This technical data sheet describes a Valve Regulated Lead Acid Battery designed for Uninterruptible Power Supply (UPS) standby power applications, manufactured by C&D Technologies' Dynasty UPS product line. The High Rate Max battery series includes multiple models (UPS12-100MR through UPS6-620MR) with 12V and 6V configurations, offering 10-year design life, Absorbent Glass Mat (AGM) technology, and features such as efficient gas recombination, flame-retardant design, and compatibility with various transportation regulations. Key applications include data centers, network operations centers, industrial facilities, semiconductor manufacturing, banks, power generation plants, hospitals, and emergency response centers.

The battery specifications include detailed performance data across different discharge rates and operating times, with models ranging from 26.0 to 199 Ampere-Hours (AH) at the 20-hour rate. Notable features include a patented Long Life Alloy with minimal calcium levels, UL Recognized Flame-arresting vents, thermally welded case-to-cover construction, and operational flexibility in various orientations. The technical data sheet provides comprehensive information on operating temperature ranges, charging voltages, terminal configurations, and dimensional specifications for each battery model, making it a comprehensive reference for technical professionals selecting UPS battery solutions.

View the file

Other files

File Type Posted
Attachment_3_142010-25-0104.pdf PDF
Sol_1305M325Q0193.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications.

FEATURES & BENEFITS

12-1029

TECHNICAL DATA

UPS

APPLICATIONS

• Data Centers

• Network Operations Centers

• Industrial Process Control Facilities

• Internet Housing Sites

• Semiconductor Manufacturing

• Banks & Financial Markets

• Power Generation Plants

• Hospitals & Testing Laboratories

• Emergency 911 Response Centers

• 10 year design life @ 25˚C

• Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99% and freedom from electrolyte maintenance.

• 3 Year Warranty (refer Dynasty warranty card, 41-9027)

• Patented Long Life Alloy having the lowest calcium levels in the industry -minimizing grid growth, reducing gassing, and extending battery life.

• Patented UL Recognized Flame-arresting vents in each cell for safety and long life.

• Designed with the same recombination, thermal runaway prevention, gassing and flame retardant characteristics of the Bellcore 4228 compliant Dynasty Telecom products.

• Flame retardant polypropylene case and cover compliant with UL 1778

• Proprietary Fixed Orifice Plate Pasting technology applying active materials on both sides of the grid for consistent cell-to-cell performance, higher capacity and uniform grid protection.

• Thermally welded case-to-cover bond to eliminate leakage.

• Can be operated in any orientation.

Upright, side or end mounting recommended.

• Not restricted for air transport - Complies with IATA/ICAO Special Provisions A67.

• Not restricted for surface transport - Classified as non-hazardous material as related to DOT-CFR Title 49 parts 171-189.

• Not restricted for water transport - Classified as non-hazardous material per IMDG Amendment 27.

Model

UPS12-100MR

UPS12-150MR

UPS12-210MR

UPS12-300MR

UPS12-350MR

UPS12-400MR

UPS12-490MRLP

UPS12-490MR

UPS12-540MR

UPS6-620MR

Voltage Weight Weight

20 hr*

AH

5 10 15 20 30 40 45 50 60 90 lbs kg

26.0 172

21.0 27.3 40.0 58.4 67.4 75.8 83.0 100.0

100.0 72.0

10.0 12.4 18.0 26.5 30.5 34.4 38.0 45.0

45.0 33.0

34.6 53.8 78.6 93.2

Watts Per Cell @ 77˚F (25˚C) Operating Time (in minutes) to 1.67 Volts per Cell

* Nominal 20 hr rate to 1.75 VPC in Ampere-Hours.

DIMENSIONS

*All dimensions in inches (mm). All dimensions are for reference only. Contact a C&D Representative for complete dimension information.

NOTE: Batteries to be mounted with 0.5 in (1.25 cm) spacing minimum and free air ventilation.

E

B

A

D

C

F

.3

.8

0.25 6.42

0.64 16.18

0.18 4.67

0.50 12.62

.2

.5

.5

.7

1/4-20 UNC

.3

.6

.1

.1

1.13 28.70

1/4-20 UNC

3.50 89.0

.7

.0

.1

.1

1/4-20 UNC

.3

.3

1.22 31.10

.1

.1

1/4-20 UNC

.3

.3

1.22 31.10

.1

.1

1/4-20 UNC

.3

.7

0.98 24.9

.1

.2

UPS12-490MR/UPS12-540MRUPS12-350MR UPS12-400MR/UPS12-490MRLP UPS6-620MR

UPS12-210MR UPS 12-300MRUPS12-150MR

Battery Termination

UPS12-100MR

A B C D E F

UPS12-100MR 6.54

(166.2)

6.45 (163.7)

5.17 (131.3)

5.07 (128.8)

6.37 (161.7)

6.86 (174.3)

7.76 (197.1)

7.54 (191.4)

5.19 (131.9)

5.02 (127.6)

6.52 (165.7)

6.80 (172.7)

9.0 (228.6)

8.86 (225.1)

5.48 (139.2)

5.31 (134.8)

7.89 (200.3)

8.07 (205.1)

10.27 (260.9)

10.17 (258.4)

6.83 (173.4)

6.65 (168.9)

7.89 (200.3)

8.01 (203.5)

12.04 (305.8)

11.95 (303.5)

6.83 (173.4)

6.65 (168.9)

7.94 (201.6)

8.06 (204.8)

13.42 (340.9)

12.75 (323.7)

6.80 (172.7)

6.54 (166.0)

8.40 (213.2)

8.52 (216.4)

13.57 (344.7)

12.74 (323.6)

6.80 (172.7)

6.63 (168.4)

10.81 (274.5)

10.93 (277.7)

12.63 (320.8)

12.51 (317.8)

6.97 (177.0)

6.83 (173.4)

8.82 (224.0)

8.94 (227.2)

UPS12-150MR

UPS12-210MR

UPS12-300MR

UPS12-350MR

UPS12-400MR

UPS12-490MR

UPS12-490MRLP

UPS12-540MR

UPS6-620MR

.6

.6

0.75 19.0

.1

.7

#10-32 UNF

.6

.1

0.87 22.2

.1

.7

#10-32 UNF

UPS

Operating Temperature Range Discharge: -40˚F (-40˚C) to +160˚F (71˚C) with temperature compensation Charge: -10˚F (-23˚C) to +140˚F (60˚C) Nominal Operating Temperature Range +74˚F (-23˚C) to +80˚F (27˚C) Recommended Maximum Charging C/5 amperes @ 20hr rate Current Limit Float Charging Voltage 13.65 ± 0.15 VDC average per 12V unit (6.75 to 6.90 per 6V unit) Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.

Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20 Self Discharge Battery can be stored up to 6 months at 77°F (25°C) before a freshening charge is required. Batteries stored at temperatures greater than 77°F (25°C) will require recharge sooner than batteries stored at lower temperatures. See C&D brochure 41-7272, Self-Discharge and Inventory Control for details.

Equalize charge and 14.40 to 14.80 VDC average per 12V unit @ 77˚F (25˚C) (7.20 to 7.40 VDC per 6V unit.)

cycle service voltage Terminal: Flag 0.22 in. clearance hole to accept 0.1875 in. or 10-32 bolt (UPS12-100MR) Terminal: Inserted Threaded copper alloy insert terminal to accept

10-32 UNF bolt (UPS12-150MR, UPS12-210MR) 1⁄4-20 UNC bolt (UPS12-300MR, UPS12-350MR, UPS12-400MR, UPS12-490MRLP, UPS12-490MR, UPS12-540MR, UPS6-620MR)

Terminal Hardware Annual Retorque 32 in.-lbs (3.48 N-m) (UPS12-100MR) Terminal Hardware Initial Torque: 40 in.-lbs. (4.5 N-m) (UPS12-100MR) Inserted Terminal 30 in.-lbs. (3.4 N-m) (UPS12-150MR, UPS12-210MR)

110 in.-lbs. (12.4 N-m) (UPS12-300MR, UPS12-350MR, UPS12-400MR, UPS12-490MRLP, UPS12-490MR, UPS12-540MR, UPS6-620MR)

SPECIFICATIONS

Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C) Operating Time to End Point Voltage (in minutes)

End Point Volts/Cell 5 10 15 20 30 40 45 50 60 90

1.75 157 114 87.5 72.1 54.9 45.0 41.5 38.5 33.7 24.0

1.70 168 115 89.6 74.4 56.5 46.0 42.1 38.9 33.8 24.4

1.67 172 117 90.9 75.4 57.2 46.5 42.6 39.3 34.1 24.6

1.65 174 118 91.5 75.9 57.6 46.9 42.9 39.7 34.5 24.8

1.60 179 119 92.5 76.8 58.3 47.4 43.4 40.1 34.8 25.0

Constant Current Discharge Ratings - Amperes @ 77˚F (25˚C) Operating Time to End Point Voltage (in hours)

End Point Volts/Cell 1 2 3 5 8 10 12 20 24 72

1.85 22.8 13.0 9.08 5.70 3.76 3.10 2.64 1.64 1.38 0.47

1.80 24.2 13.6 9.46 5.91 3.90 3.21 2.72 1.69 1.41 0.48

1.75 25.4 14.1 9.80 6.11 4.00 3.28 2.79 1.73 1.45 0.49

Constant Current Discharge Ratings - Amperes @ 77˚F (25˚C) Operating Time to End Point Voltage (in hours)

End Point Volts/Cell .083 .25 .5 .75 1 2 3 5 8 10 12 20 24 72 100

1.90 50.8 32.9 22.5 17.1 13.8 8.29 6.04 3.95 2.61 2.15 1.82 1.14 0.96 0.34 0.24

1.85 63.2 38.1 25.3 18.6 15.0 8.99 6.56 4.30 2.84 2.33 1.98 1.24 1.05 0.37 0.26

1.80 71.8 41.6 27.5 20.3 16.1 9.42 6.83 4.46 2.95 2.42 2.05 1.28 1.08 0.38 0.27

1.75 85.5 45.7 28.7 21.4 17.0 9.74 6.99 4.54 3.00 2.45 2.08 1.30 1.10 0.39 0.28

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.

Above ratings do not include interunit connector voltage drops.

UPS12-100MR

SPECIFICATIONS

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.

Above ratings do not include interunit connector voltage drops.

UPS12-150MR

UPS

Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C) Operating Time to End Point Voltage (in minutes)

End Point Volts/Cell 5 10 15 20 30 40 45 50 60 90

1.75 273 182 140 115 85.7 68.8 62.7 57.6 49.7 35.0

1.70 284 188 144 117 87.1 69.8 63.6 58.4 50.3 35.7

1.67 290 193 147 120 88.9 71.1 64.7 59.4 51.1 36.1

1.65 294 196 149 122 90.0 71.8 65.3 60.0 51.5 36.4

1.60 297 200 152 124 91.0 72.5 65.9 60.5 51.9 36.6

Model

UPS12-100MR 6 500 1750 0.0060

6 500 2500 0.0060 6 600 3000 0.0045 6 800 3600 0.0040 6 800 4200 0.0030 6 800 5100 0.0025 6 800 5000 0.0023

6 800 5000 0.0023 6 800 4350 0.0012

UPS12-150MR

UPS12-210MR

UPS12-300MR

UPS12-350MR

UPS12-400MR

UPS12-490MRLP

UPS12-540MR

UPS6-620MR

6 800 6000 0.0022UPS12-490MR

Cells per Unit

Maximum Discharge Current (AMPS)

Short Circuit Current (AMPS @ 0.1 sec)

Ohms Impedance 60 Hz (Ω)

Additional product details available on the C&D Battery Sizing Program at www.cdstandbypower.net. Cabinet systems also available.

Constant Current Discharge Ratings - Amperes @ 77˚F (25˚C) Operating Time to End Point Voltage (in hours)

End Point Volts/Cell 1 2 3 5 8 10 12 20 24 72

1.85 48.3 28.1 19.9 12.6 8.36 6.82 5.79 3.62 3.05 1.05

1.80 51.1 29.3 20.7 13.1 8.84 7.23 6.13 3.83 3.22 1.08

1.75 52.7 30.1 21.2 13.4 9.16 7.46 6.32 3.93 3.30 1.10

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.

Above ratings do not include interunit connector voltage drops.

UPS12-300MR

Constant Current Discharge Ratings - Amperes @ 77˚F (25˚C) Operating Time to End Point Voltage (in hours)

End Point Volts/Cell 1 2 3 5 8 10 12 20 24 72

1.85 53.0 31.8 22.9 14.8 10.6 8.73 7.38 4.56 3.84 1.29

1.80 58.8 34.5 24.6 15.7 10.1 8.35 7.09 4.39 3.69 1.32

1.75 62.6 36.3 25.8 16.4 11.0 8.98 7.57 4.66 3.92 1.34

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.

Above ratings do not include interunit connector voltage drops.

UPS12-350MR

UPS

Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C) Operating Time to End Point Voltage (in minutes)

End Point Volts/Cell 5 10 15 20 30 40 45 50 60 90

1.75 493 360 281 232 175 141 129 119 103 73.5

1.70 525 379 293 240 179 144 131 120 104 74.0

1.67 546 385 298 245 183 147 134 123 106 75.0

1.65 564 395 302 247 183 147 134 124 107 76.2

1.60 579 402 306 250 186 150 137 126 109 77.7

Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C) Operating Time to End Point Voltage (in minutes)

End Point Volts/Cell 5 10 15 20 30 40 45 50 60 90

1.75 534 410 327 272 205 165 150 138 119 84.3

1.70 596 425 337 280 211 169 154 141 121 84.9

1.67 619 440 348 289 216 173 157 144 123 85.9

1.65 638 455 358 296 220 175 159 145 124 86.5

1.60 669 471 367 302 223 177 161 147 126 87.6

Constant Power Discharge Ratings - Amperes @ 77˚F (25˚C) Operating Time to End Point Voltage (in hours)

End Point Volts/Cell 1 2 3 5 8 10 12 20 24 72

1.85 32.6 19.1 13.6 8.68 5.79 4.72 4.01 2.51 2.12 0.73

1.80 34.8 20.3 14.4 9.20 6.12 5.00 4.24 2.65 2.23 0.76

1.75 36.7 21.1 14.9 9.43 6.25 5.05 4.28 2.69 2.27 0.77

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.

Above ratings do not include interunit connector voltage drops.

UPS12-210MR

Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C) Operating Time to End Point Voltage (in minutes)

End Point Volts/Cell 5 10 15 20 30 40 45 50 60 90

1.75 341 243 193 162 123 99.0 90.3 83.0 71.5 50.6

1.70 366 253 200 166 125 100 91.1 83.6 71.8 50.4

1.67 373 261 204 169 127 102 92.6 85.1 73.3 51.9

1.65 378 262 205 170 128 102 93.3 85.7 73.8 52.1

1.60 391 265 207 172 129 103 94.0 86.3 74.2 52.3

Constant Current Discharge Ratings - Amperes @ 77˚F (25˚C) Operating Time to End Point Voltage (in hours)

End Point Volts/Cell 1 2 3 5 8 10 12 20 24 72

1.85 80.8 48.4 34.8 22.4 15.0 12.3 10.5 6.66 5.64 1.93

1.80 86.4 51.3 36.7 23.4 15.6 12.7 10.8 6.88 5.82 1.99

1.75 91.0 53.5 38.2 24.4 16.2 13.1 11.1 7.06 5.98 2.03

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.

Above ratings do not include interunit connector voltage drops.

UPS12-490MR

UPS

Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C) Operating Time to End Point Voltage (in minutes)

End Point Volts/Cell 5 10 15 20 30 40 45 50 60 90

1.75 655 527 443 382 300 247 227 210 183 132

1.70 740 573 470 400 310 253 233 215 187 134

1.67 771 593 485 411 317 258 237 218 189 135

1.65 799 614 497 419 321 261 239 220 191 137

1.60 838 640 513 429 325 264 241 222 193 138

Constant Current Discharge Ratings - Amperes @ 77˚F (25˚C) Operating Time to End Point Voltage (in hours)

End Point Volts/Cell 1 2 3 5 8 10 12 20 24 72

1.85 77.3 44.4 31.1 19.7 12.9 10.6 8.89 5.60 4.68 1.62

1.80 82.6 46.6 32.4 20.4 13.3 10.9 9.15 5.79 4.85 1.66

1.75 86.2 47.8 33.5 21.0 13.7 11.1 9.36 5.90 4.94 1.69

UPS12-490MRLP

Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C) Operating Time to End Point Voltage (in minutes)

End Point Volts/Cell 5 10 15 20 30 40 45 50 60 90

1.75 670 540 445 375 282 224 203 185 158 109

1.70 747 583 471 392 291 230 209 190 162 112

1.67 787 608 487 403 297 234 211 193 164 112

1.65 817 627 500 412 302 237 214 195 165 113

1.60 858 648 512 420 306 240 216 196 166 114

Constant Current Discharge Ratings - Amperes @ 77˚F (25˚C) Operating Time to End Point Voltage (in hours)

End Point Volts/Cell 1 2 3 5 8 10 12 20 24 72

1.85 56.2 33.7 24.4 15.7 10.8 8.85 7.56 4.8 4.06 1.38

1.80 62.1 36.5 26.1 16.7 11.4 9.38 8.00 5.03 4.23 1.43

1.75 67.9 39.2 27.8 17.6 11.9 9.73 8.26 5.17 4.35 1.46

UPS12-400MR

Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C) Operating Time to End Point Voltage (in minutes)

End Point Volts/Cell 5 10 15 20 30 40 45 50 60 90

1.75 612 470 374 310 232 186 169 155 134 94.7

1.70 678 490 388 323 241 193 176 161 138 96.6

1.67 716 506 397 328 244 195 177 162 139 97.2

1.65 740 515 403 332 247 197 179 164 140 98.1

1.60 767 530 411 337 249 199 180 165 142 99.2

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.

Above ratings do not include interunit connector voltage drops.

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.

Above ratings do not include interunit connector voltage drops.

Any data, descriptions or specifications presented herein are subject to revision by C&D Technologies, Inc. without notice. While such information is believed to be accurate as indicated herein, C&D Technologies, Inc. makes no warranty and hereby disclaims all warranties, express or implied, with regard to the accuracy or completeness of such information. Further, because the product(s) featured herein may be used under conditions beyond its control, C&D Technologies, Inc. hereby disclaims all warranties, either express or implied, concerning the fitness or suit-ability of such product(s) for any particular use or in any specific application or arising from any course of dealing or usage of trade. The user is solely responsible for determining the suitability of the product(s) featured herein for user’s intended purpose and in user’s specific application.

Copyright 2009 C&D TECHNOLOGIES, INC. Printed in U.S.A. 12-1029 0109/CD

1400 Union Meeting Road P.O. Box 3053 • Blue Bell, PA 19422-0858

(215) 619-2700 • Fax (215) 619-7899 • (800) 543-8630 customersvc@cdtechno.com www.cdtechno.com

UPS

High Rate Max Part Number Manufacturer Approved Premium Replacement for:

UPS12-100MR UPS12-100FR

UPS12-150MR UPS12-140FR & MR12-150

UPS12-210MR UPS12-170FR, UPS12-200FR & MR12-210

UPS12-300MR UPS12-270FR & MR12-300

UPS12-350MR UPS12-310FR & MR12-350

UPS12-400MR UPS12-370FR & MR12-400

UPS12-490MRLP UPS12-475FR, MR12-490 & UPS12-490MR (Low profile high rate applications) UPS12-490MR UPS12-475FR & MR12-490 (Extended run applications)

UPS12-540MR UPS12-530FR & MR12-540

UPS6-620MR UPS6-620FR

Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C) Operating Time to End Point Voltage (in minutes)

End Point Volts/Cell 5 10 15 20 30 40 45 50 60 90

1.75 862 681 573 497 392 323 297 274 238 169

1.70 890 718 602 517 403 330 302 278 241 171

1.67 938 747 620 530 410 335 307 283 245 174

1.65 951 763 634 542 419 342 313 288 250 178

1.60 1000 794 655 557 429 349 320 295 256 183

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.

Above ratings do not include interunit connector voltage drops.

UPS6-620MR

Constant Current Discharge Ratings - Amperes @ 77˚F (25˚C) Operating Time to End Point Voltage (in hours)

End Point Volts/Cell 1 2 3 5 8 10 12 20 24 72

1.85 82.7 49.5 35.6 22.9 15.0 12.6 10.9 7.05 5.98 2.00

1.80 89.6 53.1 38.1 24.4 15.9 13.2 11.3 7.29 6.18 2.07

1.75 98.9 57.0 40.3 25.5 16.5 13.6 11.7 7.46 6.31 2.11

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.

Above ratings do not include interunit connector voltage drops.

UPS12-540MR

Constant Current Discharge Ratings - Amperes @ 77˚F (25˚C) Operating Time to End Point Voltage (in hours)

End Point Volts/Cell 1 2 3 5 8 10 12 20 24 72

1.85 106 63.6 46.2 30.1 20.3 16.9 14.5 9.27 7.85 2.73

1.80 114 67.6 48.8 31.6 21.2 17.6 15.1 9.66 8.10 2.83

1.75 121 71.2 50.9 32.6 21.9 18.1 15.6 9.96 8.42 2.87

Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C) Operating Time to End Point Voltage (in minutes)

End Point Volts/Cell 5 10 15 20 30 40 45 50 60 90

1.75 728 564 471 406 318 261 239 221 191 136

1.70 833 626 511 433 332 269 246 226 195 138

1.67 875 657 534 451 343 277 252 231 198 139

1.65 912 683 550 462 349 280 255 234 201 141

1.60 959 701 560 468 353 283 258 237 203 143