Appendix C (Specs)
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Duplex_Strainers_Q A.docx | DOCX document | |
| N65540-15-T-5418-0001.pdf | ||
| Approx._Duplex_Strainer_Inlet_ _Outlet_Dimensions.docx | DOCX document | |
| Duplex_Strainers_Appendix_E_-_Spec_8037_0003.docx | DOCX document | |
| CDRLS DUPLEX_STRAINERS_1.PDF | ||
| N65540-15-T-5418_Redacted.pdf | ||
| SOW_-_Duplex_Strainers_(17_Aug_2015).docx | DOCX document | |
| Duplex_Strainers_Appendix_D_-_Spec_8036_0003.docx | DOCX document | |
| Duplex_Strainers_Appendix_F_-_Spec_8038_0003.docx | DOCX document | |
| Duplex_Strainers-Appendix_A.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NAVSSES Closed Loop Cooling Water Duplex Strainer Technical Specification Appendix C – UID 8035_0002 Date: June 2015
| CLOSED LOOP COOLING WATER DUPLEX STRAINER TECHNICAL SPECIFICATION DOCUMENT NAVSSES |
| Appendix C |
June 2015
Table of Contents
| List of Tables | 2 | |
| 1 | Scope of this Specification | 3 |
| 2 | Equipment Overview | 3 |
| 3 | Applicable Codes, Standards, and Regulations | 3 |
| 4 | Rating, Conditions of Service, and Performance Warranty | 4 |
| 4.1 | Equipment Ratings, Materials, and Workmanship | 4 |
| 4.2 | Conditions of Service | 4 |
| 4.3 | Acceptance, Performance Warranty and Defects Liability | 4 |
| 5 | Performance Requirements | 4 |
| 6 | Inspections and Tests | 11 |
List of Tables
| Table 1: Duplex Strainer Technical Requirements | 5 |
| Table 2: Required Equipment Inspections and Tests | 11 |
Scope of this Specification A. This specification provides the technical requirements for the design, performance, construction, inspection, testing, and warranty of three (3) duplex strainers to support a facility closed loop cooling water system.
B. This specification is broken down into the following sections:
1. Scope of this Specification
2. Equipment Overview
3. Applicable Codes, Standards, and Regulations
4. Rating, Conditions of Service, and Performance Warranty
5. Performance Requirements
6. Inspections and Tests C. Throughout this specification the following terms apply:
1. “Seller” refers to the Original Equipment Manufacturer (OEM) / Equipment Provider.
2. “Buyer” refers to NAVSSES (Naval Ship Systems Engineering Station).
3. “Manufacturer” refers to the party or parties that manufacture a part or parts of the equipment or material.
Equipment Overview A. The duplex strainers will all be installed and operated indoors on the Government provided site at NAVSSES (Philadelphia, PA). The duplex strainers will be installed in a facility closed loop cooling water system. To mitigate any potential contamination of the system end users, a suitably sized full-flow duplex strainer will be installed downstream of the system plate heat exchanger and upstream of each supply branch main header to the associated end users.
Applicable Codes, Standards, and Regulations A. The equipment shall be in compliance with the latest applicable regulations of applicable industry standards such as the American Society of Mechanical Engineers (ASME), American Society for Testing and Materials (ASTM), and the American Welding Society (AWS).
B. ASME Standards
ASME Section VIII, Div 1, Design and Fabrication of Pressure Vessels ASME B16.5, Pipe Flanges and Flanged Fittings ASME B40.1, Accuracy for Pressure Indicating Dial Type, Elastic Element Gauges
C. ASTM Standards
ASTM A182, Standard Specification for Forged or Rolled Alloy and Stainless Steel Pipe Flanges, Forged Fittings, and Valves and Parts for High-Temperature Service ASTM A312, Standard Specification for Seamless, Welded, and Heavily Cold Worked Austenitic Stainless Steel Pipes ASTM A403, Standard Specification for Wrought Austenitic Stainless Steel Piping Fittings
D. AWS Codes
AWS D1.1, Structural Welding Code - Steel Rating, Conditions of Service, and Performance Warranty Equipment Ratings, Materials, and Workmanship A. The equipment provided shall meet the performance data provided in Section 5 of this specification.
B. Materials used for work performed under this contract shall be new, of the highest quality, and suitable for the intended service conditions of the equipment.
C. Work shall be performed by skilled mechanics in the various crafts and be executed in a first class and workmanlike manner in accordance with recognized good practice in the industry.
Conditions of Service A. The equipment will be located indoors in a non-climate controlled space and shall be designed for, and be protected against, these prevailing conditions as well as those identified in this specification. The duplex strainers shall function at any continuous environmental temperature from 40° F to 122° F.
Acceptance, Performance Warranty and Defects Liability A. Acceptance of the equipment by the Buyer shall follow the successful completion of all tests identified in Section 6 of this specification, including the review and approval of all Seller test reports by the Buyer upon successful completion of all tests.
B. The Seller shall warrant that the equipment supplied shall be entirely suitable for the intended service and is free from faults in design, and is of sufficient capability to meet the specified performance requirements (Section 5).
C. The Seller shall warrant the equipment for a period of at least twelve (12) months from the date of delivery. This shall warrant all equipment furnished by the Seller against defects in design, material, and workmanship.
Performance Requirements A. General Construction:
· The strainers shall be of the duplex basket type with valves and constructed to be readily opened for examination, removal, and cleaning of the baskets. The strainers shall be provided with shifting means to permit changeover (the act of shifting flow from strainer basket to the other) without damage to any parts or disruption of normal system operation for basket removal / cleaning. The strainer compartments shall each have a set of vent and drain valves. A changeover mechanism and an equalizing feature shall be included in the design for each strainer. Flow through the basket shall be “inside-out”.
B. Safety Interlocks:
· Positive interlocks shall be provided to prevent the following operator actions:
· Changeover to an off-duty compartment when the off-duty compartment cover is off or when the drain and equalizing valves are open
· Remove or loosen the cover when the compartment is pressurized
· Open the drain valve on the compartment in service
C. The following technical requirements shall be satisfied by the provided duplex strainers:
Table 1: Duplex Strainer Technical Requirements
| Design Requirement |
| Description |
| Notes / Technical Rationale |
| Duplex Strainer 1 |
| Duplex Strainers 2 and 3 |
| Qty Required |
| One (1) strainer |
| Two (2) strainers |
| Fluid Type |
| Freshwater |
| Freshwater |
| System fluid. |
| Inlet / Outlet Pipe Nominal Size and SCH |
| 3” NPS, SCH 40S |
| 12” NPS, SCH 40S |
| Compatibility with system inlet / outlet pipe size connections. |
| Strainer Type |
| Duplex: 2 independent baskets |
| Duplex: 2 independent baskets |
| Strainer type will allow continuous system operation without disruption. |
| Specifications |
| Strainer and Header Bodies in accordance with ASME Section VIII, Div 1 |
| Strainer and Header Bodies in accordance with ASME Section VIII, Div 1 |
| Standard ASME specifications for strainer design. |
Normal System Flow Rate
| 145 gpm (Seller shall include 20% margin above this value for system growth) |
| 2100 gpm (Duplex Strainer 2); 2900 gpm (Duplex Strainer 3) |
| System normal operating flow rates. |
| Maximum Pressure Drop at Normal Flow, Clean Basket, Water Service |
| 1.50 psid |
| 1.25 psid (Duplex Strainer 2); 2.5 psid (Duplex Strainer 3) |
| Maximum Pressure Drop at Normal Flow, 70% or 80% Blockage, Water Service |
| 2.625 psid (70% Blockage) |
| 4.5 psid (Duplex Strainer 2, 80% Blockage); 9.00 psid (Duplex Strainer 3, 80% Blockage) |
| End Connections (Sizes and Types) |
| 3” 150# RF ASME B16.5, inlet/outlet |
| 12” 150# RF ASME B16.5, inlet/outlet |
| Ensure compatibility with system flanges. |
| End Connection Configuration |
| Offset |
| Offset |
| Standard strainer configuration. |
| Hydrostatic Test Pressure |
| 225 psig |
| 225 psig |
| System hydrostatic test pressure. |
| MAWP |
| 150 psig |
| 150 psig |
| System design pressure. |
| Design Temperature |
| 150°F |
| 150°F |
| System design temperature. |
| Working Temperature |
| 35-100°F |
| 35-100°F |
| Based on normal expected system temperatures. |
| Pipe Material |
| Stainless Steel 304 (ASTM A312, Grade TP-304) |
| Stainless Steel 304 (ASTM A312, Grade TP-304) |
| Ensure compatibility with system materials. |
| Tee Fittings |
| Stainless Steel (ASTM A 403, Grade WP-304) |
| Stainless Steel (ASTM A 403, Grade WP-304) |
| Ensure compatibility with system materials. |
| Class 150 Blind Cover Material |
| Stainless Steel 304 (ASTM A182, Grade F-304) |
| Stainless Steel 304 (ASTM A182, Grade F-304) |
| Ensure compatibility with system materials. |
| Basket Material |
| Stainless Steel 304 |
| Stainless Steel 304 |
| Ensure compatibility with system materials. |
| Gasket / O-ring Material |
| Nitrile Buna-N |
| Nitrile Buna-N |
| Ensure compatibility with system water quality requirements. |
| Inlet / Outlet Flange Specification and Material |
| ANSI B16.5 Class 150 Weld Neck, Stainless Steel 304 (ASTM A182, Grade F-304) |
| ANSI B16.5 Class 150 Weld Neck, Stainless Steel 304 (ASTM A182, Grade F-304) |
| Ensure compatibility with system materials. |
| Shutoff Valves/Equalizing Valves – Material and Type |
| Stainless Steel 304 Butterfly Valves, Single Gear Operator |
Stainless steel 304 ball valves (full port) for the changeover valves may also be used as an alternative. The use of two 3-port ball valves in place of inlet and outlet valves for each side of the strainer may also be included as an alternative design. The equalizing valve shall be separately operated from the changeover valve so that the offline basket can be filled / vented prior to any opening of the inlet or outlet port for the offline basket.
Stainless Steel 304 Butterfly Valves, Single Gear Operator Stainless steel 304 ball valves (full port) for the changeover valves may also be used as an alternative. The use of two 3-port ball valves in place of inlet and outlet valves for each side of the strainer may also be included as an alternative design. The equalizing valve shall be separately operated from the changeover valve so that the offline basket can be filled / vented prior to any opening of the inlet or outlet port for the offline basket.
Ensure compatibility with system materials.
| Fastener Materials |
| Stainless Steel 304 or 316 |
| Stainless Steel 304 or 316 |
| Ensure compatibility with system materials. |
| Perforation Sizes |
| 1/8” on 3/16” or ¼” centers, staggered |
| 1/8” on 3/16” or ¼” centers, staggered |
| System filtration requirements |
| Minimum Open Area Ratio (OAR) |
| 4:1 (min) |
| 4:1 (min) |
| 4:1 OAR (min) is required to reduce the time the strainer will operate without cleaning even when clogged. |
| Ratio of the Total Flow Area of the Basket to the Cross-sectional Area of the Discharge Piping |
| The total clear area (flow area) of the perforations should be not less than 3 times the cross-sectional area of the strainer discharge piping. |
| The total clear area (flow area) of the perforations should be not less than 3 times the cross-sectional area of the strainer discharge piping. |
| Drains |
| 3/4” NPT drain connections (qty 2) located at basket housing bottom to fully drain strainer |
If drain valves (not required) are also provided by the Seller, drain valves shall be 3/4” ball valves with a hose connection and cap.
2” NPT drain connections (qty 2) located at basket housing bottom to fully drain strainer If drain valves (not required) are also provided by the Seller, drain valves shall be 2” ball valves with a hose connection and cap.
Required to drain strainer.
| Vents |
| ½” NPT vent connections (qty 2) located on basket covers to fully vent strainer |
If vent valves (not required) are also provided by the Seller, vent valves shall be ½” ball valves with a hose connection and cap.
½” NPT vent connections (qty 2) located on basket covers to fully vent strainer If vent valves (not required) are also provided by the Seller, vent valves shall be ½” ball valves with a hose connection and cap.
Required to vent strainer.
| Cover Design |
| Quick open covers are required: T-bolt hinged covers, davit assembly covers, yoke hinged covers, or quick opening covers shall be installed; the covers shall effect a positive seal on a gasket or o-ring recessed in the body |
| Quick open covers are required: T-bolt hinged covers, davit assembly covers, yoke hinged covers, or quick opening covers shall be installed; the covers shall effect a positive seal on a gasket or o-ring recessed in the body |
| Ensure easy accessibility of the strainer baskets for cleaning / removal. |
| Header Design |
| Welded headers in accordance with ASME Section VIII, Div 1 |
| Welded headers in accordance with ASME Section VIII, Div 1 |
| Maximum Flange-to-Flange Dimension |
| 22” (max) |
| 36” (max) |
| Ensure duplex strainer can be installed in the current piping arrangement. |
| Maximum Height of Duplex Strainer |
| 42” (max) as measured from base of strainer to the top of strainer cover |
| 72” (max) as measured from base of strainer to the top of strainer cover |
| Minimize the pull space required. |
| Maximum Horizontal Distance between Strainer Basket Vertical Centerlines |
| 36” (max) as measured horizontally between the vertical centerlines of the strainer baskets |
| 72” (max) as measured horizontally between the vertical centerlines of the strainer baskets |
| Ensure duplex strainer can be installed in the current piping arrangement. |
| Additional Options – DP Gauge (NOT REQUIRED BUT CAN BE PROVIDED BY SELLER IF AVAILABLE) |
| DP Gauge, gauge connections, and valves (if available) |
If supplied, each DP gauge shall be as follows: 0-10 psid range, 2 psi figure intervals, 0.25 or 0.5 psi smallest gradation, +/- 1.0% accuracy of span, gauge shall be red-lined per DP (max) at normal system flow (clean); required gauge connections, tubing, and valves shall be provided by the Seller; all DP gauges shall be tested and calibrated in accordance with the requirements of ASME B40.1 Class 1A.
DP Gauge, gauge connections, and valves (if available) If supplied, each DP gauge shall be as follows: 0-10 psid range, 2 psi figure intervals, 0.25 or 0.5 psi smallest gradation, +/- 1.0% accuracy of span, gauge shall be red-lined per DP (max) at normal system flow (clean); required gauge connections, tubing, and valves shall be provided by the Seller; all DP gauges shall be tested and calibrated in accordance with the requirements of ASME B40.1 Class 1A.
DP Gauge will facilitate local monitoring of the DP across strainer and initiate cleaning process if required.
| Additional Options – DP Switch (NOT REQUIRED BUT CAN BE PROVIDED BY SELLER IF AVAILABLE) |
| DP Switch and switch connections (if available) |
If supplied, each DP switch shall be as follows: 0-10 psid range, stainless steel wetted materials and pressure connections, watertight enclosure, adjustable setpoint, SPDT or 2 SPDT contacts DP Switch and switch connections (if available) If supplied, each DP switch shall be as follows: 0-10 psid range, stainless steel wetted materials and pressure connections, watertight enclosure, adjustable setpoint, SPDT or 2 SPDT DP switch will facilitate remote monitoring with alarm of the DP across strainer and initiate cleaning process if required.
Inspections and Tests A. Final inspection and testing of the equipment shall be performed by the Seller or Manufacturer as follows:
Table 2: Required Equipment Inspections and Tests
| A. General |
| Each duplex strainer shall be subjected to the following tests by the Seller or Manufacturer. The Seller or Manufacturer shall have a documented program for the application, calibration, and maintenance of gages and instruments used during these tests. |
| B. Quality Assurance |
| Quality Assurance for each duplex strainer shall be based on the requirements of ASME Boiler and Pressure Vessel Code, Section VIII, Division 1. |
| C. Hydrostatic Test |
| Each completely assembled duplex strainer shall be tested by the Seller or Manufacturer to a pressure equal to 150% of the design pressure (150 psi) for a duration of 60 minutes. A duplex strainer(s) not maintaining zero leakage shall be rejected. The testing medium shall be water. |
| D. Tightness Test (Leakage) |
| Each duplex strainer shall be tested by the Seller or Manufacturer for a duration of 30 minutes to verify the seal tightness of each changeover valve at 100% of design pressure (150 psi) using water as the test medium. A duplex strainer(s) not maintaining zero leakage shall be rejected. The observation of wetting at the fluid boundary formed by the seal does not constitute leakage. To be called leakage, the fluid must form drops that become large enough to drop or flow away from the point of formation and into the basket compartment. |
| E. Visual and Dimensional Inspection |
| Each duplex strainer shall be visually and dimensionally examined by the Seller or Manufacturer to verify conformance to the requirements of this specification and the applicable drawing. A duplex strainer(s) having one (1) or more defects shall be rejected. |
| F. Operating Test |
| Each duplex strainer shall be tested by the Seller or Manufacturer for the pressure drop (clean) across the strainer at the specified design flow capacity and pressure using water as the test medium. Flow through the basket shall be “inside-out”. There shall be no internal leakage that can bypass the strainer basket. A duplex strainer(s) exceeding the specified clean pressure drop at design flow capacity shall be rejected. |
| G. Non-destructive Test |
| The inspection of all strainer welds and fabrication by the Seller or Manufacturer shall be in accordance with the requirements of AWS D1.1 or equal. |
| H. Verification of Safety Interlock Effectiveness |
| The Seller or Manufacturer shall demonstrate that the actions prohibited in Section 5.B are positively prevented by the interlocks. A strainer permitting the actions in Section 5.B shall be rejected. |
| I. Final Inspection |
| The Seller or Manufacturer shall perform a post fabrication inspection to confirm that the equipment is in conformance to this specification, conformance to the final outline and detail drawings, and the equipment suitable for service including identification of missing or loose hardware and proper mechanical fit up. |