Appendix D (Specs)

View the file

Other files for this federal contract opportunity

Other files attached to Duplex Strainers, newest first.
File Type Posted
N65540-15-T-5418-0001.pdf PDF
Duplex_Strainers_Q A.docx DOCX document
Approx._Duplex_Strainer_Inlet_ _Outlet_Dimensions.docx DOCX document
Duplex_Strainers_Appendix_F_-_Spec_8038_0003.docx DOCX document
Duplex_Strainers-Appendix_A.xlsx XLSX spreadsheet
N65540-15-T-5418_Redacted.pdf PDF
SOW_-_Duplex_Strainers_(17_Aug_2015).docx DOCX document
Duplex_Strainers_Appendix_C_-_Spec_8035_0002.docx DOCX document
Duplex_Strainers_Appendix_E_-_Spec_8037_0003.docx DOCX document
CDRLS DUPLEX_STRAINERS_1.PDF PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NAVSSES De-ionized Water Duplex Strainer Technical Specification Appendix D – UID 8036_0003 Date: June 2015

DE-IONIZED WATER DUPLEX STRAINER TECHNICAL SPECIFICATION DOCUMENT NAVSSES
Appendix D

June 2015

Table of Contents

Table of Contents2
List of Tables2
1Scope of this Specification3
2Equipment Overview3
3Applicable Codes, Standards, and Regulations3
4Rating, Conditions of Service, and Performance Warranty4
4.1Equipment Ratings, Materials, and Workmanship4
4.2Conditions of Service4
4.3Acceptance, Performance Warranty and Defects Liability4
5Performance Requirements4
6Inspections and Tests9

List of Tables

Table 1: Duplex Strainer Technical Requirements5
Table 2: Required Equipment Inspections and Tests10

Scope of this Specification A. This specification provides the technical requirements for the design, performance, construction, inspection, testing, and warranty of one (1) duplex strainer to support a facility de-ionized (DI) cooling water system.

B. This specification is broken down into the following sections:

1. Scope of this Specification

2. Equipment Overview

3. Applicable Codes, Standards, and Regulations

4. Rating, Conditions of Service, and Performance Warranty

5. Performance Requirements

6. Inspections and Tests C. Throughout this specification the following terms apply:

1. “Seller” refers to the Original Equipment Manufacturer (OEM) / Equipment Provider.

2. “Buyer” refers to Naval Ship Systems Engineering Station (NAVSSES).

3. “Manufacturer” refers to the party or parties that manufacture a part or parts of the equipment or material.

Equipment Overview A. The duplex strainer will be installed and operated indoors on the Government provided site at NAVSSES (Philadelphia, PA). The duplex strainer will be installed in the facility DI cooling water system. To mitigate any potential contamination of the system end users, a suitably sized full-flow duplex strainer will be installed downstream of the system plate heat exchanger and upstream of the supply branch connections to the end users.

Applicable Codes, Standards, and Regulations A. The equipment shall be in compliance with the latest applicable regulations of applicable industry standards such as the American Society of Mechanical Engineers (ASME), the American Society for Testing and Materials (ASTM), and the American Welding Society (AWS).

B. ASME Standards

ASME Section VIII, Div 1, Design and Fabrication of Pressure Vessels ASME B16.5, Pipe Flanges and Flanged Fittings ASME B40.1, Accuracy for Pressure Indicating Dial Type, Elastic Element Gauges

C. ASTM Standards

ASTM A182, Standard Specification for Forged or Rolled Alloy and Stainless Steel Pipe Flanges, Forged Fittings, and Valves and Parts for High-Temperature Service ASTM A312, Standard Specification for Seamless, Welded, and Heavily Cold Worked Austenitic Stainless Steel Pipes ASTM A403, Standard Specification for Wrought Austenitic Stainless Steel Piping Fittings

D. AWS Codes

AWS D1.1, Structural Welding Code - Steel Rating, Conditions of Service, and Performance Warranty Equipment Ratings, Materials, and Workmanship A. The equipment provided shall meet the performance data provided in Section 5 of this specification.

B. Materials used for work performed under this contract shall be new, of the highest quality, and suitable for the intended service conditions of the equipment.

C. Work shall be performed by skilled mechanics in the various crafts and be executed in a first class and workmanlike manner in accordance with recognized good practice in the industry.

Conditions of Service A. The equipment will be located indoors in a non-climate controlled space and shall be designed for, and be protected against, these prevailing conditions as well as those identified in this specification. The duplex strainer shall function at any continuous environmental temperature from 40° F to 122° F.

Acceptance, Performance Warranty and Defects Liability A. Acceptance of the equipment by the Buyer shall follow the successful completion of all tests identified in Section 6 of this specification, including the review and approval of all Seller test reports by the Buyer upon successful completion of all tests.

B. The Seller shall warrant that the equipment supplied shall be entirely suitable for the intended service and is free from faults in design, and is of sufficient capability to meet the specified performance requirements (Section 5).

C. The Seller shall warrant the equipment for a period of at least twelve (12) months from the date of delivery. This shall warrant all equipment furnished by the Seller against defects in design, material, and workmanship.

Performance Requirements A. General Construction:

· The strainer shall be of the duplex basket type with valves and constructed to be readily opened for examination, removal, and cleaning of the baskets. The strainer shall be provided with shifting means to permit changeover (the act of shifting flow from strainer basket to the other) without damage to any parts or disruption of normal system operation for basket removal / cleaning. The strainer compartments shall each have a set of vent and drain valves. A changeover mechanism and an equalizing feature shall be included in the design for the strainer. Flow through the basket shall be “inside-out”.

B. Safety Interlocks:

· Positive interlocks shall be provided to prevent the following operator actions:

· Changeover to an off-duty compartment when the off-duty compartment cover is off or when the drain and equalizing valves are open

· Remove or loosen the cover when the compartment is pressurized

· Open the drain valve on the compartment in service

C. The following technical requirements shall be satisfied by the provided duplex strainers:

Table 1: Duplex Strainer Technical Requirements

Design Requirement
Description
Notes / Technical Rationale
Strainers Required, Qty
1
Fluid Type
DI Water
Ensure compatibility with system fluid type.
Inlet / Outlet Pipe Nominal Size and SCH
8” NPS, SCH 40S
Ensure compatibility with system inlet / outlet pipe size connections.
Strainer Type
Duplex: 2 independent baskets
Strainer type will allow continuous system operation without disruption.
Specifications
Strainer and Header Bodies in accordance with ASME Section VIII, Div 1
Ensure compatibility with the standard ASME specification for strainer design.

Normal System Flow Rate through Strainer

1200 gpm
Ensure compatibility with the normal system flow rate.
Abnormal System Flow Rate through Strainer
1600 gpm
The duplex strainer shall be capable of withstanding the abnormal system flow rate for a very brief duration without being damaged.
Maximum Pressure Drop at Normal Flow, Clean Basket, Water Service
3.0 psid at 1200 gpm
Minimize the pressure drop across the duplex strainer and maximize the supply pressure to end users.
Maximum Pressure Drop at Normal Flow (psid), 80% Blockage, Water Service
5.25 psid
See above.
End Connection Configuration
Offset
Ensure compatibility with the standard configuration for large strainers.
Hydrostatic Test Pressure
225 psig
Ensure compatibility with the system hydrostatic test pressure.
Maximum Allowable Working Pressure (MAWP)
150 psig
Ensure compatibility with the system design pressure.
Design Temperature
150°F
Ensure compatibility with the system design temperature.
Working Temperature Range
35-107°F
Working temperature range is based on normal expected system temperatures.
Pipe Material
Stainless Steel 304 (ASTM A312, Grade TP-304)
Ensure compatibility with system materials.
Tee Fittings
Stainless Steel (ASTM A 403, Grade WP-304)
Ensure compatibility with system materials.
Class 150 Blind Cover Material
Stainless Steel 304 (ASTM A182, Grade F-304)
Ensure compatibility with system materials.
Basket Material
Stainless Steel 304
Ensure compatibility with system materials.
Gasket / O-ring Material
Nitrile Buna-N
Ensure compatibility with system water quality requirements.
End Connections: Inlet / Outlet Flange Sizes, Specification and Material
8” ASME B16.5 Class 150 Weld Neck, Stainless Steel 304 (ASTM A182, Grade F-304)
Ensure compatibility with system materials.
Shutoff Valves/Equalizing Valves – Material and Type
Stainless Steel 304 Butterfly Valves, Single Gear Operator

Stainless steel 304 ball valves (full port) for the changeover valves may also be used as an alternative. The use of two (2) 3-port ball valves in place of inlet and outlet valves for each side of the strainer may also be included as an alternative design. The equalizing valve shall be separately operated from the changeover valve so that the offline basket can be filled / vented prior to any opening of the inlet or outlet port for the offline basket.

Ensure compatibility with system materials.

Fastener Materials
Stainless Steel 304 or 316
Ensure compatibility with the system materials.
Perforation Size
1/8” on 3/16” or ¼” centers, staggered
System filtration requirement.
Minimum Open Area Ratio (OAR)
4:1 (min)
Required to reduce the time the strainer will operate without cleaning even when clogged.
Ratio of the Total Flow Area of the Basket to the Cross-sectional Area of the Discharge Piping
The total clear area (flow area) of the perforations should be not less than 3 times the cross-sectional area of the strainer discharge piping.
Required to reduce the time the strainer will operate without cleaning even when clogged.
Drains
2” NPT drain connections (qty 2) located at basket housing bottom to fully drain strainer

If drain valves (not required) are also provided by the Seller, drain valves shall be 2” ball valves with a hose connection and cap.

Required to drain strainer.

Vents
½” NPT vent connections (qty 2) located on basket covers to fully vent strainer

If vent valves (not required) are also provided by the Seller, vent valves shall be ½” ball valves with a hose connection and cap.

Required to vent strainer.

Cover Design
Quick open covers are required: T-bolt hinged covers, davit assembly covers, yoke hinged covers, or quick opening covers shall be installed; the covers shall effect a positive seal on a gasket or o-ring recessed in the body
Ensure easy accessibility of the strainer baskets for cleaning / removal.
Header Design
Welded headers in accordance with ASME Section VIII, Div 1
Maximum Flange-to-Flange Dimension
30” (max)
Ensure duplex strainer can be installed in the current piping arrangement.
Maximum Height of Duplex Strainer
54” (max) as measured from base of strainer to the top of strainer cover
Minimize the pull space required.
Maximum Horizontal Distance between Strainer Basket Vertical Centerlines
60” (max) as measured horizontally between the vertical centerlines of the strainer baskets
Ensure duplex strainer can be installed in the current piping arrangement.
Additional Options – Differential Pressure (DP) Gauge (NOT REQUIRED BUT CAN BE PROVIDED BY SELLER IF AVAILABLE)
A DP gauge, connections, tubing, and instrumentation valves may be supplied by the Seller with the duplex strainer.

If supplied, each DP gauge shall be as follows: 0-10 psid range, 2 psi figure intervals, 0.25 or 0.5 psi smallest gradation, +/- 1.0% accuracy of span, gauge shall be red-lined per DP (max) at normal system flow (clean); required gauge connections, tubing, and valves shall be provided by the Seller; DP gauge shall be tested and calibrated in accordance with the requirements of ASME B40.1 Class 1A or equal.

DP gauge will facilitate local monitoring of the DP across the strainer and initiate the cleaning process if required.

Additional Options – DP Switch (NOT REQUIRED BUT CAN BE PROVIDED BY SELLER IF AVAILABLE)
A DP Switch, switch connections, tubing, and instrumentation valves may be supplied by the Seller with the duplex strainer.

If supplied, the DP switch shall be as follows: 0-10 psid range, stainless steel wetted materials and pressure connections, watertight enclosure, adjustable setpoint, SPDT or 2 SPDT contacts.

DP switch will provide remote alarm indication and initiate the cleaning process if required.

Inspections and Tests A. Final inspection and testing of the equipment shall be performed by the Seller or Manufacturer as follows:

Table 2: Required Equipment Inspections and Tests

A. General
The duplex strainer shall be subjected to the following tests by the Seller or Manufacturer. The Seller or Manufacturer shall have a documented program for the application, calibration, and maintenance of gages and instruments used during these tests.
B. Quality Assurance
Quality Assurance for the duplex strainer shall be based on the requirements of ASME Boiler and Pressure Vessel Code, Section VIII, Division 1.
C. Hydrostatic Test
The completely assembled duplex strainer shall be tested by the Seller or Manufacturer to a pressure equal to 150% of the design pressure (150 psi) for a duration of 60 minutes. A duplex strainer not maintaining zero leakage shall be rejected. The testing medium shall be water.
D. Tightness Test (Leakage)
The duplex strainer shall be tested by the Seller or Manufacturer for a duration of 30 minutes to verify the seal tightness of each changeover valve at 100% of design pressure (150 psi) using water as the test medium. A duplex strainer not maintaining zero leakage shall be rejected. The observation of wetting at the fluid boundary formed by the seal does not constitute leakage. To be called leakage, the fluid must form drops that become large enough to drop or flow away from the point of formation and into the basket compartment.
E. Visual and Dimensional Inspection
The duplex strainer shall be visually and dimensionally examined by the Seller or Manufacturer to verify conformance to the requirements of this specification and the applicable outline / detail drawing. A duplex strainer having one (1) or more defects shall be rejected.
F. Operating Test
The duplex strainer shall be tested by the Seller or Manufacturer for the pressure drop (clean) across the strainer at the specified normal design flow (1200 gpm) and pressure using water as the test medium. Flow through the basket shall be “inside-out”. There shall be no internal leakage that can bypass the strainer basket. A duplex strainer exceeding the specified clean pressure drop (3.0 psid) at normal design flow (1200 gpm) shall be rejected.
G. Non-destructive Test
The inspection of all strainer welds and fabrication by the Seller or Manufacturer shall be in accordance with the requirements of AWS D1.1 or equal.
H. Verification of Safety Interlock Effectiveness
The Seller or Manufacturer shall demonstrate that the actions prohibited in Section 5.B are positively prevented by the interlocks. A strainer permitting the actions in Section 5.B shall be rejected.
I. Final Inspection
The Seller or Manufacturer shall perform a post fabrication inspection to confirm that the equipment is in conformance to this specification, conformance to the final outline and detail drawings, and the equipment suitable for service including identification of missing or loose hardware and proper mechanical fit up.