This document contains a request for clarification regarding a midterm availability solicitation on the USNS WASHINGTON CHAMBERS. The solicitation from the Department of the Navy Military Sealift Command seeks maintenance and repair services, including replacement of handrails, inspection and maintenance of incinerators, preservation and repair of gypsy and hauling winches, and weather deck drain work. The request for clarification provides responses to technical questions from offerors regarding drawings, references, equipment sizes, and availability for ship inspections. Photos and technical documents are also attached to aid offerors in preparation of their proposals.
View the file
Other files for this federal contract opportunity
Show all 29
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N3220521R4221
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION J - LIST OF DOCUMENTS, EXHIBITS & OTHER ATTACHMENTS
The following have been added by full text:
RFC #1
MILITARY SEALIFT COMMAND
N3220521R4221
Request for Clarification
QUESTION #1:
Regarding Specification Item no. 0101 Paragraph/Section no. 2.1 Title: HANDRAIL REPLACEMENT
Need NAVSEA Drawing No. 802-8498848, General Arrangement Mark Up.
ANSWER:
DWG 8499000 Is applicable to the CHAMBERS. Ship’s Bosn and Chief Mate have the locations to be replaced. Due to turnover, Mark Up is not available. Ship personnel and Port Engineer can identify hand rails requiring replacement not to exceed amount called out in the Work Item upon vessel arrival.
QUESTION #2:
Regarding Specification Item no. 0167 Paragraph/Section no. 2.1.1 Title: REPLACE HANGAR ROLLER CURTAIN INTERLOCK SWITCH (T-ALT 199)
Need Federal Equipment Company drawing 60587-6744E03 F
Provided SEPCOR to Contracting POC.
QUESTION #3:
Regarding Specification Item no. 0520 Paragraph/Section no. 2.1 Title: CPVC Weather Deck Drains
Need 526-8499171 Weather Deck & Miscellaneous Drains System Diagram
DWG 8499019 is specific to CHAMBERS. Noted DWG in Work Item is for TAKE 13.
QUESTION #4:
Regarding Specification Item no. 0521 Paragraph/Section no. 2.1, 2.2 Title: INCINERATOR INSPECTION AND MAINTENANCE
Need Tech Manual T9593-DD-MMC-010, Rev. 1 - INCINERATOR, TYPE ATLAS 800 SL WS P, W/ WEDGE BELT DRIVEN FAN Service Report 2021
References provided SEPOC to Contracting POC.
QUESTION #5:
Regarding Specification Item no. 1003 Paragraph/Section no. 2.1 Title: GYPSY WINCH, FOUNDATION AND ELECTRICAL MOTOR PRESERVATION AND REPAIR
Need: NAVSEA TG813-AW-MMA-010 Winch, Gypsy winch
Provided SEPCOR to Contracting POC. Note Tech Manual is SG vice TG
QUESTION #6
Regarding Specification Item no. 1001 Paragraph/Section no. 2.3 Title: HAULING WINCH BAND BRAKE REFURBISHMENT
Need NAVSEA Dwg. 5210332, Brake band weldment
Provided SEPCOR to Contracting POC.
Question #7:
Regarding Specification Item no. 0603 and 0662 Paragraph Section no. ALL TITLE: Kettle Deck Preservation & TAKE_CCSI_A_DEEP FAT FRYER INSPECTION (1YR)
Specifications for WI’s 0603 & 0662 were not provided in the J-1 spec package, but our on the J-2 for pricing.
Will MSC provide missing specifications or should they be removed from the J-2?
Answer:
These Work Items should be removed from the J-2.
Question #8:
Regarding Specification Item 1002 Paragraph/section no. 2
TITLE: HAULING WINCH BAND BRAKE REFURBISHMENT
References provided do not show brake drum or brake band size.
Please provide brake drum size and approximate band width.
Answer:
Approximate Brake Drum Size – 35-1/4” Band Width – 3-1/2”
Question #9
Regarding Specification Item 1002 Paragraph/section no. 2 TITLE: Winch Control (Controlex) Riser
Reference 2.1 was not provided.
Please provide missing ref, NAVSEA DWG. 5210548 Please also provide pictures of existing risers showing any interferences contractors may need to account for or provide a ship check availability for contractors to inspect.
Photos and DWG provided to Contracting POC. Risers are bolted in place.
Question #10
Regarding Specification Item 1003 Paragraph/section no. 2.1
TITLE: GYPSY WINCH, FOUNDATION AND ELECTRICAL MOTOR PRESERVATION AND REPAIR.
Reference 2.1 was not provided.
Please provide missing ref, 2.1 NAVSEA TG813-AW-MMA-010 Winch, Gypsy winch Please also provide pictures of existing winch Master Control Pedestal support plates/brackets for renewal, or provide a ship check availability for contractors to inspect.
Photos and Tech Manual Provided to Contracting POC. Tech Manual Should be SG vice TG.
(End of Summary of Changes) image1.wmf