NewsomeParkES_Drawings_FINAL_1-12-24.pdf
PDF 25 MB Posted
- Solicitation number
- 58707
- Issued by
- Newport News City, Virginia
About this file
The document provided is a set of drawings titled "NewsomeParkES_Drawings_FINAL_1-12-24.pdf" related to the "Newsome Park Elementary School Security Vestibule & Office Alterations" project in Newport News, Virginia. This project consists of constructing a 250 S.F. vestibule enclosure at the main entrance of the existing Newsome Park Elementary School, as well as interior alterations to the adjacent main entrance, lobby, corridor, and administrative offices.
The project is being managed by the Newport News City jurisdiction. No additional details are provided regarding pricing terms, set-asides, incumbents, funding requirements and sources, or the contract term and renewal options.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RICHARD S. CORNER
Lic. No. 007014
NEWSOME PARK ELEMENTARY SCHOOL
SECURITY VESTIBULE & OFFICE ALTERATIONS
NEWSOME PARK
ELEMENTARY SCHOOL
SECURITY VESTIBULE &
OFFICE ALTERATIONS
I.F.B. NO. 012-0-2024/SNB
RICHARD S. CORNER
Lic. No. 007014
NEWSOME PARK
ELEMENTARY SCHOOL
SECURITY VESTIBULE &
STRUCTURAL ABBREVIATIONS
A.B. ANCHOR BOLT
A.C.I. AMERICAN CONCRETE
INSTITUTE
ADJ. ADJACENT
A.I.S.C. AMERICAN INSTITUTE OF
STEEL CONSTRUCTION
A.S.D. ALLOWABLE STRESS
DESIGN
A.S.T.M. AMERICAN SOCIETY FOR
TESTING AND MATERIALS
ARCH. ARCHITECT OR
ARCHITECTURAL
B.D. BAR DIAMETER(S)
B.E.J. BUILDING EXPANSION JOINT
BLDG. BUILDING
B.O.S. BOTTOM OF STEEL
BM. BEAM
BRCG. BRACING
BRDG. BRIDGING
BRG. BEARING
BTWN. BETWEEN
CANT. CANTILEVER
C.G. CENTER OF GRAVITY
C.I.P. CAST IN PLACE
CL. CLEAR
CMU CONCRETE MASONRY
UNIT
COL. COLUMN
CONC. CONCRETE
CONT. CONTINUOUS
COORD. COORDINATE
D. DEPTH OR DEEP
DBL. DOUBLE
DET. DETAIL
DIA. DIAMETER
DIAG. DIAGONAL
DWG. DRAWING
DWL. DOWEL
EA. EACH
E.F. EACH FACE
E.W. EACH WAY
EL. ELEVATION
ELEV. ELEVATION
EMB. EMBEDMENT OR EMBED
ENG. ENGINEER
EQ. EQUAL
EXIST. EXISTING
EXP. EXPANSION
FDN. FOUNDATION
FIN. FINISHED OR FINISH
FLR. FLOOR
F.O. FACE OF
FTG. FOOTING
GA. GAGE
GALV. GALVANIZED
G.C. GENERAL CONTRACTOR
H.C. HOLLOW CORE
H.D.G. HOT DIPPED GALVANIZED
HK. HOOK
HORIZ. HORIZONTAL
H.S. HIGH STRENGTH
J.B.E. JOIST BEARING
ELEVATION
JT. JOINT
K KIPS
K.S.F. KIPS PER SQUARE FOOT
K.S.I. KIPS PER SQUARE INCH
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
L.R.F.D. LOAD & RESISTANCE
FACTOR DESIGN
MANUF. MANUFACTURER OR
MANUFACTURER'S
MATL. MATERIAL
MAX. MAXIMUM
MECH. MECHANICAL
MIN. MINIMUM
M.O.S. MIDDLE OF SLAB
M.O.W. MIDDLE OF WALL
MTL. METAL
N.T.S. NOT TO SCALE
O/C ON CENTER
OPP. OPPOSITE
O.H. OPPOSITE HAND
P.A.F. POWDER ACTUATED
FASTENER
P.C. PRECAST
P.S. PRESTRESSED
P.S.F. POUNDS PER SQUARE
FOOT
P.S.I. POUNDS PER SQUARE
INCH
Pc. PIECE
PROJ. PROJECTION
P.T. PRESSURE TREATED
R. RADIUS
REF. REFERENCE
REINF. REINFORCING OR
REINFORCED
REQ'D. REQUIRED
REV. REVISION
S.O.G. SLAB ON GRADE
S.F. STEPPED FOOTING
SCHED. SCHEDULE
SECT. SECTION
SHT. SHEET
SIM. SIMILAR
SL. SLOPE
SPA. SPACE
S.S. STAINLESS STEEL
STD. STANDARD
STIFF. STIFFENER
STIR. STIRRUPS
STL. STEEL
STRUCT. STRUCTURAL
T.O.S. TOP OF STEEL
TEMP. TEMPERATURE
TYP. TYPICAL
T.S. THICKENED SLAB
U.O.N. UNLESS OTHERWISE
NOTED
O.W.T. OPEN WEB TRUSS
VERT. VERTICAL
W. WIDTH OR WIDE
w/ WITH
W.P. WORKING POINT
W.W.F. WELDED WIRE FABRIC
C CENTERLINE
ø DIAMETER
° DEGREES
± PLUS/MINUS
P PLATE
L
L
BEAM SPLICE
WELD
X
SX.X SECTION
X
SX.X PLAN DETAIL
SPOT ELEVATION
SHEARWALL MARK (ABOVE)
HD (A)
BEARING PLATEBP
SHEARWALL HOLDOWN (ABOVE)
WXxXX STEEL BEAM MARK x
REVISION MARK
STRUCTURAL SYMBOL LEGEND
A PLAN NOTE
STRUCTURAL COLUMN
CFX.X COLUMN FOOTING MARK
WFX.X WALL FOOTING MARK
SLAB STEP LOCATION
-X'-X"
FOOTING ELEVATION
INDICATOR PILE
MOMENT CONNECTION
XXk BEAM REACTION
SLAB SLOPE LOCATION
X COLUMN GRID MARK
GB-X GRADE BEAM MARK
P-X PILE CAP MARK
L-X MASONRY LINTEL MARK
H-X HEADER MARK
CBXXxXX CONCRETE BEAM MARK
SHEARWALL MARK (BELOW)
SW-X (A)
SW-X (B)
SHEARWALL HOLDOWN (BELOW)HD (B)
ELEVATIONSX.XX
SHEARWALL EXTENTS
GENERAL FRAMING NOTES
1. THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL PLANS,
SECTIONS AND DETAILS TO SET ALL STRUCTURAL WORK INCLUDING
LOCATION OF ALL STUD BEARING WALLS, STRUCTURAL BEAMS, SUPPORT
POSTS, ETC. WHERE DISCREPANCIES OCCUR BETWEEN THE
ARCHITECTURAL AND STRUCTURAL DRAWINGS, THE ARCHITECTURAL
DRAWINGS SHALL GOVERN.
2. THE CONTRACTOR SHALL ENSURE THAT ALL STRUCTURAL BEAMS,
SUPPORT POSTS, AND STUD BEARING WALLS HAVE ADEQUATE WOOD
BLOCKING AS REQUIRED TO TRANSFER THE LOADS TO THE FOUNDATION
WORK BELOW.
3. THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY SHORING OR
BRACING AS REQUIRED TO HOLD THE STRUCTURAL WORK IN PROPER
ALIGNMENT UNTIL ALL FRAMING AND/OR SHEATHING IS NAILED IN PLACE.
GENERAL NOTES
1. UNDER NO CIRCUMSTANCES SHALL THE CONTRACT DRAWINGS BE
REPRODUCED AND USED AS SHOP DRAWINGS.
2. THE CONTRACTOR SHALL SUBMIT PAPER HARD-COPY SHOP
DRAWINGS TO THE ARCHITECT IN SUITABLE QUANTITIES TO PERMIT
ADEQUATE DISTRIBUTION FOR REVIEW.
3. THE CONTRACTOR SHALL COORDINATE AND VERIFY ALL DIMENSIONS
PRIOR TO STARTING CONSTRUCTION. ANY DISCREPANCIES SHALL BE
BROUGHT TO THE ATTENTION OF THE ARCHITECT.
4. THE STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH
THE ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS. THE
CONTRACTOR SHALL VERIFY THE REQUIREMENTS OF OTHER TRADES AS TO
SLEEVES, CHASES, HANGERS, INSERTS, ANCHORS, HOLES, ETC., TO SET THE
STRUCTURAL WORK.
5. BACK CHARGES FOR CHANGE ORDERS, CORRECTIVE WORK OR
REPLACED MATERIALS WILL NOT BE ACCEPTED UNLESS EXPRESSLY
AUTHORIZED IN WRITING BY SINCLAIR PRATT CAMERON, P.C. BEFORE ANY
SUCH COSTS ARE INCURRED.
6. THE GENERAL CONTRACTOR SHALL CALL A PRECONSTRUCTION
MEETING WITH ALL NECESSARY PARTIES PRIOR TO CONSTRUCTION. THIS
MEETING SHALL ADDRESS THE RESPONSIBILITIES AND THE SCHEDULING OF
ALL PARTICIPANTS INVOLVED IN INSPECTION SERVICES; INCLUDING THE
"SCHEDULE OF SPECIAL INSPECTIONS," IF REQUIRED. THE GOVERNING
MUNICIPALITY SHOULD BE INVITED TO JOIN THIS MEETING TO ESTABLISH
THEIR REQUIREMENTS.
7. THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL PLANS,
SECTIONS AND DETAILS TO SET ALL STRUCTURAL WORK INCLUDING
LOCATION OF ALL STUD BEARING WALLS, STRUCTURAL BEAMS, SUPPORT
POSTS, ETC. WHERE DISCREPANCIES OCCUR BETWEEN THE
ARCHITECTURAL AND STRUCTURAL DRAWINGS, BOTH THE ARCHITECT AND
ENGINEER OF RECORD SHALL BE CONTACTED FOR DIRECTION.
8. THE CONTRACTOR SHALL ENSURE THAT ALL STRUCTURAL BEAMS,
SUPPORT POSTS, AND STUD BEARING WALLS HAVE ADEQUATE WOOD
BLOCKING AS REQUIRED TO TRANSFER THE LOADS TO THE FOUNDATION
WORK BELOW.
9. THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY SHORING OR
BRACING AS REQUIRED TO HOLD THE STRUCTURAL WORK IN PROPER
ALIGNMENT UNTIL ALL FRAMING AND/OR SHEATHING IS NAILED IN PLACE.
DESIGN CRITERIA
1. THE STRUCTURAL DESIGN IS IN ACCORDANCE WITH THE 2018 VIRGINIA
CONSTRUCTION CODE.
2. DESIGN LOADS ARE AS FOLLOWS:
LIVE LOADS (PER IBC):
ROOF LIVE LOAD 20 PSF
DEAD LOADS (PER IBC):
ROOF DEAD LOAD 20 PSF
CONCRETE SLABS ON GRADE (PER ACI):
4" THICK SLAB ON GRADE 100 PSF
SNOW LOADS (PER ASCE):
GROUND SNOW LOAD (PG) 10 PSF
FLAT ROOF SNOW LOAD (Pf) 6.9 PSF MINIMUM SNOW LOAD (Pmin) 11 PSF SNOW EXPOSURE FACTOR (Ce) 0.90
SNOW LOAD IMPORTANCE FACTOR (I) 1.10
ROOF THERMAL FACTOR (Ct) 1.00
WIND LOADS (PER ASCE):
NORMAL DESIGN WIND SPEED (Vasd) 98 MPH ULTIMATE DESIGN WIND SPEED (Vult) 126 MPH
WIND EXPOSURE B
RISK CATEGORY III
INTERNAL PRESSURE COEFFICIENT (GCpi) ±0.18
BUILDING DESIGNED TO BE FULLY ENCLOSED
REINFORCED MASONRY NOTES
1. ALL MASONRY AND GROUTING PROCEDURES SHALL BE IN
COMPLIANCE WITH THE LATEST EDITION OF THE BUILDING CODE FOR
MASONRY STRUCTURES, A.C.I. 530.
2. ALL BLOCK MASONRY WALLS SHALL BE LAID WITH TYPE 'S' HIGH
STRENGTH MORTAR (1800 PSI) BOUGHT PRE-MIXED BY THE BAG OR MIXED
TO THE FOLLOWING PROPORTIONS:
1 BAG MASONRY CEMENT
1/2 BAG PORTLAND CEMENT
4 1/2 CUBIC FEET OF SAND BY VOLUME
3. ALL HOLLOW CMU BLOCK MASONRY SHALL BE GRADE 'N' LOAD
BEARING UNITS IN ACCORDANCE WITH ASTM C-90 SPECIFICATIONS
(MINIMUM ULTIMATE NET CONCRETE STRENGTH = 2000 PSI).
4. ALL GROUT FOR VERTICAL REINFORCING AND BOND BEAMS SHALL BE
2,000 PSI FINE GROUT, 8" - 10" SLUMP.
5. ALL HORIZONTAL JOINT REINFORCING SHALL BE LADDER TYPE. SEE
ARCHITECTURAL DRAWINGS FOR SIZE AND SPACING.
6. THE CONTRACTOR SHALL SUBMIT HIS COLD WEATHER MASONRY
PROCEDURES FOR APPROVAL IF THE AMBIENT TEMPERATURES ARE
BELOW 40 DEGREES FAHRENHEIT.
7. ALL VERTICAL REINFORCING STEEL SHALL LAP 48 BAR DIAMETERS
UNLESS OTHERWISE NOTED ON PLANS, SECTIONS OR DETAILS.
LOW LIFT GROUTING
8. ALL REINFORCED HOLLOW UNIT MASONRY SHALL BE BUILT TO
PRESERVE THE UNOBSTRUCTED VERTICAL CONTINUITY OF THE CELLS TO
BE FILLED. WALLS AND CROSS WEBS FORMING SUCH CELLS TO BE FILLED
SHALL BE FULL-BEDDED IN MORTAR TO PREVENT LEAKAGE OF GROUT. ALL
HEAD (OR END) JOINTS SHALL BE SOLIDLY FILLED WITH MORTAR FOR A
DISTANCE IN FROM THE FACE OF THE WALL OR UNIT NOT LESS THAN THE
THICKNESS OF THE LONGITUDINAL FACE SHELLS. BOND SHALL BE
PROVIDED BY LAPPING UNITS IN SUCCESSIVE VERTICAL COURSES OR BY
EQUIVALENT MECHANICAL ANCHORAGE.
9. VERTICAL CELLS TO BE FILLED SHALL HAVE VERTICAL ALIGNMENT
SUFFICIENT TO MAINTAIN A CLEAR, UNOBSTRUCTED CONTINUOUS
VERTICAL CELL MEASURING NOT LESS THAN 2 INCHES BY 3 INCHES. NO
MORTAR PROJECTIONS INTO THE CELL MAY EXCEED 1/4".
10. ALL CELLS CONTAINING REINFORCEMENT SHALL BE FILLED SOLIDLY
WITH GROUT. GROUT SHALL BE PLACED IN LIFTS OF 5 FEET MAXIMUM
HEIGHT. ALL GROUT SHALL BE CONSOLIDATED APPROXIMATELY 5 TO 10
MINUTES AFTER POURING; BY VIBRATING AND BEFORE PLASTICITY IS LOST.
WHEN THE GROUTING IS STOPPED FOR ONE HOUR OR LONGER,
HORIZONTAL CONSTRUCTION JOINTS SHALL BE FORMED BY STOPPING THE
POUR OF GROUT NOT LESS THAN 1/2 INCH BELOW THE TOP OF THE UPPER-
MOST UNIT GROUTED. HORIZONTAL STEEL SHALL BE FULLY EMBEDDED BY
GROUT IN AN UNINTERRUPTED POUR.
© 2022 Sinclair Pratt Cameron, P.C.
J O B N U M B E R
1/22/2024 5:15:02 PM
S0.1
JANUARY 12, 2024
GENERAL NOTES
4200 MARSHALL AVE
NEWPORT NEWS VA 23607
NEWSOME PARK
ELEMENTARY SCHOOL
SECURITY VESTIBULE
757.417.0565 * 757.417.0568 (fax)
VIRGINIA BEACH, VA 23451-6188
1630 DONNA DRIVE - SUITE 105
SINCLAIR PRATT CAMERON, P.C.
WWW.SPC-ENG.COM
Designed: BIM:
23-0580
SBQKLR
A I
N I
G
RI
V
FOHTLAE
W
N O
M M
O C
P R
O F
ESS IONAL EN
G
IN
E
E R
Lic. No. 47291
KEVIN L. RAINEY
12 JANUARY 2024
NEWSOME PARK
ELEMENTARY SCHOOL
E X
IS
T
IN
G
J O
IS
T
S
E X
IS
T
IN
G
J O
IS
T
S
EXISTING JOISTS
EXISTING JOISTS
A
S1.0
S1.0
L-5 L-5
L-2
L-4 L-6 L-5
L -1
L -3
L -5
S1.0
S1.0
E X
IS
T
IN
G
B E
A M
E X
IS
T
IN
G
B E
A M
RTU (919 LBS.)
VAPOR BARRIER
POROUS FILL
SLAB - SEE PLAN
1 - #4 CONT.
NOSING BAR
STOREFRONT -
SEE ARCH. DWGS.
SLAB - SEE PLAN
1' - 0"
STOREFRONT -
SEE ARCH. DWGS.
600S125-54
METAL STUDS
@ 16" O/C
400S125-54 DIAGONAL
STUD BRACE @ 16" O/C
L4X4X1/4 CONT.
AT JOIST BOTTOM
CHORD
16 GAGE CLIP AT EACH
BRACE - ATTACH TO
ANGLE WITH 2 - 0.145"ø
P.A.F. AND TO BRACE
WITH 3 - #10 TEK SCREWS
EXISTING JOIST
EXISTING METAL
ROOF DECK
3 - #10 TEK
SCREWS
600T125-54 CONT.
METAL STUD TRACK
(TOP AND BOTTOM)
3/16 2" @ EACH JOIST
VAPOR BARRIER
POROUS FILL
SLAB - SEE PLAN
1 - #4 CONT.
NOSING BAR
STOREFRONT -
SEE ARCH. DWGS.
1' - 0"
STOREFRONT -
SEE ARCH. DWGS.
600S125-54 METAL
STUDS @ 16" O/C
EXISTING JOIST
EXISTING METAL
ROOF DECK
600T125-54 CONT.
METAL STUD TRACK
(TOP AND BOTTOM)
EXTERIOR
SHEATHING
FINISH - SEE
ARCH. DWGS.
400S125-54 DIAGONAL
STUD BRACE @ 16" O/C
16 GAGE CLIP AT EACH
BRACE - ATTACH TO
ANGLE WITH 2 - 0.145"ø
P.A.F. AND TO BRACE
WITH 3 - #10 TEK SCREWS
© 2022 Sinclair Pratt Cameron, P.C.
J O B N U M B E R
1/22/2024 5:15:02 PM
S1.0
JANUARY 12, 2024
FOUNDATION PLAN AND
LINTEL PLAN
4200 MARSHALL AVE
NEWPORT NEWS VA 23607
NEWSOME PARK
ELEMENTARY SCHOOL
SECURITY VESTIBULE
757.417.0565 * 757.417.0568 (fax)
VIRGINIA BEACH, VA 23451-6188
1630 DONNA DRIVE - SUITE 105
SINCLAIR PRATT CAMERON, P.C.
WWW.SPC-ENG.COM
Designed: BIM:
23-0580
SBQKLR
1/8" = 1'-0"
FOUNDATION PLAN
1/8" = 1'-0"
LINTEL PLAN
LINTEL PLAN NOTES
A ALL MASONRY LINTEL SHALL BE DENOTED AS L-X. SEE SHEET S3.0 FOR LINTEL SCHEDULE.
FOUNDATION PLAN NOTES
A SLAB ON GRADE SHALL BE 4" THICK CONCRETE REINFORCED WITH 6x6-W1.4xW1.4 WELDED WIRE FABRIC 2" FROM THE
TOP OF SLAB. THE SLAB SHALL BE PLACED ON A 10 MIL POLYETHYLENE VAPOR BARRIER & 4" OF POROUS FILL.
B REENTRANT BARS - SEE DETAIL ON SHEET S2.0.
C SEE SHEET S2.0 FOR FOUNDATION & SLAB ON GRADE DETAILS.
3/4" = 1'-0"S1.0
1 SECTION
3/4" = 1'-0"S1.0
3 SECTION
3/4" = 1'-0"S1.0
2 SECTION
3/4" = 1'-0"S1.0
4 SECTION
A I
N I
G
RI
V
FOHTLAE
W
N O
M M
O C
P R
O F
ESS IONAL EN
G
IN
E
E R
Lic. No. 47291
KEVIN L. RAINEY
12 JANUARY 2024
NEWSOME PARK
ELEMENTARY SCHOOL
5/8"ø x 12" LONG
SMOOTH DOWELS
SPACED @ 24" O/C
(12" O/C w/ 6"+ SLAB) -
GREASE ONE END
W.W.F.
2" CLR.
FILL GROOVE
WITH SEALANT
AS REQUIRED
DEPTH OF
CUT = 't'/4
CONSTRUCTION JOINT (C.J.) SAWED JOINT (S.J.)
2" CLR.
W.W.F.
NOTE: 't' = SLAB THICKNESS 't' 1' - 0" 't'
't' 't' 't'
SLAB ON GRADE DETAILS
NOT TO SCALE
DISCONTINUOUS JOINTS RE-ENTRANT CORNERS
2' - 0" 2' - 0"
4' - 0"
45°
2" 4"
2 - #4 BARS
MIDDLE OF SLAB
SLAB JOINTS
CMU WALL
2 - #4 BARS
MIDDLE OF
SLAB
SLAB ON GRADE REINFORCING DETAILS
NOT TO SCALE
SEE ARCH. DWGS.
DOOR OPENING -
2'
0" (T
Y P.)
#4 @ 12" O/C
CENTERED IN SLAB
CMU WALL
#4 REENTRANT BARS
CENTERED IN SLAB
PROVIDE CONSTRUCTION
JOINT AT DOOR OPENINGS
OR PROVIDE 1/8" WIDE x 1"
DEEP TOOLED JOINT IN
LINE WITH CMU WALL -
FILL GROOVE WITH
SEALANT AS REQUIRED)
AT INTERIOR DOOR OPENINGS - OPTION "A"
FILL GROOVE WITH
SEALANT AS REQ'D
4'
0"
2'
0"
2'
0"
SEE ARCH. DWGS.
DOOR OPENING -
CMU WALL
#4 REENTRANT BARS
CENTERED IN SLAB
AT INTERIOR DOOR OPENINGS - OPTION "B"
SLAB POURED
CONTINUOUS
THROUGH DOOR
OPENING
SEE ARCH. DWGS.
DOOR OPENING -
2'
0" (T
Y P.)
#4 @ 12" O/C
CENTERED IN SLAB
CMU WALL
#4 REENTRANT BARS
CENTERED IN SLAB
SLAB POURED TO
OUTSIDE FACE OF CMU
AND TURNED DOWN ONTO
FOUNDATION WALL - SEE
"THRESHOLD DETAIL" ON
THIS SHEET
AT EXTERIOR DOOR OPENINGS
THRESHOLD DETAIL
NOT TO SCALE
FOOTING -
SEE PLAN AND
TYPICALS
CMU - SEE
SECTIONS
SEE SITE PLAN
VAPOR BARRIER
POROUS FILL
#4 REENTRANT BAR -
SEE "SLAB ON GRADE
REINFORCING DETAILS"
ON THIS SHEET
SLAB - SEE PLAN
1/4" TOOLED JOINT
1 - #4 CONT.
NOSING BAR
P L A
N
S E
E
© 2022 Sinclair Pratt Cameron, P.C.
J O B N U M B E R
1/22/2024 5:15:02 PM
S2.0
JANUARY 12, 2024
FOUNDATION DETAILS
4200 MARSHALL AVE
NEWPORT NEWS VA 23607
NEWSOME PARK
ELEMENTARY SCHOOL
SECURITY VESTIBULE
757.417.0565 * 757.417.0568 (fax)
VIRGINIA BEACH, VA 23451-6188
1630 DONNA DRIVE - SUITE 105
SINCLAIR PRATT CAMERON, P.C.
WWW.SPC-ENG.COM
Designed: BIM:
23-0580
SBQKLR
A I
N I
G
RI
V
FOHTLAE
W
N O
M M
O C
P R
O F
ESS IONAL EN
G
IN
E
E R
Lic. No. 47291
KEVIN L. RAINEY
12 JANUARY 2024
NEWSOME PARK
ELEMENTARY SCHOOL
TYPICAL JAMB ELEVATIONTYPICAL SECTION TYPICAL CONTROL JOINT ELEVATION
BOND BEAM LINTEL DETAILS
NOT TO SCALE
1/2"
TYPICAL VERTICAL
REINFORCING (IF
SPACING IS LESS
THAN CLEAR SPAN)
TOP REINFORCING
(IF REQUIRED)
BOTTOM
REINFORCING - SEE
LINTEL SCHEDULE
SEE ARCH. DRAWINGS
FOR LINTEL HEIGHT
NOTE: VENEER MASONRY & SHELF
ANGLES NOT SHOWN FOR CLARITY -
SEE LINTEL SCHEDULE
TYPICAL VERTICAL JAMB
REINFORCING FULL HEIGHT
CMU BOND BEAM LINTEL -
SEE SCHEDULE
BOND BEAM REINFORCING -
SEE SCHEDULE
TYPICAL VERTICAL
REINFORCING (IF
SPACING IS LESS
THAN CLEAR SPAN)
BRG.
8" CLEAR SPAN
(MASONRY OPENING)
CLEAR SPAN
(MASONRY OPENING)BRG.
8"
MASONRY CONTROL JOINT -
SEE ARCH. DWGS.
CONTINUE VERTICAL JAMB
REINFORCING FULL HEIGHT
FROM BOND BEAM
LAY BOND BEAM ON 3/8"
HARDBOARD (NO MORTAR)
SEE TYPICAL JAMB ELEVATION
FOR NOTES NOT SHOWN
(T Y
P
IC
A L x B
A R
D
IA
(TYPICAL)
24 x BAR DIA.
(TYPICAL)
24 x BAR DIA.
(TYPICAL)
24 x BAR DIA.
CORNER INTERSECTION SECTION
PROVIDE ADDITIONAL CORNER
BARS SAME SIZE AS TYPICAL
BOND BEAM REINFORCING
TYPICAL BOND BEAM
REINFORCING - SEE
PLANS & SECTIONS
CONT. CMU
BOND BEAM
NOTE: BOND BEAM REINFORCING SHALL
RUN CONTINUOUS ACROSS CONTROL
JOINTS BUT SHALL BE DISCONTINUOUS
AT BUILDING EXPANSION JOINTS.
BOND BEAM REINFORCING DETAILS
NOT TO SCALE
MARK TYPE DESCRIPTION REMARKS
L-1
L-2
L-3
L-4
L-5
8" CMU BOND BEAM
LINTEL REINFORCED
WITH 2 - #4 BARS CONT.
(GROUT SOLID WITH
2000 PSI FINE GROUT)
12" CMU BOND BEAM
LINTEL REINFORCED
WITH 2 - #5 BARS CONT.
(GROUT SOLID WITH
2000 PSI FINE GROUT)
8" CMU BOND BEAM
LINTEL REINFORCED
WITH 2 - #4 BARS CONT.
WITH CONT. L 4 x 4 x 1/4
BRICK SHELF
W 8 x 10 LINTEL WITH 5/16" x 11" PLATE
WELDED TO BOTTOM
FLANGE
8" MINIMUM
BEARING
EACH END
8" MINIMUM
BEARING
EACH END
8" MINIMUM
BEARING
EACH END
1/2" x 6" x 6"
BEARING
PLATE EACH
END
LINTEL SCHEDULE
NOTE: ALL EXTERIOR STEEL BEAMS, PLATES & ANGLES SHALL BE HOT-DIP
GALVANIZED.
8" x 16" HIGH CMU BOND
BEAM LINTEL REINF'D
WITH 2 - #5 BARS CONT.
TOP & BOTTOM
(GROUT SOLID WITH
2000 PSI FINE GROUT)
8" MINIMUM
BEARING
EACH END
L-6
8" MINIMUM
BEARING
EACH END
W 8 x 10 LINTEL
MASONRY REINFORCING & GROUTING DETAILS
NOT TO SCALE
L A
Y U
P
G R
O U
T N
E X
T
A F
T E
R G
R O
U T
O F
I N
IT
IA
L
G R
O U
T P
O U
R I S
M A
X
IM
U M
H E
IG
H
T O
F
(S E
E S
C H
E D
V E
R T
IC
A
L L
A P
(S E
E S
C H
E D
V E
R T
IC
A
L L
A P
/2
M
IN
LOW LIFT GROUTING
(S E
E S
C H
E D
V E
R T
IC
A
L L
A P
HIGH LIFT GROUTING
G R
O U
T P
O U
R I S
M A
X
IM
U M
H E
IG
H
T O
F
G R
O U
T P
O U
R I S
M A
X
IM
U M
H E
IG
H
T O
F
/2
M
IN
BAR POSITIONER AT TOP OF WALL
BAR POSITIONERS SHALL BE SPACED
AT INTERVALS NOT TO EXCEED 200
BAR DIAMETERS - SEE SCHEDULE
STOP POUR NO LESS THAN 1/2"
BELOW TOP OF UNIT IF POUR IS
DELAYED ONE HOUR OR MORE
IN A CONTINUOUS POUR
BAR POSITIONER ABOVE
THE LAP AT THE DOWELS
PROVIDE CLEAN-OUT OPENINGS
(MINIMUM 3" x 4") AT BOTTOM OF
EACH GROUT POUR & TIE VERTICAL
REINFORCING TO DOWELS & SEAL
AFTER INSPECTION
NOTE: AFTER PLACEMENT OF
GROUT, DELAY APPROX. 5 TO 10
MINUTES TO ALLOW EXCESS
WATER TO BE ABSORBED, THEN
CONSOLIDATE GROUT BY
MECHANICAL VIBRATOR
BAR
SIZE
#4 #5 #6 #7 #8
MINIMUM
LAPS
24" 30" 36" 42" 48"
MAXIMUM BAR
POSITIONER SPACING
8'-4" O/C 10'-5" O/C 12'-6" O/C 14'-7" O/C 16'-8" O/C
REINFORCING SCHEDULE
CORNERINTERSECTION OPENING/END CONTROL JOINT
EXTERIOR OR
PARTITION WALL
VERTICAL BARS SAME
SIZE AS TYPICAL VERT.
WALL REINF'G (GROUT
CELLS SOLID)
3/8" CONTROL JOINT
FOR STRUCTURAL
PARTITIONS (3/4" FOR
NON-STRUCTURAL
PARTITIONS)
ADDITIONAL VERTICAL
BAR AT OPENINGS
GREATER THAN 9'-0"
(GROUT CELLS SOLID)
SEE ARCH.
DRAWINGS FOR
C.J. LOCATIONS
& DETAILS
VERTICAL BARS SAME
SIZE AS TYPICAL VERT.
WALL REINFORCING
(GROUT CELLS SOLID)
VERTICAL BARS SAME
SIZE AS TYPICAL VERT.
WALL REINF'G (GROUT
CELLS SOLID)
PARTITION WALL
MASONRY VERTICAL WALL REINFORCING DETAILS
NOT TO SCALE
1 1/2" 1/2"
3/16 2 - 12
CONTINUE VERT.
REINF. ABOVE
LINTEL - PROVIDE
GRADE 40 STEEL
WELDED TO
STEEL BEAM
VERTICAL WALL
REINFORCING -
FILL CELLS SOLID
WITH GROUT
LINTEL BEAM -
SEE SCHEDULE
TYP. VERT. REINF. (IF
SPACING IS LESS
THAN CLEAR SPAN) -
PROVIDE GRADE 40
STEEL WELDED TO
STEEL BEAM *OR*
5/8"ø x 4" HEADED
STUD ANCHORS
(SPACING TO MATCH
REINF. SPACING)
MASONRY PLATE -
SEE SCHEDULE
BEARING PLATE -
SEE SCHEDULE
1" NON-SHRINK
GROUT
STEEL LINTEL BEAM BEARING DETAIL
NOT TO SCALE
MASONRY WALL
2 - 5/8"ø x 16" LONG
HEADED STUD ANCHORS
FILL THREE COURSES
SOLID WITH 2000 PSI
PEA GRAVEL CONCRETE
1/8
1/4 4
JOISTS - SEE PLAN
L 3 x 3 x 1/4 FRAME
WELD DECK TO
ANGLE FRAME
@ 6" O/C (TYP.)
L3X3X/4 FRAME
JOISTS - SEE PLAN
OPENING
JOISTS
ROOF OPENING DECK SUPPORT DETAIL
NOT TO SCALE
1/8
1/8
1/8
SUPPORT DETAILS AT ROOF TOP MOUNTED EQUIPMENT (UNIT WEIGHT: 1000 LBS.)
NOT TO SCALE
DECK SUPPORT
ANGLES AT DECK
OPENING NOT
SHOWN FOR CLARITY
SEE DESIGN NOTE
JOIST - SEE PLAN
RTU - SEE
MECH. DWGS.
RTU CURB BY
MANUFACTURER
RTU - SEE
MECH. DWGS.
RTU CURB BY
MANUFACTURER
C6X8.2 CHANNEL
(TYP.)
JOIST - SEE PLAN
SEE "JOIST REINFORCING
DETAIL" WHERE CHANNEL
DOES NOT LAND ON JOIST
PANEL POINT
NOTE: LOCATE
CHANNELS AT JOIST
PANEL POINTS
WHERE POSSIBLE
DECK SUPPORT
ANGLES - SEE
"ROOF DECK
OPENING SUPPORT
DETAIL" THIS SHEET
ELEVATION PARALLEL TO SUPPORT ANGLES ELEVATION PERPENDICULAR TO SUPPORT ANGLES
4' - 0" O/C MAX.
WHERE ADDITIONAL LOADS ARE APPLIED
TO THE TOP CHORDS OF JOISTS, IF IT
DOES NOT OCCUR WITHIN 4" OF A PANEL
POINT, ADD 2 - L1 1/4X1 1/4X1/8 TO
BOTTOM CHORD PANEL POINT AS SHOWN
LOAD > 100#
JOIST -
SEE PLAN
WHERE ADDITIONAL LOADS ARE
APPLIED TO THE BOTTOM CHORDS
OF JOISTS, IF IT DOES NOT OCCUR
WITHIN 4" OF A PANEL POINT, ADD
2 - L1 1/4X1 1/4X1/8 TO TOP CHORD
PANEL POINT AS SHOWN
LOAD > 100#
JOIST REINFORCING DETAIL
NOT TO SCALE
© 2022 Sinclair Pratt Cameron, P.C.
J O B N U M B E R
1/22/2024 5:15:02 PM
S3.0
JANUARY 12, 2024
MASONRY AND FRAMING
DETAILS
4200 MARSHALL AVE
NEWPORT NEWS VA 23607
NEWSOME PARK
ELEMENTARY SCHOOL
SECURITY VESTIBULE
757.417.0565 * 757.417.0568 (fax)
VIRGINIA BEACH, VA 23451-6188
1630 DONNA DRIVE - SUITE 105
SINCLAIR PRATT CAMERON, P.C.
WWW.SPC-ENG.COM
Designed: BIM:
23-0580
SBQKLR
A I
N I
G
RI
V
FOHTLAE
W
N O
M M
O C
P R
O F
ESS IONAL EN
G
IN
E
E R
Lic. No. 47291
KEVIN L. RAINEY
12 JANUARY 2024
NEWSOME PARK
ELEMENTARY SCHOOL
NEWSOME PARK
ELEMENTARY SCHOOL
NEWSOME PARK
ELEMENTARY SCHOOL
NEWSOME PARK
ELEMENTARY SCHOOL
SECURITY VESTIBULE &
OFFICE ALTERATIONS
Richard Corner Rectangle
NEWSOME PARK
ELEMENTARY SCHOOL
NEWSOME PARK
ELEMENTARY SCHOOL
NEWSOME PARK
ELEMENTARY SCHOOL
NEWSOME PARK
ELEMENTARY SCHOOL
NEWSOME PARK
ELEMENTARY SCHOOL
NEWSOME PARK
ELEMENTARY SCHOOL
NEWSOME PARK
ELEMENTARY SCHOOL
NEWSOME PARK
ELEMENTARY SCHOOL
NEWSOME PARK
ELEMENTARY SCHOOL
NEWSOME PARK
ELEMENTARY SCHOOL
NEWSOME PARK
ELEMENTARY SCHOOL
SECURITY VESTIBULE &
OFFICE ALTERATIONS
AutoCAD SHX Text
PROVIDE ALUM STOREFRONT
AutoCAD SHX Text
HM DOOR & FRAME BEYOND
AutoCAD SHX Text
PROVIDE RAILS FOR EXT RAMPS
AutoCAD SHX Text
RETAINING WALL
AutoCAD SHX Text
CANOPY TO REMAIN
AutoCAD SHX Text
SCHOOL BEYOND TO REMAIN
AutoCAD SHX Text
SIDEWALK BEYOND
AutoCAD SHX Text
WINDOW TO REMAIN
AutoCAD SHX Text
PROVIDE ALUMINUM WINDOW
AutoCAD SHX Text
MAS WALL BEYOND (MATCH FIELD BRICK)
AutoCAD SHX Text
MAS PIER TO REMAIN
AutoCAD SHX Text
RAMP BEYOND
AutoCAD SHX Text
SIDEWALK TO REMAIN
AutoCAD SHX Text
TELEPHONE BOX TO REMAIN
AutoCAD SHX Text
POWER CONDUIT TO REMAIN
AutoCAD SHX Text
SPEAKER TO REMAIN
AutoCAD SHX Text
COMMON BOX TO REMAIN
AutoCAD SHX Text A3.01
AutoCAD SHX Text A2
AutoCAD SHX Text A3.01
AutoCAD SHX Text A3
AutoCAD SHX Text
TOOTH & MATCH BRICK VEENER
AutoCAD SHX Text
DOWNSPOUT NOZZLE
AutoCAD SHX Text PROVIDE SAFETY/SECURITY FILM AT INTERIOR SURFACES OF ALL GLASS @ WINDOWS/ DOORS INDICATED
AutoCAD SHX Text A3.02
AutoCAD SHX Text A1
AutoCAD SHX Text
PROVIDE ALUMINUM STOREFRONT
AutoCAD SHX Text
MATCH STUCCO TEXTURE OF CANOPY TO REMAIN
AutoCAD SHX Text
PROVIDE GUTTER
AutoCAD SHX Text
BUILDING BEYOND TO REMAIN
AutoCAD SHX Text
PROVIDE DOWNSPOUT
AutoCAD SHX Text
RAIL BEYOND
AutoCAD SHX Text
CANOPY TO REMAIN
AutoCAD SHX Text
SIDEWALK TO REMAIN
AutoCAD SHX Text A3.01
AutoCAD SHX Text D3
AutoCAD SHX Text
BRICK VENEER
AutoCAD SHX Text
MTL COPING
AutoCAD SHX Text PROVIDE SAFETY/SECURITY FILM AT INTERIOR SURFACES OF ALL GLASS @ WINDOWS/ DOORS INDICATED
AutoCAD SHX Text
NEWSOME PARK ELEMENATARY
AutoCAD SHX Text
BRICK VENEER TO REMAIN
AutoCAD SHX Text
HM FRAME WINDOWS, TYP
AutoCAD SHX Text
HM DOOR FRAME W/ WD DOOR
AutoCAD SHX Text
GWB SOFFIT
AutoCAD SHX Text
AUDITORIUM DOORS TO REMAIN
AutoCAD SHX Text
HEADER COURSE BRICK
AutoCAD SHX Text
ALUM STOREFRONT ENTRANCE
AutoCAD SHX Text
VEST 101
AutoCAD SHX Text
LOBBY 106
AutoCAD SHX Text
SS CORNER GUARD TO REMAIN
AutoCAD SHX Text
CT BASE
AutoCAD SHX Text
CT BASE
AutoCAD SHX Text
BRICK WALL TO REMAIN
AutoCAD SHX Text
PTD CMU TO REMAIN
AutoCAD SHX Text
DOOR TO REMAIN
AutoCAD SHX Text
ELEC PANEL & FIRE STROBE TO REMAIN
AutoCAD SHX Text
CORRIDOR (BEYOND) (BEYOND)
AutoCAD SHX Text
CT TO REMAIN
AutoCAD SHX Text
CUT METAL LETTERS
AutoCAD SHX Text
INTERIOR ELEV LEGEND:
AutoCAD SHX Text
CERAMIC WALL TILE - COLOR A
AutoCAD SHX Text
CERAMIC WALL TILE - COLOR B
AutoCAD SHX Text
BRICK VENEER TO REMAIN
AutoCAD SHX Text
BRICK VENEER
AutoCAD SHX Text
BULLETIN BOARD TO REMAIN
AutoCAD SHX Text
ALUM STOREFRONT ENTRANCE
AutoCAD SHX Text
CROSS CORRIDOR GATE RECEIVER POST TO REMAIN
AutoCAD SHX Text
ELECTRICAL PANEL TO REMAIN
AutoCAD SHX Text
CT WAINSCOT TO REMAIN
AutoCAD SHX Text
GWB SOFFIT
AutoCAD SHX Text
PTD CMU TO REMAIN
AutoCAD SHX Text
CT WAINSCOT
AutoCAD SHX Text
CT WAINSCOT
AutoCAD SHX Text
CT WAINSCOT TO REMAIN
AutoCAD SHX Text
WATER DISPENSER TO REMAIN
AutoCAD SHX Text
PTD CMU INFILL
AutoCAD SHX Text
HM DOOR FRAME W/ WD DOOR
AutoCAD SHX Text
DOOR TO REMAIN
AutoCAD SHX Text
LOBBY 106
AutoCAD SHX Text
PTD CMU TO REMAIN
AutoCAD SHX Text H U D S O N + A S S O C I A T E S
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text H
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text
120 WEST QUEENS WAY SUITE 201
AutoCAD SHX Text
(757) 722-1964
AutoCAD SHX Text
HAMPTON, VA.
AutoCAD SHX Text 23669
AutoCAD SHX Text J
AutoCAD SHX Text O
AutoCAD SHX Text B
AutoCAD SHX Text N
AutoCAD SHX Text U
AutoCAD SHX Text M
AutoCAD SHX Text B
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text
NEWSOME PARK
AutoCAD SHX Text
ELEMENTARY SCHOOL
AutoCAD SHX Text
SECURITY VESTIBULE
AutoCAD SHX Text
& OFFICE ALTERATIONS
AutoCAD SHX Text
4200 MARSHALL AVE
AutoCAD SHX Text
NEWPORT NEWS VA 23607
AutoCAD SHX Text
JANUARY 12, 2024
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text V
AutoCAD SHX Text H
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text W
AutoCAD SHX Text C
AutoCAD SHX Text O
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text 1-12-2024
AutoCAD SHX Text
EXTERIOR & INTERIOR ELEVATIONS
AutoCAD SHX Text A2.01
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 1/4" = 1'-0"
AutoCAD SHX Text
WEST ELEVATION
AutoCAD SHX Text A4
AutoCAD SHX Text A2.01
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 1/4" = 1'-0"
AutoCAD SHX Text
NORTH ELEVATION
AutoCAD SHX Text D4
AutoCAD SHX Text A2.01
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 1/4" = 1'-0"
AutoCAD SHX Text
INT ELEVATION LOBBY & VESTIBULE
AutoCAD SHX Text A2
AutoCAD SHX Text A2.01
AutoCAD SHX Text NOTE: SEE BUILDING SECTIONS SHEET A3.01 SEE BUILDING SECTIONS SHEET A3.01 FOR ADDITIONAL INTERIOR ELEVATIONS
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 1/4" = 1'-0"
AutoCAD SHX Text
INT ELEVATION CORRIDOR
AutoCAD SHX Text A1
AutoCAD SHX Text A2.01
NEWSOME PARK
ELEMENTARY SCHOOL
NEWSOME PARK
ELEMENTARY SCHOOL
NEWSOME PARK
ELEMENTARY SCHOOL
NEWSOME PARK
ELEMENTARY SCHOOL
• •••• •• ••• RICHARD S. CORNER
NEWSOME PARK
ELEMENTARY SCHOOL
NEWSOME PARK
ELEMENTARY SCHOOL
NEWSOME PARK
ELEMENTARY SCHOOL
NEWSOME PARK
ELEMENTARY SCHOOL
NEWSOME PARK
ELEMENTARY SCHOOL
EXTERIOR RAMP
PLAN &
SECTIONS
NEWSOME PARK
ELEMENTARY SCHOOL
EXTERIOR RAMP
SECTIONS
NEWSOME PARK
ELEMENTARY SCHOOL
NEWSOME PARK
ELEMENTARY SCHOOL
Consulting Engineers
THOMPSON
2809 S. LYNNHAVEN ROAD VA BEACH, VA 23452
TELEPHONE: (757)599-4415 PROJECT NUMBER: 23-061
4323 COX ROAD GLEN ALLEN, VA 23060
22 ENTERPRISE PARKWAY HAMPTON, VA 23666
01-12-2024
1. WHERE EQUIPMENT IS INDICATED TO BE REMOVED, IT SHALL MEAN COMPLETE REMOVAL
OF EQUIPMENT, INCLUDING SUPPORTS, CONTROLS AND INCIDENTAL ITEMS CONNECTED
OR FASTENED TO EQUIPMENT. OWNER MAINTAINS THE OWNERSHIP OF ALL ITEMS
TAGGED OR IDENTIFIED.
2. WHERE PIPING IS INDICATED TO BE REMOVED, IT SHALL MEAN COMPLETE REMOVAL OF
PIPING, INCLUDING VALVES, FITTINGS, INSULATION, SUPPORTS, CONTROLS AND
INCIDENTAL ITEMS CONNECTED OR FASTENED TO THE PIPING. PIPING IS DIAGRAMMATIC
AND INDICATES THE GENERAL EXTENT OF WORK. NO ATTEMPT IS MADE TO SHOW EVERY
ELL, TEE, OFFSET, FITTING AND VALVE. REMOVE PIPING AS INDICATED AND SPECIFIED.
3. WHERE DUCTWORK IS INDICATED TO BE REMOVED, IT SHALL MEAN COMPLETE REMOVAL
OF DUCTWORK, INCLUDING FITTINGS, INSULATION, SUPPORTS, CONTROLS AND
INCIDENTAL ITEMS CONNECTED OR FASTENED TO THE DUCTWORK. DUCTWORK IS
DIAGRAMMATIC AND INDICATES THE GENERAL EXTENT OF WORK. NO ATTEMPT IS MADE
TO SHOW EVERY ELL, TEE, OFFSET AND FITTING. REMOVE DUCTWORK AS INDICATED
AND SPECIFIED.
4. REFER TO REFLECTED CEILING PLANS FOR DEMOLITION AND NEW WORK RELATED TO
CEILINGS.
GENERAL DEMOLITION NOTES
1. CONTRACTOR SHALL VISIT JOB SITE TO DETERMINE EXTENT OF WORK INVOLVED PRIOR
TO BIDDING THE PROJECT.
2. THE MECHANICAL SYSTEM HAS BEEN DESIGNED IN ACCORDANCE WITH THE 2018
VIRGINIA UNIFORM STATEWIDE BUILDING CODE.
3. COORDINATE LOCATION OF ALL DUCTWORK, SUPPLY AND RETURN DEVICES, EXHAUST
FANS, THERMOSTATS AND OTHER WALL OR CEILING MOUNTED EQUIPMENT WITH
REFLECTED PLANS, LIGHT FIXTURES, SPRINKLER SYSTEMS AND ACCESSORIES
INSTALLED BY OTHER TRADES SO AS TO PRESENT A NEAT AND ATTRACTIVE
INSTALLATION THROUGHOUT THE BUILDING.
4. COORDINATE ALL AIR INTAKES AND RELIEF OUTLETS, SIZE AND LOCATION, WITH
ARCHITECTURAL DRAWINGS.
5. ALL DUCTWORK, ETC., SHALL BE CONCEALED UNLESS OTHERWISE NOTED.
6. PIPING ARRANGEMENTS ARE DIAGRAMMATIC.
7. ARRANGE DUCTWORK PARTICULARLY ABOVE CEILING AS REQUIRED TO CLEAR
STRUCTURE, CONDUIT, LIGHTS, ETC., ALLOWING SPACE FOR HANGERS, INSULATION,
ETC.
8. SEAL AROUND AND MAKE AIRTIGHT ALL DUCTS PENETRATING INSULATED CEILINGS AND
WALLS.
9. DUCT DIMENSIONS MAY BE MODIFIED AS APPROVED BY ENGINEER.
10. DUCT SIZES SHOWN ARE INSIDE FREE AREA DIMENSIONS.
11. FINAL LOCATION OF SPACE THERMOSTATS, HUMIDISTATS, AND SENSORS SHALL BE
APPROVED BY ARCHITECT.
12. INSTALL ALL WALL MOUNTED NON-ADJUSTABLE SENSORS AT 5'-0" FROM FINISHED
FLOOR TO TOP OF SENSOR. ADJUSTABLE DEVICE SHALL BE INSTALLED 4'-0" ABOVE
FINISHED FLOOR.
13. ALL ROUND BRANCH DUCTS TO DIFFUSERS SHALL MATCH NECK SIZES SHOWN ON
SCHEDULE, UNLESS OTHERWISE NOTED.
14. ALL DIFFUSERS, GRILLES AND REGISTERS SHALL BE SIZED TO HAVE A MINIMUM FREE
AREA OF 70% AND MEET PERFORMANCE CRITERIA SCHEDULED.
15. CONTRACTOR SHALL ONLY USE DESIGNATED AREAS WITHIN THE EQUIPMENT FOR
PENETRATIONS OF ELECTRICAL CONDUITS AND CONTROL CONDUITS. THESE
PENETRATIONS MUST BE WEATHERTIGHT. IF A CONTRACTOR PENETRATES ANY AREAS
IN THE EQUIPMENT THAT IS NOT DESIGNATED BY THE MANUFACTURER FOR
PENETRATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL REPAIRS TO THE
EQUIPMENT, TO INSURE IT IS WEATHERTIGHT. IF EQUIPMENT CAN NOT BE MADE
WEATHER TIGHT THE CONTRACTOR SHALL BE REQUIRED TO REPLACE EQUIPMENT AT
HIS OWN EXPENSE.
16. REFER TO STRUCTURAL DRAWINGS FOR STRUCTURAL WORK REQUIRED FOR
INSTALLATION OF ROOF MOUNTED HVAC EQUIPMENT.
GENERAL NOTES
ABBREVIATIONS
ø DIAMETER
CFM CUBIC FEET PER MINUTE
COMP COMPRESSOR
COP COEFFICIENT OF PERFORMANCE
(CU-x) CONDENSING UNIT (EXISTING)
(CUH-x) CABINET UNIT HEATER (EXISTING)
D CONDENSATE DRAIN
DB DRY BULB
DDC DIRECT DIGITAL CONTROL
(DOAS-x) DEDICATED OUTSIDE AIR UNIT (EXISTING)
DX DIRECT EXPANSION
EAT ENTERING AIR TEMPERATURE
EF-x EXHAUST FAN DESIGNATION
ESP EXTERNAL STATIC PRESSURE
°F DEGREES FAHRENHEIT
FLA FULL LOAD AMPS
HP HORSE POWER
(HP-x) HEAT PUMP (EXISTING)
IN INCH/INCHES
KW KILOWATTS
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
MBH 1000 BRITISH THERMAL UNITS PER HOUR
MCA MINIMUM CIRCUIT AMPS
MOCP MAXIMUM OVER CURRENT PROTECTION
NC NOISE CRITERIA
NO NUMBER
ΔP PRESSURE DIFFERENTIAL
PH PHASE
RD ROOF DRAIN (EXISTING)
RL REFRIGERANT LIQUID
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION
RTU-x ROOFTOP UNIT DESIGNATION
SENS SENSIBLE
TEMP TEMPERATURE
(UV-x) UNIT VENTILATOR (EXISTING)
V VOLTS
(VAV-x) VARIABLE AIR VOLUME (EXISTING)
WB WET BULB
WC WATER COLUMN
LEGEND
XX
XX
ø
THERMOSTAT OR TEMPERATURE SENSOR,
CONTROLLING UNIT AS INDICATED
VOLUME DAMPER
3/4" DOOR UNDERCUT
SENSOR WITH GUARD
90° DUCT ELBOW - TURNED DOWN
DUCT ELBOW WITH TURNING VANES
90° DUCT ELBOW - TURNED UP
DUCT TRANSITION
SQUARE TO ROUND DUCT TRANSITION
ROOF MOUNTED EXHAUST FAN
SUPPLY AIR DEVICE
RETURN AIR DEVICE
NEW DUCT
FLEXIBLE DUCT
ROUND DUCT
DIRECTION OF AIRFLOW
POINT OF CONNECTION FOR NEW WORK
REMOVE EXISTING TO THIS POINT
DEMOLITION NOTE
NEW WORK NOTE
EXISTING TO REMAIN
NEW WORK
EXISTING TO BE REMOVED
BALANCE EXISTING AIR TERMINAL TO CFM INDICATEDXXX
D
NEW PIPING
DIRECTION OF PITCH FOR PIPING OR DUCTWORK
PIPE DOWN
DRAIN PIPING
T
D1
(X"/X") EXISTING SIZES AS INDICATED
HUMIDISTAT OR HUMIDITY SENSORH
A CFM DIFFUSER, REGISTER, AND GRILLE, CFM AS INDICATED
NEWSOME PARK
ELEMENTARY SCHOOL
2809 S. LYNNHAVEN ROAD VA BEACH, VA 23452
TELEPHONE: (757)599-4415 PROJECT NUMBER: 23-061
4323 COX ROAD GLEN ALLEN, VA 23060
22 ENTERPRISE PARKWAY HAMPTON, VA 23666
01-12-2024
PACKAGED ROOFTOP HEAT PUMP UNIT SCHEDULE
SUPPLY FAN DATA
REMARKS
SELECTION
BASED ON
"AAON"
UNIT
WEIGHT
(LBS)
UNIT
NO.
REMARKS: 1 PROVIDE WITH 14" HIGH ROOF CURB.
PROVIDE DOWNFLOW DISCHARGE CONFIGURATION.
UNIT SHALL UTILIZE REFRIGERANT R-410A.
PROVIDE WITH CONDENSATE OVERFLOW SWITCH.
TOTAL
CFM
OA
CFM
ESP
(IN.WC) HP RPM
NO.
OF
COMP FLA
(EACH)
HP
(EACH)
DX COOLING COIL PERFORMANCE
EAT
DB°F WB°F
LAT
DB°F WB°F
TOTAL
MBH
SENS
MBH
AMBIENT
TEMP
(°F) MBH
EAT
(°F) DB
LAT
(°F) DB
CAPACITY
MBH
EAT
(°F) DB
LAT
(°F) DB
ELECTRICAL DATA
V PH MCA MOCP
NO. OF
FANS
CONDENSER
FANS
5 PROVIDE WITH SINGLE POINT POWER CONNECTION.
COOLING CAPACITY INDICATED DOES NOT INCLUDE FAN HEAT.
PROVIDE WITH BIPOLAR IONIZATION AIR PURIFICATION SYSTEM. REFER TO
SPECIFICATION 230500 2.9.B FOR REQUIREMENTS.
PROVIDE INTAKE AND RELIEF HOODS WITH INTEGRAL BIRD SCREENS.
9 PROVIDE DUCT MOUNTED ION DETECTOR
DOWNSTREAM OF BI-POLAR IONIZATION SYSTEM.
UNIT WEIGHT DOES NOT INCLUDE ROOF CURB AND
ACOUSTICAL SYSTEM.
PROVIDE FACTORY MOUNTED AND WIRED
CONVENIENCE OUTLET.
AREA
SERVED
4 11
SYSTEM
TYPE
RTU-8 160 RQ-003719720 10.5 0.5 1,041 1 1 1.60.3 81.0 69.0 51.2 51.7 36.9 21.9 95 56.2 83.4 2.6 15.9 51.2 72.0 460 3 19 2023.9 3 4 5 6 7 8 9 10MAIN OFFICE 11 12SINGLE ZONE VAV
HOT GAS REHEAT DISCHARGE TEMPERATURE SETPOINT SHALL BE 72°F
ADJUSTABLE.
MODULATING HOT GAS
REHEAT DATA
REMARKSWHEELTYPE ARRANGEMENT
EXHAUST FAN SCHEDULE
MOTOR DATA
DRIVE CFM
HP V PH
ESP
(IN. WC)
MAX.
TIP SPEED
CONTROL
METHOD
MAX.
SONES
SELECTION
BASED ON
"GREENHECK"
FAN
(RPM)
UNIT
NO.
REMARKS: 1 PROVIDE WITH PRE-WIRED FACTORY MOUNTED DISCONNECT.
PROVIDE BACKDRAFT DAMPER.
PROVIDE WITH SOLID STATE SPEED CONTROLLER.
G-060-DDIRECT 75 0.3 1,550POWER ROOF VENTILATOR DOWNBLAST BACKWARD INCLINED
CENTRIFUGAL 3,297 1/60 120 1 DDC 3.5 1 2 3EF-19
MARK
GRILLE, REGISTER & DIFFUSER SCHEDULE
C
B
A 6"ø
8"ø
10"ø
NECK
SIZE DESCRIPTION
LOUVERED FACE ADJUSTABLE
CEILING DIFFUSER
LOUVERED FACE ADJUSTABLE
CEILING DIFFUSER
LOUVERED FACE ADJUSTABLE
CEILING DIFFUSER
SHAPEMATERIAL FINISH REMARKS
SCDA
SCDA
SCDA
STEEL WHITE NO 0.1" 25
NO
NO
SQUARE
SQUARE
SQUARE
VOLUME
DAMPER
MAXIMUM
P
MAXIMUM
NC
SELECTION
BASED ON
"PRICE"
0.1"
0.1"
WHITE
WHITE
STEEL
STEEL
1 3
Z 530STEEL WHITE NO 0.1" 25SQUARE 1
REMARKS: 1 REFER TO ARCHITECT'S REFLECTED CEILING PLAN FOR CEILING TYPES. FOR ACOUSTIC CEILING, PROVIDE WITH 24" x 24" PANEL SUITABLE FOR MOUNTING IN LAY-IN GRID. FOR GYPSUM BOARD CEILING, PROVIDE WITH SMALL FACE AND SURFACE MOUNT FRAME.
2 PROVIDE 3-CONE, 12" x 12" FACE MOUNTED IN 2' x 2' METAL PANEL.
CEILING RETURN OR EXHAUST GRILLE
45° DEFLECTION, 3/4" SPACING8" x 8"
3 PROVIDE 4-CONE, 24" x 24" FACE MOUNTED IN 2' x 2' METAL PANEL.
W 530STEEL WHITE NO 0.1" 25SQUARE 1CEILING RETURN OR EXHAUST GRILLE
45° DEFLECTION, 3/4" SPACING22" x 22"
COP
REVERSE CYCLE HEATING
CAPACITY @15°F
KW EAT
(°F) DB
LAT
(°F) DB
10 56.2 99.7
EMERGENCY HEATING
CAPACITY
MBH
34.1
D 14"ø LOUVERED FACE ADJUSTABLE
CEILING DIFFUSER SCDANO SQUARE 250.1"WHITESTEEL 1 3
NEWSOME PARK
ELEMENTARY SCHOOL
2809 S. LYNNHAVEN ROAD VA BEACH, VA 23452
TELEPHONE: (757)599-4415 PROJECT NUMBER: 23-061
4323 COX ROAD GLEN ALLEN, VA 23060
22 ENTERPRISE PARKWAY HAMPTON, VA 23666
01-12-2024
(12"/12") (20"/12")
12"/12" 20"/12"
20"/12"
(UV-A28)
(3/4")
D D
CO CO
D
D
(3/4")
UV-A34
3/4"
(UV-A31)
T H
UV-A34
T
HUV-A31
(2") (2")(2")(2")
(2")
14"ø 18"ø22"ø
(6"ø)
(EF-7)
T
VAV-1-2
TVAV-1-1
(14"/10")
(14"/12")
(VAV-1-1)
(VAV-1-2)
8"/8"
8"/6"
10"/10"
TVAV-1-3
T CUH-A5
(12"/10")
(8"/6")
(10"/8") (12"/10")
(8"/6")
(6"ø)
(EF-9)
(CUH-B3)
T
CUH-B3(12"/12")
T
CUH-B4
(CUH-B4)
(12"/12")
(8"/6")
(14"/10") (16"/12")
(10"/8")
(8"/8")
(10"/10") (EF-8) ON
ROOF
(8"/6")
T
HP-B6
(DOAS-2)
ON ROOF
(6"ø)
(14"/10") UP
(14"/10")
T HP-D1H
(8"/8")
(10"/8")
(HP-B7)
(CU-B7)
ON ROOF
(8"/8")
(12"/10")
(12"/10")
RG/RL
(250 CFM)
(CU-D1)
ON ROOF
RL/RS
(CU-B6)
ON ROOF
(HP-B6)
D
(3/4")
(VAV-1-3)
(8"ø) (10"ø)
(14"/12")
(2")
(20"/14") (20"/14")
UP TO
(RTU-2)
SD
(8"/6")
14"/12" UP TO (RTU-2 )
(RTU-2) ON ROOF
S
(20"/12")
20"/12"
(16"/14")
UP
(10"/10")
DEMOLITION FLOOR PLAN - MECHANICAL
SCALE: 1/8" = 1'-0"
D1
CUH-A5
REMOVE CABINET UNIT HEATER AND SUPPORTS
COMPLETE AND SAVE FOR REINSTALLATION.
REMOVE THERMOSTAT AND SECURITY GUARD AND
SAVE FOR REINSTALLATION.
REMOVE DIFFUSERS AND GRILLES AND SAVE FOR
REINSTALLATION.
REMOVE THERMOSTAT AND SAVE FOR
REINSTALLATION.
REMOVE DUCTWORK AND GRILLES BACK TO POINT
INDICATED.
REMOVE SIDEWALL GRILLE, REFER TO ARCHITECTURAL
DRAWINGS FOR WALL PATCHING INFORMATION.
REMOVE THERMOSTAT/HUMIDISTAT COMPLETE.
REMOVE UNIT VENTILATOR AND CONTROLS COMPLETE.
DEMOLITION NOTES
DESCRIPTIONNO.
D1
D2
D3
D2
D4
D4
D5
D6
D7
D8
D5
D6
D7
D8
D9
TYP
D5
(HP-D1)
RL/RS
D7
D3
NOTE: EXISTING CONDITIONS ILLUSTRATED HAVE BEEN
DETERMINED FROM ORIGINAL CONSTRUCTION
DOCUMENTS AND LIMITED NON-INVASIVE FIELD
INVESTIGATION. THE CONTRACTOR SHALL INVESTIGATE
FIELD CONDITIONS PRIOR TO COMMENCEMENT OF WORK,
COORDINATE AND MAKE ADJUSTMENTS AS NECESSARY.
NEWSOME PARK
ELEMENTARY SCHOOL
2809 S. LYNNHAVEN ROAD VA BEACH, VA 23452
TELEPHONE: (757)599-4415 PROJECT NUMBER: 23-061
4323 COX ROAD GLEN ALLEN, VA 23060
22 ENTERPRISE PARKWAY HAMPTON, VA 23666
01-12-2024
NEW WORK FLOOR PLAN - MECHANICAL
SCALE: 1/8" = 1'-0"
(12"/12") (20"/12")
20"/12"
(UV-A28)
(3/4")
D D
CO CO
D
D
(3/4")
(UV-A31)
T
HUV-A31
(2") (2")(2")(2")
(2")
14"ø 18"ø22"ø
(6"ø)
(EF-7)
(14"/10")
(14"/12")
(VAV-1-1)
(VAV-1-2)
TVAV-1-3
(12"/10")
(8"/6")
(10"/8") (12"/10")
(8"/6")
(6"ø)
(EF-9)
(CUH-B3)
T
CUH-B3(12"/12")
T
CUH-B4
(CUH-B4)
(12"/12")
(8"/6")
(14"/10") (16"/12")
(10"/8")
(8"/8")
(10"/10") (EF-8) ON
ROOF
(8"/6")
T
HP-B6
(DOAS-2)
ON ROOF
(6"ø)
(14"/10") UP
(14"/10")
T HP-D1H
(8"/8")
(10"/8")
(HP-B7)
(CU-B7)
ON ROOF
(8"/8")
(12"/10")
(12"/10")
RG/RL
(250 CFM)
(CU-D1)
ON ROOF
RL/RS
(CU-B6)
ON ROOF
(HP-B6)
D
(3/4")
(VAV-1-3)
(8"ø) (10"ø)
(14"/12")
(2")
(20"/14") (20"/14")
UP TO
(RTU-2)
SD
(8"/6")
14"/12" UP TO (RTU-2 )
(RTU-2) ON ROOF
S
(20"/12")
(16"/14")
UP
(10"/10")
(HP-D1)
RL/RS
PROVIDE ROOFTOP UNIT, CONTROLS AND ROOF CURB
COMPLETE.
PROVIDE DUCTWORK, INSULATION AND SUPPORTS.
PROVIDE THERMOSTAT AND CONTROL WIRING
COMPLETE.
PROVIDE ROOF MOUNTED EXHAUST FAN, SUPPORTS
AND CONTROLS COMPLETE.
PROVIDE TEMPERATURE SENSOR/HUMIDITY SENSOR
AND CONTROL WIRING COMPLETE. SENSOR READINGS
TO BE AVERAGED TO MAINTAIN OCCUPANT COMFORT.
RELOCATE SALVAGED CABINET UNIT HEATER IN
LOCATION INDICATED.
REBALANCE VAV BOX TO MAXIMUM 730 CFM.
SAWCUT OPENING AND PROVIDE DUCT SLEEVES,
REFER TO SPECIFICATION 230100 FOR ADDITIONAL
INFORMATION.
REINSTALL SALVAGED RETURN GRILLE AND CONNECT
TO DUCTWORK.
REBALANCE VAV BOX TO MAXIMUM 645 CFM.
REBALANCE RTU-3 TO 1,875 CFM SUPPLY AIR/200 CFM
OUTSIDE AIR.
REBALANCE VAV BOX TO MAXIMUM 500 CFM.
NEW WORK NOTES
DESCRIPTIONNO.
T
VAV-1-1
RTU-8
TRTU-8
EF-19
TCUH-A5
CUH-A5
C
D
D
A
Z 65
20"/12"
8"/8"
CORRIDOR
CONF RM
CLINIC
GREEN ROOM
REST
NURSE
PRINCIPAL
AUDITORIUM
STORAGE
SECURITY
VESTIBULE
LOBBY
TOILET
CLOSET
MAIN OFFICE
12"/12"
W
T VAV-1-23 3
W
14"/12"
Z
8"/8"
20"/12" UP
ASST.
PRINCIPAL
14"/12" UP
Z
W
C
C
C
14"/12"
WORK ROOM
H
B
B
B
14"/12" 8"/8"
B
14"/8"
12"/10"
8"ø
8"ø
12"/10"
FD FD
FD
NEWSOME PARK
ELEMENTARY SCHOOL
2809 S. LYNNHAVEN ROAD VA BEACH, VA 23452
TELEPHONE: (757)599-4415 PROJECT NUMBER: 23-061
4323 COX ROAD GLEN ALLEN, VA 23060
22 ENTERPRISE PARKWAY HAMPTON, VA 23666
01-12-2024
NEW WORK ROOF PLAN - MECHANICAL
SCALE: 1/8" = 1'-0"
RTU-8
EF-19
PROVIDE ROOFTOP UNIT, CONTROLS AND ROOF CURB
COMPLETE.
PROVIDE ROOF MOUNTED EXHAUST FAN, SUPPORTS
AND CONTROLS COMPLETE.
REFER TO "ROOF CURB SOUND ATTENUATION DETAIL"
ON DRAWING M3.01.
PROVIDE 1" CONDENSATE PIPING, ROUTE TO ROOF
DRAIN AND TURN DOWN.
PROVIDE CONDENSATE PIPING AND SUPPORTS
COMPLETE. REFER TO "COIL CONDENSATE TRAP
DETAIL" ON DRAWING M3.01.
REFER TO "PIPING SUPPORT DETAIL" ON DRAWING
M3.01.
NEW WORK NOTES
DESCRIPTIONNO.
HIGH ROOF
LOW ROOFOPEN TO BELOW
OPEN TO BELOW
OA
RD
NEWSOME PARK
ELEMENTARY SCHOOL
2809 S. LYNNHAVEN ROAD VA BEACH, VA 23452
TELEPHONE: (757)599-4415 PROJECT NUMBER: 23-061
4323 COX ROAD GLEN ALLEN, VA 23060
22 ENTERPRISE PARKWAY HAMPTON, VA 23666
01-12-2024
MORE USE VANED ELBOW.
X OR Y LESS THAN 12"
VD
VD
X OR W LESS THAN 12"
VDVD
VD
VD
VD
VDVD
X
R
R = W + W R = (W + W )/2
20° MAX.
W
WW
W
WW
WY
R = X+Y R = (X+Y)/2R = D
R
R R
Y
X
D
D
R
R R
RX
W
R = X+Y R = (X+Y)/2
R = W
PREFERRED OFFSET
FULL RADIUS WHERE POSSIBLE
FOR D OF 12" OR
D LESS THAN 12"
NOTE: ABOVE APPLY TO SUPPLY AND RETURN
X Y
YX
20° MAX.
RETURN ONLY
20° MAX.
FROM RECTANGULAR MAIN
ROUND DUCT TAKEOFF
1.5 D
D
D
C MORE THAN 12"
ACFM
C
CFM
BCFM Y
A
C CFM
CFM
x Y = X
X
CFM
CFM
CFM
CFM
CFM Y
C x Y = X
C LESS THAN 12"
A C
SD
A B
LOW VELOCITY DUCTWORK FITTING DETAILS
NOT TO SCALE
90° RADIUS ELBOWS OFFSETS
BRANCH TAKEOFFS 90° TEES
DUCTWORK CONSTRUCTION REQUIREMENTS
RETURN AIR
LOW PRESSURE SUPPLY AIR
SYSTEM PRESSURE CLASS SEAL CLASS
+1.0" WG
-1.0" WG
-1.0" WG
N/A
EXHAUST AIR
TRANSFER AIR
CLASS A
CLASS A
CLASS B
NOT REQUIRED
NOTE:
1. CONSTRUCT ALL DUCTWORK IN ACCORDANCE WITH "SMACNA" HVAC DUCT
CONSTRUCTION STANDARDS.
2. PROVIDE VOLUME DAMPERS FOR EACH BRANCH DUCT SERVING WATER SOURCE HEAT
PUMP.
3. ALL RECTANGULAR AND MITERED ELBOWS SHALL BE PROVIDED WITH TURNING VANES.
1 DIA.
HANGER WIRE TO STRUCTURE
SUPPLY AIR DIFFUSER FACE.
FINISHED CEILING SUPPORT
PREINSULATED FLEXIBLE DUCT
2" WIDE DUCT HANGER
TYPICAL CEILING DIFFUSER INSTALLATION DETAIL
NOT TO SCALE
INSULATION OVERLAPPING
DIFFUSER COLLAR
USE FOIL BACKED TAPE TO TRANSITION
TO FLEXIBLE DUCT INSULATION
(TYP ALL FLEXIBLE DUCTS)
FLEXIBLE DUCT SECURED WITH MECHANICAL
BAND CLAMPS, SEE SPECIFICATIONS FOR
ACCEPTABLE MATERIALS (TYP)
MINIMUM 2 DIAMETERS OF
STRAIGHT DUCT OR PROVIDE
EQUALIZING GRID AT DIFFUSER
OFFSET NO GREATER THAN D/8
WHEN FLEXIBLE RISER IS USED
RECTANGULAR TO ROUND EXPANDED
SIDE TAKE-OFF WITH DAMPER IN BRANCH
EXTERNAL INSULATION ON SHEET METAL
9"
9"
SECURE EACH
BRACKET WITH SHEET
METAL SCREW.
SECURE SUPPORT WITH
SCB-07 SECURITY BRACKET
PIPING SUPPORT DETAIL
NOT TO SCALE
CONDENSATE DRAIN PIPING
GALVANIZED CLAMP
BLACK UV STABILIZED
POLYPROPYLENE COPOLYMER BODY
WITH STRUCTURAL FOAM BASE.
MANUFACTURED BY "ROOF TOP BLOX".
GALVANIZED THREADED ROD
PRIME SURFACE WITH PRI-13 PRIMER. SECURE TO
ROOF SURFACE WITH ADH-12 STRUCTURAL ADHESIVE.
CONDENSATE (PVC) 4'-0" ON CENTERS
SYSTEM SPACING
BIRDSCREEN
MOTOR OUT OF AIRSTREAM
ROOF EXHAUST FAN DETAIL
NOT TO SCALE (TYPICAL FOR EF-19)
FACTORY INSTALLED
DISCONNECT SWITCH
CONDUIT AND WIRING
INSIDE ROOF CURB
EXHAUST DUCT
BACKDRAFT DAMPER
REFER TO ARCHITECTURAL
PLANS FOR FLASHING
REQUIREMENTS
FACTORY WIRING FROM
MOTOR TO DISCONNECT
MANUFACTURER'S
ROOF CURB
SLOPE
DRAIN
CLEANOUT (TYP)
UNIONS (TYP)
"H"
COIL CONDENSATE TRAP DETAIL
NOT TO SCALE (NEGATIVE PRESSURE)
NOTES:
1. "H" = (1" FOR EACH 1" OF MAXIMUM NEGATIVE STATIC PRESSURE) + 1".
2. "J" = HALF OF H.
3. "L" = H + J + PIPE DIAMETER + INSULATION.
4. SIZE TRAP IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
RUN TO NEAREST
ROOF DRAIN
"J" "L"
COIL
DRAIN
PAN
TYPICAL ROOFTOP UNIT
CONTINUOUS SEALER STRIP
FLASHING
METAL ROOF DECK
ROOFTOP CURB SOUND ATTENUATION DETAIL
EQUIPMENT SUPPORT - REFER TO
ARCHITECTURAL AND STRUCTURAL
DRAWINGS FOR ROOF WORK REQUIRED
ROOF MATERIAL AND INSULATION -
SEE ARCHITECTURAL DRAWINGS
12" HIGH INSULATED ROOF CURB
BY EQUIPMENT MANUFACTURER
EQUIPMENT BASE RAIL
BY UNIT MANUFACTURER
UNIT SUPPLY OR
RETURN AIR OPENING
FLEXIBLE DUCT
CONNECTOR
2 LAYERS OF "ROXUL" MODEL 1260,
1" (6 LBS/SF) THICK STONE WOOL
ACOUSTIC BLANKET INSULATION
TWO LAYERS 5/8"
GYPSUM BOARD
(TYPICAL FOR RTU-8)
REFER TO ARCHITECTURAL DRAWINGS FOR THERMAL INSULATION AND
OTHER ROOFING MATERIALS WITHIN THE ROOF CURB. ACOUSTICAL
MATERIALS DO NOT TAKE THE PLACE OF ROOFING MATERIALS WITHIN THE
ROOF CURB.
NOT TO SCALE
NEWSOME PARK
ELEMENTARY SCHOOL
2809 S. LYNNHAVEN ROAD VA BEACH, VA 23452
TELEPHONE: (757)599-4415 PROJECT NUMBER: 23-061
4323 COX ROAD GLEN ALLEN, VA 23060
22 ENTERPRISE PARKWAY HAMPTON, VA 23666
01-12-2024
SINGLE ZONE VAV PACKAGED ROOFTOP UNIT (RTU) SEQUENCE OF OPERATION
1. THE BUILDING'S DDC CONTROLLER SHALL ENABLE AND DISABLE THE
UNIT AND CONTROL AND MONITOR ALL POINTS OF CONTROL
DESCRIBED HEREIN. THE UNIT'S DDC CONTROLLER SHALL START
AND STOP THE SUPPLY FAN, CONTROL THE OUTSIDE AIR DAMPER
AND CONTROL THE RECIRCULATION DAMPER. THE UNIT CONTROLS
SHALL STAGE CONTROLS FOR DIRECT EXPANSION COOLING &
HEATING, MODULATE THE CONDENSER REHEAT COIL VALVE AND
MODULATE EMERGENCY ELECTRIC HEATING.
A. OCCUPIED:
1. WHEN THE ROOFTOP UNIT IS INDEXED TO THE OCCUPIED MODE,
THE SUPPLY AIR FAN SHALL BE ENABLED.
2. COOLING: ONCE THE SUPPLY AIR FAN OPERATION HAS BEEN
ESTABLISHED AS SENSED BY ITS RESPECTIVE PROOF OF FLOW
SWITCH, THE OUTSIDE AIR DAMPER SHALL OPEN TO ITS
RESPECTIVE MINIMUM VENTILATION POSITION AND THE RETURN
AIR DAMPER SHALL CLOSE PROPORTIONALLY. ON A RISE ABOVE
THE PROGRAMMED SPACE COOLING TEMPERATURE SET POINT
OF 74°F (ADJ.), THE UNIT SHALL BEGIN TO MODULATE THE
COMPRESSOR ON TO MAINTAIN THE COOLING SUPPLY AIR
TEMPERATURE OF 55°F (ADJ.). ON A FALL BELOW THE
PROGRAMMED SPACE TEMPERATURE SET POINT, THE REVERSE
SHALL OCCUR.
3. HEATING: ONCE THE SUPPLY AIR FAN OPERATION HAS BEEN
ESTABLISHED AS SENSED BY ITS RESPECTIVE PROOF OF FLOW
SWITCH, THE OUTSIDE AIR DAMPER SHALL MODULATE TO ITS
RESPECTIVE MINIMUM VENTILATION POSITION AND THE RETURN
AIR DAMPER SHALL CLOSE PROPORTIONALLY. THE SUPPLY FAN
SHALL MAINTAIN A CONSTANT SPEED. DISCHARGE AIR
TEMPERATURE SHALL BE MONITORED BY A DUCT-MOUNTED
TEMPERATURE SENSOR. ON A FALL BELOW THE PROGRAMMED
SPACE HEATING TEMPERATURE SET POINT OF 70°F (ADJ.), THE
UNIT MOUNTED CONTROLLER SHALL ENABLE THE COMPRESSOR
AND INDEX THE REVERSING VALVE TO THE HEATING POSITION.
THE UNIT MOUNTED CONTROLLER SHALL MODULATE THE
COMPRESSOR TO MAINTAIN THE SPACE HEATING TEMPERATURE
SETPOINT.
4. EMERGENCY ELECTRIC HEAT: UPON A CONTINUED FALL IN SPACE
TEMPERATURE, THE UNIT MOUNTED CONTROLLER SHALL
DE-ENERGIZE THE COMPRESSOR AND ENERGIZE EMERGENCY
ELECTRIC HEAT. ELECTRIC HEAT SHALL MODULATE TO MAINTAIN
THE SPACE HEATING TEMPERATURE SETPOINT. ON A RISE ABOVE
THE PROGRAMMED SPACE HEATING TEMPERATURE SET POINT,
THE UNIT MOUNTED CONTROLLER SHALL MODULATE DOWN AND
DE-ENERGIZE THE ELECTRIC HEATING COIL. UPON A CONTINUED
RISE IN SPACE TEMPERATURE, THE UNIT SHALL SWITCH BACK TO
PRIMARY HEAT PUMP HEATING.
5. ON A RISE IN SPACE RELATIVE HUMIDITY ABOVE THE SPACE
RELATIVE HUMIDITY SETPOINT OF 60% RH (ADJ.), IF AND ONLY IF
THE SPACE TEMPERATURE SETPOINT IS SATISFIED, THE OUTSIDE
AIR DAMPER SHALL MODULATE TO ITS MINIMUM POSITION (IF IN
ECONOMIZER MODE), THE RETURN AIR DAMPER SHALL MODULATE
PROPORTIONALLY OPEN AND THE DEHUMIDIFICATION CONTROL
SEQUENCE OF OPERATION SHALL BE ENABLED. THE DX COOLING
SHALL BE ENABLED AND CONTROLLED TO MAINTAIN THE
SATURATION TEMPERATURE SETPOINT OF 53°F (ADJ.) OFF THE DX
COIL. ON A FALL BELOW THE SPACE RELATIVE HUMIDITY
SETPOINT, THE REVERSE SHALL OCCUR. THE HOT GAS REHEAT
SOLENOID VALVE SHALL MODULATE TO MAINTAIN THE SPACE
TEMPERATURE SETPOINT.
6. WHEN THE OUTSIDE AIR TEMPERATURE IS 55°F (ADJ.) OR BELOW,
AND THE SPACE TEMPERATURE IS ABOVE ITS RESPECTIVE
PROGRAMMED COOLING TEMPERATURE SET POINT, THE
COMPRESSOR SHALL BE DISABLED AND THE OUTSIDE AND
RETURN AIR DAMPERS SHALL BE MODULATED OPEN AND CLOSED
RESPECTIVELY TO MAINTAIN THE SPACE TEMPERATURE
SETPOINT. ON A FALL BELOW THE SPACE TEMPERATURE
SETPOINT, THE OUTSIDE AIR DAMPER SHALL MODULATE TO ITS
MINIMUM POSITION AND THE RETURN AIR DAMPER SHALL
MODULATE PROPORTIONALLY OPEN. WHEN THE OUTSIDE AIR
TEMPERATURE RISES ABOVE 55°F, THE UNIT SHALL REVERT TO
ITS COOLING AND/OR HEATING SEQUENCES.
B. UNOCCUPIED:
1. WHEN THE ROOFTOP UNIT IS INDEXED TO THE UNOCCUPIED
MODE, THE OUTSIDE AIR DAMPER SHALL MODULATE FULLY
CLOSED, THE RETURN AIR DAMPER SHALL MODULATE FULLY
OPEN AND THE SUPPLY AIR FAN SHALL BE DISABLED.
2. COOLING: ON A RISE ABOVE THE PROGRAMMED HIGH LIMIT
SPACE TEMPERATURE SET POINT OF 80°F (ADJ.), THE SUPPLY AIR
FAN SHALL BE ENABLED. AFTER THE SUPPLY AIR FAN OPERATION
IS ESTABLISHED BY ITS RESPECTIVE CURRENT SENSING RELAY,
THE DX COOLING SHALL BE ENABLED TO MAINTAIN THE SPACE
TEMPERATURE SET POINT. ON A FALL BELOW THE UNOCCUPIED
HIGH LIMIT SPACE TEMPERATURE SET POINT, DX COOLING SHALL
BE DISABLED AND THE SUPPLY AIR FAN SHALL BE DISABLED.
3. HEATING: ON A FALL BELOW THE PROGRAMMED LOW LIMIT
SPACE TEMPERATURE SET POINT OF 60°F (ADJ.), THE SUPPLY AIR
FAN SHALL BE ENABLED. AFTER THE SUPPLY AIR FAN OPERATION
IS ESTABLISHED BY ITS RESPECTIVE CURRENT SENSING RELAY,
THE UNIT MOUNTED CONTROLLER SHALL ENABLE THE
COMPRESSOR AND INDEX THE REVERSING VALVE TO THE
HEATING POSITION. THE UNIT MOUNTED CONTROLLER SHALL
MODULATE THE COMPRESSOR TO MAINTAIN THE LOW LIMIT
SPACE TEMPERATURE SETPOINT. UPON A CONTINUED FALL IN
SPACE TEMPERATURE, THE UNIT MOUNTED CONTROLLER SHALL
MODULATE THE ELECTRIC HEATING COIL TO MAINTAIN THE LOW
LIMIT SPACE TEMPERATURE SETPOINT. ON A RISE ABOVE THE
PROGRAMMED LOW LIMIT SPACE TEMPERATURE SET POINT, THE
UNIT MOUNTED CONTROLLER SHALL MODULATE DOWN AND
DE-ENERGIZE THE ELECTRIC HEATING COIL. ON A CONTINUED
RISE ABOVE THE LOW LIMIT SPACE TEMPERATURE SET POINT,
THE UNIT MOUNTED CONTROLLER SHALL MODULATE DOWN AND
DE-ENERGIZE THE COMPRESSOR.
4. DEHUMIDIFICATION: ON A RISE IN SPACE RELATIVE HUMIDITY
ABOVE THE SPACE RELATIVE HUMIDITY SETPOINT OF 60% RH
(ADJ.), IF AND ONLY IF THE SPACE TEMPERATURE SETPOINT IS
SATISFIED, THE SUPPLY AIR FAN SHALL BE ENABLED. AFTER THE
SUPPLY AIR FAN OPERATION IS ESTABLISHED BY ITS RESPECTIVE
CURRENT SENSING RELAY, THE DX COOLING SHALL BE ENABLED
AND CONTROLLED TO MAINTAIN THE SATURATION TEMPERATURE
SETPOINT OF 53°F (ADJ.). THE HOT GAS REHEAT SOLENOID VALVE
SHALL MODULATE TO MAINTAIN THE UNOCCUPIED SPACE
TEMPERATURE SET POINT.
C. MORNING WARM-UP: ONCE THE DDC HAS COMMANDED THE UNIT
FROM THE UNOCCUPIED MODE TO THE OCCUPIED MODE, IF THE
RETURN AIR TEMPERATURE IS BELOW THE MORNING WARM-UP
TEMPERATURE SET POINT OF 70°F (ADJ.), THE WARM-UP MODE
SHALL BE INITIATED. THE UNIT MOUNTED CONTROLLER SHALL
ENABLE THE COMPRESSOR AND INDEX THE REVERSING VALVE TO
THE HEATING POSITION. THE OUTSIDE AIR DAMPER SHALL
REMAIN CLOSED DURING WARM-UP MODE. ON A RISE ABOVE THE
MORNING WARM-UP TEMPERATURE SETPOINT, THE UNIT
MOUNTED CONTROLLER SHALL DE-ENERGIZE THE COMPRESSOR.
D. MORNING COOL-DOWN: ONCE THE DDC HAS COMMANDED THE
UNIT FROM THE UNOCCUPIED MODE TO THE OCCUPIED MODE, IF
THE RETURN AIR TEMPERATURE IS ABOVE THE MORNING
COOL-DOWN TEMPERATURE SET POINT OF 74°F (ADJ.), THE
COOL-DOWN MODE SHALL BE INITIATED AND THE DX COOLING
SHALL BE ENABLED. THE OUTSIDE AIR DAMPER SHALL REMAIN
CLOSED DURING COOL-DOWN MODE. ON A FALL BELOW THE
MORNING COOL-DOWN TEMPERATURE, THE DX COOLING SHALL
BE DISABLED.
E. SINGLE ZONE VARIABLE AIR VOLUME: THE SUPPLY FAN SHALL
OPERATE CONTINUOUSLY BETWEEN A SPECIFIED MINIMUM AND
MAXIMUM SPEED. THE UNIT CONTROLLER SHALL MODULATE THE
SUPPLY FAN BETWEEN THE MINIMUM AND MAXIMUM BASED ON
HOW NEAR OR FAR THE SPACE TEMPERATURE IS AWAY FROM
SETPOINT.
F. BIPOLAR IONIZATION: THE BIPOLAR IONIZATION GENERATOR SHALL
BE POWERED BY A CONTROL TRANSFORMER PROVIDED WITH THE
UNIT BY THE UNIT MANUFACTURER. THE ION GENERATOR SHALL
CYCLE ON AND OFF WITH THE SUPPLY FAN. THE DUCT MOUNTED ION
SENSOR SHALL COMMUNICATE AN ALARM TO THE OWNER'S
WORKSTATION IF ION CONCENTRATION FALLS BELOW THE
ACCEPTABLE THRESHOLD WHILE THE ION GENERATOR IS
ENERGIZED.
(TYPICAL FOR RTU-1 THRU RTU-3)
POINT NAME
EXHAUST FANS
ENABLE/DISABLE
Hardware Points
AI
TREND
AO BI BO AV BV
X
XROOF MOUNTED EXHAUST FAN CONTROLS DIAGRAM
NOT TO SCALE
SHOW
ON
GRAPHIC
ALARM
MISCELLANEOUS
X X
Software Points
EF
BO EF ENABLE
LINE
VOLTAGE
GENERAL EXHAUST FANS
1. THE DDC SYSTEM SHALL START AND STOP THE DDC CONTROLLED EXHAUST AIR
FANS BASED ON A USER-DEFINED SCHEDULE. THE DDC SYSTEM SHALL
MONITOR COMMAND AND RUN STATUS INDICATIONS AND TRANSMIT AN ALARM
TO THE DDC OPERATOR'S WORKSTATION ANYTIME THE FAN'S COMMANDED
STATE DOES NOT MATCH THE RUN STATUS INDICATION.
2. FANS SHALL BE ENERGIZED AND REMAIN OPERABLE DURING OCCUPIED PERIODS
AS DETERMINED BY THE USER-DEFINED SCHEDULE.
EXHAUST FAN POINTS LIST
EA
(TYPICAL FOR EF-19)
NOTE: REFER TO DRAWING M4.02 FOR SINGLE ZONE VAV
PACKAGED ROOFTOP UNIT CONTROL POINTS AND
CONTROLS DIAGRAM.
NEWSOME PARK
ELEMENTARY SCHOOL
2809 S. LYNNHAVEN ROAD VA BEACH, VA 23452
TELEPHONE: (757)599-4415 PROJECT NUMBER: 23-061
4323 COX ROAD GLEN ALLEN, VA 23060
22 ENTERPRISE PARKWAY HAMPTON, VA 23666
01-12-2024
SINGLE ZONE VAV PACKAGED ROOFTOP UNIT (RTU) DDC CONTROLS DIAGRAM
NOT TO SCALE
AISPACE
TEMP.
CONTROLS
CONTRACTOR
PROVIDED SPACE
TEMPERTURE
SENSOR
S/S
SPEED
BACNET
STATUS
AO
BO
BI
ENTERING FAN AIR
TEMPERATURE
BI CONDENSATE
SWITCH ALARM
WIRED BY DDC
CONTRACTOR
TO ALARM UNIT
UNIT MANUFACTURER SHALL
PROVIDED ALL REFRIGERANT
MANAGEMENT CONTROLS AND
BACNET INTERFACE, COORDINATE
WITH DDC CONTRACTOR
XDOA
AO
OA DAMPER
FILTER
BI
RA
AI
RETURN AIR
TEMPERATURE
EA
AI
MIXED AIR
TEMPERATURE
BACNET COMM TO
NEXT CONTROLLER
BACNET COMM FROM
PREVIOUS CONTROLLER
AISPACE
HUMIDITY
CONTROLS
CONTRACTOR
PROVIDED
SPACE HUMIDITY
SENSOR
SA
AI
DUCT MOUNTED
DISCHARGE AIR
TEMPERATURE
SENSOR BI
DUCT
MOUNTED
ION SENSOR
BI-POLAR
IONIZATION
DEVICE
BI
RA DAMPER
DIFFERENTIAL
PRESSURE
GH
HOT GAS
REHEAT
AI MODULATING
HOT GAS
REHEAT…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .