Attachment_5_-_Tech_Capability_Cert.docx
DOCX document 22 KB Posted
- Attached to
- Rental of One HAZMAT Container
- Solicitation number
- N4215819Q0041
About this file
Technical Capability Cert
View the file
Other files
| File | Type | Posted |
|---|---|---|
| N4215819Q0041_-_Amendment_1_-_0003.pdf | ||
| Attachment_2_-_Enclosure_2.docx | DOCX document | |
| Attachment_1_-_Enclosure_1.doc | DOC document | |
| Solicitation_-_N4215819Q0041.pdf | ||
| Attachment_4_-_Enclosure_4.docx | DOCX document | |
| Attachment_3_-_Enclosure_3.docx | DOCX document | |
| Solicitation_-_N4215819Q0041.pdf | ||
| Technical_Capabilities_Cert.pdf | ||
| Attachment_4_-_Enclosure_4.docx | DOCX document | |
| Attachment_2_-_Enclosure_2.docx | DOCX document | |
| Attachment_3_-_Enclosure_3.docx | DOCX document | |
| Attachment_1_-_Enclosure_1.doc | DOC document |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N42158-19-Q-0004 ATTACHMENT 1
TECHNICAL CAPABILITY CERTIFICATIONS
Vendor shall self-certify that the equipment and services proposed either meets or does not meet the Government’s minimum requirements specified in the associated Statement of Work (SOW) reference by initialing in the “YES” or “NO” area of the chart below.
Any deviation to the Government specifications shall be identified as such – A detailed explanation shall be provided for each negative response.
Note: In order to be considered for award, the table must be completed in its entirety and submitted with your quotation in accordance with FAR 52.212-1 Instructions of Offerors ADDENDUM.
Technical Capabilities Statement
Item #1 Specifications for One (1) HAZMAT Container with minimum dimensions of 8’ width x 9’ height x 20’ length (see enclosures)
| Shall be provided with the following capabilities, features, and specifications: |
| YES |
| NO |
General Requirements
· Contractor shall provide one (1) HAZMAT Container with minimum dimensions of 8’ width x 9’ height x 20’ length.
· The HAZMAT Container shall provide a space that is suitable for the storage of hazardous material. It shall contain a sump to collect leakage and a dry chemical fire suppression system as described in the following sections.
· Shall have a minimum sump capacity of 850 gallons__________________
· Shall have A/C and heat required to maintain unit at 70 degrees at all times, year round
· Shall have a dry chemical fire suppression system which meets all NFPA, and OSHA requirements.
· Shall have a minimum 120/240V, 100A, 3 wire, single phase UL listed load center (NEMA 3R)_______
· Shall have exterior camlok connection box feeding a 600V, 40A 2-pole circuit breaker enclosed in a NEMA 3R enclosure feeding a 15kva, 440/240V primary:240/120V secondary, single-phase transformer. This transformer to provide power to load center. See enclosure (1) and (2).
· Shall be in compliance with applicable NFPA and NEC requirements
· Hurricane proof to 110 MPH winds; must also be water resistant.
· All doors are to swing outward. Cipher locks are not required for the HAZMAT enclosures; however, the doors must be capable of being locked.
· Energy efficient heat pump in each HAZMAT enclosure, in all cases, the unit must be able to maintain 70 degrees Fahrenheit in summer or winter. The unit shall be energy star rated.
· There shall be no windows in the units.
· Floor covering shall be a steel grate allowing the flow of hazardous material directly into the sump. The steel grating shall be designed to withstand the exposure to hazardous material.
Electrical Requirements
· One row of surface mount fluorescent twin tube strip type interior light fixtures with energy efficient electronic ballast and 32 watt fluorescent bulbs. Mount in center of enclosure. Light fixtures shall be blast proof.
· All Wire must be THHN or THWN, 75 degrees Celsius (min), size as indicated. Do not substitute wiring type/temperature rating unless the ampacity of wire and conduit fill requirements are evaluated to ensure NEC compliance.
· Electrical Metallic Tubing (EMT) is specified on drawings. The NEC requires EMT to be supported within 3 ft of each box or conduit body and supported every 10 ft (min).
· Liquid Tight Flexible Metal Conduit (LFMC) may be used on the exterior instead of EMT. The NEC requires LFMC to be supported within 1 ft of each box or conduit body and supported every 4.5 ft (min).
· The NEC requires the following color code:
· Neutral (grounded conductor) = white
· Ground (Equipment grounding conductor) = green
· Exterior wiring to include a camlok connection box feeding a 600 Volt, 40 amp, 2 pole circuit breaker enclosed in a NEMA 3R circuit breaker enclosure. This is to feed a 15 kva, 480/240 volt primary, 240/120 volt secondary single phase transformer (see enclosure (2)). See enclosure (4) for a list of exterior equipment. Equivalent material may be substituted.
· Contractor may use a fusible disconnect switch, NEMA 3R with current limiting fuses rated the same size as the circuit breaker in the enclosure (2) ( PC-4 and PC-5).
· Receptacles: 120 volt, 20 Amp Quad type receptacle wired on a #12 AWG (min of two Quad Receptacles per circuit). Provide (1) ea 120 volt, 15 amp duplex GFCI test type receptacle wired on a dedicated circuit mounted on the exterior in a weatherproof box beside the HVAC unit.
· A typical transformer wiring diagram is shown in enclosure (3) in the drawing, use the manufacturers wiring schematic to connect transformer (schematic usually located on front panel of transformer). Transformer size may be adjusted depending on load demand of HAZMAT enclosure.
· Input connections of the HAZMAT enclosures electrical system shall be per NEC requirements and using camlok receptacles (see enclosure (1)).
· Wiring of units electrical system shall comply NFPA 70 (National Electric Code) where applicable.
· Transformer frame shall be bonded to unit frame using appropriate size bonding jumper from NEC table 250.122, per NEC.
Relocation
· The equipment shall be provided with a lifting sketch/rigging diagram that meets the requirements of Section (11).
· Units shall be stiffened as required to eliminate swaying of the upper units.
· Units are to be outfitted with suitable attachments for overhead AND forklift lifting.
In order to be considered technically acceptable, this form must be completed in its entirety.
Vendor shall certify that his product meets or does not meet each specification listed above by initialing in the applicable YES or NO box beside each specification.
Print Name Signature
Vendor’s Certification is as of __________________.