Bldg 465 Replace Heatpump eProject # 1633010 Page 1 of 14
Europe, Africa and Southwest Asia – NAS Sigonella PWD
Building 465 Replace Heatpump eProject # 1633010
NAS Sigonella, Sicily, Italy Date: 25 January 2019
STATEMENT OF WORK
1. GENERAL INTENTION/GENERAL DESCRIPTION:
It is the declared and acknowledged intention and meaning to replace one existing heatpump at Building 465 Base Communication Office by means of a firm fixed price construction contract complete and ready for use. The following paragraphs are intended to provide amplifying or additional information with respect to specific details of the project and are not intended to subordinate any regulatory or statutory requirements contained in the contract. All work shall be performed in accordance with the Corps of Engineers Safety Manual, EM-385-1-1, the most current version, in accordance with Italian Laws, Norms and Regulations regarding Safety at Temporary Work Site (Norme per la Sicurezza nei Cantieri Temporanei e Mobili), and with all NFPA applicable codes (NFPA 101 & NFPA 99).
The contractor shall perform the following work:
2. LOCATION: The work to be performed is located at, NAS II, facility# 465
3. PERIOD OF PERFORMANCE: Ninety (90) calendar days.
4. DESCRIPTION OF WORK:
4.1 Secure power and hydronic lines connected to one AERMEC, damaged and beyond repair, heatpump unit at BLDG 465 Base Communication Office.
4.2 Provide for removal and disposal of the AERMEC heatpump unit.
4.3 Provide one new heatpump unit matching the same characteristics and accessories of the existing unit. See attached mechanical schedule of existing heatpump unit on sheet 465/M-606.
This task involves the replacement of the 2ea main interception valves, minor modifications to the hydronic connections and power supply circuitry. After installation restore connection to existing Direct Digital Control (DDC) system in order to operate as per its original design intent and sequence of operation.
4.4 Perform Test and Balance and commission new heatpump unit to ensure it meets the design performance and is seamlessly integrated into existing DDC system.
Bldg 465 Replace Heatpump eProject # 1633010 Page 2 of 14
5. SPECIAL SCHEDULING:
a. The Contractor shall have all materials approved and available before work begins.
b. The area of work will remain in operation during the entire performance period, and the
Contractor shall conduct his operations so as to cause the least possible interference with the normal operations of the activity. The work under this contract requires special attention to scheduling interruptions of utility systems and Activity operations.
Interruptions of utility services will be permitted only when they will cause no interference with the operations of the activity. All utility cutovers shall be made after the Government's regular working hours or on weekends. Anticipated costs of utility cutovers shall be included in the bid.
c. Outages/Road closures: Permission to interrupt and Station roads or utility service shall be requested in writing a minimum of 21 working days prior to the desired date of interruption. Make utility cutovers and interruptions after normal working hours or on weekends or Government holidays. Interruption to water, sanitary sewer, storm sewer, telephone service, electric service, air conditioning, heating, fire alarm, compressed air, and gas shall be subject to the restrictions above.
6. CONTRACT DRAWINGS AND SPECIFICATIONS:
The work shall conform to the specifications and the contract sketches identified in the list below:
LIST OF SKETCHES
LIST OF DRAWINGS DESCRIPTION
1 of 3 Photos of Existing Heatpump 2 of 3 Existing Heatpump Cutsheets 3 of 3 As-Built Drawings
7. SUBMITTALS:
Pre-Construction Submittals
SUBMITTAL/BENCHMARK DURATION BENCHMARK RECEIVED STATUS
1 Quality Control Plan 15 Days After Award
2 Specific Safety Data Sheets 15 Days After Award
3 Construction Schedule 15 Days After Award
Bldg 465 Replace Heatpump eProject # 1633010 Page 3 of 14
4 Safety and Health Plan 15 Days After Award
5 Schedule of Prices 15 Days After Award
6 Operation and Maintenance
Information
15 Days After BOD
7 Licenses, Permits, and
Declarations
15 Days After Award
8 Badge Requests 10 Days After Award
9 Submittal Register 15 Days After Award
10 Performance/Payment Bonds 15 Days After Award
11 Environmental Protection Plan 15 Days After Award
12 Certificates of Insurance 15 Days After Award
13 DD1354 (if applicable) 45 Days Prior to BOD
Note:
Quality Control Plan - Attached Contractor QC Plan Assessment Checklist must be filled out and attached with Quality Control Plan Accident Prevention Plan - Attached Accident Prevention Plan NAVFAC Reviewer Checklist must be filled out and attached with Accident Prevention Plan
Construction Submittals The contractor may submit material and product cut-sheets, certifications, warranty info, etc.
from the intended manufacturer with the specification section in which submittal of that material or product is required during design submittals.
Material submitted for approval shall be accompanied by complete information concerning the material, articles, and/or design proposed for use in sufficient detail to show compliance with the intent of the contract prior to incorporation into the work, Approval thereof will not be construed as relieving the contractor of compliance with the specification even if such approval is made in writing, unless the attention of the Contracting Office is called to the non-complying features by letter accompanying the submitted matter.
Partial submittals of less than the whole of any system made up of interdependent components will not be considered. Approval of drawings, cuts, and samples by the Contracting Officer shall not be construed as a complete check or approval of the detailed dimensions, weights, gauges, and similar details of the proposed articles. The conformance of such details with the contract requirement, together with the necessary coordination of dimensions and details with the contract requirement, together with the necessary coordination of dimensions and details between the various elements of the work and between the various subcontractors and suppliers shall be solely the responsibility of the contractor, approval of submitted matter notwithstanding.
Bldg 465 Replace Heatpump eProject # 1633010 Page 4 of 14
- The Contractor shall submit at least one original manufacturer literature with each submittal, including an English translation.
1. Heatpump Cutsheet
8. APPROVAL OF SAMPLES, CUTS AND DRAWINGS: For this project, all submittals of an administrative nature shall be submitted to the FEAD Office. Technical submittals shall be addressed via the Contracting Officer to the Public Works Department to the attention of FEAD
9. TESTING:
The Contractor shall perform:
1. Test and Balance
2. Commission DDC System
10. TRAINING: N/A
11. NOTES: N/A
Bldg 465 Replace Heatpump eProject # 1633010 Page 5 of 14
CONTRACTOR QUALITY CONTROL (QC) PROGRAM & PLAN
ASSESSMENT CHECKLIST
ROICC Office: Date:
Contract No.:
Project Title:
Contractor:
Superintendent: Individual Responsible for Jobsite Safety:
QC Manager: Alternate QC Manager:
Note: Items with the word PLAN and in bold are required in the QC Plan. This checklist serves two functions. For the ROICC office, to aid in reviewing a Contractor’s QC Plan, identifies what is contractually required by specification and checks completeness of your QC specification; can also be used for constructibility reviews. For the CAV Team, as a tool for doing project reviews to check a Contractor’s QC Program and Plan.
Item No.
ITEM Yes No N/A Comments
ROICC CAV
Quality Control Specification Section (01450N/01451N/01455N):
1. PLAN. Was the QC Plan submitted in accordance with QC
Specification?
a.
In a three-ring binder b.
Includes a table of contents c.
Major sections identified with tabs d.
Pages numbered sequentially
QC Organization:
2. PLAN. Is there a chart showing the Contractor’s
QC organization structure?
3. PLAN. Does the chart show the relationship of the QC organization to other elements of the Prime Contractor’s company? The chart needs to show the relationship of the QC Manager to company officer(s), to the QC staff, to outside organizations, to the project superintendent.
4. PLAN. Does the chart show the relationship of the QC organization to subcontractors, suppliers, outside organizations?
5. Is the QC Manager responsible for safety, i.e., designated as the safety competent person?
NOTE: The QC Manager is not to be designated as the safety competent person.
Names and Qualifications:
6. PLAN. Contains the names and qualifications for each person in the QC organization, in resume format?
7. PLAN. Does the QC Manager have a current CQM for Contractors training certificate?
8. PLAN. Does the Alternate QC Manager have a current CQM for Contractors training certificate?
Bldg 465 Replace Heatpump eProject # 1633010 Page 6 of 14
9. PLAN. Are the current CQM for Contractor training certificates in the QC Plan?
10. PLAN. Do the qualifications and past experiences of the following QC staff meet the Contract specification requirements:
QC Manager
Alternate QC Manager
QC Specialist(s) d.
Submittal Reviewer(s) e.
Registered Fire Protection Engineer
Duties, Responsibility and Authority of QC Personnel:
11. PLAN. Are the duties, area of responsibilities and authority of each person in the QC organization stated in detail in the QC Plan, in particular the QC Manager and the Alternate QC Manager?
12. Per Specification, is the QC Manager allowed to be the project superintendent?
13. Does the QC Manager understand the responsibility for managing and coordinating the Three Phases of Control and documentation performed by any QC specialists, testing laboratory personnel, and any other inspection and testing personnel required by this Contract?
Outside Organizations:
14. PLAN. Is there a listing of outside organizations, such as architectural and consulting engineering firms, that will be used by the Prime Contractor?
15. PLAN. Does this listing contain a description of the work and services to be performed?
Appointment Letters:
16. PLAN. Are there appointment letters, signed by an officer of the firm, appointing the QC Manager and the Alternate QC Manager and include the following:
Outlining their duties, responsibilities and authority for implementing and managing the QC Program?
Responsibility to manage and implement the Three Phases of Control?
The authority to stop any work not complying with the Contract, and the removal and replacement of any defective work?
17. PLAN. Are there letters of direction to the Assistant QC Manager and all QC specialists outlining their duties, authorities, and responsibilities?
Submittal Procedures and Initial Submittal Register:
18. PLAN. Are there procedures for reviewing, Bldg 465 Replace Heatpump eProject # 1633010 Page 7 of 14 approving, and managing submittals?
19. PLAN. Is there a list of name(s) of people in the QC organization authorized to review and certify submittals?
20. PLAN. Is the initial Submittal Register as specified included in the QC Plan?
Testing Laboratory Information:
21. PLAN. Is there a list of construction material testing laboratories to be used for this Contract?
22. PLAN. Is there a description of the service(s) these testing laboratories will provide?
23. PLAN. Is the Contractor using accredited testing laboratories and are there current copies of the Certificate of Accreditation and Scope of Accreditation for the testing laboratories listed?
24. PLAN. Do the testing laboratory’s scope of accreditation include the appropriate ASTM standards listed in the technical specification sections?
Testing Plan and Log:
25. PLAN. Is there a Testing Plan and Log that includes the tests required, referenced by the specification paragraph number requiring the test, the frequency, and the person responsible for each test.
Procedures to Complete Rework Items:
26. PLAN. Are there procedures to identify, record, track, and complete rework items?
Document Procedures:
27. PLAN. Are there procedures for documentation, e.g. daily reports, inspection and testing, including copies of all forms?
List of Definable Features:
28. PLAN. Is there a list of DFOWs in the QC Plan? A
Definable Feature of Work (DFOW) is a task that is separate and distinct from other tasks and has control requirements and work crews unique to that task.
29. PLAN. As a minimum, is the list of DFOWs cross referenced to the Contractor’s contract schedule and the specification sections?
30. PLAN. Does the list include, but not limited to, all critical path activities?
31. PLAN. Does this list include all activities which require QC specialists or specialty inspection personnel?
32. PLAN. (DB) Does each design development stage and submittal package have separate DFOWs?
Procedures for Performing the Three Phases of Control:
Bldg 465 Replace Heatpump eProject # 1633010 Page 8 of 14
33. PLAN. Does the Plan contain procedures to use to ensure the three phases of control are used to manage the quality on this Contract?
Personnel Matrix:
34. Does the Specification require the QC Plan to have a
Personnel Matrix?
35. PLAN. If required, does the matrix show for each specification section:
Who will review and approve submittals?
Who will perform and document the three phases of control?
Who will perform and document the testing?
Procedures for Completion Inspection:
36. Does the Specification require the QC Plan to have procedures for completion inspections?
37. PLAN. If required, does the procedure identify the responsible party for punch out inspection, pre-final inspection, and final acceptance inspection?
Training Procedures and Training Log:
38. Does the Specification require the QC Plan to have training procedures?
39. PLAN. If required, are there procedures for coordinating and documenting the training of personnel as required by the Contract?
40. PLAN. If required, has a sample record of training been included in the QC Plan which reports what systems, who provides the training, when and where the training is to be performed and who attended?
Bldg 465 Replace Heatpump eProject # 1633010 Page 9 of 14
ACCIDENT PREVENTION PLAN NAVFAC REVIEWER CHECKLIST
CONTRACTOR: DATE:
CONTRACT: SIGNATURE:
A qualified reviewer shall check to assure submitted coies of the following items applicable from EM 385-1-1 Appendix A are included in the APP
YES NO N/A
REMARKS
1. SIGNATURE SHEET: Plan Preparer, Approval, Concurrence
2. BACKGROUDN INFO: Contractor, Contract #, Project Name, Brief Project Description, Contractor Accident Experience (EMR, OSHA) Corp. Trend Analysis, list of activities requiring
AHA.
3. STATEMENT OF SAFETY & HEALTH POLICY
4. RESPONSIBILITIES & LINES OF AUTHORITY:
Identification of personnel responsible for safety (Corp. & Project Level)
5. SUBCONTRACTOR & SUPPLIERS: Identification of Subs and Suppliers; means for controlling & controlling; safety responsibilities
6. TRAINING: List subjects in safety indoctrination; mandatory training & certification, emergency response, outline requirements for supv and employee safety meetings
7. SAFETY & HEALTH INSPECTIONS: Identify who will conduct inspections, when & how it will be conducted & recorded, deficiency tracking system and follow-up procedures.
Any external inspections/certifications (e.g. Coast Guard, etc.)
8. SAFETY & HEALTH EXPECTATIONS, INCENTIVE
PROGRAMS AND COMPLIANCE: Company’s written safety program goals, objectives, and accident experience goals;
description of company’s safety incentive program;
policy/procedures for non-compliance with safety requirements;
written company procedures for holding mgr./supvs accountable for safety
9. ACCIDENT REPORTING: Identify person who completes the following: how and when; exposure data (m/hrs worked);
accident investigations, reports a7 logs; immediate notification of major accidents
10. MEDICAL SUPPORT: Outline on-site medical support and off-site medical arrangements
11. PERSONAL PROTECTIVE EQUIPMENT: Outline procedures (who, when, how) for conducting hazard assessments & written certifications for use of personal protective equipment
12. PLANS (PROGRAMS, PROCEDURES) REQUIRED BY THE
SAFETY MANUAL:
A. Hazard Communication B. Emergency Response Plans C. Layout Plans D. Respiratory Protection Plan E. Health hazard Control Program F. Lead/Asbestos Abatement Plan G. Abrasive Blasting H. Confined Space I. Hazardous Energy Control plan J. Critical Lift Procedures K. Contingency Plan For Severe Weather L. Access/haul Road Plan M. Demolition Plan (Engineering and Asbestos Surveys) N. Compressed Air Plan O. Formwork and Shoring Erection and Removal Plans P. Lift Slab Plans Q. SHP/SSHP (for HTRW work) R. Driving Plan S. Alcohol Drug Abuse Prevention Plan T. Fall Protection Plan
Bldg 465 Replace Heatpump eProject # 1633010 Page 10 of 14
13. Information on how the contractor will meet the requirements of the major sections of EM 385-1-1 in the accident prevention plan.
Particular attention shall be paid to:
A. Excavations B. Scaffolding C. Medical/First Aid Requirements D. Sanitation
E. PPE
F. Fire Prevention G. Machinery and Mechanized Equipment H. Electrical Safety I. Chemical, physical agent and biological occupational exposure prevention requirements
J. Detailed site specific hazards and controls shall be provided in the activity hazard analysis for each phase of the operation
K. A list of the anticipated AHAs should be submitted with the
APP
14. Plans for maintaining job cleanup and safe access
15. Public safety requirements (e.g. fencing, signs)
LANT Form 385-APP
Drawing 1 of 3 Photos of Existing Heatpump
Photo 1: Existing Heatpump (HP-2)
Photo 2: Existing Mechanical Yard
Drawing 2 of 3 Existing Heatpump Cutsheets
SCatanzaro Text Box
HEAT PUMP MULTIPURPOSE
Line
Rectangle
Magellano - Aermec S.p.A. 1
Model: NRP1250A2°°°P2R2
Description: SEZIONE EDIFICIO BDLG 465
Cooling Capacity kW 312,9
Input power kW 114,2
Input current A 211
E.E.R. W/W 2,74
Height above sea level m 0
Dry bulb air inlet temperature °C 37,2
Inlet water temperature °C 12,0
Temperature difference °C 5,0
Outlet water temperature °C 7,0
Ethylene glycol % 0
Water flow rate l/s 14,8381
Available pressure kPa 77
Fouling factor (m² K)/W 0,00005
Heating - System side Capacity kW 258,3
Input power kW 124,1
Input current A 217
C.O.P. W/W 2,08
Dry bulb ambient air temperature °C 3,0
Inlet water temperature °C 45,0
Temperature difference °C 5,0
Outlet water temperature °C 50,0
Ethylene glycol % 0
Water flow rate l/s 12,6256
Available pressure kPa 138
Heating (DHW side) Capacity kW 269,1
Input power kW 112,8
Input current A 198
C.O.P. W/W 2,39
Dry bulb ambient air temperature °C 3,0
Inlet water temperature °C 40,0
Temperature difference °C 5,0
Magellano - Aermec S.p.A. 2
Outlet water temperature °C 45,0
Ethylene glycol % 0
Water flow rate l/s 13,1372
Available pressure kPa 148
Fouling factor (m² K)/W 0,00005
Cooling + Heating (DHW side) Cooling capacity kW 340,8
Heating capacity kW 434,0
Input power kW 99,8
T.E.R. W/W 7,76
Users circuit (Cooling)
Outlet water temperature °C 7,0
Temperature difference °C 5,0
Ethylene glycol % 0
Water flow rate l/s 14,8381
Available pressure kPa 77
Users circuit (Heating)
Outlet water temperature °C 45,0
Temperature difference °C 7,9
Ethylene glycol % 0
Water flow rate l/s 13,4203
Available pressure kPa 153
Fouling factor (m² K)/W 0,00005
Data declared according to EN 14511:2013
Magellano - Aermec S.p.A. 3
Magellano - Aermec S.p.A. 4
Performances in average climatic conditions Pdesignh 55 °C 323,00
SCOP 55 °C 3,40
ƞs 55 °C 133,00
Electric data
Power supply 400V/3/50Hz with thermal-magnetic cut-outs
Magellano - Aermec S.p.A. 5
Multipurpose units for 2-pipe systems
NRP RANGE
Range The multipurpose 2-pipe units have been made to meet the needs of a two pipe air-conditioning system and DHW throughout the year.
This occurs thanks to the two braze-welded plate heat exchangers; one is entirely dedicated to the production of cold/hot water for the system depending on the climatic season, while the other is responsible for producing DHW.
· PRODUCTION OF CHILLED WATER ONLY: the multipurpose unit acts as a classical chiller: cool water to the system, and condensation heat disposal outside, through finned coils.
· PRODUCTION OF HOT WATER ONLY: the multipurpose unit acts as a heat pump. Exploiting the heat of outside air through the finned coil (evaporator), it raises the temperature of the water for the system through a plate heat exchanger (condenser).
· PRODUCTION OF DOMESTIC HOT WATER ONLY: the multipurpose unit acts as a heat pump.
Exploiting the heat of outside air through the finned coil (evaporator), it raises the temperature of DHW through a plate heat exchanger (condenser).
· COMBINED PRODUCTION: if the utility requires at the same time DHW and cold water, the unit acts as a water heating unit, controlling condensation and evaporation on two separate plate heat exchangers associated to the circulation of cold and hot water in the system for DHW production. The transition from one configuration to another takes place automatically (managed by an on-board microprocessor) trying to optimise the spent energy depending on the utility demand.
Size Cooling capacity from 43 to 477 kW.
Heating capacity from 46 to 544 kW.
Cooling circuit Two independent cooling circuits allowing the production of hot and chilled water simultaneously or not simultaneously.
Operational fields
· PRODUCTION OF CHILLED WATER ONLY: chilled water temperature producible from 4 °C to 18 °C, with outdoor air from -10 °C to 46 °C.
· PRODUCTION OF HOT WATER ONLY: hot water temperature producible from 25 °C to 55 °C, with outdoor air from -15 °C to 42 °C.
· COMBINED PRODUCTION: hot water temperature from 30 °C to 55 °C, and chilled water producible from 4 °C to 18 °C.
Refrigerant NRP range chillers use HFC R410A near-azeotropic mixture as a refrigerant; it is characterised by nil ODP (Ozone Depletion Potential), and classified within the safety group A1 according to the ASHRAE 34-1997 Standard.
Version High efficiency version. The unit uses increased finned core coils with a wide exchange surface.
Supporting frame Made of hot galvanised sheet steel with suitable thickness, and painted with polyester powders able to withstand weathering over time. The supporting structure is made so as to ensure maximum accessibility for service and/or maintenance operations.
Composition The unit consists of a frame with a single module.
Number of compressors 4 scroll compressors and 2 circuits (each circuit is equipped with two compressors).
Description of the compressors The scroll-type hermetic compressors mounted on NRPs are optimised to work with R410A refrigerant and feature high efficiency and low power consumption. They are provided as standard with a sump anti-freeze electrical resistance. This is powered automatically at each stop to keep the unit under tension. They are driven by 2-pole electric motors with internal circuit breaker protection, chilled by intake gas. They are assembled on rubber shock absorbers placed at the base. To minimize noise, the compressors are enclosed in a sound proof compartment.
Thermostatic valve Standard mechanical thermostatic valve with outdoor equaliser placed at the exit of the evaporator, and bulb sensitive to the intake temperature. Depending on the heat load, it modulates the gas flow, while maintaining the correct degree of superheat of the intake gas to the compressor. This makes it possible to work with a minimum temperature of the produced water at 4 °C.
Magellano - Aermec S.p.A. 6
Plate heat exchanger Plate type, high efficiency, dry expansion water-refrigerant exchanger, made of braze welded AISI 316 stainless steel.
Externally isolated with closed cell material to prevent the formation of condensation and reduce heat loss. An anti-freeze electrical resistance to protect the exchanger when the unit is not operating is fitted as standard.
Source side heat exchanger (coils) Air-refrigerant exchangers, made up of fin coils with copper pipes and hydrophilic aluminium louvered fins, blocked by pipes mechanical expansion. Source side exchangers can operate as condensers or evaporators or be excluded from the circuit (depending on the operation mode of the multipurpose unit).
Description of the cooling circuit Made of copper pipes with welded joints in silver alloy including the following components in addition to the compressors and exchangers:
· thermostatic valve modulating the gas flow depending on the refrigerant load;
· mechanical dehydrator filter made of ceramics and hygroscopic material, capable of retaining impurities and any traces of humidity in the cooling circuit;
· liquid indicator to check the presence of humidity in the cooling circuit;
· solenoid valve on the liquid line closing when the compressor switches off, blocking the refrigerant gas flow to the evaporator;
· cooling cycle reversing valve that reverses the refrigerant flow when operation modes change during defrosting cycles;
· one-way valves to direct the refrigerant in the correct flow direction;
· accumulation of the liquid to retain the refrigerant gas in its liquid state, whenever the machine has a surplus at that particular point of operation;
· compressor intake liquid separator: used to prevent the flow of liquid into the compressor inlet.
Ventilation Unit Standard fan unit consisting of helical fans (with an IP 54 degree of protection). The rotors are balanced statically and dynamically, driven directly by 6-pole electric motors. Electrically protected by incorporated magnet circuit breakers, and mechanically with accident-prevention protection nets fixed on the upper part of the timber framework.
Number of fans The ventilation unit for the disposal of the heat produced by the condensers is composed of 6 fans with rotor of 800 mm.
Electric Control Board Contains the power section and the controls and safety devices management unit. It is in compliance with the LVD 2006/95/EC Directive, and the EMC 2004/108/EC, regarding electromagnetic compatibility. Moreover, all cables are numbered allowing quick recognition of all electrical components.
It is always equipped with a door-lock isolating switch: the electric control board can be accessed disconnecting power supply and acting on the opening lever of the control board. This lever can be locked using one or more padlocks during maintenance work to prevent an unwanted power-up of the unit. Inside the control board is a control keyboard allowing complete control of the unit.
Power supply Power supply 400V/3N/50Hz with magnetic circuit breakers.
Safety and protection devices The chiller is always provided with the following devices:
· fixed calibration high pressure gauge (40 bar) with manual reset: it is located on the pressing line side of the compressor and has the task to stop the compressor operation in the event of abnormal operating pressure;
· high pressure transducer: it is placed on the low pressing line side of the compressor and signals the work pressure to the control board, generating a pre-warning and alarm in case of abnormal pressure;
· low pressure transducer operating as a low pressure gauge: it is placed on the intake pipe of the compressor and signals the work pressure to the control board, generating a pre-warning and alarm in the event of abnormal operating pressure;
· cooling circuit safety valves, the one on the low pressure side is calibrated at 30 bar, the one on the high pressure side at 45 bar: they operate discharging the overpressure in the event of abnormal pressure;
· DCPX condensation pressure controller: it allows successful operation with outdoor temperatures below 10 °C, and up to – 10 °C. It is an adjustment circuit board which varies the number of fan revs according to the condensation pressure read by the high pressure transducer, in order to keep it
Magellano - Aermec S.p.A. 7 sufficiently high for a correct operation of the unit. It also allows a proper operation in heating mode with outdoor temperatures above 30 °C and up to 42 °C;
· the electric control board is protected by an interlock system of the access door: this lever can be locked using one or more padlocks during maintenance work to prevent the unit from being powered up accidentally.
· The electric board comes complete with: a transformer for the control circuit, a door-lock isolating switch, fuses for compressors and fans, clamps for the remote panel, spring type control circuit terminals, electrical board to be mounted outside with double door and gaskets, electronic controller, control consent relay for evaporator and recovery pumps (only for models without pump units);
· also available: magnetic circuit-breaker protection devices for compressors, magnetic circuit-breaker protection devices for fans, magnetic circuit-breaker protection device for the auxiliary circuit, thermostat controlling the temperature of the exhaust gas of each circuit, phase sequence research (RCS) to control sequence and phases.
Probes and transducers The unit comes complete with: input and output water temperature probes. This way it is possible to operate the compressors in order to keep the temperature of the water produced, or the temperature of the water returning from the system, constant. The unit also has high pressure transducers (one per circuit), and low pressure transducers (one per circuit): these make it possible to view on the microprocessor board the values of the working pressure in the pipe in which they have been installed, and stop the operation of the compressor in the event of abnormal working pressure.
Electronic adjustment The microprocessor has the following functions:
· complete management of the unit by means of a multilingual interface;
· complete management of the compressors according to compressor time periods (stand-by between peaks, minimum operating time, minimum switch-off time, etc.) and rotation of the compressors according to working hours and minimum stand-by times (giving priority to the unit efficiency and accuracy in determining water temperature);
· display of all main variables affecting the chiller operation;
· possibility to modify the main operation parameters;
· pumping unit management;
· antifreeze management on the evaporator by means of resistors and circulation pump contacts;
· remote control by: remote control panel (PGD1 accessory), potential-free contacts, RS485 serial and compatible with Modbus protocol (AER485P1 accessory);
· a multipurpose contact that can be used for power and setpoint requirements, and power limitation;
· temperature controlled by means of a step thermostat at the chiller water inlet (proportional control) or outlet (proportional + integral control);
· daily/weekly timer with 4 time periods per day;
· operation differential and low load (water flow low) automatic calculation);
· operating mode automatic calculation according to the outdoor temperature;
· intelligent control of the system inertia (PULL DOWN and PULL UP functions);
· management of any anomalies of the chiller by means of automatic reset warnings, alarms, and chronological history of the anomalies to help diagnosis the fault;
· unit and black box alarm history feature (alarm history transferable to PC);
· possibility to adjust the flow temperature of the unit based on the outdoor temperature;
· intelligent defrosting; evaporation control by reducing the tan speed;
· the board also allows to display all operation parameters read by probes, such as water temperature, delivery pressure, etc.
System side hydronic unit P2. Only low head pump, and reserve pump DHW preparation side hydronic unit R2. With low head pump, and reserve pump Description of the standard components of the hydraulic circuit The unit is supplied with a Y type water filter. This allows to block and remove any impurities in the hydraulic circuits. It contains a filtering mesh with holes that do not exceed one millimetre in diameter. There is also a flow switch (which blocks the unit in case water is not circulating in the pipes) and a bleed valve.
System side hydronic unit management
Magellano - Aermec S.p.A. 8
One pump plus a reserve pump with rotation managed by the circuit board. Pump rotation takes place cyclically every 2 hours, so as to optimise working hours; during exchange there is always an overlapping by a few seconds so as to ensure the flow switch closing. Exchange takes place automatically in case the operation pump should break.
DHW preparation side pumping unit management One pump plus a reserve pump with rotation managed by the circuit board. Pump rotation takes place cyclically every 2 hours, so as to optimise working hours; during exchange there is always an overlapping by a few seconds so as to ensure the flow switch closing. Exchange takes place automatically in case the operation pump should break.
Available accessories
· AER485P1: RS-485 interface for supervision systems with MODBUS protocol.
· AERWEB300. The AERWEB300 device allows the remote control of the chiller from a common PC via a serial link, by means of a standard PC via Ethernet using a standard browser. Four models are available:
· AERWEB300-6: Web server for monitoring and controlling a maximum of 6 devices in RS485 network;
· AERWEB300-18: Web server for monitoring and controlling a maximum of 18 devices in RS485 network;
· AERWEB300-6G: Web server for the monitoring and control of a maximum of 6 devices in an RS485 network with inbuilt GPRS modem;
· AERWEB300-18G: Web server for the monitoring and control of a maximum of 18 devices in an RS485 network with inbuilt GPRS modem;
· DRE: Electronic device to reduce peak current. It can only be applied in the factory.
· GP: Protection grid protecting the outdoor coil from accidental impacts, and preventing access to the underlying area where the compressors and the chiller circuit are located (each kit includes 2 grids).
· PGD1: Simplified remote panel. It allows performing basic controls of the unit with alarm signals.
Remote controllable to 500 m with a 2 pair shielded twisted pair cable, and TCONN6J000.
· RIF: Current rephaser. Connected in parallel to the motor, it allows a reduction of the input current
(approx. 10%). Only applicable in the manufacturing phase, it should be requested at time of order.
· TRX1: Metal cap replacing the plastic cap mounted for protection in storage tanks with holes and integrative resistances.
· VT and AVX: Anti-vibration mounts to be installed under the base. They help reduce vibrations transmitted to the structure.
Compliance The installation and user manual will be provided with each unit, together with a declaration of conformity pursuant to the unit serial number. The data plate must bear the EC mark.
The NRP range AERMEC chiller unit complies with the following harmonised standards:
· IEC EN 60335-2-40 (Safety standard regarding electrical heat pumps, air conditioners, and dehumidifiers);
· IEC EN 61000-6-1 and IEC EN 61000-6-3 (Electromagnetic emissions and immunity levels for residential environments);
· IEC EN 61000-6-2 and IEC EN 61000-6-4 (Electromagnetic emissions and immunity levels for industrial environments);
· EN378 (Refrigerating system and heat pumps - safety and environmental requirements);
· UNI EN 12735 (Seamless, round copper tubes for air conditioning and refrigeration);
· UNI EN 14276 (Pressure equipment for cooling systems and heat pumps).
It thus complies with the essential requirements of the following directives:
· LVD Directive: 2006/95/EC
· Electromagnetic Compatibility Directive 2004/108/EC
· Machinery Directive 2006/42/EC
· Pressure Equipment Directive 97/23/EC
The product, in accordance with Directive 97/23/EC, meets the Quality Assurance Procedure (form H) with certificate no.06/270-QT3664 Rev.5 issued by notified body n.1131: CEC, via Pisacane 46, Legnano (Milano), Italy.
Drawing 3 of 3 As-Built Drawings
Ramp-2
427A
427B
T-648
Taxiway
Delta
Taxiway
Charlie
E-28 Arresting Gear #3
L
PAR
ITAF
Taxiway
Echo
Ramp-5
Ramp-4
Secondary Red Label
Ramp-3
Taxiway Foxtrot
Taxiway
Bravo
Temp.
Air Force
Pad
419417
E-28 Arresting Gear #1
Inboard
T
T
T
P
T
CP
P
CP
CP
CP
CP
PARKING
LOT
Sentry
House
P
T
P
T
T
T
P
CP
1-D
4-R
2-D
1-D
1-D
4-R
2-D
1-R
1-D
1-D
2-D
4-R
2-R
T
CB
P
1-R
2-D
2-D
2-R
3-R
2-D
4-R
3-D
FIELD
SOCCER
545 547
P
P
P
P
P
VOLLEY
BALL
COURT
CP
P
P
CP
CP
B
A
A
B
VOLLEY
BALL
COURT
S
C P
P
P
CP
P
P
P
P
P
1-R
1-D
EARTH
MOUND
4-R
1-D
F
F
F
T
T
F
F
F
F
F
F
F
S
F
F
F
F
FUEL
CHILL
CHILL
GEN
2-D
1-R
3-D
S
F
1-D
F
P
T
F
CP
CP
PARKING
AREA
EXTERNAL
HELO LIFT
PAD
PRIMARY RED LABEL
Taxiway
Delta
Taxiway
Charlie
Taxiway
Bravo
Taxiway Foxtrot
Inboard
Outboard Outboard
R
Delta
Hammer
Head
E-28 Arresting Gear #2
ITAF
ITAF Crash
Truck
Staging Area
US
TACAN
ITAF
TACAN
Taxiway
Echo
Compass
Rose
ITAF
ITAF
ITAF
ITAF
ITAF
ITAF
ITAF
ITAF
OPS Access
MAFFS
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
YARD
PARKING
It
CP
PARKING
It
A/C
Washrack
CP
T
WATER
TANK
COMM
TOWER
T
T
T
T
T
T
T
F
F
F
F
F
F
F
F
F
F F
F
F
F
F
F F
CRANE
TEST
CELL
ITAF
It 66
It 98
It 195
It //29
It 143
It //31
It 158
It 139
It 179
It 180
It 140
It 160
It 204
It 146
It 211
It 178
It 153
It 200
It 171
It 172
It 173
It 208
It 210
It 174
It //18
It //10
SF1
It //25
It 217 It 165 It 164 It 157
It 176
It 193
It 177
It //07
It //30
It 50
It 49
It 201
It 48
It 45
It 133
It 46
It 212
It 114
It 156
It //03
It //34
It //22
It //51
It //21
It 181
It 44
It 39
It 41
It 40
It 162
It //40
It 39
It 135
It 1152
It 141
It 10
It 12
It 101
It 8
It 102
It 125
It 166
It 168
It 159
It 159
It 16
It 17
It 167
It 169
It 215
It 216
It 183
It //02
It 184
It 187
It 205
It //26
It //59
It //53
It 21
It 56
It 129
It 124
//42
//06It 145
It
C.A. //09
It 214
It 42
It 103
It 65
It //65
It 37
It 35
It 33
It 29
It 137
It 151
It 151
It 147
It 161
It 57 It 207
It //62
It 202
It 203
It //35
It //32
It //67
It 209
It 121
It //04 It 122 It 105
It //05
It //41
It 149
It 111
SVASS
It 213
It 128
It 43
It 107
It // 37
It //37
It // 37
It // 37
It // 27
It 127
It //04
It 99
It //44
It //48
It 38
It 31
It 31
It 147
It 120 It //23
It 28
It 195
It 24
It 7
It 36
It //24
It 109
It 19
It //49
It 106
It 97
It //16
It 199
It //14
It 25
AREA ESPROPRIO ITAF
F
7.00 m
17.00 m
BL
DG
CO
VE
R
SH
EE
T
465/G-00
BLDG 465
D/ B
EN
ER
G Y
CO
NS
ER
VA
TI
O
N M
EA
SU
RE
S
(E
CM
s) , V
AR
IO
US
BU
IL
DI
NG
S at N
AS
I&
II,
S ig on el la
Ita ly
1 2 3 4 5
3 4 5
A
B
C
D
1 2
A
B
C
D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
CONSTR. CONTR. NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
NAVFAC DRAWING NO.
AutoCAD SHX Text
DES
AutoCAD SHX Text
DRW
AutoCAD SHX Text
SYM
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DATE
AutoCAD SHX Text
APPR
AutoCAD SHX Text
DRAWFORM REVISION: 9 MAY 2017
AutoCAD SHX Text
CHK
AutoCAD SHX Text
SATISFACTORY TO
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
ACTIVITY
AutoCAD SHX Text
FOR COMMANDER NAVFAC
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
A/E INFO
AutoCAD SHX Text
OF
AutoCAD SHX Text
EPROJECT NO.:
AutoCAD SHX Text
DEPARTMENT OF THE NAVY
AutoCAD SHX Text
NAVAL FACILITIES ENGINEERING COMMAND
AutoCAD SHX Text
LANT CAPITAL IMPROVEMENTS
AutoCAD SHX Text
NAPLES, ITALY
AutoCAD SHX Text
NAVAL FACILITIES ENGINEERING COMMAND ~ EURAFSWA
AutoCAD SHX Text
CONCEPT DESIGN
AutoCAD SHX Text
NOV 2016
AutoCAD SHX Text
NAVAL AIR STATION II
AutoCAD SHX Text
SIGONELLA, SICILY, ITALY
AutoCAD SHX Text N33191-16-D-1010/0002
AutoCAD SHX Text STUDIO TECNICO DOTT. ING. SALVATORE SANTAMARIA SANTAMARIA engineering & consulting
AutoCAD SHX Text
DESIGN DEVELOPMENT (35%)
AutoCAD SHX Text
DEC 2016
AutoCAD SHX Text
PREFINAL DESIGN
AutoCAD SHX Text
MAR 2017
AutoCAD SHX Text
FINAL DESIGN
AutoCAD SHX Text
MAY 2017
PIPES IN TUNNEL
UP-0,65
DW-0,65
EXISTING CONCRETE BASEMENT
BASAMENTO IN CLS ESISTENTE
TUBAZIONI IN CUNICOLO
DN 50
CONNESSIONE ALLE
TUBAZIONI ESISTENTI Ø4"
CONNECTION TO
EXISTING PIPE Ø4"
DN 50
DN 50 DN 32
DN 50
DN 160
DN 63
DN 63
VERSO CIRCUITO
POST ESISTENTE
TO CIRCUIT
EXISTING POST
VOLANO ACQUA
FREDDO NUOVO
NEW COLD
WATER TANK
UNITÀ IDRONICHE
INTERNE A CASSETTA
ELECTRICAL PANEL
QUADRO ELETTRICO
HYDRONIC CASSETTES
INDOOR UNIT
BATTERY LIMIT
LIMITE DI TAGLIO
VOLANO ACQUA
CALDA NUOVO
NEW HOT
WATER TANK
PRECISION AIR CONDITIONER
CONDIZIONATORE DI PRECISIONE
INGRESSO TUBI NEL CONTROSOFFITTO
ELECTRICAL PANEL
QUADRO ELETTRICO
VOLANO ESISTENTE
EXISTING
STORAGE TANK
D N
DN 160
DN 160
EXISTING
CONCRETE
BASEMENT
BASAMENTO IN
CLS ESISTENTE
SIPHON CONDENSATE
DRAIN LINE
SCARICO CONDENSA
SIFONATO
SIPHON CONDENSATE DISCHARGE
SCARICO CONDENSA SIFONATO
COLLEGAMENTO ALL'IMPIANTO ESISTENTE.VEDI SCHEMA TAV. M601
REALIZATION OF CONCRETE BASEMENT SLAB WHICH ACCOMODATES THE
NEW EQUIPMENT
INSTALL THE PRECISION AIR CONDITIONER
INSTALLAZIONE DI CONDIZIONATORE DI PRECISIONE
INSTALL HYDRONIC CASSETTES INDOOR UNIT
INSTALLAZIONE DI UNITÀ IDRONICHE A CASSETTA
WORK ITEMS
VOCI DI LAVORO
NUOVA UNITÀ POMPA DI CALORE
NEW HEAT PUMP UNIT
REALIZZAZIONE DEL BASAMENTO IN CLS DESTINATO AD ACCOGLIERE LE
NUOVE APPARECCHIATURE
CONNECTION TO THE PIPES EXISTING.SEE TABLE TAV. M601
VOLANO ACQUA CALDA/FREDDA NUOVO COIBENTATO IN POLIURETANO ESPANSO E
RIVESTITO IN LAMIERINO D'ALLUMINIO
NEW HOT/COLD WATER TANK INSULATED WITH POLYURETHANEFOAM AND COATED
ALUMINUM SHEET
ESEGUIRE LO STAFFAGGIO DEI TUBI CON COLLARI IN GOMMA. LA DISTANZA MINIMA
DEL TUBO DALLA PARETE DEVE ESSERE DI 100 MM. LE DISTANZE MINIME TRA I
COLLARI SONO RIPORTATE NEL FOGLIO M-506
EXECUTE THE PIPES CLAMPING WITH RUBBER COLLARS. THE MINIMUM DISTANCE
OF THE PIPE FROM THE WALL MUST BE 100 MM. THE MINIMUM DISTANCES BETWEEN
COLLARS ARE SHOWN IN M-506 SHEET
Sentry
House
P
F
FUEL
CHILL
CHILL
GEN
F
NO TO SCALE
SCALE 1:100
PROJECT OF THE PIPING AND CONDENSATE DRAIN LINE
PROGETTO TUBAZIONI E LINEA DI SCARICO CONDENSA
UNIT OF MEASUREMENT: MILLIMETER
UNITÀ DI RIFERIMENTO: MILLIMETRI
William.Albertson Rectangle
William.Albertson Text Box Chiller to be Replaced
William.Albertson
BATTERY LIMIT
ELETRICAL PANEL
NEW PRECISION AIR CONDITIONER
INLET TUBES IN THE FALSE CEILING
QUADRO ELETTRICO
LIMITE DI TAGLIO
INGRESSO TUBI NEL CONTROSOFFITTO
NUOVO CONDIZIONATORE DI PRECISIONE
PIPES IN TUNNEL
UP-0,65
DW-0,65
TUBAZIONI IN CUNICOLO
DN 50
CONNESSIONE ALLE
TUBAZIONI ESISTENTI Ø4"
CONNECTION TO
EXISTING PIPE Ø4"
DN 50
DN 50 DN 32
DN 50
DN 160
DN 160
DN 160
DN 160
DN 160
DN 160
DN 63
EXISTING CONCRETE BASEMENT
NEW HEAT PUMP 1 (MULTIPURPOSE)
NUOVA UNITÀ POMPA DI CALORE
BASAMENTO IN CLS ESISTENTE
NEW HEAT PUMP 1 (MULTIPURPOSE)
NUOVA UNITÀ POMPA DI CALORE
VOLANO ACQUA
FREDDO NUOVO
NEW COLD
WATER TANK
VOLANO ACQUA
CALDA NUOVO
NEW HOT
WATER TANK
VOLANO ESISTENTE
EXISTING
STORAGE TANK
EXISTING
CONCRETE
BASEMENT
BASAMENTO IN
CLS ESISTENTE
DN 63
VERSO CIRCUITO
POST ESISTENTE
TO CIRCUIT
EXISTING POST
HYDRONIC CASSETTES INDOOR UNIT
UNITÀ IDRONICHE INTERNE A CASSETTA
ELECTRICAL PANEL
QUADRO ELETTRICO
COLLEGAMENTO ALL'IMPIANTO ESISTENTE.VEDI SCHEMA TAV. M601
REALIZATION OF CONCRETE BASEMENT SLAB WHICH ACCOMODATES THE
NEW EQUIPMENT
INSTALL THE PRECISION AIR CONDITIONER
INSTALLAZIONE DI CONDIZIONATORE DI PRECISIONE
INSTALL HYDRONIC CASSETTES INDOOR UNIT
INSTALLAZIONE DI UNITÀ IDRONICHE A CASSETTA
WORK ITEMS
VOCI DI LAVORO
NUOVA UNITÀ POMPA DI CALORE
NEW HEAT PUMP UNIT
REALIZZAZIONE DEL BASAMENTO IN CLS DESTINATO AD ACCOGLIERE LE
NUOVE APPARECCHIATURE
CONNECTION TO THE PIPES EXISTING.SEE TABLE TAV. M601
VOLANO ACQUA CALDA/FREDDA NUOVO COIBENTATO IN POLIURETANO ESPANSO E
RIVESTITO IN LAMIERINO D'ALLUMINIO
NEW HOT/COLD WATER TANK INSULATED WITH POLYURETHANEFOAM AND COATED
ALUMINUM SHEET
ESEGUIRE LO STAFFAGGIO DEI TUBI CON COLLARI IN GOMMA. LA DISTANZA MINIMA
DEL TUBO DALLA PARETE DEVE ESSERE DI 100 MM. LE DISTANZE MINIME TRA I
COLLARI SONO RIPORTATE NEL FOGLIO M-506
EXECUTE THE PIPES CLAMPING WITH RUBBER COLLARS. THE MINIMUM DISTANCE
OF THE PIPE FROM THE WALL MUST BE 100 MM. THE MINIMUM DISTANCES BETWEEN
COLLARS ARE SHOWN IN M-506 SHEET
Sentry
House
P
F
FUEL
CHILL
CHILL
GEN
F
NO TO SCALE
SCALE 1:50
465M-401
SCALE 1:50 SCALE 1:50
465M-401 465M-401
UNIT OF MEASUREMENT: MILLIMETER
UNITÀ DI RIFERIMENTO: MILLIMETRI
4.72 1.000 4.72 1.600
DN 160 DN 160
DN 160
DN 160
GIUNTO
ANTIVIBRANTE
A MOLLA
JOINT SPRING
ANTIVIBRATION
NOT TO SCALE
FUORI SCALA
HEAT PUMP 1 (MULTIPURPOSE)
POMPA DI CALORE 1 (MULTIPURPOSE)
HEAT PUMP 1 (MULTIPURPOSE)
POMPA DI CALORE 1 (MULTIPURPOSE)
NEW HOT WATER TANK
VOLANO ACQUA CALDA NUOVO
EXISTING CONCRETE BASEMENT
NEW CONCRETE BASEMENT
BASAMENTO IN CLS ESISTENTE
BASAMENTO IN CLS NUOVO
ELETRICAL PANEL
QUADRO ELETTRICO
1.222
CONCRETE BASEMENT OF HOT AND COLD TANKS
BASAMENTO IN CLS DEL VOLANI CALDO E FREDDO
Ø 8 passo 200 mm
Ø 8 passo 200 mm
1.600
1.
PLANT'S ARMOR AVAILABLE
DISPOSIZIONE ARMATURA IN PIANTA
SCALE 1:20
465/M-501
SCALE 1:5
UNIT OF MEASUREMENT: MILLIMETER
UNITÀ DI RIFERIMENTO: MILLIMETRI
SCALE 1:20
465/M-501
3.850
4.250
1.925808100
HEAT PUMP UNIT SECTION
2.
2.200
HEAT PUMP UNIT FRONT OF VIEW
HEAT PUMP UNIT PLAN
1.100
HEAT PUMP UNIT PLAN
WITH REQUIRED DISTANCE
SCALE 1:20
465/M-504
SLAB
SOLETTA
WALL
PARETE
WALL
PARETE
EXSTERIOR PIPE SUPPORT
WELDED TO ANGLE LEGS.
50 X 50 X 6mm STEEL ANGLE FRAMING. ALL-WELDED
10 X 100mm ANCHOR BOLT - TYPICAL OF FOUR
DOUBLE NUTS AND WASHERS. (TYPICAL)
ABCHOR TO SUPPORT WITH STAINLESS STEEL
WITH MITERED JOINTS.
EACH LEG.
REINFORCED CONCRETE.
GRADE.
100 X 100 X 6mm STEEL BASE PLATW
8mm GALVANIZED THREADED U-BOLT.
CAVALLOTTO A "U" DI 8mm IN ACCIAIO
ZINCATO E FILETTATO.
PIASTRA 100 X 100 X 6 DI BASE IN ACCIAIO
SALDATO AGLI ANGOLARI DI SUPPORTO.
10 X 100 mm BULLONE DI ANCORAGGIO PER
TUTTE E QUATTRO LE GAMBE.
ANCORARE IL SUPPORTO CON DOPPI BULLONI
E RONDELLE IN ACCIAIO INOSSIDABILE.
TERRENO.
CALCESTRUZZO ARMATO.
50 X 50 X 6mm TELAIO IN ANGOLARE DI
ACCIAIO TUTTO SALDATO CON ANGOLARI A
45°.
SUPPORTO TUBAZIONE ESTERNA
MULTIPLE CEILING PIPE SUPPORT DETAIL
THREADED ROD
RAIL SUPPORT
PIPE
ANGLE IRON
EXPANSION BOLT
GALVANIZED THREADED U-BOLT.
BOLT
POLYURETHANE FOAM
PARTICOLARE SUPPORTO TUBAZIONI MULTIPLE A SOFFITTO
TASSELLO AD ESPANSIONE
ANGOLARE DI FERRO
BARRA FILETTATA
TUBAZIONE
PROFILATO
CAVALLOTTO A "U" IN ACCIAIO
ZINCATO E FILETTATO.
BULLONE
SCHIUMA DI POLIURETANO
WALL PIPE SUPPORT DETAIL
EXPANSION BOLT
GALVANIZED COLLAR
PIPE WITH INSULATION
PARTICOLARE SUPPORTO TUBAZIONE A PARETE
TUBAZIONE CON ISOLAMENTO
COLLARE ZINCATO
TASSELLO AD ESPANSIONE
VERTICAL PIPE SUPPORT DETAIL
GALVANIZED BOLT Ø 12
PIPE
INSULATION
GALVANIZED COLLAR
NEOPRENE GASKET
GALVANIZED EXPANSION BOLT Ø 16
GALVANIZED IRON ANGLE
GALVANIZED STEEL PLATE
PARTICOLARE SUPPORTO TUBAZIONE VERTICALE
GUARNIZIONE IN NEOPRENE
COLLARE ZINCATO
BULLONE ZINCATO Ø 12
ISOLAMENTO
TUBAZIONE
TASSELLI AD ESPANSIONE ZINCATI Ø 16
ANGOLARE FERRO ZINCATO
PIATTINA DI ACCIAIO ZINCATO
WALL
PARETE
SLAB
SOLETTA
PIPE SLEEVE DETAIL
GALVANIZED FLANGE
INSULATION WITH JACKET
PIPE
GALVANIZED PIPE SLEEVE
CONCEALED SPACES 25 mm EXTENSION
NO EXTENTION IN FINISHED EXPOSED WALL
ROCKWOOL OR FIBERGLASS PACKING
FIREPROOF SEALANT (QUANTITY AS REQUIRED
TO MANTAIN SLAB RATING)
TUBAZIONE
ISOLAMENTO CON RIVESTIMENTO ESTERNO
CONTROTUBO ZINCATO
ESTENSIONE 25 mm NEGLI SPAZI NON IN VISTA
NO ESTENSIONE SU PARETE ESPOSTA IN VISTA
FLANGIA ZINCATA
RIEMPITIVO IN LANA DI ROCCIA
O FIBRA DI VETRO
SIGILLANTE IGNIFUGO (IN QUANTITÀ NECESSARIA
PER MANTENERE LA CLASSE DELLA SOLETTA)
PARTICOLARE CONTROTUBO PER TUBAZIONE
AUTOMATIC AIR VENT DETAIL
AUTOMATIC AIR VENT
INSULATION WITH JACKET
PIPE
SEALANT
COCK
TUBAZIONE
ISOLAMENTO CON RIVESTIMENTO ESTERNO
SIGILLANTE
RUBINETTO
SFOGO D'ARIA AUTOMATICO
PARTICOLARE SFOGO D'ARIA AUTOMATICO
NO TO SCALE
465/M-505
MAXIMUM DISTANCE FROM
SUPPORT TO PIPES
DIAMETER (Ø)
fmax
L
=1000 mm
Ø 32
=1400 mm
Ø 50
=1750 mm
Ø 90
=1550 mm
Ø 63
=1750 mm
Ø 110
=1800 mm
Ø 125
=1850 mm
Ø 160 de di s s
DD
UNIT OF MEASUREMENT: MILLIMETER
UNITÀ DI RIFERIMENTO: MILLIMETRI
NOT TO SCALE
465/M-506
6 bar 1/2"
6 bar 1/2"
Ø160/124.2
Ø160/124.2
Ø 160/124.2
Ø160/124.2
CIRCUITO FREDDO
ALLE BATTERIE DI
RISCALDAMENTO
TERMINALI ESISTENTI
TUBAZIONI NUOVE PER COLLEGAMENTO ALL'IMPIANTO
ESISTENTE BATTERIE DI POSTRISCALDO
COLLEGAMENTO
ALL'IMPIANTO
ESISTENTE AHU/CAC
W A
TE
R
L O
A D
C A
R
IC
O
ID
R
IC
O
LOCALE SERVER ROOM
RECTIFIER ROOM
CAC
C. COOLER
W A
TE
R
L O
A D
C A
R
IC
O
ID
R
IC
O
UI1-UI2-UI3
C. COOLER:
Ø160/124.2
Ø160/124.2
Ø160/124.2
Ø160/124.2
Ø160/124.2
Ø160/124.2
Ø160/124.2
Ø32/24.6 Ø32/24.6
Ø 50/38.8
Ø 50/38.8
1.720 l/h Ø63/48.8 14.020 l/h
COLD WATER
STORAGE TANK
HOT WATER
STORAGE TANK
ALIMENTAZIONE
ELETTRICA ESISTENTE
EXISTING POWER SUPPLY
ALIMENTAZIONE
ELETTRICA ESISTENTE
EXISTING POWER SUPPLY
JOINT SPRING
ANTIVIBRATION
GIUNTO
ANTIVIBRANTE
A MOLLA
JOINT SPRING
ANTIVIBRATION
GIUNTO
ANTIVIBRANTE
A MOLLA
COLD CIRCUIT
CIRCUITO CALDO
HOT CIRCUIT
VOLANO ACQUA
FREDDA
VOLANO ACQUA
CALDA
CONNECTION
EXISTING IMPLANT
CTA / CAC
NEW PIPES FOR LINK TO THE EXISTING
RE-HEAT BATTERIES
HEAT PUMP 1 (MULTIPURPOSE)
POMPA DI CALORE 1 (MULTIPURPOSE)
TO THE EXISTING
HEATING BATTERIES
ST2
ST1
HEAT PUMP 1 (MULTIPURPOSE)
POMPA DI CALORE 1 (MULTIPURPOSE)
Ø160/124.2
CIRCUITO FREDDO
Ø160/124.2
Ø160/124.2
COLD CIRCUIT
Ø160/124.2
CIRCUITO CALDO
HOT CIRCUIT
Ø160/124.2
Ø 50/38.8
Ø 50/38.8
3.510 l/h
2.814 l/h
N.C.
N.C.
LEGEND
LEGENDA
HEATING WATER RETURN LINE
TUBAZIONE RITORNO RISCALDAMENTO
HEATING WATER SUPPLY LINE
TUBAZIONE MANDATA RISCALDAMENTO
CHILLED WATER RETURN LINE
TUBAZIONE RITORNO REFRIGERAZIONE
CHILLED WATER SUPPLY LINE
TUBAZIONE MANDATA REFRIGERAZIONE
SHUT-OFF VALVE
VALVOLA DI INTERCETTAZIONE
3-WAY MIXING VALVE
VALVOLA MISCELATRICE A 3 VIE
CHECK VALVE
VALVOLA DI RITEGNO
MANOMETER
MANOMETRO
THERMOMETER
TERMOMETRO
FLOWMTER
FLUSSOSTATO
1/2" PRESSURE REDUCER
RIDUTTORE DI PRESSIONE DA 1/2"
WATER GAUGE
VALVOLA DI SFOGO ARIA AUTOMATICA
SAFETY VALVE
VALVOLA DI SICUREZZA A MOLLA
Ø.../...
FLEXIBLE CONNECTION
COLLEGAMENTO FLESSIBILE
BALANCING VALVE
VALVOLA DI BILANCIAMENTO
PIPELINE EXTERNAL/INTERNAL DIAMETER
DIAMETRO ESTERNO/DIAMETRO INTERNO TUBAZIONE
EXISTING PLANT
IMPIANTO ESISTENTE
HEAT PUMP
POMPA DI CALORE
COLD WATER STORAGE TANK
VOLANO FREDDO
CONDENSATE PUMP INTEGRAL WITH COMPUTER ROOM UNIT
CONDENSATORE ESTERNO INTEGRATO CON L'UNITA' DEL LOCALE COMPUTER
CHECK UNDER CONSTRUCTION THE NEED 'TO REPLACE
EXISTING POWER ELECTRICAL CABLES
VERIFICARE IN FASE DI REALIZZAZIONE LA NECESSITA' DI SOSTITUIRE
I CAVI ELETTRICI ESISTENTI
TUTTE LE NUOVE TUBAZIONI SARANNO IN PPR CON ISOLAMENTO
E FINITURA IN LAMIERINO DI ALLUMINIO
NEW PIPES OF PPR WITH INSULATION AND ALUMINIUM PLATE FINISH
HOT WATER STORAGE TANK
VOLANO CALDO
WORK ITEMS
VOCI DI LAVORO
GENERAL NOTE
NOTE GENERALI
OGNI VOLTA CHE VENGONO UTILIZZATI TUBI IDRONICI ESISTENTI, È NECESSARIO ESEGUIRE UNA COMPLETA VALIDAZIONE, PIÙ LA PROVA DI PERDITE D'ACQUA E LA PROVA DI CORROSIONE E TUTTE LE TUBAZIONI DEVONO ESSERE SVUOTATE
EVERY TIME EXISTING HYDRONIC PIPES ARE USED, FULL VALIDATION SHOULD BE DONE PLUS WATER
LEAK TEST AND CORROSION TEST AND ALL PIPELINES SHOULD BE FLUSHED
NOT TO SCALE
HYDRONIC HEATING SYSTEM DIAGRAM
SCHEMA FUNZIONALE IMPIANTO RISCALDAMENTO IDRONICO
TREND SUPERVISOR
CONTROLLER
MEASURING
ELECTRIC ENERGY
MODBUS RS485
HEAT PUMP 1
MULTIPURPOSE
HEAT PUMP 2
MULTIPURPOSE
CAC
TCP/IP
DDC TREND
C A
V O
U
TP
MISURATORE ENERGIA
ELETTRICA
MEASURING
ELECTRIC ENERGY
MISURATORE ENERGIA
ELETTRICA
MEASURING
ELECTRIC ENERGY
MISURATORE ENERGIA
ELETTRICA
POMPA DI CALORE 1
POMPA DI CALORE 2
HOT WATER
COLD WATER
ACQUA FREDDA
ACQUA CALDA
HOT WATER
COLD WATER
ACQUA FREDDA
ACQUA CALDA
SUPERVISORE TREND
BATTERY LIMIT
EXISTING TELECOM SWITCH TO
ETHERNET…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it.