APPENDIX B

FOR A

MEZZANINE

AT

LUKE AIR FORCE BASE, Arizonia

BUILDING 1390

CSN: ALK906

DATE: 5 April 2022

PREPARED BY:

Joshua A Payne Joshua Payne

AFLCMC/EZPAE

_ Andrew J. Huser Andrew Huser

AFLCMC/EZPAE

FA8604-22-R-B011 Attachment 3 Page 1 of 19

Luke AFB App B - Page i

Table of Contents

1. SCOPE

.............................................................. ER

ROR! BOOKMARK NOT DEFINED.

1.1. GENERAL SCOPE

.............................................................. ER

ROR! BOOKMARK NOT DEFINED.

1.2. DEFINITIONS

.............................................................. ER

ROR! BOOKMARK NOT DEFINED.

2. APPLICABLE DOCUMENTS

.............................................................. ER

ROR! BOOKMARK NOT DEFINED.

3. REQUIREMENTS

.............................................................. ER

ROR! BOOKMARK NOT DEFINED.

3.1. System Description TABLE OF CONTENTS

.............................................................. ER

ROR! BOOKMARK NOT DEFINED.

3.2. CHARACTERISTICS

.............................................................. ER

ROR! BOOKMARK NOT DEFINED.

3.2.1. PERFORMANCE AND PHYSICAL CHARACTERISTICS

.............................................................. ER

ROR! BOOKMARK NOT DEFINED.

3.2.1.1. LOAD CAPACITY

.............................................................. ER

ROR! BOOKMARK NOT DEFINED.

3.2.1.2. FREESTANDING STRUCTURE

.............................................................. ER

ROR! BOOKMARK NOT DEFINED.

3.2.1.2.1 PRE-ENGINEERED

3.2.1.3. DEFLECTION UNDER LOAD

.............................................................. ER

ROR! BOOKMARK NOT DEFINED.

3.2.1.4. DIMENSION AND CLEAR HEIGHT

.............................................................. ER

ROR! BOOKMARK NOT DEFINED.

3.2.1.5. SEISMIC

.............................................................. ER

ROR! BOOKMARK NOT DEFINED.

FA8604-22-R-B011 Attachment 3 Page 2 of 19

3.2.1.6. COLUMNS

.............................................................. ER

ROR! BOOKMARK NOT DEFINED. 3.2.1.6.1 BASE PLATES

3.2.1.7 FRAMING

3.2.1.7.1 BEAMS

3.2.1.7.2 JOINTS

3.2.1.7.3 BRIDGING

3.2.1.8. DECKING

.............................................................. ER

ROR! BOOKMARK NOT DEFINED.

3.2.1.8.1 BAR GRATING

3.2.1.9 STAIRWAY

3.2.1.9.1 STAIRWAY TREADS

3.2.1.9.2 STRINGERS

3.2.1.9.3 RAILINGS

3.2.1.9.4 PLATFORMS

3.2.1.10. MEZZANINE RAILING

.............................................................. ER

ROR! BOOKMARK NOT DEFINED.

3.2.1.11. KICKPLATE

.............................................................. ER

ROR! BOOKMARK NOT DEFINED.

3.2.2 ELECTRICAL CHARACTERISTICS

3.2.2.1 LIGHTING

3.2.2.1.1 FIXTURES

3.2.2.1.2 ON/OFF SWITCHES

3.2.3. SAFETY FEATURES

.............................................................. ER

ROR! BOOKMARK NOT DEFINED.

3.2.3.1. CAPACITY MARKINGS

.............................................................. ER

ROR! BOOKMARK NOT DEFINED.

3.2.3.2. NO-STEP MARKINGS

.............................................................. ER

ROR! BOOKMARK NOT DEFINED.

3.2.3.3 SAFETY FACTOR

3.3 CAGE

3.4 CHARACTERISTICS

3.4.1 PANELS

3.4.2 POSTS

4. QUALITY CONFORMANCE

.............................................................. ER

FA8604-22-R-B011 Attachment 3 Page 3 of 19

4.1. INSPECTIONS

.............................................................. ER

ROR! BOOKMARK NOT DEFINED.

4.2. TEST

.............................................................. ER

ROR! BOOKMARK NOT DEFINED.

4.3. CERTIFICATIONS

.............................................................. ER

FA8604-22-R-B011 Attachment 3 Page 4 of 19

Luke AFB App B - Page 1

1. SCOPE

1.1. GENERAL SCOPE

This appendix establishes the minimum performance, design, fabrication, installation, and test requirements for a mezzanine at Bldg. 1390, Luke Air Force Base (AFB), AZ. The work shall be completed in accordance with this appendix, the Cover Purchase Description (PD), and Air Force (AF) Drawing ALK906-02, through This appendix covers all equipment, materials, and labor necessary to complete installation of the system.

1.2. DEFINITIONS

Beams - Structural steel supporting member which connect the columns.

Bridging - Steel channels used to provide lateral stability and prevent joists from twisting.

Column - Structural steel that supports beams and joist.

Framing - Consists of beams, joists, and bridging.

Joists - Structural steel member supporting the decking.

2. APPLICABLE DOCUMENTS

Applicable documents shall be in accordance with Section 2 of the Cover PD and the following:

AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM)

ASTM A36/A36M-97A Standard Specification for Structural

Steel

ASTM A366/A366M-91 Standard Specification for Steel

Sheet, Carbon Cold-Rolled, Commercial Quality

ASTM 446/A446M-89 Standard Specification for Steel

Sheet, Zinc-Coated (Galvanized) by the Hot-Dip Process, Structural (Physical)

FA8604-22-R-B011 Attachment 3 Page 5 of 19

Luke AFB App B - Page 2

ASTM A500-98 Standard Specification for Cold-Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes

ASTM A570 Standard Specification for Steel, Sheet and Strip, Carbon, Hot-Rolled, Structural Quality

ASTM A611 Standard Specification for Steel, Sheet, Carbon, Cold-Rolled, Structural

(Applications for copies should be addressed to the American Society for Testing and Materials, 1916 Race Street, Philadelphia PA 19103)

US PRODUCT STANDARDS

USPS 1-95 For Construction and Industrial

Plywood with Typical APA Trademark

(Applications for copies should be addressed to the American Plywood Association, PO Box 11700, Tacoma WA 98411-0700).

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 13-99 Standard for the Installation of

Sprinkler Systems

NFPA 255-90 Standard Method of Test of Surface

Burning Characteristics of Building Materials

Applications for copies shall be addressed to the National Fire Protection Association, One Batterymarch Park, P. O. Box 9101, Quincy MA 02269-9101)

UNIFIED FACILTIES CRITERIA (UFC)

UFC 3-600-01 Fire Protection Engineering for

Facilities

3. REQUIREMENTS

3.1. SYSTEM DESCRIPTION

FA8604-22-R-B011 Attachment 3 Page 6 of 19

Luke AFB App B - Page 3

The mezzanine shall be located according to AF Drawing ALK906-

02. The mezzanine shall be used to store miscellaneous items such as, modular cabinets, tools, and any small items deemed of use by its operators. The mezzanine system shall consist of the following components:

a. Freestanding, structural steel mezzanine with columns, beams, joists, decking, and bridging.

b. Stairs, platforms, handrails, midrails, and kickplates.

c. Lighting.

h. Conduit, wiring, mechanical fasteners, and all other items required to install a functional mezzanine system.

3.2. CHARACTERISTICS

3.2.1. PERFORMANCE AND PHYSICAL CHARACTERISTICS

3.2.1.1. LOAD CAPACITY

All components of the mezzanine shall be designed to support a minimum capacity of 125 pounds per square foot. The mezzanine shall be capable of sustaining the point loads of the operating personnel and miscellaneous items without permanent deflection or deformation.

3.2.1.2. FREESTANDING STRUCTURE

The mezzanine shall not be attached to any existing building wall or column and shall not require cross bracing between columns.

3.2.1.2.1. PRE-ENGINEERED

All components of the mezzanine shall be pre-engineered so that on-site welding is eliminated.

3.2.1.3. DEFLECTION UNDER LOAD

No component of the mezzanine shall exhibit deflections greater than the length of the component divided by 360 (L/360) under uniformly loaded conditions.

3.2.1.4. DIMENSION AND CLEAR HEIGHT

FA8604-22-R-B011 Attachment 3 Page 7 of 19

Luke AFB App B - Page 4

The mezzanine shall be a nominal 46 feet long, 7 feet 10 inches deep The mezzanine shall have a nominal clear height of 8 feet underneath all components of the mezzanine. The under neath shall have half of the area enclosed in a cage with a double door, leaving the other half open. Light switch is indicated in red. See fig (1).

Figure 1

3.2.1.5. SEISMIC

The mezzanine shall be designed and constructed in accordance with state and local codes at Luke AFB AZ The mezzanine shall be designed to seismic conditions per the International Building Code for Eglin AFB locality. The Contractor shall familiarize themselves with local seismic conditions identified in the IBC and ensure mezzanine design is based on local conditions.

3.2.1.6. COLUMNS

Columns shall be cold formed, structural steel tubing and shall meet or exceed the requirements of ASTM A500, Grade B, FY-46KSI.

Columns shall be spaced as shown on AF Drawing ALK906-02 The columns shall be pre-punched at the top to provide a secure connection to beams and joists. Columns shall be a minimum of 5 inches X 5 inches X 3/16 inch thick.

3.2.1.6.1. BASE PLATES

FA8604-22-R-B011 Attachment 3 Page 8 of 19

Luke AFB App B - Page 5

Base plates shall be used under each column to distribute the load. The base plates shall be factory welded to the columns and prepunched to provide a secure connection to the floor. The base plates shall be anchored in accordance with the manufacturers recommended procedure. The base plates shall meet or exceed the requirements of ASTM A36 and shall be a minimum of 10 inches X 10 inches X 5/8 inch. Base plate grout shall be used as required.

3.2.1.7. FRAMING

Hot rolled structural steel members shall meet or exceed the requirements of ASTM A570. Cold-formed structural steel members shall meet or exceed the requirements of ASTM A500 or ASTM A611.

Framing shall consist of beams, joists and bridging as defined in 1.2. The framing shall be designed to support the full rated load and the decking.

3.2.1.7.1. BEAMS

All beams shall be structural steel and shall be prepunched for secure connection to the columns and joists with A325 bolts.

3.2.1.7.2. JOISTS

All joists shall be structural steel and shall be prepunched for secure connection to the beams with A325 bolts.

3.2.1.7.3. BRIDGING

Structural steel bridging channels shall be minimum 18-gauge steel.

3.2.1.8. DECKING

The decking shall be painted open bar grate type or galvanized open plank grating. The decking shall sustain the load specified in 3.2.1.1.

3.2.1.8.1. BAR GRATING

If bar grating is used, the bearing bars shall be minimum 1 inch X 1/8 inch bearing plate spaced on nominal 1 inch centers. The cross bars shall be resistance welded at right angles to the bearing bars and spaced on maximum 4.5-inch centers. Bar grating shall conform to the standards established by the National Association of Architectural Metal Manufacturers. Bar grating

FA8604-22-R-B011 Attachment 3 Page 9 of 19

Luke AFB App B - Page 6 shall be securely fastened to the framing with steel clips and plated, self-tapping steel screws.

3.2.1.9. STAIRWAY SYSTEMS

Stairway systems shall be provided at the location shown on AF Drawing ALK906-02. Stairway system shall include stairs, structural steel stringers, railing, platforms, and all necessary hardware to install the stairways. Stairways shall be 36 inches wide Stairways shall be designed and constructed in accordance with OSHA 1910.24 and International Building Code requirements. Intermediate platforms shall be utilized as required to ensure that the angle of incline does not exceed 40 degrees. Stairway systems shall be painted safety yellow.

3.2.1.9.1. STAIR TREADS

Stairs shall be open tread type with bar grating or closed tread with diamond plate.

3.2.1.9.2. STRINGERS

Stringers shall meet or exceed the requirements of ASTM A36.

3.2.1.9.3. RAILING

Railing shall be provided on the open sides of all exposed stairways and platforms. Rails shall be designed and constructed in accordance with OSHA 1910.23 and shall be of either the 2-rail or 3-rail type. The top rail surface shall be between 30-34 inches above the stair tread surface. Railing shall be minimum 1-1/4 inch, schedule 40 steel tubing. Rail sections shall be joined together with either galvanized fittings or a pre-engineered union. Railing for the stairway shall be bolt connected or factory welded to the stringer such that it is capable of withstanding a load of at least 200 pounds applied in any direction at any point on the top rail.

3.2.1.9.4. PLATFORMS

Platforms shall be the same width as the stairway. Platforms shall be even and level with the mezzanine floor.

3.2.1.10. MEZZANINE RAILING

Railing shall be provided on the open sides of all exposed mezzanine floor. Rails shall be designed and constructed in

FA8604-22-R-B011 Attachment 3 Page 10 of 19

Luke AFB App B - Page 7 accordance with OSHA 1910.23 and shall be of either the 2-rail or 3-rail type. The top rail surface shall be 42-inches above the mezzanine decking. Railing shall be minimum 1-1/2 inch diameter, schedule 40 steel tubing. Rail sections shall be joined together with either galvanized fittings or a pre-engineered union. Railing for the mezzanine shall be bolt-connected to a structural framing beam such that it is capable of withstanding a load of at least 200 pounds applied in any direction at any point on the top rail. Support posts shall be spaced on a maximum of 8-foot centers.

3.2.1.11. KICKPLATE

A kickplate shall be provided on all open sides of the mezzanine and platforms. The kickplate shall be a minimum 4-inches high with no more than 1/4-inch clearance between the floor and the bottom of the kickplate. The kickplate shall be minimum 14-gauge steel and shall be securely fastened to the mezzanine or railing.

3.2.2. ELECTRICAL CHARACTERISTICS

3.2.2.1. LIGHTING

The Contractor shall provide LED lighting underneath the mezzanine with a minimum illuminance level of 50 foot-candles measured at 30 inches above the floor. Lighting shall be supported by the mezzanine. Lighting shall be motion sensing and timed to turn off if no motion/occupancy is detected for a set period of time.

3.2.2.1.1. FIXTURES

Lighting fixture boxes shall not be smaller than 4 inches (octagonal), except where required by fixture configuration and approved by the COTR. Fixtures shall provide rapid start lighting. Fixtures shall not be suspended. T-8 LED light fixtures and lights shall be utilized. LED lighting using 4-foot tubes shall be utilized to light the mezzanine area. Lenses shall be provided for all lights.

3.2.2.1.2. ON/OFF SWITCHES

On/off switches shall be located as shown on AF Drawing ALK906- 02 Switches shall be of the totally enclosed, tumbler type.

Switches shall be located 52 inches +/- 2 inches in height from the floor.

FA8604-22-R-B011 Attachment 3 Page 11 of 19

Luke AFB App B - Page 8

3.2.3. SAFETY FEATURES

3.2.3.1. CAPACITY MARKINGS

Live load capacity metal signs shall be displayed on all sides of the mezzanine.

3.2.3.2. NO-STEP MARKINGS

Signs shall be posted on the railings indicating that the rails are not steps. Signs shall be posted on a maximum of 20-foot centers.

3.2.3.3. SAFETY FACTOR

All vertical members of the mezzanine shall have a minimum safety factor of 1.92 to 1 and all horizontal members shall have a minimum safety factor of 1.67 to 1.

3.3. CAGE

The Contractor shall install a wire mesh security cage as shown in AF Drawing ALK906-02. The cage shall be installed under the mezzanine (8’ Clear Height) and include posts, panels, sliding gate with lock, base plates, anchors, and hardware.

3.4. CHARACTERISTICS

The cage shall be installed as shown in Figure 1.

3.4.1. PANELS

Panels shall be 10 gauge woven or welded wire with no more than a 2” X 2” mesh opening. The cage shall span from floor to a nominal height of 96”. The cage shall be rigid. A top channel or stiffening supports shall be provided if required to maintain rigidity.

3.4.2. POSTS

Posts shall be nominal 2” x 2” steel tubing and provide no more than a 3-1/2” sweep space. Base plates shall be welded to the support posts and factory drilled to accept 3/8” anchors.

Posts/foot plates shall be anchored per manufacturers’s recommended procedures.

FA8604-22-R-B011 Attachment 3 Page 12 of 19

Luke AFB App B - Page 9

4. QUALITY CONFORMANCE

4.1. INSPECTIONS

The system shall be inspected to verify that it meets all the requirements of sections 1, 2, and 3 of this appendix and the Cover Purchase Description. These inspections shall be completed as part of the system checkout test and again as a part of the quality conformance test.

4.2. TEST

The following test shall be performed on the system as part of the system checkout test and again as a part of the quality conformance test.

No. Description

1. The COTR shall select three joists. At the midpoint of the joists, the distance from the bottom of the joist to the floor will be measured in inches and recorded as M1.

A minimum of three pallets weighing {CAPACITY} pounds per square foot shall be placed over the joists. After a continuous 4 hours, the distance from the midpoint of the joist to the floor will be measured in inches and recorded as M2. The deflection shall be calculated by using the following formula:

(M1 - M2) / (Span of joist in inches) = Deflection

If the deflection is greater than (Span of joist in inches)/360 or any permanent deformation has occurred, the mezzanine shall fail the test.

2. The lighting under the mezzanine shall be turned on. Test the lighting with a light meter 30 inches from the floor.

If the lighting is not a minimum of 50 foot-candles then the system shall fail the test.

4.3. CERTIFICATIONS

The Contractor shall provide certification that the following requirements have been met. All certifications shall be provided in accordance with the Contract Data Requirements List.

No. Paragraph Certification

FA8604-22-R-B011 Attachment 3 Page 13 of 19

Luke AFB App B - Page 10

1.

2.

3.2.1.1.

3.2.1.5.

All components of the mezzanine shall be designed to support a minimum capacity of 125 pounds per square foot.

The mezzanine is designed to seismic conditions per the International Building Code for Luke AFB locality.

3. 3.2.3.3. All vertical members of the mezzanine shall have a minimum safety factor of 1.92 to 1 and all horizontal members shall have a minimum safety factor of 1.67 to 1.

FA8604-22-R-B011 Attachment 3 Page 14 of 19

Mezzanine System - Page 1 of 5

MEZZANINE SYSTEM

Solicitation Number: FA8604- -R- Project Title:

Base: CSN:

Appendix B, Mezzanine, 6 May 2022

The Offeror shall complete this questionnaire. The questionnaire will be used to determine the Offeror's understanding of the requirements and acceptability of the proposed equipment.

Please attach product literature/cut sheets for all equipment detailed in this questionnaire and attach any exceptions to the Purchase Description Appendix.

Mezzanine Manufacturer: ________________________________________

Paragraph Characteristics

3.2.1.1. All components are designed to support a minimum

of __________________________________________ psf

3.2.1.2. Is the mezzanine freestanding?

YES NO

Are all components pre-engineered so that on site welding is eliminated? YES NO

3.2.1.3. All components are designed so that deflection is

not greater than _______________________________.

3.2.1.4. The clear height underneath the mezzanine is

______feet.

The height of the decking surface above the finished floor is ____ feet.

What are the dimensions of the mezzanine? ______ feet long X ______ feet deep.

3.2.1.6. The columns are on _______ foot centers.

FA8604-22-R-B011 Attachment 3 Page 15 of 19

Mezzanine System - Page 2 of 5

The dimensions of the columns are ______ inches X ______ inches.

Are the columns structural steel tubing?

3.2.1.6.1. The dimensions of the base plates are ______

inches X ______ inches

3.2.1.6.2. Are footers required? YES NO

3.2.1.7. What type of framing are you proposing?___________

3.2.1.7.1. Will all beams and joists be structural steel and

pre-punched for connection?

Will A325 bolts be used for connection?

3.2.1.11. What type of decking are you proposing?

What is the brand name of the decking? ___________

3.2.1.12. How many sets of stairs are you providing? ______

What is the width of the stairs? ______ inches

3.2.1.12.1

Are stairs open tread type with bar grating or closed tread with diamond plate? _________________

FA8604-22-R-B011 Attachment 3 Page 16 of 19

Mezzanine System - Page 3 of 5

3.2.1.12.3

Are the handrails in accordance with OSHA 1910.23?

Are rail sections joined with galvanized fittings or are they a pre-engineered union? ______________

3.2.1.12.4

Are the platforms the same width as the stairs?

What is the length of the platform? _____ inches

3.2.1.13. Are the railings in accordance with OSHA 1910.23?

3.2.1.19. The kickplate is ____ inches high.

3.2.2.1. The lighting will provide a minimum illumination

level of ___ foot-candles measured at 30 inches above the floor.

Is lighting motion sensing and turn off when no motion/occupancy is detected? YES NO

3.2.2.1.2. Are wall switches of the totally enclosed, tumbler type? YES NO

3.2.3.1. Are capacity markings provided? YES NO

3.2.3.2. Are no-step markings provided? YES NO

3.2.3.3. Vertical members have a minimum safety factor of

_____ to __.

Horizontal members have a minimum safety factor of______ to ___.

FA8604-22-R-B011 Attachment 3 Page 17 of 19

Mezzanine System - Page 4 of 5

THIS AREA LEFT BLANK INTENTIONALLY

FA8604-22-R-B011 Attachment 3 Page 18 of 19

Mezzanine System - Page 5 of 5

EXCEPTIONS

Identify below any exceptions taken to the Purchase Description Appendix. Please outline those concerns in detail. Your exceptions will be reviewed to determine acceptability.

Are exceptions taken? YES NO

EXCEPTIONS:

FA8604-22-R-B011 Attachment 3 Page 19 of 19

SCOPE
General scope
Definitions
APPLICABLE DOCUMENTS
REQUIREMENTS
System Description
Characteristics
Performance and Physical characteristics
Load capacity
Freestanding structure
Deflection under load
Dimension and clear height
Seismic
Columns
Base plates
Framing
Beams
Joists
Bridging
Decking
Bar grating
Stairway systems
Stair treads
Stringers
Railing
Platforms
Mezzanine Railing
Kickplate
Electrical characteristics
Lighting
Fixtures
On/Off switches
Safety features
Capacity markings
No-Step markings
Safety factor
cage
Characteristics
3.4.1. Panels
3.4.2. POSTS
QUALITY CONFORMANCE
Inspections
Test
Certifications