACIDS, ALKALIES, ORGANIC
MATERIALS OR DELETERIOUS SUBSTANCES.
9. AIR ENTERTAINING ADMIXTURE SHALL CONFORM TO ASTM C 260.
10. CALCIUM CHLORIDE ADMIXTURES, THIOCYANATE ADMIXTURES OR ANY ADMIXTURES CONTAINING
MORE THAN 0.5% CHLORIDE IONS ARE NOT PERMITTED.
11. REINFORCING STEEL AND CONCRETE TO BE PLACED IN ACCORDANCE WITH ACI 318 LATEST EDITION.
12. THE ALLOWABLE CONCRETE SLUMP SHALL BE 5" MAX UNLESS SUPERPLASTICIZERS ARE USED. THE
ENGINEER SHALL APPROVE SUPERPLASTICIZER USE.
13. CONCRETE SHALL CONFORM TO THE FOLLOWING REQUIREMENTS
A. COMPRESSIVE STRENGTH AT AGE 28-DAYS: 4000 PSI
B. LARGE AGGREGATE: HARDROCK, 3/4" MAXIMUM SIZE CONFORMING TO ASTM C-53
C. CEMENT: ASTM C-150, TYPE II PORTLAND CEMENT
D. MAXIMUM WATER CEMENT RATIO: 0.5
E. NO ADMIXTURES EXCEPT FOR ENTRAINED AIR, AND AS APPROVED BY THE ENGINEER
14. AS REQUIRED BY OWNER, SLUMP TEST SHALL BE MADE IN ACCORDANCE WITH ASTM C 143.
15. NO CONCRETE SHALL BE PLACED WHEN THE ATMOSPHERIC TEMPERATURE IS BELOW 40° F WITHOUT
PERMISSION OF THE ENGINEER.
16. AVOID HOT WEATHER CONCRETE PLACEMENT. CONCRETE PROVIDER TO PROVIDE HOT
WEATHER CONCRETE PLACEMENT PLAN FOR CONCRETE PLACED IN TEMPERATURE IN EXCESS
OF 90 DEGREES.
17. THE ENGINEER OR THE OWNER MAY ACCEPT OR REJECT ANY WORK THAT DOES NOT MEET
THE REQUIREMENTS OF THESE NOTES OR THE PROJECT DRAWINGS.
18. IF REQUIRED BY OWNER, CONTRACTOR SHALL MAKE ARRANGEMENTS FOR TESTING THE
SLUMP, AIR CONTENT, AND CONCRETE CYLINDERS (BY A THIRD PARTY).
19. IF REQUIRED BY THE OWNER, COMPRESSIVE STRENGTH OF THE CONCRETE CYLINDERS SHALL BE TESTED AT 3 DAYS, 7 DAYS, AND 28 DAYS. APPROPRIATE NUMBER OF CYLINDERS SHALL BE
COLLECTED TO PERFORM THE TESTING. CYLINDERS SHALL BE TESTED IN ACCORDANCE WITH
ASTM C 39.
20. PROVIDE 1/2" SAWCUT CONTRACTION JOINTS PER PLANS AT 15' MAXIMUM SPACING. SAWCUT
JOINTS TO BE MADE AS SOON AS THE CONCRETE HAS CURED SUFFICIENTLY TO ALLOW THE
WORK WITHOUT DAMAGING THE CONCRETE.
21. CONFIRM ANCHOR PLACEMENT PRIOR TO CUTTING JOINTS. ENSURE 3" CLEARANCE BETWEEN
ANCHOR CENTERS AND JOINT AND CUT JOINTS AS SHOWN ON PLAN VIEW.
REINFORCEMENT:
1. SLAB REINFORCING TO BE INSTALLED AT MID-DEPTH OF THE SLAB AND SHALL EXTEND
THROUGH ENTIRE SLAB. UTILIZE SUFFICIENT NUMBER OF CHAIRS TO MAINTAIN
REINFORCEMENT POSITION.
2. INSTALL ADDITIONAL / UPGRADED REINFORCEMENT AS REQUIRED BY LOCAL CODE.
COORDINATE REBAR LOCATIONS TO AVOID ANCHORS.
3. PROVIDE VAPOR BARRIER BELOW THE SLAB. (10 MIL. MIN. W/ MIN. 12" OVERLAP AT VAPOR
BARRIER JOINTS)
PROPERTY OF NATIONAL FITNESS CAMPAIGN ©
THIS DOCUMENT IS PROPERTY OF NFC (THE NATIONAL FITNESS CAMPAIGN). THIS
DOCUMENT CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION AND MAY
ONLY BE USED BY PERMISSION FROM NFC AND FOR THE PURPOSES AUTHORIZED BY
NFC. DISCLOSURE, DUPLICATION, MODIFICATION, OR OTHER USE OF THIS
DOCUMENT IS NOT PERMITTED WITHOUT THE PRIOR WRITTEN PERMISSION OF NFC.
(FOR FLAT TOP SLAB / TILE FLOOR INSTALLATION)
CONCRETE FINISHING NOTES:
1. THE FINISHED CONCRETE SURFACE SHALL BE SLOPED AWAY FROM THE WALL. THE SURFACE
SLOPE SHALL BE 1/8" PER 12"
2. THE FINISHED CONCRETE SURFACE SHALL BE SMOOTH TO PREVENT IRREGULARITIES,
ROUGHNESS, OR OTHER DEFECTS THAT WOULD AFFECT THE FINISHED FLOOR SURFACE. THE
SURFACE SHALL BE FLAT TO THE EQUIVALENT OF 1/8" OVER 10'.
3. THE FINISHED CONCRETE SURFACE SHALL HAVE A LIGHT BROOM FINISH TO PROVIDE THE BEST
SURFACE FOR COURT SURFACE ADHESION. THIS IS CRITICAL.
4. IMPORTANT: FLOORING INSTALLATIONS REQUIRE A 28 DAY CURE TIME AFTER CONCRETE
PLACEMENT.
5. SPRAYLOCK P3 INDUSTRIAL CONCRETE SEALER IS REQUIRED (NO EQUAL). THE SPRAYLOCK
PRODUCT WILL ALLOW FLOORING INSTALLATION AS SOON AS 14 DAYS AFTER CONCRETE
PLACEMENT AND SPRAYLOCK APPLICATION. APPLY SPRAYLOCK PRODUCT THE DAY OF THE
CONCRETE PLACEMENT PER MANUFACTURER'S INSTRUCTIONS.
ANCHOR NOTES: (INSTALLATION OF FLOOR ANCHORS BY OTHERS)
GENERAL:
1. SITE PREPARATION REQUIREMENTS AND CONCRETE SLAB DESIGN SHALL BE REVIEWED BY
LOCAL CIVIL OR SOILS ENGINEER TO CONFIRM SUITABILITY BASED UPON SITE SPECIFIC NEEDS
AND CONDITIONS. THIS DESIGN REPRESENTS THE MINIMUM STANDARD OF NFC.
SHEET #:
N
AT
IO
N
AL
F
IT
N
ES
S
C
AM
PA
IG
N
SA
N F
R
AN
C
IS
C O
. C A
DRAWING NAME:
Date: 2/13/25 Drawn By: DH Checked By: DH Engineer of Record:
Wells L. Holmes S.E.
OF
REV.: 9.0
NFC STANDARD
SPECIFICATIONS
AutoCAD SHX Text
STANDARD CONSTRUCTION DETAILS
4 CONCRETE SURFACE FINISH
1 CONTRACTION JOINT 2 CONSTRUCTION/COLD JOINT 3 ISOLATION/EXPANSION JOINT
JOINTS MAY BE CUT OR SCORED (TOOLED). MAX 1/4" RADIUS WHEN
CONTRACTION JOINT IS TOOLED INSTEAD OF SAW CUT. SAW CUT
JOINTS ARE PREFERRED.
CUT CONCRETE AS SOON AS ABLE TO WALK ON CONCRETE - WITHIN 24
HOURS OF POUR.
* SAWCUT DEPTH SHOULD NOT EXCEED 25% OF SLAB DEPTH
DO NOT USE SMOOTH ROUND BAR. USE DEFORMED TIE
BAR EMBEDDED INTO BOTH SLABS.
AVOID CONSTRUCTION JOINTS WHEN POSSIBLE.
WHEN USED, PLEASE FOLLOW THE REQUIREMENTS.
CONCRETE SUBSTRATE SHOULD NOT BE SMOOTH AND REFLECTIVE; IT
MUST HAVE A CONCRETE SURFACE PROFILE OF CSP 1-3 (SIMILAR TO A
LIGHT / FINE BROOMED FINISH).
DO AVOID
LIGHT BROOM FINISH MEDIUM TO HEAVY
BROOM FINISH
PROPERTY OF NATIONAL FITNESS CAMPAIGN ©
THIS DOCUMENT IS PROPERTY OF NFC (THE NATIONAL FITNESS CAMPAIGN). THIS
DOCUMENT CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION AND MAY
ONLY BE USED BY PERMISSION FROM NFC AND FOR THE PURPOSES AUTHORIZED BY
NFC. DISCLOSURE, DUPLICATION, MODIFICATION, OR OTHER USE OF THIS
DOCUMENT IS NOT PERMITTED WITHOUT THE PRIOR WRITTEN PERMISSION OF NFC.
SAWCUT CONTRACTION JOINTS PREFERRED.
1" *
4"
1/8" - 3/8" TYP.
CONFIRM THAT FINISH
SURFACES ARE LEVEL AND
SMOOTH TO AVOID TRIPPING
HAZARD. GRIND SMOOTH IF
REQUIRED.
TOOLED EDGE OR
ADD FILLET TO
FORM
#4 BAR
(36" MIN. LENGTH AT
12" O.C.)
18"
2"
4"
18"
2"
NFC RECOMMENDS NOT USING ANY ISOLATION JOINTS
ANYWHERE IN THE CONCRETE SLAB.
DO NOT USE ISOLATION JOINTS UNDER FITNESS WALL
OR TILE WITHOUT WRITTEN APPROVAL OF NFC.
WHEN APPROVED:
USE SMOOTH DOWEL JOINT ON ONE END OR SIMILAR TO ALLOW
FOR EXPANSION AND PROTECT FROM DIFFERENTIAL
SETTLEMENT.
THE EXPANSION AND CONTRACTION OF THE CONCRETE WILL CAUSE
THE TILE ADHESIVE TO FAIL OR THE TILE TO BUCKLE OR SPLIT.
NFC REQUIRES A COORDINATE EFFORT TO DESIGN EXPANSION
JOINTS INTO THE CONCRETE SLAB TO AVOID FAILURE OF THE TILE
OR OTHER STRUCTURAL ELEMENTS. CONTACT YOUR NFC PM TO
COORDINATE DESIGN.
4"
1" MAX.
SHEET #:
N
AT
IO
N
AL
F
IT
N
ES
S
C
AM
PA
IG
N
SA
N F
R
AN
C
IS
C O
. C A
DRAWING NAME:
Date: 2/13/25 Drawn By: DH Checked By: DH Engineer of Record:
Wells L. Holmes S.E.
OF
REV.: 9.0
STANDARD
DETAILS
AutoCAD SHX Text
SHT 3
A
1% SLOPE
PERPENDICULAR
TO FACE OF WALL
FI
TN
ES
S
W
AL
L
- S
EE
N
O
TE
S
33'-0"
TILE FLOOR (BY OTHERS)
STUDIO FLOOR SIDE 2'-21
2"2'-21
2"
2' -0
'-0
TI
LE
F
LO
O R
(B Y
O
TH
ER
S)
2' -0
73'-0"
MINIMUM CONCRETE SLAB LENGTH
'-0
M
IN
IM
U M
C O
N C
R
ET
E
SL
AB
W
ID
TH
33'-0"
TILE FLOOR (BY OTHERS)
EQUIPMENT SIDE
14'-7 3 16"
CONTRACTION JOINT
SPACING 14'-7 3
16" 14'-7 3 16" 14'-7 3
16" 14'-7 3 16"
'-8
'-8
'-8
C
O N
TR
AC
TI
O
N J
O
IN
T
SP
AC
IN
G
CONCRETE SLAB PLAN
(FOR FLAT TOP SLAB / TILE FLOOR INSTALLATION)
PROPERTY OF NATIONAL FITNESS CAMPAIGN ©
THIS DOCUMENT IS PROPERTY OF NFC (THE NATIONAL FITNESS CAMPAIGN). THIS
DOCUMENT CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION AND MAY
ONLY BE USED BY PERMISSION FROM NFC AND FOR THE PURPOSES AUTHORIZED BY
NFC. DISCLOSURE, DUPLICATION, MODIFICATION, OR OTHER USE OF THIS
DOCUMENT IS NOT PERMITTED WITHOUT THE PRIOR WRITTEN PERMISSION OF NFC.
FITNESS COURT SPECIALTY TILE
EXERCISE FLOOR AREA (BY OTHERS).
CONCRETE FINISH FOR SPECIALTY FLOORING:
THE FINISHED CONCRETE SURFACE SHOULD BE A LIGHT
BROOM FINISH AND SHOULD PREVENT IRREGULARITIES,
ROUGHNESS, OR OTHER DEFECTS THAT WOULD AFFECT
THE FINISHED FLOOR SURFACE. THE SURFACE
SHOULD BE FLAT TO THE EQUIVALENT OF 1/8"
OVER 10'. THE FINISHED CONCRETE SURFACE
SHOULD HAVE A LIGHT BROOM FINISH TO
PROVIDE THE BEST SURFACE FOR COURT
SURFACE ADHESION.
NOTES:
1. FITNESS WALL (BY OTHERS) (2'-7" WIDE).
2. CONTRACTOR TO VERIFY WALL LOCATION
TO ENSURE CORRECT ORIENTATION OF
THE SLOPE OF THE SLAB AND THE
LOCATION OF REBAR REINFORCEMENT
UNDER THE WALL.
3. THE FITNESS WALL IS INSTALLED LEVEL.
ANY ADDITIONAL SLOPE IN THE CONCRETE
PAD PARALLEL TO THE WALL WILL LEAD TO
A GAP BETWEEN THE BOTTOM OF THE
WALL AND THE TOP OF THE CONCRETE.
4. THERE SHALL BE NO COLD JOINTS OR
ISOLATION JOINTS WITHIN THE 10' AREA IN
FRONT OF THE WALL. SEE ADDITIONAL
REQUIREMENTS IF SHADE STRUCTURE IS
INCLUDED.
12" BORDER RAMP TILE (BY OTHERS)
2'-7"
4"
SLOPE ENTIRE SLAB FROM FROM EDGE TO EDGE
PERPENDICULAR TO FACE OF WALL- 1%
WALL BY
OTHERS
SECTION A - A
(ROTATED)
POB (POINT OF
BEGINNING)
10'-0"
SEE NOTE 4
37'-91
2" SLOPE FROM BACK OF WALL TO
EDGE OF EQUIPMENT SIDE SLAB
35'-21
2" SLOPE FROM BACK OF WALL TO
EDGE OF STUDIO SIDE SLAB
2'-7"
DEPTH
OF WALL
CONSTRUCTION JOINT ALLOWED
BEHIND WALL IF NEEDED PER
DETAIL 2 ON SHT. 3.
SHEET #:
N
AT
IO
N
AL
F
IT
N
ES
S
C
AM
PA
IG
N
SA
N F
R
AN
C
IS
C O
. C A
DRAWING NAME:
Date: 2/13/25 Drawn By: DH Checked By: DH Engineer of Record:
Wells L. Holmes S.E.
OF
REV.: 9.0
FITNESS COURT
STUDIO LAYOUT
AutoCAD SHX Text 37'-9 "12"
AutoCAD SHX Text 35'-2 "12"
AutoCAD SHX Text
1. 1" FITNESS TILE (BY OTHERS)
2. TILE ADHESIVE (BY OTHERS)
3. SPRAYLOCK APPLICATION
4. 4" MIN CONCRETE SLAB
5. NOT USED
6. WELDED WIRE MESH REINFORCEMENT
6x6 W2.9/W2.9
7. VAPOR BARRIER (10 MIL. MIN.)
-REF. ACI302-1R.15
8. 4" TO 6" GRAVEL
9. COMPACTED SOIL
NOTE: WALL
NOT SHOWN
FOR CLARITY.
REINFORCEMENT / PREP DETAIL
(FOR FLAT TOP SLAB / TILE FLOOR INSTALLATION)
PROPERTY OF NATIONAL FITNESS CAMPAIGN ©
THIS DOCUMENT IS PROPERTY OF NFC (THE NATIONAL FITNESS CAMPAIGN). THIS
DOCUMENT CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION AND MAY
ONLY BE USED BY PERMISSION FROM NFC AND FOR THE PURPOSES AUTHORIZED BY
NFC. DISCLOSURE, DUPLICATION, MODIFICATION, OR OTHER USE OF THIS
DOCUMENT IS NOT PERMITTED WITHOUT THE PRIOR WRITTEN PERMISSION OF NFC.
38'-0" NOM
2" MIN SPACING BETWEEN
REINFORCEMENT
AND EDGE OF CONCRETE (ALL SIDES)
REINFORCING TO BE PLACED AT MID-DEPTH OF THE SLAB AND SHALL
EXTEND THROUGH ENTIRE SLAB UNLESS NOTED OTHERWISE. UTILIZE
SUFFICIENT NUMBER OF CHAIRS TO MAINTAIN REINFORCEMENT POSITION.
INSTALL ADDITIONAL REINFORCEMENT AS REQUIRED BY LOCAL CODE.
TYP. SECTION DETAIL
2" MIN.
OUTLINE OF WALL
(BY OTHERS)
SHEET #:
N
AT
IO
N
AL
F
IT
N
ES
S
C
AM
PA
IG
N
SA
N F
R
AN
C
IS
C O
. C A
DRAWING NAME:
Date: 2/13/25 Drawn By: DH Checked By: DH Engineer of Record:
Wells L. Holmes S.E.
OF
REV.: 9.0
REINFORCEMENT
LAYOUT
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ANCHOR DETAILS FOR TILE
APPLIES TO THE TILE INSTALLATION ONLY.
REQUEST ALTERNATE DRAWING FOR POUR-IN-PLACE.
(ALSO SEE ANCHOR NOTES ON SLAB NOTES DRAWING)
PROPERTY OF NATIONAL FITNESS CAMPAIGN ©
THIS DOCUMENT IS PROPERTY OF NFC (THE NATIONAL FITNESS CAMPAIGN). THIS
DOCUMENT CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION AND MAY
ONLY BE USED BY PERMISSION FROM NFC AND FOR THE PURPOSES AUTHORIZED BY
NFC. DISCLOSURE, DUPLICATION, MODIFICATION, OR OTHER USE OF THIS
DOCUMENT IS NOT PERMITTED WITHOUT THE PRIOR WRITTEN PERMISSION OF NFC.
NOTE: ANCHORS INSTALLED BY OTHERS
SEE NFC FITNESS COURT INSTALLATION
MANUAL FOR ADDITIONAL ANCHOR
SPECIFICATIONS AS NEEDED
ANCHOR HOLE INSTRUCTIONS FOR MECHANICAL ANCHOR
1. DRILL HOLES FOR ANCHORS TO SPECIFIED
DIAMETER AND DEPTH.
2. USE COMPRESSED AIR TO REMOVE CONCRETE
DUST AND DEBRIS FROM HOLES PRIOR TO ANCHOR
INSTALLATION.
3. REFER TO FITNESS COURT INSTALLATION
INSTRUCTIONS FOR ADDITIONAL ANCHOR
INSTALLATION STEPS.
ANCHOR A EPOXY NOTE:
ANCHOR A MUST BE INSTALLED WITH THE ANCHOR
EPOXY SPECIFIED OR ACCEPTABLE ALTERNATIVE.
FOLLOW EPOXY MANUFACTURER'S INSTALLATION
PROCEDURES.
2 3/4"
1-1/4"
MIN
1-5/8"
MAX
±12"
TOP OF
CONCRETE
WALL
FRAME BY
OTHERS
SEE BELOW FOR
INSTALLATION
INSTRUCTIONS
5/8" HEAVY HEX NUT,
HDG STEEL - QTY:2
1/4" THICK x 2" ROUND
OR SQ PLATE WASHER,
HDG STEEL - QTY:2
Ø5/8" x 12" LONG ALL THREADED
ROD - ASTM A307 GR. A.
INSTALL WITH SIMPSON AT-3G
ANCHOR EPOXY, SIMPSON
SET-3G , OR HILTI HIT-HY 200 V3
OR APPROVED EQUAL.
ANCHOR DESIGN BASED ON
MINIMUM 6" EDGE DISTANCE
ANCHOR A - WALL ANCHOR
INSTALL ANCHOR IN
3/4" DRILLED HOLE.
DRILL AND PREPARE
HOLE PER MFR
RECOMMENDATIONS
1" TILE
1-5/8"
MIN
STEEL EQUIPMENT
BASE PLATE
3/8" FLAT WASHER
(18-8 SS) ON TOP OF
EQUIPMENT PLATE
REDHEAD MULTI-SET II RL-38
S.S. DROP IN ANCHOR INSERT
AND SET ANCHOR PER MFR
RECOMMENDATIONS OR
APPROVED EQUAL
BOTT, SURFACE OF
TILE FLOOR AND TOP
OF CONCRETE
INSTALL ANCHOR IN Ø1/2"
DRILLED HOLE. DRILL AND
PREPARE HOLE PER MFR
RECOMMENDATIONS
CONC. SLAB PER
SHEET 4 & 5
ANCHOR B
DROP-IN ANCHOR
3/8" LOCK WASHER
(18-8-SS) ON TOP OF
FLAT WASHER
1"
TILE
1-3/4"
MIN
5"
MIN
STEEL EQUIPMENT
BASE PLATE
3/8" FLAT WASHER
(18-8 SS) ON TOP OF
EQUIPMENT PLATE
BOTT, SURFACE OF
TILE FLOOR AND TOP
ON CONCRETE
CONC. SLAB PER
SHEET 4 & 5
INSTALL ANCHOR IN Ø3/8"
DRILLED HOLE. DRILL AND
PREPARE HOLE PER MFR
RECOMMENDATIONS
REDHEAD TRUBOLT WEDGE
ANCHOR, PART #: WW-3850.
INSERT AND SET ANCHOR PER
MFR RECOMMENDATIONS OR
APPROVED EQUAL
ANCHOR C
WEDGE ANCHOR
MIN 2-1/2"
HOLE DEPTH
SHEET #:
N
AT
IO
N
AL
F
IT
N
ES
S
C
AM
PA
IG
N
SA
N F
R
AN
C
IS
C O
. C A
DRAWING NAME:
Date: 2/13/25 Drawn By: DH Checked By: DH Engineer of Record:
Wells L. Holmes S.E.
OF
REV.: 9.0
ANCHOR
DETAILS
AutoCAD SHX Text
PLYO BOX 5 AND 6
2 ANCHORS PER BOX IN
OPPOSITE CORNERS UPPER LEFT
AND LOWER RIGHT PER CENTER
MARKS.
PLYO BOX 1 AND 2
4 ANCHORS PER BOX IN OUTSIDE
CORNERS PER CENTER MARKS.
PLYO BOX 3 AND 4
6 ANCHORS PER BOX IN ALL
TEMPLATE HOLES PER CENTER
MARKS.
IMPORTANT NOTE:
DIMENSIONS APPLY TO CUSHION FLOORS
ONLY. FOR TILE FLOORS, PUSH STATION
ANCHORS ARE TO BE LOCATED AFTER
WALL PLACEMENT AND PUSH STATIONS
ARE IN FINAL LOCATION.
'-6
/2
'-6
/2
'-1
1/
4"
'-1
1/
4"
'-6
/4
'-8
'-9
/4
'-2
/2
'-7
"3 1/
4"
4'-1/8"
9'-8 3/4"
17'-3/4"
24'-4 3/4"
13'-4"
20'-8"
25'-7 1/4" 25'-9 1/4"
17'-4 1/2"
7' -8
/2
9'-4 1/2"
25'-4 1/2" 8'
-8
/2
4'-6 9/16"
3' -5
5/
'-3
/1
6"
2'-2" UP
FROM POB
5" UP
FROM POB
PROPERTY OF NATIONAL FITNESS CAMPAIGN ©
THIS DOCUMENT IS PROPERTY OF NFC (THE NATIONAL FITNESS CAMPAIGN). THIS
DOCUMENT CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION AND MAY
ONLY BE USED BY PERMISSION FROM NFC AND FOR THE PURPOSES AUTHORIZED BY
NFC. DISCLOSURE, DUPLICATION, MODIFICATION, OR OTHER USE OF THIS
DOCUMENT IS NOT PERMITTED WITHOUT THE PRIOR WRITTEN PERMISSION OF NFC.
** THESE DIMENSIONS MEASURED TO THE RIGHT FROM POB **
T
H
ES
E D
IM
EN
SI
O
N S
M
EA
SU
R
ED
D
O W
N F
R O
M P
O B
(A W
A Y
FR
O
M W
A
LL
ANCHOR LOCATIONS
NOTE: ANCHORS INSTALLED BY OTHERS
IMPORTANT NOTE:
ALL DIMENSIONS ORIGINATE FROM
UPPER LEFT CORNER OF FITNESS
COURT AREA POB (POINT OF
BEGINNING).
LOCATION OF UPPER LEFT
ANCHORS SHOWN FOR EACH
PIECE OF EQUIPMENT. LOCATE
UPPER LEFT HOLE AND USE
TEMPLATES TO LOCATE REMAINING
HOLES.
WALL ANCHORS
(ANCHOR A)
COUPLING ANCHORS
(ANCHOR B)
ANCHOR C TO BE INSTALLED
IN ALL LOCATIONS UNLESS
NOTED OTHERWISE.
12' ADA BORDER TILE
COUPLING ANCHORS
(ANCHOR B)
2 CUTS EACH WAY
CONTRACTION CUTS (SAWCUTS) IN LOCATIONS
TO AVOID ANCHOR PLACEMENT.
SEE LAYOUT PLAN FOR RECOMMENDED DIMENSIONS
SHEET #:
N
AT
IO
N
AL
F
IT
N
ES
S
C
AM
PA
IG
N
SA
N F
R
AN
C
IS
C O
. C A
DRAWING NAME:
Date: 2/13/25 Drawn By: DH Checked By: DH Engineer of Record:
Wells L. Holmes S.E.
OF
REV.: 9.0
ANCHOR
LOCATIONS
AutoCAD SHX Text
DO's & DON'Ts
CONTRACTION JOINT LOCATIONS
PLASTIC SHRINKING CRACKING
WHEN APPROVED, DO NOT LET EXPANSION JOINTS RUN UNDER
EQUIPMENT OR THE FITNESS WALL.
NO CRAZING
DO NOT USE OLD TENNIS COURTS FOR A FITNESS COURT FOUNDATION.
COORDINATE AND CONSULT WITH YOUR NFC PROJECT MANAGER TO
VALIDATE ANY EXISTING CONCRETE SLABS FOR USE UNDER A FITNESS
COURT.
AVOID PUTTING CONTRACTION JOINTS IN SLAB WITHOUT NFC APPROVAL.
NEVER PLACE TILE ACROSS EXPANSION JOINTS.
CRAZING IS MOST OFTEN CAUSED BY A HIGHER WATER TO CEMENT RATIO
AT THE SURFACE OF THE CONCRETE AS A RESULT OF OVER-TROWELING,
SPRINKLING WATER ON THE SURFACE OF THE CONCRETE DURING
FINISHING OPERATIONS, OR FINISHING CONCRETE WHILE BLEED WATER IS
STILL PRESENT.
AVOID PLACING CONCRETE DURING ADVERSE WEATHER CONDITIONS
THAT WILL LEAD TO PLASTIC SHRINKAGE CRACKS. PLASTIC SHRINKAGE
CRACKS CAN OCCUR WHEN WEATHER CONDITIONS CAUSE RAPID
EVAPORATION OF BLEED WATER BEFORE IT CAN BE REPLACED
NATURALLY BY SUBSURFACE CONCRETE. LOW RELATIVE HUMIDITY, HIGH
WINDS, AND HIGH CONCRETE TEMPERATURE CAN ALL CONTRIBUTE TO
PLASTIC SHRINKAGE CRACKING.
CONTRACTION JOINT PLACEMENT
REUSE OF EXISTING FOUNDATIONS
PROPERTY OF NATIONAL FITNESS CAMPAIGN ©
THIS DOCUMENT IS PROPERTY OF NFC (THE NATIONAL FITNESS CAMPAIGN). THIS
DOCUMENT CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION AND MAY
ONLY BE USED BY PERMISSION FROM NFC AND FOR THE PURPOSES AUTHORIZED BY
NFC. DISCLOSURE, DUPLICATION, MODIFICATION, OR OTHER USE OF THIS
DOCUMENT IS NOT PERMITTED WITHOUT THE PRIOR WRITTEN PERMISSION OF NFC.
EXPANSION
JOINT
PLYO
BOX
SHEET #:
N
AT
IO
N
AL
F
IT
N
ES
S
C
AM
PA
IG
N
SA
N F
R
AN
C
IS
C O
. C A
DRAWING NAME:
Date: 2/13/25 Drawn By: DH Checked By: DH Engineer of Record:
Wells L. Holmes S.E.
OF
REV.: 9.0
DOS & DON'TS
AutoCAD SHX Text
| Sheets and Views |
| NFC Fitness Court Studio Concrete Slab Drawing C -9.0 R2025-FITNESS COURT COVER |
| NFC Fitness Court Studio Concrete Slab Drawing C -9.0 R2025-SPECIFICATIONS |
| NFC Fitness Court Studio Concrete Slab Drawing C -9.0 R2025-3- Standard Details |
| NFC Fitness Court Studio Concrete Slab Drawing C -9.0 R2025-FCS B 4- Concrete Slab Layout |
| NFC Fitness Court Studio Concrete Slab Drawing C -9.0 R2025-5- Site Prep Layout |
| NFC Fitness Court Studio Concrete Slab Drawing C -9.0 R2025-6- Anchor Details |
| NFC Fitness Court Studio Concrete Slab Drawing C -9.0 R2025-7-AB Layout Plan |
| NFC Fitness Court Studio Concrete Slab Drawing C -9.0 R2025-8- Dos & Don'ts |
File details come from the government source that posted it. Updated .