LVE457453 Attachment 1 Specification Document for B735 vac pump.docx

DOCX document 20 KB Posted

Attached to
Vacuum Pump System or Equivalent
Solicitation number
LVE457453
Issued by

About this file

This is a technical specification document attached to RFQ LVE457453 for a vacuum pump system replacement for Brookhaven National Laboratory (BNL), issued by the Department of Energy Office of Science. The document details requirements for replacing an existing Amico Model V-LRW-D-120E-BS-N-030-46063 vacuum pump system, specifying dimensional constraints (42" width, 86" height, 97 3/4" length), electrical requirements (460V, 3-phase, 12 FLA max), and performance requirements that must match or exceed the existing system.

The associated solicitation seeks a firm-fixed-price quote for a duplex contactless claw vacuum pump system with a 120-gallon painted horizontal ASME air receiver, 5" HMI touch screen control panel, and 2 HP motor (460V, 60Hz, 3-phase). The system must provide 16 SCFM capacity at 19" HG with one pump on reserve. Requirements include owner training, 30-month warranty, and installation support. Vendors must provide origin of manufacture, UEI number, published price list, insurance documentation if applicable, and SAM registration. Pricing must remain valid for 60 days and include all freight and handling costs. Award will be made to the lowest-priced, technically acceptable offer.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment 1 RFQ NO: LVE457453 Specification

Specification Document for B735 (CFN) Vacuum Pump System Replacement

1. General Requirements The replacement vacuum pump system shall meet or exceed the specifications of the existing Manufacturer Amico Model V-LRW-D-120E-BS-N-030-46063, ensuring compatibility and performance equivalence.

2. Existing System Specifications

· Manufacturer: Amico

· Model Number: V-LRW-D-120E-BS-N-030-46063

· Pump Serial Numbers: 14006, 14005

· Current Pump Specification: Tuthill Vacuum Blower Systems 36E663

· Voltage: 460V

· Phase: 3 Phase

· Full Load Amps (FLA): 12 Amps Maximum

3. Dimensional Constraints The replacement vacuum pump system must adhere to the following maximum dimensions:

· Width: 42 inches

· Height: 86 inches

· Length: 97 3/4 inches

4. Performance Requirements

· The replacement system shall provide equivalent vacuum pressure and flow rate compared to the existing system.

· It must be designed for continuous operation in an industrial environment.

· The system should include necessary controls, monitoring, and safety features to ensure reliability and efficiency.

5. Electrical Requirements

· The system shall operate at 460V, 3-phase power supply.

· It must not exceed 12 FLA during full-load operation.

· Electrical components must comply with relevant industry safety and performance standards.

6. Installation and Compatibility

· The system should fit within the existing footprint and infrastructure with minimal modifications.

· It must be compatible with existing piping, electrical connections, and control systems.

· The vendor shall provide installation support and documentation, including wiring diagrams and operational manuals.

7. Compliance and Certification

· The vacuum pump system must comply with all relevant local, state, and federal regulations.

· UL, CE, or equivalent certification is required for electrical components.